1 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1

2 Table of contents Terminology... Technical Data... Contents of Delivery... Installation and Arrangements... To Mount the Control Panel... Description of Inputs and Outputs. Periphery Devices Assembly... Description and Mounting of Devices to L1, L2 and L3 Inputs... Description and Mounting of Devices to Manual Release Input... Description and Mounting of Devices Mode Select Input... Description and Mounting of Devices Hold Input... Description and Mounting of Devices On/Off Exting Input... Description and Mounting of Devices Low Press Input... Description and Mounting of Devices Exting Output... Description and Mounting of Devices Sounder S1 and Sounder S2 Outputs... Description and Mounting of Devices to Outputs OK1, OK andи OK3 Open Collector Type... Description and Mounting of Devices to Rel Fire Output... Description and Mounting of Devices Rel 1 ST and Rel 2ST Outputs... Description and Mounting of Devices to Rel Fault Output... Description and Mounting of Devices to RS485 Interface Terminals... Power Supply Connection... General Information... Access Levels... Indications and Buttons for Control... Conditions of the Fire Extinguishing Control Panel... Duty Mode... Description... Indication... Using the Keypad... Fire Condition Stage I... Description... Indication... Using the Keypad... Fire Condition Stage II... Description... Indication... Using the keypad... Using the Switch for Mode Selection (Automatic/Manual/Disabled)... Fault Condition... Description... Indication... Using the Keypad... Disabled Component... Description... Indication... Using the Keypad... Test Mode... Description... Indication... Using the Keypad... Information and Control Mode... Description... Indication... Using the Keypad... Using the Menus... Menu View Faults Instruction Manual Page 2

3 Menu View Disables... Menu View Test... Menu Statuses... Menu System Functions... Setup Mode... Description... Indication... Using the Keypad... Using the Menus... Menu Fire Extinguishing Control Panel... Menu CAN Parameters... Menu Inputs/Outputs... Menu Time Extinguishing... Menu Time Evacuation... Menu Factory Settings... Menu Clear archive... Menu new Password... Extinguishing Control Algorithm... Labour Protection Requirements... Fire Extinguishing Control Panel Start Up... Operation, Storage and Transportation... Warranty... Appendixes Instruction Manual Page 3

4 Introduction The fire extinguishing control panel FS5200Е is designated for fire protection, monitoring and control of systems for active extinguishing. After processing the signals from the automatic fire detectors and/or manual call points the control panel it sends commands to the executive devices for extinguishing, sound-light signalers, air conditioning and ventilation devices, it sends information to a repeater, PC or another intelligent devices. FS5200Еcould be used in gas, powder, aerosol, water and other types of systems for active extinguishing. The fire extinguishing control panel is designed for extinguishing in one zone. It is possible up to 15 zones to be protected when the fire extinguishing control panel is connected in a network via interface RS485 and a repeater FS5200R. The fire extinguishing control panel could be connected and become a part of the Interactive Fire Control System IFS7002 / production/. The fire extinguishing control panel FS5200Е is designed and produced in compliance with standards EN 54-2:1997/ А1:2006/AC: 2009, EN 54-4:1997/A2: 2006/AC: 2009, EN : Some of its main features and possibilities are: adjustment of operating modes and parameters of each fire alarm line, output and input via built in keypad; user oriented menu dialogue for easy and convenient operation; LCD for visualization of system checkup and set up modes; LEDs indication for early warning of a break down or extreme conditions; energy independent archive memory saving the event type, date and time, allowing for detailed analysis of the actions of the authorized personnel and of possible problems in the fire protection process of the area; user oriented test modes allowing for a total control of the site protected; built-in serial interface RS485 and CAN for connection to other fire control panels; compatible to random installation design, within the range of the available fire extinguishing control panels resources. All these are realizable via fire extinguishing control panel s keypad and after a detailed examination of the instructions set herewith. 1. Terminology OUTPUT monitored or relay output, programmed by the user to be activated during the different stages of the extinguishing. EVACUATION TIME the time from occurring the situation for extinguishing to the moment of switching on the extinguishing automatics. This time should be enough for the evacuation of the staff from the premises. The evacuation time is user defined for the specific site. The evacuation time is shown on the LCD display and it counts down the remaining time until the release of the extinguishing automatics. DISABLED LINE the fire detecting line is switched off (not power supplied) and it is not monitored for turned out fire detector and a fault condition. This feature is user defined. The indication for a disabled line is common light indication and text messages on the LCD display. DISABLED OUTPUT the output is switched off (the executive device can not be activated) and is not monitored for a fault condition in the monitored outputs. This feature is user defined. The indication for a disabled monitored output is common light indication and text messages on the LCD display. DISABLE EXTINGUISHING condition of the fire extinguishing control panel when regardless the input actions the executive extinguishing device cannot be activated. Disable extinguishing is Instruction Manual Page 4

5 defined by on status of the monitored input On/Off Exting (See section 4.2.) or by the secret switch on the front panel. The indication for disable extinguishing is an individual light indication. HOLD EXTINGUISHING condition of the fire extinguishing control panel when the release signal to the executive extinguishing device is delayed. Hold extinguishing is defined by on status of the monitored input Hold. Hold extinguishing could be controlled by a manual button if extra evacuation time is needed and monitoring if the doors of the protected premise are tightly closed. After the hold signal is cancelled the timer for the evacuation time is started automatically. After the evacuation time expires the extinguishing executive device is switched on. The indication for hold extinguishing is an individual light indication. GROUNDS non-system non-fatal fault condition, due to leakage to a grounded wire. MONITORED INPUT input that monitors the serviceability of the connection wires between the fire extinguishing control panel and the executive devices. Follow the special diagram for connection. (See section 5.2.). MONITORED OUTPUT a potential output that monitors the serviceability of the connection wires between the fire extinguishing control panel and the executive device. Follow the special diagram for connection. (See section 5.2.). SHORT CIRCUIT IN A LINE, MONITORED OUTPUT OR MONITORED INPUT non-system, non-fatal fault condition, entered due to registered current value, exceeding a threshold value. LINE IN TEST a line, set in Test condition by the user. The line is switched on (supplied) and reset (the power supply is switched off for 3 s) periodically every 60 s. The events registered in a line in Test condition are not saved in the archive and do not trigger the outputs or the light and sound signaling. The indication for a line in Test condition is a text message in the display field for the respective line. LOCAL SOUNDER a sounder built-in the fire extinguishing control panel. NON-FATAL FAULT CONDITION fault condition that allows the fire extinguishing control panel to continue operation. The non-fatal fault condition is not usually a system fault condition. The indication is common light indication, local sound indication and text messages on the LCD display. ACCESS LEVEL access level to various indications and control functions (See section 5.1). LOW BATTERY non-system fatal fault condition due to full discharge of the backup batteries upon interrupted power supply. SUPPRESSED OUTPUT a monitored or relay output, which should be activated (for the respective Extinguishing stage) but it is switched off manually by the user. FIRE DETECTING LINE (further in the text only LINE) a combination of fire detectors, physically connected by two-wire connection. Maximum 32 fire detectors could be connected in each line. FIRE CONDITION STAGE I phase of Fire condition; upon activation of automatic fire detector only in one line the fire extinguishing control panel enters Fire condition. It continues until the line is manually reset by Reset Alarm. The indication for Fire condition stage 1 is common light indication. Local sound signaling and text messages on the LCD display. FIRE CONDITION STAGE II phase of Fire condition when active extinguishing procedure is started. The fire extinguishing control panel enters this stage in the event of: а) Fire condition along both fire detecting lines; Instruction Manual Page 5

