Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Size: px
Start display at page:

Download "Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM"

Transcription

1 of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement: Response Message: Annex C has been added to the document. This information needs to be balloted separate referencing Annex C.

2 of 66 5/18/2015 1:01 PM Second Revision No. 1-NFPA [ Section No ] This standard prescribes safeguards intended to prevent fires and explosions, and other related hazards involving drycleaning, and associated wetcleaning, and/or laundry processes and to minimize the personal injury and property damage consequences of such incidents. Submittal Date: Tue Mar 10 10:11:37 EDT 2015 Committee Statement: The scope of the standard deals with a primary main occupancy containing drycleaning processes, not primarily wetcleaning and laundry. Readers of the standard may believe that this standard should be used when designing Laundromats or incidental laundry rooms that are not associated with drycleaning facilities. Response Message: Public Comment No. 3-NFPA [Section No ]

3 of 66 5/18/2015 1:01 PM Second Revision No. 58-NFPA [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 30, Flammable and Combustible Liquids Code, 2015 edition. NFPA 36, Standard for Solvent Extraction Plants, 2013 edition. NFPA 58, Liquefied Petroleum Gas Code, 2014 edition. NFPA 70, National Electrical Code, edition. NFPA 79, Electrical Standard for Industrial Machinery, 2015 edition. NFPA 86, Standard for Ovens and Furnaces, 2015 edition. NFPA 99, Health Care Facilities Code, 2015 edition. Organization: National Fire Protection Assoc Submittal Date: Tue Mar 31 09:19:43 EDT 2015 : updated to current edtion of NFPA 70.

4 of 66 5/18/2015 1:01 PM Second Revision No. 7-NFPA [ Section No ] Conversion. Any modification(s) made to newor existing drycleaning equipment that permits the use of a solvent of a different class or permits a change to a different solvent in the same class, other than that which is specified on the original manufacturer s specifications and product nameplate. (See also, Section 6.2.) Submittal Date: Mon Mar 16 08:12:57 EDT 2015 Committee Statement: Response Message: The term conversion is no longer used in the document. Changes to solvents and changes to equipment are explained in the document with requirements but the term conversion is no longer used.

5 of 66 5/18/2015 1:01 PM Second Revision No. 8-NFPA [ Section No ] Drycleaning. The process of removing dirt, grease, paints, and other stains from such items as apparel, textiles, fabrics, and rugs by use of nonaqueous liquids. Submittal Date: Mon Mar 16 08:17:04 EDT 2015 Committee Statement: Response Message: Annex material to be deleted since it did not add any information of substance to the definition. Asterisk removed.

6 Second Revision No. 9-NFPA [ Section No ] Dryer. Unless otherwise specified as a laundry dryer, the term dryer refers to a drycleaning dryer Drycleaning Dryer. A piece of equipment used to dry apparel, textiles, fabrics, and rugs that were cleaned with drycleaning solvents Laundry Dryer. Any equipment in which water-cleaned textiles are tumbled, agitated, and dried or deodorized while heated air circulates through the load to remove the water Reclaiming Dryer. A piece of equipment used to dry and reclaim solvents from textiles thereby limiting fugitive emissions Wetcleaning Dryer. Any equipment with a humidistat in which water-cleaned textiles are tumbled, agitated, and dried or deodorized while heated air circulates through the load to remove the water. Submittal Date: Mon Mar 16 08:19:12 EDT 2015 Committee Statement: Response Message: The term dryer alone is not used in the document. Each time the term is used it has been described as a drycleaning, laundry, reclaiming or wetcleaning dryer to ensure that the proper requirements are applied. The term wetcleaning dryer has been added and defined. of 66 5/18/2015 1:01 PM

7 Second Revision No. 10-NFPA [ Section No ] Equipment (Drycleaning Equipment). Any equipment in which textiles are immersed or nonimmersed non-immersed, agitated in solvent, or in which drycleaning solvent is reclaimed from textiles and/or dried Version I Equipment. An open system, employing combustible or noncombustible liquid, that is continuously open to the atmosphere Version II Equipment. An open-circuit system, employing combustible or noncombustible liquid, that releases fugitive emissions, suppresses and controls combustion, and that has safety controls Version III Equipment. A closed-loop system, employing combustible or noncombustible liquid, that does not release emissions, prevents combustion, and that has safety controls Version IV Equipment. A closed-loop system for noncombustible liquids that has safety controls for noncombustible liquids and that does not release emissions. Supplemental Information File Name A docx Description Submittal Date: Mon Mar 16 08:31:25 EDT 2015 Committee Statement: Response Message: The definitions have been clarified by specifying the types of liquids used in the various versions of equipment. Asterisks have been added to Version I-III equipment definitions since there is annex material specifically attached to those definitions. of 66 5/18/2015 1:01 PM

8 A Examples include reclaiming dryers, drycleaning dryers, drycleaning washers

9 Second Revision No. 11-NFPA [ Section No ] Facility (Drycleaning Facility). An occupancy in which drycleaning and associated mercantile operations are conducted, which can include an office, a retail counter, storage rooms, garment racks and conveyors, boiler rooms, shipping and receiving areas, and a drive-up service area. The facility type is defined based on the lowest numerical class of solvent used in the equipment * Type I Facility. Facilities employing class Class I solvents * Type II Facility. Facilities employing class Class II solvents * Type III Facility. Facilities employing class Class IIIA and IIIB solvents * Type IV Facility. Facilities employing class Class IV solvents. Supplemental Information File Name A docx Description Submittal Date: Mon Mar 16 08:46:26 EDT 2015 : Annex material added to assist the user in applying the definition. of 66 5/18/2015 1:01 PM

10 A A Facility type is defined based on the lowest numerical class of solvent. Facilities employing multiple drycleaning solvents in different solvent classes, blended or unadulterated, are defined by the solvent in the numerically lowest class of solvent. A facility, may use Class III and Class IV solvents but since the Type of facility is based on the lowest numerical class it would be considered a Type III facility.

11 of 66 5/18/2015 1:01 PM Second Revision No. 15-NFPA [ New Section after ] Intrinsically Safe. As applied to equipment and wiring, equipment and wiring that are incapable of releasing sufficient electrical energy under normal or abnormal conditions to cause ignition of a specific hazardous atmospheric mixture. (HYP) [ 99, 2015] Submittal Date: Mon Mar 16 09:14:41 EDT 2015 : Added new definition.

12 Second Revision No. 12-NFPA [ Sections , ] LEL. Lower Explosive Limit See , Lower Flammable Limit LFL. Lower Flammable Limit See , Lower Flammable Limit. Submittal Date: Mon Mar 16 08:57:29 EDT 2015 : Better clarifies the acronyms and cross references. 0 of 66 5/18/2015 1:01 PM

13 1 of 66 5/18/2015 1:01 PM Second Revision No. 13-NFPA [ Section No ] Class I Solvents. Liquids having a flash point below 22.8 C 38 C (73 F 100 F ). Submittal Date: Mon Mar 16 09:02:40 EDT 2015 : Corrected error in definition of Class I liquid.

