1X30 Trip Circuit Supervision Relay

Size: px
Start display at page:

Download "1X30 Trip Circuit Supervision Relay"

Transcription

1 echnical ulletin ip Circuit Supervision Relay Features Monitors trip circuit supply Monitors trip circuit wiring integrity Monitors circuit breaker operate coil continuity Monitors circuit breaker 5a and 5b auxiliary switches in open and closed positions >00ms time delay to avoid nuisance alarms during normal C operation Compact design Simple through hole panel mount De-mountable terminal blocks complete with locking screws Extra large Remote indication via one output contact Custom front panel label Cost effective Range of supervision voltages Front view Rear view pplication he ip Circuit Supervision relay has been designed as a simple and cost effective device for monitoring the condition of the trip circuit supply, trip circuit wiring and circuit breaker operate coil continuity. Local visual indication of fuse or circuit failure is provided by a large ultra high intensity. Remote indication is made possible through a single alarm relay output contact. he relay is characterized by it s compact size, plug in connection base and simple panel mounting configuration. number of models are available to cover a range of sensing circuits. Operation Made in ustralia he relay is comprised of two electromechanical output relays which are wired across the protection trip contact and the circuit breaker a and b pallet switches. his results in the alarm relay being normally energized provided the trip supply, the trip circuit and the circuit breaker coil are all healthy. Failure of the trip supply, the circuit under supervision or the C coil will cause the alarm relay to be de-energized providing a remote warning signal and the front panel alarm changing state. he relay incorporates an electronic time delay to avoid nuisance alarm signals during normal operation of the circuit breaker between the open and closed state. n important characteristic of the design is the low level of current required to flow through the C coil for correct operation of the supervision scheme. constant low supervision current is maintained irrespective of the C open or closed position. his results in low power dissipation in the circuit and the C coil which avoids the possibility of nuisance tripping. wo supervision schemes are available to provide a range of and visual alarm and output contact options. he relay is designed for flush mounting utilizing the single 5mm mounting point which also houses the indicator. Electrical termination is made via ten (0) screw terminals on the rear of the case. his terminal block is of a plug in type further simplifying installation. Due to RMS continuous product improvement policy this information is subject to change without notice. /Iss. G//08/ - /

2 echnical Data C RIP - reaker Opening SUPERVISED CIRCUIS he trip supply, circuit and C coil are continuously monitored under all conditions as depicted in the following diagrams: he thick blue lines depicted below identify the supervised trip circuit and the red arrows the path of the supervision current under different conditions. SUPERVISION WIH C CLOSED Loss of the DC trip supply or circuit continuity through the indicated current path for >00ms will cause the normally energised fail alarm relay to drop out. SUPERVISION DURING C OPERION 00ms time delay holds in alarm contact during C operation. he will remain off while the protection trip contact closed. SUPERVISION WIH C OPEN lternate supervision current path when the C is open. Note: * >00ms delay * ip Coil he protection contact may be a latching type lockout relay. In this case supervision current will not flow through supervision element. Supervision element will continue to function and maintain the normally energised fail alarm contact to remain picked up. 5 ip Coil 5 RNSIEN CONDIION (Momentary flashing of the will occur during operation of the C) ip Coil 5 SUPERVISION SCHEMES wo different supervision schemes are available as described on page. VOLGE OPERING RNGE 70% to 5% of nominal voltage. DROP OU VOLGE Drop out between 5 and 0% of nominal rated operate voltage. SUPERVISION OPERING CURREN he circuit design is optimized to minimize the supervision current in the trip coil to avoid the possibility of nuisance tripping. Supervision Circuit (C open and closed) Nominal Resistance (ohms) supply Supervision ip coil (Maximum) * current V DC m V DC,600 0m 8V DC, m 0V DC, m 5V DC 5, m Note: * he maximum recommended C trip coil resistance stated above equates to a minimum C operating power of 0W. URDEN otal power dissipated in the supervision and alarm circuits at nominal operating voltage is tabulated below: Red versions: Nominal Normal conditions supply C Closed C Open V DC.8W.W V DC.W.W 8V DC.0W.5W 0V DC.W 0.9W 5V DC.W.0W Green versions: Nominal Normal conditions supply C Closed C Open V DC.W.7W V DC.7W.W 8V DC.W.9W 0V DC.W.8W 5V DC.W.0W VISUL INDICOR Panel mounted extra large red, yellow or green. INSULION WIHSND in accordance with IEC 55-5: KV RMS and./50 5KV impulse between input and output. LRM DELY >00ms at nominal operating voltage. OUPU RELY CONC CONFIGURION contact as indicated in supervision scheme diagrams KV isolation across open contacts OUPU CONC RING Make and carry 0 C or DC (Limits L/R=0ms and 00V max.) for 0.s 0 C or DC (Limits L/R=0ms and 00V max.) for 0.5s 5 C or DC continuously reak (Limits 5 and 00V max.),50v C resistive 50V at 0.PF C inductive 75W DC resistive 0W DC inductive L/R = 0ms 50W DC inductive L/R = 0ms Minimum recommended load 0.5W, 0m or 5V minimum. Due to RMS continuous product improvement policy this information is subject to change without notice. /Iss. G//08/ - /