6 b) Manual button release for forced extinguishing. The indication for Fire condition stage 1 is common light indication. Local sound signaling and text messages on the LCD display. INTERRUPTED LINE, MONITORED OUTPUT OR MONITORED INPUT non-system non-fatal fault condition entered when parameters lower than the threshold value are registered. RELAY OUTPUT a relay, potential-free switching outputs provided for controlling external executive devices. MANUAL RELEASE condition entered by the fire extinguishing control panel in the event of Fire condition stage II, regardless the status of the Fire detecting lines. The manual release is defined by on status of the monitored input Manual Release. MANUAL MODE condition when the fire extinguishing control panel could release the extinguishing devices only by manual release command. The manual mode is defined by on status of the monitored input Mode Select. The mode indication is an individual light indication. SYSTEM FAULT CONDITION fault condition due to a fault in the fire extinguishing control panel (system s) component panel. The system fault condition could be fatal or non-fatal. The indication is common light indication, local sound indication and text messages on the LCD display. REMOVED FIRE DETECTOR /FD/ non-system non-fatal fault condition entered when a removed fire detector in a line is registered. In order this function to be utilized follow the special diagram for connection (See section 5.2.). LINE STATUS, MONITORED OUTPUT OR MONITORED INPUT the current status of a line, monitored output or input: duty mode; fire condition (only for the fire detecting lines); fault condition (specifying the type of the fault condition). FATAL FAULT CONDITION fault condition that prevents the fire extinguishing control panel, or the part of it related to the communication with the user, from continuing its operation. The fatal fault condition is usually a system one, except Law Battery fault condition. The indication is common light indication, local sound indication and text messages on the LCD display. 2. Technical data Fire detecting lines For extinguishing control - 2 Without extinguishing control - 1 Maximum number of fire detectors in a line - 32 Type of the connecting line - two-wire Maximum resistance of a loop Output resistance of the line Current thresholds in a line per default parameters for: 0 3mA* - interruption 3 12mA* - duty mode 12 60mA* - fire condition >80mA - short circuit * It is possible the current in the lines for interruption, duty mode and fire condition to be adjusted ( ) Monitored outputs for control the fire extinguishing control panel performance: Instruction Manual Page 6

7 Type 2.3. Monitored outputs for the sound-light indication Type Electrical characteristics 2.4. Monitored output for the extinguishing devices Type Electrical characteristics 2.5. Relay outputs for common purpose Type Electrical characteristics 2.6. Relay output for fault condition Type Electrical characteristics 2.7. Relay output for fire alarm Type Electrical characteristics - balanced - potential relay - (24±3)V/0.5 A - potential relay - (24±3)V/1.5A - potential free, switching - 3A/125VAC; 3A/30VDC - potential free, switching - 3A/125VAC; 3A/30VDC - potential free, switching - 3A/125VAC; 3A/30VDC 2.8. Performance characteristics Control over the lines, the monitored inputs and outputs for fault condition (short circuit and interruption) and automatic reset Control over the lines for removed fire detector and automatic reset Ability to set the evacuation time Ability to set the time when the extinguishing executive device is switched on Built-in sounder for fire alarm first stage one tonal, discontinuous, can be switched off Built-in sounder for fire alarm second stage one tonal, continuous, can be switched off Built-in sounder for fault condition one tonal, discontinuous, can be switched off Built-in real time clock Set of test modes and options for adjustment: Setting the clock; Check ups on light and sound indications; Test of the fire detecting lines; Adjustment of outputs and integrated external devices; Current measurement in the fire detecting lines; Programming of parameters and modes of operation; Remote programming of the parameters from distant operator control point; Energy independent archive of registered events by the fire extinguishing control panel with the events type, date and hour up to 100 events; Interfaces for communication with external devices - RS-485 and CAN Indications of registered events Light indication - LED Text message - LED display - 4 lines 20 characters per line, Cyrillic, backlit Sound signaling - built-in sounder Power supply Mains voltage - 220/230V frequency - 50/60Hz Back up batteries battery type number of batteries connection - led, gel electrolyte - 2 pcs - serial connection Instruction Manual Page 7

8 nominal voltage of the back up battery - 2x12V nominal capacity C 20 - (7-12)Ah extreme discharge voltage - 21V charge voltage - 28,2V Consumption on back up batteries supply At 24V - < 120mA Power supply to external devices Voltage - (24±3)V Maximum current value (including current of monitored outputs ) - 2,5А Dimensions Overall dimensions Weight weight (batteries not included), maximum - 450х355х115mm - 6,6kg 3. Contents of delivery 3.1. Fire extinguishing control panel Fire detecting control panel FS5200Е Resistors 3,0k / 0,25W Resistors 1,5k / 0,25W Diode 1N4004 Jumper for the back up batteries Fuse 4A CD (Instruction manual,operator s manual) Packing - 1 pc pcs. - 5 pcs. - 1 pc. - 1 pc. - 2 pcs. - 1 pc. - 1 pc. 4. Installation and arrangements When fire detectors and periphery devices are integrated in the fire extinguishing control panel, avoid arranging wires in closed loops; it will reduce the control panel s resistance to electro magnetic interferences To mount the control panel unpack the control panel; put the dowels on the determined places for fixing the control panel; fasten the control panel to the dowels through the three holes provided on the chassis Description of inputs and outputs. Periphery devices assembly to the control panel. All connections are to be made by means of terminals, mounted on the printed circuit board. Be advised, that the total consumption of the voltage powering the external devices (terminal + 28V ) plus the consumption of the monitored outputs shall not exceed 2.5A in heavy duty mode. L1, L2 Inputs for switching automatic Fire detectors. In Fire condition an extinguishing procedure starts along both lines according to set up algorithm. L3 Fire detecting line input. Manual Release Input with line status monitoring. The input sends a signal to the control panel from a manual button to start the extinguishing procedure. Mode Select - Input with line status monitoring. The input sends a signal to the control panel from a switch for the operating mode. The modes are Manual-Automatic and Manual. Hold - Input with line status monitoring. The input sends a signal to the control panel Instruction Manual Page 8

