SECTION CLIENT-SERVER INFORMATION / DATABASE INTEGRATION

Size: px
Start display at page:

Download "SECTION CLIENT-SERVER INFORMATION / DATABASE INTEGRATION"

Transcription

1 SECTION CLIENT-SERVER INFORMATION / DATABASE INTEGRATION PART 1 - GENERAL 1.1 SUMMARY A. Section includes the database generation and integration for the DDC system. B. This section defines the specific Niagara database generation and integration requirements for the equipment or devices defined in project Scope of Work. This can include new DDC hardware and devices furnished by Controls Contractor; vendor- specific third-party equipment furnished by other Contractors; and existing controls systems or devices. C. Related Sections: 1. Stanford FDG Commissioning Integrated Automation Building Controls Systems Server Integration Protocols Graphics 1.2 REFERENCES A. Refer to Integrated Automation B. Object Naming and Tags Spreadsheet. Latest version furnished to Contractor by Stanford FAC. C. Stanford University Niagara 4 Standards. Latest version furnished to Contractor by Stanford FAC. 1.3 DEFINITIONS A. Refer to Integrated Automation Definitions 1.4 SYSTEM DESCRIPTION A. The integration of the systems as specified or as shown on construction documents throughout the facility using protocols specified in section B. Remote read/write capabilities of Integrated Automated Systems using open and industry standard protocols. C. Scope includes but not limited to: 1. Data collection 2. Database generation. 3. Graphics generation. 4. Scheduling generation. 5. Trending and storage of all points 6. Alarm generation and management. 7. Reports generation 8. Coordination of integration activities. 1.5 SUBMITTALS A. Refer to Integrated Automation November 2018 Page 1 of FDG Section

2 B. All programming and configuration, including graphics, directory structure, Tagging, Hierarchies Templates and point naming in Building Control System Server, Building Level Controllers, Local Control Units and any additional devices included in the project scope of work, must be submitted for approval of FAC before Contractor may proceed with work. Contractor assumes all responsibility for required submissions. Failure to submit any required submittal does not alleviate Contractor s responsibility to implement Owner s corrections, at no additional cost to Owner and with no slippage of installation schedule. C. All modifications to Owner-furnished Stations, programming code and Stanford Standard graphics must be described in writing and submitted for approval of FAC before Contractor may proceed with work. Failure to submit any required submittal does not alleviate Contractor s responsibility to implement Owner s corrections, at no additional cost to Owner and with no slippage of installation schedule. D. All Contractor modifications to Owner-furnished Stations, programming code and Stanford Standard graphics that are not described in writing and submitted for approval of FAC shall be corrected by the Contractor to the satisfaction of Owner, at no additional cost to Owner and with no slippage of installation schedule. 1.6 QUALITY ASSURANCE A. Refer to Integrated Automation B. Each copy of Tridium Niagara software shall include a 5 year Niagara Software Maintenance Agreement. PART 2 - PRODUCTS 2.1 NOT USED. PART 3 - EXECUTION 3.1 Use of Owner-furnished Stations, programming code and Stanford Standard graphics. A. To ensure consistency of programming, consistency of database structure, and consistency of Look and Feel of User Interface, Stanford University FAC provides Niagara 4 template stations for new or AX-upgraded Niagara installations. These station templates are named BuildingWS.ntpl and BuildingJace.ntpl for new N4 projects and for projects that migrate existing AX sites to N4. Each include several preconfigured components key to a successful implementation of Stanford N4 Standards, namely; a Stanford Kerberos Authentication Scheme, Stanford Categories, Stanford Standard Prototypes and Roles, and a Stanford Tag Dictionary. Preconfigured objects also include Data Modeling examples in the form of Hierarchies typically used for a Stanford site, sample graphics for common equipment types, and a sample navigation scheme with core site pages, Alarm Classes, and representative alarm messages with correct Bformatting; one Modbus JACE station with representative Modbus points configured, and representative gfx code for each type of Distech controller. B. The term representative shall mean it is understood that the Stations, graphics and gfx code are copied from a project that is very close to, but may not exactly match, the requirements of this project. Upon receipt of Stations, graphics and gfx code, Contractor shall have 30 business days to thoroughly review and study the furnished Stations, graphics, Niagara wiresheets and gfx code, and to list, in writing, any reason why the furnished material cannot be adapted to this project. For each reason, Contractor shall include a proposed solution that is consistent with Stanford Standards and will not adversely impact the project schedule. Owner shall be the final judge of acceptance of proposed alternative programming solutions. November 2018 Page 2 of FDG Section

3 C. After 30 business days to thoroughly review and study the furnished Stations, graphics, wiresheets and gfx code, Contractor shall inherit full responsibility for the functionality and performance of the furnished Stations, graphics, wiresheets and gfx code. D. Contractor is completely responsible for successfully passing all Functional Performance Testing (FPT) prior to project close out. The fact that Contractor is using a code template that was furnished to them, or the fact that code passed FPT at the beginning of the project, will not be considered acceptable reasons for failure to pass any commissioning FPT at project close out. 3.2 Compliance to Owner s Computing and Security policies. A. The Contractor shall at all times fully comply with all Stanford University Computer Policies. B. Be forewarned that Stanford University Computer Policies are constantly evolving and may change to be increasingly restrictive during the execution of this contract. The Contractor shall at all times fully comply with all Stanford University Computer Policies immediately as the policies become effective. C. Owner does not guarantee that Contractor will have remote (off-campus) access to the controls system. D. Violation of Stanford University Computer Policies may result in revocation of User access to the Stanford University Computer Network and/or computing equipment physically removed from the Stanford University Computer Network. E. Examples of controls system security policies include: 1. Minimum password length. 2. User access credentials cannot be shared. Each user accessing system must have unique credentials. 3. User credentials may not be transmitted by or text message. User credentials inside a password-protected zip file may be transmitted via Deleting, restricting access to, or modifying operating system or control system log files is not permitted. 5. Contractor passwords shall be unique to Stanford site passwords used at any other site are not acceptable. Ubiquitous Branch passwords are not acceptable. 6. Contractor to apply all software updates and security patches immediately (within 72 hours) as they become available. 7. Owner shall, at all times, have at least 1 Windows Operating System administrator account on all servers, Niagara Super User Station accounts for all JACEs and Supervisor Stations, all Niagara Pass Phrases and credentials for access to all Platforms. 8. Any and all required IDs and passwords, including hardware locks for access to any component or software program shall be immediately provided to the Owner upon request, at no additional cost to Owner. 3.3 SYSTEM ACCESS A. Operator specific password access protection shall be provided for each application to allow the administrator to limit access to point control, display and data base manipulation capabilities as deemed appropriate for each user, based upon an assigned password. There shall be 6 access levels as defined below. 1. Super User No restriction. Can set or override adjustable setpoints on graphics. 2. Administrator Full WebUI and Workbench access to Station except to files that can potentially corrupt database. Can set or override adjustable setpoints on graphics. Can set passwords and add users. 3. Integrator - WebUI and Workbench access to Station. Same access level as Administrator except cannot set passwords and add users. Can set or override adjustable setpoints on graphics. Can change own user name, password and address November 2018 Page 3 of FDG Section

