PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM

Size: px
Start display at page:

Download "PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM"

Transcription

1 PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0)

2 Document Revision Details Issue Modification Detail Author Date 01 Document Creation RB 15/11/2015 N Issue 1 Page 2 of 10 Protec Fire Detection PLC 2015

3 Table of Contents 1.0 SCOPE OF DOCUMENT USER RESPONSIBILITIES INTRODUCTION PROPOINTPLUS GENERAL OVERVIEW DISPLAY FAULT PRE-ALARM FIRE FAULTS TECHNICAL SPECIFICATIONS There are no user serviceable parts inside the ProPointPlus. A competent person trained to undertake such work MUST carry out any internal maintenance work. A separate installation and commissioning manual is available. applicable This equipment has been manufactured in conformance with the requirements of all EU council directives and regulations. Electrical or electronic devices that are no longer serviceable must be collected separately and sent for environmentally compatible recycling (in accordance with the European Waste Electrical and Electronic Equipment Directive). To dispose of old electrical or electronic devices, you should use the return and collection systems put in place in the country concerned. The policy of Protec Fire Detection plc is one of continuous improvement. As such we reserve the right to make changes to product specifications at any time and without prior notice. Errors and omissions excepted. N Issue 1 Page 3 of 10 Protec Fire Detection PLC 2015

4 1.0 Scope of document This document details the user information for the Protec ProPointPlus Aspirating Smoke Detector with specific attention to the basic system operations of the product. The Protec ProPointPlus Aspirating Smoke Detector has been designed and manufactured in the United Kingdom and complies fully with current standard dictating aspirating smoke detector design practice (EN54 parts 20). 2.0 User Responsibilities The registered owner of the fire alarm system has specific responsibilities regarding the installation, testing and maintenance of the fire alarm system. BS5839 Pt 1: 2013 Section 7 states that the user of the fire alarm system must appoint a single named person to supervise all matters regarding the fire alarm system. Summarised below are the responsibilities expected of the named person, It is strongly advised that a full copy of BS5839 Pt 1: 2013 is obtained and thoroughly read and understood. 3.0 Introduction Aspirating detection is now a recognised solution for many different fire detection applications. ProPointPlus provides up to four separate detectors within a common aspirator enclosure and therefore provides four individually identifiable areas of detection per aspirator. Each of the four plug in Scatter Camber Detectors (SCD s) detector use independent and integrated alarm decision making. Complex algorithms are used to extend the range of particle detection, confirm genuine alarms and reduce unwanted alarms. Installation, configuration and commissioning of the ProPointPlus detectors is very simple and installer friendly. Configuration to either Class A, Class B or Class C sensitivity options is achieved through a multifunction OLED display without the need for a PC connection. The features of the ProPointPlus are: High performance optical detection with optional enhanced CO detection. 1 to 4 individual detectors. Protec 6000 series digital addressable protocol. Simple sensitivity configuration setup: Class A, Class B, Class C and Prison. 3 Programmable input contacts. Airflow monitoring per pipe. Variable blower speed control. Integral OLED display for fault reporting and ease of setup. Commissioning menu access code protected. On-board loop isolator. Support multiple language menu functions. Common Fault output contact. TCP/IP Network configurable. 5 Programmable output contacts. N Issue 1 Page 4 of 10 Protec Fire Detection PLC 2015

5 4.0 ProPointPlus General Overview The ProPointPlus detector is capable of displaying all faults and fire events on the OLED screen. The detector is fitted with an internal buzzer. The buzzer will sound distinctive pulse tones when the unit is in Fault, Pre-alarm or Fire (providing the buzzer is enabled at commissioning). The buzzer can be muted by pressing any button. LED indicators are programmed to illuminate corresponding to a specific event. The button functions are to navigate thought the commissioning menu and are therefore not a requirement for the user. 4.1 Display Power LED (Green) OLED Display Fault LED (Amber) Fire LED (Red) Pre Alarm LED (Amber) Escape / Back Decrement Increment Enter / Accept Figure 4.1 ProPointPlus display detector normal N Issue 1 Page 5 of 10 Protec Fire Detection PLC 2015