9 from a manual button or controlled contact for holding (delaying) the extinguishing procedure. On/Off Exting - Input with line status monitoring. The input sends a signal to the control panel from a switch for disabling the extinguishing procedure. Low Press - Input with line status monitoring. The input sends a signal to the control panel from pressostat contact, balance or other device to show the extinguishing agents draining. GND Terminal for sending GND potential to the periphery devices. Еxting Active level output with line status monitoring. The output switches the extinguishing automation valves on. S2 Sounder Active level output with line status monitoring. The output switches the sound-light indication on in Fire condition stage II. S1 Sounder Active level output with line status monitoring. The output switches the sound-light indication on in Fire condition stage I. Rele Fire Output, relay, potential free, the line status is not monitored. The output controls the devices in Fire condition of the control panel, registered by the fire detecting lines. Rel Fault Output, relay, potential free, the line status is not monitored. The output controls the devices in Fault condition of the control panel. +28V Three terminals for supplying 28V voltage to the periphery devices as well as the positive potential of the open collectors OK1, OK2 and OK3. OK1 Output open collector /in active status it supplies GND potential, in non-active status it has potential +28V via resistor 47k/0.125W/. The output controls relays, LEDs and other devices, with total consumption not exceeding 100mA. The output is active when the control panel has registered extinguishing reagent leakage. OK2 Output open collector /in active status it supplies GND potential, in non-active status it has potential +28V via resistor 47k/0.125W/. The output controls relays, LEDs and other devices, with total consumption not exceeding 100mA. The output is active when the control panel is in Disable Extinguishing Mode. OK3 Output open collector /in active status it supplies GND potential, in non-active status it has potential +28V via resistor 1k/0.125W/. The output controls relays, LEDs and other devices, with total consumption not exceeding 100mA. The output is active when the control panel is in manual Mode. Rel 2ST Output, relay, potential free, the line status is not monitored. The output controls the devices in Fire condition stage II of the control panel. Rel 1ST Output, relay, potential free, the line status is not monitored. The output controls the devices in Fire condition stage I of the control panel. CAN Terminals to connect the two-wire line of CAN interface. The connection with the Interactive system IFS7002 /production of LTD/ is executed via this interface. A jumper is provided that shunts the line by 120 ohms. It is needed if the fire extinguishing control panel is the final point in the interface line. The interface requires resistors 120 ohms to be mounted in both ends of the line. RS 485 Terminals to connect the two-wire line of RS 485 interface. The connection with a repeater, PC and other devices realized by exchange protocol - UniProtocol /FS5200E interface/ is executed via this interface. As the case with CAN interface, a jumper is provided here too with the same functions. Terminal to connect a third wire /screen/ of the interfaces cable. Instruction Manual Page 9

10 A RS485 B H CAN L RS485 term CAN term GND NC NO NC NO NO NC C REL Fault Rele Fire NC NO 3k 3k + S1 - Sounder + S2 - Sounder + - Exting 1,5 k 3k Low Press. FS5200E 1,5k 3k On/Off Exting 1,5k 3k Hold 1,5k 3k Mode Select 1,5k 3k 1,5k Manual Release 3k FD FD FD 3k FD FD FD 3k FD FD FD Interface CAN (join to system IFS7002) Jump (RS485) Interface RS 485 (repeater, PC and other devices) Relay output in condition Fire Alarm Phase 1 Jump (CAN) Jump Rel 1ST Rel 1ST Rel 2ST OK1 +28V OK2 +28V OK3 +28V Relay output in condition Fire Alarm Phase 2 Output Open Collector Active in case of extinguisher leakage (+28V) Output Open Collector Active in case of extinguishind disable (+28V) Output Open Collector Active in manual mode (+28V) Jump Rel 2ST Relay output in Fault Alarm condition Relay output in Fire condition Jump relay Fire Sounder Fire Alarm Phase 1 (28V/0,5A) Sounder Fire Alarm Phase 2 (28V/0,5A) 1N4004 Device Extinguishing (28V/1,5A) Switch for monitoring extinguisher leakage Switch for extinguishing disable Button for extinguishing delay Switch mode manual/manual-automatic Buttons manual extinguishing activation + L1 - + L2 - + L3 - Fire Alarm Line 1 Fire Alarm Line 2 Fire Alarm Line 3 Drawing1 Instruction Manual Page 10

11 Description and mounting of devices to L1, L2 and L3 inputs Connect a two-wire line at L1, L2 and L3 inputs for connection with the Fire detectors. The line total resistance shall not exceed 100. The recommended wire section depending on the lines length is: To 500 m -cable 2 х 0.5 mm 2 To 1000 m -cable 2 х 1.0 mm 2 To 1500 m -cable 2 х.1.5 mm 2 It is recommended to make a check with a multicet before connecting the fire detecting line to the fire extinguishing control panel. If the line is installed correctly (with mounted final resistor 3kΩ / 0.25W) between the plus and minus of the cable entering the fire extinguishing control panel the measured resistance should be 3kΩ (+/-10%). Also when measuring both wires to ground the multicet should show no connection or leakage. Make the connection to the terminals + Lx - (where x is the line number). Observe the shown polarity (Drawing 2). First detector Last detector - Lx + FS5200E 1N5819* +OUT +IN FD80xx -IN/OUT RI/KL- 1N5819* 5 4 FD30xx 2 1 3k/0.25W Drawing 2 * Diode 1N5819 or similar Use automatic fire detectors FD3000 or FD8000 series or other compatible automatic fire detectors. Mount resistor 3 kω / 0.25W on the last fire detector in the line. Mount diodes, for example 1N5819 or similar in the shown direction if you are to use the fire extinguishing control panel function to register Fault condition removed fire detector. Maximum 32 fire detectors could be mounted to one line regardless of their type. When mounting the fire detectors take into consideration the specific technical characteristics of the fire detector with the fire extinguishing control panel parameters for the current threshold in the different conditions. Change the current threshold from Set up menu. Current thresholds in a line with default parameters for the conditions: 0 3mA* - interruption 3 12mA* - duty mode 12 80mA* - fire condition >80mA - short circuit Mount fire detectors on Lines 1 and 2 in the premise where the extinguishing will be performed. The first and the second line are in a logical dependence I ; the fire extinguishing control panel enters Fire condition stage II if only both lines are activated and the extinguishing algorithm is possible to be executed. Line 3 is only Fire detecting and it serves for fire protection of the adjoining premises to the extinguished zone. When this line is activated it switches on the outputs for Fire condition stage I as well as the common output for Fire condition. This line is not included in the extinguishing algorithm logic. Line 3 can be assumed as a standard line of a Fire control panel. Instruction Manual Page 11

12 Description and mounting of devices to Manual Release input Connect a two-wire line to the Manual Release input for connection with the manual release buttons for extinguishing activation. It is possible to mount maximum three buttons. The line is balanced and it is monitored for interruption and short circuit. Install resistors to the button terminals as shown in the connecting diagrams to monitor the condition. Install resistor 3k to the last button if 2 or 3 buttons are mounted (Drawing 3). Connecting diagram with 1 button FS5200E Button for manual activation of the extinguishing Release Manual 3k/ 0.25W 1.5k/ 0.25W Connecting diagram with 2 buttons FS5200E Button 1 Button 2 Release Manual 1.5k/ 0.25W 3k/ 0.25W 1.5k/ 0.25W Connecting diagram with 3 buttons FS5200E Button 1 Button2 Button 3 Release Manual 1.5k/ 0.25W 1.5k/ 0.25W 3k/ 0.25W 1.5k/ 0.25W Drawing 3 When the contact is closed the fire extinguishing control panel accepts the button to be active Description and mounting of devices to Mode Select input Connect a two-wire line to the Mode Select input for connection with a switch to select the fire extinguishing control panel mode Manual-Automatic or Manual. The line is balanced and it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition. When the contact is closed the fire extinguishing control panel accepts Manual Mode; when it is opened Manual-Automatic Mode. Output Open collector type is activated in Manual Mode. That output could be used as switch indication, if this option is provided. Instruction Manual Page 12

