Early Suppression Fast Response Sprinklers and Obstructions

Size: px
Start display at page:

Download "Early Suppression Fast Response Sprinklers and Obstructions"

Transcription

1 Early Suppression Fast Response Sprinklers and Obstructions Presented at SUPDET 2016 March 1, 2016 San Antonio, Texas Presented by: Garner Palenske, P.E. Senior Vice President Aon Fire Protection Engineering Corporation

2 Outline Introduction ESFR Sprinkler Design Concept Actual Delivered Density Testing Full-scale Testing Questions 1

3 Introduction Project Goal: Develop a tool which can be used to provide a reliable analysis of the impact of obstructions on ESFR sprinkler performance. Existing data New fire testing/analysis Phase I of the project included: Literature review GAP analysis Test plan development Phase II of the project included: Actual Delivered Density testing Full-scale fire testing The results of the project will be provided to the NFPA 13 Technical Committee to develop requirements for inclusion in the standard. 2

4 Actual Delivered Density (ADD) Testing Goal: Determine the ESFR K17 sprinkler to be used in the full scale testing. ADD Testing of three different manufacturer s ESFR sprinklers: Tyco Reliable Viking Apparatus UL Third Generation ADD Apparatus Fire Size 2.5 MW fire to simulate the heat release rate of the 30 Ft. Group A plastic commodity in full scale test 3

5 Actual Delivered Density (ADD) Apparatus 4

6 Bar Joist Obstruction ADD Testing 5

7 Bar Joist Obstruction ADD Testing 6

8 Bar Joist Obstruction ADD Testing 7

9 Bar Joist and Bridging Member Diagram 8

10 Actual Delivered Density (ADD) Testing ESFR Sprinkler Comparison Testing - Each of the 3 sprinklers (Tyco, Viking, Reliable) were tested as follows (12 ADD tests total): Test Number Obstruction Horizontal Offset (Tip of Joist to Sprinkler Centerline) Fire Location Clearance from Ceiling to Top of Apparatus 1 Baseline None None 2 22 In. deep bar joist 3 In In. deep bar joist 3 In. Under one sprinkler Under one sprinkler Under one sprinkler 10 Ft. 10 Ft. 10 Ft In. deep bar joist with 1½ In. x 1½ In. bridging member positioned on joist centered under sprinkler 3 In. Under one sprinkler 10 Ft. 9

11 Actual Delivered Density (ADD) Testing Sprinkler A was selected. Selection Criteria: Lowest ADD with obstruction Largest percent difference (Obstructed vs. Non-Obstructed) Most number of collection pans with 0 discharge 10

12 ESFR Full Scale Testing Overview Test Array Standard Group A commodity 30 ft. storage, 40 ft. ceiling Double row racks, 6 in longitudinal and transverse flue space ESFR K17 sprinklers, 52 psi 4 ft. aisles 4 bay target arrays Sprinkler spacing 10 ft. x 10 ft. The ignition point will be under one sprinkler offset in the transverse flue space. 11

13 Full Scale Testing Logic- Sample TEST 1 Joist Depth: 22" OFFSET: 3" PASS Joist Depth: 30" OFFSET: 3" FAIL Joist Depth: 22" OFFSET: 6" PASS Joist Depth: 36" OFFSET: 3" FAIL Joist Depth: 30" OFFSET: 6" PASS Joist Depth: 30" OFFSET: 3" FAIL Joist Depth: 22" OFFSET: 9" PASS STOP PASS STOP FAIL Joist Depth: 36" OFFSET: 6" FAIL Joist Depth: 36" OFFSET: 9" STOP PASS Continue with Joist Depth: 36" OFFSET: 3" Path FAIL Joist Depth: 30" OFFSET: 9" PASS/FAIL Continue with Joist Depth: 36" OFFSET: 3" Path PASS STOP PASS Joist Depth: 36" OFFSET: 3" FAIL Joist Depth: 36" OFFSET: 6" FAIL Joist Depth:30" OFFSET: 9" FAIL Joist Depth: 30" OFFSET: 6" PASS Joist Depth: 36" OFFSET: 3" PASS/FAIL Continue with Joist Depth: 30" OFFSET: 3" Path PASS STOP FAIL Joist Depth: 36" OFFSET: 9" STOP PASS/FAIL Contiue with Joist Depth: 36" OFFSET 3" Path PASS STOP FAIL Joist Depth: 36" OFFSET: 9" STOP FAIL Joist Depth: 36" OFFSET: 6" PASS STOP 12