6 4.2 Fault The ProPointPlus displays all faults on the OLED display. Providing no pre-alarms or fires are active the text Fault or Faults will be displayed; including the number of faults indicated in front of the text. A brief description of the device fault is displayed in the centre of the display. When more than one faults is reported; the faults are automatically scrolled though each fault on the display. The fault LED will be illuminated. If the fault is pipe specific; the pipe number is displayed in brackets next to the fault for example below shows (1) Airflow Fault describes an airflow fault on pipe 1. Figure 4.2 ProPointPlus displaying a fault condition Refer to section 4.1 which lists all fault including a description and action. Muting the buzzer The buzzer can be muted by pressing any button. N Issue 1 Page 6 of 10 Protec Fire Detection PLC 2015

7 4.3 Pre-alarm The Pre-alarm condition takes priority over faults. When a pre-alarm condition is activated the display shows all pipes commissioned (1, 2, 3 or 4). The Pre-alarm text is represented as Warning. The figure 3.2 below shows 4 pipes; where Pipe 1 and Pipe 2 are in Pre-Alarm condition: Warning, Pipe 3 and Pipe 4 are in Normal condition. The Pre-Alarm LED is illuminated, any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel. Figure 4.3 ProPointPlus displaying Pre-Alarm condition The appointed Responsible Person should investigate the relevant area following the official procedures for the building. Extreme care must be exercised at all times. Muting the buzzer The buzzer can be muted by pressing any button. N Issue 1 Page 7 of 10 Protec Fire Detection PLC 2015

8 4.4 Fire The Fire condition is prioritised over Pre-Alarm and faults. When a fire condition is activated the display shows all pipes commissioned (1, 2, 3 or 4). The fire text is represented as Fire. The example picture below shows 4 pipes; where Pipe 2 are in Fire condition, Pipe 1, Pipe 3 and Pipe 4 are in Normal condition. The Fire LED is illuminated, any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel. Figure 4.4 ProPointPlus displaying Fire Alarm condition The building fire plan must be executed immediately. Muting the buzzer The buzzer can be muted by pressing any button. N Issue 1 Page 8 of 10 Protec Fire Detection PLC 2015

9 5.0 Faults The ProPointPlus monitors various aspects of the unit to ensure the unit is fully operational. During faults the fault LED will illuminate and the buzzer will sound a slow pulse tone. Listed below are the diagnosed faults indicated on the unit. Table 1 System Faults Fault Description Action Device Missing Device Added Airflow Fault Supply Fault High Optical Background Low Background Link Fault Output Override Corrupt Settings Low Supply Corrupt File Calibration Fault LED Fault Airflow Ignored CO Cell Fault Fan Fault Isolated Fault Heat Fault Incomplete Manufacture Fault (85) A communication problem to a device within the unit has been detected or a device has been removed from the unit. A new device has been added to the unit but the device has not been commissioned. The airflow measurement has moved outside the acceptable tolerance range either by an increase or decrease in normalised airflow. The supply fault monitoring input is reading low. Typically connected to the external power supply charger unit. The optical value has increased outside the normal operation range. The optical value has decreased outside the normal operation range. The data (RS485) path has failed. The inputs check to test option is active, activated using the ProView.exe PC software. Internal settings are outside the expected values. Unit will default to factory settings. The supply voltage to the unit is below the operating value (<19V DC ). Web server file is corrupt. The SCD calibration offset value is out of limits. The SCD optical LED is damaged. A pipe airflow is set to be ignored, activated using the ProView.exe PC software. The SCD Carbon Monoxide (CO) cell has expired its life capacity or is missing. The fan is damage or under/over performing. Either the SCD(s) have been individually disabled or the isolate input is active. The heat thermistor reading is out of range. The manufacturing details have not been stored in the unit. An incorrect SCD device fitted in the unit. Check the device in fault is fitted correctly otherwise contact a Protec operative or a Protec distributor. Check sampling pipe installation is correct as per commissioning, ensure no pipes are blocked. If fault persists contact a Protec operative or a It may be necessary to look at the power supply charger unit to determine the cause of the fault. If fault persists contact a Protec operative or a If used check external input isolation equipment. Otherwise contact a Protec operative or a N Issue 1 Page 9 of 10 Protec Fire Detection PLC 2015

