Rosemount 2088, 2090P, and 2090F Pressure Transmitters
|
|
- Ashlie Blair
- 5 years ago
- Views:
Transcription
1 April 2013 Rosemount 2088 and 2090 Rosemount 2088, 2090P, and 2090F Pressure Transmitters with 4-20 ma HART and 1-5 Vdc HART Low Power Protocol Start Step 1: Mount the Transmitter Step 2: Set the Jumpers Step 3: Connect the Wiring and Power Step 4: Verify Configuration Step 5: Trim the Transmitter Safety Instrumented Systems Product Certifications End
2 Rosemount 2088 and 2090 April Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Emerson Process Management Rosemount Division 8200 Market Boulevard Chanhassen, MN USA T (US) (800) T (Intnl) (952) F (952) Emerson Process Management Asia Pacific Private Limited 1 Pandan Crescent Singapore T (65) F (65) / Emerson Process Management GmbH & Co. OHG Argelsrieder Feld Wessling Germany T 49 (8153) 9390 F49 (8153) Beijing Rosemount Far East Instrument Co., Ltd No. 6 North Street, Hepingli, Dong Cheng District Beijing , China T (86) (10) F (86) (10) IMPORTANT NOTICE This installation guide provides basic guidelines for the Rosemount 2088 and 2090 transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 2088/2090 reference manual (document number ) for more instruction and low power output. This manual is also available electronically on WARNING Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the Rosemount 2088/2090 manual for any restrictions associated with a safe installation. Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices. In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit. Process leaks may cause harm or result in death Use appropriately rated sanitary clamps and gaskets during installation. The maximum working pressure of the clamp and gasket must be greater than or equal to the working pressure range of the transmitter. Electrical shock can result in death or serious injury Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. 2
3 April 2013 Rosemount 2088 and 2090 STEP 1: MOUNT THE TRANSMITTER Rosemount 2088 Mount directly to the impulse line without using an additional mounting bracket or mount directly to a wall, panel, or two-inch pipe using an optional mounting bracket. Rosemount 2090P Mount directly to the process pipe using an existing weld spud, or have a skilled welder install a new weld spud using a TIG welder. Refer to Reference Manual for complete welding instructions (document number ). Improper installation may result in weld spud distortion. Recommended mounting in upright or horizontal position to allow proper draining of vent. Rosemount 2090F Mount directly to the process pipe using a standard sanitary fitting (either a 1.5- or 2-inch Tri-Clamp connection). Recommended mounting in upright or horizontal position to allow proper draining of vent. Do not apply torque directly to the electronics housing. To avoid damage, apply torque only to the hex-shaped process connection P 2090F 1.5 in. 1.0 in. 1 /2 14 NPT Female Process Connection Vessel Wall Weld Spud Vessel Wall O-ring 1 1 /2 or 2-in. Tri-Clamp Connection Panel Mount Pipe Mount 3
4 Rosemount 2088 and 2090 April 2013 STEP 1 CONTINUED... Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. Gas Flow Applications 1. Place taps in the top or side of the line. 2. Mount level or above the taps. Steam Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Fill impulse lines with water. 4
5 April 2013 Rosemount 2088 and 2090 Gage Transmitter Orientation The low side pressure port (atmospheric reference) on the gage transmitters with aluminum housings are located in the neck of the transmitter, behind the housing. The vent path is 360 around the transmitter between the housing and sensor. (See Figure 1.) Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the process can drain away. Figure 1. Gage Low Side Pressure Port Low side pressure port (atmospheric reference) 5
6 Rosemount 2088 and 2090 April 2013 STEP 2: SET THE JUMPERS If alarm and security jumpers are not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off. 1. If the transmitter is installed, secure the loop, and remove power. 2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live. 3. Reposition the jumper. Avoid contact with the leads and the terminals. See Figure 2 for the location of the jumper and the ON and OFF positions. 4. Reattach the transmitter cover. The cover must be fully engaged to comply with explosion-proof requirements. Figure Transmitter Electronics Board Without LCD Alarm With LCD Display Alarm Security Security Low Power without LCD Low Power with LCD Display Alarm Security Alarm Security 6
7 April 2013 Rosemount 2088 and 2090 STEP 3: CONNECT THE WIRING AND POWER Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINALS. 2. Connect the positive lead to the PWR/COMM+ terminal, and the negative lead to the terminal. 3. Ensure proper grounding. It is important that the instrument cable shield: be trimmed close and insulated from touching the transmitter housing. be connected to the next shield if cable is routed through a junction box. be connected to a good earth at the power supply end. NOTE Installation of the transient protection terminal block does not provide transient protection unless the 2088 case is properly grounded. NOTE Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the test connection. Twisted pair cable yields best results. For high EMI/RFI environments, shielded twisted pair cable should be used. Use 24 AWG or larger wire and do not exceed 5,000 feet (1,500 meters). 4. Plug and seal unused conduit connections. 5. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing. 6. Replace the housing cover. Figure 3 and Figure 4 show wiring connections necessary to power a 2088 transmitter and enable communications with a hand-held Field Communicator. 7