14 Actual Delivered Density (ADD) Testing Results 0-inch Offset Center 4 Pans Center 16 Pans Bar Joist Depth No OBST OBST % Diff No OBST OBST % Diff 22-inch % % 30-inch % % 36-inch % % 3-inch Offset Center 4 Pans Center 16 Pans Bar Joist Depth No OBST OBST % Diff No OBST OBST % Diff 22-inch % % 30-inch % % 36-inch % % 6-inch Offset Center 4 Pans Center 16 Pans Bar Joist Depth No OBST OBST % Diff No OBST OBST % Diff 22-inch % % 30-inch % % 36-inch % % 13

15 Plan View of Test Arrangement 4 Bay Targets with Single Line Obstruction 14

16 BIM 15

17 Pass/Fail Criteria for Full Scale ESFR Tests The following pass/fail criteria were established: A maximum of eight sprinklers activate The fire is generally contained to the ignition array Ceiling gas temperatures are such that exposed structural steel would not be endangered (peak one minute average temperatures less than 1,000 F) 16

18 ESFR Full Scale Testing Overview Test Number Primary Obstruction 36 inch deep steel joist, tip of lower chord 6 inches from centerline of sprinkler 30 inch deep steel joist, tip of lower chord 3 inches from centerline of sprinkler 36 inch deep steel joist, tip of lower chord 6 inches from centerline of sprinkler 36 inch deep steel joist, tip of lower chord 6 inches from centerline of sprinkler 22 inch deep steel joist, tip of lower chord 6 inches from centerline of sprinkler Secondary Obstruction None None 1-1/2 in. by 1-1/2 in. bridging member; 1-1/2 in. away from sprinkler 1-1/2 in. by 1-1/2 in. bridging member; Centered below sprinkler 1-1/2 in. by 1-1/2 in. bridging member; Centered below sprinkler 17

19 ESFR Full Scale Testing Overview Test 1-36-inch Bar Joist, 6 Inch Horizontal Offset 18

20 ESFR Full Scale Testing Overview Test 1-36-inch Bar Joist, 6 Inch Horizontal Offset Length of Test, minutes 31 First Sprinkler Operation Time, min:sec 0:56 Last Sprinkler Operation Time, min:sec 6:08 Number of Operated Sprinklers 3 Peak Gas Temperature at Ceiling Above Ignition, F 294 Maximum 1 minute Average Gas Temperature at Ceiling Above Ignition, F Peak Steel Temperature at Ceiling Above Ignition, F Maximum 1 minute Average Steel Temperature at Ceiling Above Ignition, F Ignition Time of Target Array, min:sec :36 (North Target) Fire Travel to Extremities of Test Array No 19

21 Test 1 Sprinkler Activation 20

22 Test 1: 36-inch Deep Bar Joist with 6-inch Offset ADD Data Overlay 21

23 Show video test 1 22

24 Test 1 Main Array North Side 23

25 ESFR Full Scale Testing Overview Test 2 30-inch Bar Joist, 3 Inch Horizontal Offset 24

26 ESFR Full Scale Testing Overview Test 2-30-inch Bar Joist, 3 Inch Horizontal Offset. Length of Test, minutes 32 First Sprinkler Operation Time, min:sec 1:42 Last Sprinkler Operation Time, min:sec 7:37 Number of Operated Sprinklers 12 Peak Gas Temperature at Ceiling Above Ignition, F Maximum 1 minute Average Gas Temperature at Ceiling Above Ignition, F Peak Steel Temperature at Ceiling Above Ignition, F Maximum 1 minute Average Steel Temperature at Ceiling Above Ignition, F Ignition Time of Target Array, min:sec Fire Travel to Extremities of Test Array 256 * 157 * 157 * 3:24 (North Target) No 25

