La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Size: px
Start display at page:

Download "La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual"

Transcription

1 La Marche Manufacturing Company Option 46 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain the newest version of the manual at Bradrock Dr. Des Plaines, IL CPN Instruction Drawing Number: P25-LOPT46SERIES-1 i Tel: Fax: Revision A04 Rev. Date: 03/17 ECN: 21360

2 1.0 Option 46 Series Operation 1.1 General Description The 46 series option includes the user-interface LCD display panel which has three LED indicators on the front panel and two LED indicators on the door. Two LEDs on the panel are used as status indicators for Float and Equalize mode and one LED refers to the alarm present (if any). Refer to Figure 1. Four buttons are provided on the display for menu navigation RESET, MODE, UP, and DOWN Figure 1 LCD Display Showing System Outputs (while in Float Mode) NOTE: In the 46J, 46Q, 46T, and 46U option, two LEDs will be provided on the front panel as positive ground and negative ground alarm indicators. Refer to Figure 2A. In the 46P and 46T option, an audible alarm with silence switch will be provided on the front panel. In the 46A option, ten LEDs will be provided on the front panel. The AC ON LED will illuminate (in green) whenever power is provided to the charger. The remaining nine LEDs will illuminate (in red) each under a specific alarm condition. Refer to Figure 2B. Figure 2A Negative and Positive Ground LEDs (On Front Panel 46J/Q/T/U Option) Figure 2B LED indicators (On Front Panel 46A Option) Pushing the UP or DOWN button changes the display. The following items can be displayed: EQ Timer Setting Displays what the Equalize timer is currently set to. Time until next Equalize Displays a countdown to the next Equalize charge cycle. Timer Mode Shows what Equalize timer mode the charger is currently in with a short description listed on the second line. When the charger is in Equalize mode, the display will change to show the DC output voltage and DC output current, as well as the time remaining in the current Equalize charge cycle. Pushing the UP or DOWN button will change the display in Equalize mode as well. Refer to Figure 3. Figure 3 LCD Display Showing System Output and EQ Timer (while in Equalize Mode) 2

3 1.2 Selecting the Charging Mode The digital display used in the 46 series has two modes for DC output voltage Float mode and Equalize mode. Float charging mode is used for all normal battery charging needs. Equalize mode is used when it is necessary to Equalize (or balance) the level of charge across all cells present in the battery. Two LEDs, marked Float and Equalize on the front panel, indicate the present mode of operation of the charger. If the charger is in Float mode, simply press the MODE button to switch into Equalize mode. If the charger is in Equalize mode, it will automatically switch back to Float mode after the designated Equalize time cycle is complete; alternatively, the charger can manually be switched to Float mode by pressing the MODE button. 2.0 Alarms The available alarms for the 46 Series are: Low Voltage1, Low Voltage2, End of Discharge, Low Current, Overload Current/Current Limit, High Voltage, High Voltage Shutdown, Positive Ground, Negative Ground, AC Power Failure, Charger Failure, Over Temperature, and Summary. The LCD display will show a message when an alarm is triggered, if applicable. Figures 4A 4E illustrate the alarm relays provided on the 198 relay board, dependent on the option. Each set of alarm relays have two sets of dry form C contacts which function identical to each other. Not all alarms have a set of alarm relays assigned and not all alarm relays function the same; refer to Table 1 for the logic of each relay. Figure 4A (46J/T Option) Figure 4B (46E/G/P Option) Figure 4C (46L Option) S2A-198 Relay Information Relay Function High DC Voltage Shutdown Low DC Current High DC Voltage Low DC Voltage 1/ Low DC Voltage 2 (End of Discharge) AC Power Failure Summary Positive Ground Negative Ground Logic Energize On Fail De-Energize On Fail Energize On Fail De-Energize On Fail De-Energize On Fail De-Energize On Fail Energize On Fail Energize On Fail Figure 4D (46Q Option) Figure 4E (46U Option) Table 1 NOTE: See schematic or manual cover page to determine which alarm option is included. 3

