MWL Consulting Company

Size: px
Start display at page:

Download "MWL Consulting Company"

Transcription

1 MWL Consulting Company NFPA Member since1990 Fire Service Section Fire Marshal (retired) Newport Fire Department Michael W. Leber 17 Whitwell Avenue Newport, RI Mobile Phone February 24, 2017 Prepared for: Steve Kirby Kirby Commercial Newport, RI Property Location: 11 Bowler Lane Newport, RI 02840

2 Building Summary 11 Bowler Lane is composed of two buildings with a common wall and roof. The larger section is a two-story wood-frame commercial mixed use building built in the early 1900 s. The two buildings are joined and may not be treated separately for fire code purposes. The left (west) structure, as you face it is a brick clad one story office building having around 1370 sq. ft. of office space. The right (east) part of the complex is the two-story wood-frame structure having some heavy timber elements and covering approximately 3500 sq. ft. per level with an additional attached single level garage on the east end having nearly 420 square feet. The roofs of both sections are wood-framed with an asphalt shingle finish. The brick faced section s roof leads continuously up on a pitch up to the peak of the first of two gable roofs over the wood-frame (east) section. There is a concrete block wall between the east and west section that, while providing some fire separation, is not complete enough to claim a rated fire separation. Further, the sections have a common wood roof noted above. There is no space below grade in either section that was observed. Because the sections discussed are not separated and there is no fire separation between any of the various occupied areas of the whole complex it must be treated as a mixed occupancy. This means that the inspector will compare the various occupancy chapters of the fire code that apply and is required to use the most stringent of each chapter and apply that to the entire complex. In this case we are looking at business, storage and industrial occupancies sharing space in this complex. The brick building is ground level only and is office (business) space. The larger two story section to the east has storage areas and light industrial/storage areas. The storage is extensive and dense in areas and is comprised mostly of ordinary combustibles. There is some vehicle and equipment storage along with a wide range of items in the three garage areas on the first level. The rest of the first floor contains more ordinary storage and a workshop at the end of the first floor corridor (approximately 550 square feet). Access to the second floor is by way of an open wooden stair in the central corridor. Almost the entire second floor is occupied by rental spaces used for crafts/artisans of various kinds sail maker-marine craft-photographers-interior decorator-pottery-crafts/storage. These spaces represent the industrial aspect of the occupancy that is more accurately described by the building code as a Factory Industrial F-1 Moderate-Hazard Occupancy that assembles, fabricates, finishes, and repairs etc. materials including: photo equipment, canvas or similar fabric, carpets, clothing etc. There is an additional uncovered exterior stair leading from the pottery space on the NE exterior of the building. It is my understanding that the rest of the occupancies do not have access to this egress because as a private space it is locked when not in use--fire code subclass of industrial occupancy is general industrial occupancy This building is going to be reviewed now under the existing business chapter as it is the most stringent of the three occupancies described. If there is a change of use of the property in the future it will be reviewed by an inspector under the new occupancy chapter. For example, if you made a residential space(s) in place of the existing uses it would require a review under the new (and stricter) chapter of the code. 2

3 Fire Code Survey The building in this report was reviewed for compliance under the RI Fire Safety Code 2012 edition: FIRE SAFETY CODE SECTIONS 7 AND 8 OF THE RHODE ISLAND LIFE SAFETY CODE 11 Bowler Lane Newport, RI Section 7 RI Uniform Fire Code 11.1 Electrical Fire Safety All electrical appliances, fixtures, equipment, or wiring shall be installed and maintained in accordance with NFPA 70, National Electrical Code. General electrical safety issues such as covers where needed and storage around equipment. 3

4 Section 8 RI Life Safety Code Chapter 39 Existing Business (Business Occupancy. An occupancy used for the transaction of business other than mercantile.) Classification of Hazard of Contents. The contents of business occupancies shall be classified as ordinary hazard in accordance with Section 6.2. Ordinary hazard is what is typically found in contents of most occupancies Ordinary hazard would apply throughout. Storage in some areas is very dense with a considerable build up of combustibles. This shows a storage area 1 st floor with significant storage under unprotected wood floor/ceiling assembly 4