13 FS5200E Switch modes Manual/Manual-automatic Select Mode 1.5k/ 0.25W Description and mounting of devices to Hold input Connect a two-wire line to the Hold input for connection with a switch to activate hold extinguishing function. The line is balanced and it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition (Drawing 4). FS5200E Switch Extinguishing delay Hold 3k/ 0.25W 1.5k/ 0.25W Drawing 4 Set up the input active status: OPEN or CLOSED contact from menu System functions > Set up > Input/Outputs > Hold input. Attention! The active status of the default parameters is OPEN contact of the switch in order the fire extinguishing control panel to accept Hold Extinguishing function Description and mounting of devices to On/Off Exting input Connect a two-wire line to the On/Off Exting input for connection with a switch to disable extinguishing. The line is balanced and it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition (Drawing 5). FS5200E Switch Extinguishing disable On/Off Exting 3k/ 0.25W 1.5k/ 0.25W Drawing 5 When the contact is closed the fire extinguishing control panel accepts Disable Extinguishing. Output Open collector type is activated in Disable Extinguishing. That output could be used as switch indication, if this option is provided. Instruction Manual Page 13

14 Description and mounting of devices to Low Press input Connect a two-wire line to the Low Press. input for connection with a pressostat contact, balance or other devices registering a Fault condition in the extinguishing installation. The line is balanced and it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition (Drawing 6). FS5200E Pressure Press. Low 3k/ 0.25W 1.5k/ 0.25W Drawing 6 Set up the input active status: OPEN or CLOSED contact from menu System functions > Set up > Input/Outputs > Low Press input. Attention! The active status of the default parameters is OPEN contact of the switch in order the fire extinguishing control panel to accept the function Leaked extinguishing agent or Fault condition Description and mounting of devices to Exting output Connect a two-wire line to the Exting output for connection with a magnetic valve or other device to activate the extinguishing automation. The line is balanced and it is monitored for interruption and short circuit. Install a diode 1N4004 or similar to the executive device terminals in the direction as shown in the connecting diagram as the valve winding resistance shall be in the range: 30Ω 3kΩ. (Drawing 7). Install a parallel resistor 3kΩ / 0.25W and a serial diode 1N5401 on the line if the winding resistance is less than 30Ω (Drawing 8). Connecting diagram if the winding valve active resistance is from 30 Ω to 3к Ω FS5200E Electromagnetic valve Exting + - 1N4004 V Rv - 30 Ohms up to 3 k Drawing 7 Connecting diagram if the winding valve active resistance is less than 30 Ω Instruction Manual Page 14

15 FS5200E Electromagnetic valve Exting + - 3k/ 0.25W 1N4004 1N5401 V Rv - < 30 Ohms Drawing 8 Upon the output activation the supplied voltage (24±3)V is with load-carrying capacity of 1.5А. The time for output activation could be set from 2 to 255 seconds from menu System functions > Set up > Extinguishing time and it depends on the type of the used executive device. The default setting is 10 seconds Description and mounting of devices to Sounder S1 and Sounder S2 outputs Connect a two-wire line to the Sounder output for connection with sound and light signaling devices. The line is balanced and it is monitored for interruption and short circuit. Install a resistor 3kΩ/0.25W to the signaling device terminals to monitor the condition (Drawing 9). FS5200E Sounder - Sx + 3k/ 0.25W Drawing 9 Upon the outputs activation the supplied voltage (24±3)V is with load-carrying capacity of 0.5А. The outputs are activated for Fire condition stage I and Fire condition stage II, respectively. The fire extinguishing control panel provides the option for Sounder S1 output disable from menu System functions > Disables > Disable S1 output Description and mounting of devices to outputs OK1, OK2 and OK3 open collector type OKx outputs send a signal to relays, LEDs and other devices to follow and monitor the fire extinguishing control panel condition. The outputs are not monitored for the line status. 28V +28V 47k OKx GND Drawing 10 Upon activation of the outputs GND potential is supplied with load-carrying capacity of 0.1А. The internal diagram of output Open collector type is presented on the drawing (Drawing 10) Description and mounting of devices to Rel Fire output Rel Fire is a potential free, relay output. The logic of the contact - Normally Open or Normally Closed could be adjusted by means of a jumper. The output is not monitored. The output is activated in Fire condition along one or both fire detecting lines. Instruction Manual Page 15

16 Description and mounting of devices to Rel 1 ST and Rel 2 ND outputs Rel 1 ST and Rel 2 ND are potential free, relay outputs. The logic of the contact - Normally Open or Normally Closed could be adjusted by means of a jumper. The outputs are not monitored. The outputs are activated in Fire condition stage I and Fire condition stage II, respectively. The fire extinguishing control panel provides the option to disable the activation of Rel 1 ST and Rel 2 ND outputs from menu System functions > Disables > Disable Rel 1ST / Disable Rel 2ND Description and mounting of devices to Rel Fault output Rel Fault is a potential free, relay output, as both relay contacts are possible Normally Open or Normally Closed. The output is not monitored Description and mounting of devices to RS485 interface terminals RS485 interface is designed to transmit information and to receive commands from FS5200R repeater. The following connection configurations are possible: One fire extinguishing control panel and one repeater One fire extinguishing control panel and up to 6 repeaters Up to 15 fire extinguishing control panels and 1 repeater Up to 6 repeaters and up to 10 fire extinguishing control panels (If less than 6 repeaters are installed they could be substituted by fire extinguishing control panels, i.e. configuration of 3 repeaters and 13 fire extinguishing control panels, etc.) FS5200R repeater receives information from all fire extinguishing control panels as it indicates the occurred events by sound signaling, light indication and text messages. It is also possible a remote fire extinguishing control panel to be reset. RS485 interface could be used also for communication with other intelligent devices and PCs. The connection between the devices along RS485 is parallel connection. Observe the requirement potential A and B not to be crossed. The maximum distance between the end devices is 1000 meters. Jumper to shunt the line by 120 ohms has to be installed on the first and the last device regardless the line length. On all other devices the jumper has to be removed (Drawing 11). End device FS5200x 120 FS5200x 120 End device FS5200x 120 А В RS485 J А В RS485 А В RS485 J RS485 А В RS485 А В FS5200x 120 FS5200x 120 Drawing Power supply connection Connect a feeding cable to the terminal with mains fuse, observing the following positions (Appendix 3): P power wire Phase ; Instruction Manual Page 16

17 N power wire Null ; Ground - safety ground wire. The cable shall be double insulated and of 0,5mm 2 section for the power supply wires, and of 1,5mm 2 section for the safety ground wire. The other end of the feeding cable is connected to the mains power supply by means of junction box. The mains power supply of the fire control panel shall be in a separate loop. 5. General information 5.1. Access levels 4 levels of access to the variable indications and control functions of FS5200Е are available Access level 1 All persons who would presumably find out and react to alarm upon fire condition or fault condition have access to level 1. The following actions are accessible: Displaying suppressed messages for Fire condition stage I, Fire Condition stage II, Fault condition, Disabled components; Forced proceeding from phase Fire condition stage I to phase Fire condition stage II ; Suppressing the local sounder; Displaying the status of the lines and the monitored outputs (see section 12.5); All light indicators are visible Access level 2 The personnel in charge of the fire protection have access to level 2; they shall be trained and authorized to operate the fire control panel in the following conditions: Duty Mode; Fire condition stage I; Fire condition stage II; Fault condition; Disabled component; Information and adjustment. To enter Access level 2, turn the key on the front panel of the fire extinguishing control panel into position. The following features of the fire extinguishing control panel are accessible: All features accessible at Level 1; Switching off the outputs, activated upon fire condition; Exit of Fire condition; System functions of the fire extinguishing control panel except entering Set up Mode (see section Error! Reference source not found.) Access level 3 Accessible for personnel trained and authorized for: Reconfiguration of specific data of the protected site or of the fire extinguishing control panel saved in the memory; Maintenance of the fire control panel. This level has two sublevels of access - 3A and 3B. Level 3, sublevel 3A, is accessed through a password entered at Access level 2. At this sublevel the functions for reconfiguration of specific data for the protected site or the fire extinguishing control panel are accessible. Level 3, sublevel 3B is accessed when the fire extinguishing control panel is opened. The following features are accessible: Replacing a burnt fuse; Adding, removing or replacing a module; Connecting fire detecting lines and executive devices. Instruction Manual Page 17

