1 FIRE DEPARTMENT Kitchen Range Hood Fire Suppression System Acceptance Test Project Name: Project Address: Installer Name: Installer Address: Date of Inspection: DOCUMENTATION NO Plans have been reviewed by the Fishers Fire Department. If NO, obtain plans and reschedule acceptance test. The installer has certified that the system has been installed in accordance with the approved plans and the manufacturer s listed installation and maintenance manual. The owner has been provided with a copy of the manufacturers listed installation and maintenance manual or listed owner s manual. HOOD INSTALLATION NO A Type I hood is installed in accordance with manufacturer s installation instructions. All seams, joints and penetrations of the hood enclosure that directs and captures grease-laden vapors and exhaust gases have a liquid tight continuous external weld or are sealed by labeled devices. Insulation materials other than electrical insulation has a flame spread rating of twenty-five (25) or less. The inside edge of the a canopy hood overhangs or extends a horizontal distance of not less than six (6) inches beyond the edge of the cooking surface on all exposed sides. Hood has a vertical distance between the lip of the canopy hood and the cooking surface does not exceed four (4) feet. n-canopy hoods shall be located a maximum of three (3) feet above the cooking surface with an overhang of three (3) inches on exposed ends. The front of the hood is set back a maximum of twelve (12) inches from the cooking surface. Filters are of a baffle-type. Mesh filters are not permitted. Filters are tight fitting and firmly held in place and installed at an angle not less than 45 degrees. Make-up air is provided at a rate to prevent negative pressure in the commercial cooking areas The exhaust duct is free of wiring or wiring systems. FFD-INSP
2 Hoods and ducts shall have a clearance of at least 18 inches from combustible materials, 3 inches to limited combustible materials, and 0 inches to noncombustible material. If these distances cannot be met then one of the exceptions in the Indiana Mechanical Code shall be met. FIRE SUPPRESSION SYSTEM System Manufacturer: System Model: TYPE OF SYSTEM: Wet Chemical Dry Chemical Wet Chemical w/ Water Spray Carbon Dioxide AMOUNT OF AGENT: LBS./GAL Number of Agent Containers Date Agent Mfg. PIPING: All penetrations in the ductwork are sealed by a liquid-tight continuous external weld or a labeled device. NOZZLES: Total Number of zzles Duct Plenum Surface Discharge nozzles are labeled for the purpose and are provided with caps to prevent entrance of grease vapors into piping. DETECTION DEVICES: Fusible links are positioned above each piece of equipment or groups of equipment protected by a single nozzle. Number of 360 degree links: Number of 500 degree links: EQUIPMENT INSTALLATION A Class K wet chemical fire extinguisher is provided no more than thirty (30)feet from the cooking area. Movable cooking equipment is provided with a means to ensure that it is correctly positioned in relation to the appliance discharge nozzle during cooking operations. List the equipment protected by the kitchen fire suppression system: Deep Fryers Grills Range Top (no. of burners) Char-broilers Upright Broiler Other: FFD-INSP
3 (draft equipment layout below) EXPELLANT: Carbon Dioxide Cartridge - wt. Pressurized Cylinder - PSI Nitrogen Cartridge - PSI Other - SHUTDOWN DEVICES System is equipped with an electrical shutdown device. Shunt Trip Breaker Contactor System is equipped with a fuel shutdown device. Mechanical Gas Valve Size Electric Gas Valve Size MANUAL RELEASE: Manual activation device is accessible and located not more than five (5) feet above the floor. Manual activation does not require a force of more than 40 lb or a movement of more than 14 inches to secure operation. Remote pulls are identified as to the hazard they protect. HYDROSTATIC TEST: Date of current hydrostatic test ACCEPTANCE TESTING FFD-INSP
4 Manual pull successfully activated system. Air pressure not less than twenty (20) PSI was used to test the pipe continuity. Test link was used to simulate mechanical system activation via detection device. Did all shutdown devices work during acceptance tests. The exhaust fan continued to run when the system was tripped. Make-up air shut down once fire suppression system activated. N/A The building is equipped with a fire alarm system. The extinguishing system activates the fire alarm system when operated. If, the alarm receipt location was notified before the system was tested. Name of the person at alarm receipt location: Was the alarm activation satisfactory. Smoke test confirms good air balance between the exhaust and supply airflow. System passed acceptance tests. System was left in service and fully operational. Remarks: Fishers FD Representative Date Fire Suppression System Installer Date FFD-INSP