4 4. Programmer WebUI and Workbench access to Station. Same access level as Administrator except cannot set passwords and add users. Can set or override adjustable setpoints on graphics. Can change own user name, password and address. 5. Operator WebUi access only. View all graphics and override points only, no set point access, can acknowledge alarms. Can override adjustable setpoints on graphics. Can change own user name, password and address. 6. Read Only Read only WebUI access. Can change own user name, password and address. 7. Scheduler Read only WebUI access with ability to modify equipment schedules as required. Can change own user name, password and address. 8. Owner will furnish a written matrix of Categories, Permissions and Roles that must be followed exactly. 9. As directed by Owner, Contractor shall remove all User Accounts created by Contractor. 3.4 DATA COLLECTION: A. Provide mapping of points from various control systems. Provide the ability to read and display any value of any used property of any object from any networked device including properties available and supported optional properties, as well as proprietary extensions. B. Unless otherwise specified trend points simultaneously no longer than every 15 minutes. C. Timestamp all data. D. Normalize data points shown in contract documents for ease of database management, graphic displays, readability, and simple identification. 3.5 DATABASE GENERATION: A. Develop database of data objects, time stamps, events, alarms, and transactions. B. Archive all data points, graphics, reports, alarms, trends, events, and transactions. 1. Store a minimum of 2 years of data on Building Control System Server. 2. Schedule and synchronize trend point data collected on the building level controller to be archived to the building control systems server to allow enough capacity in the building level controller to hold data if first sync fails. C. Develop databases including: 1. Applications 2. Configuration 3. Trending of historical Data 4. Event (operator actions / alarming etc) storage D. Provide an electronic copy of the installed/commissioned database in the Building Control Systems Server, every building level controller; and every local control unit for emergency recovery. 3.6 Collection and Analysis of Historical Data A. Provide trending capabilities that allow the user to easily monitor and preserve records of system activity over an extended period of time. Any system point may be trended automatically at timebased intervals or change of value, both of which shall be user-definable. Trend data may be stored on hard disk for future diagnostics and reporting. Additionally, trend data may be archived to network drives or removable disk media for future retrieval. B. Trend data reports shall be provided to allow the user to view all trended point data. Reports may be customized to include individual points or predefined groups of at least six points. Provide additional functionality to allow predefined groups of trended points to be easily transferred on-line November 2018 Page 4 of FDG Section

5 to Microsoft Excel. Contractor shall provide up to four custom designed spreadsheet reports for use by Owner to track energy usage and cost, equipment run times, equipment efficiency, and/or building environmental conditions. Contractor shall provide setup of up to four custom reports including creation of data format templates for monthly or weekly reports. C. Provide additional functionality that allows the user to view real-time trend data on trend graph displays. Ten points may be graphed, regardless of whether they have been predefined for trending. The dynamic graphs shall continuously update point values. At any time the user may redefine sampling times or range scales for any point. In addition, the user may pause the graph and take "snapshots" of screens to be stored on the workstation disk for future recall and analysis. Exact point values may be viewed and the graphs may be printed. D. Histories shall utilize Hierarchies to facilitate easy and logical navigation to histories in History Viewer,. Histories shall no longer utilize obsolete History Groups to facilitate navigation to histories. E. On each History Extension, the History Name shall be correctly bformatted to automatically prepend the Point Display Name, with JACE Name and Controller Name, in the format: JACEName_ControllerNAme_PointName. F. Contractor shall demonstrate History Hierarchy navigation structure to Owner s Representative for written approval prior to creating History Extensions. G. All trending shall reside in the Station of the Building Level Controller that directly supervises the controllers that are on a LON network connected to that Building Level Controller. Trends stored in the JACE shall be archived in the Supervisor Station a maximum of every 2 hours. 3.7 DATABASE BACKUP A. Provide automatic weekly backup of all building level controllers and local control unit databases to a location on the Building Control Systems Server. Backups will be limited to a maximum of 52 backups, at which time newest backup shall overwrite oldest backup. Each backup shall be written with a file name that includes a date code for date of backup or a unique folder with a folder name that includes a date code and shall not overwrite or append previous backup files. Owner shall have the ability to restore the database in the building level controller or local control unit using a backup from a known good database at any previous week necessary. B. Owner will automate the backup of the building control system server to the campus master DDC server. 3.8 POINTS LIST A. Adjustable points fall into 1 of 3 categories: 1. Points adjustable from the Supervisor Station using Niagara Workbench (WBS-. a. WBS-Adj. point shall be a dedicated Niagara Numeric Writable Point. Hard coding the value into a calculation block is not acceptable. b. The Niagara Numeric Writable Point shall be the same object name for every instance of same WBS-Adj. point to facilitate batch editing of WBS-Adj. points. c. WBS-Adj. point shall be adjustable from Workbench on the Supervisor Station by anyone with Programmer or higher level of access. 2. Points adjustable from a JACE using Niagara Workbench (WBJ-. a. WBJ-Adj. point shall be a dedicated Niagara Numeric Writable Point. Hard coding the value into a calculation block is not acceptable. b. The Niagara Numeric Writable Point shall be the same object name for every instance of same WBJ-Adj. point to facilitate batch editing of WBJ-Adj. points. November 2018 Page 5 of FDG Section

6 c. WBJ-Adj. point shall be adjustable from Workbench by anyone with Programmer or higher level of access. 3. Points adjustable from Graphic Page (GR-. a. GR-Adj. points shall be adjustable from Graphic Page. Adjustability shall be based on operator s access level. B. Submit points list for Owner Approval, prior to database generation. C. The VAV with Reheat Coil terminal unit controller shall monitor and trend the following points as specified in the table below. The VAV with Reheat Coil terminal unit graphic shall display points as specified in the table below. 1. Note: additional AHU points may be mapped via Modbus to be displayed on VAV graphic. D. Contractor shall include any additional points required to meet specification section Graphics. E. Contractor shall include any additional points required to meet specification section Control Sequences. November 2018 Page 6 of FDG Section

7 Point Hardware Points Software Points From DeltaV Cx Trend (1) Cont. Trend (2) Show On Graphic Adjustable Zone AI 15 min. Zone Setpoint Adjustment AI COV Airflow AI 15 min. Discharge Air AI 15 min. Zone Damper Position AO 15 min. GR-Adj. Reheat Valve Position AO 15 min. GR-Adj. Zone Occupancy Override BI COV WBS-Adj. Airflow Setpoint AV 15 min. Max Cooling Airflow AV COV GR-Adj. Min Cooling Airflow AV COV GR-Adj. Max Heating Airflow AV COV GR-Adj. Min Heating Airflow AV COV GR-Adj. Zone Setpoint AV COV GR-Adj. Occupied Heating Setpoint AV Occupied Cooling Setpoint AV Standby Heating Setpoint AV Standby Cooling Setpoint AV Un-Occupied Heating Setpoint AV WBS-Adj. Un-Occupied Cooling Setpoint AV WBS-Adj. Effective Heating Setpoint AV 15 min. Effective Cooling Setpoint AV 15 min. Zone Criticality (Reset Weighting) AV GR-Adj. Occupancy Mode AV 15 min. GR-Adj. Terminal Load (Heating/Cooling Demand) AV 15 min. Cooling Request AV 15 min. Cooling Request Hi & Lo Setpoints AV WBJ-Adj. Reheat Valve Request AV 15 min. RH-V Request Hi & Lo Setpoints AV WBJ-Adj. Damper Request AV 15 min. Damper Request Hi & Lo Setpoints AV WBJ-Adj. Cooling Satisfied AV 15 min. Cooling Satisfied Hi & Lo Setpoints AV WBJ-Adj. Reheat Valve Satisfied AV 15 min. RH-V Satisfied Hi & Lo Setpoints AV WBJ-Adj. November 2018 Page 7 of FDG Section