18 Access Level 4 Accessible for personnel trained and authorized by the Producer to repair the fire extinguishing control panel and to modify the software. Special means are required to enter this level Indications and buttons for control Table 1 gives detail description of the indications for each status, Table 2 presents the basic function of the control buttons. Appendix 1 shows the front panel of FS5200 with the indications and buttons for control. Table 1 Conditions of the fire extinguishing control panel All conditions - The fire extinguishing control panel is power supplied Fire condition Fire condition Stage I and Stage II Fire condition Fire condition Stage I Fire condition Fire condition Stage II Manual Mode a signal for manual mode of extinguishing control is given Manual Mode a signal for manual mode of extinguishing control is given Disabled extinguishing a signal disabling the extinguishing is given Extinguishing held a signal holding the extinguishing is given Fire Condition and Fault Condition the sound indication is suppressed Fire condition Stage I - The fire condition stage I outputs are suppressed Fault condition - All faults except for Battery Low Fault condition System Error and new Configuration Fault condition Fault in mains supply or backup battery Fault condition fault condition in monitored line Fault condition fault condition Low pressure in the extinguishing installation Disabled component - Disabled line or monitored output Fire condition Stage I Fire condition Stage II Indication Indicator Power Supply continuous green light Individual indicators for Fire condition in the fire detecting lines Common indicator Fire condition Stage I continuous red light Common indicator Fire condition Stage II flashing red light during the evacuation time and continuous red light after the automated extinguishing is switched on Indicator Manual Mode - continuous yellow light Indicator Manual-Automatic Mode - continuous yellow light Indicator Disabled Extinguishing - continuous yellow light Indicator Extinguishing Held - - continuous yellow light Indicator Stop Alarm - continuous red light Indicator Suppressed Outputs - continuous red light Common indicator Fault Condition - continuous yellow light Indicator System Error - continuous yellow light Indicator mains Supply Fault - continuous yellow light Indicator Monitored Line Fault - continuous yellow light Indicator Low Pressure Fault - continuous yellow light Indicator Disabled Component continuous yellow light Local sounder discontinuous signal: 4 sound impulses for 1 s, followed by 1 s break Local sounder continuous signal Instruction Manual Page 18

19 Conditions of the fire extinguishing control panel Fault condition - All faults except for Battery Low Fault condition - Low battery Indication Local sounder discontinuous signal: 1 s sound, followed by 1 s break Local sounder discontinuous signal: 1 s sound, followed by 3 s break Instruction Manual Page 19

20 Table 2 Means of control Condition of the fire extinguishing control panel Access level operation Access level 2 key Button Line Reset Button Outputs Button Alarm Button Menu Button Down Button Up Button Cancel Level 1 Level 2 Fire condition Level 2 Fire condition, phase Fire condition Stage I Fire condition, phase Fire condition Stage II Fire condition Stage I or Stage II and Fault condition* Duty Mode, Fire condition, Fault condition*, Test and Disabled component Information and Control Mode Set up Mode Level 2 Level 2 Level 1 Levels 1 and 2 Levels 1 and 2 Level 3А Status Status Output from Fire Condition stage I or Fire condition stage II initiated on the display - if outcomes for Fire condition Stage I are activated to suppress them; - if outcomes for Fire condition Stage I are suppressed to activate them - If the common output for fire condition is activated to suppress it; - if there is no activated common output for fire condition to activate it To suppress/activate the local sounder To enter Information and Control Mode - To enter the selected menu; - To execute the selected command; - To save the modified parameter Fire condition Levels 1 and 2 To show on the display the next message for fire condition Information and Control Mode Set up Mode Fire Condition Information and Control Mode Set up Mode Information and Control Mode Set up Mode Levels 1 and 2 Level 3А Levels 1 and 2 Levels 1 and 2 Level 3А Levels 1 and 2 Level 3А - To show on the display the next element from the menu; - To move the cursor; - To modify the selected parameter To show on the display the previous message for fire condition - To show on the display the previous element from the menu; - To modify the selected parameter - To exit a function without saving changes in the parameter; the command will not be executed; - To exit the current menu and to move to an upper hierarchy menu * Not operating in Fault condition (fatal fault condition except New Configuration) Conditions of the Fire Extinguishing Control Panel The fire extinguishing control panel FS5200Е monitors the fire detecting lines and the monitored outputs as it scans consecutively their status. Depending on the current the fire extinguishing control panel could be in Duty Mode, in Fire condition or Fault condition (short circuit or interruption). Depending on the measured parameters the inputs could be in Fault condition (short circuit or Instruction Manual Page 20

21 interruption) or active status. Simultaneously the monitored outputs are followed constantly for in Fault condition (short circuit or interruption). The fire extinguishing control panel FS5200Е operates in eight main conditions: Duty Mode, Fire condition Stage I, Fire condition Stage II, Fault Condition, Disabled component, Test Mode, Information and Control Mode and Set up Mode. At any time the fire extinguishing control panel could be in each one of these conditions or in random combination of the conditions: Fire condition Stage I, Fire condition Stage II, Fault Condition, Disabled component, Test Mode, Information and Control Mode. Duty Mode, Set up Mode and Remote Control cannot be combined with another condition: the fire extinguishing control panel enters Duty Mode when it is not in any of the other conditions; to enter Set up Mode and Remote Control the fire extinguishing control panel has to exit the other conditions. 6. Duty Mode 6.1. Description The fire extinguishing control panel is in Duty Mode, when it is not in any other of the rest eight possible conditions Indication LED and sound indication In Duty Mode only the green LED indicator is activated (Power supply) and the yellow indicator (Manual Mode activated if only the fire extinguishing control panel is in Manual Mode. The local sounder is off Text message The display is divided into panels. The last line shows the condition of both Fire detecting lines that shall be in Protection status. The display also shows the message Protection and the current astronomic time: 6.3. Using the keypad The only accessible button in Duty Mode is enters Information and Control Mode (p.12). (Menu). Press it and the fire control panel 7. Fire Condition Stage I 7.1. Description The fire extinguishing control panel enters Fire condition phase Fire condition Stage I, when - An automatic fire detector is activated only along one of the Fire detecting lines; Instruction Manual Page 21

