Model 4880 Status Output Display Module Manual

Size: px
Start display at page:

Download "Model 4880 Status Output Display Module Manual"

Transcription

1 Model 4880 Status Output Display Module Manual

2 Section 1 Introduction The 4880 provides 16 switched outputs, 4 form C relay contacts, and an X10 module interface. See Table 2-1 for electrical specifications for the outputs and relays. The 4821/4820 supports up to 16 X10 house codes (16 devices per house code). Note: X10 devices are not UL listed. The 4880 is fully supervised by the SBUS through which it connects to the 4821/4820. In conjunction with 4821/4820 programmable I/O statements, the 4880 can be programmed to activate upon virtually any system action. The many types of applications the 4880 is suitable for include: Separating bell outputs in a multi-partitioned system Annunciation of specific types of alarms Allowing X10 devices to interact with 4821/4820 system events Section 2.3 of this manual shows some examples of how installations could be programmed. The I/O Application Programming Manual (P/N ) describes I/O programming details

3 Section 2 Installation Figure 2-1 below shows the 4880 board layout. Figure Board Layout

4 Model 4880 Status Output Display Manual 2.1 Electrical Specifications Table 2-1: 4880 Terminal Description Name Terminal Description Electrical Rating 1 -S Expansion Bus (-) 2 +S Expansion Bus (+) 10.0 to 14.0 VDC, 1 Amp max. 3 A Expansion Bus (data) 0-5 VDC 4 B Expansion Bus (data) 0-5 VDC 5 N.O.1 Relay Contact (Normally Open) #1 2.5 Amps 24 VDC 6 COM1 Relay Contact (Common) #1 7 N.C.1 Relay Contact (Normally Closed) #1 8 N.O.2 Relay Contact (Normally Open) #2 9 COM2 Relay Contact (Common) #2 10 N.C.2 Relay Contact (Normally Closed) #2 11 N.O.3 Relay Contact (Normally Open) #3 12 COM3 Relay Contact (Common) #3 13 N.C.3 Relay Contact (Normally Closed) #3 14 N.O.4 Relay Contact (Normally Open) #4 15 COM4 Relay Contact (Common) #4 16 N.C.4 Relay Contact (Normally Closed) #

5 Installation 2.2 Pin Connectors (P1 and P2) Pin connectors P1 and P2 on the 4880 board are for powering the switched outputs. Each output can provide up to 100 ma of current. Each output can be active simultaneously (for a total of 1600 ma per 4880). Table 2-2: Connector P1 Pin Number Wire Color Description 1 Brown P1-1 Output 1 2 Red P1-2 Output 2 3 Orange P1-3 Output 3 4 Yellow P1-4 Output 4 5 Green P1-5 Output 5 6 Blue P1-6 Output 6 7 Violet P1-7 Output 7 8 Gray P1-8 Output 8 9 White +5 to +32 VDC Input Must be connected to a power source. 10 Black GND Table 2-3: Connector P2 Pin Number Wire Color Description 1 Brown P2-1 Output 9 2 Red P2-2 Output 10 3 Orange P2-3 Output 11 4 Yellow P2-4 Output 12 5 Green P2-5 Output 13 6 Blue P2-6 Output 14 7 Violet P2-7 Output 15 8 Gray P2-8 Output 16 9 White +5 to +32 VDC Input Must be connected to a power source. 10 Black GND

6 Model 4880 Status Output Display Manual 2.3 Sample 4880 Applications This section provides some sample applications showing how I/O programming statements can be used to control the 4880 and other devices (X10 modules) which react to data from the system. Example 1: Separating Sounding Device Outputs Between Partitions Figure 2-2 shows a 4880 used in a two-partition 4821/4820 system. In this application, a burglary alarm condition in Partition 2 outputs on P1-8 which activates a sounding device attached to Output 20. Because the I/O programming statement specifies Partition 2, a burglary alarm condition in Partition 1 will not activate the sounding device. IMPORTANT: The sample script on the next page is a partial script only. It will not operate properly as shown. Do not attempt to create I/O application scripts until you have read the I/O Application Programming Manual (P/N )