10 6.0 Technical Specifications Table 2 Technical Specifications Parameter Operating Conditions / Limitations Power Supply 21V DC to 28V DC, Minimum 2A DC : Approved to EN54 Part 4 Power Supply Fuse 1.6A Voltage Operating Range 21V DC to 28 V DC Maximum Current Consumption 600mA DC maximum at 24V DC (blower set to 100%, 4 Pipe Detector) Loop Protocol Protec Algo-tec 6000 Loop Isolator On board consult Protec DEL2110 for details Loop Quiescent Current Consumption 0.7mA Fault Contact Rated at 30 V DC DC 1 A DC maximum [Normally open] 3 Programmable monitored inputs 30 V DC [Active Low] Input Contacts [1 to 3] Max applied voltage 30 V DC, Open Circuit Voltage ~16 V DC Closed Circuit Resistance 1k5Ω Output Contacts [1 to 5] 5 Programmable Clean Contact Outputs Rated at 30 V DC, 1 A DC max [Normally open] Power Supply Input Monitor Normal 24V DC Input, Fault 2.5V DC Temperature Range 0 C to 45 C ambient Humidity Limit 0-95% non-condensing ambient Power [Green LED] Fault [Amber LED] Indicators Pre-Alarm [Amber LED] Alarm/Fire [Red LED] OLED Display Unit status (Faults, Pre-Alarm and Fire), and Commissioning menu Holes per Pre-Alarm pipe Level 1* Fire Level 1* (max) Sensitivity A = High B = Enhanced C = Normal Number = sampling hole alternative to point type smoke detector A1, A2, A %/m %/m B1, B2, B3, B4, B %/m %/m C1, C2, C3, C4, C5, C6, C7, C %/m %/m Prison 1 Max area coverage per pipe 800m 2 (C8 setting to British Standards or see local design -codes) CO area coverage 100m 2 (Settings A1, B1, C1 and Prison sensitivity only) Sensitivity Range 0.12%/m to 11%/m Sound Pressure Levels 70dB [peak] (Blower at 100%) Airflow Monitoring High and Low airflow monitoring Airflow Monitoring Range ± 5% to 50% respectively. For EN54 Part 20 compliance, Unit tolerance set to 20% set by the PC commission tool. Airflow Velocity Range 0.5 m/s to 6 m/s Event Log 256 events stored on FIFO basis Environmental History Typically 1 Month depending on activity IP Rating IP30 Cable Access 10x 20mm replaceable knockouts Cable Termination Screw terminal blocks ( mm 2, 30-12AWG) Connectivity TCP/IP Networking Protocol RJ45 Socket connection USB type B Socket connection Pipe OD 25mm Pipe Length Maximum 200m (To be confirmed by sampling pipe calculation program) N Issue 1 Page 10 of 10 Protec Fire Detection PLC 2015

PROPOINTPLUS ASPIRATING SMOKE DETECTION SYSTEM

PROPOINTPLUS ASPIRATING SMOKE DETECTION SYSTEM PROPOINTPLUS ASPIRATING SMOKE DETECTION SYSTEM INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL 3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk

More information

General Alarm System. User Manual. Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND

General Alarm System. User Manual. Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND General Alarm System User Manual Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk sales@protec.co.uk Document Revision Details

More information

CIRRUS PRO. User Manual and Responsibilities ASPIRATING FIRE DETECTOR

CIRRUS PRO. User Manual and Responsibilities ASPIRATING FIRE DETECTOR CIRRUS PRO ASPIRATING FIRE DETECTOR User Manual and Responsibilities Protec Fire Detection (Export) Ltd, Protec House, Churchill Way, Nelson, Lancashire. BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Protec Protec Algo-TecTM 6100 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL

More information

HERCULES 6 GRAPHICS SYSTEM

HERCULES 6 GRAPHICS SYSTEM HERCULES 6 GRAPHICS SYSTEM USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web: www.protec.co.uk

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Fire Detection - Addressable Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Fire Detection - Addressable Protec Protec Algo-TecTM

More information

PROTEC CIRRUS HYBRID ASPIRATING SMOKE DETECTION SYSTEMS

PROTEC CIRRUS HYBRID ASPIRATING SMOKE DETECTION SYSTEMS PROTEC CIRRUS HYBRID ASPIRATING SMOKE DETECTION SYSTEMS INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6500/6600 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) COMMISSIONING MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Fire Detection Pty Ltd Fire Detection - Addressable Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Fire Detection

More information

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0)

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Aspirating Detection System. Protec Aspirating Detection System Atria Design Guide. MED2199 Atria Design Guide Issue 0 Page 1 of 22

Aspirating Detection System. Protec Aspirating Detection System Atria Design Guide. MED2199 Atria Design Guide Issue 0 Page 1 of 22 Aspirating Detection System Protec Aspirating Detection System Atria Design Guide MED2199 Atria Design Guide Issue 0 Page 1 of 22 Document Revision Details Issue Modification Detail Author(s) Approved

