CO 2 Fire Extinguishing Systems
|
|
- Rosemary Todd
- 5 years ago
- Views:
Transcription
1 Guidelines for Fire Extinguishing Systems Planning and Installation Content 0 Foreword Application of the VdS guidelines General Scope Aims Description Effectiveness and application Alarm organisation Approval VdS-approved installers, components, and systems Completion Periodical inspections Normative references Definitions Contract planning and documentation General Initial considerations Preparation stage Planning stage General Layout and design Start of installation Installation certificate Life safety General Operating party's obligations Danger zone Ventilation concept Coaction of equipment parts as specified Organisational measures Provision of pressure gas tanks for fire extinguishing purposes
2 5 System design Units System type and structural requirements Openings outwards Smoke and heat exhaust ventilation systems Design quantity Minimum design quantity Design quantity including the surface area Maximum design quantity Height and temperature correction of the design quantity Additional requirements Supply quantity Reserve quantity Storage of extinguishing agent CO 2 High pressure CO 2 Low pressure Storage area of the extinguishing system Hydraulic calculation Discharge times Hold time Distribution pipework Pipes Pipe supports Selector valves Nozzles Certification and testing Fire detection Selection criteria for fire detection elements Fire detection elements Mechanic and pneumatic fire detection elements Triggering and actuation Delay device Manual triggering Disable device Electrical locking Emergency stop device Secondary flooding Alarm Wiring Pneumatic pilot lines Control container Shutdown of equipment Power supply of electrical installations Initial inspection and revision inspection Full discharge test Partial discharge CO 2 High pressure CO 2 Low pressure Explosive atmosphere
3 10 Maintenance of operational readiness General Instruction and training of personnel Controls Daily controls Weekly controls Monthly controls Log book Modifications Shutdown Maintenance Monitoring of extinguishing systems General Disable and triggering devices and selector valves CO 2 High pressure CO 2 Low pressure Quantity of extinguishing agent CO 2 High pressure CO 2 Low pressure Pressure Electrical lines Electrically operated components of the extinguishing system Indicator and control groups Fault indicator group Monitoring of disable devices Control groups Control and indicating equipment Indication of faults and blockings Power supply of the monitoring system Requirements for components of the monitoring equipment
4 Annex A Protection of zones of special type and use A.1 Concept for fire protection systems of rolling mills A.1.1 General A.1.2 Protection objective A.1.3 Requirements A.1.4 Fire detection system A.1.5 Extinguishing system A.1.6 Miscellaneous A.2 Concept for fire protection systems of hardening plants A.2.1 General A.2.2 Protection objective A.2.3 Requirements A.2.4 Fire detection system A.2.5 Extinguishing system A.2.6 Miscellaneous A.3 Concept for fire protection systems of deep fat fryers and the corresponding extractor hoods A.3.1 General A.3.2 Protection objective A.3.3 Requirements A.3.4 Fire detection system A.3.5 Extinguishing system A.4 Concept for fire protection systems of rotogravure web fed presses A.4.1 General A.4.2 Protection objective A.4.3 Extinguishing system A.5 Concept for fire protection systems of coating plants featuring spraying of ignitable substances A.5.1 Scope A.5.2 Normative references A.5.3 General A.5.4 Protection objective A.5.5 Requirements A.5.6 Particularities A.5.7 Operation A.6 Protection concept for fire protection systems of electrostatic coating plants (local protection) A.6.1 Scope A.6.2 Protection objective A.6.3 Requirements A.6.4 Fire and extinguishing tests at electrostatic spraying devices for powders and paints A.7 Concept for local protection of electric and electronic equipment A.7.1 Scope Annex B Physical properties of extinguishing gases B.1 Purity requirements B.2 Physical properties Annex C K B factors C.1 General survey Annex D Block diagram for extinguishing gas systems
