LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

Size: px
Start display at page:

Download "LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems"

Transcription

1 LINETRAXX RCMA420 Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems RCMA420_D00059_01_D_XXEN/

2 LINETRAXX RCMA420 Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems Product description The AC/DC sensitive residual current monitor RCMA420 is designed for monitoring earthed power supply systems (TN and TT systems) where smooth DC fault currents or residual currents continuously greater than zero may occur. These are in particular loads containing six-pulse rectifiers or one way rectifiers with smoothing, such as converters, battery chargers, construction site equipment with frequency-controlled drives. Currents in single conductors can be monitored too. The prewarning stage ( % of the set response value I Δn2) allow to distinguish between prewarning and alarm. Since the values are measured with measuring current transformers, the device is nearly independent of the load current and the nominal voltage of the system. LINETRAXX RCMA420 Device features AC/DC sensitive residual current monitor Type B acc. to IEC and IEC/TR r.m.s. value measurement (AC+DC) Two separately adjustable response values ma Frequency range Hz Start-up delay, response delay and delay on release Digital measured value display via LC display Measured value memory for operating value CT connection monitoring LEDs: Power On, Alarm 1, Alarm 2 Internal/external test/reset button Two separate alarm relays (one changeover contact each) N/O or N/C operation and fault memory selectable Continuous self monitoring Multi-functional LC display Password protection for device settings Sealable transparent cover Two-module enclosure (36 mm) RoHS compliant Push-wire terminal (two terminals per connection) Applications AC/DC sensitive residual current monitoring in earthed two, three or four conductor systems (TN and TT systems) Monitoring of variable-speed drives, UPS systems, construction site equipment, printing machines, battery systems, laboratory equipment, wood working machines, MF welding systems, furniture industry, medical electrical equipment, etc. AC/DC sensitive current monitoring of, in the normal case, de-energised single conductors (e.g. N and PE conductors) Function Once the supply voltage U S is applied, the start-up delay is activated. Measured values changing during this time do not influence the switching state of the alarm relays. Residual current measurement takes place via an external measuring current transformer of the W20AB W60AB series. The currently measured value is shown on the LC display. In this way any changes, for example when circuits are connected to the system, can be recognised easily. If the measured value exceeds the set response values, the response delays t on1/2 begin. Once the response delay ton1/2 has elapsed, the K1/K2 alarm relays switch and the alarm LEDs AL1/AL2 light up. If the current falls below the release value (response value plus hysteresis), the release delay t off. When toff has elapsed, the alarm relays return to their initial position and the alarm LEDs AL1/AL2 go out. If the fault memory is activated, the alarm relays remain in the alarm state and the LEDs light until the reset button is pressed or until the supply voltage is interrupted. The device function can be tested using the test button. Parameters are assigned to the device via the LCD and the control buttons on the front panel; this function can be password-protected. Connection monitoring The function of the device and the CT connections are continuously monitored. In the event of a fault, the alarm relays K1/K2 switch without delay, the alarm LEDs AL1/AL2/ON flash. On removal of the fault, the alarm relays return to their initial position either automatically or by pressing the reset button. Approvals 2 RCMA420_D00059_01_D_XXEN/

3 Residual current monitor LINETRAXX RCMA420 Operating and display elements Wiring diagram U S Power On LED ON (green); lights when supply voltage is applied and flashes in the event of system fault alarm respectively in the event of CT malfunction. 2 - Alarm LED AL1 (yellow), prewarning; lights when the set response value I Δn1 is exceeded or flashes in the event of system fault alarm respectively in the event of CT malfunction 3 - Alarm LED AL2 (yellow), alarm; lights when the set response value I Δn2 is exceeded or flashes in the event of system fault alarm respectively in the event of CT malfunction. 4 - Multi-functional LC display Test button T : to call up the self test. Arrow up button: parameter change, to move up in the menu 6 - Reset button R : to delete saved alarms. Arrow down button: parameter change, to move down in the menu 7 - MENU button: to call up the menu system. Enter button: to confirm parameter change. ESC button: press the button > 1.5 seconds Supply voltage US see ordering information, 6 A fuse recommended 2 - Connector for the external W20AB W60AB series measuring current transformer 3 - Alarm relay K1 : I Δn1 (prewarning) 4 - Alarm relay K2 : alarm I Δn2 (alarm) 5 - Combined test and reset button T/R short-time pressing (< 1.5 s) = RESET long-time pressing (> 1.5 s) = TEST 3 4 Do not route the PE conductor through the measuring current transformer! RCMA420_D00059_01_D_XXEN/