5 Fire Department Dry/Wet Chemical &Powder System Installer Certification Building Permit #: Date: Business Name: Address: Owner/Occupant System Installer System Supplier Contact: Telephone #: Approved plans on site? Certification of System Installation: Complete this section after system is installed but prior to conducting operational acceptance tests. This system installation was inspected by (person) on and was found to comply with the installation requirements of: Please check: NFPA 17 17A 96 Indiana Fire Code, Indiana Building Code, Indiana Mechanical Code Manufacturer s Instruction/Specifications (provide) Other (specify & provide) Print Name: Signed: Organization: Date: Certification of System Operation: All operations features and functions of this system were tested by (person) on and found to be operating properly in accordance with the requirements of: Please check: NFPA 17 17A 96 Indiana Fire Code, Indiana Building Code, Indiana Mechanical Code FFD-INSP
6 Job Specs Manufacturer s Instructions (provide) Other (specify & provide) Print Name: Signed: Organization: Date: FFD-INSP
CORE Protection Fire System Specification
CORE Protection Fire System Specification The CORE restaurant fire suppression system is a pre-engineered, duct and plenum water spray system in conjunction with a wet chemical, cartridge-operated, regulated
More informationLABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY
STAFF USE ONLY Thurston County Resource Stewardship 2000 Lakeridge Dr. S.W. Olympia, WA 98502 (360)786-5490 / (360)754-2939 (Fax) TDD Line (360) 754-2933 Email: permit@co.thurston.wa.us www.co.thurston.wa.us/permitting
More informationCHAPTER 5: EXHAUST SYSTEMS
MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such
More informationKitchen Fire Suppression Systems Post-Event Analysis
Kitchen Fire Suppression Systems Post-Event Analysis Adam Farnham, PE, CSP, IAAI-CFI Fire Protection/Mechanical Engineer Snohomish, Washington October 22, 2014 Presentation Outline 1. Overview of System
More informationNFPA 96, 2017 REVIEW SUMMARY
NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile
More informationCOMMERCIAL KITCHEN FIRE SAFETY
COMMERCIAL KITCHEN FIRE SAFETY COMMERCIAL KITCHEN FIRE SAFETY Commercial grade kitchens are a common feature found in senior living communities. Operation of a commercial grade kitchen, many safety considerations
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationLombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS
Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS (630) 620-5750 Fax: (630) 629-2374 www.villageoflombard.org COMMERCIAL HOOD & DUCT SYSTEM PLAN REVIEW REQUIREMENTS International
More informationCORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS
CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS FIRE EXTINGUISHER REQUIREMENTS 1. All commercial cooking operations require at least one 2A10BC rated (5 or 6 pound size) fire extinguisher.
More informationSECTION COMMERCIAL-KITCHEN HOODS
SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber
More informationContents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS
Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS 1 Ventilation and Exhaust 2 Seminar Introduction Seminar addresses key concepts
More informationREQUIREMENTS FOR HOOD PLANS
DEPARTMENT OF PUBLIC HEALTH Division of Environmental Health REQUIREMENTS FOR HOOD PLANS Submit one (1) set of plans drawn to scale of at least ¼-inch per foot. Plans shall conform to applicable California
More information2015 ICC Commercial Cooking Systems
2015 ICC Commercial Cooking Systems Based on the: 2015 International Building Code (IBC ) 2015 International Mechanical Code (IMC ) 2015 International Fire Code (IFC ) 2015 International Fuel Gas Code
More informationDear Concessionaire,
Dear Concessionaire, In order to provide a comprehensive review & inspection of the Vendor application please review the following as guidance to a complete application and preparedness for inspection.