14 Second Revision No. 14-NFPA [ Sections , ] UEL. Upper Explosive Limit. See , Upper Flammable Limit UFL. Upper Flammable Limit. See , Upper Flammable Limit. Submittal Date: Mon Mar 16 09:04:30 EDT 2015 : Better describes the acronyms and provides cross references. 2 of 66 5/18/2015 1:01 PM

15 Second Revision No. 16-NFPA [ Section No ] Class I Solvents. Class I solvents used shall be prohibited in drycleaning equipment shall be prohibited * Change of Solvents. A change of solvents from a higher to a lower class of solvent for use in existing equipment shall be prohibited. Supplemental Information File Name A docx Description Submittal Date: Tue Mar 17 15:29:26 EDT 2015 Committee Statement: Response Message: This information was included in the previous TIA on conversions. In order to emphasize the potential hazard created by converting from a higher class solvent to a lower class solvent the committee added this in the prohibited activities section of the document. Annex material explains the reason for the prohibition. 3 of 66 5/18/2015 1:01 PM

16 A For example, equipment designed for Class IV solvents cannot be used for Class III or II solvents. The Committee is unaware of any acceptable conversions in which a machine using a higherclass solvent has been converted to a lower-class solvent which is why this has been prohibited by the Standard

17 4 of 66 5/18/2015 1:01 PM Second Revision No. 17-NFPA [ Section No ] Wetcleaning of Textiles That Have Been Drycleaned or Laundry Dryers. Textiles cleaned in with a nonaqueous solvent shall not be dried in a laundry or wetcleaning dryer. Submittal Date: Tue Mar 17 15:40:52 EDT 2015 Committee Statement: Response Message: The requirements of this section apply to both types of dryers. Both dryer types have been defined in the document.

18 5 of 66 5/18/2015 1:01 PM Second Revision No. 18-NFPA [ Section No ] The drycleaning facility shall be located not less than 3 m (10 ft) from the line of an adjoining property, unless the wall facing the line of the adjoining property has a fire resistance rating of not less than 2 hours without openings. in accordance with the provisions of NFPA Submittal Date: Tue Mar 17 15:43:22 EDT 2015 Committee Statement: Response Message: The committee reviewed this requirement and found that it was in the first edition of NFPA 32 from At that time, most of the solvents in use were Class I solvents, with some Class II solvent use on occasion. Currently Class I solvents are prohibited in drycleaning facilities and the use of Class II solvents is rare. The committee believes that the appropriate document for construction and location requirements is NFPA 5000 (which incorporates NFPA 30 requirements) and that NFPA 32 should not be establishing these requirements.

19 Second Revision No. 19-NFPA [ Section No ] Ventilation. Ventilation of all types of drycleaning facilities shall be in accordance with all applicable codes and the public in accordance with all applicable government regulations Ventilation for Type II facilities shall be in accordance with Chapter 7. Submittal Date: Tue Mar 17 16:04:53 EDT 2015 Committee Statement: The committee removed this verbiage since in all cases applicable government regulations would apply. 6 of 66 5/18/2015 1:01 PM

20 7 of 66 5/18/2015 1:01 PM Second Revision No. 20-NFPA [ Section No ] Drycleaning equipment shall be separated from apparatus with open flames or exposed electric heating elements by one of the following means: (1) Ensuring that Providing air intakes are provided for combustion air (2) Ensuring that Locating exhaust vents from the equipment are located, if they exist, remotely from the air intakes of the apparatus Submittal Date: Tue Mar 17 16:07:19 EDT 2015 : Clarified requirement.

21 Second Revision No. 21-NFPA [ Section No ] Solvent Containment Drycleaning departments shall be designed to prevent the discharge of solvents or solvent waste streams to public waterways, public sewers, or adjoining properties Where containment pans are not located under the drycleaning equipment, curbs Curbs, dikes, or a special drainage system shall be required to control the migration of spilled solvent unless otherwise indicated in Facilities that have containment pans under the drycleaning equipment do not need further containment. Submittal Date: Tue Mar 17 16:10:28 EDT 2015 : Rearranged requirements so provided in logical order. 8 of 66 5/18/2015 1:01 PM

22 9 of 66 5/18/2015 1:01 PM Second Revision No. 22-NFPA [ Section No ] Opening into boiler Boiler rooms in a Type III facility with Version III equipment shall be allowed to open directly into the drycleaning department where only Class III solvents are used in the listed equipment, provided the openings is protected in accordance with and is at least 10 ft (3 m) from any equipment. Submittal Date: Tue Mar 17 16:13:34 EDT 2015 : Cleaned up verbiage.

23 Second Revision No. 23-NFPA [ Section No ] Automatic Fire-Extinguishing Systems. Where required by this standard, automatic fire-extinguishing systems, including, but not limited to, water mist carbon dioxide systems, clean agent,, and carbon dioxide systems, and water mist shall be installed in accordance with the applicable reference standard Carbon Dioxide Fire-Extinguishing Systems. Carbon dioxide fire-extinguishing systems shall comply with NFPA Clean Agent Fire-Extinguishing Systems. Clean agent fire-extinguishing systems shall comply with NFPA Water Mist Fire-Extinguishing Systems. Water mist fire-extinguishing systems shall comply with NFPA Carbon Dioxide Fire-Extinguishing Systems. Carbon dioxide fire-extinguishing systems shall comply with NFPA Clean Agent Fire-Extinguishing Systems. Clean agent fire-extinguishing systems shall comply with NFPA Water Mist Fire-Extinguishing Systems. Water mist fire-extinguishing systems shall comply with NFPA Inspection, Testing, and Maintenance. Except for approved steam-injection extinguishing systems, automatic fire-extinguishing systems shall be periodically inspected, tested, and maintained in accordance with the applicable reference standard and the manufacturer's operation and maintenance procedures Approved steam-injection extinguishing systems shall be inspected at least annually in accordance with the manufacturer s specifications Portable Fire Extinguishers. Portable fire extinguishers shall be installed and maintained throughout the drycleaning facility in accordance with NFPA 10. Submittal Date: Tue Mar 17 16:15:55 EDT 2015 : Relocated extinguishing systems to the proper section of the document. 0 of 66 5/18/2015 1:01 PM

24 1 of 66 5/18/2015 1:01 PM Second Revision No. 2-NFPA [ Section No. 5.1 [Excluding any Sub-Sections] ] This chapter shall apply to drycleaning and associated wetcleaning and laundering operations, training, and equipment maintenance as it relates to fire and other related hazards. Submittal Date: Tue Mar 10 14:18:17 EDT 2015 Committee Statement: The scope of the standard deals with a primary main occupancy containing drycleaning processes, not primarily wetcleaning and laundry. Readers of the standard may believe that this standard should be used when designing Laundromats or incidental laundry rooms that are not associated with drycleaning facilities. Response Message: Public Comment No. 4-NFPA [Section No. 5.1 [Excluding any Sub-Sections]]

25 2 of 66 5/18/2015 1:01 PM Second Revision No. 24-NFPA [ Section No ] Training on operating procedures Operator training shall be directly applicable specific to the equipment and solvents used in the facility and shall be consistent with safety requirements and the equipment and solvent manufacturers recommendations. Submittal Date: Tue Mar 17 16:24:07 EDT 2015 : Cleaned up language.

26 3 of 66 5/18/2015 1:01 PM Second Revision No. 25-NFPA [ Section No ] Operating Procedures. Routine and emergency condition procedures shall be established for the following: (1) Equipment operation, including equipment parameters and prohibited procedures (2) Solvent handling (3) Spotting, with emphasis on proper removal of spotting agents prior to processing, if applicable. (4) Waste handling (5) Lockout/Tagout procedures Submittal Date: Tue Mar 17 16:25:13 EDT 2015 Committee Statement: The committee wanted lockout/tagout to be listed since it is an important part of operating procedures.