4 2.1 Alarm Contact Specifications Load Resistive Load (P.F. = 1) Contact Material Ag (Au clad) Maximum Allowed Current 2 A 0.5 A at 125 VAC Max. Operating Voltage and Current 0.25 A at 125 VDC 2 A at 30 VDC Max. Switching Capacity VA 60 W Min. Permissible Load 10 ua, 10 mvdc 2.2 Alarm Definitions Table 2 AC POWER FAILURE ALARM will trigger, the green AC ON LED will turn off (if applicable), and the red AC FAILURE LED will turn on (if applicable) if the AC power to the charger is lost for longer than 5 seconds. The alarm will automatically reset when AC power is restored to the charger. When AC power is lost, the front panel display and indicators will remain powered by the connected batteries. LOW DC VOLTAGE ALARM will trigger and the red LOW DC VOLTAGE LED will turn on (if applicable) if the DC voltage falls below the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the low DC voltage condition is no longer present. END OF DISCHARGE ALARM will trigger and the red BATTERY END OF DISCHARGE LED will turn on (if applicable) if the DC voltage falls below the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the low DC voltage condition is no longer present. Some options will define this as an End of Discharge Alarm with a different threshold. HIGH DC VOLTAGE SHUTDOWN ALARM will trigger and the red HIGH DC VOLTAGE SHUT DOWN LED will turn on (if applicable) if the output DC voltage of the charger rises above the alarm threshold for longer than 20 seconds and there is load on the charger. If the High DC Voltage Shutdown alarm activates, the DC output of the charger shuts off to prevent irreversible damage to the battery. This alarm will stay latched until the charger is reset by isolating from all power sources or pushing the RESET button. NOTE: This alarm will not trigger if there is a Low Current alarm present. HIGH DC VOLTAGE ALARM will trigger and the red HIGH DC VOLTAGE LED will turn on (if applicable) if the output DC voltage rises above the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the high DC voltage condition is no longer present. LOW DC CURRENT ALARM will trigger and the red LOW DC CURRENT LED will turn on (if applicable) if the output DC current of the charger falls below the alarm threshold for longer than 5 seconds. This alarm can be disabled if considered a nuisance alarm. OVERLOAD/CURRENT LIMIT LED will turn on (if applicable) if the DC current exceeds the specified current threshold of the alarm for longer than 5 seconds. SUMMARY ALARM will default trigger if any of the other alarms are triggered. There is no Summary alarm LED, only alarm contacts. The Low Current, AC Power Failure, Overload Current, and Ground Detection alarms can be removed from the Summary alarm, but are included by default. POSITIVE GROUND ALARM will trigger and the green POSITIVE GROUND LED will turn on if 1.2mA or greater current is measured between the positive terminal of the battery and earth ground for longer than 5 seconds. The alarm will clear once the positive ground fault is no longer present. NEGATIVE GROUND ALARM will trigger and the green NEGATIVE GROUND LED will turn on if 1.2mA or greater current is measured between the negative terminal of the battery and earth ground for longer than 5 seconds. The alarm will clear once the negative ground fault is no longer present. 4

5 NOTE: The Charger Failure alarm does not have an LED indicator on the front panel; if the alarm occurs, it will appear on the digital display. A Charger Failure alarm occurs when one of the following conditions are present: Simultaneous Low DC Voltage and Low DC Current, or High Voltage Shutdown. Alarm Delay (sec.) Summary Selectable Clearing Threshold Alarming Threshold (V/C) LED Indication (If Applicable) AC Power Failure 5 Yes - - AC FAILURE Low DC Voltage 5 No 5% LA / 1.2 NC LOW DC VOLTAGE End of Discharge 5 No 5% (of shown DCV) 1.75 LA / 1.1 NC BATTERY END OF DISCHARGE High DC Voltage 5 No LA / 1.61 NC HIGH DC VOLTAGE High Voltage Shut Down 20 No LA / 1.65 NC HIGH DC VOLTAGE SHUTDOWN Low DC Current 5 Yes * * LOW DC CURRENT Overload/ Current Limit 5 Yes - Refer to Manual OVERLOAD / CURRENT LIMIT Summary Other Alarms - Positive Ground 5 Yes - - POSITIVE GROUND Negative Ground 5 Yes - - NEGATIVE GROUND Charger Failure None - - Low DCV & Low DCA / High DCV Shutdown - Table 3 Alarm Default Values & Indications * Low Current alarming threshold is dependent on shunt size V/C Volts per Cell, LA Lead Acid, NC Nickel Cadmium NOTE: These recommended parameters are set as factory default settings. If required, change the alarm threshold levels after verifying with battery manufacturer. 2.3 Alarm Connection Procedure Before making any alarm connections, ensure that the AC power is off at the main breaker. Verify that no voltage is present by using a voltmeter at all AC and DC terminals. For relays mentioned as ENERGIZED on alarm condition: If it is desired that the annunciator be active until the alarm triggers, connect the annunciator leads to the NC and C contacts of the desired alarm (located on the relay alarm contacts on S2A-198 board). If it is desired that the annunciator be deactivated until the alarm triggers, connect the annunciator leads to the NO and C contacts of the desired alarm. For relays mentioned as DE-ENERGIZED on alarm condition: If it is desired that the annunciator be active until the alarm triggers, connect the annunciator leads to the NO and C contacts of the desired alarm (located on the relay alarm contacts on S2A-198 board). If it is desired that the annunciator be deactivated until the alarm triggers, connect the annunciator leads to the NC and C contacts of the desired alarm. 5