5 Annex E Components, systems, and calculation method E.1 Components E.2 Systems E.3 Calculation method Annex F Test procedure to determine the extinguishing concentrations of combustible liquids and gases by means of cup burner test F.1 Principles F.2 Apparatus F.3 Test procedure for combustible liquids F.4 Test procedure for combustible gases F.5 Calculation of design concentration Annex G Test procedure to determine the extinguishing concentrations by means of room tests G.1 General G.2 Extinguishing system G.3 Test room G.4 Extinguishing concentration G.5 Cold discharge test G.6 Measuring equipment G.6.1 Requirements G.6.2 Measurement of oxygen concentrations G.6.3 Nozzle pressure G.6.4 Room temperature G.6.5 Video / observations G.6.6 Measurement of extinguishing concentration G.6.7 Quantity of extinguishing agent G.6.8 Atmospheric pressure G.6.9 Positioning G.6.10 Data recording G.7 Documentation G.8 Wood crib test G.8.1 Ignition source G.8.2 Description of the burning object G.8.3 Data recording G.8.4 Documentation G.9 Heptane pan test G.9.1 Ignition source G.9.2 Description of the burning object G.9.3 Test method G.9.4 Determination of the design concentration of extinguishing agent G.9.5 Data recording G.9.6 Documentation G.10 Plastic sheet fire tests G.10.1 Ignition source G.10.2 Description of the fire object G.10.3 Test method G.10.4 Determination of the design concentration of extinguishing agent G.10.5 Data recording G.10.6 Documentation
6 Annex H Structural separation of the enclosure H.1 Example H.2 Permissible exceptions for protection objective H.3 Information on selection of the protection objective and the enclosures Annex I Calculation formulae for pipework I.1 Pressure drop along the pipe system I.2 Local phase change I.3 Working pressure in the container I.4 Universal calculation set-up for the nozzle pressure drop Annex J Pressure relief openings for the enclosure of rooms protected by extinguishing gas J.1 Equation for the calculation of the pressure relief openings J.2 Derivation Annex K Requirements for pressure relief devices K.1 Basic requirements for pressure relief devices K.2 Types of drives and pressure relief devices K.2.1 Pressure relief device independent of external power supply K.2.2 Pressure relief devices depending on external power supply K.3 Requirements for the structural quality of pressure relief devices K.3.1 Fire protection system requirements K.3.2 Requirements for the structural design of pressure relief ducts K.4 Calculation procedures for pressure relief devices K.4.1 Pressure relief directly into the open K.4.2 Pressure relief through ducts K.4.3 Pressure relief through secondary rooms K.4.4 Distribution of extinguishing gas in the secondary room Annex L Door fan test to determine the hold time L.1 Scope L.2 Test methods to determine the hold time L.2.1 Principle L.2.2 Test facility L.2.3 Calibration and accuracy of apparatus L.2.4 Preparation L.2.5 Evaluation of the test room L.2.6 Measurement of the test room L.2.7 Test procedure L.2.8 Calculation L.3 Treatment of test rooms with theoretical hold times less than the recommended value L.3.1 General L.3.2 Leakage areas L.3.3 Sealing of the test room L.3.4 Quantification and location of leaks L.3.5 Final calculation of the hold time L.4 Report Annex M Requirements for material and fire resistance classes and their classification in accordance with DIN 4102 and DIN EN M.1 Principles M.2 Combustibility of building materials M.3 Fire resistance of components
7 Annex N Purge certificate Annex O Sample form: Instruction document Annex P Sample form: Handover and/or approval document Operating party Name of representative Date, signature List of tables List of figures Index
AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS
SPECIAL HAZARDS PROTECTION AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS Hazard type The risks considered, according to existing regulations, are Class A risk: solids fire. Class B risk: fire of flammable
More informationFire Protection for Catering Kitchens KS 2000 Compact Extinguishing System. Safe for certain.
SPECIAL EXTINGUISHING SYSTEMS COMPACT EXTINGUISHING SYSTEMS Fire Protection for Catering Kitchens KS 2000 Compact Extinguishing System Safe for certain. ISK DETECTION Catering kitchens tend to use large
More informationFire Protection for Catering Kitchens KS 2000 Compact Extinguishing System. Safe for certain.