22 - An automatic fire detector is activated along the first or the second or the third line To exit this condition press button at Access level Indication LED and sound indication In this condition: - The indicator (Power Supply) illuminates in green light; - The indicator (Fire condition Stage I) illuminates in red light; - The indicator of the respective line in Fire condition illuminates in red light; - If the outputs for phase Fire condition Stage I are suppressed by button (Outputs), the LED indicator of the button illuminates in continuous red light. - If the sound indication is suppressed by button (Alarm) the LED indicator of the button illuminates in continues red light. - The indicator (Manual Mode) or the indicator (Manual-Automatic Mode) illuminates in yellow light depending on the selected mode of operation. The local sounder produces discontinuous signal Text message In this condition the display is divided into two text fields. The top one shows the condition of the control panel, the bottom one the condition of the lines. Example: Fire condition is registered along the first line. The indicator of line 1 and the indicator for Fire condition Stage I illuminate in red light. The text message shows the Fire condition stage and the line in which the fire extinguishing control panel is in Fire condition. Potential free relays Rele 1St and Rele Fire are activated. Voltage 28V DC is supplied to the sounder output S Using the keypad Button Access level all Button (Alarm) Operation Press it to: - suppress the local sounder; - activate the local sounder if the fire extinguishing control panel is in Fire condition Stage I or Fault condition and the local sounder has been suppressed by previous pressing of the same button. Additional information The button operation is reversive i.e. press it once to change the current condition alternatively suppressed or activated local sounder. The LED indicator illuminates if the active condition of the local sounder is suppressed. The local sounder is activated again: - when the fire Instruction Manual Page 22

23 extinguishing control panel enters Fire condition Stage II; - upon Fault condition. Button (Outputs) 2, 3 and 4 Press the button to: suppress the outputs activated for phase Fire condition Stage I to activate the suppressed outputs, if any Access level 2 is required to for operation with this button. The key on the front panel should be in position. The button operation is reversive i.e. press it once to change the current condition alternatively suppressed or activated outputs. The LED indicator illuminates if the active condition is suppressed outputs. Button (Line Reset) 2, 3 and 4 Press it to force the fire extinguishing control panel to exit Fire condition Stage I and to reset the line that was in Fire condition (the power supply is switched off for 3s). Access level 2 is required to for operation with this button. The key on the front panel should be in position. Button (Menu) all Press it to enter Information and Control Mode. Button (Cancel) all Press it to exit Information and Control Mode. The main screen for the current status Fire condition Stage I is visualized. of: 8. Fire Condition Stage II 8.1. Description The fire extinguishing control panel enters Fire condition phase Fire condition Stage II, in the case а) fire condition along both fire detecting lines; б) manual button activation for forced extinguishing. In this phase the active extinguishing procedure is initiated. In phase Fire Condition Stage II the following steps are formed connected with the algorithm of the extinguishing procedure: Evacuation time; Activation of the devices to Release the extinguishing mixture 8.2. Indication LED and sound indication In Fire Condition Stage II and the fire extinguishing control panel in the evacuation step the LED indicator illuminates in red flashing light (Fire Stage II). Instruction Manual Page 23

24 In Fire Condition Stage II and expired evacuation time the fire extinguishing control panel activates the extinguishing devices and the LED indicator continuous light. (Fire Stage II) illuminates in red The indicator (Manual Mode) or the indicator (Manual-Automatic Mode) illuminates in yellow light depending on the selected mode of operation. The local sounder produces continuous signal. If the sound signaling is suppressed by button (Alarm), the LED indicator of the button illuminates in continuous red light Text messages during the evacuation step and fire along both lines. The display shows: The message EVACUATION and the remaining time for the activation of the extinguishing devices message FIRE STAGE 2 and information for the current status of the lines: Example: Fire condition along line 1 and line 2. The fire extinguishing control panel is in evacuation phase. The indicator for Fire condition Stage II illuminates in flashing red light. The individual indicators for line 1 and line 2 are illuminated too. Text message for the phase of fire alarm, the remaining time for activation of the extinguishing devices and the current status of the lines is visualized on the display. The local sounder produces continuous signal. Potential free relays Rele 2St and Rele Fire are activated. Voltage 28V DC is supplied to the sounder output S Text messages during the evacuation step and manual button activation. The display shows: The message EVACUATION and the remaining time for the activation of the extinguishing devices message FIRE STAGE 2 Message showing manual activation and information for the current status of the lines Text messages when the extinguishing device is activated. Instruction Manual Page 24

25 The display shows: The message ATTENTION GAS! and EXTINGUISHING ON indicating that the extinguishing agent is released. Information for the current status of the lines: This indication could be suppressed by the screens in Fire condition. The suppressed messages could be displayed in Information and Control Mode. Example: Fire condition along line 1 and line 2. The fire extinguishing control panel is in phase to start extinguishing procedure. The indicator for Fire condition Stage II illuminates in continuous red light. The individual indicators for line 1 and line 2 are illuminated too. The display shows warning messages and the condition of the fire detecting lines. The local sounder produces continuous signal. Potential free relays Rele 2St and Rele Fire are activated. Voltage 28V DC is supplied to the outputs S2 and Exting.. Note: The entry of the fire extinguishing control panel in Fire condition along a new line (e.g. the 3 rd one) is indicated by the standard sound and light indication and text messages Using the keypad Button Access level all Button (Alarm) Operation Press it to: - suppress the local sounder; - activate the local sounder if the fire extinguishing control panel is in Fire condition Stage II or Fault condition and the local sounder has been suppressed by previous pressing of the same button. Additional information The button operation is reversive i.e. press it once to change the current condition alternatively suppressed or activated local sounder. The LED indicator illuminates if the active condition of the local sounder is suppressed. The local sounder is activated again: - when the fire extinguishing control panel enters Fire condition long a new line; - upon Fault condition. Button (Outputs) 2, 3 and 4 Press the button to suppress/activate the fire relay Rele Fire Access level 2 is required to for operation with this button. The key on the front panel should be in position. The button operation is reversive i.e. press it once to change the current condition alternatively suppressed or activated outputs. The LED indicator illuminates if the active condition is suppressed outputs. Instruction Manual Page 25

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Fire Control Panel FS4000

Fire Control Panel FS4000 Fire Control Panel FS4000 INSTRUCTION MANUAL Revision 4/02.11 Contents 1. Introduction... 4 2. Terminology... 4 3. Function... 5 4. Technical features... 5 4.1 Fire alarm lines... 5 4.2. Current thresholds

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Fire Control Panel FS4000

Fire Control Panel FS4000 Fire Control Panel FS4000 INSTRUCTION MANUAL Revision 11/01.17 Contents 1. Introduction... 3 2. Terminology... 3 3. Function... 4 4. Technical features... 4 4.1 Fire alarm lines... 4 4.2. Current thresholds

More information

UniPOS Wireless Fire Alarm Control Panel VIT 01 WIRELESS FIRE ALARM CONTROL PANEL VIT01 INSTRUCTION MANUAL

UniPOS Wireless Fire Alarm Control Panel VIT 01 WIRELESS FIRE ALARM CONTROL PANEL VIT01 INSTRUCTION MANUAL WIRELESS FIRE ALARM CONTROL PANEL VIT01 INSTRUCTION MANUAL Revision 8/10.13 Instruction manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.3. 4.4. 5. 5.1. 5.2. 5.3. 6. 6.1. 6.2. 6.3. 7. 7.1 7.2. 7.3. 8. 8.1. 8.2. 8.3.