8 Rosemount 2088 and 2090 April 2013 Figure 3. Bench Hook-up Wiring Diagrams (4 20 ma Transmitters) R L Vdc Supply Figure 4. Field Wiring for 2088 Low Power Option Code N Voltmeter Power Supply Current Meter Power Supply The dc power supply (Option S: Figure 5. Maximum Loop Resistance = 43.5 * (Power Supply V and Option N: 6 - Voltage 10.5) 14 V) should provide power with 1387 less than two percent ripple. The total resistance load is the sum of 1000 the resistance of the signal leads and the load resistance of the 500 Operating controller, indicator, and related Region pieces. The resistance of intrinsic 0 safety barriers, if used, must be included. Voltage (Vdc) 42.4 The Field Communicator requires a minimum loop resistance of 250 for communication. Load (Ohms) 8
9 April 2013 Rosemount 2088 and 2090 STEP 4: VERIFY CONFIGURATION A check ( ) indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure. Function HART Fast Key Sequence Analog Output Alarm 1, 4, 3, 2, 4 Burst Mode Control 1, 4, 3, 3, 3 Burst Option 1, 4, 3, 3, 4 Calibration 1, 2, 3 Damping 1, 3, 5 Date 1, 3, 4, 1 Descriptor 1, 3, 4, 2 Digital To Analog Trim (4 20 ma Output) 1, 2, 3, 2, 1 Disable Local Span/Zero Adjustment 1, 4, 4, 1, 7 Field Device Info 1, 4, 4, 1 Keypad Input 1, 2, 3, 1, 1 Loop Test 1, 2, 2 Lower Range Value 4, 1 Lower Sensor Trim 1, 2, 3, 3, 2 Message 1, 3, 4, 3 Meter Type 1, 3, 6, 1 Number of Requested Preambles 1, 4, 3, 3, 2 Output Trim 1, 2, 3, 2 Percent Range 1, 1, 2 Poll Address 1, 4, 3, 3, 1 Range Values 1, 3, 3 Rerange 1, 2, 3, 1 Scaled D/A Trim (4 20 ma Output) 1, 2, 3, 2, 2 Self Test (Transmitter) 1, 2, 1, 1 Sensor Info 1, 4, 4, 2 Sensor Trim (Full Trim) 1, 2, 3, 3 Sensor Trim Points 1, 2, 3, 3, 5 Status 1, 2, 1, 2 Tag 1, 3, 1 Transmitter Security (Write Protect) 1, 3, 4, 4 Units (Process Variable) 1, 3, 2 Upper Range Value 5, 2 Upper Sensor Trim 1, 2, 3, 3, 3 Zero Trim 1, 2, 3, 3, 1 9
10 Rosemount 2088 and 2090 April 2013 STEP 5: TRIM THE TRANSMITTER NOTE Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit). Zero Trim A zero trim is a single-point adjustment used for compensating mounting position effects. If zero offset is less than 3% of true zero, follow the Using the Field Communicator instructions below. If zero offset is greater than 3% of true zero, follow the Using the Transmitter Zero Adjustment Button instructions below to rerange. Using the Field Communicator Fast Keys Steps 1, 2, 3, 3, 1 1. Vent the transmitter and connect Field Communicator. 2. At the menu, input the HART Fast Key sequence. 3. Follow the commands to perform a zero trim. Using the Transmitter Zero Adjustment Button 1. Loosen the certifications label screw and rotate the label to expose the zero adjustment button. 2. Apply the desired pressure for the 4 ma output. 3. Set the 4 ma point by pressing the zero button for 2 seconds. Verify that the output is 4 ma. The optional LCD will display ZERO PASS. Zero Adjustment Button 10
11 April 2013 Rosemount 2088 and 2090 SAFETY INSTRUMENTED SYSTEMS The following section applies to 2088 transmitters used in SIS applications. NOTE Transmitter output is not safety-rated during the following: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during transmitter configuration and maintenance activities. Installation No special installation is required in addition to the standard installation practices outlined in this document. Always ensure a proper seal by installing the electronics housing cover(s) so that metal contacts metal. The loop must be designed so the terminal voltage does not drop below 10.5 Vdc when the transmitter output is 22.5 ma. Position the security switch to the ON position to prevent accidental or deliberate change of configuration data during normal operation. Configuration Use any HART-compliant master to communicate with and verify configuration of the User-selected damping will affect the transmitters ability to respond to changes in the applied process. The damping value + response time must not exceed the loop requirements. NOTE DCS or safety logic solver must be configured to match transmitter configuration. Figure 6 identifies the two alarm levels available and their operation values. Position the alarm switch to the required HI or LO alarm position. Figure 6. Alarm Levels Rosemount Alarm Level Normal Operation ma 20 ma (2) ma (1) 3.9 ma 20.8 ma low saturation high saturation Namur Alarm Level 3.6 ma (1) 3.8 ma low saturation Normal Operation (1) Transmitter Failure, hardware alarm in LO position. (2) Transmitter Failure, hardware alarm in HI position. 4 ma 20 ma 22.5 (2) 20.5 ma high saturation NOTE Some detected faults are indicated on the analog output at a level above high alarm regardless of the alarm switch selection. 11
12 Rosemount 2088 and 2090 April 2013 Operation and Maintenance Proof Test and Inspection The following proof tests are recommended. Proof test results and corrective actions taken must be documented at in the event that an error is found in the safety functionality. Use "Table 1: Input Parameters" to perform a Loop Test, Analog Output Trim, or Sensor Trim. See the 2088 reference manual ( ) for additional information. Proof Test This proof test will detect 92% of DU failures not detected by the 2088 automatic diagnostics. 1. Bypass the safety PLC and take appropriate action to avoid a false trip. 2. Send a HART command to the transmitter to go to the high alarm current output and verify that the analog current reaches that value (1). 3. Send a HART command to the transmitter to go to the low alarm current output and verify that the analog current reaches that value (2). 