SPECIAL EXTINGUISHING SYSTEMS COMPACT EXTINGUISHING SYSTEMS Fire Protection for Catering Kitchens KS 2000 Compact Extinguishing System Safe for certain. ISKS IDENTIFYING Catering kitchens tend to use large
More informationMAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES
SHIPPING NOTICE Maritime Authority of the Cayman Islands Head Office 3 rd Floor, Government Administration Building, 133 Elgin Avenue PO Box 2256, Grand Cayman, KY1-1107, Cayman Islands Tel: +1 345 949
More informationautomatic FiReFighTing SYSTeMS in PainT booths
SPECIAL HAZARDS PROTECTION automatic FiReFighTing SYSTeMS in PainT booths hazard type The risks considered, according to existing regulations, are Class A risk: solids fire. Class B risk: fire of flammable
More informationGUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS
12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety
More informationWatermist Fire Protection of Plant Rooms
Guidance Note Watermist Fire Protection of Plant Rooms SCOPE This document sets out the requirements for protection of plant rooms with watermist systems and should be read in conjunction with BS8489-1.
More informationGAS EXTINGUISHING SYSTEMS INERT GAS. Argotec with argon or nitrogen
GAS EXTINGUISHING SYSTEMS INERT GAS Argotec with argon or nitrogen NATUR AL without any damage to the atmosphere The extinguishing gases Argon and nitrogen extinguish a fire by oxygen displacement. When
More informationElement C3.4 Fire Fighting Equipment
.4 Fire Fighting Equipment Classification of Fires Class A Solids. Wood, paper, plastics Class B Liquids Petrol oil, paint Class C Gases LPG, natural gas Classification of Fires Class D Metals Zinc, sodium,
More informationSpecial solution KS marine. Kitchen protection system KS marine Fire prevention for galleys
Special solution KS 2000-8 marine Kitchen protection system KS 2000-8 marine Fire prevention for galleys RiskDeep fat fryer fire Safety requirements for passengers and crew are especially high at sea.
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 61241-1-2 Second edition 1999-06 Electrical apparatus for use in the presence of combustible dust Part 1-2: Electrical apparatus protected by enclosures and surface temperature
More informationAS AS Australian Standard. Industrial fuel-fired appliances. This is a free 9 page sample. Access the full version online.
AS 1375 2013 AS 1375 2013 Australian Standard Industrial fuel-fired appliances This Australian Standard was prepared by Committee AG-011, Industrial and Commercial Gas Fired Appliances. It was approved
More informationNFPA 45 NFPA 211 NFPA 1600
NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA
More informationCO2 COCO GAS FLOODING SYSTEM
PRE INTRODUCTION: CO2 COCO GAS FLOODING SYSTEM The importance of erection, testing and commissioning are overlooked, in many projects while installing fixed Co2 extinguishing system. It is very common
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-26992-0 SOUTH AFRICAN NATIONAL STANDARD Fire detection and alarm systems for buildings System design, installation and servicing Published by SABS Standards Division 1 Dr Lategan Road Groenkloof
More informationSpark Extinguishing Systems
VdS Guidelines for VdS 2518en Requirements and Test Methods VdS 2518en : 2008-08 (01) Publishing house: VdS Schadenverhütung GmbH Amsterdamer Str. 172-174 50735 Köln, Germany Phone: +49 221 77 66 0; Fax:
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-28897-6 IEC 61869-1:2007 SOUTH AFRICAN NATIONAL STANDARD Instrument transformers Part 1: General requirements This national standard is the identical implementation of IEC 61869-1:2007 and
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS
FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber
More informationCO 2 EXTINGUISHING SYSTEMS
CO 2 EXTINGUISHING SYSTEMS CO 2 THE FIRE EXTINGUISHING CLASSIC: CLEAN, FAST AND RELIABLE TOTAL WALTHER, the acknowledged specialist in fire protection systems, has been manufacturing CO 2 extinguishing
More informationDiocese of Cleveland Facilities Services Corporation
Diocese of Cleveland Facilities Services Corporation BOILER MAINTENANCE and SERVICING SEASONAL MAINTENANCE - to be performed by trained boiler technician or boiler contractor only: 1. Disassemble the low
More informationDIRECTIVE NO: D-B
DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting
More informationTechnologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230
Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec
More informationANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL
Annex 2, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Section 1 Application 1 The following new sentence is added to the end of paragraph 1.2:
More informationOxeo extinguishing systems
Experts in fire protection Oxeo extinguishing systems TECHNOLOGIES GAS EXTINGUISHING SYSTEMS Residue-free fire extinguishing Oxeo extinguishing systems from Minimax use nitrogen and argon to fight fire.
