Burner Management System

Size: px
Start display at page:

Download "Burner Management System"

Transcription

1 7 541 Burner Management System MV Burner control with integrated air / fuel ratio control for forced draft burners. The MV27.1 are designed for intermittent operation. The MV and this Data Sheet are intended for use by OEMs which integrate the burner management system in their products! Use The MV burner management system is a microprocessor-based unit with matching system components for the control and supervision of forced draft burners of medium to high capacity HVAC Products

2 Warning notes For additional safety notes, refer to the Basic Documentation of the MV system (P7541)! To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! The MV is a safety device! Do not open, interfere with or modify the unit. Siemens will not assume responsibility for any damage resulting from unauthorized interference! All activities (mounting, installation and service work, etc.) must be performed by qualified staff Before making any wiring changes in the connection area of the MV27.1, completely isolate the unit from the mains supply (all-polar disconnection) Ensure protection against electric shock hazard by providing adequate protection for the burner control s connection terals Each time work has been carried out (mounting, installation, service work, etc.), check to ensure that wiring and parameters is in an orderly state Fall or shock can adversely affect the safety functions. Such units must not be put into operation, even if they do not exhibit any damage For display of the flame on the AZ2, following general conditions apply: - Display is subject to various component tolerances so that deviations of ± 10 % can occur - Note that for physical reasons there is no linear relationship between flame display and detector signal values Mounting notes Ensure that the relevant national safety regulations are complied with Mounting Additional mounting surfaces z298e/0606 M5 x 4 Outer contour of housing 0.3 (103.5) Installation notes Always run high-voltage ignition cables separately while observing the greatest possible distance to the unit and to other cables Do not mix up live and neutral conductors 2/17

3 Electrical connection of the flame detectors It is important to achieve practically disturbance- and loss-free signal transmission: Never run the detector cable together with other cables ine capacitance reduces the magnitude of the flame signal Use a separate cable Observe the maximum permissible detector cable lengths The ionization probe is not protected against electric shock hazard. It is mainspowered and must be protected against accidental contact ocate the ignition electrode and the ionization probe such that the ignition spark cannot arc over to the ionization probe (risk of electrical overloads) Standards and certificates Conformity to EEC directives - Electromagnetic compatibility EMC (immunity) - Directive for gas appliances - ow-voltage directive 89 / 336 / EEC 90 / 396 / EEC 73 / 23 / EEC ISO 9001: 2000 Cert ISO 14001: 2004 Cert Identification code to EN 298 chapter 4 F T / M C B B Service notes If fuses are blown, the unit must be returned to Siemens Disposal notes The unit contains electrical and electronic components and must not be disposed of together with domestic waste. ocal and currently valid legislation must be observed. 3/17

4 Mechanical design The MV is a microprocessor-based system with matching system components for the control and supervision of forced draft burners of medium to high capacity. The following system components are integrated in the MV27.1 basic unit: Burner control with gas valve proving system Electronic air / fuel ratio control with a maximum of 2 actuators Modbus interface Example: Modulating gas burner The system components (display and operating unit, actuators) are connected directly to the MV27.1 basic unit. All safety-related digital inputs and outputs of the system are monitored by a contact feedback network (CFN). For intermittent operation in connection with the MV , an ionization probe or optical flame detector type QRB or QRC is used. The burner management system is operated and parameterized with the help of the AZ2 display and operating unit or a PC tool. The AZ2... features an CD and menu-driven operation, offering straightforward operation and targeted diagnostics. To simplify diagnostics, the display shows the operating states, the type of fault and the point in time the fault occurred. The different parameter setting levels for the burner / boiler manufacturer and the heating engineer are protected by passwords. Basic settings that the plant operator can make on site do not demand a password. There is also a communication interface COM from which higher level systems such as building automation (GA). Using the BCI and OCI410 interfaces, a PC with ACS410 software can be connected. Among other features, the software affords convenient readout of settings and operating states, parameterization of the MV , and trend logging. The burner / boiler manufacturer can choose from a number of different fuel trains and has a wide variety of parameter setting choices (program times, configuration of inputs and outputs, etc.) to ensure optimum adaptation to the relevant application. The SQM3... and SQN1 actuators are driven by stepper motors and offer highresolution positioning. The characteristics and settings of the actuators are defined by the MV basic unit. 4/17