7 Installation Figure Relay Used to Activate Sounding Device in Multi-Partitioned 4821/4820 System Example 2: X10 Module Use (Model 4181) Figure 2-4 shows an X10 module used to turn on a lamp during a time schedule that has been specified by an I/O programming statement. (The system supports up to 16 house codes, with 16 devices per house code.) Figure 2-3 shows the hardware setup required for the application

8 Model 4880 Status Output Display Manual Figure 2-3 Sample X10 Hardware Setup IMPORTANT: The sample script below is a partial script only. It will not operate properly as shown. Do not attempt to create I/O application scripts until you have read the I/O Application Programming Manual (P/N ). Figure 2-4 Sample X10 Application

DS7465i. Installation Instructions. Input/Output Module

DS7465i. Installation Instructions. Input/Output Module DS7465i EN Installation Instructions Input/Output Module DS7465i Installation Instructions.0 Introduction EN 2.0 Introduction The DS7465i Input/Output Module operates with compatible multiplex systems.

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

PRX-320 Waterproof Proximity Access Operating Instructions and Installation Manual

PRX-320 Waterproof Proximity Access Operating Instructions and Installation Manual PRX-320 Waterproof Proximity Access Operating Instructions and Installation Manual Contents I. SPECIAL FEATURES 1 II. FRONT PANEL 1 III. INSTALLATION PROCEDURES AND PROXIMITY CARD TYPES 2 IV. SETTING

More information

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual Annunciators, 8 LED D7030X, D7030X-S2, and D7030X-S8 en Installation Manual Annunciators, 8 LED Notices en 3 1 Notices These instructions cover the installation of the D703X, D7030X-S2, and D7030X-S8

More information

Greentrol Automation, Inc.

Greentrol Automation, Inc. Model GA-100 Technical Manual GreenAlert 100 Series Greentrol Automation, Inc. Installation, Operation and Maintenance Technical Manual GA-100 Document Name: TM_GA-100_R1C TM_GA-100_R1C Part Number: 960--0000

More information

PRX-320 Waterproof Proximity Access Operating Instructions and Installation Manual

PRX-320 Waterproof Proximity Access Operating Instructions and Installation Manual PRX-320 Waterproof Proximity Access Operating Instructions and Installation Manual Contents I. SPECIAL FEATURES 1 II. FRONT PANEL 1 III. INSTALLATION PROCEDURES AND PROXIMITY CARD TYPES 2 IV. SETTING

More information

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE The Door Switch 11772 Westline Industrial Drive St. Louis, Mo 63146 (877) 998-5625 www.thedoorswitch.com Patent No. RE42,991 and RE44,039 CONTROL PANEL TRANSFORMER (SUPPLIED WITH CONTROL PANEL) NOTIFICATION

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

Independent Zone Control (I.Z.C.)

Independent Zone Control (I.Z.C.) Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics

More information

Y-Plant Alert. Alarm Annunciator and Sequence of Event Recording System. BU 04M01A02-01E-A

Y-Plant Alert. Alarm Annunciator and Sequence of Event Recording System.  BU 04M01A02-01E-A Y-Plant Alert Alarm Annunciator and Sequence of Event Recording System BU 04M01A02-01E-A www.yokogawa.com/us Y-Plant Alert TM Alarm Annunciator and Sequence of Event Recording System Mission critical facilities

More information

INSTALLATION GUIDE XR2400F ADDRESSABLE FIRE ALARM CONTROL PANEL

INSTALLATION GUIDE XR2400F ADDRESSABLE FIRE ALARM CONTROL PANEL INTALLATION GUIDE XR2400F ADDREABLE FIRE ALARM CONTROL PANEL MODEL XR2400F Addressable Fire Alarm Control Panel INTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and,

More information

385 SERIES REMOTE HANDHELD SIREN ETSA385HR

385 SERIES REMOTE HANDHELD SIREN ETSA385HR ! WARNING Sirens produce loud sounds that may damage hearing: - Roll up windows. - Wear hearing protection. - Use only for emergency response. - Avoid exposure to siren sound outside of vehicle. Please