4. Perform a minimum two-point sensor calibration check using the 4-20 ma range points as the calibration points and verify that the ma output corresponds to the pressure input value (3). 5. Restore loop to full operation. 6. Remove the bypass and otherwise restore normal operation. Product Repair All failures detected by the transmitter diagnostics or by the proof-test must be reported. Feedback can be submitted electronically at The 2088 is repairable by major component replacement. Follow the instructions in the 2088 reference manual (document number ) for additional information. Reference Specifications The 2088 must be operated in accordance to the functional and performance specifications provided in the 2088 reference manual. Failure Rate Data The FMEDA report includes failure rates. This report is available at (1) This tests for compliance voltage problems such as a low loop power supply voltage or increased wiring resistance. This also tests for other possible failures. (2) This tests for possible quiescent current related failures. (3) If the two-point calibration is performed with electrical instrumentation, this proof test will not detect any failures of the sensor. 12
13 April 2013 Rosemount 2088 and Safety Failure Values Safety accuracy: 2.0% (1) Safety response time: 1.5 sec Product Life 50 years based on worst case component wear-out mechanisms not based on wear-out process wetted materials. (1) A 2% variation of the transmitter ma output is allowed before a safety trip. Trip values in the DCS or safety logic solver should be derated by 2%. 13
14 Rosemount 2088 and 2090 April 2013 PRODUCT CERTIFICATIONS Approved Manufacturing Locations Rosemount Inc. - Chanhassen, Minnesota, USA Emerson Process Management GmbH & Co. - Wessling, Germany Emerson Process Management Asia Pacific Private Limited - Singapore Beijing Rosemount Far East Instrument Co., Limited - Beijing, China European Directive Information The EC declaration of conformity can be found on page 14. The most recent revision can be found at ATEX Directive (94/9/EC) Emerson Process Management complies with the ATEX Directive. European Pressure Equipment Directive (PED) (97/23/EC) Model 2088/2090 Pressure Transmitters - Sound Engineering Practice Electro Magnetic Compatibility (EMC) (2004/108/EC) All Model 2088/2090 Pressure Transmitter: EN :2006 Hazardous Locations Certifications North American Certifications Factory Mutual (FM) E5 Explosion-proof and Dust Ignition Proof Certificate No.: 1V2A8.AE Applicable Standards: FM Class , FM Class , FM Class Markings: Explosion-proof for Class I, Division 1, Groups B, C, and D. Dust Ignition-Proof for Class II/III, Division 1, Groups E, F and G. Temperature Code: T5 (Ta = -40 C to + 85 C) Factory Sealed, Enclosure Type 4X. For input parameters see control drawing I5 Intrinsically Safe and Non-Incendive Certificate No.: 0V9A7.AX Applicable Standards: FM Class , FM Class , FM Class , FM Class Markings: Intrinsically safe for use in Class I, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, and G; and Class III, Division 1 Temperature Code: T4 (Ta = 70 C) in accordance with Rosemount drawing Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Code: T4 (Ta = 85 C), Enclosure Type 4X. For input parameters see control drawing
15 April 2013 Rosemount 2088 and 2090 Canadian Standards Association (CSA) All CSA hazardous approved transmitters are certified per ANSI/ISA C6 Explosion-Proof, Intrinsically Safe, Dust Ignition-Proof and Class I Division 2 Applicable Standards: CAN/CSA Std. C22.2 No. 0-M91, CSA Std. C22.2 No , CSA Std. C22.2 No M1986, CAN/CSA Std. C22.2 No M91, CSA Std. C22.2 No M1987, CAN/CSA Std. C22.2 No , CSA Std. C22.2 No M1987, ANSI/ISA Markings: Explosion-proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II, Division 1, Groups E, F, G, Class III. Suitable for Class I, Division 2, Groups A, B, C, and D. Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. Temperature Code: T3C. Enclosure Type 4X. Factory sealed. Single Seal. See control drawing European Certifications ED ATEX Flameproof Certification No.: KEMA97ATEX2378X Applicable Standards: EN :2006, EN :2007, EN :2007 Markings: II 1/2 G Ex d IIC T6 (-40 C T amb 40 C); T4 (-40 C T amb 80 C) 1180 Vmax = 36 (with Output Code S) Vmax = 14 (with Output Code N) I1 Special Conditions for Safe Use (x): 1.The cable and conduit entry devices shall be of a certified flameproof type Ex d, suitable for the conditions of use and correctly installed. 2.With the use of conduit entries a sealing device shall be provided immediately on the entrance thereto. 3.Unused apertures shall be closed with suitable Ex d certified blanking elements. 4.Suitable heat-resisting cables shall be used when the ambient temperature at the cable or conduit entries exceed 65 C. 5.This device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime. 6.For information on the dimensions of the flameproof joints the manufacturer shall be contacted. ATEX Intrinsic Safety Certificate No.: BAS00ATEX1166X Applicable Standards: EN :2012, EN : 2012 Markings: II 1 G Ex ia IIC T5 Ga ( 55 C Tamb +40 C) Ex ia IIC T4 Ga ( 55 C T amb +70 C)