More informationTECHNICAL AND USER REQUIREMENTS FOR PERSONAL ALERT SAFETY SYSTEMS
Centrum Naukowo Badawcze Ochrony PrzeciwpoŜarowej (Scientific and Research Centre for Fire Protection) Nadwiślańska 213, 05-420 Józefów, Poland Telephone (+48) 22 789 11 11 Fax.: (+48) 22 769 33 45 e-mail:
More informationSERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY
Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not
More informationISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source
INTERNATIONAL STANDARD ISO 9239-1 Third edition 2010-06-15 Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source Essais de réaction au feu des
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE
FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification
More informationFIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION
CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)
FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building
More informationAS/NZS :2008
AS/NZS 60079.29.2:2008 Australian/New Zealand Standard Explosive atmospheres Part 29.2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen AS/NZS 60079.29.2:2008
More informationTechnologies Gas extinguishing systems. MX 200 Fire Extinguishing Systems Fighting Fire using HFC-227ea
Technologies Gas extinguishing systems MX 200 Fire Extinguishing Systems Fighting Fire using HFC-227ea ire protection Efficient and compact MX 200 fire extinguishing systems fight fires using HFC-227ea.
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE
FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification
More informationObjectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts
Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives
More informationThis document is a preview generated by EVS
INTERNATIONAL STANDARD IEC 60092-502 Fifth edition 1999-02 Electrical installations in ships Part 502: Tankers Special features Installations électriques à bord des navires Partie 502: Navires-citernes
More informationContractor Worksheet Underground Fires Major Hazard Standard
WMC Environment, Health & Safety Management System Worksheet Major Hazard Standard MHS-02 DocsOpen Ref: 57267, 17/10/2001 Uncontrolled copy check web for latest revision Revision Reviewed Description of
More informationGAS EXTINGUISHING SYSTEMS INERT GAS. Argon Extinguishing Systems. Fire Protection Systems
GAS EXTINGUISHING SYSTEMS Argon Extinguishing Systems Fire Protection Systems EFFECTIVE NATURAL no damage to the atmosphere technology for complex applications EXAMPLE GAS EXTINGUISHING SYSTEMS solution
More informationExplosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen
IEC 60079-29-2 Edition 2.0 2015-03 REDLINE VERSION colour inside Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen
More informationISO INTERNATIONAL STANDARD. Testing of valves Fire type-testing requirements. Essais des appareils de robinetterie Exigences de l'essai au feu
INTERNATIONAL STANDARD ISO 10497 Third edition 2010-02-15 Testing of valves Fire type-testing requirements Essais des appareils de robinetterie Exigences de l'essai au feu Reference number ISO 10497:2010(E)
More informationSBI. Single Burning Item - EN THE BENCHMARK IN FIRE TESTING
SBI Single Burning Item - EN 13823 THE BENCHMARK IN FIRE TESTING FTT Single Burning Item (SBI) The importance of the SBI The European Construction Products Directive requires that all European Member states
More informationhighline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10
highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60079-29-2 Edition 2.0 2015-03 Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen INTERNATIONAL
More informationAustralian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS
AS 4214 2002 (Incorporating Amendment No. 1) AS 4214 2002 Australian Standard Gaseous fire extinguishing systems This Australian Standard was prepared by Committee FP-011, Gaseous Fire Protection. It was
More informationShips and marine technology Fireextinguishing. of galley cooking equipment
INTERNATIONAL STANDARD ISO 15371 Third edition 2015-11-15 Ships and marine technology Fireextinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d extinction
More informationProcedure for the Approval of New Fire Detection and Alarm Technologies
VdS Guidelines for Automatic Fire Detection and Fire Alarm Systems VdS 3469en Procedure for the Approval of New Fire Detection and Alarm Technologies VdS 3469en : 2016-01 (01) Publisher and publishing
More informationCLEAN AGENTS Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition
1 CLEAN AGENTS 2015 Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition APRIL 2015 M O-KAN SFPE CHAPTER M EETING APRIL 6, 2015 PRESENTED BY C. DAVIS & D. O DONNELL
More informationHOT WORK PERMIT PROCEDURES
HOT WORK PERMIT PROCEDURES 1. An approved YYC Hot Work Permit is required when any cutting, grinding, welding, or soldering work is being done. As well, any work that creates a dust cloud which can set
More informationINTERNATIONAL STANDARD
IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60
More informationfixed dry aerosol fire extinguishing components FirePro Systems Ltd.