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

Remote Chexit Module (RCM) System. General Information

Remote Chexit Module (RCM) System. General Information *911032-00* 911032-00 Wiring and Configuration Remote Chexit Module (RCM) System Installation Instructions General Information The Von Duprin RCM is designed for controlled egress applications. It meets

More information

Multi-Application Peripherals and Accessories

Multi-Application Peripherals and Accessories ON UL, ULC Listed FM Approved MultiApplication Peripherals and Accessories Communicating Devices Communications Individually Addressable Devices FEATURES Individually addressable communications over a

More information

ANNUNCIATOR FIXED MODULE

ANNUNCIATOR FIXED MODULE 12 Clintonville Road Northford, CT 06472 Phone: 203-484-7161 Fax: 203-484-7118 THE ANNUNCIATOR FIXED MODULE Installation Manual for the AFM-16ATF and AFM-32AF Annunciator Modules Document # 15970 3/27/95

More information

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147) -961112-0003 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

VISTA-128FBP/ V128FBP-24 Commercial Fire and Partitioned Burglary Alarm Control Panel

VISTA-128FBP/ V128FBP-24 Commercial Fire and Partitioned Burglary Alarm Control Panel VISTA-128FBP/ V128FBP-24 Commercial Fire and Partitioned Burglary Alarm Control Panel Designed to integrate seamlessly with, access control, and ADEMCO s full range of fire and burglary components, the

More information

General Purpose IO Technical Manual

General Purpose IO Technical Manual General Purpose IO Technical Manual Revision 1.06 8 November 2013 Pakton Technologies PAE222 GPIO Manual.docx Page 1 of 21 Revision 1.06 Last updated 8/11/2013 Table of Contents INTRODUCTION...3 Scope

More information

INNtouch PRIVACY MAKE UP ROOM P564

INNtouch PRIVACY MAKE UP ROOM P564 Overview The INNtouch system is a two-part device (plus power supply) that provides guests with a convenient method of communicating their privacy and service preferences. INNtouch contributes to the ability

More information

TruPortal Wireless Locks Quick Reference

TruPortal Wireless Locks Quick Reference TruPortal Wireless Locks Quick Reference en-us Introduction This document describes how to connect the following wireless locks to TruPortal hardware: Schlage AD-400, which connects to TruPortal hardware

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

DE5300 Delayed Egress System. General Information

DE5300 Delayed Egress System. General Information *911031-00* 911031-00 Wiring and Configuration DE5300 Delayed Egress System Installation Instructions General Information The Von Duprin DE5300 is designed for controlled egress applications when used

More information

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide Product Overview The IntelliKnight 5820XL is an intelligent addressable fire alarm control panel designed for flexibility and reliability.

More information

GLOBAL. InstallatIon & operation manual

GLOBAL. InstallatIon & operation manual InstallatIon & operation manual INDEX 1. INTRODUCTION... 5 2. FEATURES AND FUNCTIONS 2.1 Reporting Options... 2.2 Interfaces... 2.3 Programming... 2.4 Indicators and Controls...... 6 6 6 6 6 3. INSTALLATION...

More information

Flair 500 Series Annunciators

Flair 500 Series Annunciators Flair 500 Series s Basics Flair Multi-Zone s (MZAs) are fully functional, flexible, programmable micro controller based alarm control panels. They can be used independently d or in conjunction with other

More information

Ethernet General Purpose

Ethernet General Purpose Ethernet General Purpose Technical Manual Revision 1.03 8 November 2013 Pakton Technologies IO PAE224 Ethernet GPIO Manual.docx Page 1 of 22 Revision 1.03 Last updated 8/11/2013 Table of Contents INTRODUCTION...3

More information

VISTA-32FB. Commercial Fire/Burg/CCTV and Access Control Platform FEATURES: Designed to integrate seamlessly with CCTV, access