5 If flammable liquids are stored they need suitable storage cabinets. The presence of vehicles and some fuels does not warrant high hazard classification of contents per (Storage Occupancy) 39.2 Means of Egress Requirements In existing buildings, a door assembly at the top of a stair shall be permitted to open directly at a stair, provided that the door leaf does not swing over the stair and that the door opening serves an area with an occupant load of fewer than 50 persons. 5

6 Stair into storage 1 st floor 10.5 inch drop from corridor The hand rail sizing is fine (1 ¾ diameter) but the rail is too high (38 max.) and guards are not provided * Open guards, other than approved existing open guards, shall have intermediate rails or an ornamental pattern such that a sphere 4 in. (100 mm) in diameter is not able to pass through any opening up to a height of 34 in. (865 mm) This means that balusters are required along the length of the rails unless previously approved 6

7 Enclosure and Protection of Stairs Enclosures All inside stairs serving as an exit or exit component shall be enclosed in accordance with Where this Code requires an exit to be separated from other parts of the building, the separating construction shall meet the requirements of Section 8.2 and the following: (1)* The separation shall have a minimum 1-hour fire resistance rating where the exit connects three or fewer stories. The stairwell is required to be enclosed in a one hour fire separation. This includes walls, doors and hardware and providing a landing as required. The tread depth and riser height of the stairs are within the parameters for an existing stairwell but the open risers are not allowed (suggested in the fire code via and specified in the building code) The second floor has only this one egress accessible to all the occupants at all times. The exterior stair from the 2 nd floor NE is in a private (and presumably) locked space when not in use. To use the single-exit provision of 38/ , all five of the following criteria must be met: 1. Occupant load fewer than 100 persons 2. Direct exit to a street or to an open exterior area at ground level 3. Total distance of not more than 100 ft (30 m) from any point in the room to the exterior [note that this is total distance from any point to the exterior, not travel distance as measured in Section 7.6; therefore, total distance includes the distance traveled on enclosed stairs (exit)] 4. Stairs not more than 15 ft (4570 mm) in height 5. Stairs completely enclosed with no door openings between the stair enclosure and the rest of the building, or stairs meeting requirements applicable to outside stairs (see ) 7

8 Exit signage is required. (In the Storage Occupancy chapter emergency lighting is required) Marking of Means of Egress. Means of egress shall have signs in accordance with Section The existing stairwell is considered a vertical opening in the structure and it must be protected against travel of products of combustion. Where an unprotected vertical opening is allowed it cannot be used as part of a means of egress. Penetrations exist in the floor/ceiling between the 1 st and 2 nd floor provide appropriate barrier material Protection of Vertical Openings Vertical openings shall be enclosed or protected in accordance with Section 8.6 If in the judgment of the fire inspector the type of work being done or the hazard of the storage in a section of the building warrants it the space must be protected with a fire separation. If the hazard is deemed more significant the inspector can require fire separation and sprinkler protection for the space Protection from Hazards * General. Hazardous areas including, but not limited to, areas used for general storage, boiler or furnace rooms, and maintenance shops that include woodworking and painting areas shall be protected in accordance with Section Cooking Equipment. Cooking equipment shall be protected in accordance with 9.2.3, unless the cooking equipment is one of the following types: (1) Outdoor equipment (2) Portable equipment not flueconnected (3) Equipment used only for food warming The fire inspector will make a judgment as to the need for protection of any cooking space. This decision would determine the call for a commercial hood system and fire alarm connection 8