More information

REPEATER FS5200R OPERATION MANUAL

REPEATER FS5200R OPERATION MANUAL REPEATER FS5200R OPERATION MANUAL 1. Function Repeater FS5200R receives and transmits data for Fire condition and Fault condition from remote fire control panels (repeaters) and provides information about

More information

CONVENTIONAL FIRE CONTROL PANELS FS 5100 and FS 5200

CONVENTIONAL FIRE CONTROL PANELS FS 5100 and FS 5200 CONVENTIONAL FIRE CONTROL PANELS FS 500 and FS 500 BASIC FEATURES Fire Control Panels FS 500 and FS 500 are up-to-date, highly reliable, multifunctional and versatile units, providing the user with unexpected

More information

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual S2000-ASPT Fire Alarm and Extinguishing Control Panel Engineer s and User s Manual FIRE ALARM AND EXTINGUISHING CONTROL PANEL ATTENTION! To modify the panel configuration parameters use the program UProg.exe

More information

Extension Module. Fig.1

Extension Module. Fig.1 Extension Module Type FD 4201 05/12.17 General Description Module FD 4201 is optional for the fire control panel FS4000. Expands the functionality of the fire control panel, as follow: - Connection of

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

S INTRUSION&FIRE ALARM AND ACCESS CONTROL PANEL

S INTRUSION&FIRE ALARM AND ACCESS CONTROL PANEL S2000-4 INTRUSION&FIRE ALARM AND ACCESS CONTROL PANEL Installer s and User s manual S2000-4 INTRUSION&FIRE AND ACCEESS CONTROL PANEL ATTENTION! To modify configuration parameters use the program uprog.exe

More information

ZSC100 Gas Detection and Alarm System Controller

ZSC100 Gas Detection and Alarm System Controller ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

VAP304 PRO INSTALLATION & OPERATION MANUAL

VAP304 PRO INSTALLATION & OPERATION MANUAL VAP304 PRO INSTALLATION & OPERATION MANUAL Panic Fire Duress Program Bypass Report Chime Test Memory B A D C Program Chime Panic Duress Exit Fire Report Bypass Memory Test Reset Password Exit Reset Password

More information

"DMTeh" Ltd. Pleven. Fire conventional panel FP 9000 Installation, setup and operation.

DMTeh Ltd. Pleven. Fire conventional panel FP 9000 Installation, setup and operation. ISO 9001:2008 Certified Company Tel./Fax : +359 64 801 597 e-mail : office@dm-teh.com web : www.dm-teh.com Address : Pleven,Bulgaria 5800 34 Gen. Lt. Atanas Stefanov Str. "DMTeh" Ltd. Pleven Fire conventional

More information

ANALOGUE ADDRESSABLE FIRE PANEL MAGPRO96 INSTALLATION AND PROGRAMMING MANUAL

ANALOGUE ADDRESSABLE FIRE PANEL MAGPRO96 INSTALLATION AND PROGRAMMING MANUAL ANALOGUE ADDRESSABLE FIRE PANEL MAGPRO96 INSTALLATION AND PROGRAMMING MANUAL C 1293 Contents 1. INTRODUCTION...4 1.1 General Description... 4 1.2 General Specifications... 4 1.2.1 General Technical Specifications...

More information

DIGITAL TEMPERATURE RELAY TR-100

DIGITAL TEMPERATURE RELAY TR-100 LTD Research-and-Manufacture Company DIGITAL TEMPERATURE RELAY USER S MANUAL www.novatek-electro.com - 2 - Service manual is intended for getting acquaints with hardware, operation principals, modes of

More information

Orion ISS. Intrusion and Fire Alarm Panel. Signal-10. User s Manual

Orion ISS. Intrusion and Fire Alarm Panel. Signal-10. User s Manual Orion ISS Intrusion and Fire Alarm Panel Signal-10 User s Manual This User s Manual is intended to help for studying operability principles and maintenance of Signal-10 Intrusion and Fire Alarm Panel of

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-5:2000+A1:2002 EN54-25:2008 0359 Electro Detectors Ltd. Electro House Edinburgh

More information

InBio X60 Series Access Control Panel User Manual

InBio X60 Series Access Control Panel User Manual InBio X60 Series Access Control Panel User Manual Version: 1.4 Date: Nov., 2015 About This Manual This manual introduces the installation connection and user manual of the InBio X60 Series Access Control

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

Building Technologies. FDUL221 en Line tester operating instructions for electricians

Building Technologies. FDUL221 en Line tester operating instructions for electricians FDUL221 en Line tester operating instructions for electricians 1. Intended use The FDUL221 line tester is used to diagnose an addressed detector line in FDnet/C-NET. During diagnosis, the detector line

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

Insulation fault evaluator EDS460-DG

Insulation fault evaluator EDS460-DG Insulation fault evaluator for localising insulation faults in DC IT systems with a number of branch circuits where high system leakage capacitances are involved Preliminary data sheet TDB108021en/09.2008

More information

ANALOGUE ADDRESSABLE FIRE PANEL

ANALOGUE ADDRESSABLE FIRE PANEL ANALOGUE ADDRESSABLE FIRE PANEL INSTALLATION AND PROGRAMMING MANUAL Contents 1. Introduction... 5 1.1 General Description... 5 1.2 General Specifications... 5 1.2.1 General Technical Specifications...6

More information

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Operating instructions SENTRI4 Control panel based Fire detection and alarm system 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32

IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32 1) DESCRIPTION IFP-2.2 Manual IFP-2.8 and IFP-2.2 is a microprocessor controlled Fire Panel with 2 loops intended either for privat Homes & Apartments or larger installations. The two loops are balanced

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

CONTROL AND INDICATOR MODULE. Potok-BKI INSTRUCTION MANUAL

CONTROL AND INDICATOR MODULE. Potok-BKI INSTRUCTION MANUAL CONTROL AND INDICATOR MODULE Potok-BKI INSTRUCTION MANUAL 1. TECHNICAL DATA 1.1 General 1.1.1 The control and indicator module Potok-BKI of version 1.00 (hereinafter referred to as the module) is designed

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Interface Module RS232/485. INTERFACE MODULE RS232/485 Instruction Manual 03-INT-02-17

Interface Module RS232/485. INTERFACE MODULE RS232/485 Instruction Manual 03-INT-02-17 Ter.bus Interface Module RS/485 INTERFACE MODULE RS/485 Instruction Manual 0-INT-0-7 General description Interface Module RS/485 is designed for implementing the communication function between fire control

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1 ViewMatrix Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels Version: 2.0 Revision: 0.1 CONTENTS 1. Introduction...3 2. Keyboard...5 2.1 POWER indication - Normal Operation...5

More information

IGNIS 1520M AUTOMATIC FIRE EXTINGUISHING SYSTEM CONTROLLER

IGNIS 1520M AUTOMATIC FIRE EXTINGUISHING SYSTEM CONTROLLER IGNIS 1000 FIRE DETECTION SYSTEM IGNIS 1520M AUTOMATIC FIRE EXTINGUISHING SYSTEM CONTROLLER Installation and Maintenance Manual ID-E294-011GB IA Edition 2 ID-E294-011GB The IGNIS 1520M automatic fire extinguishing

More information

CPA6. Installation & User Guide. Intelligent Security & Fire Ltd. Compatible Equipment

CPA6. Installation & User Guide. Intelligent Security & Fire Ltd. Compatible Equipment Installation & User Guide Compatible Equipment CPA6 OM - Output Module 9040 - Loudspeaker DC54/58 - Digital Communicators (Stand Alone Only) 496524 Issue A 1 of 16 CPA6 Overview Introduction Facilities