More informationVENTLESS EXHAUST HOOD OPERATORS MANUAL AND PARTS LIST REV. MAY 2016
VENTLESS EXHAUST HOOD OPERATORS MANUAL AND PARTS LIST REV. MAY 2016 HOODMART 172 REASER COURT ELYRIA, OH 44035 PHONE: (800)-715-1014 FAX: (800)-716-1214 1 THIS PAGE LEFT BLANK INTERNTIONALLY 2 LIMITED
More informationMinimum Information Required to Process your Special Occasion Application. Parking area Access to site
FIRE CODE PERMIT SPECIAL OCCASION APPLICATION YAKIMA COUNTY FIRE MARSHAL S OFFICE International Fire Code 128 N. 2nd Street, 4th floor, Yakima, WA 98901 - (509) 574-2300 FORM: BFS45A 6/5/18 Minimum Information
More informationEVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS
ICC-ES Report PMG-1004 Reissued 08/2017 This report is subject to renewal 08/2018 EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING (HVAC)
More informationKitchen Ventilation Hood Permit Application
TOWN OF BRIGHTON Office of the Fire Marshal 2300 Elmwood Avenue Rochester, New York 14618 (585) 784-5220 Office (585) 784-5207 Fax Kitchen Ventilation Hood Permit Application Plan Submittals and Installation
More informationIMC Significant Changes Summary Tier I
2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just
More information2012 ICC Commercial Kitchen Hoods
Welcome 2012 ICC Commercial Cooking Hoods Based on the: 2012 International Mechanical Code (IMC ) 2012 International Fire Code (IFC ) 2012 International Fuel Gas Code, (IFGC ) 2012 International Building
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationTypes of Detection. Fusible Link Detection - Most Common
Types of Detection Fusible Link Detection - Most Common Types of Detection Electric Detection Types of Detection Pneumatic Detection-Tubing Pneumatic Tubing 3 Year Service life Survey Hazard 1) List all
More informationINSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods
INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods Ultra Series Models: UL2824 UL2830 UL2836 CONTENTS: Part 1 - Planning The Installation Part 2 - Electrical Connection Part 3
More information*** Inspection *** Please identify yourself as a Cintas representative when arriving onsite.
Tech Clock-In/Out IVR: 1-877-349-2906 Job #: Tech ID #: 2902 FP Service Instructions Job #: *** Inspection *** You must clock in and out of this job through Cintas's IVR phone system! Call 1-877-349-2906
More informationShips and marine technology Fireextinguishing. of galley cooking equipment
INTERNATIONAL STANDARD ISO 15371 Third edition 2015-11-15 Ships and marine technology Fireextinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d extinction
More informationREAD AND SAVE THESE INSTRUCTIONS WARNING! TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS OBSERVE THE FOLLOWING:
DANVER INSTALLATION INSTRUCTIONS & USE & CARE GUIDE DANVER DOHC Series Range Hood 1300 CFM DOHC Séries Models: 36 48 60 CONTENTS: Part 1 - Planning The Installation Part 2 - Electrical Connection Part
More informationSECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM
PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary
More informationXRRS Specification Fire Ready Hood
XRRS Specification Fire Ready Hood ************************************************************************************************************************ Note to User: This document is subject to copyright
More informationTo expedite the plan review and inspection processes, please refer to the information below.
Guidelines: The goal of the Denison Fire Department is to assist its customers in understanding our submittal, plan review and inspection process and policies, as they pertain to new construction. Familiarity
More informationSecond Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM
1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,
More informationJADE RANGE LOG BROILER MODELS: JLB SERIES
Jade Range LLC, A Middleby Company 2650 Orbiter Ave. Brea, CA 92821 Telephone (714) 961-2400 FAX (714) 961-2550 JADE RANGE LOG BROILER MODELS: JLB SERIES INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
More informationISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment
INTERNATIONAL STANDARD ISO 15371 Second edition 2009-03-15 Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d'extinction
More informationR-102 RESTAURANT FIRE SUPPRESSION SYSTEM
R-102 RESTAURANT FIRE SUPPRESSION SYSTEM DESIGN, INSTALLATION, Recharge, and Maintenance Manual One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com Copyright 2014 Tyco
More informationMSYS 4490 AC Systems
MSYS 4490 AC Systems Winter 2015 KITCHEN VENTILATION SYSTEMS By Satwinder Singh 12/02/2015 1 12/02/2015 2 By Satwinder Singh 1 12/02/2015 3 12/02/2015 4 By Satwinder Singh 2 Type I: Types of Hoods used
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationChecklist For Building Inspection & Fire Safety
INSPECTION CHECKLIST Date of Inspection: Location/Address: Weather Condition: Inspector: AFTER COMPLETING YOUR INSPECTION, TRANSFER YOUR CONCERNS/OBSERVATIONS TO THIS AREA Facility: Name: Staff Contact:
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationKITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM
PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.
More informationCOMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET
COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET Colorado Springs Fire Department Division of the Fire Marshal October 2013 Table of Contents PURPOSE... 3 SCOPE... 3 DEFINITIONS... 3 GUIDELINES...
More information24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY
24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY 06/13/2011 Rev. 6 Pollution Control Unit PCU CORE CONNECTIONS, 3/8" NPT CONNECTION, ONE PER MODULE LINE FROM PACKAGE MUST BE BRANCHED TO EACH MODULE..
More informationSPECIAL EVENTS INSTRUCTIONS AND REQUIREMENTS Must apply at least 2 weeks PRIOR to Event Date
SPECIAL EVENTS INSTRUCTIONS AND REQUIREMENTS Must apply at least 2 weeks PRIOR to Event Date 1. Any organization planning an event in the City of Pembroke Pines shall contact Zoning at (954) 392-2110 prior
More informationThe Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE
Worldwide Safety Services Fire Extinguisher Training D 1 Objectives Understand the combustion process and different fire classes. Understand d fire extinguisher i types, operating procedures, capabilities,
More informationNotable Changes in the Mechanical Codes
Notable Changes in the Mechanical Codes July 2004 The following are some of the changes between the 1997 Uniform Mechanical Code and the 2003 International Mechanical Code(M) and the 2003 International
More informationOwner s Guide Installation & Operation
Owner s Guide Installation & Operation Char Broiler HCH Series Hestan Commercial Corporation 3375 E. La Palma Ave Anaheim, CA 92806 (888) 905-7463 RETAIN THIS MANUAL FOR FUTURE REFERENCE P/N 002134 REV
More information24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY
24V PCU CORE FIRE PROTECTION INSTALLATION SUMMARY 11/12/2012 Rev. 10 Pollution Control Unit PCU CORE CONNECTIONS, 3/8" NPT CONNECTION, ONE PER MODULE LINE FROM PACKAGE MUST BE BRANCHED AND ADAPTED TO EACH
More informationInstallation. Professional Built-in Hoods
Installation Professional Built-in Hoods Table of Contents Warnings & Important Information _ 3 VWH 0 H. Wall Hoods w/standard Ventilator 30, & 36 Dimensions & Specifications _ 5 Clearance Dimensions _
More informationComparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems
Comparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems Matrix 2008 First Edition Comparative Matrix 2008 Phil Ackland First Edition 1 This
More informationUse, Care, and Installation Guide
Use, Care, and Installation Guide Model PSU-E30AS XP022421(1) 182766 Safety Notice... 2-3 List of Materials... 4 D ucting Calculation Sheet... 5 Mounting Height & Clearance... 6 Ducting Options... 7 Hood
More informationFIRE DEPARTMENT PERMIT GUIDELINES
FIRE DEPARTMENT PERMIT GUIDELINES SPECIAL EVENT PUBLIC ASSEMBLY (EACH EVENT) The Special Event Assembly Permit is applicable to any public event, exhibit space, booth, festival or any other similar event
More informationB.C.S. Shop Heaters 26, 30 & 36 (36 shown)
BIOMASS COMBUSTION SYSTEMS, INC. 67 MILLBROOK ST., SUITE 502 WORCESTER, MA 01606 508-798-5970 - FAX 508-798-5971 B.C.S. Shop Heaters 26, 30 & 36 (36 shown) INSTALLATION MANUAL HAND FIRED SYSTEMS 8-09 Biomass
More informationChapter One Commercial Kitchen Fires
Table of Contents Table of Contents Chapter One Commercial Kitchen Fires COMMERCIAL KITCHEN FIRES... 2 The Commercial Kitchen Fire Problem... 2 Unreported Fires... 2 Cooking By-Products... 3 Grease Accumulation
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;
More informationIVI WARNINGS: Must be followed carefully to avoid personal injury. [VL
INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Bull Outdoor Products BBQ Hood 1250 CFM Item# 66009 CONTENTS: Part 1 - Planning The Installation Part 2 - Electrical Connection Part 3 - Direction of Vent and
More informationThe D1000. Typical Specifications: activate the mechanical fire suppression system. (pressurized potassium citrate / potassium acetate mix)
Fan 10 Ductwork Cabinet 7 to 10 adaptor set Range Hood Fan D1000-I_-DF Air Flow Plenum Ready Supply Cable to Fan 120VAC Input Supply Line 120VAC Output Line, Power Disconnect D1000-I_-DF-NFPA101 12 Ductwork
More informationCALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300
CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION
More informationFort Bragg Fire and Emergency Services Division Fire Safety Survey For use of this form, see FB Reg 420-1, the proponent agency for this form is DES.