9 Interior Wall and Ceiling Finish Interior wall and ceiling finish materials complying with Section 10.2 shall be Class A or Class B in exits and in exit access corridors Interior wall and ceiling finishes shall be Class A, Class B, or Class C in areas other than those specified in Interior finish can be difficult to determine when the specific materials are not known. In this case the minimum rating allowed in exit access corridors is class B. The unfinished wood on the ceiling is probably not going to reach a class B rating as determined by the fire inspector. For example, the rating for untreated southern yellow pine is and for oak it is 100. Class B can be 75 maximum and Class C up to 200. It is possible that the other areas with unfinished will be allowed but the exit access areas require a finish that will achieve Class B status. (Storage requires Class C) (Amd) General A fire alarm system in accordance with Section 9.6 shall be provided in all business occupancies where any one of the following conditions exists: (1) The building is three or more stories in height. (2) The occupancy is subject to 50 or more occupants above or below the level of exit discharge (5,000 Square feet). A fire alarm is not required based on the area of the building not being 5000 square feet on a level above or below the level of exit discharge Extinguishment Requirements. Portable fire extinguishers shall be provided in every business occupancy in accordance with There are a number of extinguishers placed throughout the building. Placement should be reviewed and starting a regular inspection program would be appropriate. 9

10 Heating, Ventilating, and Air-Conditioning. Heating, ventilating, and air-conditioning equipment shall comply with the provisions of Section 9.2. Heat is provided in the individual rental spaces by means of natural gas-fired unit heaters and wall units. If installed and maintained properly there is no need for action with regard to them. The Skutt Kiln model KM-822 is a UL listed product that is safe if installed and used according to manufacturers specifications including: A. Install kiln in well-ventilated, sheltered area. Do not permit temperature to exceed 105 degrees F while kiln is in use. B. Provide a minimum of 18 inches between kiln and adjacent walls, other kilns, shelving, and other obstructions. When installing multiple kilns in the same room, ensure that the control boxes on the kilns are not facing adjacent kilns. 10

11 C. Locate kiln in a room or space with a bare concrete floor. If a bare concrete floor is not available provide a non-combustible substrate and two (2) inches of masonry below the kiln extending a minimum of 12 inches beyond the outside dimensions of the kiln Extinguisher Training. Designated employees of business occupancies shall be periodically instructed in the use of portable fire extinguishers. Provide extinguisher training. 11

12 Summary review These are the primary issues and comments in the survey From the survey General electrical safety issues such as covers where needed and storage around equipment. Ordinary content hazard would apply throughout. Storage is very dense in some locations with a considerable build up of combustibles. This shows a storage area 1 st floor with significant storage under unprotected wood floor ceiling assembly If flammable liquids are stored they need suitable storage cabinets. The presence of vehicles and some fuels does not warrant high hazard classification of contents per (Storage Occupancy) Stair into storage 1 st floor 10.5 inch drop from corridor The hand rail sizing is fine (1 ¾ diameter) but the rail is too high (38 max.) and guards are not provided. This means that balusters are required along the length of the rails unless previously approved by fire authority The stairwell is required to be enclosed in a one hour fire separation. This includes walls, doors and hardware and providing a landing as required. The existing stairwell is considered a vertical opening in the structure and it must be protected against travel of products of combustion. Where an unprotected vertical opening is allowed it cannot be used as part of a means of egress. Penetrations exist in the floor/ceiling between the 1 st and 2 nd floor provide appropriate barrier material. The tread depth and riser height of the stairs are within the parameters for an existing stairwell but the open risers are not allowed (suggested in the fire code via and specified in the building code) The second floor has only one egress accessible to all the occupants at all times. The exterior stair from the 2 nd floor NE is in a private (and presumably) locked space when not in use. Exit signage is required. (In the Storage Occupancy chapter emergency lighting is required) If in the judgment of the fire inspector the type of work being done or the hazard of the storage in a section of the building warrants it the space must be protected with a fire 12