16 Rosemount 2088 and 2090 April 2013 Table 1. Input Parameters Loop/Power U i = 30 Vdc I i = 200 ma P i = 0.9 W C i = F Special Conditions for Safe Use (X): The apparatus is not capable of withstanding the 500V insulation test required by EN This must be taken into account when installing the apparatus. N1 ATEX Non-incendive/Type n Certificate No.: BAS 00ATEX3167X Applicable Standards: EN :2012, EN : 2010 Markings: II 3 D Ex na IIC T5 Gc (-40 C < T amb < +70 C) Ui = 50 Vdc max 1180 Special Conditions for Safe Use (X): The apparatus is not capable of withstanding the 500V insulation test required by EN This must be taken into account when installing the apparatus. ND ATEX Dust Certificate No.: BAS01ATEX1427X Applicable Standards: EN :2012, EN : 2009 Markings: II 1 D Ex t IIIC T50 C T C Da Vmax = 36 V dc; Ii = 22 ma 1180 Special Conditions for Safe Use (X): 1.The user must ensure that the maximum rated voltage and current (36 volts, 24 ma, D.C.) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category ib circuit according to EN Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 3.Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66. 4.Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test. 5.The 2088/2090 sensor module must be securely screwed in place to maintain the ingress protection of the enclosure. 16
17 April 2013 Rosemount 2088 and 2090 IECEx Certifications E7 IECEx Flameproof Certification No.: IECEx KEM X Applicable Standards: IEC :2004, IEC :2003, IEC :2004 Markings: Ex d IIC T4 (-20 C T amb C) Ex d IIC T6 (-20 C T amb C) I7 IECEx Intrinsic Safety Certificate No.: IECEx BAS X Applicable Standards: IEC :2011, IEC : 2011 Markings: Ex ia IIC T5 Ga (-55 C T amb 40 C) Ex ia IIC T4 Ga ( 55 C T amb +70 C) Table 2. Input Parameters Loop/Power U i = 30 Vdc I i = 200 ma P i = 0.9 W C i = F Special Conditions for Safe Use (X): The equipment is not capable of withstanding the 500V insulation test required by EN This must be taken into account when installing the equipment. N7 IECEx Non-incendive/Type n Certificate No.: IECEx BAS X Applicable Standards: EN :202012, EN : 2010 Markings: Ex na IIC T5 Gc (-40 C Tamb +70 C) Ui = 50 Vdc max Input Parameters Loop/Power U i = 30 Vdc I i = 200 ma P i = 0.9 W C i = F Special Conditions for Safe Use (X): The equipment is not capable of withstanding the 500V insulation test required by EN This must be taken into account when installing the equipment. NK IECEx Dust Certificate No.: IECEx BAS X Applicable Standards: IEC :2011, IEC : 2008 Markings: Ex t IIIC T50 C T C Da Vmax = 36 Vdc; Ii = 24 ma 17
18 Rosemount 2088 and 2090 April 2013 Special Conditions for Safe Use (X): 1.The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime. 2.Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 3.Unused cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 4.Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact. 5.The 2088/2090 sensor module must be securely screwed in place to maintain the ingress protection of the enclosure. Japanese Certifications E4 TIIS Flame-Proof Ex d IIC T6 Certificate TC15874 TC15873 TC15872 TC15871 Description 2088 with Alloy C-276 wetted parts (with display) 2088 with SST wetted parts (with display) 2088 with Alloy C-276 wetted parts (no display) 2088 with SST wetted parts (no display) Brazil Certifications I2 INMETRO Intrinsic Safety Certificate No.: CEPEL X; Markings: Ex ia IIC T5/T4 Ga/Gb T5 (-20 C Tamb +40 C); T4 (-20 C Tamb +60 C) E2 INMETRO Flameproof (2088 Series only) Certificate No.: CEPEL Markings: Ex d IIC T6/T5 Gb T6 (-20 C Tamb +40 C); T5 (-20 C Tamb +60 C) China Certifications I3 China Intrinsic Safety Certificate No.: GYJ111063X (2088 Series); GYJ111065X (2090 Series) Applicable Standards: GB , GB Markings: Ex ia IIC T4/T5 T4 (-55 C Tamb +70 C); T5 (-55 C Tamb +40 C) 18 Table 3. Input Parameters Loop/Power U i = 30 Vdc I i = 200 ma P i = 0.9 W C i = F Refer to Appendix B of the 2088/2090 Reference Manual (document number ) for Special Conditions for Safe Use.
19 April 2013 Rosemount 2088 and 2090 E3 China Flameproof Certificate No.: GYJ (2088 Series); GYJ (2090 Series) Applicable Standards: GB , GB Markings: Ex d IIC T4/T6 T4 (-20 C T amb +40 C); T6 (-20 C T amb +80 C) Refer to Appendix B of the 2088/2090 Reference Manual (document number ) for Special Conditions for Safe Use. N3 China Type n Non-Sparking Certificate No.: GYJ101126X (2088 Series) Applicable Standards: GB , GB Markings: Ex na nl IIC T5 (-40 C Tamb +70 C) Refer to Appendix B of the 2088/2090 Reference Manual (document number ) for Special Conditions for Safe Use. Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types. K1 K5 K6 K7 KB KH I1, N1, ED, and ND combination E5 and I5 combination C6, I1 and ED combination E7, I7, N7, and NK combination K5, and C6 combination K5, ED, and I1 combination 19
20 Rosemount 2088 and 2090 April
21 April 2013 Rosemount 2088 and
22 Rosemount 2088 and 2090 April
Rosemount 4500 Hygienic Pressure Transmitter. Start
Quick Installation Guide June 2007 Rosemount 4500 Rosemount 4500 Hygienic Pressure Transmitter ProductDiscontinued Start Step 1: Mount the Transmitter Step 2: Set the Switches Step 3: Connect Wiring and
More informationRosemount 2051 Pressure Transmitter with 4-20 ma HART and 1-5 Vdc HART Low Power Protocol
Quick Installation Guide August 2009 Rosemount 2051 Rosemount 2051 Pressure Transmitter with 4-20 ma HART and 1-5 Vdc HART Low Power Protocol Start Step 1: Mount the Transmitter Step 2: Consider Housing
More informationRosemount 3051 Pressure Transmitter
Quick Start Guide 00825-0100-4001, rev. JA Rosemount 3051 Pressure Transmitter with 4-20 ma HART and 1-5 Vdc Low Power Protocol Rosemount 3051CF Series Flowmeter Transmitter with 4-20 ma HART and 1-5 Vdc
More informationRosemount 3051 Pressure Transmitter Includes Transmitter Option TR ProductDiscontinued. Start
Quick Installation Guide June 2009 Rosemount 3051 Rosemount 3051 Pressure Transmitter Includes Transmitter Option TR ProductDiscontinued Start Step 1: Mount the Transmitter Step 2: Consider Housing Rotation
More informationAnnubar Flowmeter Series
Reference Manual Appendix B Approvals Annubar Flowmeter Series Hazardous Locations Installations.................. page B-1 Rosemount 3051SFA Product Certifications.......... page B-1 Rosemount 3095MFA
More informationJ. Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter with HART Protocol.
