SDG&E Feeder Protection Philosophy:

Size: px
Start display at page:

Download "SDG&E Feeder Protection Philosophy:"

Transcription

1 SDG&E Feeder Protection Philosophy: Reliability Without Compromising Safety Karl Iliev System Protection and Control Engineering (SPACE) SDG&E 1

2 SDG&E Distribution System 22,000 miles of lines 60% underground and 40% overhead Reactively Grounded Three wire (Grounded) and Four wire systems Nominally 12kV and 4kV Distribution >160 distribution substations >700 medium power transformers (138/12kV & 69/12kV) 2

3 Traditional Distribution Circuit (Simplified) R Tie SUBSTATION

4 Distribution Circuit of Today (Simplified) R IR R IR R F6 SUBSTATION R AE R IR PME 10 F6 R IR R F6

5 Distribution Circuit of Today (Simplified) PV LINE MONITOR RECLOSER RECLOSER Zone 3 Zone 2 TRAYER Vz N.O. Vy Vy Vz VOLTAGE REG Zone 1 Vv IR Zone 4 CB SUBSTATON 5

6 System Protection is a Balancing Act SPEED SENSITIVITY SELECTIVITY SECURITY SIMPLICITY FAST TO MINIMIZE DAMAGE RELAY SEES FAULT REMOVE FAULTED ELEMENT ONLY DO NOT TRIP FALSELY SIMPLE CONTROL SCHEMES

7 Protection Philosophy: Non traditional layers of protection: FCP Falling Conductor Protection detects break in conductor Speed Trips before the fault Coordination FCP should be first SGF Sensitive Ground Fault detects high impedance ground fault Slow 3.5 to 5.5 seconds Coordination between devices is unlikely Could Trip on Load Advanced SGF More sensitive than SGF using adaptive set point, spike counting, and/or harmonics (Cooper DCD, SEL ArcSense, or IR algorithm) Slower > 5 seconds Coordination between devices is unlikely Could Trip on Load and external faults or other system conditions Operational Changes: Reclosing Policy Changes (Disable reclosing during elevated fire risk) Eliminate Fuse Saving Schemes Pulse Closing Devices HLT Hot Line Tag allows fast trip, does not protect from contact Profile 3 Fast and Sensitive for safety during high risk fire conditions Fast cycles Coordination between devices is unlikely

8 Falling Conductor Protection (FCP) Phase Angle Comparison Requires PMUs and high speed communication Detection Methods dv/dt (change Detection) V0 & V2 magnitude V0 & V2 angle Synchrophasor Data Visualization Source Source 2 1 PMU1 PMU2 PMU3 PMU4 FC 1 not aligned with the other PMUs Source Source PMU1 PMU2 PMU3 PMU4 1 and 2 aligned with each other 3 and 4 aligned with each other FC Sequence Components Analysis 8

9 High Impedance Faults Random and Dynamic Requires Advanced Strategies because they are NOT like conventional (3P, PP and LG) faults. High Impedence Faults can be exhibit near zero fault current. We typically see 5 50 amp events

10 Sensitive Ground Fault (SGF): T SGF Element GROUND Similar to conventional ground protection element but is set more sensitively with a longer time delay to detect high impedance faults. The setting is fixed and typically 5 30A higher than neutral current trending on PI seen by the recloser for one year. Challenge is distinguishing Low Current Faults vs Load Imbalance I

11 SGF Pickup Setting vs. Neutral Load Current Neutral: 0 25 A

12 High Impedance Faults Cannot detect ½ cycle spiking with conventional SGF definite time elements.

13 Advanced SGF Introduces innovative logic to increase sensitivity Spike detection and accumulator algorithms to address both random, intermittent spiking and sustained low level ground faults Adaptive set point control to continuously adjust the spike pick up setting based on average neutral current loading Harmonic spike detector for arcing faults Optimizes sensitivity across the load range Reduces the need for field setting revisions due to system changes Each vender has different technology and algorithms

14 Advanced SGF Cooper DCD

15 Advanced SGF Intelliruptor Fault Starts - 01:54:05 (0 sec) Final Reset - 01:54:46 (40 sec) Trip - 01:55:27 (82 sec) seconds si nce begi nni ng of event

16 Ground Spike Duration IR Data Fault Starts - 01:54:05 (0 sec) Final Reset - 01:54:46 (40 sec) Trip - 01:55:27 (82 sec) # of pickup events < to < to < to < to < to < # Spikes & Duration, sec (Max = 6.9 sec) Avg Drop Out = sec

17 Advanced SGF SEL ArcSense Complex algorithms independent of neutral current Uses SDI (sum of difference current) calculations of odd harmonics between each successive cycle. Uses adaptive learning of circuit history and trending to fine tune sensitivity.