More information

Aspirating Detection System. Protec Aspirating Detection System Lift Shaft Design Guide. MED2198 Lift Shaft Design Guide Issue 0 Page 1 of 23

Aspirating Detection System. Protec Aspirating Detection System Lift Shaft Design Guide. MED2198 Lift Shaft Design Guide Issue 0 Page 1 of 23 Aspirating Detection System Protec Aspirating Detection System Lift Shaft Design Guide MED2198 Lift Shaft Design Guide Issue 0 Page 1 of 23 Document Revision Details Issue Modification Detail Author(s)

More information

Protec. Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network

Protec. Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network Protec Protec Fire Detection plc Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

Fire Detection - Addressable

Fire Detection - Addressable Technical Specification 6400 Series Common Specifications Temperature Range 0-40 C. Maximum Humidity 85% Non-Condensing. Working Voltage 21.5-30V dc. Secure Network Dual channel RS485 fault tolerant communications

More information

The EN54 Part 2, 4 and 13 Fire System

The EN54 Part 2, 4 and 13 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

FIRE ALARM CONTROL PANEL FVC01-08

FIRE ALARM CONTROL PANEL FVC01-08 FIRE ALARM CONTROL PANEL FVC01-08 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Radal Technology Limited Unit 1, Webber Court Billington Road, Burnley Lancashire, BB11 5UB Tel: +44 (0) 1282 463 770 Fax: +44

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

LaserFOCUS VLF-250 Engineering Specification

LaserFOCUS VLF-250 Engineering Specification Vision Fire & Security LaserFOCUS VLF-250 Engineering Specification May 2004 Part Number 20296 LaserFOCUS VESDA 2 VESDA LaserFOCUS Contents Scope...4 Description...4 General...4 Approvals...4 Codes, Standards

More information

The Protec driver connects to the Protec Fire Detection range of digital addressable fire control panels. Available for Commander and ObSys.

The Protec driver connects to the Protec Fire Detection range of digital addressable fire control panels. Available for Commander and ObSys. The Protec Driver The Protec driver connects to the Protec Fire Detection range of digital addressable fire control panels. Available for Commander and ObSys. This document relates to Protec driver version

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

Protec. Protec Algo-Tec TM 6400 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6400 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Algo-Tec TM 6400 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE CAUTION Protec Protec Algo-Tec 6400 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections. ISSUES ISSUE DATE RELEASED DETAILS OF CHANGE AUTHOR 4 Rev 2 September 2004 Changes for 4000 series. DB 4 Rev 3 April 2005 Screen shots updated and other minor changes K.Z. 4 Rev 4 September 2006 4 Rev

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

PROFYRE C8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

PROFYRE C8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Approved Document No: EF-PFC8UM-1 Contents 1. FIRE ALARM CONTROL PANEL SAFETY ISSUES... 2 2. THE PURPOSE OF A FIRE ALARM SYSTEM... 2 3.

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI E N G L I S H FIRE ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL0EI, MI-FL0EI AND MI-FL0EI mm mm 0 mm DESCRIPTION The LT MI-FL0 Series is part of the Fire Alarm

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Firmware Versions: PANEL 1.84 & LOOP CARD 3.70 MKII PROTOCOL ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT-215-7-2 TABLE OF CONTENTS WHAT

More information

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax: Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: 01730 268 231. Fax: 01730 265 552 Scimitar user manual & log book SCIMITAR USER MANUAL Approved Document No. DFU7001001 Rev 2

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm. E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0E FL0E FL0E mm mm 0 mm DESCRIPTION The LT FL0 Series is part of the Fire Alarm Aspiration

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Page 1 TABLE OF CONTENTS WHAT TO DO IF THE FIRE ALARM PANEL SHOWS AN ALARM (RED LED)... 4 WHAT TO DO IF

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK. CONTENTS 1. FIRE ALARM CONTROL PANEL SAFETY

More information

Protec. Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network. Fire Detection - Addressable Protec Protec Fire Detection Pty Ltd Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE CAUTION

More information

Door Release Power Supply

Door Release Power Supply www.protectingpeople.co.uk Door Release Power Supply Engineer / Installation Manual Document: VI55.1 Protecting People Printed : 04/03/2004-1 - Ventcroft Ltd Door Release Power Supply Engineer / Installation

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

Apollo Intelligent Auto Aligning Beam Detector. User Guide

Apollo Intelligent Auto Aligning Beam Detector. User Guide Apollo Intelligent Auto Aligning Beam Detector User Guide EN 1. General Information 50cm 50cm 8-100m Ensure clear line of sight from Detector to Reflector Mount on solid surfaces (structural wall or girder)