Quick Installation Guide Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter with HART Protocol Rosemount 3051S Start Step 1: Mount the Transmitter Step 2: Consider Housing
More informationRosemount 2090P Pulp and Paper Pressure Transmitter
Product Data Sheet Rosemount 2090P Pulp and Paper Pressure Transmitter Rosemount 2090P 1-inch flush mount compatible with a PMC process connection, or 1 1 /2-inch threaded mounting connection Absolute
More informationRosemount 2090F Hygienic Pressure Transmitter
Hygienic Pressure Transmitter Conforms to 3-A Sanitary s Features CIP/SIP service for process temperatures up to 284 F (140 C) Absolute or gage pressure ranges from 0-1.5 to 0-300 psi Mounts with either
More informationRosemount 2088, 2090F, and 2090P Pressure Transmitter
Quick Start Guide 00825-0100-4108, Rev BA Rosemount 2088, 2090F, and 2090P Pressure Transmitter with 4-20 ma HART and 1-5 Vdc Low Power HART Protocol (Revision 5 and 7) Quick Start Guide NOTICE This guide
More informationRosemount 3051S MultiVariable Transmitter
HART Reference Card HART Rosemount 3051SMV Rosemount 3051S MultiVariable Transmitter A check ( ) indicates the basic configuration parameters. At minimum, these parameters should be verified as part of
More informationRosemount 2090F Sanitary Pressure Transmitter with HART Protocol
Sanitary Pressure Transmitter with HART Protocol A TRADITION OF EXCELLENCE IN PERFORMANCE Conforms to 3-A Sanitary Standards Features CIP/SIP service with an upper temperature limit of 284 F (140 C) USDA
More informationRosemount 2088 Absolute and Gage Pressure Transmitter
Product Data Sheet Rosemount 2088 Rosemount 2088 Absolute and Gage Pressure Transmitter Performance of 0.075% with High Accuracy option Lightweight, compact design for cost effective installation Protocols
More informationRosemount 248 Temperature Transmitter. Quick Start Guide , Rev. EA April 2013
Rosemount 248 Temperature Transmitter 00825-0100-4825, Rev. EA NOTICE This installation guide provides basic guidelines for the Rosemount 248 Wireless. It does not provide instructions for detailed configuration,
More informationRosemount 4600 Oil & Gas Panel Pressure Transmitter. Quick Start Guide , Rev GA September 2017
Rosemount 4600 Oil & Gas Panel Pressure Transmitter 00825-0100-4022, Rev GA NOTICE NOTICE This guide provides basic guidelines for the Rosemount 4600 Oil & Gas Panel Pressure Transmitter. It does not provide
More informationModel 144H. Product Data Sheet , Rev DB February Content
Rosemount 144 PC-Programmable Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement accuracy
More informationRosemount 8800D Series Vortex Flowmeter
Quick Installation Guide Rosemount 8800D Rosemount 8800D Series Vortex Flowmeter Start Step 1: Mount the Flowmeter Step 2: Consider Housing Rotation Step 3: Set Jumpers and Switches Step 4: Connect Wiring
More informationQuick Start Guide , Rev. BB February Rosemount 1495 Orifice Plate Rosemount 1496 Orifice Flange Union
00825-0100-4792, Rev. BB Rosemount 1495 Orifice Plate Rosemount 1496 Orifice Flange Union NOTICE This installation guide provides basic guidelines for Rosemount 1495 Conditioning Orifice Plate. It does
More informationRosemount 2051G Pressure Transmitter
Quick Start Guide 00825-0700-4101, Rev AB Rosemount 2051G Pressure Transmitter with 4 20 ma HART Protocol (Revision 5 and 7) Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount
More informationRosemount 2090F Hygienic Pressure Transmitter
Rosemount 2090F Hygienic Pressure Transmitter Product Data Sheet November 2016 00813-0100-4698, Rev FC Conforms to 3-A Sanitary Standards Features CIP/SIP service for process temperatures up to 284 F (140
More informationRosemount Pipe Clamp Sensor. Reference Manual , Rev BA February 2014
Rosemount Pipe Clamp Sensor Reference Manual Reference Manual Title Page The Rosemount 0085 Pipe Clamp Sensor NOTICE Read this manual before working with the product. For personal and system safety, and
More informationRosemount 2088 Absolute and Gage Pressure Transmitter
Product Data Sheet Rosemount 2088 Rosemount 2088 Absolute and Gage Pressure Transmitter Absolute and gage pressure ranges from 0 1.5 psi to 0 4,000 psi (0 0.1 to 0 276 bar) Performance of 0.075% with high
More informationRosemount 2088, 2090P, and 2090F Pressure Transmitters
Quick Start Guide 00825-0100-4690, Rev FD Rosemount 2088, 2090P, and 2090F Pressure Transmitters with 4 20 ma HART and 1 5 Vdc HART Low Power Protocol Quick Start Guide NOTICE This installation guide provides
More informationSmartPower Solutions [ SmartPower Solutions. Quick Installation Guide , Rev AC January 2012
Start Step 1: Physical Installation Step 2: Verify Operation Disposal/Recycling of Depleted Power Modules Product Certifications EC Declaration of Conformity End 00825-0100-4701[ 2012 Rosemount Inc. All
More informationRosemount 2090F Hygienic Pressure Transmitter
Rosemount 2090F Hygienic Pressure Transmitter Product Data Sheet December 2017 00813-0100-4698, Rev GA Conforms to 3-A Sanitary Standards Features CIP/SIP service for process temperatures up to 284 F (140
More informationRosemount 1595 Conditioning Orifice Plate
Quick Installation Guide December 2007 Rosemount 1595 Rosemount 1595 Conditioning Orifice Plate Start Step 1: Primary Element Location Step 2: Primary Element Orientation Step 3: Primary Element Installation
More informationRosemount 3144P Temperature Transmitter with HART Protocol
Quick Installation Guide Rosemount 3144P Rosemount 3144P Temperature Transmitter with HART Protocol Start Step 1: Configure (Bench Calibration) Step 2: Verify Configuration Step 3: Set the Switches Step
More informationRosemount 752 Fieldbus Remote Indicator
Product Data Sheet Rosemount 752 Rosemount 752 Fieldbus Remote Indicator ROSEMOUNT 752 DELIVERS: Two-wire segment powered device Displays up to 8 values Link Master Capability Optional PID, Characterizer,