18 Profile 3/Hot Line Tag (HLT) Time Profile 3 PHASE GROUND Profile 1 Current

19 Intellirupter (IR) PulseClosing SDG&E Implemented to increase SCADA penetration in backcountry Multiple IRs on Circuits Unique PulseClosing Technology Confirms there s no fault on the line before initiating point on wave closing Reduction in fire risk due to reduced arcing produced Conventional reclose results in 170ms of fault current Pulseclose results in only 5ms of fault current 19

20 Protection Philosophy: Continuous Improvement Undesirable Feeder Operations (UFO) Cross departmental team to investigate UFOs with a charter to review outages where the unexpected protection device or more than on device, isolates the circuit fault. Essential to understand impacts caused by the ever increasing feeder complexity. Increases awareness and improve operating procedures. Balances risk, reliability, and cost

21 Undesirable Feeder Operation (UFO) Team Year Investigated UFOs UFO % of Total Completed UFO Initiatives Include: Expand high impendence fault detection (Advanced SGF) through various vender technology (e.g. SEL, S&C, Cooper) Enable Autosectionalizing switch positions that were previously disabled Reprogram of all Trayer Switches for better protection coordination (Trayer Switches were operating faster than expected, not allowing time for fuses to operate) Redefined Fuse Sizing Criteria to determine fuse sizes based on historical load as opposed to connected KVA 21

22 Multiple Adjacent Recloser Staggering (MARS): SGF settings currently set with 5 sec delay. Poses issues when multiple reclosers in series. Settings to be staggered by 0.5 sec. R1 R2 R3 SGF Time Delay: 5.5s SGF Time Delay: 5.0s SGF Time Delay: 4.5s SGF Time Delay: 4.0s

23 Example #1: Profile 3 Success UFO: Yesterday we had an outage with no cause determined. Today, we had another outage, currently patrolling again. Same devices tripped with profile 3 enabled. Outage Cause: Broken strand of AWAC Isolation Devices: R1 & R2 Investigation: Both R1 and R2 tripped and saw targets on A & B. Both devices were set to profile 3 and the fault current for A & B was greater than 400A UFO: No 12kV Sub R1 R2 2 65A 2 25A

24 Example #1: Profile 3 Success

25 Example #2: Profile 3 Frustration UFO: SCADA Device tripped on unbalance. Grid reports TL tripped open at same time. Full patrol will have to wait for daylight. Outage Cause: Phase Ground Fault on 69kV System Isolation Devices: R1 & R2 Investigation: Both R1 and R2 tripped on unbalance UFO: Yes 69/12kV Sub R1 R2

26 Example #2: Profile 3 Frustration 26

27 Example #3: Advanced SGF Frustration Investigation: Feeder tripped via electromechanical relays and locked out (went through it s full reclosing cycle). At the same time, neighboring circuits saw outages: R1 and R2 tripped and locked out on Advanced SGF targets due to bus voltage fluctuations. These reclosers were downstream of the fault. The cause of the outage was bad tees in a man hole, which all three circuits share in common. Reclosers tripped on DCD (fundamental frequency and THD). Outage Cause: Bad Tees Isolation Devices: Feeder CB, R1, R2 UFO: Yes R1 Sub MH R2

28 Example #3: Advanced SGF Frustration Fault location R2 R1 Cir1: 9.1% OH / 89.9% UG Cir2: 22.3% OH / 77.7% UG Cir3: 40.0% OH / 60% UG

29 Example #3: Advanced SGF Frustration

30 Example #3: Advanced SGF Frustration

31 Example #3: Advanced SGF Frustration

32 Example #3: Advanced SGF Frustration

33 Example #4: Falling Conductor Protection Investigation: FCP trip occurred. It was raining at the time and this is suspected to be related. ETS patrolled and no damage was found. Comm was noticed to be going in and out. There were data gaps but not during the event. The cause appears to be a faulty voltage sensor that reported a sharp change in voltage. Outage Cause: FCP Trip on V0 Faulted Sensor Isolation Devices: CB, R1 Follow Up: Short term solution is to raise the voltage threshold(s) in the field. Long term we will need to get a better sensor. UFO: Yes