27 Test 2: 30-inch Deep Bar Joist with 3-inch Offset ADD Data Overlay 26

28 dno dno dno dno dno dno dno dno Test 2 Sprinkler Activation dno dno dno 4:04 4:08 7:34 dno dno dno dno dno dno 7:37 4:14 dno dno dno dno 4:14 1:42 4:35 4:07 dno dno dno dno dno dno 3:56 4:11 dno dno dno dno dno dno 4:03 dno dno dno 27

29 Show video Test 2 and Gopro 28

30 Test 2 Main Array North Side 29

31 Test 1\2 Damage Comparison Test 1 Main Array North Side Test 2 Main Array North Side 30

32 ESFR Full Scale Testing Overview Test 4-36-inch Bar Joist, 6 Inch Horizontal Offset, Bridging Member Centered Below Sprinkler 31

33 ESFR Full Scale Testing Overview Test 4-36-inch Bar Joist, 6 Inch Horizontal Offset, Bridging Member Centered Below Sprinkler. Length of Test, minutes 32 First Sprinkler Operation Time, min:sec 1:11 Last Sprinkler Operation Time, min:sec 1:11 Number of Operated Sprinklers 1 Peak Gas Temperature at Ceiling Above Ignition, F 250 Maximum 1 minute Average Gas Temperature at Ceiling Above Ignition, F Peak Steel Temperature at Ceiling Above Ignition, F Maximum 1 minute Average Steel Temperature at Ceiling Above Ignition, F Ignition Time of Target Array, min:sec Fire Travel to Extremities of Test Array N/A No 32

34 Test 4 Sprinkler Activation 33

35 Show video Test 4 and Gopro 34

36 Show video Side By Side Test 2 and 3 Gopro 35

37 Test 4 Main Array North Side 36

38 Test 1,2, 4 Damage Comparison Test 1 Main Array North Side Test 2 Main Array North Side Test 4 Main Array North Side 37

39 ESFR Full Scale Testing Overview Test 5-22-inch Bar Joist, 6 Inch Horizontal Offset, Bridging Member Centered Below Sprinkler 38

40 ESFR Full Scale Testing Overview Test 5-22-inch Bar Joist, 6 Inch Horizontal Offset, Bridging Member Centered Below Sprinkler. Length of Test, minutes 32 First Sprinkler Operation Time, min:sec 1:01 Last Sprinkler Operation Time, min:sec 6:42 Number of Operated Sprinklers 23 Peak Gas Temperature at Ceiling Above Ignition, F 1264 Maximum 1 minute Average Gas Temperature at Ceiling Above Ignition, F Peak Steel Temperature at Ceiling Above Ignition, F Maximum 1 minute Average Steel Temperature at Ceiling Above Ignition, F Ignition Time of Target Array, min:sec Fire Travel to Extremities of Test Array :26 (North Target) Yes (North Target) 39