4 Residual current monitor LINETRAXX RCMA420 Connection of measuring current transformers Dimension diagram XM420 I( n ) 500 ma I( n ) > 500 ma Dimensions in mm Open the front plate cover in direction of arrow! Screw mounting Note: The upper mounting clip must be ordered separately (see ordering information) Ordering information Supply voltage 1) US AC DC Type Art. No V, Hz V RCMA420-D-1 B V, Hz V RCMA420-D-2 B Device version with screw terminals on request. 1) Absolute values Accessories Type designation Mounting clip for screw mounting (1 piece per device) Art. No. B Suitable system components Type designation Measuring current transformers Internal diameter (mm) Type Art. No ø 20 W20AB B ø 35 W35AB B ø 60 W60AB B Connection to the RCMA420 residual current monitor using the WX- connecting cable. Colour coding for WX : k = yellow, l = green, -12 V = black, GND = brown, +12 V = red, Test (T) = orange Type designation Length/m Type Art. No Connection cable measuring current transformer 1 WX-100 B ,5 WX-250 B WX-500 B WX-1000 B RCMA420_D00059_01_D_XXEN/

5 Residual current monitor LINETRAXX RCMA420 Technical data Insulation coordination acc. to IEC /IEC RCMA420-D-1: Rated insulation voltage Rated impulse voltage/pollution degree Overvoltage category RCMA420-D-2: Rated insulation voltage Rated impulse voltage/pollution degree Overvoltage category Supply voltage 100 V 2,5 kv/3 III 250 V 4 kv/3 III RCMA420-D-1: Supply voltage range U S AC V/DC V Operating range U S AC V/DC V Frequency range U S DC, Hz RCMA420-D-2: Supply voltage range U S AC/DC V Operating range U S AC/DC V Frequency range U S Hz Protective separation (reinforced insulation) between (A1, A2) - (k/l, T/R) - (11, 12, 14) - (21, 22, 24) Voltage test according to IEC kv Power consumption 6,5 VA Measuring circuit External measuring current transformer W20AB, W35AB(P), W60AB(P) series Rated insulation voltage (measuring current transformer) 800 V Operating characteristic acc. to IEC and IEC/TR Type B Frequency range Hz Measuring range AC A Measuring range DC ma Relative uncertainty for f 2 Hz or 16 Hz 0-35 % Relative uncertainty for f >2 <16 Hz % Operating uncertainty 0 35% Response values Rated residual operating current I Δn1 (prewarning, AL1) % x IΔn2, (50 %)* Rated residual operating current I Δn2 (Alarm, AL2) ma (30 ma)* Hysteresis % (15%)* Specified times Starting delay t Response delay t on2 (alarm) Response delay t on1 (prewarning) Delay on release t off Operating time t ae at I Δn = 1 x I Δn1/2 Operating time t ae at I Δn = 5 x I Δn1/2 Response time t an Recovery time t b Displays, memory Display range, measured value AC Display range, measured value DC Error of indication Measured-value memory for alarm value Password Fault memory alarm relay 0 10 s (0.5 s)* 0 10 s (0 s)* 0 10 s (1 s)* 0 99 s (1 s)* 180 ms 30 ms t an = t ae + t on1/2 300 ms A ma ±17.5 %/± 2 digit data record measured values off/0 999 (off)* on/off (on)* Inputs/outputs Cable length for external test/reset button Cable lengths for measuring current transformers Connection WX or alternatively: single wire 6 x 0.75 mm² Switching elements 0 10 m 1 m/2.5 m/5 m/10 m 0 10 m Number of switching elements 2 x 1 changeover contact Operating principle N/C operation/n/o operation (N/C operation)* Electrical service life under rated operating conditions switching operations Contact data acc. to IEC Utilization category AC-13 AC-14 DC-12 DC-12 DC-12 Rated operational voltage 230 V 230 V 24 V 110 V 220 V Rated operational voltage UL 200 V 200 V 24 V 110 V 200 V Rated operational current 5 A 3 A 1 A 0.2 A 0.1 A Minimum contact load 1 ma at AC/DC 10 V Environment/EMC EMC IEC Operating temperature ºC Classification of climatic conditions IEC Stationary use (IEC ) 3K5 (except condensation and formation of ice) Transportation (IEC ) 2K3 (except condensation and formation of ice) Storage (IEC ) 1K4 (except condensation and formation of ice) Classification of mechanical conditions acc. to IEC 60721: Stationary use (IEC ) 3M4 Transportation (IEC ) 2M2 Storage (IEC ) 1M3 Connection For UL applications: use 60 C/70 C copper conductors only Connection type Connection properties: Rigid Flexible without ferrules Flexible with ferrules Stripping length Opening force Test opening, diameter Other push-wire terminals mm² (AWG 24 14) mm² (AWG 19 14) mm² (AWG 24 16) 10 mm 50 N 2.1 mm Operating mode continuous operation Position of normal use display-oriented Degree of protection, internal components (IEC 60529) IP30 Degree of protection, terminals (IEC 60529) IP20 Enclosure material polycarbonate Flammability class UL94V-0 DIN rail mounting acc. to IEC Screw fixing 2 x M4 with mounting clip Documentation number D00059 Weight 150 g ( )* = factory setting RCMA420_D00059_01_D_XXEN/