5 Type summary Microprocessor-based burner control for single-fuel burners of any capacity, electronic air / fuel ratio control, up to 2 actuators, integrated gas valve proving system. Type reference Mains voltage Parameter set Type of flame detector MV27.100A2 AC 230 V Europe QRA2 / QRA4 (USA) / QRA10 / QRB / QRC / ION TSA Gas Oil 3 s 5 s Technical data MV27.1 basic unit Teral loading «Inputs» Mains voltage AC 230 V -15 % / +10 % Mains frequency 50 / 60 Hz ±6 % Power consumption < 30 W (typically) Safety class I, with parts according to II and III to DIN EN Degree of protection IP00 Note: The burner or boiler manufacturer must ensure degree of protection IP40 to DIN EN 529 for burner controls by adequate installation of the MV2 Perm. mains primary fuse max. 16 AT (externally) Unit fuse F1 (internally) 6.3 AT (DIN EN / 5) Mains supply: Input current depending on the operating state of the unit Undervoltage Safety shutdown from operating approx. AC 186 V position at mains voltage Restart on rise in mains voltage approx. AC 195 V Status inputs: Status inputs (with the exception of the safety loop) of the contact feedback network (CFN) are used for system supervision and require mains-related input voltage Input safety loop refer to «Teral loading outputs» Input currents and input voltages - UeMax UN +10 % - UeMin UN -15 % - IeMax 1.5 ma peak - IeMin 0.7 ma peak Contact material recommendation gold-plated silver contacts for external signal sources (P,, max, etc.) Transition / settling behavior / bounce - Perm. bounce time of contacts when switching on / off UN AC 230 V Voltage detection - On AC V - Off < AC 80 V max. 50 ms (after the bounce time, the contact must stay closed or open) 5/17

6 Technical data (cont d) Teral loading «Outputs» Total contact loading: Noal voltage AC 230 V, 50 / 60 Hz Unit input current (safety loop) from: max. 5 A - Fan motor contactor - Ignition transformer - Valves - Oil pump / magnetic clutch Individual contact loading: Fan motor contactor Noal voltage AC 230 V, 50 / 60 Hz Noal current 2 A Power factor cosϕ > 0.4 Alarm output Noal voltage AC 230 V, 50 / 60 Hz Noal current 1 A factor cosϕ > 0.4 Ignition transformer Noal voltage AC 230 V, 50 / 60 Hz Noal current 2 A Power factor cosϕ > 0.2 Fuel valves Noal voltage AC 230 V, 50 / 60 Hz Noal current 2 A Power factor cosϕ > 0.4 Operation display Noal voltage AC 230 V, 50 / 60 Hz Noal current 0.5 A Power factor cosϕ > 0.4 Cable lengths Mains line AC 230 V max. 100 m (100 pf / m) Display, BCI max. 3 m (100 pf / m) for used outside the burner cover or the control panel in assessment: max. 10 m (100 pf / m) for used outside the burner cover oad controller R max. 20 m (100 pf / m) External lockout reset button max. 20 m (100 pf / m) Other lines max. 3 m (100 pf / m) Specification as per EN Type of shutdown or interruption of each circuit Shutdown with microswitch 1-pole Mode of operation type 2 B 6/17

7 Technical data (cont d) Cross-sectional areas The cross-sectional areas of the mains power lines (, N, and ) and, if required, the safety loop (safety limit thermostat, water shortage, etc.) must be sized for noal currents according to the selected external primary fuse. The cross-sectional areas of the other cables must be sized in accordance with the internal unit fuse (max. 6.3 AT). Min. cross-sectional area 0.75 mm² (single- or multi-core to VDE 0100) Cable insulation must meet the relevant temperature requirements and environmental conditions. Fuses used in the MV basic unit - F1 6.3 AT DIN EN / 5 Connecting cable display BCI Environmental conditions Standard signal cable standard length 0.3 m and 2 m ocation under the burner cover or in the control panel Delivery Specification H Supplier Hütter Storage DIN EN Climatic conditions class 1K3 Mechanical conditions class 1M2 Temperature range C Humidity < 95 % r.h. Transport DIN EN Climatic conditions class 2K2 Mechanical conditions class 2M2 Temperature range C Humidity < 95 % r.h. Operation DIN EN Climatic conditions class 3K3 Mechanical conditions class 3M3 Temperature range C Humidity < 95 % r.h. Condensation, formation of ice and ingress of water are not permitted! 7/17