34 Example #4: Falling Conductor Protection PV LINE MONITOR RECLOSER RECLOSER Zone 3 Zone 2 TRAYER Vz N.O. Vy Vy Vz VOLTAGE REG Zone 1 Vv IR Zone 4 CB SUBSTATON 34

35 Example #4: Falling Conductor Protection No high current change fluctuation was detected at any of the SCADA devices that could have caused the sudden drop in voltage on B phase

36 Example #4: Falling Conductor Protection Voltage differences between line and load sensors for reclosers, including a drop on B phase on the z side of R

37 Example #4: Falling Conductor Protection The drop in the voltage on B phase at recloser 1 caused the zero sequence voltage to trip above the pickup value of 400V

38 Example #4: Falling Conductor Protection Voltage on multiple MVRs in area show similar issues during rain.

39 Elimination of ALL risk is impossible Selectivity Security Adv.SGF Multiple SRs AE FCP IT FLISR Speed Profile 3/HLT SGF TCC Sensitivity Simplicity 39

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

Microgrid Fault Protection Based on Symmetrical and Differential Current Components Microgrid Fault Protection Based on Symmetrical and Differential Current Components Prepared for Public Interest Energy Research California Energy Commission Prepared by Hassan Nikkhajoei and Robert H.

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

Distribution Control Center Operator Training

Distribution Control Center Operator Training Distribution Control Center Operator Training OnlineTraining 15-Hour Course COURSE I BASIC DISTRIBUTION 1. Introduction to Distribution Systems a. Terminology b. Basic electricity and Ohm s Law c. BES

More information

What Utility Analytics means to Exelon

What Utility Analytics means to Exelon What Utility Analytics means to Exelon Presented by Bart Enright IT Director Smart Grid Initiatives at ComEd Exelon s Analytic Journey Exelon Utilities Overview T&D Grids Data Visualization Data Analytics/Notifications

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

Transmission Line Protection End to End Testing

Transmission Line Protection End to End Testing Transmission Line Protection End to End Testing Hands on Relay School, March 15, 2018 Chris Gallacher Protection Engineer Greg Sharpes Senior Relay Technician Mark Babin Senior Relay Technician Presentation

More information

Electrical Energy department

Electrical Energy department Al-Balqa Applied University Power systems Protection course Dr Audih al-faoury Electrical Energy department 2018-2019 Department of Electrical Energy Engineering 1 Part 1 Power System protection Introduction

More information

SENTINEL D - Fault Passage Monitoring

SENTINEL D - Fault Passage Monitoring SENTINEL D - Fault Passage Monitoring DIRECTIONAL FAULT PASSAGE INDICATORS FOR OVERHEAD MV NETWORKS Installed on poles of overhead lines, the Overhead-Sentinel-D range allows locating the fault arisen

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers on September 6, 2011. Officer approval of this revision is not required. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Utility with

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

AQ 100 Series. Arc Flash Protection System

AQ 100 Series. Arc Flash Protection System AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts

More information

SENTINEL A - Fault Passage Indicator

SENTINEL A - Fault Passage Indicator SENTINEL A - Fault Passage Indicator AMPEREMETRIC FAULT PASSAGE INDICATORS FOR OVERHEAD MV NETWORKS Installed on poles of overhead lines, the Overhead-Sentinel-A range allows locating the fault arisen

More information

Major Fault Caused by Stator Winding Circuit Ring Failure

Major Fault Caused by Stator Winding Circuit Ring Failure Case study Major Fault Caused by Stator Winding Circuit Ring Failure Joël Pedneault-Desroches, P. Eng. Presentation Outline Introduction Inspection report Chronology of events Repair Conclusion 2 Introduction

More information

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc flash detection units. Product picture Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize

More information

Communications Point Data Base for Communications Protocol IEC

Communications Point Data Base for Communications Protocol IEC Switchgear Technical Data TD280017EN Effective July 2015 Supersedes R280-90-36 8/2012 Communications Point Data Base for Communications Protocol IEC60870-5 For use with Eaton s Cooper Power series Form

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 INTRODUCTION Thank you for purchasing the Hokkim Integrated Automatic Mains Failure Control Board model HAMF- 8 or HAMF-4. We shall