VISTA-32FB. Commercial Fire/Burg/CCTV and Access Control Platform FEATURES: Designed to integrate seamlessly with CCTV, access Designed to integrate seamlessly with, access control and ADEMCO s full range of fire and burglary components, the VISTA-32FB provides the ultimate protection of life and property. The UL listed Fire and

More information

TPM Product Type 107-D108-XNT 64-channel digital output module with pluggable terminal

TPM Product Type 107-D108-XNT 64-channel digital output module with pluggable terminal Product Type 107-D108-XNT 64-channel digital output module with pluggable terminal Specifications Size: (L122 x W123 x H104 mm) Series Interface: Half duplex RS-485 with transformer isolation Cable Type:

More information

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

CM-RQE70 PIR REQUEST TO EXIT DETECTOR Door Activation Devices CM-RQE70 PIR REQUEST TO EXIT DETECTOR THIS PACKAGE INCLUDES (1) Wiring Harness (2) #6 x 3/4" Screws (2) 3/16" Wall Plugs (6) Wire Nuts (2) 's BP7175 1. GENERAL DESCRIPTION Camden

More information

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual Revision 1.03 8 November 2013 JVA Technologies Ethernet General Purpose IO Technical Manual www.jva-fence.com.au Table of Contents INTRODUCTION...3 Scope and Purpose...3 Glossary...3 SPECIFICATIONS...4

More information

MODEL ZA-8N EIGHT ZONE ANNUNCIATOR FOR ALL MONITORING APPLICATIONS OUTSTANDING FEATURES

MODEL ZA-8N EIGHT ZONE ANNUNCIATOR FOR ALL MONITORING APPLICATIONS OUTSTANDING FEATURES MODEL ZA-8N EIGHT ZONE ANNUNCIATOR FOR ALL MONITORING APPLICATIONS OUTSTANDING FEATURES INDEPENDENT ZONE ANNUNCIATION WITH ZONE STATUS INDICATION EIGHT RED LEDS INDICATE ZONE STATUS SELECTABLE NORMALLY-OPEN,

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

ESP TECHNOLOGIES LIMITED

ESP TECHNOLOGIES LIMITED Alarm Technology ESPAN-01 Series Annunciator System Combination type User Manual (Rev. 1) ESP TECHNOLOGIES LIMITED www.esptechno.com Content Page Introduction 2 General Description 2 Overview - Annunciator

More information

SENTROL ZX440F. Security System Control. Installation/ Programming

SENTROL ZX440F. Security System Control. Installation/ Programming SENTROL ZX440F Security System Control Installation/ Programming 1 TABLE OF CONTENTS Table of Contents New Features... 6 ZX440F Wiring Diagram... 7 ZX440F Terminal Descriptions... 8 ZXCFM Connection Descriptions...

More information

Rev Pulse Modulating Anti- Sweat Control (PMAC II) Installation and Operation Manual

Rev Pulse Modulating Anti- Sweat Control (PMAC II) Installation and Operation Manual 026-1501 Rev 5 3-20-03 Pulse Modulating Anti- Sweat Control (PMAC II) Installation and Operation Manual 1640 Airport Road, Suite 104 Kennesaw, GA 31044 Phone: (770) 425-2724 Fax: (770) 425-9319 ALL RIGHTS

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

20 Light Remote Annunciator

20 Light Remote Annunciator Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

Multiplex Eight Input Remote Modules

Multiplex Eight Input Remote Modules Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control

More information

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels D9412GV2/D7412GV2 EN Approved Applications Compliance Guide Control Panels D9412GV2/D7412GV2 Approved Applications Compliance Guide Listings and Approvals Listings and Approvals Fire UL Underwriters Laboratories

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: -961112-0002 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING 48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT SPEC SHEET Simple Expansion Solutions Expand your DMP panel options with a wide array of expansion modules. Add supervised Class B burglary zones. Connect non-powered burglary or fire type devices for

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA) R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM

SECURITY ACCESS AND SURVEILLANCE SECTION VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA 250BP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568 SECTION 13850 DETECTION