product certificate Issued 2013-01-11 Valid untill 2013-11-19 Replaces K21477/11 Page 1 of 22 FirePro fixed dry aerosol fire extinguishing components STATEMENT BY KIWA With this product certificate, issued
More informationTitle: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015
Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Fire Protection I. INTRODUCTION II. GENERAL GUIDELINES III.
More informationBasically, the instruction handbook shall contain the following information:
TESTBODY INFO Issue: 2015/08 Order Nr. 901e Instruction for drafting the Instruction handbook For every machine, an Instruction handbook shall be drawn up in one of the languages of the country where the
More informationWet alarm valve stations
VdS Guidelines for water extinguishing systems VdS 2100-01en Requirements and test methods VdS 2100-01en : 2011-05 (02) Publishing house: VdS Schadenverhütung GmbH Amsterdamer Str. 172-174 50735 Köln,
More informationThis policy applies to all Hot Work jobs performed on the Calhoun mill property by AbitibiAbitibiBowater employees.
Reviewed: July 30, 2009 Revised: July 30, 2009 Effective: October 1, 2007 I. PURPOSE The purpose of this policy is to protect employees and prevent property loss due to fire and/or explosion during welding
More informationOWNER'S OPERATION AND MAINTENANCE MANUAL
OWNER'S OPERATION AND MAINTENANCE MANUAL P/N 15064 Amerex Industrial Dry Chemical Fire Suppression System MODELS IS18ABC (18 lb. ABC) / IS35ABC (35 lb. ABC) / IS45ABC (45 lb. ABC) / Manufactured by: AMEREX
More informationCO 2. fire extinguishing systems
fire extinguishing systems Extinguishing technique is a colourless, odourless and electrical non-conductive gas. In systems the is mixed with a special identifiable odour. The extinguishing effect of is
More information26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1007 26 June 2001 GUIDELINES FOR THE
More informationAustralian Standard. Water mist fire protection systems System design, installation and commissioning AS
AS 4587 1999 Australian Standard Water mist fire protection systems System design, installation and commissioning This Australian Standard was prepared by Committee FP/12, Aqueous Fire Protection Systems.