27 4 of 66 5/18/2015 1:01 PM Second Revision No. 26-NFPA [ Section No ] The training shall ensure that all employees are knowledgeable about the applicable safety requirements for their job jobs, including the following: (1) Hazards of their workplace, including chemical hazards (2) General facility safety rules (3) The necessity for proper functioning or related fire and explosion protection systems (4) Equipment maintenance requirements and practices (5) Housekeeping policies and procedures (6) Emergency response plans and procedures (7) Basic PPE requirements (8) Start-up, shutdown, and lockout/tagout procedures (9) Safety data sheet (SDS) requirements Submittal Date: Tue Mar 17 16:27:28 EDT 2015 Committee Statement: The committee added SDS sheets to emphasize the requirement for employee training on SDSs.

28 Second Revision No. 27-NFPA [ Sections 5.5.1, ] The facility owner or the facility owner s representative shall verify that all employees have been trained in equipment use, spotting, and waste handling as outlined in All employee training shall be documented and include the type method of training and the date the training was completed. Submittal Date: Tue Mar 17 16:30:21 EDT 2015 : Cleaned up language and provided cross reference to section on waste handling. 5 of 66 5/18/2015 1:01 PM

29 6 of 66 5/18/2015 1:01 PM Second Revision No. 28-NFPA [ Chapter 6 [Title Only] ] General Equipment and Solvent Requirements Submittal Date: Tue Mar 17 16:33:49 EDT 2015 : This chapter refers to both solvent and equipment requirements.

30 7 of 66 5/18/2015 1:01 PM Second Revision No. 31-NFPA [ Section No ] All drycleaning equipment shall comply with the provisions of and be listed and labeled to comply with this chapter The requirements of this chapter shall apply to all drycleaning equipment. Submittal Date: Tue Mar 17 16:40:38 EDT 2015 : Listing and labeling requirements are already included in the chapter requirements.

31 8 of 66 5/18/2015 1:01 PM Second Revision No. 30-NFPA [ Section No ] All solvent in a facility and employed in drycleaning equipment shall comply with the provisions of this chapter and with the specific applicable requirements of Chapters 7 through 10, depending on the type of facility. Submittal Date: Tue Mar 17 16:39:27 EDT 2015 : Proper term is applicable, not specific.

32 9 of 66 5/18/2015 1:01 PM Second Revision No. 29-NFPA [ Section No ] Where a change in solvent class is proposed for use with existing equipment, the specific requirements of Section 6.2 and the applicable requirements of Chapters 7 through 10 applicable to the new solvent class shall be met 10 shall apply Where there is a change in the version of equipment is proposed, the specific requirements of Section 6.3 and the applicable requirements of Chapters 7 through 9 applicable to the new equipment shall be met shall apply. Submittal Date: Tue Mar 17 16:35:35 EDT 2015 Committee Statement: References to the applicable sections in Chapter 6 were added and language was cleaned up.

33 0 of 66 5/18/2015 1:01 PM Second Revision No. 4-NFPA [ Section No ] Equipment and solvent manufacturers and/or suppliers shall provide the facility operator with written instructions covering proper installation and safe use and operation. Submittal Date: Tue Mar 10 15:13:57 EDT 2015 Committee Statement: The committee agreed that suppliers in some cases are the ones who will provide instructions. Instructions should not just accompany the equipment and solvent but should be provided to the facility operator to ensure that the facility operator is held accountable to ensure that instructions are followed and that equipment and solvent are compatible. Response Message: Public Comment No. 5-NFPA [Section No ]

34 Second Revision No. 32-NFPA [ Section No. 6.2 ] 6.2 Change of Solvent Change of Solvent in a Different Class. The AHJ shall be notified of a proposed change in solvent class, in accordance with A change from a higher to a lower class of solvent for use in existing equipment shall be prohibited Where an existing facility proposes a change in solvent class with new equipment, the provisions of Chapters 4 through 9 shall be met for the new class of solvent The AHJ shall be notified of a proposed change in solvent class, in accordance with Where a change in solvent class is proposed for use with new or existing equipment, the provisions of Chapters 4 through 9 shall be met for the new solvent Change of Solvent Within the Same Class. A change of solvent within the same solvent class shall be allowed if one of the following conditions has been met: (1) The original equipment manufacturer accepts the solvent for use in the machine as indicated on the nameplate. (2) The facility owner has written documentation for the use of the solvent in the machine by the original equipment manufacturer. (3) The solvent manufacturer has obtained authorization from the equipment manufacturer for use of the solvent in the equipment Explosion Protection Hazards associated with the conversions described in shall be provided with explosion protection in accordance with Equipment with explosion hazards resulting from modification of existing equipment or change in solvent class from a previous approval shall be provided with explosion protection, in accordance with NFPA 69. Submittal Date: Tue Mar 17 16:55:47 EDT 2015 Committee Statement: Response Message: The requirements associated with a change of solvent both within the same class and with different classes were rewritten and included in Chapter 6. 1 of 66 5/18/2015 1:01 PM

35 Second Revision No. 33-NFPA [ Section No. 6.3 ] 6.3 Change in Version of Drycleaning Equipment in Existing Facilities The AHJ shall be notified of a proposed change in the version of equipment, in accordance with Where a change in the version of equipment occurs, the applicable provisions of Chapters 6 through 9 shall apply. Submittal Date: Tue Mar 17 17:01:56 EDT 2015 Committee Statement: Response Message: A change in version of drycleaning equipment is of concern in existing facilities since the electrical classifications of the equipment may not be appropriate for the class of solvent already in use. 2 of 66 5/18/2015 1:01 PM

36 3 of 66 5/18/2015 1:01 PM Second Revision No. 35-NFPA [ Section No ] All solvents Solvents used in equipment shall meet not be used unless they meet one of the following requirements: (1) The original equipment manufacturer shall obtain has provided authorization to use the solvent in the equipment as authorization to use the solvent in the equipment as indicated identified on the nameplate. (See Annex C.) (2) (3) * The solvent manufacturer shall provide test data and/or independent third-party documentation, including flashpoint, UFL, LFL, stability, and corrosivity for the machine. The original equipment manufacturer has provided written documentation authorizing the use of the solvent in the equipment. * A qualified testing laboratory or inspection agency concerned with product evaluations has provided evidence of solvent testing and equipment evaluation indicating the solvent can be used in the equipment. Supplemental Information File Name A6.5.3_3_.docx Description Submittal Date: Tue Mar 17 17:15:04 EDT 2015 Committee Statement: The type of documentation to show that a solvent is acceptable for use in equipment has been clarified.

37 A.6.5.3(3) Qualified testing laboratories may include third party independent laboratories or Nationally Recognized Testing Laboratories. Testing may include flashpoint, UFL, LFL, stability and corrosivity of the solvent.