8 Point Hardware Points Software Points From DeltaV Cx Trend (1) Cont. Trend (2) Show On Graphic Adjustable Damper Satisfied AV 15 min. Damper Satisfied Hi & Lo Setpoints AV WBJ-Adj. Box Size String WBS-Adj. Box Type String WBS-Adj. AHU SAT AV 15 min. AHU SAT Setpoint 15 min. AHU Occupancy Status AV 15 min. AHU Name or Number 15 min. AHU Duct Static Pressure AV 15 min. AHU Duct Static Pressure Setpoint 15 min. Outside CO2 AV 15 min. Global Occupied Heating Offset AV Global Occupied Cooling Offset AV Global Standby Heating Offset AV Global Standby Cooling Offset AV Totals AI Analog Input; AO Analog output; BI Binary Input; BO Binary output; AV Analog Value; BV Binary Value (1) Cx Trend requirements: 5 minute interval, 1 month duration, (2) Continuous Trend requirements: Either 15 minute interval or COV as specified above, 24 hour duration November 2018 Page 8 of FDG Section

9 G. The Cooling Only VAV terminal unit controller shall monitor and trend the following points as specified in the table below. The Cooling Only VAV terminal unit graphic shall display points as specified in the table below. H. Contractor shall include any additional points required to meet specification section Graphics. I. Contractor shall include any additional points required to meet specification section Control Sequences. November 2018 Page 9 of FDG Section

10 Point Hardware Points Software Points From DeltaV Cx Trend (1) Cont. Trend (2) Show On Graphic Adjustable Zone AI 15 min. Zone Setpoint Adjustment AI COV Airflow AI 15 min. Zone Damper Position AO 15 min. GR-Adj. Zone Occupancy Override BI COV WBS-Adj. Airflow Setpoint AV 15 min. Max Cooling Airflow AV COV GR-Adj. Min Cooling Airflow AV COV GR-Adj. Zone Setpoint AV COV GR-Adj. Occupied Heating Setpoint AV Occupied Cooling Setpoint AV Standby Heating Setpoint AV Standby Cooling Setpoint AV Un-Occupied Heating Setpoint AV WBS-Adj. Un-Occupied Cooling Setpoint AV WBS-Adj. Effective Heating Setpoint AV 15 min. Effective Cooling Setpoint AV 15 min. Zone Criticality (Reset Weighting) AV GR-Adj. Occupancy Mode AV 15 min. GR-Adj. Terminal Load (Heating/Cooling Demand) AV 15 min. Cooling Request AV 15 min. Cooling Request Hi & Lo Setpoints AV WBJ-Adj. Reheat Valve Request AV 15 min. RH-V Request Hi & Lo Setpoints AV WBJ-Adj. Damper Request AV 15 min. Damper Request Hi & Lo Setpoints AV WBJ-Adj. Cooling Satisfied AV 15 min. Cooling Satisfied Hi & Lo Setpoints AV WBJ-Adj. Reheat Valve Satisfied AV 15 min. RH-V Satisfied Hi & Lo Setpoints AV WBJ-Adj. Damper Satisfied AV 15 min. Damper Satisfied Hi & Lo Setpoints AV WBJ-Adj. Box Size String WBS-Adj. Box Type String WBS-Adj. November 2018 Page 10 of FDG Section

11 Point Hardware Points Software Points From DeltaV Cx Trend (1) Cont. Trend (2) Show On Graphic Adjustable AHU SAT AV 15 min. AHU SAT Setpoint 15 min. AHU Occupancy Status AV 15 min. AHU Name or Number 15 min. AHU Duct Static Pressure AV 15 min. AHU Duct Static Pressure Setpoint 15 min. Outside CO2 AV 15 min. Global Occupied Heating Offset AV Global Occupied Cooling Offset AV Global Standby Heating Offset AV Global Standby Cooling Offset AV Totals AI Analog Input; AO Analog output; BI Binary Input; BO Binary output; AV Analog Value; BV Binary Value (1) Cx Trend requirements: 5 minute interval, 1 month duration, (2) Continuous Trend requirements: Either 15 minute interval or COV as specified above, 24 hour duration November 2018 Page 11 of FDG Section

12 K. The Fan Coil Unit controller shall monitor and trend the following points as specified in the table below. The Fan Coil Unit graphic shall display points as specified in the table below. L. Contractor shall include any additional points required to meet specification section Graphics. M. Contractor shall include any additional points required to meet specification section Control Sequences. Point Hardware Points Software Points From DeltaV Cx Trend (1) Cont. Trend (2) Show On Graphic Adjustable Zone AI 15 min. Zone Setpoint Adjustment AI COV Discharge Air AI 15 min. Valve Position AO 15 min. WBS-Adj. Zone Override BI COV WBS-Adj. Fan Status BI COV Fan Start/Stop BO COV WBS-Adj. Zone Setpoint AV COV WBS-Adj. Occupied Heating Setpoint AV GR-Adj Occupied Cooling Setpoint AV GR-Adj Standby Heating Setpoint AV WBS-Adj Standby Cooling Setpoint AV WBS-Adj Effective Heating Setpoint AV 15 min. Effective Cooling Setpoint AV 15 min. Critical Zone AV GR-Adj. Occupied Mode BV 15 min. GR-Adj. Terminal Load AV 15 min. Totals AI Analog Input; AO Analog output; BI Binary Input; BO Binary output; AV Analog Value; BV Binary Value (1) Cx Trend requirements: 5 minute interval, 1 month duration, (2) Continuous Trend requirements: Either 15 minute interval or COV as specified above, 24 hour duration November 2018 Page 12 of FDG Section

13 O. The VAV Exhaust System controller shall monitor and trend the following points as specified in the table below. The VAV Exhaust System graphic shall display points as specified in the table below. P. Contractor shall include any additional points required to meet specification section Graphics. Q. Contractor shall include any additional points required to meet specification section Control Sequences. Point Exhaust duct pressure Hardware Points AI Software Points From Cx Cont. Show Trend Trend On DeltaV (1) (2) Graphic 15 min. Adjustable Exhaust fan start stop DO COV GR-Adj. Exhaust fan speed control AO 15 min. GR-Adj. Exhaust fan run status DI COV Make-up air damper control Exhaust pressure set point AO AV 15 min. COV GR-Adj. GR-Adj. AI Analog Input; AO Analog output; BI Binary Input; BO Binary output; AV Analog Value; BV Binary Value (1) Cx Trend requirements: 5 minute interval, 1 month duration, (2) Continuous Trend requirements: Either 15 minute interval or COV as specified above, 24 hour duration November 2018 Page 13 of FDG Section

14 S. The VAV Air Handler controller shall monitor and trend the following points as specified in the table below. The VAV Air Handler graphic shall display points as specified in the table below. T. Contractor shall include any additional points required to meet specification section Graphics. U. Contractor shall include any additional points required to meet specification section Control Sequences. Point Return air temperature Hardware Points AI Software Points From Cx Cont. Show Trend Trend On DeltaV (1) (2) Graphic 15 min. Adjustable Outside air temperature AI 15 min. Mixed air temperature AI 15 min. Supply air temperature AI 15 min. Supply duct static pressure Building static pressure AI AI 15 min. 15 min. Outside air damper AO 15 min. GR-Adj. Return air damper AO 15 min. GR-Adj. Exhaust air damper AO 15 min. GR-Adj. Supply fan start stop DO COV GR-Adj. Return fan start stop DO COV GR-Adj. Supply fan run status DI COV return fan run status DI COV Supply fan speed control AO 15 min. GR-Adj. return fan speed control AO 15 min. GR-Adj. HW coil control valve AO 15 min. GR-Adj. CHW coil control valve AO 15 min. GR-Adj. Supply air set point AV 15 min. GR-Adj. Preheat set point AV 15 min. GR-Adj. Duct static set point AV 15 min. GR-Adj. Building static set point AV 15 min. GR-Adj. November 2018 Page 14 of FDG Section