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

IFP-2000 F r a en e h n y h t y PH P D

IFP-2000 F r a en e h n y h t y PH P D IFP-2000 Farenhyt PHD Power Supplies Module 4 Course Objectives At the end of this course you will be able to: Explain the advantages of Conventional Distributed power supplies Explain the advantages of

More information

ANC BBX-FXMNS or BBX Audio Network Controller Board Installation Instructions TNC-5000 ANC Module Mounting Locations

ANC BBX-FXMNS or BBX Audio Network Controller Board Installation Instructions TNC-5000 ANC Module Mounting Locations Audio Network Controller Board Installation Instructions Module Mounting Locations The Audio Network Controller board can be mounted in two places. One position is over the Audio Network Controller module

More information

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel 12 Clintonville Road Northford, CT. 06472 (203) 484-7161 FAX:(203) 484-7118 The TC-4F Time Control Module For the Sensican 2000 Fire Alarm Control Panel Document # 15972 3/27/95 Revision C P/N 15972:C

More information

Battery charger modules

Battery charger modules Battery charger modules D8132 and D8132LT en Installation manual Battery charger modules Notices en 3 1 Notices These instructions cover the installation of the D8132 Battery Charger and the D8132LT Battery

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSI 3.10 CTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

MBCE-110/230UV Flame Sensor Module

MBCE-110/230UV Flame Sensor Module MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

NT DUAL CHANNEL DISPLAY. User Guide

NT DUAL CHANNEL DISPLAY. User Guide NT DUAL CHANNEL DISPLAY User Guide Table of Contents Introduction... 2 Input Signals... 2 Output Signals... 2 User Programmable Features... 2 Installation... 3 Mechanical Installation... 3 Dimensional

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

INSTALLATION GUIDE XR150/XR550 SERIES CONTROL PANEL

INSTALLATION GUIDE XR150/XR550 SERIES CONTROL PANEL GUIDE XR150/XR550 SERIES CONTROL PANEL MODEL XR150/XR550 SERIES INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed and used properly in strict

More information

Installation Instructions. Fire Command Center/Fire Alarm Annunciators D1256/D1257

Installation Instructions. Fire Command Center/Fire Alarm Annunciators D1256/D1257 Instructions Fire Command Center/Fire Alarm Annunciators D1256/D1257 74-06925-000-H Page 2 2004 Bosch Security Systems Contents 1.0 Introduction...5 1.1 Before You Begin...5 1.2 Type Styles Used Here...5

More information

TELGUARD TG-4 CDMA. Revised August 14, PROPRIETARY INFORMATION For use by TELGUARD customers only. Distribution to others strictly prohibited.

TELGUARD TG-4 CDMA. Revised August 14, PROPRIETARY INFORMATION For use by TELGUARD customers only. Distribution to others strictly prohibited. TELGUARD TG-4 CDMA RESIDENTIAL & SMALL BUSINESS CELLULAR ALARM COMMUNICATOR QUICK INSTALL GUIDE Revised August 14, 2014 PROPRIETARY INFORMATI For use by TELGUARD customers only. Distribution to others

More information

Exit Stopper. STI-6400 Series

Exit Stopper. STI-6400 Series Exit Stopper STI-6400 Series Features Alarm helps prevent unauthorized exits/entries through doors. Easy to install. Select volume, alarm duration and delay settings. May be mounted on top, right, left

More information

380 SERIES REMOTE SIREN ETSA380R

380 SERIES REMOTE SIREN ETSA380R ! WARNING Sirens produce loud sounds that may damage hearing: - Roll up windows. - Wear hearing protection. - Use only for emergency response. - Avoid exposure to siren sound outside of vehicle. Please

More information

MAXSYS Zone Control Panel PC4020. Maxsys Commercial Fire Panel PC4020CF. MAXSYS 16 Output Module PC4216

MAXSYS Zone Control Panel PC4020. Maxsys Commercial Fire Panel PC4020CF. MAXSYS 16 Output Module PC4216 16-128 Zone Control Panel PC4020 16 zones on main control panel supports up to 16 hardwired keypads Expandable up to 128 zones using hardwire, wireless modules and addressable zones COMBUS hardwired expansion