Fort Bragg Fire and Emergency Services Division Fire Safety Survey For use of this form, see FB Reg 420-1, the proponent agency for this form is DES. Date of Survey: Building Number: UNIT / Organization:
More informationWausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records
VIOLATION Code AISLES/EXITS NFPA 1-14.13.2.1 NFPA 1-14.4.1 NFPA 1-14.4.2.1 NFPA 101-7.10.9 Violation Codes Description Aisles and Exits Emergency Lighting Working Required emergency lighting systems shall
More informationVariable Ventilation for the Kitchen:
Variable Ventilation for the Kitchen: How It Works and Why It s Important for Your Restaurant YOUR ENERGY COSTS $ JAN FEB MAR MAP LEGEND lighting & signage control hvac & kitchen ventilation control energy
More informationBasic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives
Design Considerations for Commercial Kitchen Ventilation By John A. Clark, P.E., Member ASHRAE Commercial kitchen ventilation (CKV) design must consider everything needed to be coordinated to form a system
More informationSummary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016
Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,
More informationLow Wall Back Shelf Exhaust Canopy
ITEM NO. 710 Powerline Road Suite H Deerfield Beach, FL 33442 (954) 570-9860 (800) 322-8730 FAX (954) 570-9865 Low Wall Back Shelf Exhaust Canopy Model LW APPLICATION Wall mounted canopy style ventilator
More informationDO NOT REMOVE THE MONITORS FOR SERVICE! COVER THEM WITH PLASTIC AND TAKE A PICTURE OF THE MONITORS COVERED.
Tech Clock-In/Out IVR: 919-261-5182 Job #: Tech ID #: 2066 KEC Service Instructions Service Date/Time: 11/01/2016 11:00pm Job #: Technician: Patrick McCarthy* Location: Chili's #0979 Leominster Phone:
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationKITCHEN A104 CAFETERIA A103 RECEIVING WALK-IN FREEZER WALK-IN COOLER ENTRY EXIT EXIT COOKING PREP ENTRY WAREWASHING DRY STORAGE TRAY RETURN
4/19/2014 6:48:50 PM FROM FILE: S:\2013\-4j_Howard_Elementary_School\Drawings\Revit\_HES_ARH_Bldg_14.rvt REEIVING DRY STORAGE WALK-IN OOLER PREP WALK-IN FREEZER KITHEN A104 OOKING WAREWAING AFETERIA A103
More informationCOPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE
COPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE DESIGNER SERIES MODELS Model Width CFM Type of Motor & Blower VSL430 BF 28-3/8" * Remote VSL436 BF 34-3/8" * Remote VSL442 BF 40-3/8" * Remote
More informationFirst Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM
of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide
More informationIs the address of your property clearly visible and marked in large numbers that can be easily seen from the street?
PRE-INSPECTION CHECKLIST THE FOLLOWING INFORMATION IS PROVIDED TO YOU TO ASSIST YOUR FACILITY IN BECOMING COMPLIANT WITH THE NEW YORK STATE FIRE CODE, LOCAL LAWS, AND ORDINANCES GOVERNING THE TOWN OF BABYLON.