41 Test 5 Sprinkler Activation 40

42 Show video Test 5 and Gopro 41

43 Test 5- North Array 42

44 Test 5 North Target 43

45 Test Number Primary Obstruction 36 inch deep steel joist, tip of lower chord 6 inches from centerline of sprinkler 30 inch deep steel joist, tip of lower chord 3 inches from centerline of sprinkler 36 inch deep steel joist, tip of lower chord 6 inches from centerline of sprinkler 36 inch deep steel joist, tip of lower chord 6 inches from centerline of sprinkler 22 inch deep steel joist, tip of lower chord 6 inches from centerline of sprinkler Secondary Obstruction Length of Test, minutes First Sprinkler Operation Time, (min:sec) Number of Operated Sprinklers Peak Gas Temp. at Ceiling Above Ignition ( F) Fire Travel to Extremities of Test Array None None 1-1/2 in. by 1-1/2 in. BM; 1-1/2 in. away from sprinkler 1-1/2 in. by 1-1/2 in. BM; Centered below sprinkler 1-1/2 in. by 1-1/2 in. BM; Centered below sprinkler :56 1:46 1:19 1:11 1: * No No No No Yes (North Target) North Target Array Ignition Time 3:36 3:24 N/A N/A 2:26 44

46 Temperture ( c) Test Fire Growth Rate Comparison: Temperature Profiles Temperature Profiles Test 1 Test 3 Test 4 Test 5 Test Time (sec) 45

47 Show video Test 1/2 Side by Side 46

48 Vertical Growth Tier Number Sprinkler Operation Ceiling Time from top of 3rd Tier of Storage to Sprinkler Operation, seconds: Test 1 - April 14, 2015 Test 2 - April 16, 2015 Test 3 - April 20, 2015 Test 4 - April 22, 2015 Test 5 - April 24, Time, Seconds 47

49 BIM Sprinkler Model 48

50 Conclusion K-17 ESFR sprinkler obstructed by a bar joist with 6-inch offset produced acceptable results. K-17 ESFR sprinkler obstructed by a bar joist with 3-inch offset controlled the fire with 12 sprinklers operating. Regardless of horizontal offset, a bridging member with vertical separation of 19.5 inches produced acceptable results. A bridging member directly underneath the sprinkler with a vertical separation of 6 inches produced unacceptable results. Data is still needed for various other obstruction situations such as miscellaneous piping, light fixtures or duct work. 49

51 Questions and Answers Aon Fire Protection Engineering Corporation 50

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT PREPARED BY: Garner A. Palenske, P.E., and William N. Fletcher, P.E. Aon Fire Protection Engineering San Diego, CA, USA September 2015 Fire Protection

More information

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers Michael Billstroem Director of International Technical Services The Reliable Automatic Sprinkler Co.,

More information

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Suppression, Detection and Signaling Research and Applications Conference SupDet 2015 March 5, 2015

More information

Obstructions and ESFR Sprinklers Phase 1

Obstructions and ESFR Sprinklers Phase 1 Obstructions and ESFR Sprinklers Phase 1 Final Report Prepared by: Garner A. Palenske, P.E. William N. Fletcher Aon Fire Protection Engineering Corporation San Diego, CA October 2014 Fire Protection Research

More information

Today's Topics & Sustainability Themes

Today's Topics & Sustainability Themes 2012 Chicago Symposium Fire Safety Design and Sustainable Buildings: Challenges and Opportunities Research Efforts in Fire Protection Engineering are Contributing to Sustainability Goals Dan O Connor,

More information

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology Warehouse Protection of Exposed Expanded Group-A Plastics with Sprinkler Technology Zachary L. Magnone, Jeremiah Crocker, Pedriant Peña Tyco Fire Protection Products, Cranston, RI, USA Abstract The focus

More information

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection

More information

Tire Storage. Michigan Fire Inspectors Society Fall Conference

Tire Storage. Michigan Fire Inspectors Society Fall Conference Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,

More information

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers Final Report Prepared by: UL LLC The Fire Protection Research Foundation One Batterymarch Park Quincy,

More information

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Significant Advancements in Water Based Fire Suppression for Storage Occupancies Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products Higher Faster - Further How high can we go? Ceiling

More information

High challenge warehouse case study Summary

High challenge warehouse case study Summary High challenge warehouse case study Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation Objectives Review the results of the high challenge warehouse workshop Recognize