More information

Fault Indicators for the Safe, Reliable, and Economical Operation of Modern Power Systems

Fault Indicators for the Safe, Reliable, and Economical Operation of Modern Power Systems Fault Indicators for the Safe, Reliable, and Economical Operation of Modern Power Systems 2010 Schweitzer Engineering Laboratories, Inc. All rights reserved Table of Contents Fault Indicators for the Safe,

More information

PGR-8800 TECHNICAL FAQ

PGR-8800 TECHNICAL FAQ PGR-8800 SOLAR ARC-FLASH PRODUCTS RELAY CATALOG TECHNICAL FAQ What are the typical applications / system voltages? The PGR-8800 can be used on electrical systems operating at any voltage (AC or DC) since

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers with final approval by an officer of Oncor Electric Delivery on. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Customer with the Company

More information

CIRCUIT BREAKER FAIL PROTECTION

CIRCUIT BREAKER FAIL PROTECTION CIRCUIT BREAKER FAIL PROTECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any losses

More information

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits Arc Protection 01 VAmP 120 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during

More information

Lecture 4 Power System Protection. Course map

Lecture 4 Power System Protection. Course map Lecture 4 Power System Protection 1 Course map 2 1 Outline of the Lecture Relays and IEDs Protection Principles Protection requirements Protection Schemes 3 What can we control? Breakers Valves Tap changers

More information

FCR 05, FCR 07. Power factor correction controller. User and service manual

FCR 05, FCR 07. Power factor correction controller. User and service manual FCR 05, FCR 07 Power factor correction controller User and service manual version 2.3 Czech Republic Czech Republic 1 Content 1. Control and signal elements... 3 2. Device description... 4 3. Instruction

More information

Palak Parikh, Lalit Lopez GE Digital Energy. Acknowledgment: Scottish and Southern Energy(SSE)

Palak Parikh, Lalit Lopez GE Digital Energy. Acknowledgment: Scottish and Southern Energy(SSE) Palak Parikh, Lalit Lopez GE Digital Energy Acknowledgment: Scottish and Southern Energy(SSE) Outline Why LV network monitoring? Challenges and Opportunities LV Monitoring Node Architecture Advance LV

More information

TELECOMMUNICATION EQUIPMENT LOCATED IN THE VICINITY OF PROPOSED DISTRIBUTION HV EARTHS

TELECOMMUNICATION EQUIPMENT LOCATED IN THE VICINITY OF PROPOSED DISTRIBUTION HV EARTHS Network Asset Technical Document TELECOMMUNICATION EQUIPMENT LOCATED IN THE VICINITY OF PROPOSED DISTRIBUTION HV EARTHS Original Issue: August 2006 Prepared by: M. Lamparski This Revision: Rev 1 October

More information

Three Terminal 230kV System Protection and Restoration at Calpine s Creed and Goose Haven Energy Centers Suisun City, California

Three Terminal 230kV System Protection and Restoration at Calpine s Creed and Goose Haven Energy Centers Suisun City, California Three Terminal 230kV System Protection and Restoration at Calpine s Creed and Goose Haven Energy Centers Suisun City, California Larry Henriksen POWER Engineers, Inc. Hailey, Idaho Daren Phelps Calpine

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

Table of Contents. Protective Relays

Table of Contents. Protective Relays Table of Contents KILOVAC WD Series, DIN Rail or Screw Mounted Introduction..........................................................11-2 KILOVAC WD25 Paralleling Relays........................................11-3

More information

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits 01 VAMP 120 & 121 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during work

More information

Root Cause Analysis Report Tesoro Golden Eagle Refinery Refinery Power Outage

Root Cause Analysis Report Tesoro Golden Eagle Refinery Refinery Power Outage Summary of Event: The Golden Eagle Refinery (Refinery) experienced a partial electrical outage December 10, 2010 at 10:12 hrs when a transformer at Switching Station #7 failed. A CWS Level 1 report was

More information

Moulded case circuit brakers

Moulded case circuit brakers Moulded case circuit brakers CONTENT Range 1 Protection Releases 2 Salient Features 5 Accessories 7 Widest Range 10 Time Current Characteristics 12 Overall Dimensions 14 SN4 SN3 SN2 SN1 3 RANGE SN1 Rated

More information

Synchrophasor Technology in Control Centers Clemson University, SC March 12, 2014 Vikram S. Budhraja

