CW9000 Wireless Fire System. Installation Manual

Size: px
Start display at page:

Download "CW9000 Wireless Fire System. Installation Manual"

Transcription

1 CW9000 Wireless Fire System Installation Manual

2 CONTENTS 1 PROJECT PROCESS PLANNING SITE SURVEY EQUIPMENT INSTALLATION COMMISSIONING / CONFIGURATION SYSTEM INSTALLATION SUPPLIED WITH THE CONTROL PANEL STANDARDS FREQUENCY ALLOCATION SITE PLAN SYSTEM COMPATABILITY FIELD EQUIPMENT CONTROL PANEL INSTALLATION GENERAL PANEL MOUNTING AERIALS CABLES MAINS SUPPLY OTHER EXTERNAL CIRCUITS Alarm Sounders Auxiliary Relay Fault Output PANEL CONNECTION NETWORKING COMMISSIONING INTRODUCTION SUGGESTED ORDER OF WORK POWERING THE PANEL SCREEN COVER FAULTS ACCESS TO PANEL MENUS ACCESS LEVEL 1(USER) ACCESS LEVEL 2(SUPERVISOR) ACCESS LEVEL 3 (ENGINEER) CHANGING PASS CODES... 23

3 CONTENTS 4.8 SETTING TIME AND DATE SETTING NUMBER OF PANELS (NETWORKING) SETTING PANEL NUMBER (NETWORKING) SETTING SYSTEM ID SETTING SYSTEM FREQUENCY FREQUENCY CHANNEL SELECTION GUIDE HARD RESET PANEL SYNCHRONISATION WIRED SYNCHRONISATION WIRELESS SYNCHRONISATION PRE-COMMISSIONING AUTOMATIC COMMISSIONING COMMISSIONING DEVICES TO PANEL COMMISSIONING DEVICES VIA A BOOSTER MANUAL COMMISSIONING COMMISSIONING DEVICES TO PANEL COMMISSIONING DEVICES VIA A BOOSTER SOFT ADDRESSING COMMISSIONING COMMISSIONING DEVICES TO PANEL COMMISSIONING DEVICES VIA A BOOSTER SYSTEM RESCAN ENDING COMMISSIONING ADDING DEVICE TEXT ADDING ZONE TEXT ADDING PANEL TEXT MAINTENANCE SYSTEM MAINTENANCE SYSTEM SHUT-DOWN WIRELESS RECEPTION CHANGING BATTERIES DISABLING AN ADDRESS DISABLING A ZONE PRODUCT DATA SHEETS... 68

4 PROJECT PROCESS 1 PROJECT PROCESS 1.1 PLANNING The system requirements are determined by evacuation procedures, configuration of the building and the use to which it is to be put need to be determined accurately by consulting all interested parties. The involvement will vary according to the size and complexity of the installation, but may include: User / purchaser Enforcing authority Insurer System designer Equipment supplier Installer In small simple systems the consultation may be minimal, but all decisions should be recorded and available for reference. 1.2 SITE SURVEY Site Surveys are critical to the successful installation of wireless fire alarm systems by evaluating a site for the following: 1) Interference on the 15 system channels, the Survey Tool channel, and the 2 Commissioning channels 2) If any of the 15 system channels are already in use by another system 3) The signal path quality between the Panel/Booster location and each remote device location on all 15 system channels. 4) The optimum system frequency/frequencies for the installation. To ensure that a site survey portrays an accurate picture of the site it is critical that every remote device location is surveyed and in the location the device will be installed. It is also critical that when a site requires a Booster that a survey is conducted between the Booster location and every remote device location associated with the Booster. A site plan should be generated that clearly shows the location of each device (including the Panel) and is marked with the address the location will be surveyed as (making it simple to relate survey results to a physical device). Devices should be clearly marked on the site plan to indicate whether they are directly commissioned to the panel or via which Booster to simplify commissioning. 1.3 EQUIPMENT INSTALLATION The control panel and signal boosters should be fixed in accordance with the site plan and wired first. The bases, mounting plates, and back boxes of the remote devices should be fixed in accordance with the site plan. The remote devices should then be commissioned to the fire panel/boosters and then installed. 1.4 COMMISSIONING / CONFIGURATION Commissioning and system configuration should follow the guidance in the Installation Manual and using Wireless Commissioning Tools and Site Installer software as necessary 4