38 Second Revision No. 34-NFPA [ Section No ] Flash Point and Flammability Limits * The solvent manufacturer shall be responsible for certifying the lower and upper flammability limits of the solvent under the anticipated conditions of drycleaning operations The solvent manufacturer shall be responsible for certifying the flash point of the solvent under the anticipated conditions of drycleaning operation operations The flash point of a solvent shall be determined in accordance with NFPA 30. Submittal Date: Tue Mar 17 17:08:17 EDT 2015 Committee Statement: Response Message: The solvent manufacturer should provide information on the flashpoint based on the use of the solvent in the drycleaning operation. If flashpoints are expected to change with continued recirculation and reuse of solvent, the manufacturer should provide that information to the user. 4 of 66 5/18/2015 1:01 PM

39 5 of 66 5/18/2015 1:01 PM Second Revision No. 5-NFPA [ Section No ] The solvent manufacturer or supplier shall be responsible for providing the user facility operator with specific written instructions for the proper use and safe handling of the product in the workplace and for updating the instructions in a timely fashion as necessary. Submittal Date: Tue Mar 10 15:29:07 EDT 2015 Committee Statement: The committee agreed that suppliers in some cases are the ones who will provide instructions. Instructions should be provided to the facility operator to ensure that the facility operator is held accountable to ensure that instructions are followed and that equipment and solvent are compatible. Response Message: Public Comment No. 6-NFPA [Section No ]

40 6 of 66 5/18/2015 1:01 PM Second Revision No. 37-NFPA [ Chapter 7 [Title Only] ] Type II Drycleaning Facility Facilities Submittal Date: Tue Mar 17 17:22:53 EDT 2015 : Applies to multiple facilities.

41 Second Revision No. 38-NFPA [ Section No. 7.2 ] 7.2 Location and Construction of Facility Facilities * Separation. Type II facilities located in buildings with other occupancies shall be separated vertically and horizontally from other occupancies in accordance with Section Facilities employing both Version II and Version III equipment shall comply with the provisions for Version II equipment, except where the equipment of each version is separated by the use of a drycleaning room in accordance with Facilities Using Version II Equipment Requiring Four-Hour Construction Facilities employing Version II equipment shall be separated from assembly, educational, day care, health care, detention, ambulatory health care, correctional, and residential occupancies by a fire barrier having a minimum fire resistance rating of 4 hours. Openings shall have a 3-hour fire rated assembly with self-closing or automatic-closing opening protection having a minimum 3-hour fire protection rating, devices except as permitted in In facilities where the quantity of Class II solvents in Version II equipment and storage does not exceed 568 L (150 gal), the required fire barrier shall be permitted to have a 2-hour fire resistance rating, with self-closing or automatic-closing opening protection having a hour fire protection rating providing the equipment incorporates an integral automatic fire-extinguishing system, is intrinsically safe, and is in a drycleaning room in accordance with Openings shall have a hour fire rated assembly with self-closing or automatic-closing devices Facilities Using Version II Equipment Requiring Two-Hour Construction Facilities employing Version II equipment shall be separated from business, factory/industrial, mercantile, and storage-type businesses, and other similar occupancies by a fire barrier having a minimum fire resistance rating of 2 hours. Openings shall have a hour fire rated assembly with self-closing or automatic-closing devices opening protection having a minimum hour fire protection rating, except as permitted in In facilities where the quantity of Class II solvents in Version II equipment and storage does not exceed 568L 568 L (150 gal), the required fire barrier shall be permitted to have a 1-hour fire resistance rating with self-closing or automatic-closing opening protection having a 3 4-hour fire protection rating, providing the equipment incorporates an integral automatic fire-extinguishing system, is intrinsically safe, and is in a drycleaning room in accordance with Openings shall have a hour fire rated assembly with self-closing or automatic-closing devices Facilities with Version III Equipment Requiring Four-Hour Construction Facilities employing Version III equipment shall be separated from assembly, educational, day care, health care, detention, ambulatory health care, correctional, and residential occupancies by a fire barrier having a minimum fire resistance rating of 4 hours. Openings shall have a 3-hour fire rated assembly with self-closing or automatic-closing opening protection having a minimum 3-hour fire protection rating, devices except as permitted in of 66 5/18/2015 1:01 PM

42 In facilities where the quantity of Class II solvents in Version III equipment and storage does not exceed 568 L (150 gal), the required fire barrier shall be permitted to have a 1-hour fire resistance rating with self-closing or automatic-closing opening protection rating with openings having a 3 4-hour fire protection rating, rated assembly with self-closing or automatic-closing devices providing the equipment incorporates an integral automatic fire-extinguishing system, and includes instrumentation, equipment, or controls that provide any one of the following: (1) Features that limit oxygen concentrations to less than 8 percent by volume (2) Features that limit solvent vapor concentration to less than 25 percent of the LEL (3)* Features that limit solvent vapor concentration at or below 60 percent of the LEL, where automatic instrumentation with safety interlocks is provided in accordance with NFPA Facilities with Version III Equipment Requiring Two-Hour Construction Facilities employing Version III equipment, shall be separated from business, factory/industrial, mercantile, and storage-type businesses and other similar occupancies by a fire barrier having a minimum fire resistance rating of 2 hours. Openings shall have a hour fire rated assembly with self-closing or automatic-closing with self-closing or automatic-closing opening protection having a minimum hour fire protection rating devices except as permitted in In facilities where the quantity of Class II solvents in Version III equipment and storage does not exceed 568 L (150 gal), the required fire barrier shall be permitted to have a 1-hour fire resistance rating with self- openings having a 3 4-hour fire rated assembly with self - closing or automatic-closing opening protection having a 3 4-hour fire protection rating closing devices, providing the equipment incorporates an integral automatic fire-extinguishing system, and includes instrumentation, equipment, or controls that provide any one of the following: (1) Features that limit oxygen concentrations to less than 8 percent by volume (2) Features that limit solvent vapor concentration to less than 25 percent of the LEL (3)* Features that limit solvent vapor concentration at or below 60 percent of the LEL, where automatic instrumentation with safety interlocks is provided in accordance with NFPA Drycleaning Room Where the quantity of solvent in equipment and storage exceeds 568 L (150 gal), the room where the equipment is used shall be separated from the rest of the facility by a fire barrier having a fire resistance rating of not less than 2 hours. Openings shall have a hour fire rated assembly with self-closing or automatic-closing opening protection having a minimum of hour fire protection rating devices Doors to drycleaning rooms shall remain closed during normal operations A facility that constructs a drycleaning room in accordance with to contain the equipment shall not be required to comply with for locations outside the drycleaning room. Submittal Date: Tue Mar 17 17:25:49 EDT of 66 5/18/2015 1:01 PM

43 9 of 66 5/18/2015 1:01 PM Committee Statement: The committee cleaned up language for fire ratings of materials of construction to be consistent with other NFPA codes. The committee added a requirement for doors to drycleaning rooms to remain closed during normal operations. This allows areas outside all drycleaning rooms to be unclassified. Response Message: Public Comment No. 7-NFPA [Section No ]

44 Second Revision No. 39-NFPA [ Section No ] Facilities shall be protected throughout by an approved automatic sprinkler system in accordance with except as permitted in Automatic sprinklers shall not be required in facilities where the quantity of Class II solvents for facilities using Version III equipment, and storage does not exceed 568 L (150 gal), providing the equipment incorporates an integral automatic fire-extinguishing system, and includes instrumentation, equipment, or controls that provide one of the following: (1) Features that limit oxygen concentrations to less than 8 percent by volume (2) Features that limit solvent vapor concentration to less than 25 percent of the LEL (3)* Features that limit solvent vapor concentration at or below 60 percent of the LEL, where automatic instrumentation with safety interlocks is provided in accordance with NFPA 69 Submittal Date: Tue Mar 17 17:59:40 EDT 2015 : Provides correct cross reference. 0 of 66 5/18/2015 1:01 PM