15 AI Analog Input; AO Analog output; BI Binary Input; BO Binary output; AV Analog Value; BV Binary Value (1) Cx Trend requirements: 5 minute interval, 1 month duration, (2) Continuous Trend requirements: Either 15 minute interval or COV as specified above, 24 hour duration 3.9 OCCUPANCY/EQUIPMENT SCHEDULING AND OVERRIDES A. Coordinate initial occupancy and equipment schedules requirements with owner. B. Program initial occupancy and equipment schedules per owner request. C. Install and configure Stanford custom 25Live driver to automatically control equipment serving 25Live spaces, as directed by Owner. D. Occupancy and/or Equipment schedules may change during the course of this project. Contractor shall modify programing to meet any Occupancy and/or Equipment schedules revised by Owner, until project is accepted by Owner, at no additional cost to Owner. E. Contractor accepts that programming the occupancy schedule of a Terminal Unit, may also require programming the occupancy schedule of other Terminal Units served by the same Air Handler, or other equipment schedules, F. Schedules reside in the Building Level Controller(s) to ensure time scheduling when Supervisor PC is off-line, Supervisor PC is not required to execute time scheduling. G. Define schedule capabilities either by floor or by air handler. H. Override options include room sensor integrated pushbutton or hardwired switch in common area. I. Define areas that have standby & 24/7 occupancy ALARM MANAGEMENT A. Provide alarms including: 1. All alarms shown in tables below. 2. Contractor shall include any additional alarms required to meet specification section Graphics. 3. Contractor shall include any additional alarms required to meet specification section Control Sequences. 4. Contractor shall include any additional alarms depicted on control system drawings. B. Niagara Bformatting shall be utilized in all To offnormal Text, To Fault Text and To Normal Text. For example, instead of Space Temp Too High, use the following Bformatting: the High Limit of C. For alarms not listed in this schedule, use the following guidelines. The device name(s), present value(s) and alarm threshold(s) or condition(s), shall be expressed in Bformatting. Hard coded values shall not be acceptable. D. All Bformatting subject to approval of FAC. November 2018 Page 15 of FDG Section

16 E. On each Alarm Extension, the Alarm Source Name shall be correctly bformatted to automatically prepend the Point Display Name, with JACE Name (Station Name if alarm extension resides in Supervisor) and Controller Name, in the format: JACEName_ControllerNAme_PointName, in both the Source and Message Text fields of each alarm record as it appears in any alarm console. F. Alarm values shall be adjustable from a JACE using Niagara Workbench (WBJ-. 1. Any WBJ-Adj. value, that is not integral to an alarm extension, i.e. external setpoint or alarm differential, shall be a dedicated Niagara Numeric Writable Point. Hard coding the value into a calculation block is not acceptable. 2. The Niagara Numeric Writable Point shall be the same object name for every instance of same WBJ-Adj. point to facilitate batch editing of WBJ-Adj. points. 3. WBJ-Adj. point shall be adjustable from Workbench by anyone with Programmer or higher level of access. G. Use of Boolean Alarm extensions, on analog (Numeric) values, is not acceptable. H. Provide alarms per project I/O table. Coordinate with Owner points requiring DDC alarming and include the following: 1. Point Name and Description 2. Alarm differentials (automatically adjust with setpoints) 3. Units 4. Coordinate settings (limits or state) with Owner 5. Instrument tag 6. Priority 7. Message I. Include the following Communication alarms: Point Description Alarm if: Delay Time Inhibit Time Priority Level Alarm Class Alarm Text To Normal Text Niagara Network Heath Alarm Any Niagara Station Offline > 5 min. (WBJ- 5 min 10 Communication Prepend with bformatting: BuildingName_StationName: Prepend with bformatting: BuildingName_StationName: LON Network Heath Alarm Any LON Device Offline > 5 min. (WBJ- 5 min 10 Communication Prepend with bformatting: JACEName_DeviceName: if multiple LON trunks on JACE JACEName_LONtrunkID_DeviceName: Prepend with bformatting: JACEName_DeviceName: Modbus Network Health Alarm Modbus missing timing pulse > 5 min. (WBJ- 5 min 10 Communication Prepend with bformatting: BuildingName_StationName: Prepend with bformatting: BuildingName_StationName: November 2018 Page 16 of FDG Section

17 J. Include the following alarms for all VAV boxes with Reheat Coil: Point Description Alarm if: Delay Time Inhibit Time Priority Level Alarm Class Alarm Text To Normal Text Space >4 F (WBJ- above Cooling SP 20 min 2 hrs 200 Troubleshooting >4 F (WBJ- below Heating SP 20 min 2 hrs 200 Troubleshooting >95 F (WBJ- 150 Critical Temps <55 F (WBJ- 150 Critical Temps Special Space >3 F (WBJ- above setpoint over 4 hours (WB- 150 Troubleshooting Special Space > 3 F (WBJ- below setpoint over 4 hours (WB- 150 Troubleshooting Special Space >82 F (WBJ- 5 min 150 Critical Temps Special Space <63 F (WBJ- 5 min 150 Critical Temps November 2018 Page 17 of FDG Section

18 Critical Airflow Actual Airflow <80% (WBJ- of Minimum Airflow SP in Lab Zone 20 min 30 Critical Terminal Load 100% (WBJ- 4 hrs 200 Troubleshooting Terminal Load -100% (WBJ- 4 hrs 200 Troubleshooting Damper Position 100% (WBJ- 4 hrs 200 Troubleshooting %alarmdata.highlimit% Discharge Air (DAT) > DAT SP + 5 F (WBJ- 20 min 200 Troubleshooting Discharge Air (DAT) < DAT SP 5 F (WBJ- 20 min 200 Troubleshooting Valve Alarm DAT > AHU SAT + 8 F (WBJ-; while reheat valve position = 0% (WBJ- 20 min 200 Troubleshooting while the HW Valve is Closed %alarmdata.highlimit% while the HW Valve is Fully Closed Valve Alarm DAT < 72 F (WBJ-; while reheat valve position = 100% (WBJ- 20 min 200 Troubleshooting Offnormal Algorithm, low Limit Text: while the HW Valve is 100% Open while the HW Valve is 100% Open Reheat Valve Position 100% (WBJ- 4 hrs 2 hrs 200 Troubleshooting %alarmdata.highlimit% November 2018 Page 18 of FDG Section

19 Actual Air Flow >120% (WBJ- of Air Flow SP 20 min 200 Troubleshooting Actual Air Flow <80% (WBJ- of Air Flow SP 200 Troubleshooting Damper Position Damper Position = 0% (WBJ-; while airflow is greater than 50 (WBJ- CFM 5 min 200 Troubleshooting %alarmdata.presentvalue%, while airflow is greater than 50 CFM., while airflow is greater than 50 CFM. Damper Position Damper position = 100% (WBJ- ; while airflow is less than 50 CFM (WBJ- 5 min 200 Troubleshooting %alarmdata.presentvalue%, while airflow is less than 50 CFM. Check Damper Position. CO2 (1) > 1000 ppm (WBJ- 30 min 200 Troubleshooting CO2 (2) < 300 ppm (WBJ- 30 min 200 Troubleshooting CO2 (3) >2,500 ppm (WBJ- 20 Life Safety the Unsafe High Limit of %alarmdata.highlimit% returned to a Safe Level of below the Unsafe High Limit of %alarmdata.highlimit% November 2018 Page 19 of FDG Section