8 Technical data (cont d) Flame detectors Ionization probe No-load voltage at ION teral (X10 05 teral 2) approx. UNetz Caution! Protect the ionization probe against electric shock hazard! Short-circuit current max. AC 1 ma Required detector current. DC 4 µa, flame display approx. 30 % Possible detector current max. DC µa, flame display approx. 100 % Max. perm. length of detector cable 3 m (wire ground 100 pf / m) (laid separately) Note: With increasing detector cable capacitance (cable length), the voltage at the ionization probe, and thus the current, drops. ong cable lengths plus very highly resistive flames might necessitate low-capacitance detector cables (e.g. ignition cable). In spite of technical measures taken in the circuitry aimed at compensating potential adverse effects of the ignition spark on the ionization current, it must be made certain that the imum detector current required will already be reached during the ignition phase. If this is not the case, the connections on the primary side of the ignition transformer must be changed and / or the electrodes relocated. Photoresistive detectors QRB No-load voltage at QRB... teral (X10 05 teral 3) Max. perm. length of QRB... detector cable (laid separately) approx. DC 5 V 3 m (wire wire 100 pf / m) Note: A detector resistance of RF < 500 Ω is identified as a short-circuit and leads to safety shutdown in operation as if the flame had been lost. For this reason, before considering the use of a highly sensitive photoresistive detector (QRB1B... or QRB3S), it should be checked whether this type of flame detector is really required! Increased line capacitance between QRB... connection and mains live wire has an adverse effect on sensitivity and increases the risk of damaged flame detectors due to overvoltage. Always run detector cables separately! Threshold value flame supervision QRB with MV2 Start prevention (extraneous light) with RQRB Operation with RQRB Short-circuit detection with RQRB < 400 kω intensity > 10 % < 230 kω intensity > 16 % < 0.5 kω 8/17

9 Technical data (cont d) Flame detectors QRA2 / QRA4 (U.S.) / QRA10 Blue-flame detectors QRC Caution! If flame detectors type QRA2 / QRA4 are used for flame supervision with the MV2, it must be ensured that the detector is permanently connected to power (conforg to EN 230), thus enabling the system to detect flame detector failures during startup. Aquivalent threshold value: Operation approx. 20 µa (measured with DC 15 V / 4.5 kω series resistor) For system-specific reasons, the display of flame intensity is limited to a maximum of approximately 55 %. 9/17

10 Block diagram inputs / outputs Burner flange Motor Alarm Motor continuous SV Z V3 P P N N N T Siemens marking umberg code umberg code Siemens marking GP T GP X5-01 X9-04 X7-02 X4-02 X6-03 X3-05 X K54 03K30 03K10 03K66 03K57 03K80 02K15 02K02 04K01 02K13 04K80 03K34 05K30 X3-02 X5-03 X8-04 X8-02 X7-01 X N N N 2 3 On/off pa Safety loop V2 V1 B4 Reset P GP max P max X K31 02K43 X QRA... 05K37 X QRB... ION RXD0 TXD0 U Display X56 02K37 X Signal input Voltage umberg code Siemens marking / RAST2.5 X / RAST2.5 X / RAST2.5 X AK 1550/5-3.5-gr X Name PTR Siemens marking RXD1 TXD1 U Bus ACT0 Input B ACT0 Input A ACT0 Output B ACT0 Output A U ACT ACT1 Input B ACT1 Input A ACT1 Output B ACT1 Output A U ACT Analog output external 24 V external input b Display / BCI Fuel counter COM Actuator Fuel Actuator Air oad output AK 1550/5-3.5-gr X a14e/0606 Reserve 10/17

11 Inputs / outputs (cont d) X3-03 X3-05 X6-03 X4-02 X7-02 X9-04 X5-01 X5-02 FUSE 1 T6.3 IEC /V X75 X10-05 X10-06 X3-02 X5-03 X8-04 X8-02 X7-01 X3-04 N BCI X56 VSD X z297/0506 COM X92 1 FUE X54 1 AIR X53 1 X /17

12 Connection diagram MV2... X Wiring point for series valves MV2... X X Fuel valve V1 X X Fuel valve V2 X X Fuel valve V3 X X Fuel valve SV X X Ignition Power signal for air pressure switch (P) X P X Air pressure switch (P) 1' X Reset / manual locking On/Off X Controller (on / off) 3 X Controller closing / stage 3 Power signal for controller X X P 2 X X Controller opening / stage 2 Pressure switch- Power signal for pressure switch X X P P max T (CPI) X X Pressure switch-max Pressure switch-dk-fas / T or valve closing contact (CPI) X QRA... (+) Flame QRA... + QRB... / 1) only QRC... X X X QRA... (-) Protective earth () ION 1) X Power signal () X QRB... / QRC... signal voltage X Ionization probe (ION) X Indication oil / gas Fan X Continuous fan operation X Fan motor contactor Fan X Alarm X End switch burner flange (component of safety loop) X Power signal for end switch burner flange STB AUX Water shortage X X Safety loop Power signal for safety loop X Protective earth () N X Power supply neutral conductor (N) 1 F 6.3AT 1' X Power supply phase conductor () 7541a15e/ /17