13 separation. If the hazard is deemed more significant the inspector can require fire separation and sprinkler protection for the space. The fire inspector will make a judgment as to the need for protection of any cooking space. This decision would determine the call for a commercial hood system and fire alarm connection Interior finish can be difficult to determine when the specific materials are not known. In this case the minimum rating allowed in exit access corridors is class B. The unfinished wood on the ceiling is probably not going to reach a class B rating as determined by the fire inspector. For example, the rating for untreated southern yellow pine is and for oak it is 100. Class B can be 75 maximum and Class C up to 200. It is possible that the other areas with unfinished will be allowed but the exit access areas require a finish that will achieve Class B status. (Storage requires Class C) A fire alarm is required if the area of any level above or below exit discharge exceeds 5000 square feet in a business occupancy. In this case the 2 nd floor is approximately 3500 square feet and there is no space below ground level. There are a number of extinguishers placed throughout the building. Placement should be reviewed and set up a regular inspection program. Commentary The owner can anticipate that a full inspection of this building complex may result with a visit to the Fire Safety Board of Appeal and Review to allow a possible compromise on some issues. While being reviewed in this survey as a Business Occupancy we would expect some negotiation is in order given the size of the building and low occupant load. Also some attention must be noted regarding the fact that in practical terms the existing use of most of the space is storage or industrial. Further, there is a degree of separation between the brick faced section and the woodframe section that may be enhanced or even allowed as it stands as a form of separation in its current condition. Proposing to install a fire alarm system increases the chances for success before the Board if that is needed. Regarding the requirement for two exits from the second level when using the Industrial chapter the building comes very close to compliance if the existing open stairwell becomes part of a fire rated enclosure. The guards needed to improve the stairwell may not be necessary if the stair is enclosed (depending on the design used) and the open risers can be corrected at the same time. A fire alarm system in association with a fire sprinkler system would go a long way toward resolving almost any issues that the complex faces and certainly would be welcomed by the local fire inspector and the Board of Appeal and Review. There also should be some resulting benefit with the building insurance premiums. 13

14 It is common when hiring a fire alarm contractor that the bids include as a package the exit signage and emergency lighting and a Knox Box (locked entry keys for FD) when required with the fire alarm. If the fire inspector decides that areas of hazard need to be protected it could done on a case by case basis in the various rental spaces. If the subject of protecting the cooking area on the 2 nd floor arises then the equipment can simply be removed. Any interior finish deficiency should be able to be resolved with an intumescent paint that improves the surface interior finish rating. Selected Estimated Costs range Fire alarm There can be a wide range in what you can pay for a system that will be acceptable to the Fire Department. Factors influencing this can be the equipment manufacturer, degree of hiding the wiring (unless wireless is chosen) and the biggest difference will be the choice of contractor. $15,000 to $30,000 Stair enclosure $7,500 to $20,000 Intumescent paint and application in all bare wood areas (if needed) $5,000 to $10,000 14

15 7 Bowler Lane 7 Bowler Lane is a 750 sq. ft. footprint storage building without running water. Heat is provided by individual units within each area and not requiring protection. There is an open space on the second level used as office space. A fire inspector could require an exit sign on the 2 nd floor and emergency lighting in the storage area. 7 Bowler Lane used for storage with accessory office space on the second level Ordinary hazard contents The storage at ground level has side hinged swinging doors locked from the outside. Exterior stairs lead to the office space on the second level. 15

16 The threshold to the upstairs office space exceeds ½ inch. The door itself is 69 inches in height while 80 inches is required in a new door (see reference to allowing tread and riser sizing) The wooden stairs are inconsistent in sizing and shape and the handrails exceed size for diameter width. The exit discharge at base of stairs is uneven. A fire alarm is not required. * MWL Consulting is not responsible for compliance with any codes or other requirements. This survey cannot substitute for a full fire department review.* 16

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH January 3, 2014 Redpoint Jackets Ltd. PAGE 1 SUMMARY The four story factory housing Redpoint Jackets Ltd. located in Dhaka Export Processing

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT KAROONI KNIT COMPOSITE RATANPUR, SHAFIPUR KALIAKOIR OTHER FACTORIES: NONE April 5, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/5/2014 by Hughes Associates, Inc.