More information

Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input

Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input User Manual 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

ZERIO PLUS EDA-Z5008, Z5020 & Z5100 ZERIO PLUS EDA-Z5008, Z5020 & Z5100 USER MANUAL Revision 1.00 EDA-Z5008, Z5020 & Z5100 User Manual 0359 Electro Detectors Limited Electro House Edinburgh Way Harlow, Essex CM20 2EG, UK 14 0359 CPR 00226

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK ONE OR TWO LOOP ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Approved Document No: GLT.MAN-108 TABLE OF CONTENTS WHAT TO DO IF THE FIRE ALARM PANEL SHOWS AN ALARM

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation Sinteso Cerberus PRO FDA241, FDA221 ASD Aspirating smoke detector Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation Patented technology Early

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs User Manual Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs Models 89800-03 and 89800-04 THE STANDARD IN PRECISION MEASUREMENT Table of Contents

More information

FDA241, FDA221 Siemens ASD

FDA241, FDA221 Siemens ASD FDA241, FDA221 Siemens ASD Patented Technology Sinteso TM Cerberus PRO Compatible with the Siemens FDnet/C-NET loops (requires FDCC221S option) Advanced dual Wavelength optical detection (Blue & Infra-red)

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

Installation Instructions. Fire Command Center/Fire Alarm Annunciators D1256/D1257

Installation Instructions. Fire Command Center/Fire Alarm Annunciators D1256/D1257 Instructions Fire Command Center/Fire Alarm Annunciators D1256/D1257 74-06925-000-H Page 2 2004 Bosch Security Systems Contents 1.0 Introduction...5 1.1 Before You Begin...5 1.2 Type Styles Used Here...5

More information

M1000 Alarm Annunciator

M1000 Alarm Annunciator Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3

More information

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date: Gas Safety Products Merlin 1000S+i Gas & Electric Utility Controller Installation, operating and maintenance Rev: 03 Date: 14-08-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1

More information

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...

More information

Sintrol Snifter A2 EX. Manual. Version 1.2.3

Sintrol Snifter A2 EX. Manual. Version 1.2.3 Sintrol Snifter A2 EX Manual Version 1.2.3 Table of Contents 1 INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 How does it work?... 4 2 INSTALLATION... 4 2.1 Selecting the installation

More information

Different types of Fire Alarm System

Different types of Fire Alarm System Different types of Fire Alarm System Conventional Fire System Generally comes with Zones. Each zone can have max 20 detectors. Addressable Fire Alarm System This comes in loops. Different manufacturer

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

Installation and Operation Manual

Installation and Operation Manual [Please read this installation & operation manual before install and use this Installation and Operation Manual Address: 8-701,Dongfangming Industry Zone, Dabao Road., Baoan, Shenzhen, China-518101 Page

More information

FAAST. Fire Alarm Aspirating Sensing Technology

FAAST. Fire Alarm Aspirating Sensing Technology FAAST Fire Alarm Aspirating Sensing Technology The FAAST range FAAST 8100e FAAST LT PipeIQ Next Generation Aspiration Detection Detection for Challenging Environments 3 in 1 Design, Confi guration and

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

Intellia Sounder Bases and Sounder Beacon Bases

Intellia Sounder Bases and Sounder Beacon Bases Intellia Bases and Beacon Bases The Base and Beacon Base are a local-area alarm devices designed for indoor use. They can be connected only to detection systems using Intellia detectors and FX control

More information

MINERVA MZX125 Digital Addressable Fire Detection System

MINERVA MZX125 Digital Addressable Fire Detection System DATASHEET MINERVA MZX125 Digital Addressable Fire Detection System The Minerva MZX125 is a highly featured digital addressable panel with a comprehensive but easy to operate user interface. The system

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

FDA241, FDA221 Siemens ASD

FDA241, FDA221 Siemens ASD FDA241, FDA221 Siemens ASD Patented Technology Compatible with the Siemens FDnet/C-NET loops (requires FDCC221S option) Advanced dual Wavelength optical detection (Blue & Infra-red) Configurable as a Standalone

More information

USER MANUAL CEF AP28 CONTROL PANEL

USER MANUAL CEF AP28 CONTROL PANEL USER MANUAL CEF AP28 CONTROL PANEL AP28 WARNINGS This product has mains voltage present within the housing. Please take the necessary precautions in not allowing any liquid to spill on or into the housing.