More information

SFPE Austin/San Antonio Chapter Meeting

SFPE Austin/San Antonio Chapter Meeting SFPE Austin/San Antonio Chapter Meeting 14 May 2014 Kerry M. Bell, P.E. Principal Engineer UL LLC 2014 Underwriters Laboratories Inc. Overview of Discussion Updates on the following areas o Dry sprinkler

More information

Storage Sprinkler U.S. Quick Reference Guide

Storage Sprinkler U.S. Quick Reference Guide Storage U.S. Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

Plan Submittal Checklist

Plan Submittal Checklist City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project

More information

The Effect of Large Orifice Sprinklers on High-Challenge Fires

The Effect of Large Orifice Sprinklers on High-Challenge Fires SUPPLEMENT 2 The Effect of Large Orifice Sprinklers on High-Challenge Fires Bill Thomas, P.E. Bill Tomes Editor s Note: Supplement 2 provides background information related to the development and application

More information

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN) Worldwide Contacts www.tyco-fire.com Model ESFR-25 25.2 K-factor Pendent Sprinkler Early Suppression, Fast Response General Description TYCO Model ESFR-25 Pendent Sprinklers are Early Suppression, Fast

More information

Redlands Fire Department Fire Protection Standard

Redlands Fire Department Fire Protection Standard Title: High piled Storage Standard Number: FS-100 Revision: A Date: 10-07-2015 Scope: To provide a standard for High Piled Storage plan review submittals. Description: A standard for High Piled Storage

More information

Box-in-Box Cold Storage Fire Protection Options

Box-in-Box Cold Storage Fire Protection Options Box-in-Box Cold Storage Fire Protection Options FireAustralia TYCO Model ESFR-17 Dry Type Pendent Sprinkler Jeffrey Barkley Tyco Fire Protection Products Objective Common Box-inBox Cold Storage Challenges

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed. Page 1 of 10 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK504 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

The Loss prevention Council. Phase 1 report

The Loss prevention Council. Phase 1 report Phase 1 report Title: Investigation of the suitability of the Actual Delivered Density Apparatus (ADD) for the performance evaluation of standard sprinklers as described in Insurance Services project proposal

More information

Large-scale fire sprinkler tests with the AutoStore compact storage system

Large-scale fire sprinkler tests with the AutoStore compact storage system Large-scale fire sprinkler tests with the AutoStore compact storage system Magnus Arvidson*, Henry Persson and Maria Hjohlman Department of Fire Technology SP Technical Research Institute of Sweden *)

More information

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed. Page of 5. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK506 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor allows

More information

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014 NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

Sprinkler Solutions for Storage Applications

Sprinkler Solutions for Storage Applications Sprinkler Solutions for Storage Applications Logistics and Distribution As storage facilities and their distribution methods have evolved, so have the challenges of protecting them. When installing a fire

More information

Antifreeze Solutions and Automatic Fire Sprinkler Systems. March 12, 2013

Antifreeze Solutions and Automatic Fire Sprinkler Systems. March 12, 2013 Antifreeze Solutions and Automatic Fire Sprinkler Systems March 12, 2013 Session Outline History of Antifreeze in the standards Science of Antifreeze Incidents involving i antifreeze in sprinklers Initial

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry Type Pendent Sprinklers (TY7229)

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA Page 1 of 7 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition of a larger K-Factor

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry

More information

High-Piled Combustible Storage

High-Piled Combustible Storage High-Piled Combustible Storage Presenters: Rob Neale & Scott Adams Tuesday, September 12, 2017 1:30 PM - 4:30 PM High-piled Combustible Storage Based on the 2015 International Fire Code ICC Annual Conference

More information

esfr dry pendent sprinkler Vk502 (k14.0)

esfr dry pendent sprinkler Vk502 (k14.0) Page 1 of 11 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) February 27, 2009 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed. Sprinkler 121a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Upright Sprinkler VK520 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