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT ALAUDDIN GARMENTS LTD. 88, KAZI NAZRUL ISLAM AVENUE, TAJGAON, DHAKA- 1215 OTHER FACTORIES: CAMBRIDGE GARMENTS, PRIMODIAL April 27, 2014 Page 2 SUMMARY was surveyed for fire

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT N.A GARMENTS PLOT # 36, ROAD # 46, GULSHAN NORTH C/A, DHAKA OTHER FACTORIES: SIDKO LIMITED, SIDKO APPARELS LIMITED, DELTA TIES LIMITED April 17, 2014 Page 2 SUMMARY was surveyed

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT A-PLUS IND LTD PLOT # 28, MILK VITA ROAD, SECTION #07, MIRPUR, DHAKA - 1216, BANGLADESH March 10, 2014 Page 2 SUMMARY was surveyed for fire safety on 3/10/2014 by Hughes Associates,

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT Page 1 FIRE SAFETY INSPECTION REPORT Impress Fashion Ltd. ACCORD ID: 12245 Dag No. 2224, Matuial, Konapara, Katherpool, Jatrabari, Dhaka-1362 Other Factories: None Date: August 27, 2015 Sl No. Category

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT HAN A HATS & CAPS LTD. ACCORD ID: 12339 DAG NO. CS &SA-115/117, RS-188/181, KHOTION NO. CS-128, SA-274, BAIPAIL, ASHULIA, SAVAR, DHAKA. OTHER FACTORIES: TEXTSTREAM FASHION

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MULTIFABS LTD KASHIMPUR, NAYAPARA Other Factories: ne April 9, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was surveyed for fire safety on

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAGPIE COMPOSITE TEXTILE LTD. 832/833, DEWAN IDRIS ROAD, AMTOLI, ASHULIA, SAVAR, DHAKA OTHER FACTORIES: NONE May 17, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/17/2014

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Letter of Recognition

Letter of Recognition Letter of Recognition The on Fire and Building Safety () hereby recognizes that: KARIM TEXTILES LIMITED (9297) orbag, Kaliakoir, Gazipur Has successfully completed all remediation measures required from

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT BEQ KNIT LTD. ZIRABO, ASHULIA, SAVAR, DHAKA Other Factories: Beq Sweaters Ltd., Tammam Design Ltd. April 22, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PADMA SWEATERS LTD. 1/B DARUS SALAM ROAD, SECTION 1. MIRPUR OTHER FACTORIES: NONE. July 9, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/9/2014 by Hughes Associates,

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT YOUNG INTERNATIONAL PLOT NO. 32-36, SECTOR 5-CEPZ, CHITTAGONG OTHER FACTORIES: NONE July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by Hughes Associates,

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PIMKIE APPARELS LTD. PLOT # 328, BLOCK # F, TONGI, INDUSTRAL AREA OTHER FACTORIES: NONE May 25, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/25/2014 by Hughes Associates,

More information

Common Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive.

Common Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive. Common Fire Code Violation Checklist Listed are some of the most commonly found fire code violations and should not be considered as all inclusive. Exterior Features All fire access roads signed per TFD

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT GLOBAL OUTWEAR LTD. PLOT # M/1, ROAD # 7, SECTION # 7, MIRPUR, DHAKA March 3, 2014 Accord - Bangladesh RMG Fire Safety Inspection Global Outwear Ltd. Page 2 SUMMARY Global

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT ABA FASHIONS LTD. SENA KALYAN COMMERCIAL COMPLEX (2ND FLOOR), PLOT # 9, BLOCK # F, TONGI, GAZIPUR March 16, 2014 Accord - Bangladesh RMG Fire Safety Inspection ABA Fashions

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 107/112 Nazrul Market 1st & 2nd floor, Chawk Bazar, Chittagong Emkay Enterprises 09 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/28 Factory

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was

More information

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION 5609 is amended, to read as follows, with the entire section being an addition to the Fire Code: SECTION 5609. FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT TUBA GARMENTS LTD. PLOT # 1682, ANANDA NAGAR, MERUL BADDA, BADDA, DHAKA OTHER FACTORIES: NONE July 5, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/5/2014 by Hughes

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

School Fire Safety Checklist

School Fire Safety Checklist Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT COMFORT APPAREL, ( PVT ) LTD. 96, DARUS SALAM, MIRPUR, DHAKA OTHER FACTORIES: SALMA FASHION WEARS LTD, COMFORT KNIT FASHION LTD March 27, 2014 Page 2 SUMMARY was surveyed

More information

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for

More information

Retain. Retain. Retain. Board Advisory. Board Advisory. Retain. Disposition. (Statute, Rule, FBC, Industry)