More informationWater Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE
Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers 8th March 2016 Dr Tim Nichols CPhys MIFireE Industrial Oil Cookers 2 What are Industrial Oil Cookers Large cooker of food
More informationProcess Control PIP PCEA001 Fixed Gas Detection Guidelines
November 2015 Process Control PIP PCEA001 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical
More informationProject Name: Project Address: Installer Name: Installer Address: Date of Inspection:
FIRE DEPARTMENT Kitchen Range Hood Fire Suppression System Acceptance Test Project Name: Project Address: Installer Name: Installer Address: Date of Inspection: DOCUMENTATION NO Plans have been reviewed
More informationRESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS
RESOLUTION MSC.292(87) THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, NOTING resolution MSC.98(73)
More informationDescription of the European standard EN 378: Refrigerating systems and heat pumps Safety and environmental requirements
: Refrigerating systems and heat pumps Safety and environmental requirements Prof. Dr. Risto Ciconkov, dipl. ing. Faculty of Mechanical Engineering, University Ss. Cyril & Methodius Skopje, R. Macedonia
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities
More informationIndustrial Explosion Suppression Technology
88 th Annual Michigan Safety Conference 2018 Tuesday April 17 th 2018-10:45 AM Industrial Division Lansing Center, Lansing, MI Industrial Explosion Suppression Technology Presenter: Rob Markle Phone: (309)
More informationISO INTERNATIONAL STANDARD. Smoke alarms using scattered light, transmitted light or ionization
INTERNATIONAL STANDARD ISO 12239 Second edition 2010-12-15 Smoke alarms using scattered light, transmitted light or ionization Détecteurs de fumée à lumière dispersée, lumière transmise ou ionisation Reference
More informationRevised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*
1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-32798-9 SOUTH AFRICAN NATIONAL STANDARD Gas measuring equipment primarily for use in mines Part 5: Fire detectors WARNING This standard references other documents normatively. Published
More informationIGEM/G/5 Edition 2 Communication 1762 Gas in multi-occupancy buildings
Communication 1762 Gas in multi-occupancy buildings Founded 1863 Royal Charter 1929 Patron: Her Majesty the Queen Communication 1762 Gas in multi-occupancy buildings Price Code: C5H The Institution of
More informationDUST COLLECTION TRAINING. Revision 2013
DUST COLLECTION TRAINING Revision 2013 TOPICS 1. Why does a school need a dust collector? 2. What is a dust collection system? 3. What are the maintenance requirements? 4. What are the hazards? WHY NFPA
More informationOfficial Journal of the European Union
C 20/16 27.1.2009 Commission communication in the framework of the implementation of the Directive 94/9/EC of the European Parliament and the Council on the approximation of the laws of the Member States
More informationD. Reference Standards (Utilize latest editions available):
1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is
More informationFire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY
Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE
More informationSmoke detection in hazardous areas:
WHITE PAPER Smoke detection in hazardous areas: What you need to know Smoke detection in hazardous areas requires detectors that operate effectively and safely in explosive environments. Having the correct
More informationEnergy saving and better heat control.
Energy saving and better heat control. Bogh Industries LLC has completed a total heater and controls rebuild of a large cure oven. The project was initiated when it was discovered that the existing heat
More informationCOMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES*
COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* *Vented appliances refer to natural draft appliances equipped with a barometric draft regulator or Category I appliances equipped with a draft
More informationPreventing Fires And Explosions In Pilot Plants And Laboratory Units
Preventing Fires And Explosions In Pilot Plants And Laboratory Units Richard Palluzi ExxonMobil Research and Engineering Co 1545 Route 22 East Annandale, NJ 08801 October, 1998 1 Introduction Pilot plants
More informationISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment
INTERNATIONAL STANDARD ISO 15371 Second edition 2009-03-15 Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d'extinction
More informationRISK ENGINEERING GUIDELINE.
RISK ENGINEERING GUIDELINE. IMPAIRMENT OF FIRE PROTECTION SYSTEMS HDI Risk Consulting Property www.hdi.global An impairment of fire protection systems increases the risk. In order to reduce the risk of
More informationSo what is a fire hazard?
So what is a fire hazard? A situation where there is a greater than normal risk of a fire starting. For a fire to start there have to be three components: fuel, ignition and oxygen. If all three are present,
More informationFire Prevention Plan Program
Fire Prevention Plan Program Effective Date: Revision #: Reference Standard Purpose Occupational Safety and Health Administration (OSHA) standard, 29 CFR 1910.39 Subpart E, Fire Prevention Plan This procedure
More informationIndustrial furnaces and associated processing equipment Safety. Part 2: Combustion and fuel handling systems
Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 13577-2 First edition 2014-09-15 Industrial furnaces and associated processing equipment Safety Part 2: Combustion and fuel handling systems Fours
More informationSELECTION, INSTALLATION & TESTING OF ELECTRICAL EQUIPMENTS IN HAZARDOUS AREA
Training Title SELECTION, INSTALLATION & TESTING OF ELECTRICAL EQUIPMENTS IN HAZARDOUS AREA Training Duration 5 days Training Venue and Dates REF EE019 Selection, Installation & Testing of Electrical Equipments
More informationSchedule of Accreditation
Schedule of Accreditation Organisation Name Trading As INAB Reg No 6023 Contact Name Address BRE Global Assurance (Ireland) Ltd David Gall Contact Phone No +353 1 882 4344 Email Website Accreditation Standard
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.