NOT YOUR AVERAGE K-FACTOR: A NOVEL SPRINKLER COMPARISON TOOL

NOT YOUR AVERAGE K-FACTOR: A NOVEL SPRINKLER COMPARISON TOOL NOT YOUR AVERAGE K-FACTOR: A NOVEL SPRINKLER COMPARISON TOOL Stephen J. Jordan Fire Protection Consultant Fire & Risk Alliance, LLC Rockville, MD, USA sjordan@fireriskalliance.com OVERVIEW Motivation Current

More information

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed. March 7, 2008 Sprinkler 120a Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent

More information

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SUMMARY NFPA FIRE INVESTIGATION REPORT BULK RETAIL STORE FIRE TEMPE, ARIZONA MARCH 19, 1998 SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 600 fpeschulte@aol.com 504/0-7475

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved,

More information

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA Page 1 of 7 1. DESCRIPTION The Viking Attic Upright VK696 is a specific application concealed space sprinkler that provides superior fire protection in combustible and non-combustible sloped attic spaces

More information

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale

More information

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications:

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications: Page 1 of 8 1. DESCRIPTION The Viking Attic Upright VK697 is a specific application attic sprinkler that provides superior fire protection in combustible and non-combustible sloped attic spaces when used

More information

HVLS Fans and Sprinkler Operation Phase 1 Research Program

HVLS Fans and Sprinkler Operation Phase 1 Research Program HVLS Fans and Sprinkler Operation Phase 1 Research Program Final Report Prepared by: Schirmer Engineering Corporation \ The Fire Protection Research Foundation One Batterymarch Park Quincy, MA, USA 02169-7471

More information

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Email: techserv@tycofp.com Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description The Tyco Model

More information

Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix

Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix FINAL REPORT BY: Justin A. Geiman, P.E. Noah L. Ryder, P.E. Fire & Risk Alliance Rockville, MD, USA October 2017 2017 Fire Protection

More information

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK500 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

Impact of a High Volume Low Speed Fan on Sprinkler Performance in Rack Storage Fires

Impact of a High Volume Low Speed Fan on Sprinkler Performance in Rack Storage Fires Research TECHNICAL REPORT Impact of a High Volume Low Speed Fan on Sprinkler Performance in Rack Storage Fires TECHNICAL REPORT Impact of a High Volume Low Speed Fan on Sprinkler Performance in Rack Storage

More information

Fire Prevention Coffee Break Training. May 2017

Fire Prevention Coffee Break Training. May 2017 Fire Prevention Coffee Break Training May 2017 Agenda Introduction Submittals - Phelan Changes to NFPA 13 - Phelan Questions and Answers Open Forum Please welcome our S ummer Intern Charlie Poppe Small

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

MODEL V-BB SPECIFIC APPLICATION TECHNICAL DATA

MODEL V-BB SPECIFIC APPLICATION TECHNICAL DATA Page 1 of 15 1. DESCRIPTION The Model V-BB (Back to Back) is a Specific Application Attic Sprinkler designed to provide superior fire protection in combustible and non-combustible sloped attic spaces when

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 847/866-7479 SPRINKLER PROTECTION BASICS: TYPES OF : SPRAY - standard response - quick response -

More information

The Situation. Modeling Storage Occupancies Under Sloped Ceilings. Concerns (Elevation View) The Concerns 4/29/ NFPA Conference & Expo

The Situation. Modeling Storage Occupancies Under Sloped Ceilings. Concerns (Elevation View) The Concerns 4/29/ NFPA Conference & Expo 2014 NFPA Conference & Expo Modeling Storage Occupancies Under Sloped Ceilings Presented by: Kenneth E. Isman NFSA Victoria B. Valentine NFSA Andre Marshal CSS NFPA 13 defines a sloped ceiling as one where

More information

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations are based upon Live Fire Testing of Prep Stations