More informationRosemount 702 Wireless Discrete Transmitter
August 2009 Rosemount 702 Rosemount 702 Wireless Discrete Transmitter Start Step 1: Physical Installation Step 2: Verify Operation Step 3: Reference Information Product Certifications EC Declaration of
More informationRosemount 644H and 644R Smart Temperature Transmitters
Quick Installation Guide March 2011 Rosemount 644 Rosemount 644H and 644R Smart Temperature Transmitters Start Step 1: Configure (Bench Calibration) Step 2: Verify Configuration Step 3: Set the Switches
More informationModel 144H. Product Data Sheet , Rev DB February Content
Rosemount 144 PC-Programmable Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement accuracy
More informationRosemount 4500 Hygienic Pressure Transmitter
Product Data Sheet Rosemount 4500 Rosemount 4500 Hygienic Pressure Transmitter Hygienic design conforms to 3-A and EHEDG standards Demonstrated best-in-class performance during SIP/CIP for process temperatures
More informationRosemount 2088, 2090F, and 2090P Pressure Transmitter
Quick Start Guide 00825-0100-4108, Rev CA Rosemount 2088, 2090F, and 2090P Pressure Transmitter with 4 20 ma HART and 1 5 Vdc Low Power HART Protocol (Revision 5 and 7) Quick Start Guide NOTICE This guide
More informationRosemount 4600 Oil & Gas Panel Pressure Transmitter
Product Data Sheet October 2017 00813-0100-4022, Rev LA Rosemount 4600 Oil & Gas Panel Pressure Transmitter A compact, lightweight, all-welded stainless steel design Up to 40:1 rangeability for increased
More informationRosemount 3144P Rosemount 3144P Temperature Transmitter
Temperature Transmitter Sensor Drift Alert and Hot Backup features improve measurement reliability while the Transmitter-Sensor Matching feature improves temperature measurement accuracy Statistical Process
More informationRosemount 3490 Series
Product Data Sheet July 2014 00813-0100-4841, Rev DA Rosemount 3490 Series 4 20 ma + HART Compatible Controller Field mounted controller with integral multi-function LCD and keypad Tough weatherproof wall
More informationRosemount 4500 Hygienic Pressure Transmitter Demonstrated best-in-class performance during SIP/CIP for process temperatures up to 400 F (204 C)
Product Data Sheet December 2012 00813-0100-4027, Rev BB Rosemount 4500 Hygienic Pressure Transmitter ProductDiscontinued R 37-01 Hygienic design conforms to 3-A and EHEDG standards Demonstrated best-in-class
More informationRosemount 148 Temperature Transmitter. Quick Start Guide , Rev GA September 2016
Rosemount 148 Temperature Transmitter 00825-0100-4148, Rev GA NOTICE This guide provides basic guidelines for the Rosemount 148. It does not provide instructions for detailed configuration, diagnostics,
More informationRosemount 3490 Series 4 20 ma + HART Compatible Controller
00825-0100-4841, Rev BA Rosemount 3490 Series 4 20 ma + HART Compatible Controller Quick Start Guide for Installation Failure to follow safe installation guidelines could result in death or serious injury
More informationRosemount 3051CFP Integral Orifice Flowmeter
December 2013 Rosemount 3051 Rosemount 3051CFP Integral Orifice Flowmeter See Specifications on page 47 and options for more details on each configuration. Rosemount 3051CFP Integral Orifice Flowmeters
More informationRosemount 2088 Absolute and Gage Pressure Transmitter
Product Data Sheet February 2015 00813-0100-4690, Rev PB Rosemount 2088 Absolute and Gage Pressure Transmitter Performance of 0.065% with High Accuracy option Lightweight, compact design for cost-effective
More informationRosemount 248 Temperature Transmitter
Product Data Sheet November 2013 00813-0100-4825, Rev KA Rosemount 248 Temperature Transmitter Basic temperature transmitter offers a reliable solution for temperature monitoring points transmitter design
More informationRosemount 752 FOUNDATION Fieldbus Remote Indicator
Rosemount 752 FOUNDATION Fieldbus Remote Indicator Product Data Sheet 00813-0100-4377, Rev FA Two-wire segment powered device Displays up to eight values Link Master Capability Optional PID, Characterizer,
More informationRosemount 3051HT Hygienic Pressure Transmitter
00825-0100-4091, Rev CA Rosemount 3051HT Hygienic Pressure Transmitter with 4 20 ma HART Revision 5 and 7 Protocol Note Before installing the transmitter, confirm the correct device driver is loaded on
More informationConfiguration Data Sheet
Product Data Sheet Configuration Data Sheet HART / 4 20 ma / AND SAFETY CERTIFIED TRANSMITTER = Default Configuration Customer Information Customer P.O. No. Sensor Model No. Line Item Sensor Type Sensor
More informationRosemount 3100 Series Ultrasonic Level Transmitters
Product Data Sheet Ultrasonic Level Transmitters Non-contacting measurement with no moving parts Integral LCD and push-buttons as standard for on-site programming Continuous measurement of level or distance-to-surface.
More informationRosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter
Quick Start Guide 00825-0100-4801, Rev NA Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter with HART Protocol Quick Start Guide NOTICE This guide provides basic guidelines
More informationRosemount 2051T In-Line Pressure Transmitter
Rosemount 2051T In-Line Pressure Transmitter 2051T In-Line Wireless Pressure Transmitter Configuration Transmitter Output Code 4-20 ma HART 2051 A 2051 with Selectable HART (1) Lower Power 2051 2051 with
More informationRosemount 214C Sensor. Quick Start Guide , Rev AF August 2017
Rosemount 214C Sensor 00825-0400-2654, Rev AF NOTICE This guide provides basic guidelines for Rosemount 214C Sensor models. If the sensor was ordered assembled to a temperature thermowell or transmitter,
More informationRosemount 3100 Series Ultrasonic Level Transmitters
Product Data Sheet Ultrasonic Level Transmitters Non-contacting measurement with no moving parts Integral LCD and push-buttons as standard for on-site programming Continuous measurement of level or distance-to-surface.