6 3.0 Adjusting Parameters All equipment is shipped from the factory fully checked and adjusted based on the customer order. Do not make any adjustments unless the equipment has been powered-up and the settings have been determined to be incorrect. If the settings have been determined to be incorrect, adjustments may be made as detailed below. 3.1 Customer Calibration Mode In Customer Calibration Mode, the customer can access and change various parameters. To access the Customer Calibration Mode, press both the UP and MODE buttons (press the UP button first - the LCD display should change. Hold it down and then press the MODE button) for about 5 seconds. After Customer Calibration Mode appears on the LCD display, release both buttons. Once in calibration mode, the customer can raise and lower values with the UP and DOWN buttons and can advance to the next parameter with the MODE button. After the last setting is passed, all settings will automatically be saved. If a setting is accidentally passed over, the customer must advance through the remaining features and restart calibration from the beginning. Alternatively, the customer can press the RESET button and restart calibration from the beginning. The calibration settings are listed in order below with a brief description and default values. NOTE: Some chargers may have additional settings included in the Customer Calibration menu; contact La Marche for further explanation of settings not mentioned below. The Customer Calibration menu is as follows: Low Voltage Alarm This setting changes the voltage threshold that causes the Low DC Voltage Alarm to activate. The default setting is 1.98 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default Low Voltage alarm setting of 47.5VDC) Battery End of Discharge Alarm This setting changes the voltage threshold that causes the Battery End of Discharge Alarm to activate. The default setting is 1.75 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default Battery End of Discharge alarm setting of 42VDC) High Voltage Shutdown Alarm This setting changes the voltage threshold that causes the High Voltage Shutdown Alarm to activate. The default setting is 2.50 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default High Voltage Shutdown alarm setting of 60VDC) High Voltage Alarm This setting changes the voltage threshold that causes the High Voltage Alarm to activate. The default setting is 2.45 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default High Voltage alarm setting of 58.8VDC) Low DC Current Alarm This setting changes the current threshold that causes the Low DC Current Alarm to activate. The default setting is dependent on the shunt size. This alarm can be disabled if considered a nuisance alarm by lowering the threshold value to OFF. Overload Current Alarm This setting changes the current value that causes the Overload Current Alarm to activate. EQ Timer Mode This setting changes the mode of the Equalize Timer. The Equalize timer mode determines when the charger will go into an Equalize charging cycle. The timer modes are Mode 0 (P0), Mode 1 (P1), Mode 2 (P2), Mode 3 (P3), and Mode 4 (P4). The default setting for the Equalize timer mode is Mode 0 (P0). The Equalize Timer Modes are discussed in further detail in Section