20 K. Include the following alarms for all Cooling Only VAV boxes: Point Description Alarm if: Delay Time Inhibit Time Priority Level Alarm Class Alarm Text To Normal Text Space >4 F (WBJ- above Cooling SP 20 min 2 hrs 200 Troubleshooting >4 F (WBJ- below Heating SP 20 min 2 hrs 200 Troubleshooting >95 F (WBJ- 150 Critical Temps <55 F (WBJ- 150 Critical Temps Special Space >3 F (WBJ- above setpoint over 4 hours (WB- 150 Troubleshooting Special Space > 3 F (WBJ- below setpoint over 4 hours (WB- 150 Troubleshooting Special Space >82 F (WBJ- 5 min 150 Critical Temps Special Space <63 F (WBJ- 5 min 150 Critical Temps November 2018 Page 20 of FDG Section

21 Critical Airflow Actual Airflow <80% (WBJ- of Minimum Airflow SP in Lab Zone 20 min 30 Critical Terminal Load 100% (WBJ- 4 hrs 200 Troubleshooting Damper Position 100% (WBJ- 4 hrs 200 Troubleshooting %alarmdata.highlimit% Discharge Air (DAT) > DAT SP + 5 F (WBJ- 20 min 200 Troubleshooting Discharge Air (DAT) < DAT SP 5 F (WBJ- 20 min 200 Troubleshooting Actual Air Flow >120% (WBJ- of Air Flow SP 20 min 200 Troubleshooting Actual Air Flow <80% (WBJ- of Air Flow SP 200 Troubleshooting Damper Position Damper Position = 0% (WBJ-; while airflow is greater than 50 (WBJ- CFM 5 min 200 Troubleshooting %alarmdata.presentvalue%, while airflow is greater than 50 CFM., while airflow is greater than 50 CFM. Damper Position Damper position = 100% (WBJ- ; while airflow is less than 50 (WBJ- CFM 5 min 200 Troubleshooting %alarmdata.presentvalue%, while airflow is less than 50 CFM. Check Damper Position. November 2018 Page 21 of FDG Section

22 CO2 (1) > 1000 ppm (WBJ- 30 min 200 Troubleshooting CO2 (2) < 300 ppm (WBJ- 30 min 200 Troubleshooting CO2 (3) >2,500 ppm (WBJ- 20 Life Safety the Unsafe High Limit of %alarmdata.highlimit% returned to a Safe Level of below the Unsafe High Limit of %alarmdata.highlimit% November 2018 Page 22 of FDG Section

23 L. Include the following alarms for all FCU s. Point Description Alarm if: Delay Time Inhibit Time Priority Level Alarm Class Alarm Text To Normal Text Heating Control Signal Valve Position Discharge air temperature (DAT) DAT Leaking Valve DAT No Heating Fan Fail Alarm Fan In Hand Alarm 100% (WBJ- 4 hrs 2 hrs 200 Troubleshooting 100% (WBJ- 4 hrs 2 hrs 200 Troubleshooting >110 F (WBJ- 20 min 200 Troubleshooting DAT > Zone + 5 F (WBJ-; while valve position = 0% and fan status is on. (For hot water fan coil units only) DAT < Zone + 5 (WBJ- F; while the valve position is greater than 30% (WBJ- and the fan status is on and the heating hot water pump is on. (For hot water fan coil units only) Status is off while Command is on. Status is on while Command is off. 30 min 200 Troubleshooting 30 min 200 Troubleshooting 5 min 200 Troubleshooting 5 min 200 Troubleshooting above the High Limit of %alarmdata.highlimit% above the High Limit of %alarmdata.highlimit% above the High Limit of %alarmdata.highlimit% %alarmdata.presentvalue% (VAV DAT), which is above the High Limit of %alarmdata.highlimit%, while the Reheat Valve Position is at 0 %, and the Fan Status is ON. Leaking Valve? below the low Limit of, while the valve position is greater than 30% and the fan status is on and the heating hot water pump is on. No Heating? To Offnormal Text: %alarmdata.sourcename% is %alarmdata.presentvalue%, while the Fan Command) is ON - Fan Failure? Check Belts and HOA Switch. To Offnormal Text: %alarmdata.sourcename% is %alarmdata.presentvalue%, while the Fan Command is OFF - Return to Automatic %alarmdata.presentvalue%, which is below the High Limit of %alarmdata.highlimit% %alarmdata.presentvalue%, which is below the High Limit of %alarmdata.highlimit% %alarmdata.presentvalue%, which is below the High Limit of %alarmdata.highlimit% returned to a normal value of %alarmdata.presentvalue%, which is below the High Limit of %alarmdata.highlimit%, while the Reheat Valve Position is at 0 %, and the Fan Status is ON. returned to a normal value of %alarmdata.presentvalue% which is above the low Limit of, while the valve position is greater than 30% and the fan status is on and the heating hot water pump is on. Returned to Normal %alarmdata.presentvalue%, while the Fan Command is ON. Returned to a Normal Status, %alarmdata.presentvalue, while the Fan Command is OFF. November 2018 Page 23 of FDG Section

24 M. Include the following alarms for all Lab Supply Air Valves / Exhaust Valves / Hoods: Point Description Alarm if: Delay Time Inhibit Time Priority Level Alarm Class Alarm Text To Normal Text Space >4 F (WBJ- above Cooling SP 20 min 2 hrs 200 Troubleshooting >4 F (WBJ- below Heating SP 20 min 2 hrs 200 Troubleshooting >95 F (WBJ- 150 Critical Temps <55 F (WBJ- 150 Critical Temps Special Space >3 F (WBJ- above setpoint over 4 hours (WB- 150 Troubleshooting Special Space > 3 F (WBJ- below setpoint over 4 hours (WB- 150 Troubleshooting Special Space >82 F (WBJ- 5 min 150 Critical Temps Special Space <63 F (WBJ- 5 min 150 Critical Temps November 2018 Page 24 of FDG Section

25 Critical Airflow Actual Airflow <80% (WBJ- of Minimum Airflow SP in Lab Zone 20 min 30 Critical Terminal Load 100% (WBJ- 4 hrs 200 Troubleshooting Terminal Load -100% (WBJ- 4 hrs 200 Troubleshooting Damper Position 100% (WBJ- 4 hrs 200 Troubleshooting %alarmdata.highlimit% Discharge Air (DAT) > DAT SP + 5 F (WBJ- 20 min 200 Troubleshooting Discharge Air (DAT) < DAT SP 5 F (WBJ- 20 min 200 Troubleshooting Valve Alarm DAT > AHU SAT + 8 F (WBJ-; while reheat valve position = 0% (WBJ- 20 min 200 Troubleshooting while the HW Valve is Closed %alarmdata.highlimit% while the HW Valve is Fully Closed Valve Alarm DAT < 72 F (WBJ-; while reheat valve position = 100% (WBJ- 20 min 200 Troubleshooting Offnormal Algorithm, low Limit Text: while the HW Valve is 100% Open while the HW Valve is 100% Open Reheat Valve Position 100% (WBJ- 4 hrs 2 hrs 200 Troubleshooting %alarmdata.highlimit% November 2018 Page 25 of FDG Section

26 Actual Air Flow >120% (WBJ- of Air Flow SP 20 min 200 Troubleshooting Actual Air Flow <80% (WBJ- of Air Flow SP 200 Troubleshooting Damper Position Damper Position = 0% (WBJ-; while airflow is greater than 50 (WBJ- CFM 5 min 200 Troubleshooting %alarmdata.presentvalue%, while airflow is greater than 50 CFM., while airflow is greater than 50 CFM. Damper Position Damper position = 100% (WBJ- ; while airflow is less than 50 CFM (WBJ- 5 min 200 Troubleshooting %alarmdata.presentvalue%, while airflow is less than 50 CFM. Check Damper Position. Exhaust Air Terminal CFM Reading >115% (WBJ- of CFM SP 15 min 200 Troubleshooting Exhaust Air Terminal CFM Reading <90% (WBJ- of CFM SP 15 min 200 Troubleshooting Air Flow Differential >110% (WBJ- of Scheduled Differential SP 5 min 200 Troubleshooting Air Flow Differential <95% (WBJ- of Scheduled Differential SP 5 min 200 Troubleshooting November 2018 Page 26 of FDG Section