More informationSanitary Pressure Transmitter
Product Data Sheet 00813-0100-4698 Sanitary Pressure Transmitter A TRADITION OF EXCELLENCE IN PERFORMANCE Absolute or gage pressure ranges from 0 3 to 0 800 psi 0.20% reference accuracy, including linearity,
More informationSmartPower Solutions. SmartPower Solutions. Product Data Sheet , Rev AC January Contents
Product Data Sheet Intrinsically Safe design enables ability to perform routine maintenance in hazardous areas Predictable life specified under installed conditions Robust design for use in harsh environments
More informationRosemount 3051SFC Compact Orifice Flowmeter
Rosemount Compact Orifice Product Data Sheet Rosemount 3051SFC Compact Orifice Flowmeter SPECIFICATIONS Performance System Reference Accuracy Percent (%) of volumetric flow rate TABLE 1. 3051SFC Compact
More informationRosemount 3051P In-Line Pressure Transmitter. Product Data Sheet August , Rev BA
Rosemount 3051P In-Line Pressure Transmitter Product Data Sheet August 2018 00813-0100-4680, Rev BA August 2018 Settings the standard for pressure measurement Proven best-in-class performance and safety
More informationRosemount 8800D Series Vortex Flowmeter. Quick Start Guide , Rev FE October 2018
Rosemount 8800D Series Vortex Flowmeter 00825-0100-4004, Rev FE 1 About this guide This guide provides basic guidelines for the Rosemount 8800D Series Vortex Flowmeter. It does not provide instructions
More informationRosemount 3051L Level Transmitter
Rosemount 3051 December 2013 Rosemount 3051L Level Transmitter The Rosemount 3051L Level transmitter combines the performance and capabilities of Rosemount 3051 transmitters with the reliability and quality
More informationRosemount 3095MFC Compact Orifice Mass Flowmeter
Rosemount 3095MFC Compact Orifice Mass Flowmeter SPECIFICATIONS Performance System Reference Accuracy Percent (%) of mass flow rate TABLE 11. 3095MFC Compact Orifice Mass Flowmeter TYPE Repeatability ±0.1%
More informationRosemount 3490 Series 4 20 ma + HART Compatible Controller
00825-0200-4841, Rev AB Rosemount 3490 Series 4 20 ma + HART Compatible Controller Failure to follow safe installation guidelines could result in death or serious injury The Rosemount 3490 Series Control
More informationRosemount 3051SFP Proplate Flowmeter
SPECIFICATIONS Rosemount 3051SFP Proplate Flowmeter Performance System Reference Accuracy Percentage (%) of volumetric flow rate (1) Beta ( ) (2) Repeatability ±0.1% Line Sizes 1 /2-in. (15 mm) 1-in. (25
More informationAbsolute and Gage Pressure Transmitter
Product Data Sheet 0083-000-4699 Absolute and Gage Pressure Transmitter ATRADITION OF EXCELLENCE IN THE PULP AND PAPER INDUSTRY Mounts flush to process media -inch flush mount compatible with a PMC process
More informationRosemount 3144P Rosemount 3144P Temperature Transmitter
Product Data Sheet Rosemount 3144P Rosemount 3144P Temperature Transmitter Industry-leading temperature transmitter delivers unmatched field reliability and innovative process measurement solutions Achieve
More informationSmartPower Solutions. Quick Start Guide , Rev CA March 2015
SmartPower Solutions 00825-0100-4701, Rev CA NOTICE This guide provides basic guidelines for the SmartPower family of products. It does not provide instructions for detailed configuration, diagnostics,
More informationRosemount 3051CFC Compact Flowmeter
CFC Compact Flowmeter CFC Compact Flowmeters provide a quick, reliable installation between existing raised face flanges. Depending on your application needs, you can reduce energy loss with the Compact
More informationQuick Start Guide , Rev CB May Rosemount 3144P Temperature Transmitters with FOUNDATION fieldbus Protocol
Quick Start Guide 00825-0100-4834, Rev CB Rosemount 3144P Temperature Transmitters with FOUNDATION fieldbus Protocol Quick Start Guide NOTICE NOTICE This guide provides basic guidelines for the Rosemount
More informationRosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter
Quick Start Guide 00825-0100-4801, Rev MC Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter with HART Protocol Quick Start Guide NOTICE This guide provides basic guidelines
More informationUser s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No
User s Manual YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters Manual Change No. 16-045 Please use this manual change for the manuals listed below. 1. Applicable manuals, revised item, revised
More informationRosemount 2051T In-line Pressure Transmitter
February 2017 T In-line Pressure Transmitter T In-line Wireless Pressure Transmitter Configuration 4 20 ma HART with Selectable HART (1) Lower Power with Selectable HART (1) FOUNDATION Fieldbus PROFIBUS
More informationRosemount 8600 Series Vortex Flowmeter. Quick Start Guide , Rev EB April 2018
Rosemount 8600 Series Vortex Flowmeter 00825-0100-4860, Rev EB April 2018 April 2018 1 About this guide This guide provides basic guidelines for the Rosemount 8600D Series Vortex Flowmeter. It does not
More informationSAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)
SAFETY MANUAL Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS) Sensor Module (GTS) Transmitter (GTX) Detector (GT3000) SAFETY CERTIFIED GT3000
More informationRosemount 3144P Temperature Transmitter
Temperature Transmitter Sensor Drift Alert and Hot Backup features improve measurement reliability while the Transmitter-Sensor Matching feature improves temperature measurement accuracy Statistical Process
More informationRosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series Flowmeter MultiVariable Transmitter
Quick Start Guide 00825-0100-4803, Rev EF Rosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series Flowmeter MultiVariable Transmitter Quick Start Guide NOTICE This guide provides basic guidelines
More informationSAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL
SAFETY MANUAL PointWatch Eclipse Infrared Hydrocarbon Gas Detector SIL 2 Certified Model PIRECL Safety Certified Model PIRECL PointWatch Eclipse IR Gas Detector This manual addresses the specific requirements
More informationRosemount 2160 Wireless Vibrating Fork Level Switch
January 2012 Rosemount 2160 Rosemount 2160 Wireless Vibrating Fork Level Switch Start Considerations and Recommendations Step 1: Physical Installation Step 2: Verify Operation Step 3: Reference Information
More informationRosemount 3051S MultiVariable Extension Supplement
Product Data Sheet April 2015 00813-0400-4801, Rev AA Rosemount 3051S MultiVariable Extension Supplement With the Rosemount 3051S MultiVariable Extensions, you can gain valuable process insight with two
More informationQuick Start Guide , Rev EA December Rosemount 0065/0185 Sensor Assembly
Quick Start Guide 00825-0200-2654, Rev EA Rosemount 0065/0185 Sensor Assembly Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 0065 and 0185 Sensor models. It does not provide
More informationRosemount 2051CF DP Flowmeters