45 1 of 66 5/18/2015 1:01 PM Second Revision No. 59-NFPA [ Section No ] The required fire barrier shall be permitted to be a 1-hour resistance rating with self-closing or automaticclosing opening protection having a 3 4-hour fire protection rating in facilities where the quantity of Class III solvent in equipment and storage does not exceed 1250 L (330 gal) and equipment is provided with instrumentation, equipment systems, or controls that provide any one of the following features in : Features that limit oxygen concentrations to less than 8 percent by volume Features that limit solvent vapor concentrations to less than 25 percent of the LEL * Features that limit solvent vapor concentration at or below 60 percent of the LEL where automatic instrumentation with safety interlocks is provided in accordance with NFPA 69 Features that incorporate intrinsically safe equipment approved for use in Class I Division 2 hazardous locations and an integral automatic fire-extinguishing system conforming with Organization: National Fire Protection Assoc Submittal Date: Wed Apr 01 16:36:19 EDT 2015 Committee Statement: Response Message: The features are deleted from this section, instead pointing to the proper place in the chapter where the separation can be relaxed if machines have particular safety features. Since the location is already a Class I Division 2 then the requirement in #4 is redundant.

46 2 of 66 5/18/2015 1:01 PM Second Revision No. 60-NFPA [ Section No ] Electrical Installations. Electrical equipment and wiring in Type III facilities shall be in accordance with NFPA 70Class I Division 2, except as permitted in for ordinary locations. Organization: National Fire Protection Assoc Submittal Date: Wed Apr 01 16:38:53 EDT 2015 Committee Statement: Response Message: The default requirement for this chapter is Class I Division 2. If safety features are installed per then the electrical requirements can be relaxed.

47 3 of 66 5/18/2015 1:01 PM Second Revision No. 61-NFPA [ Section No ] Automatic sprinkler systems shall not be required in facilities where the quantity of Class III solvent in equipment and storage does not exceed 1250 L (330 gal) and if equipment is equippedwith has instrumentation, equipment systems, or controls that provide one of the following: features in Features that limit oxygen concentrations to less than 8 percent by volume Features that limit solvent vapor concentration to less than 25 percent of the LEL * Features that limit solvent vapor concentration at or below 60 percent of the LEL where automatic instrumentation with safety interlocks is provided in accordance with NFPA 69 Features that incorporate equipment approved for use in Class I Division 2 hazardous locations and integral automatic fire-extinguishing system conforming with Organization: National Fire Protection Assoc Submittal Date: Wed Apr 01 16:41:57 EDT 2015 : Default is automatic sprinklers unless safety features installed per

48 4 of 66 5/18/2015 1:01 PM Second Revision No. 66-NFPA [ Section No [Excluding any Sub-Sections] ] Equipment with drying capabilities, reclaiming dryers, or washers with solvent heating capabilities shall be equipped with all of the following except as permitted in : (1) Automatic extinguishing systems installed and maintained in accordance with , (2) Self-closing explosion hatch area equal to at least 0.22 m 2 /m 3 (1 ft 2 /15 ft 3 ) of cylinder volume (3) Hatches that open away from the operator Organization: National Fire Protection Assoc Submittal Date: Wed Apr 01 17:29:41 EDT 2015 : Provides correct cross reference in revised standard.

49 5 of 66 5/18/2015 1:01 PM Second Revision No. 67-NFPA [ Section No ] Automatic extinguishing systems and self-closing hatches shall not be required if the equipment has integrated instrumentation, equipment systems, or controls that independently provide any one of the following: (1) Features that limit oxygen concentrations to less than 8 percent by volume (2) Features that limit solvent vapor concentrations to less than 25 percent of the LEL (3)* Features that limit solvent vapor concentration at or below 60 percent of the LEL where automatic instrumentation with safety interlocks is provided in accordance with NFPA 69 Organization: National Fire Protection Assoc Submittal Date: Thu Apr 02 10:57:26 EDT 2015 : The term systems replaces the term equipment for consistency in the document.

50 6 of 66 5/18/2015 1:01 PM Second Revision No. 65-NFPA [ Section No ] If a relief valve is provided, it shall be equipped with a vent line extending to the outside of the building. Organization: National Fire Protection Assoc Submittal Date: Wed Apr 01 17:28:23 EDT 2015 : Change clarifies that not outside the machine but outside the building.

51 7 of 66 5/18/2015 1:01 PM Second Revision No. 62-NFPA [ Section No ] * For equipment in which solvent is ordinarily For equipment in which solvent is heated heated above ambient temperatures in washing or drying to a temperature that allows the solvent vapor concentration to equal or exceed 25 percent of the LEL, the electrical equipment and wiring shall be designed to greater than 16.7 C (30 F) below the flash point, in the drying phase the electrical components and wiring on such equipment shall be in accordance with NFPA 70 Class I Division 2, except as permitted in Supplemental Information File Name A docx Description Organization: National Fire Protection Assoc Submittal Date: Wed Apr 01 16:44:56 EDT 2015 Committee Statement: Response Message: The committee recognized that there is no data showing that maintaining temperatures less than 30 degrees below the flashpoint keeps LEL concentrations to less than 25%. The more critical issue is the LEL therefore the requirements for electrical equipment are tied into the temperature at which the solvent reaches 25% LEL concentration rather than to the 30 degrees below the flashpoint. Annex material has been added to explain the requirement.

52 A Each solvent has a temperature at which vapor concentrations are produced that reach 25% of the LEL for that solvent. Either the solvent manufacturer should provide the equipment manufacturer with the temperatures that causes that solvent to reach 25% of the LEL or the equipment manufacturer should test the solvent to determine this temperature. The equipment that is approved for the solvent would have the ability to control the heating of the solvent to a level below 25% of the LEL based on the solvent that is approved for use in the machine. Equipment does not necessarily require an LEL measuring device.

53 8 of 66 5/18/2015 1:01 PM Second Revision No. 63-NFPA [ Sections , ] The electrical equipment and wiring on equipment without stills shall be in accordance with NFPA 70, and contain as long as it contains instrumentation, equipment systems, or controls that are active in washing or drying that provide any one or combination of the following: (1) Features that limit oxygen concentrations to less than 8 percent by volume (2) Features that limit solvent vapor concentration to less than 25 percent of the LEL (3)* Features that limit solvent vapor concentration at or below 60 percent of the LEL where automatic instrumentation with safety interlocks is provided in accordance with NFPA The electrical equipment and wiring on equipment with stills shall be in accordance with NFPA 70, and contain instrumentation, equipment, or controls that can automatically de-energize equipment if the Visual and audible alarm devices and automatic shutdown of non-safety related components shall be provided to de-energize equipment if its integrity of the still has been compromised and is not functioning as designed. Organization: National Fire Protection Assoc Submittal Date: Wed Apr 01 17:01:22 EDT 2015 Committee Statement: Response Message: These changes were made to clarify that safety features are working during the correct portion of a drycleaning cycle.