Retain. Retain. Retain. Board Advisory. Board Advisory. Retain. Disposition. (Statute, Rule, FBC, Industry) Florida Specific Amendment Code Reference NFPA 101 Anytime a reference is made to NFPA 1 or NFPA 101 within this Code, it shall be 1.1.1.1 the Florida specific version of NFPA 1 and NFPA 101. The Florida

More information

FIRE EXTINGUISHER SPACING & INSTALLATION GUIDELINES

FIRE EXTINGUISHER SPACING & INSTALLATION GUIDELINES FIRE EXTINGUISHER SPACING & INSTALLATION GUIDELINES Town of Brighton Office of the Fire Marshal October 2018 Fire Extinguisher Spacing & Installation Guidelines Scope The Fire Code of New York specifies

More information

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Vill: Golora, Post: Kaitta P.S. Saturia, Manikgonj Manikgonj, Dhaka The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT AMAZON TEX KNIT FASHION LTD JOBEDA PLAZA, 85 AC DHAR ROAD KALIRBAZAR May 21, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/21/2014 by Hughes Associates, Inc. This

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA 31548 912-510-4302 February 9, 2011 Greetings Camden County Businesses, As always, our department is working vigilantly

More information

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES OFFICE OF THE FIRE MARSHAL Worcester County GOVERNMENT CENTER - ONE WEST MARKET STREET - ROOM 1003 SNOW HILL, MARYLAND 21863-1194 TEL: 410-632-5666 FAX: 410-632-5664 GUIDELINES FOR INSPECTING GROUND BASED

More information

HEALTH/LIFE SAFETY ANNUAL INSPECTION CHECKLIST (ROE)

HEALTH/LIFE SAFETY ANNUAL INSPECTION CHECKLIST (ROE) HEALTH/LIFE SAFETY ANNUAL INSPECTION CHECKLIST (ROE) Administrative and General Building Requirements Safety reference plans (1) Fire alarm audibility (10) Alcohol hand-rub-dispensers (19) School safety

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT AMITY DESIGNS LTD. HOUSE#7&9, ROAD#9 BLOCK D, SECTION #11MIRPUR DHAKA OTHER FACTORIES: NONE April 21, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/21/2014 by Hughes

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010) CHAPTER 1 SCOPE AND ADMINISTRATION 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 47 and such codes and standards shall

More information

Fire and Life Safety Review Form

Fire and Life Safety Review Form Exits/Egress Fire and Life Safety Review Form 1. Doors shall swing in the direction of egress travel where serving and occupancy load of 50 or more. IFC 1010.1.2.1 2. Egress shall be readily openable from

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Assessor: Konabari, Neelnagar, Gazipur Gazipur Dhaka Bangladesh Uttaron The Alliance for Bangladesh Worker Safety Page 1/13 Introduction to the Report The following

More information

INTERIOR FINISH REVIEW

INTERIOR FINISH REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM I000 I001 I005 I010 I015 I020 INTERIOR FINISH Plans shall bear the seal of a licensed Architect currently registered with the State of Georgia are required for final

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101):

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): 1.1.1 Title. NFPA 101, Life Safety Code, shall be known as the Life Safety Code, is cited as such, and shall

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

Safety Tips for the Office

Safety Tips for the Office Safety Tips for the Office An office fire can be devastating - resulting in business interruption or permanent closure, loss of lives, jobs, property and information. Offices are loaded with combustible

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Section No. Subject Page No. 1 Authority and Purpose 10-1 2 Definitions

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the

More information

BUILDER S PRE-INSPECTION CHECKLIST

BUILDER S PRE-INSPECTION CHECKLIST Warrenton Fire Protection District 606 Fairgrounds Rd. Warrenton, MO 63383 Ph: 636-456-8935 Fax: 636-456-7764 www.warrenton-fire.org BUILDER S PRE-INSPECTION CHECKLIST This checklist is designed as a general

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT CHAITY COMPOSITE LTD. CHOTTO SHILMONDI, TRIPURDI, SONARGAON OTHER FACTORIES: NONE April 7, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/7/2014 by Hughes Associates,