More information

The Kentec driver connects to the Kentec Syncro range of fire detection panels. Available for Commander and ObSys.

The Kentec driver connects to the Kentec Syncro range of fire detection panels. Available for Commander and ObSys. The Kentec Driver The Kentec driver connects to the Kentec Syncro range of fire detection panels. Available for Commander and ObSys. This document relates to Kentec driver version 1.1 to 1.3 Please read

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

Solution F2. Fire Alarm Control Panels one step ahead.

Solution F2. Fire Alarm Control Panels one step ahead. Solution F2 Fire Alarm Control Panels one step ahead. Sicherheitstechnik Sicherheitstechnik GmbH GmbH The Fire Alarm Control Panel Solution F2 Solution F2 in B2 enclosure (B01090-00) The Concept The Solution

More information

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction... 4 2. Product Features... 4 3. Package

More information

MINERVA MZX125. Digital Addressable Fire Detection System

MINERVA MZX125. Digital Addressable Fire Detection System A C C E S S C O N T R O L C C T V E A S R F I D F I R E P R O T E C T I O N I N T R U D E R A L A R M S DATA SHEET MINERVA MZX125 Digital Addressable Fire Detection System Features: Long term service and

More information

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1 ViewMatrix Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels Version: 2.0 Revision: 0.1 CONTENTS 1. Introduction...3 2. Keyboard...5 2.1 POWER indication - Normal Operation...5

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

ZSC100 Gas Detection and Alarm System Controller

ZSC100 Gas Detection and Alarm System Controller ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2

More information

THX-DL Data Logger USER & INSTALLATION MANUAL V

THX-DL Data Logger USER & INSTALLATION MANUAL V THX-DL Data Logger USER & INSTALLATION MANUAL V1.2012 www.thermomax-refrigeration.com Contents PRESENTATION Summary of Features 2 INSTALLATION Safety Precautions 4 THX Unit 4 Sensors 4 Alarm Relay 4 Power

More information

Motorised Infrared Optical Beam Smoke Detector. User Guide

Motorised Infrared Optical Beam Smoke Detector. User Guide Motorised Infrared Optical Beam Smoke Detector User Guide EN 1. General Information 50cm 50cm 8-100m Ensure clear line of sight from Detector to Reflector Mount on solid surfaces (structural wall or girder)

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

HART XL High Sensitivity Smoke Detection

HART XL High Sensitivity Smoke Detection High Sensitivity Smoke Detection The Hart XL High Sensitivity Smoke Detection system (HSSD) is an aspirating fire detection system designed to give very early indication of an incipient fire condition.

More information

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head 4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head NET DRAFT version 2.1-2008 Pag. 1 4-20mA Cyber - DRAFT version 2.1-2008 Pag.

More information

FAAST 7100X INSTALLATION AND MAINTENANCE INSTRUCTIONS. Document Colour Code Key: (refer to Page 28) SPECIFICATIONS: TABLE OF CONTENTS

FAAST 7100X INSTALLATION AND MAINTENANCE INSTRUCTIONS. Document Colour Code Key: (refer to Page 28) SPECIFICATIONS: TABLE OF CONTENTS TABLE OF CONTENTS A. Specifications: 1 Introduction:.... 2 Description:... 2 Installation:...... 2 Wiring........... 3 User Interface:....... 5 Modes of Operation:..... 9 Logs..........11 External Monitor

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-7:2000+A1:2002+A2:2006 EN54-25:2008 0359 Electro Detectors Ltd. Electro

More information

Aspirated Smoke Detectors

Aspirated Smoke Detectors Safety Security Certainty LaserSense Aspirated Smoke Detectors We listened to you Aspirated air sampling technology Aspirated smoke detection is a method of smoke detection where the air from the protected

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

IntesisBox BACnet/IP Server - Notifier ID3000 series

IntesisBox BACnet/IP Server - Notifier ID3000 series IntesisBox Server - Notifier ID3000 series Gateway for integration of Notifier ID3000, ID3002, ID50 and ID60 fire panels into enabled control systems. Integrate your Notifier fire panels into your BACnet

More information

FAAST XT 9400XA Fire Alarm Aspiration Sensing Technology

FAAST XT 9400XA Fire Alarm Aspiration Sensing Technology COMPREHENSIVE USER GUIDE FAAST XT 9400XA Fire Alarm Aspiration Sensing Technology SPECIFICATIONS Electrical Characteristics External Supply Voltage Remote Reset Time 18 30 VDC External monitor must be

More information