Installation Manual. This panel will not operate if installed outside of North America. See section 1.1 for details.

Size: px
Start display at page:

Download "Installation Manual. This panel will not operate if installed outside of North America. See section 1.1 for details."

Transcription

1 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read. This panel will not operate if installed outside of North America. See section 1.1 for details. Installation Manual Software Version 2.3 (50/50) DLS-1 v6.7 and up See Back Cover for New Features in Version 2.3

2 WARNING Please Read Carefully Note to Installers This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users of this system. System Failures This system has been carefully designed to be as effective as possible. There are circumstances, however, involving fire, burglary, or other types of emergencies where it may not provide protection. Any alarm system of any type may be compromised deliberately or may fail to operate as expected for a variety of reasons. Some but not all of these reasons may be: Inadequate Installation A security system must be installed properly in order to provide adequate protection. Every installation should be evaluated by a security professional to ensure that all access points and areas are covered. Locks and latches on windows and doors must be secure and operate as intended. Windows, doors, walls, ceilings and other building materials must be of sufficient strength and construction to provide the level of protection expected. A reevaluation must be done during and after any construction activity. An evaluation by the fire and/or police department is highly recommended if this service is available. Criminal Knowledge This system contains security features which were known to be effective at the time of manufacture. It is possible for persons with criminal intent to develop techniques which reduce the effectiveness of these features. It is important that a security system be reviewed periodically to ensure that its features remain effective and that it be updated or replaced if it is found that it does not provide the protection expected. Access by Intruders Intruders may enter through an unprotected access point, circumvent a sensing device, evade detection by moving through an area of insufficient coverage, disconnect a warning device, or interfere with or prevent the proper operation of the system. Power Failure Control units, intrusion detectors, smoke detectors and many other security devices require an adequate power supply for proper operation. If a device operates from batteries, it is possible for the batteries to fail. Even if the batteries have not failed, they must be charged, in good condition and installed correctly. If a device operates only by AC power, any interruption, however brief, will render that device inoperative while it does not have power. Power interruptions of any length are often accompanied by voltage fluctuations which may damage electronic equipment such as a security system. After a power interruption has occurred, immediately conduct a complete system test to ensure that the system operates as intended. Failure of Replaceable Batteries This system s wireless transmitters have been designed to provide several years of battery life under normal conditions. The expected battery life is a function of the device environment, usage and type. Ambient conditions such as high humidity, high or low temperatures, or large temperature fluctuations may reduce the expected battery life. While each transmitting device has a low battery monitor which identifies when the batteries need to be replaced, this monitor may fail to operate as expected. Regular testing and maintenance will keep the system in good operating condition. Compromise of Radio Frequency (Wireless) Devices Signals may not reach the receiver under all circumstances which could include metal objects placed on or near the radio path or deliberate jamming or other inadvertent radio signal interference. System Users A user may not be able to operate a panic or emergency switch possibly due to permanent or temporary physical disability, inability to reach the device in time, or unfamiliarity with the correct operation. It is important that all system users be trained in the correct operation of the alarm system and that they know how to respond when the system indicates an alarm. Smoke Detectors Smoke detectors that are a part of this system may not properly alert occupants of a fire for a number of reasons, some of which follow. The smoke detectors may have been improperly installed or positioned. Smoke may not be able to reach the smoke detectors, such as when the fire is in a chimney, walls or roofs, or on the other side of closed doors. Smoke detectors may not detect smoke from fires on another level of the residence or building. Every fire is different in the amount of smoke produced and the rate of burning. Smoke detectors cannot sense all types of fires equally well. Smoke detectors may not provide timely warning of fires caused by carelessness or safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches or arson. Even if the smoke detector operates as intended, there may be circumstances when there is insufficient warning to allow all occupants to escape in time to avoid injury or death. Motion Detectors Motion detectors can only detect motion within the designated areas as shown in their respective installation instructions. They cannot discriminate between intruders and intended occupants. Motion detectors do not provide volumetric area protection. They have multiple beams of detection and motion can only be detected in unobstructed areas covered by these beams. They cannot detect motion which occurs behind walls, ceilings, floor, closed doors, glass partitions, glass doors or windows. Any type of tampering whether intentional or unintentional such as masking, painting, or spraying of any material on the lenses, mirrors, windows or any other part of the detection system will impair its proper operation. Passive infrared motion detectors operate by sensing changes in temperature. However their effectiveness can be reduced when the ambient temperature rises near or above body temperature or if there are intentional or unintentional sources of heat in or near the detection area. Some of these heat sources could be heaters, radiators, stoves, barbeques, fireplaces, sunlight, steam vents, lighting and so on. Warning Devices Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone sleeping if there is an intervening wall or door. If warning devices are located on a different level of the residence or premise, then it is less likely that the occupants will be alerted or awakened. Audible warning devices may be interfered with by other noise sources such as stereos, radios, televisions, air conditioners or other appliances, or passing traffic. Audible warning devices, however loud, may not be heard by a hearing-impaired person. Telephone Lines If telephone lines are used to transmit alarms, they may be out of service or busy for certain periods of time. Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may be difficult to detect. Insufficient Time There may be circumstances when the system will operate as intended, yet the occupants will not be protected from the emergency due to their inability to respond to the warnings in a timely manner. If the system is monitored, the response may not occur in time to protect the occupants or their belongings. Component Failure Although every effort has been made to make this system as reliable as possible, the system may fail to function as intended due to the failure of a component. Inadequate Testing Most problems that would prevent an alarm system from operating as intended can be found by regular testing and maintenance. The complete system should be tested weekly and immediately after a break-in, an attempted break-in, a fire, a storm, an earthquake, an accident, or any kind of construction activity inside or outside the premises. The testing should include all sensing devices, keypads, consoles, alarm indicating devices and any other operational devices that are part of the system. Security and Insurance Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm system also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation. Limited Warranty Digital Security Controls Ltd. warrants the original purchaser that for a period of twelve months from the date of purchase, the product shall be free of defects in materials and workmanship under normal use. During the warranty period, Digital Security Controls Ltd. shall, at its option, repair or replace any defective product upon return of the product to its factory, at no charge for labour and materials. Any replacement and/ or repaired parts are warranted for the remainder of the original warranty or ninety (90) days, whichever is longer. The original owner must promptly notify Digital Security Controls Ltd. in writing that there is defect in material or workmanship, such written notice to be received in all events prior to expiration of the warranty period. International Warranty The warranty for international customers is the same as for any customer within Canada and the United States, with the exception that Digital Security Controls Ltd. shall not be responsible for any customs fees, taxes, or VAT that may be due. Warranty Procedure To obtain service under this warranty, please return the item(s) in question to the point of purchase. All authorized distributors and dealers have a warranty program. Anyone returning goods to Digital Security Controls Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will not accept any shipment whatsoever for which prior authorization has not been obtained. Conditions to Void Warranty This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover: damage incurred in shipping or handling; damage caused by disaster such as fire, flood, wind, earthquake or lightning; damage due to causes beyond the control of Digital Security Controls Ltd. such as excessive voltage, mechanical shock or water damage; damage caused by unauthorized attachment, alterations, modifications or foreign objects; damage caused by peripherals (unless such peripherals were supplied by Digital Security Controls Ltd.); defects caused by failure to provide a suitable installation environment for the products; damage caused by use of the products for purposes other than those for which it was designed; damage from improper maintenance; damage arising out of any other abuse, mishandling or improper application of the products. Digital Security Controls Ltd. s liability for failure to repair the product under this warranty after a reasonable number of attempts will be limited to a replacement of the product, as the exclusive remedy for breach of warranty. Under no circumstances shall Digital Security Controls Ltd. be liable for any special, incidental, or consequential damages based upon breach of warranty, breach of contract, negligence, strict liability, or any other legal theory. Such damages include, but are not limited to, loss of profits, loss of the product or any associated equipment, cost of capital, cost of substitute or replacement equipment, facilities or services, down time, purchaser s time, the claims of third parties, including customers, and injury to property. Disclaimer of Warranties This warranty contains the entire warranty and shall be in lieu of any and all other warranties, whether expressed or implied (including all implied warranties of merchantability or fitness for a particular purpose) And of all other obligations or liabilities on the part of Digital Security Controls Ltd. Digital Security Controls Ltd. neither assumes nor authorizes any other person purporting to act on its behalf to modify or to change this warranty, nor to assume for it any other warranty or liability concerning this product. This disclaimer of warranties and limited warranty are governed by the laws of the province of Ontario, Canada. WARNING: Digital Security Controls Ltd. recommends that the entire system be completely tested on a regular basis. However, despite frequent testing, and due to, but not limited to, criminal tampering or electrical disruption, it is possible for this product to fail to perform as expected. Installer s Lockout Any products returned to DSC which have the Installer s Lockout option enabled and exhibit no other problems will be subject to a service charge. Out of Warranty Repairs Digital Security Controls Ltd. will at its option repair or replace out-of-warranty products which are returned to its factory according to the following conditions. Anyone returning goods to Digital Security Controls Ltd. must first obtain an authorization number. Digital Security Controls Ltd. will not accept any shipment whatsoever for which prior authorization has not been obtained. Products which Digital Security Controls Ltd. determines to be repairable will be repaired and returned. A set fee which Digital Security Controls Ltd. has predetermined and which may be revised from time to time, will be charged for each unit repaired. Products which Digital Security Controls Ltd. determines not to be repairable will be replaced by the nearest equivalent product available at that time. The current market price of the replacement product will be charged for each replacement unit.