13 Connection diagram (cont d) oad output DC 24 V external DC 0 / V Signal reference MV2... X74.1 X74.3 X74.2 VDS + 24 V + Mains supply input V - MV2... Fuel counter input Power supply for fuel counter Input fuel counter X75.2 X Fuel actuator Functional earth for shield connection SQM3... SHIED X54.1 X54.3 X54.4 X54.5 X54.6 UAC_SA ACT0_OUT_A ACT0_OUT_B ACT0_IN_A ACT0_IN_B AZ2... / OCI... U Display Display X56.1 DC 5 V X54.2 TXD0 X56.2 TXD0 FE RXD0 X56.3 RXD0 Air actuator Functional earth for shield connection X53.1 X53.3 X53.4 X53.5 SQM3... SHIED UAC_SA ACT1_OUT_A ACT1_OUT_B ACT1_IN_A GA U Display X56.4 GA X92.1 Signal reference DC 5 V X53.6 ACT1_IN_B TXD1 X92.2 TXD1 X53.2 RXD1 X92.3 RXD1 FE X92.4 Signal reference 7541a37e/ /17

14 Fuel train applications (examples) Direct gas ignition Program G Direct ignition SV V1 V2 DK max SA 7541s01e/0505 Gas pilot ignition 1 Program Gp1 Gas pilot SV V1 DK V2 max SA PV 7541s02e/0505 Gas pilot ignition 2 Program Gp2 Gas pilot SV V1 V2 DK max SA PV 7541s03e/0505 Fuel valve control program Direct trafo G PV *) V1 V2 TSA1 TSA2 Operation Gas (always modulating) Pilot ignition 1 Gp1 PV V1 V2 Pilot ignition 2 Gp2 PV V1 V2 egend for fuel trains: *) Not used 1) Series connection of two 115 V- valves (each requiring approx. 25 VA control power) 2) Preheating device V Fuel valve DK Gas valve proving Pressure switch HE Heating element HO Heavy fuel oil O ight fuel oil SA Actuator No Normally Open SV Shutoff valve (outside the building) PV Pilot valve 7541f01e/ /17

15 Fuel train applications (examples) Direct ignition with light fuel oil, multistage Program O V1 7541s04/ stage burner V2 Program O V1 2-stage burner 7541s05/0305 V3 V2 Program O V1 3-stage burner 7541s06/ /17

16 Fuel train applications (examples) Direct ignition with light fuel oil, modulating Program O V1 1) max M 1) Modulating burner (without shutdown facility for adjustable head) 7541s07e/0505 Program O V1 1) max M Modulating burner (with shutdown facility for adjustable head) 7541s08e/0505 Fuel valve control program ight fuel oil (Trafo direct ignition) O V1 V2 V3 TSA1 TSA2 Operation V3 V2 K position 7541f02e/0606 MIN MAX stage operation 16/17

17 Dimensions Dimensions in mm MV ,5 22,8 10,2 118, ,5 39,3 R ,5 82,5 27,2 12,5 23, ,5 19,7 100,8 118,5 76,6 53,6 25,5 7541m08/ Siemens HVAC Products GmbH Subject to change! 17/17

Burner Management System

Burner Management System 7 54 Burner Management System MV27... Burner control with integrated air / fuel ratio control for forced draft burners. The MV27. are designed for intermittent operation with ionization probe or with optical

More information

Burner Management System

Burner Management System 7 546 Burner Management System MV37.4... Burner control with integrated air / fuel ratio control for forced draft burners. The MV37.4... are designed for intermittent operation with ionization probe or

More information

Basic unit with integrated air-fuel ratio control for forced draft burners

Basic unit with integrated air-fuel ratio control for forced draft burners 7 546 Basic unit with integrated air-fuel ratio control for forced draft burners LMV37.4... The LMV37... is a microprocessor-based burner management system with matching system components for the control

More information

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division 7 547 LMV26.300... Basic unit with integrated fuel-air ratio control for forced draft burners Dual fuel switch unit AGM60.1... LMV26.300... AGM60.1... The LMV26... burner management system is a microprocessor-based

More information

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies 7 54 Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV27.00... The LMV27... is a microprocessor-based burner control with matching system components for the control and supervision

More information

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products Distribuitor: FLAME POWER SRL 021-3121727 ; 0744-340566 contact@arzatoare.ro ; www.arzatoare.ro 7 128 Oil Burner Control LOA44.252A27 Oil burner control for the supervision, startup and control of 1- or

More information

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products 7 418 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of small to medium capacity (without fan) in intermittent operation. The LGA... and this

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44... 7 130 Oil Burner Controls LMO14... LMO24... LMO44... Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Standard versions