More informationMobile Vendors Bulletin
Mobile Vendors Bulletin NUMBER: 13-01 Amended Jan 18, 2016 PURPOSE City of Penticton Regulations for Mobile Vendors This guideline is intended to provide an overview of the City of Penticton requirements
More informationFGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP)
FGR Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM FGR-8 through FGR-22 (25 HP to 1000 HP) Gas, Light Oil or Combination MANUFACTURED BY JOHN ZINK COMPANY, LLC
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-21 21 03.00 10 February 2009) ---------------------------------- Preparing Activity: USACE Superseding UFGS-21 21 03.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationUNDER CABINET RANGE HOOD
UNDER CABINET RANGE HOOD MANUAL IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS FOR DOMESTIC COOKING ONLY 1. Read all instructions before using the appliance 2. Install or locate this appliance
More informationBusiness License Pre-inspection Checklist
Business License Pre-inspection Checklist August, 2016 Alberta Fire Code business license pre-inspection and annual checklist This checklist provides business owners with Alberta Fire Code requirements
More informationSANDUSKY FIRE DEPARTMENT Fire Prevention Bureau. Dear Prospective Food Vendor:
SANDUSKY FIRE DEPARTMENT Fire Prevention Bureau 600 West Market Street Sandusky, OH 44870 Phone: 419.627.5823 FAX: 419.627.5820 www.ci.sandusky.oh.us Dear Prospective Food Vendor: The purpose of this information
More informationTHE IDEAL SOLUTION FOR KITCHENS
THE IDEAL SOLUTION FOR KITCHENS Restaurants, hotels and all types of buildings housing commercial kitchens increasingly require specific fire protection that deliver maximum protection against fire. The
More informationFire Suppression Installation (R-102) for AVI Hoods & XLT Ovens
XD 9011E ABGKSWBGHAE 10/16/2017 Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens CAUTION This appliance is for professional use by qualified personnel. This appliance must be installed by
More informationFOOD PREPARATION WITHIN EXHIBITS
FOOD PREPARATION WITHIN EXHIBITS Whenever food is prepared within an exhibit, an Application for Food Preparation within Exhibits form should be completed and forwarded to your Convention Services Manager
More informationEcolibrium. Kit and a bit UTS triumphs at the AIRAH Awards. ANNUAL AIRAH AWARDS THE OFFICIAL JOURNAL OF AIRAH FEBRUARY 2016 VOLUME 15.
THE OFFICIAL JOURNAL OF AIRAH FEBRUARY 2016 VOLUME 15.1 Ecolibrium THE ECOLIBRIUM ANNUAL AIRAH AWARDS SPECIAL Kit and a bit UTS triumphs at the AIRAH Awards. PRINT POST APPROVAL NUMBER PP352532/00001 PEER-REVIEWED
More informationImperial Cal Products, Inc.
Imperial Cal Products, Inc. Read Before Starting Installation! Inspect your range hood prior to installing! Any cosmetic defects must be reported to us prior to installation. Once this hood is installed,
More informationSheetz Inc. Fire Protection Service Guidelines
Sheetz Inc. Fire Protection Service Guidelines Overview The following are guidelines for Sheetz Fire Protection Services for the 2016/2018 contract year. Each key area is listed below with the appropriate
More informationUNDER CABINET RANGE HOOD. This manual is made with 100 % recycled paper.