6 Bender GmbH & Co. KG P.O. Box Gruenberg Germany Londorfer Strasse Gruenberg Germany Tel.: Fax: BENDER Group RCMA420_D00059_01_D_XXEN / / pdf / Bender GmbH & Co. KG, Germany Subject to change! The specified standards take into account the version that was valid at the time of printing.

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage LINETRAXX VME420 Multi-functional monitoring relay for undervoltage, overvoltage and frequency monitoring in AC/DC systems with separate supply voltage VME420_D00026_01_D_XXEN/06.2016 LINETRAXX VME420

More information

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry LINETRAXX VMD420 Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry VMD420_D00137_02_D_XXEN/06.2016 LINETRAXX VMD420 Multi-functional

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) IR425-D4_D00039_04_D_XXEN/05.2017 ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits

More information

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents) Residual current monitor RCM470LY/RCM475LY for TN and TT systems (AC and pulsating DC currents) TDB401003en/03.2010 Residual current monitor RCM470LY Residual current monitor for TN and TT systems (AC

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) Insulation monitoring device for unearthed AC/DC control circuits (IT systems) TDB103005en/05.2013 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) Product description The

More information

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual Operating Manual RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C Residual current monitor with one analogue output signal for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 505 Grünberg Tel.: 00 807-0 Fax: 00 807-259 Insulation monitoring device for unearthed AC/DC systems (IT systems for the supply of operating theatre

More information

Operating Manual RCM420

Operating Manual RCM420 Operating Manual RCM420 Residual current monitor for AC current monitoring in TN and TT systems Software version: D240 V1.2x TGH1410en/03.2012 Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Germany

More information

LINETRAXX RCMS460-D/-L RCMS490-D/-L

LINETRAXX RCMS460-D/-L RCMS490-D/-L LINETRAXX RCMS460-D/-L RCMS490-D/-L Multi-channel AC, pulsed DC and AC/DC sensitive residual current monitors for earthed AC, DC and AC/DC systems (TN and TT systems) RCMS460-490_D00067_0_D_XXEN/09.207

More information

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V IR1575_D00116_00_D_XXEN/05.2015 Insulation monitoring device for unearthed AC/3(N)AC systems up to 480

More information

RCMA423. Residual current monitor for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software-Version: D330 V1.0x.