3 Supervision Schemes SCHEME Red alarm and C/O alarm contact In this scheme a C/O alarm contact and red alarm is provided. he alarm contact remains picked up under normal healthy conditions and during switching transients. Under abnormal conditions the alarm contact will always drop out to signal a trip circuit failure. he red alarm will also become illuminated provided the trip supply has not been lost to terminal 0 on the relay. he trip supply may be wired directly to terminal 0. his will ensure that the red alarm will still illuminate even for loss of the DC trip supply to the protection trip contact. yellow alarm may be specified in place of the red. SCHEME Green healthy and C/O alarm contact In this scheme a C/O alarm contact and green healthy is provided. he alarm contact remains picked up and the green healthy illuminated under normal healthy conditions and during switching transients. Under abnormal conditions the alarm contact will always drop out to signal a trip circuit failure and the green healthy extinguished. ip Coil 5 ip Coil 5 0 RED 5 GREEN 5 RL RL Contacts shown with C Open & circuit de-energised. Red alarm illuminated he thick blue lines depicted identify the continuously supervised trip circuit (C open or closed). Connect terminal 0 to terminal OR terminal 0 direct to the protection DC supply but NO both. 9 0 Contacts shown with C Open & circuit de-energised. Green healthy extinguished. he thick blue lines depicted identify the continuously supervised trip circuit (C open or closed). Due to RMS continuous product improvement policy this information is subject to change without notice. /Iss. G//08/ - /

4 Ordering Information MOUNING Panel mounting through indicator assembly. Optional custom label fits between panel and mounting nut. CSE SYLE Double insulated high impact plastic case moulded in polystyrol. ERMINL WIRING x 5 way screw compression terminal blocks mounted in two plugin bases for easy wiring and installation. Each terminal block is polarised to ensure that it cannot be plugged into the wrong terminal socket. Screws to retail the plug-in terminal blocks are provided. erminal 9 is not used to allow adequate high voltage isolation between terminals 8 and 0. Generate the required ordering code as follows: e.g. -D - SUPERVISION VOLGE V DC D 0V DC V DC E 5V DC C 50V DC SUPERVISION SCHEME C Red alarm illuminated under fault conditions Green healthy illuminated under normal conditions Yellow alarm illuminated under fault conditions CUSOM FRON PNEL LEL Not required Required dvise x 0 characters (Maximum) of custom text for custom front panel label with order. Rear terminal layout EMPERURE RNGE Operating: Storage: -0 to +55 o C -5 to +75 o C Maximum X 0 characters CSE DIMENSIONS PNEL MOUNING HOLE DIMEER "JUMO" HIGH INENSIY NYLON REINING NU PNEL HICKNESS to mm Due to RMS continuous product improvement policy this information is subject to change without notice. /Iss. G//08/ - /