3 Table of Contents Section 1: System Introduction Specifications Additional Devices Out of the Box...2 Section 2: Getting Started Installation Steps Terminal Descriptions Keybus Operation and Wiring Current Ratings Modules and Accessories Keypad Assignment Supervision Removing Modules Zone Wiring Fire Zone Wiring Hr Auxiliary Input Wiring (PGM2) LINKS Zone Wiring* Keypad Zones...7 Section 3: Keypad Commands Arming and Disarming Auto Bypass Stay Arming Automatic Arming [*] Commands Function Keys Features Available for the LCD5500Z...12 Section 4: How to Program Installer s Programming Programming Decimal Data Programming HEX Data Programming Toggle Option Sections Viewing Programming...14 Section 5: Program Descriptions Programming Security Codes Zone Programming Zone Attributes Assigning Keypad Zones Communicator Dialing Communicator Account Numbers Communicator Telephone Numbers Communicator Reporting Codes Communicator Reporting Formats Downloading PGM Output Options Telephone Line Monitor (TLM) Bell Test Transmission Transmission Delay Fire, Auxiliary and Panic Keys Arming/Disarming Options Entry/Exit Delay Options Swinger Shutdown Event Buffer Keypad Lockout Options Keypad Blanking Keypad Backlighting Loop Response Keypad Tampers LINKS1000 Cellular Communicator* Additional System Modules* Resetting Factory Defaults* Installer s Lockout Walk Test (Installer) Section 6: Programming Worksheets 27 Appendix A: Reporting Codes 42 Appendix B: Programming LCD Keypads 44 i

4 ii PC5008 Wiring Diagram

5 Section 1: System Introduction 1.1 Specifications Downloading Software Support PC5008 v2.3 uses DLS-1 v6.7 and up. Flexible Zone Configuration Six fully programmable zones System expandable to 32 zones using: up to 8 keypad zone inputs and/or up to 32 wireless zones with the PC5132 wireless expansion module 38 access codes: one master code, one maintenance code, two duress codes, two supervision codes and 32 general access codes 27 zone types; 8 programmable zone attributes Normally closed, single EOL and double EOL zone wiring 32 wireless zones with the PC5132 Wireless Receiver Audible Alarm Output 700mA Supervised Bell Output (current limited at 3 amps), 12VDC Steady or Pulsed Output EEPROM Memory Does not lose programming or system status on complete AC and Battery failure Programmable Outputs One programmable voltage output and one programmable voltage output/input; 22 programmable options PGM1 = 50mA; PGM2 = 50mA Eight additional low current (50mA) outputs available using the PC5208 module Four additional high current (300mA) outputs available using the PC5204 module; one PC5204 output fully supervised for siren Powerful 1.5 Amp Regulated Power Supply 550 ma Auxiliary Supply, 12 VDC Positive Temperature Coefficient (PTC) components replace fuses Supervision for loss of AC power, low battery Internal clock locked to AC power frequency Power Requirements Transformer = 16.5 VAC, 40VA Battery = 12 volt 4 Ah minimum rechargeable sealed lead acid battery For household fire and burglary installations, two 7Ah batteries in parallel must be used, providing 24 hours of standby power and 4 minutes of alarm output power. For commercial burglary installations, a 4Ah (or larger) battery must be used, providing at least 4 hours of standby power and 4 minutes of alarm output power. WARNING: Do not install this panel outside of North America. By design, this panel will not work if the AC line frequency drops below 55.5Hz. Remote Keypad Specifications Keypads available: - PC5508Z eight zone LED keypad with zone input - PC5516Z sixteen zone LED keypad with zone input - PC5532Z thirty-two zone LED keypad with zone input - LCD5500Z Alphanumeric keypad with zone input All keypads have five programmable function keys Connect up to eight keypads 4-wire (Quad) connection to Keybus Built in piezoelectric buzzer *LINKS1000, LINKS2X50, and Skyroute have not been investigated by UL. Digital Communicator Specifications* Supports major communication formats including SIA and Contact ID Digital Communicator compatible receivers and their formats: Silent Knight Model 9000: 3/1, 4/1, 4/2 non-extended, 3/1 extended, 20 bps, 1400 Hz handshake. Ademco Model 685: 3/1, 4/1, 4/2 non-extended, 3/1 extended, 20 bps, 1400 Hz handshake, Contact ID. Sescoa Model 3000: 3/1, 4/1, 4/2 non-extended, 3/1 extended, 20 bps, 1400 Hz handshake. Radionics Model D6500: 3/1, 4/2 non-extended, 3/1 extended, with or without parity, 1400 and 2300 Hz handshake. Sur-Gard Model MLR2-DG: 3/1, 4/1, 4/2, without parity, 20 bps, 1400 and 2300 Hz handshake, Contact ID, SIA. Event-initiated personal paging Three programmable telephone numbers Two account numbers Supports LINKS1000 cellular communication Supports LINKS2X50 long range radio transmitter Supports Skyroute transceiver DTMF and pulse dialing DPDT line seizure Anti-jam feature Split reporting of selected transmissions to each telephone number System Supervision Features The PC5008 continuously monitors a number of possible trouble conditions including: AC power failure AUX Power Supply Trouble Fault by zone Loss of internal clock Tamper by zone Bell output trouble Fire trouble Telephone line trouble Failure to communicate Low battery condition (panel) Low battery by zone (wireless) Module fault (supervisory or tamper) False Alarm Prevention Features Audible Exit Delay Quick Exit Audible Exit Fault Cross Zone Burglary Alarm Communication Delay Rotating Keypress Buffer Urgency on Entry Delay One Restart of Exit Delay Additional Features Auto Arm at specified time Keypad-activated alarm output and communicator test All modules connect to the system via a four wire Keybus up to 1000 /305m from main panel An event buffer which records the past 128 events with both the time and date at which they occurred; buffer can be printed using PC5400 serial interface module, or viewed with the LCD5500Z keypad and DLS-1 software Supports the addition of the PC5132 wireless receiver for integration of wireless devices Uploading and downloading capability Local downloading capability through the use of the PC-LINK adaptor Supports the Escort5580 Voice Prompt Module with automation/lighting control Supports the addition of the PC5928 Audio Interface Module to integrate intercom stations Added Keybus fault protection: clock and data outputs have been programmed to withstand shorts to +12v to prevent control panel damage 1