27 Fume Hood Face Velocity >115% (WBJ- of Scheduled SP 100 FPM During Normal Operation. 60 FPM During Not In Use Periods 5 min 30 Critical Fume Hood Face Velocity <85% (WBJ- of Scheduled SP 100 FPM During Normal Operation. 60 FPM During Not In Use Periods 5 min 30 Critical Sash Height Above Maximum Sash Position 5 min 200 Troubleshooting Sash Height At Maximum Sash Position For >24 Hours 24 hour 30 Critical Sash Height Below Minimum Sash Position 5 min 200 Troubleshooting Hood Alarms Hood in Alarm 30 Critical %alarmdata.sourcename% is in Alarm returned to Normal November 2018 Page 27 of FDG Section

28 N. Include the following alarms for all Generator Rooms: Point Description Alarm if: Delay Time Inhibit Time Priority Level Alarm Class Alarm Text To Normal Text CO level in Engine Room >35 PPM (WBJ- 1 min 1 Critical_ 1 O. All VAV box alarms shall be inhibited while the AHU serving those boxes is non-functional. P. Include the following Critical Callout Alarms: 1. All Leak alarms must indicate the room number that the leak originates from in the alarm message string. 2. Owner to determine Alarm Class, i.e. Critical_1 (24/7 Technician callout) or Critical_2 (daytime Technician callout). 3. All Critical Callout Alarms require a hyperlink to Callout Instructions. BMS BMS Main Power BMS Battery Power Loss of Network Communication Automatic Transfer Switch ATS Emergency Power ATS Loss of Normal Power Generator Fuel Oil Level (Low Fuel) Fuel Oil Leak Detection (High Fuel/Leak) Generator Trouble/Not in Auto Run Status Room Leak (Elevator Pit, Mechanical Rooms, Lab Spaces, etc..) Tracetec Leak Tracetec Trouble Sump Pump Start Lag Pump High Level Alarm Power Failure Sewer Pump Start Lag Pump High Level Alarm Power Failure Fire Alarm Status November 2018 Page 28 of FDG Section

29 TGO Alarm Status Status PCW or HHW Makeup Water Water Flowrate Alarm Air Handler Unit Fan Status Supply Pressure Motor Frequency Supply Filter DeltaP Exhaust Fan Fan Status Pressure Motor Frequency Parking Garage CO Level NoX Level Critical Room and Humidity (VAV or FCU) Room Room Humidity VAV and FCU Secondary Containment Alarm Status Compressor Compressor Trouble Air Compressor Dew point Air Compressor Pressure Compressor Running Time Vacuum Pump Vacuum Pump Trouble Vacuum Pump Pressure Vacuum Pump Running Time Constant Box Constant Box (Outside Range) Constant Box Humidity (Outside Range) Constant Box Status DI/RO Loop Resistivity Below (TBD) mohm Pump Status Tank Level (High/Low) System Pressure Skid Status Other Parameters (TOC, Bacteria, UV, etc ) PCW November 2018 Page 29 of FDG Section

30 PCW Pressure PCW Supply Start Lag Pump PCW Loss of Power Specialty Gas (CO2, N2, O2, etc ) Dewar Tank Pressure Dewar Tank Alarm Bulk Chemicals (HF, ETC ) High Level Overflow Acid Line Leak Fume Scrubber Status Inverter/UPS Battery Status Chemical Waste Neutralization Tank Level Sump Level PH Secondary Containment Leak Detection Bulk Treatment Chemicals Fire Damper Actuator Status Smoke Detector Status Vivarium Room Differential Humidity Temp Condensate Transfer Unit Fault HHW HHW Discharge temp below 100 Lead Pump Status Lag Pump Status CHW Pump Status Domestic Water Pump Status Tank below 100 November 2018 Page 30 of FDG Section

31 Q. Configure the following priority level scheme: Type Priority Level Niagara Alarm Class Name Local Supervisor Station Alarm Console Local Supervisor Station Critical Alarms Console Alarms report to: facalarmcon 24/7 Callout 1 Critical_1 Yes Yes Yes Yes Daytime Callout 2 Critical_2 Yes Yes Yes Yes Communication (Not Ping Alarms) Life Safety (Obsolete. Use Critical_1) 10 Communication Yes No No Yes 20 LifeSafety NO No No No DDC Critical 30 Critical Yes No No Yes Central Plant 40 CentralPlant Yes No No Yes Main Air Handlers Limited Building Hydronics 50 AHU Yes No No Yes 100 Hydronics Yes No No Yes HVAC General 120 HVAC_General Yes No No No Important s 150 Critical_Temps Yes No No Yes Troubleshooting 200 Troubleshooting Yes No No No Remainder, including all Ping Alarms 254 Default Alarm Class Yes No No No Campus DDC Alarm Servers R. Coordinate and implement alarm notifications and routing with the Owner. Include: 1. Paging Text Messaging 4. Group and network notifications 5. Alarm acknowledgement. 6. Filter and route alarms based on user log in. 7. Alarm reports and messages will be directed to a user defined list of operator devices. S. Provide hardware or interface required to implement alarm notification and routing. T. Provide state-based alarming to prevent alarms during specific equipment states. 1. Interlock equipment status and/or modes to lock out associated alarms during shutdowns. 2. Interlock acknowledgement to lock out associated alarm for limited adjustable time period. U. Provide continuous monitoring of network connectivity for the all networks. Generate alarm upon any communication failure. V. Alarms shall be inhibited for a specified time period after a change in occupancy or for AHUs that are off. November 2018 Page 31 of FDG Section

32 W. Contractor shall ensure that alarms passed to any remote Station Recipient shall retain alarm class and priority level. X. Contractor shall use only the exact Niagara alarm class names listed above to ensure compatibility with remote station recipients. Alarm Class Mapping is not acceptable. Note: Niagara object naming conventions do not permit spaces. Y. Alarms report to LocalHost Alarm Console on building control systems server. If project scope does not include a building control systems server, alarms report to Alarm Console in building level controller. Z. Alarm Source Name shall prepend with the following B-Formatting: %parent.parent.parent.displayname%_%parent.displayname% or as required to produce the format: StationName_ControllerNAme_PointName AA. Only the tooffnormal and tofault events require the alarms to be acknowledged. BB. tonormal and toalert events shall not require the alarms to be acknowledged REPORTS A. Coordinate report requirements with owner. B. Schedule initial reports printouts monthly per owner request including: 1. Utilities or Energy Management 2. Diagnostic or system status 3. Equipment runtime 3.12 Database Point Names A. All Niagara Database point names shall match naming of the sample Stations furnished to Contractor by Stanford FAC. B. All Niagara Database point names shall match Object Naming and Tags Spreadsheet furnished to Contractor by Stanford FAC. C. All Niagara Database point names shall be submitted to Stanford FAC for approval. Approval of Submitted Point Name does not constitute approval of the programming that uses the Submitted Point Name. Any additional Niagara Database point names are subject to approval by Owner. D. Any Niagara Database point names, that are created or modified without approval of Owner, may be required to be renamed, at no additional cost to Owner and without affecting Project Construction Schedule. END OF SECTION November 2018 Page 32 of FDG Section