5 ustralian Content Unless otherwise stated the product(s) quoted are manufactured by RMS at our production facility in Melbourne ustralia. pproximately 60% of our sales volume is derived from equipment manufactured in house with a local content close to 80%. Imported components such as semi-conductors are sourced from local suppliers & preference is given for reasonable stock holding to support our build requirements. Quality ssurance RMS holds NCSI (N Certification Services International), registration number 6869 for the certification of a quality assurance system to S/NZS ISO Quality plans for all products involve 00% inspection and testing carried out before despatch. Further details on specific test plans, quality policy & procedures may be found in section of the RMS product catalogue. Product Packaging Protection relays are supplied in secure individual packing cardboard boxes with moulded styrene inserts suitable for recycling. Each product & packing box is labeled with the product part number, customer name & order details. Design References he products & components produced by RMS are based on many years of field experience since Relays Pty Ltd was formed in 955. large population of equipment is in service throughout ustralia, New Zealand, South frica & South East sia attesting to this fact. Specific product & customer reference sites may be provided on application. Product Warranty ll utility grade protection & auxiliary relay products, unless otherwise stated, are warranted for a period of months from shipment for materials & labour on a return to factory basis. Repair of products damaged through poor application or circumstances outside the product ratings will be carried out at the customer s expense. Standard Conditions of Sale Unless otherwise agreed RMS Standard erms & Conditions (QF 907) shall apply to all sales. hese are available on request or from our web site. Relay Monitoring Systems Pty Ltd 6 nzed Court, Mulgrave, Victoria 70, USRLI el: Fax: rms@rmspl.com.au Web: 0 Relay Monitoring Systems Pty Ltd Due to RMS continuous product improvement policy this information is subject to change without notice.

1S25 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide

1S25 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide 1S25 User Guide Arc Fault Monitor relay monitoring systems pty ltd Advanced Protection Devices User Guide Visit www.rmspl.com.au for the latest product information. 1S25 User Guide About This Manual This

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

Delta XRD. Supervision Relays. rms A U X I L I A R Y T R I P P I N G S U P E R V I S I O N

Delta XRD. Supervision Relays. rms A U X I L I A R Y T R I P P I N G S U P E R V I S I O N Delta XRD A U X I L I A R Y T R I P P I N G S U P E R V I S I O N Supervision Relays The XRD is a compact high performance supervision relay for power utility protection and control applications. > Trip

More information

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc flash detection units. Product picture Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize

More information

Alpha XR User Guide. Supervision Relay. relay monitoring systems pty ltd Advanced Protection Devices. User Guide

Alpha XR User Guide. Supervision Relay. relay monitoring systems pty ltd Advanced Protection Devices. User Guide Alpha XR User Guide Supervision Relay relay monitoring systems pty ltd Advanced Protection Devices User Guide Visit www.rmspl.com.au for the latest product information. Alpha XR User Guide About This Manual

More information

1S20 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide. Test Manual

1S20 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide. Test Manual 1S20 User Guide Arc Fault Monitor relay monitoring systems pty ltd Advanced Protection Devices User Guide Test Manual 1S20 User Guide About This Manual This User Guide covers all 1S20 relays manufactured

More information

7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities.

7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities. Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities. 7PG17 XR105, XR106 and XR107, XR205 and XR206 Interposing

More information

1S26 User Guide. Arc Fault Monitor + Integrated Current Check Relay. Advanced Protection Devices. relay monitoring systems pty ltd.

1S26 User Guide. Arc Fault Monitor + Integrated Current Check Relay. Advanced Protection Devices. relay monitoring systems pty ltd. 1S26 User Guide Arc Fault Monitor + Integrated Current Check Relay relay monitoring systems pty ltd Advanced Protection Devices User Guide Test Manual 1S26 User Guide About This Manual This User Guide

More information

Reyrolle Protection Devices. 7PG26 DAD High Impedance Current Relay. Answers for energy

Reyrolle Protection Devices. 7PG26 DAD High Impedance Current Relay. Answers for energy Reyrolle Protection Devices 7PG26 DAD High Impedance Current Relay Answers for energy Siemens Protection Devices Limited 2 7PG26 DAD High Impedance Circulating Current Relay Description The type DAD relay

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management Reyrolle Protection Devices 7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management 7XG3130 - RA30 Optical Arc Fault Sensor Features Compact rugged design One or two optical detectors High speed arc

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits 01 VAMP 120 & 121 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during work

More information

AQ 100 Series. Arc Flash Protection System

AQ 100 Series. Arc Flash Protection System AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts

More information

Mors Smitt Industrial Technology. Substation Protection & Control. High Performance Electromechanical Relays. RMS Mors Smitt A Wabtec company