6 1.2 Additional Devices In addition to the information below, see the back cover for a DSC module compatibility table. PC5132 Wireless Receiver The PC5132 Wireless Receiver can be used to connect up to 32 wireless devices to the system. All devices are spread spectrum, 900 MHz, fully supervised devices which use standard AAA or AA alkaline batteries. Seven devices are available. They are as follows: WLS904 Wireless Motion Detector: Adds wireless space protection to your system WLS905 Wireless Universal Transmitter: Adds wireless door or window contacts to your system. WLS906 Wireless Smoke Detector: Adds smoke detection to your system. WLS907 Wireless Slimline Universal Transmitter: A smaller wireless door or window contact. WLS908 Wireless Panic Pendant: Adds personal protection to the system. When used, the unit will indicate a non-medical emergency to the central station. WLS909 Wireless Key : Adds a simple and mobile method of arming and disarming to the system, as well as one-button access to several programmable functions. WLS910 Wireless Handheld Keypad*: A portable keypad which allows arming and disarming from anywhere on the premises. PC5400 Printer Module The PC5400 Printer Module allows the panel to print out all events that occur on the system to any serial printer. The printout will contain the time, date and the event that occurred. PC5204 Power Supply Output Module The PC5204 can provide up to 1 Amp of additional power for modules or devices connected to the control panel. The module requires a 16.5 volt AC 40 VA transformer and 4 AH battery. In addition, the module provides 4 programmable high current voltage outputs. Each output is individually programmable. (See 5.11 PGM Output Options on page 20.) (See PC5204 Installation Instructions Sheet.) PC5208 Eight Low Current Output Module Adds eight low current outputs (50 ma) to the control. Each output is individually programmable. (See 5.11 PGM Output Options on page 20.) (See PC5208 Installation Instructions Sheet.) Escort5580 Module This Escort5580 module will turn any touch tone phone into a fully functional keypad. The module also includes a built-in interface to control up to 32 line carrier type devices for lighting and temperature control. (See Escort5580 Installation Manual.) PC5928 Audio Interface Module The PC5928 Audio Interface module is a simple way to incorporate paging, intercom, baby listen-in and door answer to the PC5008 control panel. The module also has built-in talk/listen voice capability for central station. Four additional devices are available: PC5921 Intercom Audio Station Used in conjunction with the PC5928 Audio Interface Module. PC5921 EXT Door Box Audio Station Used in conjunction with the PC5928 Audio Interface Module. PC5921 EXT/R Door Box Audio Station Used in conjunction with the PC5928 Audio Interface Module. The Door Box contains a relay so the normal door bell can be used instead of the internal one generated by the PC5928 module. PC5904 Central Station Talk/Listen Module Used in conjunction with the PC5928 audio interface module for Talk/Listen-In purposes. This station provides an added level of volume to the central station operator s voice. Each station has a separate microphone and speaker. Each station must be home run to the interface module using shielded 22 gauge, 4 conductor wire. All stations can be used to sound an alarm follower. LINKS1000 Cellular Communicator* The LINKS1000 Cellular Communicator can be used three different ways: as the sole communicator for the panel, as a backup for either or both telephone numbers or as a redundant backup to the land line communicator where the panel will call both the land line and via the LINKS. LINKS2X50* Either the LINKS2150 or LINKS2450 may be used to transmit alarm information over a long range radio network. Skyroute Transceiver* The Skyroute transceiver offers a new wireless method of communication for the transmission of events using cellemetry service. Cabinets Several different cabinets are available for the PC5008 modules. They are as follows: PC5003C Cabinet Main control cabinet for the PC5008 main panel. Dimensions 288mm x 298mm x 78mm / 11.3 x 11.7 x 3 approximately. PC5004C Cabinet Cabinet to house the PC5400 Printer Module. Dimensions 229mm x 178mm x 65mm / 9 x 7 x 2.6 approximately. Backplates There are two different backplates available for keypads to locate an Audio Station next to the keypad: PC55BP1 Backplate This backplate is to be used when an Audio Station is to be located next to a keypad. Dimensions 208mm x 115mm x 18mm / 8.2 x 4.5 x 0.25 approximately. PC55BP2 Backplate This backplate is to be used when an Audio Station is to be located next to a keypad. In addition the backplate will allow you to mount a PC5208 Eight Low Current Output Module. Dimensions 208mm x 115mm x 18mm / 8.2 x 4.5 x 0.7 approximately. 1.3 Out of the Box Please verify that the following components are included in your system: one PC5003C main control cabinet one PC5008 main control circuit board one Power keypad with zone input one Installation Manual with programming worksheets one Instruction Manual for the end user one hardware pack consisting of: - one mylar cabinet label - four plastic circuit board standoffs - sixteen 5600Ω (5.6K) resistors - one 2200Ω (2.2K) resistor - one 1000Ω (1K) resistor - ground connection assembly - one cabinet door plug 2 *WLS910, LINKS1000, LINKS2X50, and Skyroute have not been investigated by UL.

7 Section 2: Getting Started The following sections provide a thorough description of how to wire and configure devices and zones. 2.1 Installation Steps Read this section completely before you begin. Once you have an overall understanding of the installation process, carefully work through each step. Step 1: Create a Layout Draw a rough sketch of the building to get an idea of where all alarm detection devices, keypads and other modules are to be located. Step 2: Mounting the Panel Mount the panel in a dry area close to an unswitched AC power source and the incoming telephone line. Before attaching the cabinet to the wall, be sure to press the four circuit board mounting studs into the cabinet from the back. After you have attached the cabinet to the wall, stick the provided DSC logo sticker on the front of the cabinet. NOTE:You must complete all wiring before connecting the battery, or applying AC to the panel. Step 3: Wiring the Keybus (Section 2.3) Wire the Keybus to each of the modules following the guidelines provided in Section 2.3 of this manual. Step 4: Zone Wiring (Section 2.8) You must power down the control panel to complete all zone wiring. Please refer to 2.8 Zone Wiring on page 5 when connecting zones using normally closed loops, single EOL resistors, double EOL resistors, Fire zones and Keyswitch Arming zones. Step 5: Complete Wiring (Section 2.2) Complete all other wiring including bells or sirens, telephone line connections, and ground connections following the guidelines provided in Section 2.2 ( Terminal Descriptions ). Step 6: Power up the Control Once all zone and Keybus wiring is complete, power up the control panel. First, connect the red battery lead to the positive terminal and the black lead to negative. Then, connect the AC. NOTE: Connect the battery before connecting the AC. You must apply AC power to the panel for at least 10 seconds, or the panel will not function. The panel will not power up on the battery connection alone. Step 7: Keypad Assignment (Section 2.5) In order for keypads to be properly supervised, each must be assigned to a different slot. Please follow the guidelines provided in Section 2.5 when assigning keypads. Step 8: Supervision (Section 2.6) The supervision of each module by the panel is automatically enabled upon power up. Please verify that all modules appear on the system according to the instructions in Section 2.6. Step 9: Programming the System (Sections 4 & 5) Section 4 explains how to program the panel. Section 5 contains a complete description of the various programmable features, which options are available and how they function. Fill out the Programming Worksheets completely before attempting to program the system. Step 10: Testing the System Test the panel thoroughly to ensure that all features and functions are operating as programmed. 2.2 Terminal Descriptions Battery Connection A 12V 4Ah rechargeable battery is used as a backup source of power in the event of an AC power failure. The battery also provides additional current when the panel s demands exceed the power output of the transformer, such as when the panel is in alarm. NOTE:Do not connect the battery until all other wiring is complete. Connect the battery before connecting the AC. Connect the RED battery lead to the positive battery terminal; connect the BLACK lead to negative. AC Terminals AC The panel requires a 16.5VAC, 40VA transformer. Connect the transformer to an unswitched AC source and connect the transformer to these terminals. NOTE:Do not connect the transformer until all other wiring is complete. Auxiliary Power Terminals AUX+ and AUX- These terminals provide up to 550 ma of additional current at 12 VDC for devices requiring power. Connect the positive side of any device requiring power to the AUX+ terminal, the negative side to AUX- (ground). The AUX output is protected. This means that if too much current is drawn from these terminals (such as a wiring short), the panel will temporarily shut off the output until the problem is corrected. Bell Output Terminals BELL+ and BELL- These terminals provide up to 700 ma of continuous current at 12 VDC for powering bells, sirens, strobes or other warningtype equipment. Connect the positive side of any alarm warning device to BELL+, the negative side to BELL. Please note that the Bell output is protected: if too much current is drawn from these terminals (such as a wiring short), the Bell PTC will open. Three amps can be drawn for short periods only. The Bell output is supervised. If no alarm warning devices are in use, connect a 1000Ω resistor across BELL+ and BELL to prevent the panel from displaying a trouble condition. For more information, please refer to [*][2] Trouble Display on page 9). For UL installations, when a bell or siren is used for fire signaling with a pulsed cadence, it must be connected between the AUX+ and BELL- terminals. To maintain bell circuit supervision, do not connect more than one device to the BELLterminal. A fire bell or siren used for this application must be UL Listed and have a current consumption of 400mA or less (e.g. Wheelock MT-12/24-R). Keybus Terminals AUX+, AUX-, YEL, GRN The Keybus is used by the panel to communicate with modules and vice versa. Each module has four Keybus terminals that must be connected to the four Keybus terminals on the panel. For more information, see section 2.3 Keybus Operation and Wiring on page 4. 3