Synchrophasor Technology in Control Centers Clemson University, SC March 12, 2014 Vikram S. Budhraja Clemson University Power Systems Conference Synchrophasor Technology in Control Centers Clemson University, SC March 12, 2014 Vikram S. Budhraja Outline Synchrophasor Technology Infrastructure Lessons

More information

To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations

To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations AGENDA ITEM NO.: 5.D.1 MEETING DATE: 0/4/014 ADMINISTRATIVE REPORT NO.: 014-48 To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations From: Tito R. Nagrampa

More information

APPLICATION NOTE. Applying pressure sensing in arc flash protection applications with air magnetic circuit breakers

APPLICATION NOTE. Applying pressure sensing in arc flash protection applications with air magnetic circuit breakers APPLICATION NOTE Applying pressure sensing in arc flash protection applications with air magnetic circuit breakers Application note Applying pressure sensing in arc flash protection 2 (6) Revision 1.0

More information

Event Detection System (EDS)

Event Detection System (EDS) WaveGrid Event Detection System (EDS) Installation, Operations and Maintenance Guide Control Module Revision 6.0 June 24 th, 2016 Sensor Module I Functional Description The Event Detection System (EDS)

More information

End To End Optical Beam Smoke Detector. Additional Information

End To End Optical Beam Smoke Detector. Additional Information End To End Optical Beam Smoke Detector Additional Information EN 1. Multiple Zone Wiring When using more than one System Controller on a single zone of a conventional Fire Control Panel (FCP), it is important

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

NextGen SCADA Europe 2013

NextGen SCADA Europe 2013 NextGen SCADA Europe 2013 Thursday 21st & Friday 22nd March 2013 Holiday Inn Amsterdam, Netherlands Brian Tapley Manager, HV Operations, North Distribution Control Centre, Ireland 1 Presentation Overview

More information

Standard PRC Transmission Relay Loadability

Standard PRC Transmission Relay Loadability A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-2 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability

More information

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS. CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS Table of Contents 2.A.1 SCADA Standards 2.5-2 2.A.1.1 Generators 2.5-2 2.A.1.2 Building

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

Description (Data Point Name) Unit Size

Description (Data Point Name) Unit Size AC-PRO-II Communications Modbus Register Map Document Revision 2.0 Firmware v2.0 AC-PRO-II: Registers 7000 7019: Output Coils 7020 7099: Information 7107 7199: User settings (can be set using Modbus Communications)

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

MAINTENANCE OF LV SWITCHGEAR SECTOR / ENGINEERING TECHNICAL & CERTIFIED TRAINING COURSE

MAINTENANCE OF LV SWITCHGEAR SECTOR / ENGINEERING TECHNICAL & CERTIFIED TRAINING COURSE SECTOR / ENGINEERING TECHNICAL & CERTIFIED TRAINING COURSE Switchgear is a general term used for any devices that breaks and makes the electrical circuit and covers right from a typical piano switch used

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

2000 Series. Program Entry Guide. Control Panels

2000 Series. Program Entry Guide. Control Panels 2000 Series EN Program Entry Guide Control Panels 2000 Series Program Entry Guide About This Manual EN 2 About This Manual This guide describes the programming parameters available to the 2000 Series Control

More information

CONTACTORS FOR AEROSPACE GROW SMARTER AND MORE CAPABLE

CONTACTORS FOR AEROSPACE GROW SMARTER AND MORE CAPABLE CONTACTORS FOR AEROSPACE GROW SMARTER AND MORE CAPABLE Karl Kitts, Director of Development Engineering for High Performance Relays AEROSPACE, DEFENSE & MARINE /// WHITE PAPER - CONTACTORS FOR AEROSPACE

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC Changes to NFPA 70E - The Role of PdM &Safe PdM Work Practices Tim Rohrer Exiscan LLC Tim@Exiscan.com 585-705-7775 Joe Gierlach ABM Joseph.Gierlach@ABM.com 412-394-4678 Preview Electrical Safety Risk Management

More information

Power System Protection Part 2 Dr.Prof. Mohammed Tawfeeq. Zones of Protection

Power System Protection Part 2 Dr.Prof. Mohammed Tawfeeq. Zones of Protection 84 Power System protection Dr. Mohamad Tawfeeq Zones of protection Zone of protection of a relay is the place or the distance that the relay can protect easily.fig.1 shows an example of protection zones

More information

National Grid / DG Installation Process Guide per NY SIR / July 2011 ver. 1.0

National Grid / DG Installation Process Guide per NY SIR / July 2011 ver. 1.0 Distributed Generation Installation Process Guide for Connections to National Grid Distribution Facilities per the New York Standardized Interconnection Requirements Introduction National Grid ( The Company

More information

Electric Power Group Presents. Welcome!