54 9 of 66 5/18/2015 1:01 PM Second Revision No. 64-NFPA [ Sections , ] For equipment in which solvent is ordinarily heated at or greater than 16.7 C (30 F) below the flash point, in the washing phase the electrical components and wiring on such equipment shall be in accordance with NFPA 70, Class I Division 2, except as permitted in Equipment in which solvent is heated at or greater than 16.7 C (30 F) below the flash point in the washing, draining, and extraction phases, and has instrumentation, equipment, or controls active during such time that provide any one of the following shall be in accordance with NFPA 70 for ordinary locations: Features that limit oxygen concentrations to less than 8 percent by volume Features that limit solvent vapor concentration to less than 25 percent of the LEL Features that limit solvent vapor concentration at or below 60 percent of the LEL where automatic instrumentation with safety interlocks is provided in accordance with NFPA 69 Organization: National Fire Protection Assoc Submittal Date: Wed Apr 01 17:24:56 EDT 2015 : These requirements have been consolidated and included in

55 0 of 66 5/18/2015 1:01 PM Second Revision No. 40-NFPA [ Section No ] This chapter shall apply to drycleaning facilities or systems utilizing Class IV solvents. Submittal Date: Thu Mar 19 16:04:53 EDT 2015 : Editorial. No needed since no

56 1 of 66 5/18/2015 1:01 PM Second Revision No. 41-NFPA [ Section No ] Electrical. All electrical equipment, devices, and wiring for light and power shall be installed in accordance with the requirements of NFPA 70 for ordinary locations. Submittal Date: Thu Mar 19 16:05:46 EDT 2015 : Editorial. No so not needed.

57 2 of 66 5/18/2015 1:01 PM Second Revision No. 42-NFPA [ Section No ] Atmospheric solvent stills shall be constructed to prevent hot solvent vapor from escaping into the facility where operated under normal conditions and at rated capacity. Submittal Date: Thu Mar 19 16:06:40 EDT 2015 Committee Statement: Response Message: Extra wording did not add any information to the text. Stills would always be operated at normal conditions and capacity.

58 3 of 66 5/18/2015 1:01 PM Second Revision No. 43-NFPA [ Section No ] * A Where carbon dioxide storage tanks are installed inside buildings, a listed gas detection system with an audible local alarm shall be installed in indoor storage areas and used to notify the building occupants if the a leak of carbon dioxide concentration reaches an unsafe level occurs. Supplemental Information File Name A docx Description Submittal Date: Thu Mar 19 16:08:32 EDT 2015 Committee Statement: Response Message: It is difficult to determine what an "unsafe level" of CO2 would be and this language is vague and unenforceable. The concern is with any leak of CO2. Annex material was added to further explain where gas detectors should be installed.

59 A Consideration shall be given to the possibility of carbon dioxide drifting and settling into adjacent places outside of where the carbon dioxide is used. A detection system should also be installed in that location.

60 4 of 66 5/18/2015 1:01 PM Second Revision No. 44-NFPA [ Section No ] Consideration shall be given to the possibility of carbon dioxide drifting and settling into adjacent places outside of where the carbon dioxide is used, and a detection system shall be installed in that location. Submittal Date: Thu Mar 19 16:13:07 EDT 2015 : This information was moved to annex for

61 5 of 66 5/18/2015 1:01 PM Second Revision No. 45-NFPA [ Section No ] Intentional or unintentional venting Venting from the equipment shall be released to the outdoors in a location a safe distance away from any air intake to prevent re- entrainment. Submittal Date: Thu Mar 19 16:14:07 EDT 2015 : Reworded to clarify the requirement is to vent outdoors away from air intakes.

62 6 of 66 5/18/2015 1:01 PM Second Revision No. 46-NFPA [ Section No ] Maintenance on the equipment shall be performed by qualified trained personnel in accordance with manufacturers recommendations. Submittal Date: Thu Mar 19 16:16:00 EDT 2015 : All maintenance should be in accordance with mfrs recommendations.

63 7 of 66 5/18/2015 1:01 PM Second Revision No. 47-NFPA [ Chapter 10 [Title Only] ] Laundry and Wetcleaning Equipment in Drycleaning Facilities Submittal Date: Thu Mar 19 16:17:50 EDT 2015 : Chapter also applies to wetcleaning when in drycleaning facilities.

64 8 of 66 5/18/2015 1:01 PM Second Revision No. 48-NFPA [ Section No ] Location. Equipment shall be located in facilities with an intake and outlet exhaust air exchange equal to or exceeding the air exchange required for the equipment. Submittal Date: Thu Mar 19 16:18:39 EDT 2015 : Exhaust is the proper term., not outlet.

65 9 of 66 5/18/2015 1:01 PM Second Revision No. 49-NFPA [ Section No ] Laundry Dryer Temperature Control. Laundry dryers, as used in drycleaning facilities, shall be equipped with safety controls to ensure proper temperature and cool-down of textiles prior to the equipment being unloaded. The textiles shall be cooled down in such a way that the risk of spontaneous combustion is safely eliminated. Submittal Date: Thu Mar 19 16:19:17 EDT 2015 Committee Statement: Clarified that this section applied to laundry dryers. Removed vague unenforceable language.

66 0 of 66 5/18/2015 1:01 PM Second Revision No. 50-NFPA [ Section No. A.7.1 ] A.7.1 Version I equipment for Type II facilities is prohibited per Submittal Date: Thu Mar 19 16:27:06 EDT 2015 : Changed to proper references.

67 1 of 66 5/18/2015 1:01 PM Second Revision No. 51-NFPA [ Section No. A ] A See NFPA 12 NFPA 704 for guidance on labeling for emergency response. See NFPA 12 for additional information on signage for carbon dioxide systems. Some examples of signage are as follows: Typical sign where carbon dioxide is stored or used: WARNING CARBON DIOXIDE GAS WHEN ALARM OPERATES, VACATE IMMEDIATELY. Typical sign in nearby space where carbon dioxide can accumulate to hazardous levels: CAUTION CARBON DIOXIDE IN A NEARBY SPACE CAN COLLECT HERE. WHEN ALARM OPERATES, VACATE IMMEDIATELY. Typical sign outside each entrance to carbon dioxide storage rooms: CAUTION CARBON DIOXIDE GAS VENTILATE THE AREA BEFORE ENTERING. A HIGH CARBON DIOXIDE GAS CONCENTRATION CAN OCCUR IN THIS AREA AND CAN CAUSE SUFFOCATION. Submittal Date: Thu Mar 19 16:28:28 EDT 2015 Committee Statement: reference to NFPA 704 added. Removed examples and instead referred to NFPA 12 for additional information.

68 2 of 66 5/18/2015 1:01 PM Second Revision No. 56-NFPA [ Section No. B.1 ] B.1 Figure B.1 shows a flowchart for determining the requirements in NFPA 32 based on the type of facility and the version of equipment in use. Figure B.1 NFPA 32 Document Requirements Flowchart. Supplemental Information File Name FINALAnnex_B_32.docx Description Organization: National Fire Protection Assoc Submittal Date: Thu Mar 26 16:04:12 EDT 2015 : Updated figure.