RCMA423. Residual current monitor for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software-Version: D330 V1.0x. EN Manual RCMA423 Residual current monitor for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software-Version: D330 V1.0x RCMA423_D00063_02_M_XXEN/05.2016 Bender GmbH & Co. KG P.O. Box

More information

CMD420 / CMD421 Series

CMD420 / CMD421 Series 3 T M CMD420 / CMD421 Series Digital Current Relay (Overcurrent and Undercurrent) For Three-Phase AC Systems Technical Bulletin NAE1032810 / 06.2016 CMD420 / CMD421 Digital overcurrent and undercurrent

More information

RCMA423-DM1C Residual current monitor

RCMA423-DM1C Residual current monitor EN Manual RCMA423-DM1C Residual current monitor with one analogue output signal and an alarm relay for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software version: D330 V1.0x RCMA423-DM1C_D00247_00_M_XXEN/06.2016

More information

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE Insulation monitoring device with integrated load and temperature monitoring and locating current injector for insulation fault location systems for medical IT systems _D00043_02_D_XXEN/09.2016 Insulation

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE / 3 GM20 Digital Ground Continuity Relay For AC Systems Technical Bulletin NAE03230 / 0.20 GM20 Ground continuity monitor For AC systems Description The GM20 monitors the loop resistance of ground conductors

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

Insulation fault evaluator EDS460-DG

Insulation fault evaluator EDS460-DG Insulation fault evaluator for localising insulation faults in DC IT systems with a number of branch circuits where high system leakage capacitances are involved Preliminary data sheet TDB108021en/09.2008

More information

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems) ISOSCAN EDS460/490 EDS461/491 Insulation fault locators with control and display function for EDS systems (insulation fault location systems) EDS460-490_D00085_01_D_XXEN/01.2017 ISOSCAN EDS460/490 EDS461/491

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) T M 1 isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012670 / 08.2013 isopv425

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Bender Incorporated 700 Fox Chase, Coatesville PA 1930 Tel.: (800) 356-466 Fax: (610) 383-7100 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control function

More information

Operating Manual VMD420

Operating Manual VMD420 Operating Manual VMD420 Voltage and frequency monitor for monitoring of 3(N)AC systems up to 0...500 V for undervoltage and overvoltage and under and overfrequency Software version: D238 V2.2x Power in

More information

Manual CME420. Multi-functional current relay, AC, overcurrent/undercurrent/ window discriminator function CME420_D00034_02_M_XXEN/05.

Manual CME420. Multi-functional current relay, AC, overcurrent/undercurrent/ window discriminator function CME420_D00034_02_M_XXEN/05. EN Manual CME420 Multi-functional current relay, AC, overcurrent/undercurrent/ window discriminator function CME420_D00034_02_M_XXEN/05.2016 Bender GmbH & Co. KG P.O. Box 1161 35301 Gruenberg Germany Londorfer

More information

VME420 Voltage and frequency monitor

VME420 Voltage and frequency monitor EN Manual VME420 Voltage and frequency monitor for monitoring AC/DC systems of 0 300 V, 15 460 Hz for undervoltage, overvoltage, underfrequency, overfrequency Software version: D235 V2.2x VME420_D00026_02_M_XXEN/06.2016

More information

VME421H Voltage and frequency monitor

VME421H Voltage and frequency monitor EN Manual VME421H Voltage and frequency monitor for monitoring AC/DC systems for undervoltage, overvoltage, underfrequency and overfrequency Software version VME421H-D-1: D236 V2.2x Software version VME421H-D-2:

More information

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 505 Grünberg Tel.: 060 807-0 Fax: 060 807-59 A-ISOMETER IRDH575 Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with