7 EQ Timer Setting This setting changes the amount of time that the charger remains in the Equalize charging cycle once activated. When an Equalize cycle is started, the charger will remain in Equalize mode until the time selected by this setting has passed. By default, the Equalize timer is set for 8 hours. The battery manufacturer documentation should be referenced for battery specific settings. LCD Backlight This setting changes the behavior of the LCD Backlight. By default, the backlight is set to turn off two minutes after the last key press on the display membrane. Alternatively, the backlight can be set to Always ON. Modbus Address This setting changes the address of the Modbus. If the customer has purchased a Communication Board (Option 21P/21Q), this setting should be set to All in order to access further options of the communication board. Modbus Baud Rate This setting changes the Modbus Baud Rate. The default baud rate is The baud rate of the charger should be set to match the baud rate of the computer that is connected. Parity Type This setting changes the parity type. The default setting is None. 3.2 Equalize Timer Modes The 46 series offers five different modes of Equalize charging operation. The Equalize mode can be viewed on the charger display by using the UP or DOWN button to scroll through the menu. The Equalize mode can be changed via the Customer Calibration menu, refer to section 3.1. In all of the Equalize modes below, the charger will return to Float mode if the MODE button is pressed or when it completes its full charge time. Mode 0 (Displayed as P0 ) Mode 0 is a manual Equalize cycle and is the default setting for the charger. When the charger is set for Mode 0, the Equalize cycle must be activated manually. Once activated, the Equalize timer will turn on and the Equalize "LED" will light. The length of the timer is eight hours by default and can be changed via Customer Calibration. After the timer cycles to zero, the charger will immediately return to Float mode. Equalize mode will not start again until it is manually activated by the user. Mode 1 (Displayed as P1 ) Mode 1 is an automatic Equalize cycle that activates every 7 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 7 days. Mode 2 (Displayed as P2 ) Mode 2 is an automatic Equalize cycle that activates every 14 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 14 days. Mode 3 (Displayed as P3 ) Mode 3 is an automatic Equalize cycle that activates every 30 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 30 days. Mode 4 (Displayed as P4 ) Mode P4 is an automatic Equalize cycle that is triggered when the battery experiences a sizeable discharge. When the DC voltage drops below the Low Voltage alarm threshold, and exceeds the Low Voltage alarm time delay, Mode 4 is activated. However, the Equalize timer will only start and run the charger in Equalize mode for the duration set in the Equalize menu after the charger has raised the battery voltage high enough to clear the Low Voltage alarm. When the Equalize timer expires, the charger will immediately return to Float mode. 7

8 4.0 Display Calibration In order to calibrate the display voltage and current to match the measured values, two small potentiometers are provided, located on the 225C display driver board. P1 potentiometer is used to calibrate the display voltage and P2 potentiometer is used to calibrate the display current. An LCD display contrast potentiometer (P3) is also provided for contrast adjustment. Please refer to Figure 5. NOTE: Adjusting the potentiometers mentioned will NOT change the output of the charger; only the display values will be changed. P3 LCD Contrast Calibration P1 (VCAL) Display Voltage Calibration P2 (ICAL) Display Current Calibration Figure 5 Display Calibration 8

9 Document Control and Revision History Part Number: Instruction Number: P25-LOPT46SERIES-1 Issue ECN: / / / / /05 9

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 16 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

A77 Series. Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger. Installation and Operation Manual

A77 Series. Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com A77 Series Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger Installation and Operation Manual This manual is subject to change

More information

TPSD. Installation and Operation Manual. Filtered Battery Charger Power Supply / Battery Eliminator

TPSD. Installation and Operation Manual. Filtered Battery Charger Power Supply / Battery Eliminator La Marche Manufacturing Company www.lamarchemfg.com TPSD Filtered Battery Charger Power Supply / Battery Eliminator Installation and Operation Manual 106 Bradrock Dr. Des Plaines 60018-1967 Tel: 847 299

More information

La Marche Manufacturing Company A36D. Battery Charger / Power Supply. Installation and Operation Manual

La Marche Manufacturing Company   A36D. Battery Charger / Power Supply. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com A36D Battery Charger / Power Supply Installation and Operation Manual 106 Bradrock Dr. Des Plaines, IL 60018-1967 Tel: 847 299 1188 Fax: 847 299 3061

More information

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A36D & TPSD Chargers with S2A-341S and S2A-383S communication cards. Option 21P,

More information

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS SCADA INTERFACE INSTRUCTIONS - OPTION 21S - FOR A36D/TPSD SYSTEMS with option 500 and 550. A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE OPTION 21S INSTRUCTIONS This manual is valid for A36D/TPSD Chargers

More information

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS with 500 and 550 option. A36D/TPSD Modbus TCP SCADA INTERFACE OPTION 21Q INSTRUCTIONS This manual is valid for A36D/TPSD Chargers equipped