More information

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44... 7 130 Oil Burner Controls LMO14... LMO24... LMO44... Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Standard versions

More information

LGA... Gas Burner Controls. Building Technologies Division

LGA... Gas Burner Controls. Building Technologies Division 7 418 Gas Burner Controls LGA... The gas burner controls are used for supervision, startup and control of atmospheric gas burners of small to medium capacity without a fan in intermittent operation. The

More information

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division 7 418 ISO 9001 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of low to medium capacity, without fan assistance, in intermittent operation. The

More information

Burner controls. Building Technologies HVAC Products

Burner controls. Building Technologies HVAC Products 7 101 Burner controls LE... Burner controls for the supervision of 1- or 2-stage gas or gas / oil burners of small to medium capacity, intermittent operation with or without fan. The LE and this Data Sheet

More information

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products 7 716 QRC1... for frontal illumination Blue-flame Detectors QRC1... for lateral illumination QRC1... Blue-flame detectors for the supervision of ue- or yellow-burning oil or gas flames. Blue-flame detectors

More information

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR 7 783 DETACTOGYR Flame Safeguard The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil or gas burners or

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

C Note! LGI16... Burner Controls. Building Technologies

C Note! LGI16... Burner Controls. Building Technologies 7 786 Burner Controls LGI16... Burner controls For use on industrial furnaces For burners in continuous operation Without fan control and air pressure supervision Flame supervision - with QR53... / QR55,

More information

Oil Burner Controls LOA3... Building Technologies HVAC Products

Oil Burner Controls LOA3... Building Technologies HVAC Products LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of - or 2-stage forced draft oil burners in intermittent operation. Oil throughput up to 0

More information

Gas Burner Controls. Building Technologies HVAC Products

Gas Burner Controls. Building Technologies HVAC Products 7 101 Gas Burner Controls E... Gas burner controls for the supervision of 1- or 2-stage gas burners of small to medium capacity, in intermittent operation. The E and this Data Sheet are intended for use

More information

Flame detector. Building Technologies Division Infrastructure & Cities Sector

Flame detector. Building Technologies Division Infrastructure & Cities Sector 7 711 Flame detector QRA4 UV flame detector for use with burner controls from Siemens for the supervision of gas or oil flames. The QRA4... and this Data Sheet are intended for use by OEMs which integrate

More information

Flame detector. The QRA4.U is for use with the following types of burner control:

Flame detector. The QRA4.U is for use with the following types of burner control: 7 711 Flame detector QRA4.U UV flame detector for use with burner controls from Siemens for the supervision of gas or oil flames. The QRA4.U and this Data Sheet are intended for use by OEMs which integrate

More information

Burner Controls. Building Technologies HVAC Products

Burner Controls. Building Technologies HVAC Products 7 101 Burner Controls E... Burner controls for the supervision of 1- or 2-stage gas or gas / oil burners of small to medium capacity, operation, with or without fan in intermittent. The E and this Data

More information

Infrared Flame Detectors

Infrared Flame Detectors 7 719 Infrared Flame Detectors QRI... Infrared flame detectors for use with Siemens burner controls, for the supervision of gas, oil and other flames that emit infrared light. The QRI... are suited for

More information

Flame detector. The QRA4.U is for use with the following types of burner control:

Flame detector. The QRA4.U is for use with the following types of burner control: 7 711 Flame detector QRA4.U UV flame detector for use with burner controls from Siemens for the supervision of gas or oil flames. The QRA4.U and this Data Sheet are intended for use by OEMs which integrate

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

LAE10 LFE10. Use. Series 02

LAE10 LFE10. Use. Series 02 ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,

More information

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit 7 618 Gas Burner Controls with automatic ignition and control functions for the heating and domestic hot water circuit ISO 9001 Microprocessor-based gas burner controls providing all control functions

More information

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products 7 711 Flame Detector QRA4.U Flame detector for use with burner controls from for the supervision of gas or oil flames. The QRA4.U and this Data Sheet are intended for use by OEMs which integrate the flame

More information

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products ISO 900 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of single- or 2-stage forced draft oil burners in intermittent operation. Oil throughput

More information

Product Range Overview

Product Range Overview 7 101 LME1 / LME2 / LME4 LME3 LME7 Product Range Overview LME LME are used for the startup and supervision of stage or modulating oil / gas burners in intermittent operation. Flame supervision takes place

More information

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55... 7 712 QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... The UV flame detectors are designed for use with Siemens burner controls, for the supervision

More information

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation.

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation. 7 2 SO 900 Burner Controls Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation. The burner controls are certified to E 230 and E 298.