More information

Bender GmbH & Co. KG. All rights reserved. Reprinting only with permission of the publisher. Subject to change! Photos: Bender archives

Bender GmbH & Co. KG. All rights reserved. Reprinting only with permission of the publisher. Subject to change! Photos: Bender archives EN Manual VMD421H Voltage and frequency monitor for undervoltage, overvoltage, underfrequency and overfrequency monitoring in 3(N)AC systems of 70...500 V Software version D239 V2.2x VMD421H_D00138_01_M_XXEN/05.2016

More information

Remote alarm indicator and test combination MK2430

Remote alarm indicator and test combination MK2430 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Tel.: 040 807-0 Fax: 040 807-259 Remote alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC

More information

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) T M 1 isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012372 / 03.2015 isopv

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Phone: 040 807-0 Fax: 040 807-259 Alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC display

More information

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

DEB71. Earth Leakage Monitoring Relay. Benefits. Description Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional

More information

LINETRAXX RCMS150. Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems)

LINETRAXX RCMS150. Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems) EN Manual LINETRAXX RCMS150 Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems) for COMTRAXX 2.1, Option C RCMS150_D00259_00_M_XXEN/08.2016

More information

TM800. Remote alarm indicator and operator panels

TM800. Remote alarm indicator and operator panels TM800 Remote alarm indicator and operator panels TM800_D00165_00_D_XXEN/12.2014 TM800 Remote alarm indicator and operator panels TM800 Device features Display, control and operation of Bender monitoring

More information

IT system floor-standing distribution

IT system floor-standing distribution IT system floor-standing distribution cabinet series -IPS-F/EDS for supplying power to medical locations in accordance with IEC 60364-7-710 and featuring a built-in insulation fault location system IT

More information

ISOMETER IRDH265 IRDH365

ISOMETER IRDH265 IRDH365 EN Manual ISOMETER IRDH265 IRDH365 Insulation monitoring devices for IT AC systems, IT AC systems with galvanically connected DC circuits and for IT DC systems (isolated power) IRDH265-365_D00014_01_M_XXEN/09.2015

More information

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE Cat. N STOP & GO automatic resetting 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat. N (s) : 4 062 88 / 4 062 89 CONTENTS PAGE 1. Description - Use... 1 2. Product

More information

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description DPB52 True RMS 3-Phase, Multifunction monitoring relay Description Benefits Measuring Voltage Range. Very wide input voltage range: from 125 to 624V ( 208V 40% to 480 + 30% ). Adjustable Voltage Ranges

More information

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description Three phase AC pumps and ventilators soft starter Description Benefits Easy to use. The is equipped with a self-learning algorithm that automatically adjusts the start parameters to optimise the motor

More information

BENDER A-ISOMETER IRDH265 IRDH365

BENDER A-ISOMETER IRDH265 IRDH365 A-ISOMETER IRDH265 IRDH365 BENDER Insulation monitoring devices for IT AC systems, IT AC systems with galvanically connected DC circuits and for IT DC systems (isolated power) Manual D0001400MXXEN Bender

More information

Operating Manual TR600

Operating Manual TR600 ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN

More information

Line Isolation Monitor (LIM) LIM2000plus

Line Isolation Monitor (LIM) LIM2000plus Line Isolation Monitor (LIM) LIM2000plus for Single and Three Phase Systems TDB207005usa/10.2008 BENDER Group Line Isolation Monitor LIM2000plus for Single and Three Phase Systems LIM2000plus Device features

More information

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440) Safety Temperature Limiter STL 50 Certified to DIN EN 14597 (replaces DIN 3440) Features M For use as: STB Protection - temperature limiter ASTB Exhaust gas - protection - temperature limiter STW Protection

More information

T M LIM2010. Line Isolation Monitor (LIM) Technical Bulletin NAE /

T M LIM2010. Line Isolation Monitor (LIM) Technical Bulletin NAE / 2 T M LIM2010 Line Isolation Monitor (LIM) Technical Bulletin NAE2022011 / 04.2015 Line Isolation Monitor LIM2010 Description The LIM2010 Line Isolation Monitor (LIM) measures the Total Hazard Current