More information

EMS510 Electrical Wiring Guide Volume 2, Rev 1.4

EMS510 Electrical Wiring Guide Volume 2, Rev 1.4 EMS510 Electrical Wiring Guide Volume 2, Rev 1.4 Prepared by Michael L. Kominske Environmental Monitor Service Inc. PO Box 4340 Yalesville, CT 06492 Phone 203.935.0102 Fax 203.634.6663 Email: sales@emsct.com

More information

ALARM... CONTROL... PANELS... AND... KEYPADS...- WIRED...

ALARM... CONTROL... PANELS... AND... KEYPADS...- WIRED... ALARM... CONTROL..... PANELS... AND... KEYPADS....- WIRED........ Securi-Prod 4 Zone Perimeter Alarm 4 x EOL zone alarm panel 2K2 Zone EOL resistance value Multiple Arm/Disarm functions Built in receiver

More information

MBCE-110/230FR Flame Sensor Module

MBCE-110/230FR Flame Sensor Module MBCE-1001 APRIL 13, 2012 MBCE-110/230FR Flame Sensor Module DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the user regarding flame presence in a combustion

More information

SIRA srl. Installation and user manual. Consolle/Digit Remote LCD Annunciator. Remote LCD Annunciator INSTALLATION & USERS MANUAL.

SIRA srl. Installation and user manual. Consolle/Digit Remote LCD Annunciator. Remote LCD Annunciator INSTALLATION & USERS MANUAL. Page 1 / 15 Installation and user manual Page 2 / 15 Sira s.r.l. reserves the right to make modifications to this manual and the product described herein without prior notice. Sira s.r.l. shall not be

More information

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card XP6-C Six Circuit Supervised Control Module and SYNC-1 Accessory Card General NOTIFIER s XP6-C six-circuit supervised control module provides intelligent alarm systems with supervised monitoring of wiring

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

NetworX Series NX-870E Fire Supervision Module Installation and Startup

NetworX Series NX-870E Fire Supervision Module Installation and Startup NetworX Series NX-870E Fire Supervision Module Installation and Startup 2002 GE Interlogix All rights reserved. Printed in the USA. NetworX is a trademark of GE Interlogix. These instructions do not purport

More information

Expansion Modules & Accessories

Expansion Modules & Accessories HONEYWELL SECURITY & COMMUNICATIONS Expansion Modules & Accessories Honeywell s wide range of expansion modules and accessories enable you to configure a system to meet any installation challenge and help

More information

VISTA-20HWSE INSTALLATION INSTRUCTIONS 2-PARTITIONED SECURITY SYSTEM

VISTA-20HWSE INSTALLATION INSTRUCTIONS 2-PARTITIONED SECURITY SYSTEM VISTA-20HWSE 2-PARTITIONED SECURITY SYSTEM INSTALLATION INSTRUCTIONS Principal changes between the VISTA-20HWSE and the former VISTA-20HW are indicated by margin lines. N7526-2V2 8/97 RECOMMENDATIONS FOR

More information

D7053. Installation Instructions Multiplex Input/Output Module

D7053. Installation Instructions Multiplex Input/Output Module D EN Installation Instructions Multiplex Input/Output Module D Installation Instructions Notices Notices These instructions cover the installation of the D Multiplex Input/Output Module in a fire system

More information

AES IntelliTAP. Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device. Version Installation Guide CONTENTS

AES IntelliTAP. Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device. Version Installation Guide CONTENTS AES IntelliTAP Satellite / Remote Dialer Data Receiver Page 1 AES IntelliTAP Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device Version 1.10 Installation Guide CONTENTS How it Works

More information

Application Note. Using XPoint Wireless Devices with Emergency Lighting. 1 of 16

Application Note. Using XPoint Wireless Devices with Emergency Lighting. 1 of 16 Using XPoint Wireless Devices with Emergency Lighting 1 of 16 Table of Contents Introduction...3 Application Summary...3 UL924 Standard Summary...4 ER Option - Normal Power Sensing Leads...4 ER Intended

More information

734N Wiegand Interface Module

734N Wiegand Interface Module Description The Wiegand Interface Module allows you to add IP network access control capability to XR100/XR500, XR150/ XR550, and XR150INT/XR550INT Series panels using proximity or mag-stripe card readers.