Electric Power Group Presents. Welcome! Electric Power Group Presents Maximizing Use of Synchrophasor Technology for Everyday Tasks Welcome! The meeting will begin at 2:00 p.m. ET / 11:00 a.m. PT Jan. 18, 2017 Today s Topic: Synchrophasor Intelligence

More information

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD.

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD. BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY RETROFIT KITS BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD. BE1-50/51B, CO Retrofits BE1-50/51B,

More information

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning

More information

Development of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1

Development of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1 Development of standards for MV Switchgear for Arc Flash protection May 20, 2013 Slide 1 Development of standards for MV Switchgear for Arc Flash protection Bryan Johnson ABB South Africa Shaping the world

More information

Ground Fault Protection Improvement Study

Ground Fault Protection Improvement Study Ground Fault Protection Improvement Study Greg Ball DNV KEMA Solar ABCs Stakeholder Meeting July 11, 2013 San Francisco, CA Study Authors 2 Bill Brooks Brooks Engineering Andy Rosenthal New Mexico State

More information

Surface Acoustic Wave Technology based Temperature Monitoring of High Voltage and High Current Switchgear Boxes

Surface Acoustic Wave Technology based Temperature Monitoring of High Voltage and High Current Switchgear Boxes Surface Acoustic Wave Technology based Temperature Monitoring of High Voltage and High Current Switchgear Boxes Summary Safety is a big concern when it comes to managing power distribution systems. High

More information

Detailed Instructions

Detailed Instructions Introduction Timer is a versatile, rugged, and easy to use indoor / outdoor appliance timer. It can be used with lights and other household appliances that require regular on-off cycles and has two main

More information

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC NFPA 70E Arc Flash Considerations for MV Equipment By: Dominik Pieniazek, P.E. dominik@hv-eng.com HV Engineering, LLC http://sites.ieee.org/houston/ Full link for PDF copies of presentations: http://sites.ieee.org/houston/communities/ie

More information

Oven Control System Operation - Ver 2.8

Oven Control System Operation - Ver 2.8 Version 2.8 - Pg:1 - Ver 2.8 This operation manual contains important information about your oven. All operators should review this manual before operating the oven. When you turn on the switch, the control

More information

Solid State Relays SOLITRON MIDI Current Sensing Type RJCS, RJCSR

Solid State Relays SOLITRON MIDI Current Sensing Type RJCS, RJCSR Solid State Relays SOLITRON MIDI Current Sensing Type, R AC semiconductor contactor Integrated current monitoring Zero switching (1A) Direct copper bonding (DCB) technology LED-indication Cage clamp output

More information

THERMAL DIAGNOSIS OF MV SWITCHBOARDS: A COST-EFFECTIVE, DEPENDABLE SOLUTION BASED ON AN OPTICAL SENSOR

THERMAL DIAGNOSIS OF MV SWITCHBOARDS: A COST-EFFECTIVE, DEPENDABLE SOLUTION BASED ON AN OPTICAL SENSOR THERMAL DIAGNOSIS OF MV SWITCHBOARDS: A COST-EFFECTIVE, DEPENDABLE SOLUTION BASED ON AN OPTICAL SENSOR Christian PETIT Anticipation manager Schneider Electric - Network protection and control unit -Marketing

More information

Relay Performance Index for a Sustainable Relay Replacement Program

Relay Performance Index for a Sustainable Relay Replacement Program Relay Performance Index for a Sustainable Relay Replacement Program Aaron Feathers, Abesh Mubaraki, Nai Paz, Anna Nungo Pacific Gas & Electric Company San Francisco, CA Western Protective Relay Conference

More information

Guide to Transmission Equipment Maintenance

Guide to Transmission Equipment Maintenance Guide to Transmission Equipment Maintenance March 2018 Revision History Issue Date Update 1 September 2013 First Issue 2 March 2016 Updated in response to SEM-15-071 Decision Paper Outturn Availability.