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Technical Information RTA421 Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Application Plant and machine construction Panel builders Process monitoring Process

More information

MK Series. Remote Indicators For Line Isolation Monitors and Fault Location. Technical Bulletin NAE /

MK Series. Remote Indicators For Line Isolation Monitors and Fault Location. Technical Bulletin NAE / 2 MK Series Remote Indicators For Line Isolation Monitors and Fault Location Technical Bulletin NAE2022020 / 09.2011 Remote Indicators MK2000 Series MK Series Device features LED display for long life

More information

Project planning (original) EN. Functional safety. Inverter i550-cabinet kw

Project planning (original) EN. Functional safety. Inverter i550-cabinet kw Project planning (original) EN Functional safety Inverter i550-cabinet 0.25... 45 kw This page intentionally left blank! Contents Contents Safety instructions 4 Basic safety measures 4 Residual hazards

More information

Process Alarm Module RTA 421

Process Alarm Module RTA 421 Technical Information TI 074R/24/ae Process Alarm Module RTA 421 Alarm module and power supply for monitoring current or voltage signals Application Areas Plant and machine construction Panel builders

More information

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content 8 Appendix 8.1 Wiring examples...4 8.2 Start configuration...4 8.3 Sensor configuration...4 8.4 Actuator configuration...5 Operating instructions.............pages 1 to 6 Original 9 EU Declaration of conformity

More information

Parameterisable compact fault annunciator with permanent display

Parameterisable compact fault annunciator with permanent display Parameterisable compact fault annunciator with permanent display FSM 10 Drop-flap fault annunciator 31.08.2010 Permanent display even on power failure Compact module for 10 alarms Supply and alarm signal

More information

SCHMIDT LED Measured Value Display MD Instructions for Use

SCHMIDT LED Measured Value Display MD Instructions for Use SCHMIDT LED Measured Value Display MD 10.010 Instructions for Use Table of Contents 1 Important Information... 3 2 Application range... 4 3 Mounting instructions... 4 4 Electrical connection... 6 5 Signalizations...

More information

Product overview. Alarm indicator, operator and display panels

Product overview. Alarm indicator, operator and display panels Product overview Alarm indicator, operator and display panels 1 2 Innovative operating concepts for safe power supply in all medical locations Despite all technology that is necessary in medical locations

More information

Operating Instructions for Limit switch Model: NBK-R NBK-RM NBK-RT NBK-RA

Operating Instructions for Limit switch Model: NBK-R NBK-RM NBK-RT NBK-RA Operating Instructions for Limit switch Model: NBK-R NBK-RM NBK-RT NBK-RA 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 3 4.1 Electrical limit switch... 4

More information

Operation and use. Functions and characteristics

Operation and use. Functions and characteristics Operation and use Function Vigirex relays measure the earth-leakage current in an electrical installation via their associated toroids. Vigirex relays may be used for: b residual-current protection (RH10,

More information

Operating Manual MSF220V(VU)

Operating Manual MSF220V(VU) ZIEHL industrie elektronik GmbH + Co KG Daimlerstr.13, 74523 Schwäbisch Hall, Germany + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperaturrelais und MINIKA Strom- und Spannungsrelais Messgeräte MINIPAN

More information

PolyGard 2-channel Gas Controller MGC-03

PolyGard 2-channel Gas Controller MGC-03 PolyGard 2-channel Gas Controller MGC-03 DESCRIPTION Gas measuring and monitoring controller based on state-ofthe-art micro-technology with integrated buzzer for continuous monitoring of the ambient air

More information

Universal fault annunciator for panel mounting

Universal fault annunciator for panel mounting Universal fault annunciator for panel mounting Communication over Ethernet USM - Universal-fault annunciator for panel mounting Low depth housing for panel mounting Versions with 8, 16, 32 or 48 inputs