More information

Section 1: General Description. Section 2: Features. Section 3: Operation. CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions.

Section 1: General Description. Section 2: Features. Section 3: Operation. CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions. CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions 1 PACKAGE CONTENTS Wiring Harness 6 Wire Nuts #6 x 3/4 Screws s BP7175 3/16 Wall Plugs Section 1: General Description Camden CM-RQE-70 Request-to-Exit

More information

Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA USA

Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA USA INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX BACKUP PUMP CONTROL SYSTEM MODEL NUMBER BPC-3 November 22, 1999 Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA 01460-1431 USA Telephone:

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK Installation Manual AQM-20 12vdc/24vdc Series Power Supplies AQM20 Supervised Power Supply/Charger 12vdc 20Amp/24vdc 10Amp Life Time Warranty Quality Manufactured in the USA AQM20 Features: The AQM20 has

More information

PRODUCT BULLETIN. Rev. A Monitoring Station offering PN Rev. B as a direct replacement. OVERVIEW / DESCRIPTION

PRODUCT BULLETIN. Rev. A Monitoring Station offering PN Rev. B as a direct replacement. OVERVIEW / DESCRIPTION PRODUCT BULLETIN ISSUE/DATE: March 28, 2008 rev A BULLETIN NUMBER: AQ032808 SUBJECT: Monitoring Station PRODUCT LINE: Aquafine UV Equipment TOPIC: REVISION TO THE 41114-1 MONITORING STATION OVERVIEW /

More information

POWERFOIL X3.0 ELECTRICAL SPECS & DIAGRAMS

POWERFOIL X3.0 ELECTRICAL SPECS & DIAGRAMS POWERFOIL X3.0 ELECTRICAL SPECS & DIAGRAMS WARNING: Disconnect power to the installation locations before installing the fan and controller! WARNING: Wait three minutes after disconnecting the VFD before

More information

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Installing the Cisco ONS FAP-4 Fuse Alarm Panel Installing the Cisco ONS 15454-FAP-4 Fuse Alarm Panel Product Number: 15454-FAP-4= This document explains how to install, test, operate, and maintain the Cisco ONS 15454-FAP-4 fuse alarm panel. This document

More information

Installation Instructions

Installation Instructions Model S5832SG Control Panel 8 to 32 Zones Installation Instructions Table of Contents Table of Contents Compliance and Regulatory Information...i Installing and Connecting the Control Panel... 1-5 Sierra

More information

Exit Stopper. STI-6400 Series

Exit Stopper. STI-6400 Series Exit Stopper STI-6400 Series Features Alarm helps prevent unauthorized exits/entries through doors. Easy to install. Select volume, duration and immediate or 15 second delay for arming and trip. May be

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

good things in small packages

good things in small packages FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with

More information

Product Manual. The `Safety Shoe (shown below):

Product Manual. The `Safety Shoe (shown below): SAFETY SHOE PBB AUTO-LEVELER BACKUP & AIRCRAFT DOOR PROTECTION PRODUCT MANUAL The `Safety Shoe (shown below): Protects the Aircraft Door as Auto-Leveler backup in normal passenger loading and unloading

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

EMERGENCY POWERHUBB NODE INSTALLATION AND OPERATION GUIDE

EMERGENCY POWERHUBB NODE INSTALLATION AND OPERATION GUIDE EMERGENCY POWERHUBB NODE INSTALLATION AND OPERATION GUIDE MODEL NUMBERS PHM4PC-xxxx-EM PHS4PC-xxxx-EM PRECAUTIONS Read and understand all instructions before beginning installation NOTICE: Follow National

More information