More information

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products 7 712 ISO 9001 QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... The flame detectors are designed for use with our burner controls, for the supervision

More information

Use. The burner controls are certified to EN 230 and EN 298.

Use. The burner controls are certified to EN 230 and EN 298. 7 421 SO 9001 Burner Controls G2... Burner controls for the supervision of single- or two-stage forced draught gas or gas / oil burners of small to medium capacity (typically up to 350 kw) in intermittent

More information

Oil Burner Controls LOA3... Building Technologies Division

Oil Burner Controls LOA3... Building Technologies Division 7 8 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of - or 2-stage forced draft oil burners in intermittent operation. Oil throughput of

More information

LME75... Burner controls. Building Technologies

LME75... Burner controls. Building Technologies 7 156 Burner controls LME75... LME76 The LME75/LME76 is a microprocessor-based unit with matching system components for controlling and supervision of forced draft burners of medium to large capacity.

More information

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55... 7 712 QRA7 with clamp QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... QRA73 QRA75 The UV flame detectors are designed for use with Siemens burner

More information

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division 7 8 ISO 900 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of single- or twostage oil burners with an oil throughput of up to 0 kg/h in intermittent

More information

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55... 7 712 QRA7 with clamp QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... QRA73 QRA75 The UV flame detectors are designed for use with Siemens burner

More information

Infrared Flame Detectors

Infrared Flame Detectors 7 719 Infrared Flame Detectors QRI... Infrared flame detectors for use with Siemens burner controls, for the supervision of gas, oil and other flames that emit infrared light. The QRI... are suited for

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Program module for burner control LME71.000

Program module for burner control LME71.000 Presentation example PME7... Presentation example LME7... PME7.2... Program module for burner control LME7.000 User Documentation Application: - -stage, direct or pilot ignited atmospheric burners - Response

More information

Blue-flame Detectors

Blue-flame Detectors 7 716 QRC1... for frontal illumination QRC1... for lateral illumination Blue-flame Detectors QRC1... Blue-flame detectors for the supervision of ue- or yellow-burning oil or gas flames. Blue-flame detectors

More information

Heating Element. Building Technologies HVAC Products

Heating Element. Building Technologies HVAC Products 7 923 Heating Element AGA63 Heating element for use with SKP... and SKL actuators. The AGA63 extends the field of use of actuators and makes them more reliable at low or significantly varying ambient temperatures.

More information

Building Technologies Division

Building Technologies Division 7 782 Flame safeguard LFS1... Flame safeguard with approval for continuous operation for the supervision of oil flames and gas flames in applications with an ionization probe and a photocell detector RAR9.

More information

LFL Series Burner Flame Safeguard Control

LFL Series Burner Flame Safeguard Control LFL Series Burner Flame Safeguard Control Technical Instructions Document No. 74US LFL Rev. 2 November, 2004 The LFL is a compact electro-mechanical primary flame safeguard control designed to provide

More information

RAR... Photocell Detectors. Building Technologies Division

RAR... Photocell Detectors. Building Technologies Division 7 71 Photocell Detectors RR... The photocell detectors are designed for use with burner controls, for the supervision of yellow-flame oil flames. They are used especially in connection with burner controls

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification SCC Inc. LMV51 Control Product Description February 7, 2017 The LMV51 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft

More information

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55... 7 712 QRA7 with clamp QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... QRA73 QRA75 The UV flame detectors are designed for use with Siemens burner

More information

Building Technologies

Building Technologies 7 782 Flame safeguard LFS1... Flame safeguard with approval for continuous operation for the supervision of oil flames and gas flames in applications with an ionization probe and a photocell detector RAR9.

More information

Control Products & Systems OEM

Control Products & Systems OEM LMV Innovative electronic air-fuel ratio control Control Products & Systems OEM www.siemens.com/buildingtechnologies-oem Complete solutions from a single source Economical operation and environmental protection

More information

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage

More information

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21... Use Type summary Operating voltage AC 24 V or DC 13.5...3 Signal output DC 0...10 V for relative humidity Signal output

More information

Burner control unit BCU 370

Burner control unit BCU 370 Burner control unit BCU 370 Product brochure GB 6 Edition 11.08 For modulating, forced draught burners for gas of unlimited capacity in intermittent or continuous operation Control of fan and butterfly

More information

PRELIMINARY EDITION

PRELIMINARY EDITION 3 131 PRELIMINARY EDITION 14.01.2003 Synco 700 Heating Controllers Heating controller for medium-size and large buildings. The is used as a heating circuit or primary controller. The controller is supplied