8 Programmable Output Terminals PGM1 and PGM2 Each PGM output is designed so that when activated by the panel, the terminal will switch to ground PGM1 can sink up to 50mA of current. Connect the positive side of the LED or buzzer to AUX+, the negative side to PGM1. PGM2 operates similarly to PGM1. If more than 50 ma of current are required, a relay must be used. Please study PGM wiring in the accompanying diagram. For a list of the programmable output options, please see section 5.11 PGM Output Options on page 20. Zone Input Terminals Z1 to Z6 Each detection device must be connected to a zone on the control panel. We suggest that one detection device be connected to each zone; wiring multiple detection devices to a single zone, however, is possible. For zone wiring specifics, please see section 2.8 Zone Wiring on page 5. Telephone Connection Terminals TIP, RING, T-1, R-1 If a telephone line is required for central station communication or downloading, connect an RJ-31X telephone jack in the following manner: Connect the PC5008 and modules which use the telephone line(s) in the following order: For example, if you are installing a PC5008 with a LINKS1000 and a PC5928 Intercom module, connect the incoming line to the LINKS1000, then from the LINKS1000 to the PC5008, then from the PC5008 to the PC5928 Intercom and then from the PC5928 to the house telephones. NOTE:Please ensure that all plugs and jacks meet the dimension, tolerance and metallic plating requirements of 47 C.F.R. Part 68, SubPart F. For proper operation, no other telephone equipment should be connected between the control panel and the telephone company facilities. Do not connect the alarm panel communicator to telephone lines intended for use with a fax machine. These lines may incorporate a voice filter which disconnects the line if anything other than fax signals are detected, resulting in incomplete transmissions. 2.3 Keybus Operation and Wiring The Keybus is used by the panel to communicate with all connected modules and vice versa. The red (AUX+) and black (AUX-) terminals are used to provide power, while the yellow (YEL) and green (GRN) terminals are clock and data respectively. NOTE: The four Keybus terminals of the panel must be connected to the four Keybus terminals or wires of all modules. The following restrictions apply to Keybus wiring: Keybus should be run in minimum 22 gauge quad (0.5mm); two pair twist is preferred. The modules should be home-run to the panel but can be connected in series or T-tapped. Any module can be connected anywhere along the Keybus. You do not need to run a separate Keybus wire for keypads, etc. No module can be more than 1,000'/305m (in wire length) from the panel. Shielded wire should not be used. Example of Keybus Wiring NOTE: Module (A) is correctly wired within 1,000'/ 305m of wire from the panel. Module (B) is correctly wired within 1,000'/ 305m of wire from the panel. Module (C) is NOT wired correctly as it is further than 1,000'/ 305m from the panel, in wire distance. 2.4 Current Ratings Modules and Accessories In order for the PC5008 system to operate properly, the power output capabilities of the main control and the expansion devices must not be exceeded. Use the data presented below to ensure that no part of the system is overloaded and cannot function properly. PC5008 (12 VDC) AUX+:...550mA: Subtract the listed rating for each keypad, expansion module and accessory connected to AUX+ or Keybus. BELL:...700mA continuous rating; 3.0A short term. Available only with standby battery connected. PC5008 Device Ratings (at 12 VDC) LCD5500Z Keypad: 85mA max. PC5508Z, PC5516Z, PC5532Z Keypads: 85mA max. PC5400 Serial Module: 65mA Escort5580 Audio Assistant: 65mA standby / 130mA online PC5204 High Current Output module: 20mA PC5208 Low Current Output module: 50mA PC5132 Wireless Receiver: 125mA PC5928 Audio Interface module: 65mA PC5921/EXT Door Box Audio Station: 20mA PC59X1EXT/R Door Box Audio Station: 35mA PC5904 Central Station Talk/Listen Module: 30mA standby, 130mA max. 4

9 G e t t i n g S t a r t e d : 2.5 Keypad Assi g n ment Other Devices Please read the manufacturer s literature carefully to determine the maximum current requirements for each device during activation or alarm and include the proper values for loading calculations. Connected devices must not exceed system capabilities during any possible operational mode. 2.5 Keypad Assignment There are eight available slots for keypads. LED keypads by default are always assigned to slot 1. LCD5500Z keypads are always assigned to slot 8. You will need to assign each keypad to its own slot (1 to 8). Keypad assignment is required, as it tells the panel which slots are occupied. The panel can then generate a fault when a keypad supervisory is not present. NOTE: One LCD keypad must be assigned to slot 8 in order to upload keypad programming using DLS-1 software. How to Assign Keypads Do the following at each keypad installed on the system: 1. Enter [*][8][installer s code] to go to installer programming 2. Enter [000] for Keypad Programming 3. Enter [0] for Slot Assignment 4. Enter a two digit number (11-18) to specify which supervisory slot the keypad will occupy. 5. Press [#] twice to exit installer programming. After assigning all keypads, perform a supervisory reset by entering section [902] in installer s programming. The panel will now supervise all assigned keypads and enrolled modules on the system. How to Program Function Keys By default, the 5 function keys on each keypad are programmed as Stay Arm (03), Away Arm (04), Chime (06), Sensor Reset (14) and Quick Exit (16). You can change the function of each key on every keypad: 1. Go to the keypad where you want to change the function key programming and enter Installer Programming. 2. Press [000] for Keypad Programming. 3. Enter [1] to [5] to select a function key to program. 4. Enter the 2 digit number, [00] to [21] to select the feature you want the function key to have. For a complete list of Function Key options see section 3.5 Function Keys on page Continue from step 3 until all function keys are programmed. 6. To exit Installer Programming, press [#] twice. 2.6 Supervision By default, all modules are supervised upon installation. Supervision is enabled at all times so that the panel can indicate a trouble if a module is removed from the system. To check which modules are currently connected and supervised, enter programming section [903] from installer s programming. The LCD keypad will allow you to scroll through the display of connected modules. A connected module which does not show as being present will appear as a trouble condition and the Trouble light on the keypad will turn ON. This condition may be due to one or more of the following reasons: the module is not connected to the Keybus there is a Keybus wiring problem the module is more than 1,000'/305m from the panel the module does not have enough power For more information regarding module supervision troubles, please refer to [*][2] Trouble Display on page Removing Modules The panel must be instructed to no longer supervise a module being removed from the system. To remove the module, disconnect it from the Keybus and reset the supervision field by entering [902] in the installer s programming. The panel will be reset to recognize and supervise all existing modules on the system. 2.8 Zone Wiring For a complete description of the operation of all zone types, please refer to 5.2 Zone Programming on page 15. There are several different ways in which zones may be wired, depending on which programming options have been selected. The panel can be programmed to supervise normally closed, End of Line, or Double End of Line loops. Please refer to the following diagrams to study each type of individually supervised zone wiring. NOTE:Any zone programmed for Fire or 24 Hour Supervisory must be wired with a single End of Line (EOL) resistor regardless of the type of zone wiring supervision selected for the panel (section [013]: [1] -[2]). See 5.2 Zone Programming on page 15. NOTE:If you change the zone supervision options from DEOL to EOL or from NC to DEOL (section [013], options [1] or [2]), you should power down the system completely, and then power it back up. If you do not, the zones may not work correctly. Normally Closed (NC) Loops To enable normally closed loops, programming section [013], option [1] must be ON. NOTE:This option should only be selected if Normally Closed (NC) detection devices or contacts are being used. Single End Of Line (EOL) Resistors (5600Ω) To enable panel detection of single end of line resistors, programming section [013], options [1] and [2] must be OFF. NOTE:This option should be selected if either Normally Closed (NC) or Normally Open (NO) detection devices or contacts are being used. 5