UNDER CABINET RANGE HOOD This manual is made with 100 % recycled paper. IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS FOR DOMESTIC COOKING ONLY 1. Read all instructions before using the
More informationGlobal Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationInstallation Instructions Remote Blowers
Installation Instructions Remote Blowers Models: REMP3, REMP16 Suitable for use in a household cooking area. Suitable for use with solid state controls. To complete this blower, a Dacor hood assembly or
More informationINSTALLATION INSTRUCTIONS & USE & CARE GUIDE Trade-Wind Professional Series Liners
INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Trade-Wind Professional Series Liners Professional Series Models Model Width CFM Type of Motor & Blower PSL736 34-3/8 * Remote PSL742 40-3/8 * Remote PSL748
More information2012 International Mechanical Code Significant Changes. About the Significant Changes
Significant Changes to the International Mechanical Code and the International Fuel Gas Code With Louisiana Amendments Copyright Materials This presentation is protected by US and International Copyright
More informationVentless Operation Supplement GBF-D-VH
Operations & Service Manual GBF-5D-VH GBF-50D-VH Ventless Operation Supplement GBF-D-VH Giles Enterprises, Inc. An ISO900 Registered Company Committed to Quality 750 Gunter Park Drive West Montgomery,
More informationIntegrated Ventilation System
Integrated Ventilation System For use with models: IVS1, IVSR1, IVS2, IVSR2 Installation Instructions Part No. 65278 Rev. K Table of Contents Important Safety Instructions... 1 Important Information About
More informationJacqueline Wilmot Fire Protection Engineer NFPA. Road Map for Mobile Food Truck Regulation
Jacqueline Wilmot Fire Protection Engineer NFPA Road Map for Mobile Food Truck Regulation Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Mobile Food Trucks Hazards Multiple
More information2012 INTERNATIONAL FUEL GAS CODE VENTS
2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with
More informationNote: The event coordinator is responsible for compliance of all regulations.
Food Booth and Vendor Regulations FIRENETS March 2000 Revised March 2016 Introduction Vendors invited to participate in events sponsored by various organizations on the UC Davis campus are expected to
More informationIntroduction to the Exhaust Fan Interceptor Commercial Exhaust Fans from a Service Perspective
2012 Introduction to the Exhaust Fan Interceptor Commercial Exhaust Fans from a Service Perspective 2012 - Superior Restaurant Services 3/21/2012 2012 - Superior Restaurant Services 2 Contents Introduction...
More informationOwner s Guide Installation & Operation
Owner s Guide Installation & Operation Hot Top HHT Series Hestan Commercial Corporation 3375 E. La Palma Ave Anaheim, CA 92806 (888) 905-7463 RETAIN THIS MANUAL FOR FUTURE REFERENCE P/N 002130 REV 1 IMPORTANT
More informationOwner s Guide Installation & Operation
Owner s Guide Installation & Operation Fryer HFR Series Hestan Commercial Corporation 3375 E. La Palma Ave Anaheim, CA 92806 (888) 905-7463 RETAIN THIS MANUAL FOR FUTURE REFERENCE P/N 002137 REV 1 IMPORTANT
More informationSystem Test Report CLEAN AGENT
City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information
More informationIntegrated Hood Liner
Integrated Hood Liner Covers models IHL30, IHL36, IHL42, IHL48 and IHL54 Installation Instructions Part No. 65268 Rev. F 2007 Dacor, all rights reserved. Table of Contents Before You Begin... 1 Important
More informationSafetyNet FIRE MARSHAL S OFFICE. Food Booth and Vendor Regulations
UC Davis Health Fire Marshal s Office 4800 2nd Ave, #1200 Sacramento, CA 95817 (916) 734-3036 hs-fireprevention@ucdavis.edu FIRE MARSHAL S OFFICE Food Booth and Vendor Regulations Introduction Vendors
More informationCommercial Kitchen Exhaust Requirements Kitchen Exhaust for Food Service Operations
Commercial Kitchen Exhaust Requirements Kitchen Exhaust for Food Service Operations District of Lake Country 10150 Bottom Wood Lake Road Lake Country, BC V4V 2M1 t: 250-766-6675 f: 250-766-0200 Inspection
More informationCHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION
CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION SECTIONS 23.20.100 Local Amendments To The International Mechanical Code, 2000 Edition 23.20.202 Definitions 23.20.301.14
More informationuser manual Model #: BLZ-HOOD
user manual Model #: BLZ-HOOD ii Table of Contents Table of Contents 1 Saftey Notice III-V 2 Diagrams 1-3 Hood Dimensions............ 1 Control Panel.............. 2 Clearance............... 3 3 Installation
More informationRevolving Oven Gas Wood Model 140
JOB MODEL 140 GAS WOOD ITEM # High temperature pizza oven. Cooking range is from 650f to 900f. CLEARANCES: Install the oven with a minimum 2 clearance on sides and back from any combustible material. Noncombustible
More information