69 Determine Type of Facility based on Lowest Class of Solvent Used in Drycleaning operation 2,3 Commented [PN1]: Insert Title NFPA Document Flowchart Type I Facility Prohibited 1 Type II Facility Chapter 7 Type III Facility Chapter 8 Type IV Facility Chapter 9 Determine Version of Equipment Determine Version of Equipment Determine Version of Equipment Version II Version III Version II Version III Version II Version III Version IV Facility Types- Facility type is defined based on the lowest numerical class of solvent used in the equipment. Type I Facility. Facilities employing class I solvents. Type II Facility. Facilities employing class II solvents. Type III Facility. Facilities employing class IIIA and IIIB solvents. Type IV Facility. Facilities employing class IV solvents. Equipment Versions Version I Equipment. Flowchart for determining the requirements in NFPA 32 based on Type of An open system employing either combustible or noncombustible liquid that is continuously open to the atmosphere facility and version of equipment in use. Version II Equipment. An open-circuit system employing combustible or noncombustible liquid, that releases fugitive emissions, suppresses and controls combustion, and that has safety controls. Version III Equipment. A closed-loop system employing combustible or noncombustible liquid that does not release emissions, prevents combustion, and that has safety controls. Version IV Equipment. A closed-loop system for noncombustible liquids that has safety controls and that does not release emissions. 1. Type I Facilities are prohibited per Drycleaning operations that also have laundry or wetcleaning operations should also refer to Chapter The requirements of Chapters 4 6 apply to all facilities.

70 3 of 66 5/18/2015 1:01 PM Second Revision No. 52-NFPA [ Section No. C.1.1 ] D.1.1 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, 2015 edition. NFPA 30, Flammable and Combustible Liquids Code, 2015 edition. NFPA 58, Liquefied Petroleum Gas Code, 2014 edition. NFPA 77, Recommended Practice on Static Electricity, 2014 edition. NFPA 704, Standard System for the Identification of the Hazards of Materials for Emergency Response, 2012 edition. Fire Protection Guide to Hazardous Materials, 14th edition, Submittal Date: Thu Mar 19 16:30:21 EDT 2015 : reference added in

71 4 of 66 5/18/2015 1:01 PM Second Revision No. 54-NFPA [ Section No. C ] D ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM D56, Test Standard Test Method for Flash Point by Tag Closed Cup Tester, ASTM D93, Standard Test Methods for Flash Point by Pensky Martens Closed Cup Tester, Submittal Date: Fri Mar 20 11:19:13 EDT 2015 : Updated to current editions and titles.

72 5 of 66 5/18/2015 1:01 PM Second Revision No. 53-NFPA [ Section No. C ] D U.S. Government Publications. U.S. Government Printing Office, Washington, DC Title 29, Code of Federal Regulations, Part , Employee Emergency Plans and Fire Prevention Plans, 1998 Plans. Title 29, Code of Federal Regulations, Part , Fire Brigades, 1998 Brigades. Title 29, Code of Federal Regulations, Part , Hazard Communication, 1998 Communication. Submittal Date: Fri Mar 20 11:12:12 EDT 2015 Committee Statement: Response Message: The CFRs are published each date but the date does not necessarily reflect a change in the regulation. Date is meaningless.

73 Second Revision No. 57-NFPA [ New Section after C.3 ] Annex C Solvent Characteristics C.1 Typical Drycleaning Solvent Characteristics Figure C.1 is not comprehensive. It is provided only as a reference for AHJs to assist in the application of requirements in NFPA 32. SDSs should be consulted prior to such application of the requirements of this standard. Figure C.1 Typical Drycleaning Solvent Characteristics. Supplemental Information File Name FINAL_ANNEX_C_SOLVENT_CHARATERISTICS.xlsx Description Organization: National Fire Protection Assoc Submittal Date: Fri Mar 27 11:03:28 EDT 2015 Committee Statement: Response Message: A new annex C has been added to provide AHJs with information on the range of solvents and solvent properties typically found in drycleaning. 6 of 66 5/18/2015 1:01 PM

Committee Input No. 60-NFPA [ Sections , ]

Committee Input No. 60-NFPA [ Sections , ] Page 1 of 15 Committee Input No. 60-NFPA 34-2013 [ Sections 3.3.7.1, 3.3.7.2 ] Sections 3.3.7.1, 3.3.7.2 3.3.7.1 Combustible Liquid. A Any liquid that has a closed-cup flash point at or above 100 F (37.8

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Page 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments: Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS Page 1 of 6 CENTRAL STATE HOSPITAL PLAN SUBJECT: SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS ANNUAL REVIEW MONTH: RESPONSIBLE FOR REVIEW: APRIL CSH SAFETY DIRECTOR LAST REVISION

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

Page 1 of 12 Input No. 62-NFPA 409-2013 [ Section No. 3.3.9 ] 3.3.9 Hangar Building Cluster. A group of buildings with more than one area for the storage and servicing of aircraft and all attached or contiguous

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

(h) Pesticide Application.

(h) Pesticide Application. Fire Code Cannabis Amendment Section 13.20.066 is added to the Marysville Municipal Code to read in its entirety as follows: 13.20.066 Cannabis Growing, Processing, or Extraction Facilities (a) Application.

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 1410-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 1500, Standard on Fire Department

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

First Revision No. 106-NFPA [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 106-NFPA [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 106-NFPA 86-2012 [ Chapter NFPA ] 7.4.10.2* The number of safety shutoff valve cycles shall be determined by one of the following ways: (1) Counting of actual safety shutoff valve open-closed

More information

Page 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Technical Policy Title: Plant Processing and Extraction

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting. Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

Public Input No. 3-NFPA [ Chapter 2 ]

Public Input No. 3-NFPA [ Chapter 2 ] Public Input No. 3-NFPA 655-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] 1 of 58 10/28/2015 10:15 AM First Revision No. 5015-NFPA 5000-2015 [ Section No. 3.3.628.11 ] 3.3.633.11* Parking Structure. A building, structure, or portion thereof used for the parking, storage, or

More information

Page 1 of /11/2016 2:36 PM. First Revision No. 30-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Page 1 of /11/2016 2:36 PM. First Revision No. 30-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 90 10/11/2016 2:36 PM First Revision No. 30-NFPA 652-2016 [ Global Input ] All instances of Dust Hazard Analysis should be Dust Hazards Analysis. Please change to the plural all throughout Organization:

More information

Page 1 of 190 Public Input No. 22-NFPA 55-2013 [ Global Input ] Throughout the document, delete ANSI from ANSI/ASME B31.3. Current Text: (multiple locations) ANSI/ASME B31.3 (found in Subsections: 2.3.2

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials Fire Preven4on Officers Associa4on of Bri4sh Columbia 2013 Annual Seminar Kelowna, Bri4sh Columbia May 9, 2013 NFPA 33 Scope

More information

Part I Extraction Process Equipment

Part I Extraction Process Equipment 745 West Colfax Avenue Denver, CO 80204 p: 720.913.3474 f: 720.913.3596 www.denvergov.org/fire MARIJUANA EXTRACTION GUIDELINE FOR COMMERCIAL / LICENSED FACILITIES The information contained within this

More information

The Committee updated the edition dates for the reference sources for extracted text within the standard per the NFPA Manual of Style.