10 Double End of Line (DEOL) Resistors Double End of Line resistors allow the panel to determine if the zone is in alarm, tampered or faulted. To enable panel detection of double end of line resistors, programming section [013], option [1] must be OFF and option [2] must be ON. NOTE: If the Double EOL supervision option is enabled, all hardwire zones on the main panel must be wired for Double EOL resistors, except for Fire and 24 Hour Supervisory zones. NOTE:Do not wire DEOL resistors on keypad zones. NOTE: Do not use DEOL resistors for Fire zones or 24 Hour Supervisory zones. Do not wire Fire zones to keypad zone terminals if the DEOL supervision option is selected LINKS Zone Wiring* LINKS Support When using the LINKS1000 cellular communicator, connect the LINKS to the main panel according to the following diagram: NOTE:If PGM2 is programmed for 24-Hr Auxiliary Input support, the connector JP1 on the main board must be removed. NOTE: This option can only be selected if Normally Closed (NC) detection devices or contacts are being used. NOTE:Only one NC contact can be connected to each zone. Wiring multiple detection devices or contacts on a single loop is not allowed. The following chart shows zone status under certain conditions: Loop Resistance Loop Status 0Ω (shorted wire, loop shorted) Fault 5600Ω (contact closed) Secure Infinite (broken wire, loop open) Tamper 11200Ω (contact open) Violated End of Line Resistors Section [013]: [1] Double End of Line Resistors Section [013]: [2] 2.9 Fire Zone Wiring 4-Wire Smoke Detectors All fire zones must be wired according to the following diagram: Hr Auxiliary Input Wiring (PGM2) If PGM2 has been programmed for 24-hour operation, the zone must be wired according to the following diagram: LINKS Supervision (24 Hour Supervisory) When using the LINKS1000 cellular communicator, any main board zone may be configured for LINKS Supervision. Program this zone as zone type [09], 24 Hour Supervisory in section [001]. With a LINKS Supervisory zone, if the LINKS1000 experiences a trouble, the zone will be violated, causing the panel to report the event to the central station. This type of zone always requires a single EOL resistor (5600Ω). Wire this zone according to the above diagram. LINKS Answer When using the LINKS1000 cellular communicator, any main board zone may be configured for LINKS Answer. A zone configured for LINKS Answer allows downloading to be performed in the event of telephone line failure. When the LINKS receives a telephone call, it will activate the RING terminal on the LINKS circuit board. The zone programmed as LINKS Answer always requires a single EOL resistor (5600Ω). Wire the LINKS Answer zone according to the above diagram. 6 *Not investigated by UL.

11 G e t t i n g S t a r t e d : Keypad Zones NOTE: The LINKS Answer zone is only required for downloading to the panel via the LINKS. NOTE: When using the LINKS, Busy Tone Detection must not be used. NOTE: Keypad zones cannot be used for 24 Hour Supervisory or LINKS Answer Keypad Zones Each z keypad on the system has a zone input to which a device - such as a door contact - can be connected. This eliminates the need to run wires back to the control panel for every device. To install the keypad, open the keypad plastic by removing the screw at the bottom of the unit. Locate the five terminals on the keypad circuit board. Connect the four Keybus wires from the control panel: the red wire to R, the black to B, the yellow to Y and the green to G. To connect the zone, run one wire to the Z terminal and the other to B. For powered devices, use red and black to supply power to the device. Run the red wire to the R (positive) terminal and the black wire to the B (negative) terminal. When using end of line supervision, connect the zone according to one of the configurations outlined in section 2.8 Zone Wiring. End of line resistors must be placed on the device end of the loop, not at the keypad. NOTE: Keypad zones do not support DEOL resistors. Assigning Keypad Zones When using keypad zone inputs, each input used must be assigned a zone number in Installer s Programming. First, ensure that you have enrolled all installed keypads into the desired slots. (See 2.5 Keypad Assignment on page 5.) Next, enter programming section [020] to assign the zones. There are eight programming locations in this section, one for each keypad slot. Enter a 2-digit zone number for each of the keypad zones. This number must be entered in the location corresponding to the keypad to which each zone is connected. Example: The zone on an LCD5500Z keypad in slot 8 is to be assigned zone 3. In section [020], scroll to option [8] and enter (03). NOTE:Keypad zones 1-6 will replace zone terminals Z1-Z6 on the control panel. NOTE: Once the keypad zones are assigned, you must also program zone definitions and zone attributes. (See also 5.4 Assigning Keypad Zones on page 17). NOTE: Keypad zones can only be used for household burglary-initiated devices. Do not place the device more than 3 feet from the keypad. The keypad zone must be tested weekly. 7

12 Section 3: Keypad Commands Use any system keypad to enter commands and/or program the PC5008 security system. The LED keypad uses function and zone indicator lights to represent alarm functions and status. The LCD keypad provides a written description on the liquid crystal display and uses function indicator lights to communicate alarm status to the user. The PC5008 Instruction Manual provides basic directions for arming and disarming the system, bypassing zones and performing user functions from the keypads. The following sections provide additional details on these functions. 3.1 Arming and Disarming For a description of basic arming and disarming, please see the PC5008 Instruction Manual. For other methods of arming, please refer to [*][0] Quick Arm, [*][9] Arming Without Entry Delay and 3.5 Function Keys on page 11. NOTE: The event buffer will log Armed in Stay Mode or Armed in Away Mode whenever the system is armed. In an attempt to prevent false alarms, the Audible Exit Fault will notify the user of an improper exit when they arm their system. If a non force-arming Delay 1 or Delay 2 type zone is left open at the end of the exit delay, the entry delay will begin immediately and the bell or siren will sound a steady alarm for the entry delay period. At the end of the entry delay period, if the system has not been disarmed it will go into alarm. This feature can be turned OFF in programming section [013], option [6]. (See 5.17 Arming/Disarming Options on page 23.) 3.2 Auto Bypass Stay Arming Stay arming allows the user to arm the system without leaving the premises. All zones programmed as stay/away will be bypassed when the user stay arms the system, so that the user does not have to bypass interior zones manually. (See 5.2 Zone Programming on page 15.) When the system is armed using a valid access code, if any zones on the system have been programmed as stay/away zones, the Bypass light will turn ON. The panel will then monitor all zones programmed as Delay 1 and Delay 2 zones, such as designated entry/exit doors. If a delay zone is not violated by the end of the exit delay, the panel will bypass all stay/away zones. The Bypass light will remain on to inform the user that the interior zones have been automatically bypassed by the panel. If a delay zone is violated during the exit delay, the system will arm in Away mode and all stay/away zones will be active after the exit delay expires. The user can arm the stay/away zones at any time by entering the [*][1] keypad command. (See [*][1] Bypassing and Activating Stay/Away Zones on page 8.) Stay arming can also be initiated by pressing and holding the Stay function key for two seconds on the PC5508Z and LCD5500Z keypads, if programmed by the installer. For more information regarding Stay arming, please see 3.5 Function Keys on page Automatic Arming The system can be programmed to Auto-Arm at a specific time every day if it is in the disarmed condition. In order for the Auto-Arm function to work properly, you must program the correct Time of Day. For programming the clock and auto-arm times, see [*][6] User Functions on page 10. When the system s internal clock matches the Auto-Arm Time, the panel will check the system status. If the system is armed, the panel will do nothing until the next day at the auto-arm time, when it will check the system again. If the system is disarmed at the auto-arm time, the panel will sound the buzzer of all keypads for one minute. If the Bell Squawk During Auto Arm option is enabled (section [014], option [2]), the bell will squawk once every 10 seconds while the system is auto-arming. If a valid access code is entered, auto-arming will be aborted. NOTE: If auto-arm is cancelled, the number of the user who cancelled the auto-arm will be logged in the event buffer. If no code is entered, the panel will auto-arm. If a zone is violated, the panel will transmit a Partial Closing Reporting Code if programmed to indicate to the central station that the system is not secure. If the zone is restored, the panel will add the zone back into the system. NOTE: Auto arming can only be cancelled by entering a valid access code at any keypad. 3.4 [*] Commands The [*] key commands provide an easy way for the user to access basic system programming such as programming access codes or bypassing zones. The user can also use the [*] key commands to check on the system s status, including viewing trouble conditions and displaying the event buffer on the LCD keypad. The [*] key commands can be performed from both LCD and LED keypads. The LED keypad uses the zone indicator lights to display command information. The LCD display provides written information, guiding the user through each command. The commands in this section are explained as viewed from an LED keypad. When using an LCD keypad, use the arrow keys (< >) to scroll through information provided. Otherwise, the functions remain the same for both keypad types. [*][1] Bypassing and Activating Stay/Away Zones Use the [*][1] keypad command to bypass individual zones. A bypassed zone will not cause an alarm. NOTE: Zones can only be bypassed when the system is not armed. If the Code Required for Bypass option is enabled (section [015], option [5]), only access codes with the bypass attribute enabled will be able to bypass zones. (See 5.1 Programming Security Codes on page 15.) If the Bypass Status Displayed While Armed option is chosen, the Bypass light will be ON while the system is armed to indicate any bypassed zones. (See 5.17 Arming/Disarming Options on page 23.) NOTE: When you disarm the system, all manually-bypassed zones will be unbypassed. Activate Stay/Away Zones If the system is armed in stay mode, the [*][1] command can be used to activate the stay/away zones. 8