More information

Multi-Gas-Controller MGC2

Multi-Gas-Controller MGC2 Page 1 Aug. 2018 Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology for continuous monitoring of the ambient air to detect toxic and combustible gases, refrigerants

More information

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document 1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for

More information

Soft Starter Centrifugal Pump Soft Starter Series

Soft Starter Centrifugal Pump Soft Starter Series Soft Starter Centrifugal Pump Soft Starter Series Type RSWT Optimised algorithm for centrifugal pumps Simple User Interface 3-phase controlled Internally bypassed Multi voltage operation Integrated overload

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions Worldwide upplier of Gas Detection olutions GfG Instrumentation 1194 Oak Valley Drive, uite 20 Ann Arbor, MI 48108 800-959-0329 tel 734-769-1888 fax email: info@gfg-inc.com GMA4100-DP Control Panel Operation

More information

Inductive Conductivity Measurement. Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement symbol.

Inductive Conductivity Measurement. Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement symbol. Process Analysis Systems Chem Energy Pharm Food Water Stratos Eco 2405 CondI Inductive Conductivity Measurement Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement

More information

AO Annunciator Module

AO Annunciator Module General Specifications GS48C43Z01-00E-N AO-543-01 Annunciator Module GENERAL Figure 1 This module has two independent annunciator circuits. The circuits handle fault signals and operator actions (acknowledge,

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point Medium - Control - System Franke & Haqenest GmbH Borngasse 1a * 04600 Altenburg Tel: 03447-499 313-0 Fax: 03447-499 313-6 email: info@mcs-gaswarnanlagen.de MCS User Guide MCS GasController Microprocessor

More information

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

EARTH LEAKAGE RELAY. User Manual - Issue 1.0 Earth Leakage Relay www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters EARTH

More information

Key-Operated Switch GMA 41 / GMA 44 SW. Operation Manual

Key-Operated Switch GMA 41 / GMA 44 SW. Operation Manual Key-Operated witch GMA 41 / GMA 44 W Operation Manual Table of contents Page Introduction... 4 Key function... 4 Distinction of GMA 41/44 W models... 4 Relays... 5 P.C. boards of GMA 41/44 W... 7 Terminal

More information

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK Analox 1000 Series User Manual Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK T: +44 (0)1642 711400 F: +44 (0)1642 713900 W: www.analox.net E: info@analox.net

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on 24 V supply lines for medical locations SELVTESTER-24

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on 24 V supply lines for medical locations SELVTESTER-24 INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on 24 V supply lines for medical locations SELVTESTER-24 1/8 More information than that reported in this

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2017-01-25 2001-2017 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2018-07-06 2001-2018 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

CONTROL DEVICE SLIDETRONIC HD

CONTROL DEVICE SLIDETRONIC HD CONTROL DEVICE SLIDETRONIC HD to control gravity self-closing fire gates Producer: Somati system s.r.o. Jihlavská 510/2c 664 41 Troubsko, okr.brno - venkov Tel.: 547 427 011 Fax: 547 427 013 E-mail: export@somati-system.cz

More information

T M. User Manual LIM2010. Line Isolation Monitor

T M. User Manual LIM2010. Line Isolation Monitor T M User Manual Line Isolation Monitor TGH1436en / NAE2025011 / 02.2013 T M Bender Inc. USA: 700 Fox Chase Coatesville, PA 19320 Toll Free: 800-356-4266 Phone: 610-383-9200 Fax: 610-466-2071 E-mail: medical@bender.org

More information

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage. Product Bulletin VeriSafe Absence of Voltage The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification

More information

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor

More information

ISIS SAFETY SYSTEM Installation guide

ISIS SAFETY SYSTEM Installation guide ISIS SAFETY SYSTEM Installation guide CAUTION This information is designed to help suitably qualified personnel install and operate Mechan Safety equipment. Before using this product, read this guide thoroughly