More information

A77 SNMPv1 SCADA INTERFACE INSTRUCTIONS

A77 SNMPv1 SCADA INTERFACE INSTRUCTIONS A77 SNMPv1 SCADA INTERFACE OPTION 21X INSTRUCTIONS This manual is only valid for A77 Chargers equipped with the following: S2A-368S card with software version P368S0111 080116 MIB file P389S-21X4-00 S2A-389S

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

A77 SNMPv3 SCADA INTERFACE INSTRUCTIONS

A77 SNMPv3 SCADA INTERFACE INSTRUCTIONS A77 SNMPv3 SCADA INTERFACE OPTION 21X INSTRUCTIONS This manual is only valid for A77 Chargers equipped with the following: S2A-368S card with software version P368S0112 MIB file P389S-21X4-01-P368S0112

More information

VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL

VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL Copyrights 2007 Victron Energy B.V. All Rights Reserved This publication or parts thereof, may not be reproduced in any form, by any method, for any purpose.

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Installation and Operation Manual

Installation and Operation Manual SENTRY Protect Plus QUADPLEX PANEL Installation and Operation Manual For Hardwired Pumps Environment e Corporation Table of Contents 1 Overview...3 2 Sentry Protect Plus Quadplex Menu Flowchart...4 3 Wiring

More information

Introduction. OM-THA2

Introduction. OM-THA2 Introduction. The OM-THA2 is a multi-function product that monitors Temperature, Humidity and Dew Point, provides alarms for out of range conditions, and continuously logs data. It consists of a base unit

More information

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY Introduction.

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd. F-2000 PC and AO OUTPUT BOARDS INSTRUCTION MANUAL Blue-White R Industries, Ltd. 500 Business Drive Huntington Beach, CA 92649 USA Phone: 714-89-8529 FAX: 714-894-9492 E mail: sales@blue-white.com or techsupport@blue-white.com

More information

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47) DIESEL ENGINE CONTROL UNIT DCU 205 - USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) 64 84 52 00 Fax: (+47) 64 84 52 12 office@auto-maskin.no - 1 - TABLE OF CONTENTS 1. INTRODUCTION TO THE DCU 205...4

More information

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000 SERVICE INSTRUCTIONS FOR Fire Alarm System MINI-2000 Version 1.3 02.04.1998 Jari Ollila Tom Brunberg Oy Esmi Ab Copyright Oy ESMI Ab, 1991... 1998 The copyright to the documentation herein is the property

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual Toxic and Explosive Smart Gas Monitor PN 151022/151023 Installation and User Manual Quest Controls, Inc. 208 9 th Street Dr. West Palmetto, FL 34221 www.questcontrols.com Phone: (941) 729-4799 Fax: (941)

More information

MPT Electric Fire Pump Controller

MPT Electric Fire Pump Controller MPT Electric Fire Pump Controller Alarm Messages and Guide This manual provides alarm descriptions, troubleshooting steps, and alarm set point configuration information for Metron MPT Fire Pump Controllers

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH CONTROL PANEL INTERFACE USING THE AUTO/OFF/MANUAL SWITCH With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting occurs when utility power source

More information

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS.  A4741 / Rev.1 DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS User Manual and Menu Map A4741 / Rev.1 www.entes.com.tr ATTENTION -Disconnect all power before connecting the device. -Don t remove

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-46 8/05 INSTALLATION INSTRUCTIONS Original Issue Date: 8/05 Model: Automatic Transfer Switches equipped with MPAC 500 Controls Market: ATS Subject: External Alarm Module (EAM) Kit GM38795-KP Introduction

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-1343 5/06b INSTALLATION INSTRUCTIONS Original Issue Date: 8/03 Model: Automatic Transfer Switches Equipped with Series 1000 Programmable Controller Market: ATS Subject: Remote Annunciator Kits GM28938-KP1,

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

NO ONE DARES COME CLOSE O WNER S GUIDE 7756V

NO ONE DARES COME CLOSE O WNER S GUIDE 7756V NO ONE DARES COME CLOSE O WNER S GUIDE M O D E L 7756V Congratulations Congratulations on the purchase of your state-of-the-art Directed Digital System. Reading this Owner s Guide prior to using your

More information

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL MYRIAD TPC VISIT OUR WEBSITE SIGMACONTROLS.COM MYRIADI&O062705 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 7,8