WARNING Software Version 2.3 / DLS-1 v6.7 and up See Back Cover for New Features in Version 2.3

WARNING Software Version 2.3 / DLS-1 v6.7 and up See Back Cover for New Features in Version 2.3 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

System Introduction. 1.1 Specifications

System Introduction. 1.1 Specifications System Introduction S E C T I O N 1 1.1 Specifications Downloading Software Support PC585 uses DLS-1 v6.5 and up. Flexible Zone Configuration Four fully programmable zones; system expandable to eight zones

More information

Installation Manual. PC1565 Software Version 2.4ZD DLS-3 v1.3 and higher

Installation Manual. PC1565 Software Version 2.4ZD DLS-3 v1.3 and higher WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

System Introduction. 1.1 PC5015 Specifications S E C T I O N 1

System Introduction. 1.1 PC5015 Specifications S E C T I O N 1 1.1 PC5015 Specifications System Introduction S E C T I O N 1 Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master, 2 Duress and 1 maintenance

More information

System Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging

System Introduction. Digital Communicator Specifications: Supports all Major Formats including SIA and Contact ID Event Initiated Personal Paging 1.1 Specifications System Introduction S E C T I O N 1 Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 38 Access Codes: 32 User, 1 System Master, 2 Partition Master,

More information

PC56O. Instruction Manual

PC56O. Instruction Manual Instruction Manual PC56O Software Version 1.OA W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the

More information

System Introduction. 1.1 Specifications S E C T I O N 1

System Introduction. 1.1 Specifications S E C T I O N 1 System Introduction S E C T I O N 1 1.1 Specifications Control Panel Specifications Flexible Zone Configuration: 8 Fully Programmable Zones 37 Access Codes: 32 User, 1 System Master, 2 Partition Master

More information

Contents. Programming Worksheets 22. Appendix A: Guidelines for Locating Smoke Detectors 27. Index 28

Contents. Programming Worksheets 22. Appendix A: Guidelines for Locating Smoke Detectors 27. Index 28 Contents Section 1: Introduction 4 1.1 How to use this Manual...4 1.2 Specifications and Features...4 1.3 Compatible Wireless Devices... 5 1.4 Batteries...5 Section 2: PC5132-RS Set up & Wiring 6 2.1 Unpack

More information

Installation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher

Installation Manual IMPORTANT. PC5020 Version 3.1 DLS-3 v1.3 and higher IMPORTANT WARNING:This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be

More information

PC51O2-433NA v1.0 Installation Manual

PC51O2-433NA v1.0 Installation Manual PC51O2-433NA v1.0 Installation Manual If you are intending to use DLS-3 software with this product, a new DLS-3 driver must be downloaded from the DSC web site at http://www.dscsec.com/dls3drivers.htm.

More information

RAM-208. Remote Multiplex Annunciator Panel. Wiring & Installation Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE

RAM-208. Remote Multiplex Annunciator Panel. Wiring & Installation Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE Advanced Life Safety Solutions RAM-208 Remote Multiplex Annunciator Panel A.C. ON COMMON TROUBLE SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE LAMP TEST SYSTEM RESET Wiring & Installation Installation

More information

P Zone Expandable Hybrid Security System

P Zone Expandable Hybrid Security System Page 1 of 11 up to 8 hardwired keypads and 4 wireless keypads 4 hardwired keypads available with zone input PWLS910 wireless handheld keypad added wireless control is provided by - PWLS908 wireless panic

More information

Programming Worksheets

Programming Worksheets WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Installation Manual RF55O1-433

Installation Manual RF55O1-433 WARNING: Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. Installation

More information

Installation Instructions Instructions d Installation Instrucciones de Instalacion

Installation Instructions Instructions d Installation Instrucciones de Instalacion LCD5511 version 1.O Installation Instructions Instructions d Installation Instrucciones de Instalacion WARNING: Please refer to the System Installation Manual for information on limitations regarding product

More information

RAM-216. Remote Multiplex Annunciator Panel. Wiring & Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE

RAM-216. Remote Multiplex Annunciator Panel. Wiring & Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE Advanced Life Safety Solutions RAM-216 Remote Multiplex Annunciator Panel A.C. ON COMMON TROUBLE SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE LAMP TEST SYSTEM RESET Wiring & Installation Manual LT-658

More information

PROGRAMMING WORKSHEETS

PROGRAMMING WORKSHEETS 16 Hook-up Diagram Table of Contents INTRODUCTION 2 Features... 2 Specifications... 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Wiring... 3 Burglary Zone Wiring... 4 Fire Zone Wiring...

More information

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring About Your Security System Your DSC security equipment has been designed to provide you with the greatest possible flexibility and convenience. Read this manual carefully and have your installer instruct

More information

Instruction Manual W A R N I N G

Instruction Manual W A R N I N G W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Installation Manual Premier LCD/LCDL INS180-4

Installation Manual Premier LCD/LCDL INS180-4 Installation Manual Premier LCD/LCDL INS180-4 1. UL/C-UL Requirements Only the following keypads are to be used in a UL/C-UL Installation. Model No DBD-0135 DBD-0133 DBD-0144 DBD-0143 DBD-0148 DBD-0147

More information

INSTALLATION MANUAL PC56O. Version 1.OA

INSTALLATION MANUAL PC56O. Version 1.OA INSTALLATION MANUAL PC56O Version 1.OA TABLE OF CONTENTS INTRODUCTION 3 Features... 3 Specifications... 3 INSTALLATION 4 Mounting the Control Panel... 4 Mounting the Keypad... 4 Wiring... 5 Burglary Zone

More information

Instruction Manual W A R N I N G

Instruction Manual W A R N I N G W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Digital Security Controls

Digital Security Controls Digital Security Controls Publications Cover Sheet Part Number: Revision: Release Number: Description: Notes: Material Type: Pieces: Printing Instructions: Master Size: # Sheets in Master: Cover Printing:

More information

Quick Reference Guide

Quick Reference Guide WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

MR-2316-AT/Z Remote Annunciator

MR-2316-AT/Z Remote Annunciator MR-2316-AT/Z Remote Annunciator Secutron LT-617SEC Rev.1 February 2011 Table of Contents Table of Contents 1.0 Introduction 7 1.1 Contact Us... 7 1.1.1 General Inquiries... 7 1.1.2 Customer Service...