The Committee updated the edition dates for the reference sources for extracted text within the standard per the NFPA Manual of Style. Second Revision No. 51-NFPA 86-2013 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 54, National Fuel Gas Code, 2009 2015 edition. NFPA 69, Standard on Explosion Prevention

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60079-29-2 Edition 2.0 2015-03 Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen INTERNATIONAL

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems Products Solutions Services CT287 Hazardous Area Classifications and Protection Systems Slide 1 Topics covered Types of Hazardous Area classifications with focus on North America Types of hazardous protection

More information

NFPA 37 Public Comment Responses Page 1 of 32

NFPA 37 Public Comment Responses Page 1 of 32 of 30 11/4/2016 3:05 PM Public Comment No. 6-NFPA 37-2016 [ New Section after 1.6 ] TITLE OF NEW CONTENT Type your content here... 1.7 Pressure Measurement. All pressures expressed in this document are

More information

Working safely with flammable liquids

Working safely with flammable liquids Flammable Liquids Fire hazards are associated with vapors from the flammable liquid. In order for a fire to occur, the following conditions must be met: Concentration of the vapor must be between the upper

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document National Fire Protection Association Report of 113 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 2/9/2016 10:50 AM Public Input No. 1-NFPA 87-2015 [ Global Input ] Throughout standard

More information

OUTLINE FOR FIRE PREVENTION ACTIVITY

OUTLINE FOR FIRE PREVENTION ACTIVITY OUTLINE FOR FIRE PREVENTION ACTIVITY Background Buildings under construction present unique fire exposures that require special attention. Fires can result in major losses and long delays in the completion

More information

Fire Prevention Plan Program

Fire Prevention Plan Program Fire Prevention Plan Program Effective Date: Revision #: Reference Standard Purpose Occupational Safety and Health Administration (OSHA) standard, 29 CFR 1910.39 Subpart E, Fire Prevention Plan This procedure

More information

AS/NZS :2008

AS/NZS :2008 AS/NZS 60079.29.2:2008 Australian/New Zealand Standard Explosive atmospheres Part 29.2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen AS/NZS 60079.29.2:2008

More information

Plant Processing and Extraction Facilities

Plant Processing and Extraction Facilities Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6180 Plant Processing and Extraction Facilities Guideline G-16 Serving the

More information

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ]

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ] of 46 11/6/2015 9:21 AM First Revision No. 208-NFPA 30-2015 [ Section No. 9.3.3.1 ] 9.3.3.1 Storage of liquids shall not physically obstruct a means of egress. Submittal Date: Wed Sep 09 18:24:20 EDT 2015

More information

BUILDING/FIRE CODE REFERENCES 2006 EDITION

BUILDING/FIRE CODE REFERENCES 2006 EDITION BUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform Fire The IBC references the IFC in 97 Code sections. This document

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Special Occupancy Requirements

Special Occupancy Requirements Special Occupancy Requirements CHAPTER 2 0 AVIATION FACILITIES CHAPTER 2 1 DRY CLEANING CHAPTER 2 2 COMBUSTIBLE DUST-PRODUCING OPERATIONS Special Occupancies The objective of this module is to make the

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Chapter 2: Definitions

Chapter 2: Definitions FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter

More information

ARTICLE 25. FUEL GAS CODE

ARTICLE 25. FUEL GAS CODE ARTICLE 25. Rule 1. Indiana Fuel Gas Code, 2003 Edition (Repealed) (Repealed by Fire Prevention and Building Safety Commission; filed Mar 18, 2008, 2:32 p.m.: 20080423-IR-675070479FRA, eff 90 days after

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference: Oklahoma 310:451-1-3. Adopted references The Board of Health hereby incorporates by reference the International Code Council (ICC) 2006 (IBC) Edition International Building Code; the 2007 Edition Standard

More information

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations Understanding Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations Michigan Safety Conference April 11, 2017 Mike Snyder PE CSP CFPS Vice President Organizational

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

Fluid Collections at the Smithsonian. Michael Kilby, P.E. Joshua Stewart, P.E. Office of Safety, Health & Environmental Management (OSHEM)

Fluid Collections at the Smithsonian. Michael Kilby, P.E. Joshua Stewart, P.E. Office of Safety, Health & Environmental Management (OSHEM) Fluid Collections at the Smithsonian Michael Kilby, P.E. Joshua Stewart, P.E. Office of Safety, Health & Environmental Management (OSHEM) Who We Are OSHEM Authority Having Jurisdiction for Smithsonian

More information

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS INTERNATIONAL MARITIME ORGANIZATION E IMO ASSEMBLY 23rd session Agenda item 17 A 23/Res.951 25 February 2004 Original: ENGLISH Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED

More information

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Fire Protection I. INTRODUCTION II. GENERAL GUIDELINES III.

More information

2010 FIRE CODE OF NEW YORK STATE

2010 FIRE CODE OF NEW YORK STATE 2010 FIRE CODE OF NEW YORK STATE CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 1401 GENERAL 1401.1 Scope. This chapter shall apply to structures in the course of construction, alteration,

More information

First Revision No. 15-NFPA [ Chapter 2 ]

First Revision No. 15-NFPA [ Chapter 2 ] Page 1 of 28 First Revision No. 15-NFPA 91-2013 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification Electrical Engineering Guide for Determining Electrical Area Classification PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice

More information

NFPA 86 Commitee Inputs Page 1 of 45

NFPA 86 Commitee Inputs Page 1 of 45 of 44 1/26/2017 2:28 PM Committee Input No. 102-NFPA 86-2016 [ Global Input ] The Committee is considering language for pre-purge of the work chambers for Class A, Class B and Class C furnaces. This could

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical on Laser Fire Protection Kimberly

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY

CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY PURPOSE The fire prevention plan provides information and procedures to minimize the occurrence of an accidental fire at the job site or office, and an efficient

More information

WSU-TFREC Fire Safety Training

WSU-TFREC Fire Safety Training WSU-TFREC Fire Safety Training WSU-TFREC Locate the nearest exits, alarms and fire extinguishers to your work area Floor plans are available online: Overley Building http://www.tfrec.wsu.edu/pages/safety/overley_building_floor_plan

More information

Airborne Toxic Control Measure for Emissions of Perchloroethylene from Dry Cleaning Operations

Airborne Toxic Control Measure for Emissions of Perchloroethylene from Dry Cleaning Operations Airborne Toxic Control Measure for Emissions of Perchloroethylene from Dry Cleaning Operations This page revised January 7, 2003 Final Regulation Order APPROVED BY THE OFFICE OF ADMINISTRATIVE LAW ON MAY

More information

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen IEC 60079-29-2 Edition 2.0 2015-03 REDLINE VERSION colour inside Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Making sense of risk Risk engineering. Metalworking operations

Making sense of risk Risk engineering. Metalworking operations Making sense of risk Risk engineering Metalworking operations Metalworking operations Metalworking operations involve the fabrication of ferrous or nonferrous metal products, structural metal products,

More information

Second Revision No. 2-NFPA [ Section No ]

Second Revision No. 2-NFPA [ Section No ] Page 1 of 8 Second Revision No. 2-NFPA 410-2014 [ Section No. 10.2 ] 10.2* Fire Extinguishers. In addition to extinguishers required by NFPA 409, extinguishers shall be provided for aircraft maintenance

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

Committee Input No. 28-NFPA 13R-2013 [ Global Input ] Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.

More information

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 1. Purpose This policy sets forth requirements for preventing and detecting fires, sounding an alarm, and suppressing fires. Fire protection

More information