More information

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08 GasScanner 8C Eight Channel Monitor Operator s Manual MINT-0281-XX Rev. A 01/29/08 Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials,

More information

Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

ARR-M Series Product Manual

ARR-M Series Product Manual ARR-M Series Product Manual PM990.7800.00, Issue 3 Issue PCO# By/Date 3 44465 WD/6-29-17 UNIPOWER, LLC 3900 Coral Ridge Drive Coral Springs, FL 33065 Phone: +1-954-346-2442 Toll Free: 1-800-440-3504 Web

More information

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to

More information

MANUAL FOR MODEL FD4 FIRE PUMP CONTROLLERS

MANUAL FOR MODEL FD4 FIRE PUMP CONTROLLERS MANUAL FOR MODEL FD4 FIRE PUMP CONTROLLERS Firmware version 5.02 This manual provides General Information, Installation, Operation, Maintenance and System Set-Up Information for METRON Model FD-4 Engine

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

Refrigerated air dryers

Refrigerated air dryers Refrigerated air dryers OPERATING AND MAINTENANCE MANUAL Original instructions 38178800319 OPERATING AND MAINTENANCE MANUAL - Contents 1 CONTENTS CONTENTS... 1 Chapter 1 IDRY ELECTRONIC CONTROLLER...

More information

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B PRODUCT BULLETIN SB 8001B Type 8001 ALARM ANNUNCIATOR TYPE8001 FEATURES 16 or 32 alarm points per flush mount enclosure Displays are backlit with long life LEDs and engraved to suit Dimmer controls built

More information

MF-PFA ver 3.x. Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction. Installation- & Operation manual [Dok. id: mi-303gb_180528]

MF-PFA ver 3.x. Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction. Installation- & Operation manual [Dok. id: mi-303gb_180528] Installation- & Operation manual [Dok. id: mi-303gb_180528] Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction and control output MF-PFA ver 3.x NOTE! Read through the entire manual

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features 1-1 Product Description The FD100 Diesel Engine Controller is designed to control and monitor 12 or 24 volt, diesel fire pump engines. All models are listed by UL and ULC, and approved by Factory Mutual

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A GasScanner 1C Single Channel Monitor Operator s Manual MINT-0278-XX Rev A Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training PowerWizard Level 1.0 & Level 2.0 Control Systems Training New Systems Current Systems Systems Comparison Level 1 Level 2 Level 3 Level 4 PowerWizard Level 3.0 PowerWizard Level 4.0 Overview Common parts

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions Bulletin E-97DC Thank you for purchasing the Dwyer DCT1000DC Dust Collector Timer Controller. You

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

CN7232 Advanced Garage Ventilation Controller

CN7232 Advanced Garage Ventilation Controller CN7232 Advanced Garage Ventilation Controller For Demand Controlled Ventilation Using: Carbon Monoxide (Gas Vehicles) Nitrogen Dioxide (Diesel) Combustible Gases (Alternative Fuels) Carbon Dioxide (Any

More information

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK Installation Manual AQM-20 12vdc/24vdc Series Power Supplies AQM20 Supervised Power Supply/Charger 12vdc 20Amp/24vdc 10Amp Life Time Warranty Quality Manufactured in the USA AQM20 Features: The AQM20 has

More information

DGC-1000 DIGITAL GENSET CONTROLLER

DGC-1000 DIGITAL GENSET CONTROLLER DGC-1000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-1000) offers a low cost microprocessor based integrated alternative for small to medium sized genset control and monitoring.

More information

ENGINE MONITOR VOTT MODEL: YEAR WARRANTY

ENGINE MONITOR VOTT MODEL: YEAR WARRANTY INSTRUCTION MANUAL ENGINE MONITOR VOTT MODEL: 023-4400-0 3 YEAR WARRANTY INTRODUCTION The VOTT meter is an ideal engine monitor, which displays data via the J1939 CAN Bus. The meter utilizes a large LCD

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,

More information

EXPERT TRI-STAR. Temperature controller. User s Manual

EXPERT TRI-STAR. Temperature controller. User s Manual Temperature controller r s Manual WARNINGS The warranty can be void if this product is used in a manner not specified by the manufacturer. Every effort has been made to ensure that this manual is complete,