More information

Operation and use. Functions and characteristics

Operation and use. Functions and characteristics Operation and use Function Vigirex relays measure the earth-leakage current in an electrical installation via their associated toroids. Vigirex relays may be used for: b residual-current protection (RH10,

More information

EUROBOX SERIES TYPES CM... SM... MM...

EUROBOX SERIES TYPES CM... SM... MM... EUROBOX SERIES TYPES CM... SM... MM... AUTOMATIC GAS BURNER CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN Application This range of electronic gas burner control systems

More information

PowerLogic ION Setup Meter Configuration Software Configuration Guide

PowerLogic ION Setup Meter Configuration Software Configuration Guide PowerLogic ION Setup Meter Configuration Software Configuration Guide 70002-0293-03 12/2010 Conventions Used in this Manual This section describes the symbols and terminology used in this guide. Symbols

More information

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS: RESIDUAL CURRENT DEVICES

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS: RESIDUAL CURRENT DEVICES INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS: RESIDUAL CURRENT DEVICES [The basis of this article was first published in Wiring Matters in issue 15, Summer 2005 and reflected the requirements of

More information

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology Warehouse Protection of Exposed Expanded Group-A Plastics with Sprinkler Technology Zachary L. Magnone, Jeremiah Crocker, Pedriant Peña Tyco Fire Protection Products, Cranston, RI, USA Abstract The focus

More information

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards v2-5058-co900h Copyright 2016 Rockwell Automation, Inc. All Rights Reserved. 1 Agenda 1. Background 2. Related Electrical

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

Lago SD3. Differential Controller with Speed Control. Operating and Installation Instructions

Lago SD3. Differential Controller with Speed Control. Operating and Installation Instructions Lago SD3 Differential Controller with Speed Control Operating and Installation Instructions Please observe the safety instructions and read through this manual carefully before commissioning the equipment.

More information

Flostop TS D7E and A8E. Operation Manual

Flostop TS D7E and A8E. Operation Manual Flostop TS D7E and A8E Operation Manual United Kingdom Spectron Gas Control Systems Ltd, Unit 4, ATU1, University of Warwick science Park, Coventry, +44 (0) 24 7641 6234 sales@spectron-gcs.com Germany

More information

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs)

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs) MRS752348-MUM Issued: 0/997 Version: F/23.6.2005 Data subject to change without notice COCB_ Circuit Breaker (2 state inputs/ 2 control inputs) Contents. Introduction... 3. Features... 3.2 Application...

More information

Ground Fault Protection Improvements to Prevent Fires Description of problem and potential solutions Presented by Bill Brooks, PE Principal, Brooks

Ground Fault Protection Improvements to Prevent Fires Description of problem and potential solutions Presented by Bill Brooks, PE Principal, Brooks Ground Fault Protection Improvements to Prevent Fires Description of problem and potential solutions Presented by Bill Brooks, PE Principal, Brooks Engineering Code Official Panel Lead, SolarABCs 1 Ground-Fault

More information

M O T I O N DETECTORS. The Paradox series of motion detectors. combines advanced features and patented. technologies to provide a high level of

M O T I O N DETECTORS. The Paradox series of motion detectors. combines advanced features and patented. technologies to provide a high level of M O T I O N DETECTORS The Paradox series of motion detectors combines advanced features and patented technologies to provide a high level of detection and false alarm prevention. Whatever the application,

More information

FACILITY CONNECTION STANDARD

FACILITY CONNECTION STANDARD FACILITY CONNECTION STANDARD Preface: This Facility Connection Standard applies to any connection to the electric system of Westar Energy, Inc. or Kansas Gas and Electric Company, both doing business as

More information

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators GPS 140 NEC Requirements for Generators WHAT YOU WILL LEARN NEC requirements for on-site power generation. Recent events have created increased interest in standby power This module organizes NEC requirements

More information

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7 Practical Power System Protection for Engineers and Technicians Contents Preface ix Chapter 1 Need for protection 1 1.1 Need for protective apparatus 1 1.2 Basic requirements of protection 2 1.3 Basic

More information

Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards

Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards LIN ZHOU M Eng, MIEAust RIZNER Australia YANG YIJUN B. Eng, Senior Engineer State Grid, Zhejiang

More information

Total Connect Box. User manual

Total Connect Box. User manual Total Connect Box User manual 1 Congratulations on your purchase of the Honeywell Total Connect Box security system. To make the best out of your system we advise you to read this manual carefully. This