33 THIS PAGE INTENTIONALLY BLANK November 2018 Page 33 of FDG Section

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Niagara4 Technical Certification Program Student Guide DAY 1 DAY 2

Niagara4 Technical Certification Program Student Guide DAY 1 DAY 2 Niagara4 Technical Certification Program Student Guide DAY 1 Welcome Course Introduction Platforms & Stations Niagara4 Fundamentals Simple Logic: Hot Water Pump Control (Thermostatic) Simple Logic: Hot

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

Samsung SDS BMS Ver.2.0. Technical Specification

Samsung SDS BMS Ver.2.0. Technical Specification Samsung SDS BMS Ver.2.0 Technical Specification Technical Specifications All rights and title, including all intellectual property rights to Samsung SDS BMS" is retained by Samsung SDS Co, Ltd. ("SDS"),

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Velocity INT-HIRSCH-A-Rev3 Copyright 2013 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation of this

More information

Building Automation System

Building Automation System University of New Hampshire University of New Hampshire Scholars' Repository Division 25 Integrated Automation Chapter 5 Technical Construction and Renovation Standards 8-1-2014 250000 - Building Automation

More information

American University Design Standards

American University Design Standards 25 95 00 CONTROL SEQUENCES FOR HVAC PART 1. GENERAL 1.01 SECTION INCLUDES A. Description of Work B. Control Sequences General Requirements C. System Specific Control Sequences 1.02 RELATED DOCUMENTS A.

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

SECTION FUNCTIONAL PERFORMANCE TESTING (FPT) PROCEDURES - CONSTRUCTION MANAGER EDITION

SECTION FUNCTIONAL PERFORMANCE TESTING (FPT) PROCEDURES - CONSTRUCTION MANAGER EDITION Montgomery County Public Schools Facilities DIVISION 1 - GENERAL REQUIREMENTS SECTION 01915 - FUNCTIONAL PERFORMANCE TESTING (FPT) PROCEDURES - CONSTRUCTION MANAGER EDITION PART 1 GENERAL 1.1 Section includes:

More information

Avigilon Control Center 5 System Integration Guide

Avigilon Control Center 5 System Integration Guide Avigilon Control Center 5 System Integration Guide with Hirsch Velocity INT-HIRSCH-B-Rev1 2012 2014 Avigilon Corporation. All rights reserved. Unless expressly granted in writing, no license is granted

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

Feature Summary. I. System

Feature Summary. I. System I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

Advanced Facility Air-Management Technology

Advanced Facility Air-Management Technology Internet-Enabled HVAC Monitoring & Control Maximum Digital Precision & Total Configuration Flexibility Pure and Simple Solutions Advanced Facility Air-Management Technology AbsolutAire s Facility Air-Management

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

i-vu CCN 4.0 Owner s Guide

i-vu CCN 4.0 Owner s Guide i-vu CCN 4.0 Owner s Guide CARRIER CORPORAION 2007 A member of the United echnologies Corporation family. Stock symbol UX. 11-808-377-01 07/07 able of Contents ACCESSING YOUR SYSEM... 3 YOUR SYSEM DEAILS...

More information

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT-1201736 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

Table of Contents. i-vu CCN Standard 4.2

Table of Contents. i-vu CCN Standard 4.2 i-vu CCN Standard 4.2 Owner's Guide CARRIER CORPORATION 2009 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-381-01 7/13/2009 Table of Contents Accessing your

More information

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS PART 1 - GENERAL 1.01 General: A. Laboratory ventilation system will ensure the health and safety of laboratory occupants. B. Room pressurization control will utilize airflow tracking to vary the volume

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Introduction. Introduction

Introduction. Introduction M-Alarm User s Guide 1-1 Chapter 1 Introduction Introduction M-Alarm allows the user to view, store, and manipulate current alarms received by N1 or BACnet Object Linking and Embedding (OLE) for Process

More information

Alarm Handling Subsystem (AHS) Requirements Specification. Enterprise Building Management System (EBMS)

Alarm Handling Subsystem (AHS) Requirements Specification. Enterprise Building Management System (EBMS) Alarm Handling Subsystem (AHS) Requirements Specification Enterprise Building Management System (EBMS) DOCUMENT HISTORY Version 0.1 0.2 0.3 1.0 1.1 1.2 Description DRAFT Delete references to alarms being

More information

Avigilon Control Center 5 System Integration Guide

Avigilon Control Center 5 System Integration Guide Avigilon Control Center 5 System Integration Guide for Paxton Net2 Access Control Systems 2014 Avigilon Corporation. All rights reserved. Unless expressly granted in writing, no license is granted with

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Gallagher Command Centre INT-CARDAX-C-Rev3 Copyright 2013 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

Delta ORCAview 3.40 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

Delta ORCAview 3.40 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT Date: December 12, 2012 Vendor Name: Delta Controls Inc. Product Name: ORCAview Product Model Number: DOW-340 Product Version: 3.40 BACnet Protocol Revision: 6 Product Description: ORCAview is an industry

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Related Sections..1 The contractor is to ensure that all related work is co ordinated among all specification sections, as well as between Division 11,

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

Student Services & Classroom Addition. Cranford, New Jersey SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Student Services & Classroom Addition. Cranford, New Jersey SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 230993 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Building Automation System (BAS) Design Criteria

Building Automation System (BAS) Design Criteria 25 0520 Building Automation System (BAS) Design Criteria 1. Design Statement a. During the various design phases of this project, the Engineer will develop options and strategies for selection of the appropriate

More information

I/A Series A 2 Software FoxAlert Alarm Manager

I/A Series A 2 Software FoxAlert Alarm Manager Product Specifications I/A Series A 2 Software FoxAlert Alarm Manager PSS 21S-2B2 B4 Current Alarms Display Most Recent Alarms Display Summary Displays By Status Alarm History Display An Extensive Collection

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

See Part II for additional information regarding Indoor Pollutant Reduction and Control, Energy Efficiency, etc.

See Part II for additional information regarding Indoor Pollutant Reduction and Control, Energy Efficiency, etc. UC Santa Cruz Campus Design Guide DIVISION 25 BUILDING AUTOMATION SYSTEMS (BAS) Includes the following sections: 25 00 00 (BAS) See Part II for additional information regarding Indoor Pollutant Reduction

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

November 11, City of Sparks 215 S. 21 st St. Sparks, NV November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of

More information

Selected Laboratory Energy Efficiency Measures

Selected Laboratory Energy Efficiency Measures Selected Laboratory Energy Efficiency Measures These are some of the most effective energy efficiency measures for laboratories 1. Reduce (optimize) air changes per hour in lab space 2. Design to the proper

More information

DeltaV Operate. DeltaV Operate. Introduction. DeltaV Product Data Sheet. Robust and secure plant operations

DeltaV Operate. DeltaV Operate. Introduction. DeltaV Product Data Sheet. Robust and secure plant operations February 2016 Page 1 DeltaV Operate You can easily manage your process with. Robust and secure plant operations Powerful operator interface, optionally up to four monitors Constant visibility and access

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

Instrumentation and Control for HVAC

Instrumentation and Control for HVAC 23 09 00 Instrumentation and Control for HVAC 1. All controls to be corporate Trane or Honeywell, no substitutes. 2. Factory Mounted controls to be Trane only, otherwise provide terminal strips for TC

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Mechanical. Environmental Control Systems. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Mechanical. Environmental Control Systems. Basis of Design Basis of Design University of Washington Specific Controls Features The following items are specific to the University of Washington: The goal is to move from pneumatic to DDC controls. This goal shall

More information

Psychrologix Controller W/ DHC

Psychrologix Controller W/ DHC Psychrologix Controller W/ DHC User Manual For Psychrologix version 1.3 Please read this entire document before connecting the Psychrologix controller. 1 *IMPORTANT PLEASE NOTE The Following: First, a

More information

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated

More information

OnGuard 7.2 Resolved Issues

OnGuard 7.2 Resolved Issues UTC Fire & Security Americas Corporation, Inc. 1212 Pittsford-Victor Road Pittsford, New York 14534 Tel 866.788.5095 Fax 585.248.9185 www.lenel.com Contents OnGuard 7.2 Resolved Issues 1. Introduction...