Product Data Sheet June 2013 00813-0400-4485, Rev EC Rosemount 2051CF DP Flowmeters Up to 2.00% volumetric flow accuracy at 5:1 turndown Available with HART and FOUNDATION fieldbus Protocols 2-year stability
More informationRosemount 248 Temperature Transmitter
Product Data Sheet March 2017 00813-0100-4825, Rev LA Rosemount 248 Temperature Transmitter Basic temperature transmitter offers a reliable solution for temperature monitoring points. Standard transmitter
More informationRosemount 644 Temperature Transmitter
Quick Start Guide 00825-0200-4728, Rev GB Rosemount 644 Temperature Transmitter with 4 20 ma HART Protocol (Revision 5 and 7) Note Before installing the transmitter, confirm the correct device driver is
More informationMobrey MSP900SH Level and MSP900FH Flow Ultrasonic Transmitters
Product Data Sheet Non-contacting measurement with no moving parts Fast and simple to install and configure Continuous measurement of level, contents (volume), or open channel flow MCERTS certified version
More informationRosemount 0085 Pipe Clamp Sensor Assembly. Quick Start Guide , Rev CA June 2016
Rosemount 0085 Pipe Clamp Sensor Assembly 00825-0100-4952, Rev CA NOTICE This guide provides basic guidelines for Rosemount 0085 Pipe Clamp Sensor. It does not provide instructions for configuration, diagnostics,
More informationRosemount 248 Temperature Transmitter
Product Data Sheet January 2018 00813-0100-4825, Rev LB Rosemount 248 Temperature Transmitter Basic temperature transmitter offers a reliable solution for temperature monitoring points. Standard transmitter
More informationRosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series MultiVariable Flowmeter
Quick Start Guide 00825-0100-4853, Rev AD Rosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series MultiVariable Flowmeter with FOUNDATION Fieldbus Protocol Quick Start Guide NOTICE This guide
More informationRosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeter
Quick Start Guide 00825-0100-4797, Rev ED Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeter with PROFIBUS PA Protocol Quick Start Guide NOTICE This installation guide provides basic
More informationRosemount 3144P Temperature Transmitter
Temperature Transmitter Sensor Drift Alert and Hot Backup features improve measurement reliability while the Transmitter-Sensor Matching feature improves temperature measurement accuracy. Communicates
More informationRosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter
Quick Start Guide 00825-0400-4101, Rev AD Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter with PROFIBUS PA Protocol Quick Start Guide NOTICE This installation guide provides basic
More informationIntrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20
Electronic Pressure Measurement Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20 Applications Chemical, Petrochemical
More informationFisher LCP100 Local Control Panel
Instruction Manual LCP100 Local Control Panel Fisher LCP100 Local Control Panel Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications... 2 Installation... 3 Hazardous Area Classifications
More informationQuick Start Guide , Rev HA January Rosemount 248 Temperature Transmitter
00825-0100-4825, Rev HA Rosemount 248 Temperature Transmitter NOTICE This guide provides basic guidelines for the Rosemount 248. It does not provide instructions for detailed configuration, diagnostics,
More informationIntrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter
PD685 Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter Actual Size Digits C US Intrinsically Safe 3½ Digits LARGE DISPLAY NEMA 4, Type 4X, IP67 Loop-Powered Field-Mount Process Meter 4-20 ma
More informationRosemount 8732E Magnetic Flowmeter System with Profibus PA digital fieldbus (Transmitter and Sensor)
Quick Installation Guide January 2010 Rosemount 8732 Rosemount 8732E Magnetic Flowmeter System with Profibus PA digital fieldbus (Transmitter and Sensor) Start Step 1: Pre-Installation Step 2: Handling
More informationRosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series Flowmeter MultiVariable Transmitter
Quick Start Guide 00825-0100-4803, Rev EA Rosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series Flowmeter MultiVariable Transmitter Quick Start Guide NOTICE This guide provides basic guidelines
More informationYTA Series Temperature Transmitters [Style: S3] EN :2006, -11:2007, -26:2007. Supply circuit: Ui=30 V, Ii=165 ma,
User s Manual YTA Series Temperature Transmitters [Style: S3] Manual Change No. 10-008 Please use the attached sheets in the following manuals when the product is with /KU2 option and EN60000 Series based
More informationRosemount 752 Remote Indicator
Quick Start Guide 00825-0100-4377, Rev EA Rosemount 752 Remote Indicator with FOUNDATION Fieldbus Protocol Quick Start Guide This guide provides basic guidelines for Rosemount 752 Remote Indicator. It
More informationRosemount 8800D Series Vortex Flowmeter
Product Data Sheet May 2013 00813-0100-4004, Rev JB Rosemount 8800D Series Vortex Flowmeter Hart and FOUNDATION fieldbus Protocols All welded, non-clog design provides maximum performance, reliability
More informationRadar Transmitters SITRANS LR400 (HART/PROFIBUS PA) Quick Start Manual 03/2013 SITRANS
Radar Transmitters SITRANS LR400 (HART/PROFIBUS PA) Quick Start Manual 03/2013 SITRANS SITRANS LR 400 Quick Start Manual This manual outlines the essential features and functions of the SITRANS LR 400
More informationRosemount Compact Orifice Flowmeter Series
Product Data Sheet Reduced installation cost compared to a traditional orifice plate Accurate and repeatable Easy-to-install direct mount assembly Self-centering Based on ASME/ISO corner tap design Patent-pending
More informationSAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors
SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY-CERTIFIED Flame DETECTORs This manual addresses the specific requirements and recommendations applicable to the proper
More informationRosemount 0085 Pipe Clamp Sensor Assembly. Quick Start Guide , Rev DC August 2017
Rosemount 0085 Pipe Clamp Sensor Assembly Quick Start Guide 00825-0100-4952, Rev DC Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 0085 Pipe Clamp Sensor. It does not provide
More informationRosemount 148 Temperature Transmitter. Reference Manual , Rev CA April 2014
Rosemount 148 Temperature Transmitter Reference Manual Reference Manual Rosemount 148 Temperature Transmitter Rosemount 148 Hardware Revision 5 NOTICE Read this manual before working with the product.
More informationQuick Start Guide For the
A Leader in Level Measurement Quick Start Guide For the Universal IV Lite and Universal IV Pro Model Transmitters 2-Wire RF Admittance / Capacitance Level Measurement System with HART Protocol For Assistance
More informationRosemount 848T FOUNDATION Fieldbus High Density Temperature Transmitter
Quick Start Guide 00825-0100-4697, Rev SF Rosemount 848T FOUNDATION Fieldbus High Density Temperature Transmitter Device Revision 8 - Requires New DD/CFF Revision Quick Start Guide NOTICE This guide provides
More information