More information

Operating Manual MS220DA

Operating Manual MS220DA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN

More information

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

A-ISOMETER IRDH575. Operating Manual

A-ISOMETER IRDH575. Operating Manual Operating Manual A-ISOMETER IRDH575 Insulation monitoring for ungrounded AC and DC systems with integrated test generator and controller for EDS46..., EDS47... and EDS49... systems Software version: D185

More information

INSTALLATION & USER MANUAL

INSTALLATION & USER MANUAL INSTALLATION & USER MANUAL HC Digital Automatic Humidistat (Y3760) CONTROLS 506808-01 3/2016 Supersedes 6/2011 picture goes here THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE NOTICE

More information

ISOMETER IRDH375 IRDH375B

ISOMETER IRDH375 IRDH375B EN Manual ISOMETER IRDH375 IRDH375B Insulation monitoring device for IT AC systems with galvanically connected rectifiers and converters and for IT DC systems IRDH375: Software-Version D0183 V1.8 IRDH375B:

More information

Radio fire warning panel SRC 3000

Radio fire warning panel SRC 3000 Radio fire warning panel SRC 3000 6 zone radio fire warning panel Operating instructions Version 1.2 Art. 32487 detectomat GmbH Headquarter: Phone: +49 (0) 4102-2114-60 An der Strusbek 5 Fax: +49 (0) 4102-2114-670

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

Monitoring Devices 11/1

Monitoring Devices 11/1 11/4 Introduction 11/6 5TE5 8 light indicators 11/7 4AC3 0, 4AC3 1 bells, buzzers 11/7 5TT3 46 fault signaling units 11/8 7LQ2 1, 5TT3 3 dusk switches 11/9 7LQ2 0 temperature controllers 11/9 5TT3 170

More information

Dräger PointGard 2100 Detection of toxic gases and vapours

Dräger PointGard 2100 Detection of toxic gases and vapours Dräger PointGard 2100 Detection of toxic gases and vapours The Dräger PointGard 2100 series is a self-contained gas detection system for the continuous area monitoring of toxic gases in ambient air PointGard

More information

LC1350 Level Controller

LC1350 Level Controller LC1350 Controller Description The Spirax Sarco LC1350 has two alarm channels that can be independently configured high or low to control the water level of a boiler, tank or vessel by operating a pump,

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

Ordering Key. Dielectric strength

Ordering Key. Dielectric strength Controllers AC Semiconductor Controller Type Soft starting and stopping of 3-phase squirrel cage motors Low inrush and reduced vibration during starting Integrated bypassing of semiconductors Rated operational

More information

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24 Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24 Soft starting of 1-Phase Scroll Compressors Enclosed solution Integrated current limit Rated operational voltage: 230 VACrms, 50/60

More information

DICTATOR Hold-Open Systems for Hazardous Areas

DICTATOR Hold-Open Systems for Hazardous Areas DICTATOR for Hazardous Areas Products to be used in hazardous areas obviously have to meet special demands. The European ATEX directives (first the EN 94/9/EG and then the directive 2014/34/ EU) brought

More information

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage. Product Bulletin The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification test to validate the

More information

Easy to use, initiate test with the push of a button No additional tools required Provides visual alert to abnormal power conditions

Easy to use, initiate test with the push of a button No additional tools required Provides visual alert to abnormal power conditions Product Bulletin VeriSafe Absence of Voltage The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification

More information

RSGD. Three phase AC motor soft starter. Benefits. Description

RSGD. Three phase AC motor soft starter. Benefits. Description Three phase AC motor soft starter Description Benefits Easy to use. The is equipped with a self-learning algorithm that automatically adjusts the start parameters to optimise the motor starts and stops.

More information

DTA. Motor thermistor relay. Benefits. Description

DTA. Motor thermistor relay. Benefits. Description DTA Motor thermistor relay Description DTA71 and are precise Motor thermistor monitoring relays. They can monitor up to 6 motor temperatures through the motor internal temperature. PTCs are connected in

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information