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates

More information

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual INSTALLATION PDD-8PCI PDD-8PCI Power Distribution Board With Supervised Interface Installation and Specifications Manual Details The PDD-8PCI board is a power distribution/control interface. This board

More information

TV2 Room Pressure Monitor Quick Start Guide

TV2 Room Pressure Monitor Quick Start Guide TV2 Room Pressure Monitor Quick Start Guide 1. The Care and Use guide for your TV2 Room Pressure Monitor can be downloaded here: www.e2di.com/usersguides.html Please print out the Users Guide. Although

More information

CommStat 4 Controller

CommStat 4 Controller CommStat 4 Controller CommStat 4 Telecom HVAC Controller The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners, heat pumps and air conditioners with

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

Dryer Master DM510 Commissioning Guide

Dryer Master DM510 Commissioning Guide COMMISSIONING GUIDE Dryer Master DM510 Dryer Moisture Systems Inc. 640 Superior Drive Waterloo, Ontario Phone 519.725.4700 Fax 519.885.4300 USA & Canada Toll Free 1-888-318-0009 E-mail: info@dryermaster.com

More information

Follett Performance Plus

Follett Performance Plus Follett Performance Plus touchscreen user guide The next level of control in undercounter refrigeration Controller Operation - Performance Plus touchscreen Use and care of the LCD Performance Plus touchscreen

More information

Flopurge TS. Operation Manual

Flopurge TS. Operation Manual Flopurge TS Operation Manual Part Number 079-0204 Spectron Gas Control Systems United Kingdom Unit 4, Herald Court, University of Warwick Science Park, Coventry, CV4 7EZ +44 (0)24 7641 6234 sales@spectron-gcs.com

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

Independent Zone Control (I.Z.C.)

Independent Zone Control (I.Z.C.) Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Multi-Gas-Controller MGC2

Multi-Gas-Controller MGC2 Page 1 Aug. 2018 Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology for continuous monitoring of the ambient air to detect toxic and combustible gases, refrigerants

More information

GLD-30 Gas Leak Detector

GLD-30 Gas Leak Detector GLD-30 Gas Leak Detector Installation, Operation & Maintenance General: The Archer Instruments GLD-30 is an ambient air monitor, used to detect the presence of a target gas (or gases) and to alert operators

More information

BSR Addressable Fire Detection control panel. Installation operation manual

BSR Addressable Fire Detection control panel. Installation operation manual BSR-1116 Addressable Fire Detection control panel Installation operation manual ATTENTION!!! READ THE MANUAL BEFORE THE INSTALLATION AND PAY ATTENTION TO PARAGRAPH 2.6.3 AND 2.6.4. Page 2 from 36 Contents

More information

Batt-Safe Battery String Monitoring System

Batt-Safe Battery String Monitoring System Batt-Safe Battery String Monitoring System Technical White Paper October 2010 Introduction Battery monitoring systems are categorized as either cell monitors or string monitors. Battery cell monitors provide

More information

Setup & Operation Index

Setup & Operation Index SENTRY PreSTAT SIMPLEX PANEL Installation and Operation Manual Environment One Corporation Setup & Operation Index Setup & Operation Index...2 Sentry PreSTAT Menu Flowchart...3 Overview...3 Wiring Instructions...5

More information

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08 GasScanner 4C Four Channel Monitor Operator s Manual MINT-0280-XX Rev. A 02/25/08 Product Warranty Matheson Tri-Gas., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger

More information

Beacon 110 Gas Monitor Operator s Manual

Beacon 110 Gas Monitor Operator s Manual Beacon 110 Gas Monitor Operator s Manual Part Number: 71-0110RK Revision: H Released: 12/5/17 RKI Instruments, Inc. www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment

More information

F4 Process Controller Installation and Operation Guide

F4 Process Controller Installation and Operation Guide F4 Process Controller Installation and Operation Guide 1.Introduction 1.1.Highlight Features Space saving, only 55mm panel depth required Higher sampling rate (1mS) results in better control performance

More information

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input April 2006 SCR-SCRF Utility & General Industry Switchgear Alarm Systems Engine Starting Railroad Emergency

More information

Ammonia Leak Detector Manual

Ammonia Leak Detector Manual Ammonia Leak Detector Manual Document No. 70-PHW-1023-R2.5 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical,

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming

More information