Mors Smitt Industrial Technology. Substation Protection & Control. High Performance Electromechanical Relays. RMS Mors Smitt A Wabtec company Mors Smitt Industrial Technology Substation Protection & Control High Performance Electromechanical Relays Power generation and distribution operators across the world rely on our relays 2 www.morssmitt.com

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description DPB52 True RMS 3-Phase, Multifunction monitoring relay Description Benefits Measuring Voltage Range. Very wide input voltage range: from 125 to 624V ( 208V 40% to 480 + 30% ). Adjustable Voltage Ranges

More information

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits Arc Protection 01 VAmP 120 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during

More information

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225. Gasflag Single Channel Control Panel Alarm Only Apparatus Installation, operating and maintenance instructions, M07225 Issue 2 1/07/05 Crowcon Detection Instruments Ltd 2 Blacklands Way Abingdon Business

More information

ESP TECHNOLOGIES LIMITED

ESP TECHNOLOGIES LIMITED Alarm Technology ESPAN-01 Series Annunciator System Combination type User Manual (Rev. 1) ESP TECHNOLOGIES LIMITED www.esptechno.com Content Page Introduction 2 General Description 2 Overview - Annunciator

More information

Welcome to Hager Presentation

Welcome to Hager Presentation Welcome to Hager Presentation Topics Intro to Hager Group Circuit Protection Enclosures Q&A IIEE Manila 4 th August 17 13.03.2009 2 Company presentation Who we are Hager Group is a leading provider of

More information

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD.

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD. BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY RETROFIT KITS BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD. BE1-50/51B, CO Retrofits BE1-50/51B,

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

Operation and use. Functions and characteristics

Operation and use. Functions and characteristics Operation and use Function Vigirex relays measure the earth-leakage current in an electrical installation via their associated toroids. Vigirex relays may be used for: b residual-current protection (RH10,

More information

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing

More information

R A D I A N T O U T D O O R H E A T E R S OPERATION, INSTALLATION AND MAINTENANCE MANUAL. TT-MTM Wall Controller

R A D I A N T O U T D O O R H E A T E R S OPERATION, INSTALLATION AND MAINTENANCE MANUAL. TT-MTM Wall Controller R A D I A N T O U T D O O R H E A T E R S OPERATION, INSTALLATION AND MAINTENANCE MANUAL TT-MTM Wall Controller TT-MTM Wall Controller Rev B JUL12 TT-MTM wall controller This controller is a custom designed

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF

More information

VAMP 121. Arc protection unit. User manual

VAMP 121. Arc protection unit. User manual VAMP 121 Arc protection unit User manual VM121.EN014_B Table of contents VAMP 121 Table of contents 1. General... 4 1.1. Arc protection unit VAMP 121... 4 2. Unit configuration... 6 3. Sensors... 8 3.1.

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE / 3 GM20 Digital Ground Continuity Relay For AC Systems Technical Bulletin NAE03230 / 0.20 GM20 Ground continuity monitor For AC systems Description The GM20 monitors the loop resistance of ground conductors

More information

I/O ZONE 560/583 AND OPERATION MANUAL

I/O ZONE 560/583 AND OPERATION MANUAL UPM I I/O ZONE 560/583 INSTALLATION AND OPERATION MANUAL 1 UNIT PROTECTION MODULE HARDWARE OPERATION IMPORTANT: This manual is for UPM board part numbers 8733 800 259. See controller label as shown in

More information

Mains Power Filter 970MF10 970MF20. Installation Instructions

Mains Power Filter 970MF10 970MF20. Installation Instructions Mains Power Filter Installation Instructions and Table of Contents 1.0 Warnings... 3 2.0 Introduction... 3 3.0 Quick Installation Overview... 3 4.0 Typical Installations... 3 5.0 Protection Concepts...

More information

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign Features DATASHEET Connects to multiple sensing instruments One/Two Channel Device Bright solid state LED Alarm Display Audible Alert (internal and external) High reliability, fully dual redundant alarm

More information

TCM-2 Thyristor Control Module DATA SHEET

TCM-2 Thyristor Control Module DATA SHEET TCM-2 Thyristor Control Module TCM-2 Thyristor DATA DATA SHEET Control Module DATA SHEET Alarm panels Type Compact Q96 design Extremely easy push-button programming (no jumpers or the like) Individual

More information

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection Ground Fault Protection GADD MKIII Ground Fault Indication System Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR

More information

PART 4 ELECTRICAL STANDARDS

PART 4 ELECTRICAL STANDARDS PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve

More information

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ZIOU/230 - MAINS IO INSTRUCTION MANUAL Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel

More information

ISIS SAFETY SYSTEM Installation guide

ISIS SAFETY SYSTEM Installation guide ISIS SAFETY SYSTEM Installation guide CAUTION This information is designed to help suitably qualified personnel install and operate Mechan Safety equipment. Before using this product, read this guide thoroughly

More information

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual ANALOX 5001 ANALOX 5001 Carbon Dioxide Monitor User Manual Analox Sensor Technology Ltd 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT T: +44 (0)1642 711400 F: +44 (0)1642 713900

More information

Ordering Key. Dielectric strength

Ordering Key. Dielectric strength Controllers AC Semiconductor Controller Type Soft starting and stopping of 3-phase squirrel cage motors Low inrush and reduced vibration during starting Integrated bypassing of semiconductors Rated operational

More information

CIRCUIT BREAKER FAIL PROTECTION

CIRCUIT BREAKER FAIL PROTECTION CIRCUIT BREAKER FAIL PROTECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any losses

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

Dale Power Solutions Ltd

Dale Power Solutions Ltd DC THYRISTOR SYSTEMS DATASHEET Features Erskine Single Phase Input DCV Range 24V, 48/50V or 110V nominal Up to 63 Amps per charger Constant voltage/current limited output Standard alarm module LCD metering

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

PRODUCT MANUAL. The intelligent, energy saving solution

PRODUCT MANUAL. The intelligent, energy saving solution PRODUCT MANUAL The envirotouch is a range of intelligent, timer based switches which allows easy, point-of-use control of lighting and electrical devices. It includes multiple pre-set, countdown timer

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

Annunciator Relay MR 11 and MRE 11 MR 21 and MRE 21. Automation Equipment. Power Station Control Systems. Control Room Technology

Annunciator Relay MR 11 and MRE 11 MR 21 and MRE 21. Automation Equipment. Power Station Control Systems. Control Room Technology Annunciator Relay MR 11 and MRE 11 MR 21 and MRE 21 Power Station Control Systems Power Distribution Control Systems Control Room Technology Automation Equipment The products described in this brochure

More information

PRODUCT MANUAL. TT-MTM2 Hard-Wired Controller with Remote

PRODUCT MANUAL. TT-MTM2 Hard-Wired Controller with Remote PRODUCT MANUAL TT-MTM2 Hard-Wired Controller with Remote TT-MTM2 Hard-Wired Controller with Remote Rev D JUN16 TT-MTM2 Wall Controller This controller is a custom designed and manufactured controller for

More information

Emergency power automatics MS-2. High resistance to shock, vibrations and transients. All output are 2A relay contacts

Emergency power automatics MS-2. High resistance to shock, vibrations and transients. All output are 2A relay contacts Emergency power automatics Type EPOMATIC MS-2, EC-2 4921240002D MS-2 EC-2 DEIF A/S All necessary functions: - mains supervision - start/supervision/stop of diesel engine - control of circuit breakers and

More information

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

ELECTRONIC FLAME SUPERVISION MULTI-BURNER MULTI-BURNER MODEL: SENS-A-FLAME II Revision: 0 7112 DESCRIPTION Model 7112 Sens-A-Flame II is a second generation solid-state programmable combustion safeguard for supervising multiple burner ovens, furnaces,

More information

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc Table of Contents Introduction...2 Mounting...2 Dimensions...2 Controls...3 Screen Displays...3 Screen Messages...4 Light Test...5 Control Power...5 Wiring...5 Inputs...7 Outputs...7 Programming...8 Technical

More information

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector CAUTION & SYMBOL DEFINITIONS: CAUTION: Gives detailed description of different situations to avoid or not avoid for the proper operation of the

More information

Tower & Obstruction Lighting

Tower & Obstruction Lighting Tower & Obstruction Lighting Selection Guide... 10.2 Beacon Flasher FA... 10.4 FS155-... 10.4 FS165-... 10.4 Lamp Monitors Incandescent Lamps FB... 10.6 SCR490D... 10.7 SCR430T... 10.8 SCR630T... 10.8

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) IR425-D4_D00039_04_D_XXEN/05.2017 ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits

More information

COMPALARM A RACK ALARM ANNUNCIATOR GENERAL TECHNICAL CHARACTERISTICS. The system is composed by: It s available in 2 different executions:

COMPALARM A RACK ALARM ANNUNCIATOR GENERAL TECHNICAL CHARACTERISTICS. The system is composed by: It s available in 2 different executions: GENERL he system is composed by: It s available in 2 different executions: he first solution is the most versatile either for assembling or displaying. s far as its operation is concerned, the alarm unit

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

EARTH LEAKAGE RELAY. User Manual - Issue 1.0 Earth Leakage Relay www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters EARTH

More information

Figure 30: Sample Case 8

Figure 30: Sample Case 8 6.9 Sample Case 8 C-A, φ-φ fault on Line 512 Hidden failure: Line 504 PCB scheme low set fault detector picked up This case illustrates the security of the line. With the low set fault detector of the

More information

CMD420 / CMD421 Series

CMD420 / CMD421 Series 3 T M CMD420 / CMD421 Series Digital Current Relay (Overcurrent and Undercurrent) For Three-Phase AC Systems Technical Bulletin NAE1032810 / 06.2016 CMD420 / CMD421 Digital overcurrent and undercurrent

More information

Electronic Standard Devices. Annunciator Relay. MR 11 and MRE 11 MR 21 and MRE 21

Electronic Standard Devices. Annunciator Relay. MR 11 and MRE 11 MR 21 and MRE 21 Electronic Standard Devices Annunciator Relay MR and MRE MR 2 and MRE 2 The products described in this brochure are intended for industrial use and meet the requirements laid down by the EU directive 7

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

Overload relays. General descriptions. Configuration of the front

Overload relays. General descriptions. Configuration of the front Overload relays General descriptions Type MT, bimetal-style, overload relays are designed to protect AC circuits and motors against overloads, phase failure, long starting times and prolonged stalling

More information

DTS SECURITY P.O.BOX 3399 Base plate-mounting EDENVALE instructions 1610 TELEPHONE

DTS SECURITY P.O.BOX 3399 Base plate-mounting EDENVALE instructions 1610 TELEPHONE DTS Megashock 5 Energizer 5J (Indoor installation) INSTALLATION MANUAL Comply to: SANS IEC 60 335-2-76 NRCS Ref. no. 7357 10 14 DTS SECURITY P.O.BOX 3399 Base plate-mounting EDENVALE instructions 1610

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 505 Grünberg Tel.: 00 807-0 Fax: 00 807-259 Insulation monitoring device for unearthed AC/DC systems (IT systems for the supply of operating theatre

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA) R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

SACE PR021/K SIGNALLING UNIT

SACE PR021/K SIGNALLING UNIT SACE PR021/K SIGNALLING UNIT 1SDH000559R0002 L3016 1/52 EN CONTENTS 1. GENERAL INFORMATION...4 1.1. FOREWORD...4 1.2. APPLICABLE SCENARIOS...5 2. TECHNICAL SPECIFICATIONS...6 2.1. ELECTRICAL CHARACTERISTICS...6

More information

LAWSON FINAL DISTRIBUTION PRODUCTS RANGE

LAWSON FINAL DISTRIBUTION PRODUCTS RANGE FINAL DISTRIBUTION PRODUCTS RANGE ISO 14001:2004 Certified ISO 9001:2008 Certified FUSES INDIA LTD Lawson Fuses India Ltd is a wholly owned subsidiary of Lawson Fuses Ltd,a long established UK company

More information

Guide To Troubleshooting INEFFICIENT COOLING FANS

Guide To Troubleshooting INEFFICIENT COOLING FANS Guide To Troubleshooting INEFFICIENT COOLING FANS TABLE OF CONTENTS Introduction Enclosure Cooling Basics Key Attributes of Enclosure Cooling Symptoms of Poor Enclosure Cooling Typical Cooling Fan Problems

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

Product & Assembly Manual

Product & Assembly Manual Product & Assembly Manual HEATSTRIP Intense Portable Electric Heater Model THY2200P For HEATSTRIP Installation video go to: www.youtube.com, search HEATSTRIP www.heatstrip.com.au Contents Manual # Rev