More information

DKG-108 POWER FACTOR CONTROLLER

DKG-108 POWER FACTOR CONTROLLER DKG-108 POWER FACTOR CONTROLLER 8 BANKS, HARMONIC DISTORTION DISPLAY FEATURES Small size Cost effective and high performance True RMS AC measurements,high accuracy 4096 samples/sec measurement rate Easy

More information

5. CBS Alarms Responding to a CBS Alarm Understanding the Alarm Condition A-CBS-008 Circuit Breaker Sentinel Page 109 of 156

5. CBS Alarms Responding to a CBS Alarm Understanding the Alarm Condition A-CBS-008 Circuit Breaker Sentinel Page 109 of 156 Page 109 of 156 5. CBS Alarms 5.1. Responding to a CBS Alarm The CBS uses its alarm contacts to signal the presence of alarm conditions. There are two alarm relays:one for Caution alarms and one for Problem

More information

NFPA Edition Review

NFPA Edition Review This is a photographic template your photograph should fit precisely within this rectangle. NFPA 70 & 99 How Recent Code Changes Effect Healthcare Facilities Sam C. Terry, P.E. Application Engineer Eaton

More information

Division 26 ELECTRICAL TABLE OF CONTENTS

Division 26 ELECTRICAL TABLE OF CONTENTS Division 26 ELECTRICAL TABLE OF CONTENTS 26 1000 GENERAL... 33 A. CODE... 3 B. RELATED SECTIONS... 3 C. ABBREVIATIONS... 3 D. DEFINITIONS... 3 E. DRAWING REQUIREMENTS... 3 F. EQUIPMENT SERVICE ACCESS AND

More information

38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION

38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION 38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION This specification is property of SEC and subject to change or modification without any notice. TABLE OF CONTENTS

More information

Results of Recent DOE Research on Development of Cable Condition Monitoring and Aging Management Technologies

Results of Recent DOE Research on Development of Cable Condition Monitoring and Aging Management Technologies Results of Recent DOE Research on Development of Cable Condition Monitoring and Aging Management Technologies C.J. Campbell, J.B. McConkey, H.M. Hashemian, C.D. Sexton, D.S. Cummins Analysis and Measurement

More information

Continuous, real-time detection, alarming and analysis of partial discharge events

Continuous, real-time detection, alarming and analysis of partial discharge events DMS PDMG-R Partial discharge monitor for EHV GIS Continuous, real-time detection, alarming and analysis of partial discharge events Automatic PD fault classification Robust design allows for reliable operation

More information

M2000 Engine Controller

M2000 Engine Controller M2000 Engine Controller Integrated control and protection of diesel and gas engines for all purposes Especially suited for auxiliary generator sets 1 IN OPERATION 1 2 STARTFAIL 2 3 OVERSPEED RPM FAIL 3

More information

Energy Saving Drives for Hot Strip Mills

Energy Saving Drives for Hot Strip Mills Energy Saving Drives for Hot Strip Mills Ralph PUGH TMEIC 060 Cook Drive Salem, VA 4153, USA Tel: 540-83-158 Fax: 540-83-395 E-mail: ralph.pugh@tmeic.com Serkay ÖZALICI TOSÇELIK Osmaniye OSB Turkey Tel:

More information

LineVision TM. Non-Contact Transmission Line Monitoring and Dynamic Line Rating

LineVision TM. Non-Contact Transmission Line Monitoring and Dynamic Line Rating LineVision TM Non-Contact Transmission Line Monitoring and Dynamic Line Rating Jonathan Marmillo, Business Development M: 484-368-4630 E: jmarmillo@genscape.com www.genscape.com 2017 Genscape Incorporated.

More information

I/O ZONE 560/583 AND OPERATION MANUAL

I/O ZONE 560/583 AND OPERATION MANUAL UPM I I/O ZONE 560/583 INSTALLATION AND OPERATION MANUAL 1 UNIT PROTECTION MODULE HARDWARE OPERATION IMPORTANT: This manual is for UPM board part numbers 8733 800 259. See controller label as shown in

More information

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24.. Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24.. Soft starting of 1-Phase Scroll Compressors Enclosed solution Integrated current limit Rated operational voltage: 230 VACrms,

More information

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification Dual Technology Wall Switch Occupancy Sensor Manual & Specification PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL ELECTRICAL CODES Douglas Lighting Controls Page 1 November 19, 2014 1. INTRODUCTION

More information