More information

ASHRAE Guideline 36 Advanced HVAC Control Sequences

ASHRAE Guideline 36 Advanced HVAC Control Sequences ASHRAE Guideline 36 Advanced HVAC Control Sequences Rick Stehmeyer - Senior Engineer Matt Napolitan, P.E., CCP, CPMP, LEED AP BD+C - Principal Image Source: http://worldatdistance.com/2013/10/07/the-complete-noobs-guide-to-making-a-website//

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

1.0 Digital Controller

1.0 Digital Controller 1.0 Digital Controller...1 1.1 Display Function Keys...1 1.2 Thermostat Display...2 1.3 Controller hardware input output points... 4 2.0 Sequence of Operation...5 2.1 States of Operation...5 2.2 Modes

More information

STEAMPAK Series BurnerPAK BMS Burner Management Systems

STEAMPAK Series BurnerPAK BMS Burner Management Systems BurnerPAK BMS Burner Management Systems Sequence of operation, ignition and control of burners Meets NFPA 85 safety standard MFT alarming with manual reset, first-out indication Optional enhanced alarming

More information

Modeling projects that require very tight space temperature control

Modeling projects that require very tight space temperature control Modeling projects that require very tight space temperature control Whereas space temperature controls for maintaining human thermal comfort typically have a deadband of several degrees between heating

More information

RPM1600 Series Room Pressure Monitors

RPM1600 Series Room Pressure Monitors RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT-12012228 Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

Integrated Automation Instrumentation & Terminal Devices

Integrated Automation Instrumentation & Terminal Devices Sections Included In This Standard: 1.1 Building Systems Control 1.2 Building Aumotation Systems (BAS) 1.1 BUILDING SYSTEMS CONTROL A. HVAC CONTROLS: 1. General: Temperature control zones shall not combine

More information

SECTION INTEGRATED AUTOMATION COMMISSIONING

SECTION INTEGRATED AUTOMATION COMMISSIONING SECTION 25 08 00 INTEGRATED AUTOMATION COMMISSIONING PART 1. GENERAL 1.01 SECTION INCLUDES: A. BAS and equipment testing and start-up B. Validation of proper and thorough installation of BAS and equipment

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Project Number QMSN Install Basewide EMCS System Moffett Federal Airfield, California

Project Number QMSN Install Basewide EMCS System Moffett Federal Airfield, California 1. Energy Management and Control System 1.1. Project Objective Project Number QMSN072015 Install Basewide EMCS System Moffett Federal Airfield, California The objective of this project is to provide a

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Picture Perfect 4 INT-PP4-A-Rev1 Copyright 2012 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation

More information

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT ENGINEERING GUIDE SPEC 1. GENERAL 1.1 SUMMARY A. Furnish all labor, materials, equipment, and service necessary for a complete and

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

DACC - NMDA BUILDINGS

DACC - NMDA BUILDINGS A PROJECT FOR: LAS CRUCES, NEW MEXICO PROJECT LOCATION LOCATION MAP INDEX OF DRAWINGS: CV001 - COVER SHEET M101 - OVERALL CAMPUS STEAM UTILITY PLAN M102 - DACC DAMA 341 PLAN M103 - DACC LRC & CLASSROOM

More information

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...

More information

BMS Specification. Lonix Ltd.

BMS Specification. Lonix Ltd. BMS Specification 1 (18) BMS Specification Lonix Ltd www.lonix.com BMS Specification 2 (18) INDEX 1 System Architecture...3 1.1 System Integration...3 1.2 Layered System Architecture...3 1.2.1 Service

More information

SECTION BUILDING AUTOMATION AND AUTOMATIC TEMPERATURE

SECTION BUILDING AUTOMATION AND AUTOMATIC TEMPERATURE SECTION 23 0900 - BUILDING AUTOMATION AND AUTOMATIC TEMPERATURE PART 1 - GENERAL 1.1 DESCRIPTION A. The work described under this division is for all labor, materials, and equipment required for the construction

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL ADDENDUM NO.1 March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL The data included hereinafter is issued by the Engineer (Engineered Systems Associates, 1355 East Center, Pocatello, ID

More information

A. GENERAL - Building Automation System (BAS) Contractor shall provide and install:

A. GENERAL - Building Automation System (BAS) Contractor shall provide and install: 11-01-2011 PART 1 GENERAL 1.01 Work Included: A. GENERAL - Building Automation System (BAS) Contractor shall provide and install: 1. A fully integrated Building Automation System (BAS), incorporating direct

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

Tech Data Sheet D01662GB0_Esgraf 4.1 and Configuration Server 30/2011 2/(5)

Tech Data Sheet D01662GB0_Esgraf 4.1 and Configuration Server 30/2011 2/(5) Tech Data Sheet D01662GB1_Esgraf 4.1 and Configuration Server 30/2011 1/(5) Esgraf 4.1 graphical user interface, configuration server and fire detectors contamination monitoring Esgraf 4.1 ESGRAF is a

More information

DeltaV Live. Introduction. Benefits. Modern, built-for-purpose operations experience

DeltaV Live. Introduction. Benefits. Modern, built-for-purpose operations experience DeltaV Distributed Control System Product Data Sheet December 2018 DeltaV Live Modern, built-for-purpose operations experience Easily create intuitive displays, with minimal to no scripting required Robust,

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 15990 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the Specifier in correctly specifying Mechanical System Testing Adjusting

More information

Monitor Alarms and Events

Monitor Alarms and Events This chapter contains the following topics: What Are Alarms and Events?, page 1 How are Alarms and Events Created and Updated?, page 2 Find and View Alarms, page 3 Set Alarm and Event Management Preferences,

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

Alarm Monitoring and Management

Alarm Monitoring and Management CHAPTER 9 This chapter describes Cisco Transport Controller (CTC) alarm management. To troubleshoot specific alarms, refer to the Cisco ONS 15310-CL Troubleshooting Guide. Chapter topics include: 9.1 Overview,

More information

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO The M & V Guided Recommissioning Process MOO Energy & Water Conservation Program September 2015 EWC Agenda MOO EWC Overview Our approach Progress Fault Detection Zone & customer feedback Variance reporting

More information

Architectural and Engineering Specification for a Security Management System. StarNet 2

Architectural and Engineering Specification for a Security Management System. StarNet 2 Architectural and Engineering Specification for a Security Management System StarNet 2 Jan 2, 2018 Page 1 of 12 AE-S2-IN-R1-EN-01/18 This document is intended to provide performance specifications and

More information

GMS GRAPHICAL MANAGEMENT SYSTEM

GMS GRAPHICAL MANAGEMENT SYSTEM GMS GRAPHICAL MANAGEMENT SYSTEM 1 GMS Security management system for multi-site organizations. PACOM Graphical Management System (GMS) is the modular client-server application that integrates all of PACOM

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Autoclave Operations Manual

Autoclave Operations Manual UNIVERSITY OF ILLINOIS AT URBANA/CHAMPAIGN - COMPOSITES MANUFACTURING LAB Autoclave Operations Manual Version 1 Written by KRH 2/21/2011 Contents ACCS... 4 Alarms... 7 Main Display Tabs... 7 Process Control

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information