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance This certificate is issued for the following: KS103SSF, KS103MSF, AND KS110CTF PANELS AS CLASS 1 INTERIOR WALL AND CEILING PANELS FOR INSTALLATION WITH NO HEIGHT RESTRICTION Prepared

More information

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91% 210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent

More information

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Product Description The Reliable Model JL-14 Early Suppression Fast Response

More information

SPRINKLER TECHNOLOGY:

SPRINKLER TECHNOLOGY: SPRINKLER TECHNOLOGY: CURRENT STATE OF THE ART AND GLIMPSE INTO THE CRYSTAL BALL James Golinveaux Senior Fellow Tyco Fire Protection Products First known patent for automatic suppression system - 1723

More information

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF PREP STATIONS

More information

TECHNICAL DATA NOTICE

TECHNICAL DATA NOTICE Page 1 of 5 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Upright Sprinkler VK520 is a fast response fusible element type sprinkler designed for early fire suppression. With a 14.0 (202

More information

Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design

Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System Part 1: Concept Design 2 Amy L. Porter, P.E. (TX,VA, NM) AND Michael Wojcik, P.E. (AZ, CO, MA,

More information

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Email: techserv@tycofp.com Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description The Tyco Model

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE November 2, 2007 Sprinkler 113a 1. DESCRIPTION The Viking Standard Response High Challenge Upright Large-Drop Sprinkler VK540 is a thermosensitive, glass-bulb sprinkler intended for use in protecting high

More information

The Science Behind Water Mist Protection of Typical Building Hazards

The Science Behind Water Mist Protection of Typical Building Hazards The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested

More information

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES FIRE PROTECTIO FOR O-STORAGE OCCUPACIES WITH HIGH CEILIG CLEARACES SOOIL AM, ATOIO BRAGA, HSIAG-CHEG KUG, and JOA M. A. TROUP FM Global Research, 1151 Boston-Providence Turnpike, orwood, Massachusetts

More information

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G Ref. T4/4.01 IMO E MSC/Circ.914 4 June 1999 GUIDELINES FOR THE APPROVAL

More information

The Worldwide Use of Fire Sprinklers

The Worldwide Use of Fire Sprinklers The Worldwide Use of Fire Sprinklers Russell P. Fleming, P.E. President, National Fire Sprinkler Association (USA) Managing Director, International Fire Sprinkler Association United States Fire Sprinkler

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,

More information

First Revision No. 632-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

First Revision No. 632-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 3 of 398 11/14/2016 10:55 AM First Revision No. 632-NFPA 13-2016 [ Global Input ] See attached

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Sprinkler System

More information

Sprinkler System Installer Level 2

Sprinkler System Installer Level 2 Sprinkler System Installer Level 2 Sprinkler System Installer Unit: A8 Electrical Principles* Level: Two Duration: 17 hours Theory: Practical: 14 hours 3 hours Overview: Upon completion of this unit the

More information

American Fire Sprinkler Association. An Introduction to the IBC and IFC

American Fire Sprinkler Association. An Introduction to the IBC and IFC American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler

More information

Koffel Associates, Inc.

Koffel Associates, Inc. NFPA 25: STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com

More information

STORAGE FIRE PROTECTION SPRINKLERS

STORAGE FIRE PROTECTION SPRINKLERS STORAGE FIRE PROTECTION SPRINKLERS HOW CAN YOU REDUCE YOUR FIRE SPRINKLER INSTALLATION COSTS? Tyco Storage Sprinklers are intended for use in storage applications such as big box retail, extra hazard,

More information

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932) Model MBEC-14 (SIN R6932) Features 1. Designed to be installed on piping that is supported by the primary structure, not the purlins. 2. Provides Extended Coverage Ordinary & Extra Hazard protection to

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-50 Model Early Suppression Fast Response Pendent Sprinklers 16.8 K-factor General Description The Model Pendent Sprinklers (Ref. Figure 1) are Early