More information

Burner control unit BCU 370

Burner control unit BCU 370 Burner control unit BCU 370 Product brochure GB 6.1.3.2 Edition 12.05 For modulating, forced draught burners for gas of unlimited capacity in intermittent or continuous operation Control of fan and butterfly

More information

Building Technologies Division

Building Technologies Division 7 154 Burner control LMO39... Burner control for the uperviion of 1- or 2-tage oil burner of mall to medium capacity, with or without fan in intermittent operation. The LMO39 and thi Data Sheet are intended

More information

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21 Operating voltage AC 24 V / DC 13535 V Signal output DC 010 V / 420 ma for relative humidity Signal output DC 010 V / 420 ma

More information

Eclipse Trilogy Flame Safeguard Modulating Sequences

Eclipse Trilogy Flame Safeguard Modulating Sequences Instruction Manual 830-2 2/25/2011 Eclipse Trilogy Flame Safeguard Modulating Sequences Series T420 Version 1 Copyright Copyright 2009 by Eclipse, Inc. All rights reserved worldwide. This publication is

More information

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE / 3 GM20 Digital Ground Continuity Relay For AC Systems Technical Bulletin NAE03230 / 0.20 GM20 Ground continuity monitor For AC systems Description The GM20 monitors the loop resistance of ground conductors

More information

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-703 120 VAC Microprocessor-Based Intermittent Pilot Ignition Control F-35-703 July 2016 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature 1 882 1882P01 Symaro Duct Sensors for relative humitidy (high accuracy) and temperature QFM31 Use Examples Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 4 20 ma for relative humidity and

More information

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - wwwmytubcouk - info@mytubcouk 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21 Use Operating voltage

More information

EUROBOX SERIES TYPES CM...N SM...N MM...N

EUROBOX SERIES TYPES CM...N SM...N MM...N EUROBOX SERIES TYPES CM...N SM...N MM...N AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN (MANUAL RESET) DESCRIPTION This series of electronic systems is suitable

More information

for relative humidity and temperature

for relative humidity and temperature 1 861 1861P01 Duct sensor for relative humidity and temperature QFM65 Operating voltage AC 24 V Signal output DC 0...10 V for relative humidity and temperature Measurement accuracy ±3 % r. h. within the

More information

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products 1 821 1821P01 Frost sensors for use on the air side Active capillary tube sensor for measuring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10 V Use On

More information

EUROBOX SERIES TYPES CM... SM... MM...

EUROBOX SERIES TYPES CM... SM... MM... EUROBOX SERIES TYPES CM... SM... MM... AUTOMATIC GAS BURNER CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN Application This range of electronic gas burner control systems

More information

for relative humidity and temperature

for relative humidity and temperature 1 860 1860P01 Duct sensor for relative humidity and temperature QFM651 Operating voltage AC 24 V Signal output DC 010 V for relative humidity Signal output L&S Ni 1000 (passive) for temperature Measurement

More information

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) T M 1 isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012670 / 08.2013 isopv425

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY AUTOMATIC BURNER CONTROL SYSTEM The burner control unit Quad400 is suitable for the control of direct ignition burners up to 350 kw, pursuant to EN 746-2. Flame control by means of UV scanner or ionization

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 505 Grünberg Tel.: 00 807-0 Fax: 00 807-259 Insulation monitoring device for unearthed AC/DC systems (IT systems for the supply of operating theatre

More information

Automation System TROVIS 5400 Boiler Controller TROVIS 5474

Automation System TROVIS 5400 Boiler Controller TROVIS 5474 Automation System TROVIS 5400 Boiler Controller TROVIS 5474 Application Weather-sensitive control of up to two boilers, designed for single-stage, two-stage or also modulating operating mode. Communication

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

Room Air Quality Sensors

Room Air Quality Sensors 1 961 1961P1 1961P2 QPA2 QPA2D Room Air Quality Sensors QPA2 With maintenance-free photoacoustic CO 2 sensing element and depending on the type of sensor VOC 1) sensing element, based on a heated tin dioxide

More information

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440) Safety Temperature Limiter STL 50 Certified to DIN EN 14597 (replaces DIN 3440) Features M For use as: STB Protection - temperature limiter ASTB Exhaust gas - protection - temperature limiter STW Protection

More information

Duct Temperature Sensors

Duct Temperature Sensors 1 762 1761P03 1762P01 Mounting flange AQM630 QAM21 Symaro Duct Temperature Sensors QAM2161040 QAM2171040 Active sensors for acquiring the air temperature in air ducts AC 24 V or DC 13535 V Signal output

More information

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01 Gamma instabus Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG1 528-1DB01 Technical Product Information Universal Dimmer for switching or dimming of dimmable lamps Supports dimmable lamps including

More information

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature 1 858 1858P01 1858P02 1859P02 Symaro Room Sensors for relative humidity (high accuracy) and temperature AQF3150 QFA31 Use Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 4 20 ma for r h and

More information

EUROFLAT SERIES TYPES C... S... M...