More informationISO INTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO 23551-1 Second edition 2012-08-15 Safety and control devices for gas burners and gas-burning appliances Particular requirements Part 1: Automatic and semi-automatic valves Dispositifs
More informationNew European Fire Testing Classification for Construction Products
New European Fire Testing Classification for Construction Products THE BENCHMARK IN FIRE TESTING EU Construction Products Directive The EU Construction Products Directive (CPD), is the basis of construction
More informationPlanned Preventative Maintenance Schedule. Fire Suppression PPM Schedule
Planned Preventative Maintenance Schedule Fire Suppression PPM Schedule Support Planned and contracted maintenance services To ensure that data centre or building services are always operating to their
More informationIndirect gas-fired air heater
Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury
More informationFORMOSA PLASTICS CORPORATION, TEXAS iv HEALTH AND SAFETY MANUAL Page 1 of 9 LIST OF RECORDS Revision Number: 197
HEALTH AND SAFETY MANUAL Page 1 of 9 Manual Name: Health and Safety FTESP001 Safety Training 1. All records generated by this procedure. FTESP002 Access Restriction 1. All records generated by this policy/procedure.
More informationAustralian/New Zealand Standard
AS/NZS 61779.6:2000 (Incorporating Amendment No. 1) AS/NZS 61779.6:2000 Australian/New Zealand Standard Electrical apparatus for the detection and measurement of flammable gases Part 6: Guide for the selection,
More informationI. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018
Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire
More informationISO INTERNATIONAL STANDARD. Determination of the resistance to jet fires of passive fire protection materials Part 1: General requirements
INTERNATIONAL STANDARD ISO 22899-1 First edition 2007-12-01 Determination of the resistance to jet fires of passive fire protection materials Part 1: General requirements Détermination de la résistance
More informationControl and Indicating Equipment
VdS Guidelines for Fire Detection and Fire Alarm Systems VdS 2540en Requirements and Test Methods VdS 2450en : 2018-12 (03) Publisher and publishing house: VdS Schadenverhütung GmbH Amsterdamer Str. 172-174
More informationEQUIPMENT INTENDED FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)
English European Commission > Enterprise & Industry > Industry Sectors > Equipment intended for use in Potentially Explosive Atmospheres (ATEX) > How to apply the Directive > Contact Search Considerations
More informationElectromagnetic Locking Devices Performance Requirements
Technical Specification Electromagnetic Locking Devices Performance Requirements DHF TS 010:2016 Technical specification produced by dhf www.dhfonline.org.uk Contents Foreword 1. Scope 2 ANNEX A Bodies
More informationLiquid Ring Vacuum Pumps, Compressors and Systems
Helmut Bannwarth Liquid Ring Vacuum Pumps, Compressors and Systems Conventional and Hermetic Design Translated by Christine Ahner WILEY- VCH WILEY-VCH Verlag GmbH & Co. KGaA XIII Foreword VII Preface IX
More informationThis document is a preview generated by EVS
INTERNATIONAL STANDARD ISO 14934-4 First edition 2014-08-15 Fire tests Calibration and use of heat flux meters Part 4: Guidance on the use of heat flux meters in fire tests Essais au feu Étalonnage et
More informationBoiler Technical Specifications (2013)
ACT Bioenergy Boiler Dimensions 0.5-0.85 Million Btu/h (150-250kW) Model CP500 CP600 CP750 CP850 Heat Output in MBtu/h (kw) 510 (150) 610 (180) 750 (220) 850 (250) Height ft (mm) 6 1 (1855) 6 1 (1855)
More informationHospitals and Major Medical Centers
Hospitals and Major Medical Centers INERGEN Fire Suppression Systems AUTOPULSE Detection and Control Equipment SENTRY Hand Portable Fire Extinguishers Medical centers have special concerns for fire safety
More information