More information

PC155O. Installation Manual W A R N I N G. Software Version 4.1 DLS-1 V6.5 and later

PC155O. Installation Manual W A R N I N G. Software Version 4.1 DLS-1 V6.5 and later Installation Manual PC155O Software Version 4.1 DLS-1 V6.5 and later W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations

More information

RAM-2644LCD. LCD Remote Annunciator. Installation Manual. Advanced Life Safety Solutions

RAM-2644LCD. LCD Remote Annunciator. Installation Manual. Advanced Life Safety Solutions Advanced Life Safety Solutions RAM-2644LCD LCD Remote Annunciator Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113 U.S.A. 60 Industrial Parkway Cheektowaga, NY 14227 Tel:

More information

PC4020 v3.5 Instruction Manual

PC4020 v3.5 Instruction Manual PC4020 v3.5 Instruction Manual WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire

More information

RF v1.0 Installation Manual

RF v1.0 Installation Manual RF5108-433 v1.0 Installation Manual Thank you for purchasing the RF5108-433 Wireless Receiver. This product is the result of several years of development and will allow you to connect up to 8 wireless

More information

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring About Your Security System Your DSC security equipment has been designed to provide you with the greatest possible flexibility and convenience. Read this manual carefully and have your installer instruct

More information

Maintenance Manual PC6010. WARNING This manual contains information on limitations regarding product use and function

Maintenance Manual PC6010. WARNING This manual contains information on limitations regarding product use and function WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Installation Guide. NT9010 v 1.0. DLS-3 v1.3 and higher

Installation Guide. NT9010 v 1.0. DLS-3 v1.3 and higher WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3W FEATURES Transmits alarm information to a long range radio network Varitech Transmission Format Note: If automatic SIA is used in

More information

System Manual W A R N I N G. PC4O2OKT Version 1.0CAP. Book 1

System Manual W A R N I N G. PC4O2OKT Version 1.0CAP. Book 1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

INSTRUCTION MANUAL PC255O

INSTRUCTION MANUAL PC255O INSTRUCTION MANUAL PC255O Canadian Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment

More information

PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3

PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3 PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the

More information

Installation Manual CFP-500. Dual Line Dialer. Version 1.0

Installation Manual CFP-500. Dual Line Dialer. Version 1.0 CFP-500 Dual Line Dialer Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of

More information

INSTRUCTION MANUAL PC255O

INSTRUCTION MANUAL PC255O INSTRUCTION MANUAL PC255O Canadian Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter W A R N I N G Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. TM

More information

DIGITAL FRONTIER Voice Alarm System DFA5300 User Manual Version 1 rev2

DIGITAL FRONTIER Voice Alarm System DFA5300 User Manual Version 1 rev2 DIGITAL FRONTIER Voice Alarm System DFA5300 User Manual Version 1 rev2 About Your Security System Your DF security equipment has been designed to give the greatest possible flexibility and convenience.

More information

Instruction Manual PC585. Direct all comments and suggestions concerning DSC publications to

Instruction Manual PC585. Direct all comments and suggestions concerning DSC publications to W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

Installation Manual Version 1.3. Long Range RF Transmitter. How to contact us:

Installation Manual Version 1.3. Long Range RF Transmitter. How to contact us: How to contact us: Technical Support If you have questions or problems when using this product, you can call Technical Support. If you are within the United States or Canada, you can get support by dialing

More information

RAX-LCD-LITE. Remote Annunciator. Installation and Operation Manual

RAX-LCD-LITE. Remote Annunciator. Installation and Operation Manual RAX-LCD-LITE Remote Annunciator Installation and Operation Manual LT-1149 Rev.1 July 2014 Table of Contents 1.0 Introduction 6 2.0 Mechanical Installation 8 2.1 Mounting Dimensions... 8 3.0 Wiring Instructions

More information

System Manual W A R N I N G. PC6O1O Software Version 2.1

System Manual W A R N I N G. PC6O1O Software Version 2.1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3

PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3 PC4020 v3.3 (US, UL) Installation Manual DLS-3 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160 All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

INTRODUCTION. The use of any power source other than a PC4204 to repower the Combus will result in a system malfunction.

INTRODUCTION. The use of any power source other than a PC4204 to repower the Combus will result in a system malfunction. INTRODUCTION The PC4020 is a highly flexible and versatile control which will enable the installer to meet the most demanding security requirements. The heart of the system is the main control panel, designated

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING 48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

INSTALLATION MANUAL PC25OO

INSTALLATION MANUAL PC25OO INSTALLATION MANUAL PC25OO NOTES ON UL INSTALLATION This equipment is UL listed in accordance with UL standard 1023 (Household Burglar Alarm System Units), UL standard 985 (Household Fire Warning Units)

More information

PC4020 v3.5 (International) Installation Manual DLS2002 or higher

PC4020 v3.5 (International) Installation Manual DLS2002 or higher PC4020 v3.5 (International) Installation Manual DLS2002 or higher This manual is in compliance with the requirements of CTR21 WARNING: This manual contains information on limitations regarding product

More information

MGD-32 and AGD-048. Remote Multiplex Graphic Driver Annunciators and Adder Boards. Wiring and Installation Manual

MGD-32 and AGD-048. Remote Multiplex Graphic Driver Annunciators and Adder Boards. Wiring and Installation Manual MGD-32 and AGD-048 Remote Multiplex Graphic Driver Annunciators and Adder Boards Wiring and Installation Manual LT-847 Rev. 8 February 2011 Table of Contents Table of Contents 1.0 Introduction 7 1.1 Contact

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

TABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E...

TABLE OF CONTENTS. General Description Standard and Optional Parts List Feature Definitions Comments about the 8600E... 5$1*(5( DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS General Description... 2 Standard and Optional Parts List... 2 Feature Definitions... 3 Comments about the 8600E... 4 Terminal

More information

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION...2 STANDARD AND OPTIONAL PARTS LIST...2 FEATURE DEFINITIONS...3 TERMINAL DRAWING AND SPECIAL NOTES...4

More information

RA-1000 Series. Remote Multiplex Annunciator Panels. Installation and Wiring Manual

RA-1000 Series. Remote Multiplex Annunciator Panels. Installation and Wiring Manual RA-1000 Series Remote Multiplex Annunciator Panels Installation and Wiring Manual LT-617 Rev. 17 July 2014 1.0 Introduction 5 1.1 Contact Us... 6 1.1.1 General Inquiries... 6 1.1.2 Customer Service...

More information

AXI LED USER MANUAL (REV. 1.0)

AXI LED USER MANUAL (REV. 1.0) Security & Home Automation System AXI LED USER MANUAL (REV. 1.0) CONTENTS PREFACE FEATURES LED KEYPAD OUTLOOK 1.0 LIGHT INDICATION 1 2 4 6 CHAPTER 1: ALARM SYSTEM CONTROL 1.0 USING LED KEYPAD 1.0.1 ARMING

More information

PC4020 v3.2 Installation Manual DLS-3 v1.3

PC4020 v3.2 Installation Manual DLS-3 v1.3 PC4020 v3.2 Installation Manual DLS-3 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer.

More information

TABLE OF CONTENTS TABLE OF CONTENTS 1

TABLE OF CONTENTS TABLE OF CONTENTS 1 TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2

More information

PC4820 v1.3 Installation Manual

PC4820 v1.3 Installation Manual PC4820 v1.3 Installation Manual WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire

More information

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

Power864. User s Guide. Now classified in accordance with ANSI/SIA CP (SIA-FAR)

Power864. User s Guide. Now classified in accordance with ANSI/SIA CP (SIA-FAR) WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147) -961112-0003 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

WLS900 Wireless Security System. Table of Contents. Your installing company is, Name: Address: Phone: Your monitoring station is, Name: Phone:

WLS900 Wireless Security System. Table of Contents. Your installing company is, Name: Address: Phone: Your monitoring station is, Name: Phone: Table of Contents WLS900 Wireless Security System 1 Introduction 2 2 Using the Keypad 3 3 Arming the System 4 3A - Arming Levels; 4 3B - Arming the System in the Away Mode 4 3C - Improper Arming Warning

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3 This manual is for the LINKS2150 software version 1.3 TABLE OF CONTENTS FEATURES 1 Keypad Programmable... 1 EEPROM Memory... 1 Static/Lightning

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: -961112-0002 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

PC4820 v1.4 Installation Manual

PC4820 v1.4 Installation Manual PC4820 v1.4 Installation Manual WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSI 3.10 CTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

PC4020 v3.2 Installation Manual DLS-3 v1.3

PC4020 v3.2 Installation Manual DLS-3 v1.3 PC4020 v3.2 Installation Manual DLS-3 v1.3 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer.