More information

2016/2017 Fee Schedule

2016/2017 Fee Schedule Corporate Office 2420 Alft Lane Elgin, IL 60124 P: 847.697.1300 F: 847.697.1310 www.firesafetyfsci.com Specializing in Fire, Building, and Life Safety 2016/2017 Fee Schedule Regional Office 23650 Woodward

More information

9/15/ Cantara Lane Vista, CA (760)

9/15/ Cantara Lane Vista, CA (760) 28 th Annual AHCA/FHEA SEMINAR Sprinkler System Inspection, Testing & Maintenance 1 Speaker Information: Bob Caputo, CFPS, CET Vice President Fire & Life Safety America 657 Cantara Lane Vista, CA 92081

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney

More information

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c 1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire

More information

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Hong-Zeng (Bert) Yu FM Global 16 th International Water Mist Conference September 21-22, 2016 Vienna,

More information

CLT Adhesive Tests in Support of Mass Timber Buildings

CLT Adhesive Tests in Support of Mass Timber Buildings CLT Adhesive Tests in Support of Mass Timber Buildings DES604 Jason Smart, P.E. Manager, Engineering Technology American Wood Council Sam Francis, C.B.O. Senior Director, National Programs American Wood

More information

Firefighter Safety in Battery Energy Storage System Fires

Firefighter Safety in Battery Energy Storage System Fires Firefighter Safety in Battery Energy Storage System Fires Erik Archibald, P.E. Kevin Marr, PhD, P.E. NFPA SUPDET November 30, 2018 Core Team O.A. (DK) Ezekoye The University of Texas at Austin UTFRG Casey

More information

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code Walker Engineering, Inc. 833 Rockingham Road Birmingham Alabama 35235-2625 205-854-0160 205-854-0160 (Fax) Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of

More information

Protection of Combustible Liquids Stored In Composite Intermediate Bulk Containers (IBCs) Research Project. Phase II Final Report.

Protection of Combustible Liquids Stored In Composite Intermediate Bulk Containers (IBCs) Research Project. Phase II Final Report. Protection of Combustible Liquids Stored In Composite Intermediate Bulk Containers (IBCs) Research Project Phase II Final Report Prepared for The Fire Protection Research Foundation Quincy, MA Prepared

More information

Models BB, SD, HIP, and AP Specific Application Sprinklers For Protecting Attics General Description

Models BB, SD, HIP, and AP Specific Application Sprinklers For Protecting Attics General Description Worldwide Contacts www.tyco-fire.com Models BB, SD, HIP, and Specific Application Sprinklers For Protecting Attics General Description The TYCO Models Back to Back Dual Directional (BB), Single Directional

More information

freedom residential flush pendent sprinkler vk476 (K4.9)

freedom residential flush pendent sprinkler vk476 (K4.9) January 6, 2010 Sprinkler 145h 1. DESCRIPTION Viking Freedom Residential Flush Pendent Sprinkler VK476 is a small high-sensitivity fusible element residential sprinkler designed for installation on concealed

More information

Zurn Pex, Inc. Residential Fire Protection Presentation. PEX Plumbing, Radiant Heating and Residential Fire Protection Systems

Zurn Pex, Inc. Residential Fire Protection Presentation. PEX Plumbing, Radiant Heating and Residential Fire Protection Systems Residential Fire Protection Presentation Zurn Pex, Inc PEX Plumbing, Radiant Heating and Residential Fire Protection Systems Matt Lawrence BDM-North Central Region 1 Presentation Outline I. IRC Mandate

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

Statue of Liberty: A Risk Analysis

Statue of Liberty: A Risk Analysis Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress

More information

B. Section Identification for Fire Suppression Piping and Equipment.

B. Section Identification for Fire Suppression Piping and Equipment. SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED

More information

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363) EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT 20-07 TASK 363) Louis Ruzzi PennDOT District 11 Igor Maevski, PhD, PE - Jacobs Agenda AASHTO T20 Technical Committee Roadway Tunnels

More information