More information

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand 5U Compact System Installation Manual V1.0 Manufactured by Enatel Ltd. 321 Tuam Street PO Box 22-333 Christchurch New Zealand Phone +64-3-366-4550 Fax +64-3-366-0884 Email sales@enatel.net www.enatel.net

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) Insulation monitoring device for unearthed AC/DC control circuits (IT systems) TDB103005en/05.2013 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) Product description The

More information

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

FIREBETA EXTINGUISHING CONTROL PANEL (ECP) F I R E D E T E C T I O N A N D C O N T R O L FIREBETA EXTINGUISHING CONTROL PANEL (ECP) Three versions: 2 areas of detection and 1 area extinguishing 4 areas of detection and 1 area extinguishing 4 areas

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

FIRElux Emergency Lighting

FIRElux Emergency Lighting ABC a FIRElux Emergency Lighting Safety In All Enviroments FIRElux is a completely new emergency lighting system. The rapid development of LED technology has made it possible to implement emergency lighting

More information

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR.. EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR.. AUTOMATIC OIL BURNER CONTROL SYSTEMS APPLICATION This range of electronic oil burner controls has been specifically designed for oil burners for non

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

HEA USER MANUAL. 1 Version: 22. June 2010

HEA USER MANUAL. 1 Version: 22. June 2010 HEA USER MANUAL 1 Version: 22. June 2010 INDEX PAGE RECEIPT OF EQUIPMENT....... 3 LIFTING AND HANDLING.... 3 INSTALLATION INSTRUCTIONS...... 4 MAINTENANCE INSTRUCTIONS... 5 CONTROL OF INSULATION... 6 THERMOSTATS.

More information

DIGITIAL PROTECTION COUPLER

DIGITIAL PROTECTION COUPLER DIGITIAL PROTECTION COUPLER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

HVAC Products. SAPHIR AirGo OEM Air Handling Unit Concept

HVAC Products. SAPHIR AirGo OEM Air Handling Unit Concept s HVAC Products OEM Air Handling Unit Concept Control solutions otal solution competence Application know-how and flexibility Access to future-oriented technologies State-of-the-art and open communication

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

QA(13) - Series Miniature Circuit Breakers

QA(13) - Series Miniature Circuit Breakers 1 pole 2 pole 3 pole 3 + N Features AC Circuit Breaker Hydraulic-Magnetic technology 100% rating capability, independent of ambient temperature VC 8036 compliant (SANS 556-1) VDE approved, CE certified

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

SERVICE DATA SHEET (9704) Rev. D

SERVICE DATA SHEET (9704) Rev. D SERVICE DATA SHEET 318047401 (9704) Rev. D Electric Wall Ovens with Electronic Oven Control (ERC III - 318010700 & 318010900) NOTICE This service data sheet is intended for use by persons having electrical

More information

PRODUCT MANUAL OPERATION, INSTALLATION AND MAINTENANCE MANUAL. Indoor Convective Panel Heater

PRODUCT MANUAL OPERATION, INSTALLATION AND MAINTENANCE MANUAL. Indoor Convective Panel Heater PRODUCT MANUAL OPERATION, INSTALLATION AND MAINTENANCE MANUAL Indoor Convective Panel Heater CONTENTS Rev A NOV14 1. Product Overview 2. Specification Data 3. Operations 4. Installation 5. Safety 6. Maintenance

More information

Hazardous Area Portable Fan Heater The Bulldog

Hazardous Area Portable Fan Heater The Bulldog Hazardous Area Portable Fan Heater The Bulldog www.exheat-industrial.com MFH The Bulldog Portable Fan Heater EXHEAT Industrial s MFH The Bulldog Portable Fan Heater is the world s first truly portable

More information

PAC1500Xi PORTABLE APPLIANCE CHECKER

PAC1500Xi PORTABLE APPLIANCE CHECKER PAC1500Xi PORTABLE APPLIANCE CHECKER OPERATING INSTRUCTIONS 211A912 CONTENTS 1) Safety... 1 2) Introduction & Description... 2 3) Applications... 2 4) Test Sequence... 3 5) Visual Inspection... 3 6) Earth

More information

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection Ground Fault Protection GADP Ground Fault Indication System Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR 737-4787

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014 Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual Man-1078EL Issue 01 February 2014 B Index Page 1. Introduction... 3 1B2. Safety and mounting... 3 2B3. Technical specification...

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information