More information

FA-102T. Fire Alarm Control Panel. Installation and Operation Manual. LT-514 Rev.7 December 2009 A.C. ON SIGNAL SILENCED

FA-102T. Fire Alarm Control Panel. Installation and Operation Manual. LT-514 Rev.7 December 2009 A.C. ON SIGNAL SILENCED Advanced Life Safety Solutions FA-102T Fire Alarm Control Panel 1 2 A.C. ON SIGNAL SILENCED Installation and Operation Manual LT-514 Rev.7 December 2009 FA-102T Installation and Operation Manual Table

More information

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

Introduction S E C T I O N 1

Introduction S E C T I O N 1 Introduction S E C T I O N 1 The PC4164-RS is a wireless signal receiver for use with Maxsys PC4010 and PC4020 v3.0 panels. The PC4164-RS receives signals from WLS9XX wireless devices. The PC4164-RS has

More information

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1.2 1725, 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX TABLE OF CONTENTS HOW DO I PROGRAM THE SYSTEM?... 4 Single Digit Data Entry Method (Hexadecimal

More information

SPECIFICATIONS Control Panel Specifications Remote Keypad Specifications 21 zones including: (PC3000RK) Audible alarm output:

SPECIFICATIONS Control Panel Specifications Remote Keypad Specifications 21 zones including: (PC3000RK) Audible alarm output: SPECIFICATIONS Control Panel Specifications 21 zones including: 16 fully programmable supervised zones (EOL resistors) Supervised fire zone 1 auxiliary normally open zone 3 keypad activated zones Audible

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming

More information

PowerSeries. PC1616/PC1832/PC1864 version 4.1. Installation Guide

PowerSeries. PC1616/PC1832/PC1864 version 4.1. Installation Guide PowerSeries PC1616/PC1832/PC1864 version 4.1 Installation Guide Note to Installer:Center pages contain important end user information. Leave with End User. WARNING: This manual contains information on

More information

WIRELESS CONTROLS & DETECTORS

WIRELESS CONTROLS & DETECTORS WIRELESS CONTROLS & DETECTORS WLS908 Panic Pendant Press 2 buttons for 2 seconds to initiate a panic alarm Water-resistant Pendant test function Supervised for low battery Each pendant is a wireless zone

More information

9,67$ 6(D 6\VWHP 6HFXULW\ 86(5 *8,'( N7229AUV2 12/99

9,67$ 6(D 6\VWHP 6HFXULW\ 86(5 *8,'( N7229AUV2 12/99 9,67$6(D 6\VWHP6HFXULW\ 86(5*8,'( N7229AUV2 12/99 TABLE OF CONTENTS SYSTEM OVERVIEW...4 General...4 Burglary Protection...4 Zones...4 Alarms...5 Fire Protection...5 Chime Feature...5 Phone Access & Voice

More information

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup NetworX Series NX-8 Commercial Fire Panel Installation and Startup 2004 GE Security All rights reserved. Printed in the United States of America. These instructions do not purport to cover all details

More information

NT9005 V ZONE SECURITY SYSTEM

NT9005 V ZONE SECURITY SYSTEM NT9005 V1.0 32 ZONE SECURITY SYSTEM User Guide WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer.

More information

Table of Contents. Appendix A Special Characters 31

Table of Contents. Appendix A Special Characters 31 Table of Contents Introduction 2 Section 1: General System Operation 3 1.1 Getting to Know Your System... 3 1.2 How to Arm... 4 1.3 Alternate Arming Methods... 5 1.4 Disarming... 6 1.5 Alarm Memory...

More information

PowerWave-16. Users Operating and Programming Guide Version P/N Rev. B N.A July 2002

PowerWave-16. Users Operating and Programming Guide Version P/N Rev. B N.A July 2002 ELECTRONIC ENGINEERING LTD. PowerWave-16 16 zone Control panel Communicator Users Operating and Programming Guide Version 6.20 P/N 7121240 Rev. B N.A July 2002 Contents Introduction...4 Meet the Crow Alarm

More information

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual RAM-5-LCD Remote Annunciator Installation and Operation Manual LT-9 Rev. July Table of Contents. Introduction 6. Contact Us... 6. Mechanical Installation 8. Mounting Dimensions... 8. Configuring the Main

More information

Installation Instructions

Installation Instructions Installation Instructions S E C U R I T Y S Y S T E M Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations

More information

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

INSTALLATION MANUAL PC15OO

INSTALLATION MANUAL PC15OO INSTALLATION MANUAL PC15OO This device complies with Parts 15 and 68 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2)

More information

Installation Manual Premier 412/816/832. Issue 10

Installation Manual Premier 412/816/832. Issue 10 Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the

More information

Technical Manuals Online! - Keypad Programming. Basic Programming

Technical Manuals Online! -   Keypad Programming. Basic Programming P r o g r a m m i n g W o r k s h e e t s Keypad Programming [000] Keypad Enrollment (Section 2.5 Keypad Assignment on page 4) NOTE: This must be done at each keypad requiring programming. [0] Slot [Valid

More information

0$(6752 0$(6752. Programming Guide. 6 and 10 Zone Alarm Control Panel ,1752'8&7,21 +(;$ 352*5$00,1* 675($0/,1(' 6(&7,21 352*5$00,1* FIGURE 1 FIGURE 2

0$(6752 0$(6752. Programming Guide. 6 and 10 Zone Alarm Control Panel ,1752'8&7,21 +(;$ 352*5$00,1* 675($0/,1(' 6(&7,21 352*5$00,1* FIGURE 1 FIGURE 2 0$(6752 0$(6752 6 and 10 Zone Alarm Control Panel Programming Guide,1752'8&7,21 The Maestro-600 and Maestro-1000 alarm control panels enable reduced number of programming steps. End-users can access most

More information

Using Your GEM-P400 Security System H

Using Your GEM-P400 Security System H Using Your GEM-P400 Security System H 1 2 3 4 AR MED STATU S 1 2 This page left blank intentionally Introduction Congratulations on your purchase of an advanced GEMINI-P400 Security System. Meticulously

More information

INTRODUCTION INSTALLATION N7635-3V2 8/ EN Series RF Receiver INSTALLATION AND SETUP GUIDE

INTRODUCTION INSTALLATION N7635-3V2 8/ EN Series RF Receiver INSTALLATION AND SETUP GUIDE N7635-3V2 8/00 5881EN Series RF Receiver INSTALLATION AND SETUP GUIDE INTRODUCTION The 5881EN series of RF receivers is designed for use with control panels that support an RF receiver connection via the

More information

System Programming Guide

System Programming Guide & System Programming Guide Software Versions 4.4 (728ULT) and 4.1 (738ULT) Installer Code (Default - 728 Ultra: 282828; 738 Ultra: 383838) Full access to programming, except user access codes (PINs). No

More information

Destiny Destiny Owners Manual

Destiny Destiny Owners Manual Destiny 4100 Destiny 4100 Owners Manual TABLE OF CONTENTS INTRODUCTION Control Panel...3 Detection Devices...3 Telephone Keypads...3 GLOSSARY... 4-5 LOCAL PHONE ACCESS Using Your Telephones As Keypads...6

More information

CC880/LP880, SC8016. Operators Guide Solution-16, Solution-16 Safecom

CC880/LP880, SC8016. Operators Guide Solution-16, Solution-16 Safecom CC880/LP880, SC8016 EN Operators Guide Solution-16, Solution-16 Safecom CC880/LP880, SC8016 Operators Guide EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch

More information