EUROFLAT SERIES TYPES C... S... M... EUROFLAT SERIES TYPES C... S... M... AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN APPLICATION The electronic systems of this range are suitable to control gas

More information

Duct Air Quality Sensors

Duct Air Quality Sensors 1 962 QPM2102D QPM2160D, QPM2162D QPM2100, QPM2102 QPM2160, QPM2162 Duct Air Quality Sensors QPM21 With maintenance-free CO 2 sensing element based on optical infrared absorption measurement (NDIR 1 )

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage forced draught and combi oil/gas burners Possible flame detectors: - Ionisation probe

More information

QFM21... Duct sensors. Symaro. for relative humidity and temperature

QFM21... Duct sensors. Symaro. for relative humidity and temperature 1 864 1864P01 Symaro Duct sensors for relative humidity and temperature QFM21... Operating voltage AC 24 V / DC 13.5...35 V Signal output DC 0...10 V / 4 20 ma for relative humidity Signal output DC 0...10

More information

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage atmospheric gas burners Flame detection: - Ionisation probe - Infrared-flicker detector

More information

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit Possible

More information

Rules for Intruder Alarm Systems

Rules for Intruder Alarm Systems Rules for Intruder Alarm Systems Opening detectors (Magnetic contacts) Part 1: Requirements VdS 2120en 03/96 (03) Subject 44 1 General; 2 Terms and definitions; 3 Classification 1 General 1.1 Scope These

More information

Distributed By: M&M Control Service, Inc Building Technologies

Distributed By: M&M Control Service, Inc Building Technologies Building Technologies Combustion Control Systems Count on Siemens. Siemens Building Technologies, the worldwide industry leader in combustion controls, delivers globally approved products specifically

More information

Monitoring Devices 11/1

Monitoring Devices 11/1 11/4 Introduction 11/6 5TE5 8 light indicators 11/7 4AC3 0, 4AC3 1 bells, buzzers 11/7 5TT3 46 fault signaling units 11/8 7LQ2 1, 5TT3 3 dusk switches 11/9 7LQ2 0 temperature controllers 11/9 5TT3 170

More information

Protective system controls, automatic burner control units, burner control units. Industrial & Commercial Thermal. 6 Edition 06.

Protective system controls, automatic burner control units, burner control units. Industrial & Commercial Thermal. 6 Edition 06. Industrial & Commercial Thermal Protective system controls, automatic burner control units, burner control units Product brochure GB 6 Edition 06.15l FCU 500 Protective system controls FCU 500 Protective

More information

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side s Frost detectors for use on the air side QAF63.2-J QAF63.6-J Active capillary tube sensor for acquiring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10

More information

for relative humidity and temperature with calibration certificates

for relative humidity and temperature with calibration certificates 1 859 1859P01 1859P02 QFA4160 AQF4150 Symaro Room Sensor for relative humidity and temperature with calibration certificates QFA4160 Operating voltage AC 24 V or DC 13.5...3 Signal output DC 0...10 V for

More information

DATASHEET. Burner control unit FDA 601x

DATASHEET. Burner control unit FDA 601x EN 298 / EN 230 2012 19 PCB 100x160mm 3HE/8TE socket DIN 41612 2-channel microprocessor controlled program air valve control for heating / cooling preventilation continuous operation with ionisation intermittent

More information

Room air quality sensors

Room air quality sensors 1 961 1961P01 QPA20 QPA20 D 1961P02 Room air quality sensors QPA20 Use With maintenance-free CO 2 sensing element based on optical infrared absorption measurement (NDIR 1) ) and depending on the type of

More information

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

YP7999A1000 ControLinks Fuel Air Ratio Control Panel YP7999A1000 ControLinks Fuel Air Ratio Control Panel FEATURES INSTALLATION INSTRUCTIONS Pre-wired and ready to install Includes the R7999A control, wiring subbase and S7999D1048 touchscreen display Commission,

More information

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit A Honeywell Company Gas Burner Safety Control For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit Possible flame detectors: - Ionisation probe - Infrared flicker

More information

Flame detector FD 2011 / FD 2012

Flame detector FD 2011 / FD 2012 only for existing plants EN 298 / EN 230 2003 19 PCB 3HE / 6TE DIN 41612 2-chanal system continuous operation ionisation with common or separate spark and supervision electrode intermitted UV-mode integrated

More information