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000 SERVICE INSTRUCTIONS FOR Fire Alarm System MINI-2000 Version 1.3 02.04.1998 Jari Ollila Tom Brunberg Oy Esmi Ab Copyright Oy ESMI Ab, 1991... 1998 The copyright to the documentation herein is the property

More information

ID2000. operating manual

ID2000. operating manual ID2000 operating manual 997-434-000-2, Issue 2 Contents ID2000 Series Operating Manual Contents 1 Introduction 1 1.1 Associated Documents 1 1.2 The ID2000 Panels 1 1.3 Cleaning 2 2 Panel Controls and Indicators

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3

More information

Fire and Gas Monitoring Panel ST7-HV

Fire and Gas Monitoring Panel ST7-HV Fire and Gas Monitoring Panel ST7-HV INTRODUCTION TO THE ST7-HV SYSTEM The ST7-HV system is a programmable PLC suitable for safety and security installations with a high technological and economic content

More information

ocbridge Plus SPECIFICATION 3. COMPONENTS Wireless sensors receiver, battery СR2032, manual, instalation CD.

ocbridge Plus SPECIFICATION 3. COMPONENTS Wireless sensors receiver, battery СR2032, manual, instalation CD. 1 2 3 4 5 6 7 8 IN OFF ON + T S B J Т1 ocbridge Plus 1. FEATURES Wireless sensors receiver ocbridge is designated for connecting compatible Ajax devices to any third party wired central unit (panel) with

More information

User Manual. Security Systems Security System L208

User Manual. Security Systems Security System L208 User Manual Security Systems Security System L208 a Contents This hand book is a technical instruction document for the installation, commissioning and operation of the L208 intrusion alarm security system.

More information

Flair 500 Series Annunciators

Flair 500 Series Annunciators Flair 500 Series s Basics Flair Multi-Zone s (MZAs) are fully functional, flexible, programmable micro controller based alarm control panels. They can be used independently d or in conjunction with other

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 3 1.2.3

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Bender Incorporated 700 Fox Chase, Coatesville PA 1930 Tel.: (800) 356-466 Fax: (610) 383-7100 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control function

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit PRODUCT INSTRUCTIONS Fire Door Control Panel (FDCP) Floats Rd, Wythenshawe, Manchester. M23 9WB T: 44 (0)161 945 4561 F: 44 (0)161 945 4566 Stock Code Description Doc No: PI115 00133 00134 Ellard Fire

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS DCA4 Digitally controlled Audio Matrix Product Specification March 2002 Current Thinking Document Number DDC DCA 7001 01 ACS Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public

More information

Planning Instructions MEW01090 Revision 4

Planning Instructions MEW01090 Revision 4 Planning Instructions MEW01090 Revision 4 Fire Alarm System EBL128 V1.1.x Author: Jan Pettersson Date of issue: 2008-07-11 Date of rev: 2011-04-08 This page has deliberately been left blank. Table of contents

More information

Fire detection and alarm system Operating instructions

Fire detection and alarm system Operating instructions Fire detection and alarm system Operating instructions Operating instructions Table of Contents User responsibility - - - - - - - - - - - - 4 Daily - - - - - - - - - - - - - - - - - - - 4 Weekly - - -

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

with internal sensor (channel 1) with an external sensor (channel 2) A-Editor software, Professional AK20 version (not for version AK4)

with internal sensor (channel 1) with an external sensor (channel 2) A-Editor software, Professional AK20 version (not for version AK4) Examples of use Example Creating an SMS-based alarm with confirmation A project file must first be created using the A-Editor software. This project file is then stored in the alarm modem. The alarm modem

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

CA60Plus. Installation manual

CA60Plus. Installation manual CA60Plus Installation manual WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire

More information

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option Description of options Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M 4189340401D SW 1.4X.X Description of option Functional description DEIF A/S Parameter list DEIF A/S,

More information

Fire control panel detect 3004 plus and accessories

Fire control panel detect 3004 plus and accessories Fire control panel detect 3004 and accessories The modular fire alarm panel detect 3004 is the basic version of a broad product portfolio of the system detect 3000. Up to 20 fire control panels can be

More information

XC10 Extinguishing control panels

XC10 Extinguishing control panels XC10 Extinguishing control panels Market package 2.1 Advanced control panels for detection and alarming as well as for the activation of the extinguishing process Microprocessor-controlled fire detection

More information

STERLING 10 Control Panel with Remote Keypads ICON and LCD INSTALLATION MANUAL

STERLING 10 Control Panel with Remote Keypads ICON and LCD INSTALLATION MANUAL STERLING 10 Control Panel with Remote Keypads ICON and LCD INSTALLATION MANUAL IMPORTANT: Please note the Sterling 10 LCD keypad is not compatible for use with the Sterling 10 ICON keypad. RINS1413-1 Pyronix

More information

5, SE GÅNGHESTER,

5, SE GÅNGHESTER, KSUB Control and monitoring unit Valid from week of manufacture 48/2005 Description The KSUB is a control and monitoring unit designed to control various types of fire/smoke dampers and fans in a flexible

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

Electro-Detectors Page 2. Revision History. EDA-Z Installation and Operation Manual

Electro-Detectors Page 2. Revision History. EDA-Z Installation and Operation Manual EDA-Z1000 Radio Fire Alarm System Operation and Installation Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2TP UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

Planning Instructions MEW01776 Revision -

Planning Instructions MEW01776 Revision - Planning Instructions MEW01776 Revision - Fire Alarm System EBL512 G3 V2.2.x Author: Jan Pettersson Date of issue: 2015-01-19 Date of rev: This page has deliberately been left blank. Table of contents

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

Chlorine gas leak detector

Chlorine gas leak detector INSTRUCTION MANUAL FOR Chlorine gas leak detector with battery back up series M 4510 C 2007 Controlmatik ABW d.o.o. 1 CONTENT 1.0 General description:... 3 2.0 The Unit... 4 3.0 Controls and Displays...

More information

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel Synova TM Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches unnecessary Automatic

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

Installation Guide for inbiox60 Series Access Control Panel

Installation Guide for inbiox60 Series Access Control Panel Installation Guide for inbiox60 Series Access Control Panel Version: 1.0 Date: April, 2011 About This Manual This manual is a guide to installation and connection of the inbiox60 series access control

More information

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL USER MANUAL Read carefully before use GENERAL INFORMATION This device is a gas control unit with RS485 serial communication, based

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE isocket Smart Relay is a complex Smart House system which is installed in the fuse cabinet (electric cabinet) in the house. We therefore assume that

More information

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-7:2000+A1:2002+A2:2006 EN54-25:2008 0359 Electro Detectors Ltd. Electro

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 OPERATORS MANUAL AFP-300/400 INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02) 9899-4155

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

BURGLAR ALARM PANEL BS-468

BURGLAR ALARM PANEL BS-468 BURGLAR ALARM PANEL BS-468 Contents 1. Description... 3 2. Instructions for the user... 4 2.1Basic operations... 4 Complete system.... 4 Split system.... 4 2.2 Armed system indication... 5 2.3 Advanced

More information

QA16 Addressable System

QA16 Addressable System QA16 Addressable System Operating Manual HORING LIH INDUSTRIAL CO., LTD. www.horinglih.com QA16 System Characteristics Each loop can connect with 250 devices. Easy system programming through PC to panel.

More information