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

Ch. 54 GROUP B EDUCATIONAL 34 CHAPTER 54. GROUP B EDUCATIONAL OCCUPANCY GROUP

Ch. 54 GROUP B EDUCATIONAL 34 CHAPTER 54. GROUP B EDUCATIONAL OCCUPANCY GROUP Ch. 54 GROUP B EDUCATIONAL 34 CHAPTER 54. GROUP B EDUCATIONAL OCCUPANCY GROUP Sec. 54.1. Group B occupancies. 54.2. Classification. 54.3. Nursery schools, day care centers and the like. 54.4. Separation

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: Assessor: Anzir Apparels Limited, Unit-1 Karim supermarket, Baipal, Baipal, Savar Savar Dhaka Bangladesh Emkay Enterprises 30 Apr 2014 The Alliance for Bangladesh

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014 Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014 Philip Rizcallah, P. Eng. NRC-IRC Canadian Codes Centre Presented by Stan Dueck CRBO Overview Where are the major

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

Short-Term & Accessory Short-Term Rental Safety Certification

Short-Term & Accessory Short-Term Rental Safety Certification Short-Term & Accessory Short-Term Rental Safety Certification Permit Application Center (City Hall) 555 Liberty St. SE, Room 320 Salem, OR 97301 503-588-6213 (For office use only) License #: If you need

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

BUILDER S PRE-INSPECTION CHECKLIST

BUILDER S PRE-INSPECTION CHECKLIST Warrenton Fire Protection District 606 Fairgrounds Rd. Warrenton, MO 63383 Ph: 636-456-8935 Fax: 636-456-7764 www.warrenton-fire.org BUILDER S PRE-INSPECTION CHECKLIST This checklist is designed as a general

More information

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:. 2012 B.C. Building Code Checklist (Division B Part 3) This checklist is provided as a reference only. The submission of this checklist with a Building Permit application should not be considered as a substitute

More information

APPLICATION FOR Large Family Day Care Permit

APPLICATION FOR Large Family Day Care Permit PLANNING SERVICES DEPARTMENT 411 Main Street (530) 879-6800 P.O. Box 3420 Chico, CA 95927 Application No. APPLICATION FOR Large Family Day Care Permit Applicant Information Applicant Daytime Phone Street

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Business License Pre-inspection Checklist

Business License Pre-inspection Checklist Business License Pre-inspection Checklist August, 2016 Alberta Fire Code business license pre-inspection and annual checklist This checklist provides business owners with Alberta Fire Code requirements

More information

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Tire Storage. Michigan Fire Inspectors Society Fall Conference

Tire Storage. Michigan Fire Inspectors Society Fall Conference Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR LIBRARY HOTEL OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: Library

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

SEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS

SEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS CITY OF SEMINOLE BUILDING DEPARTEMENT/FIRE DEPARTMENT 9199 113 th Street N. SEMINOLE, FL 33772 Phone: (727) 392-1966 - FAX (727) 319-6583 NO SMOKING UNDER THE TENT(S) Tents may be erected in any zoning

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

New Facilities. Minimum Requirements

New Facilities. Minimum Requirements 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Item Reference Violation General Requirements NFPA 1124-7.1.1 Retail sales of consumer fireworks in both new and existing buildings, structures, and

More information

NFPA 101 Life Safety Code Introduction for Fire Alarm, Security and Locksmith Qualifiers

NFPA 101 Life Safety Code Introduction for Fire Alarm, Security and Locksmith Qualifiers Introduction for Fire Alarm, Security and Locksmith Qualifiers November 20, 2014 11/20/2014 1 Rault Center Fire New Orleans November 29, 1972 11/20/2014 2 Who am I? Graduate of LSU School of Architecture

More information

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly. SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.

More information

Washoe County Department of Social Services

Washoe County Department of Social Services SECTION 30 FIRE AND LIFE SAFETY REQUIREMENTS 30.1 Authority to inspect. The facility shall meet all fire and life safety standards. Fire department inspectors shall have authority to enter, for purposes

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information