5 SYSTEM INSTALLATION 2 SYSTEM INSTALLATION 2.1 SUPPLIED WITH THE CONTROL PANEL 2 x Batteries + Battery Leads 1 x Installation Manual 1 x User Guide 2.2 STANDARDS Installation must only be undertaken by appropriately skilled and trained personnel. The wireless system components are designed to comply with all relevant European standards. The system should be designed to the guidance given by any national standards or specific requirements pertaining conditions on the site. Although the cabling required in a wireless system is minimal it must comply with local wiring codes. In some installations it may be necessary to deviate from the code, any such deviation must be listed on the Installation certificate in the system documentation. 2.3 FREQUENCY ALLOCATION Before any wireless equipment is installed on a site a full site survey must be conducted (site scan and every device position surveyed), the results saved, analysed and a report generated that clearly highlights the frequency channels required for all Panels and Boosters on site. Refer to the Survey Tool documentation for more details. 2.4 SITE PLAN A site plan should be provided that clearly shows where the devices should be installed in accordance with the site survey results. The site plan should also clearly show which devices are directly associated with each fire panel, and which devices are associated with each Booster. The site plan should also show the frequency and system ID of each Panel and Booster on site. This will greatly simplify commissioning the site. A clear and concise site plan will prevent unnecessary rework as all devices will be commissioned correctly. 2.5 SYSTEM COMPATABILITY The wireless field devices are only compatible with the CW9000 system. They are not compatible with any other wireless system and likewise other wireless field devices are not compatible with the CW9000 system. 5

6 SYSTEM INSTALLATION 2.6 FIELD EQUIPMENT Field equipment must only be fitted according to the positions determined by the site survey and highlighted on the site plan. Failure to follow the survey data could lead to unreliable operation and expensive rectification work. The only wireless devices that are compatible with this system are those from the CW9000 range. The following wireless devices are battery powered and require no cabling: Figure 1 The following wireless devices are battery powered and require input/output cabling: Figure 2 6

7 SYSTEM INSTALLATION The following wireless devices are mains powered with battery backup: Wireless Booster Figure 3 Installation of the se devices should follow the recommendations supplied with each device. There are three methods for commissioning the devices to the control panel. Depending on which method is used will determine when batteries are fitted to the equipment and therefore this could influence the installation process used on site. When installing batteries use only those supplied with the equipment or the alternatives listed on the labels fixed to the equipment. Failure to follow the recommendations may lead to increased maintenance to replace batteries and possibly unreliable operation. Wireless Boosters will require connection to a secure mains supply similar to that used for the control panel. The 3 channel I/O is battery powered, but does require wired connections to the circuits it is controlling / monitoring. The cables used should conform to the recommendations of BS

8 CONTROL PANEL INSTALLATION 3 CONTROL PANEL INSTALLATION 3.1 GENERAL Read all the instructions before starting work. Installation must be carried out by suitably qualified / trained personnel. The control panel should be mounted on a wall in a position that allows users clear access to read the display and use the controls. The location should be clean, dry, well ventilated and preferably not in direct sunlight. Temperatures in excess of +45 C or below -10 C may cause problems. 3.2 PANEL MOUNTING The control panel cannot be recessed into a wall as the aerials must be left free of obstructions. Ensure that it is positioned where there is no risk of damage to the aerials. The position should be such that the aerials on top of the control panel are clear of metal structures, cabling and piping. Where the control panel is to be mounted to a partition wall check that services such as cables and pipes are not concealed within it and that plasterboard is not foil backed. For ease of access the panel s door can be removed by opening it to 90, removing the retention bracket above the lower hinge and then sliding it upwards off the hinge spindles. Refitting is the reverse of removal. The panel should be fixed using three suitable fixings through the holes indicated below. Do not drill through the panel to locate the fixings as dust and debris will contaminate the electronics. Figure 4 8

9 CONTROL PANEL INSTALLATION 3.3 AERIALS The panel uses two aerials which are supplied with the panel along with two rubber covers. They are fitted by dropping them through the two holes in the top of the panel and then screwing the connectors fully clockwise onto the sockets provided. The rubber covers should then be dropped over the aerials and fitted so that the groove around the bottom locates with the edge of the panels casing. The covers are deliberately a tight fit and may need effort to fit around the aerial and the panel s casing. 3.4 CABLES Once the control panel has been mounted, power and other external circuits can be installed. Installation must adhere strictly to local wiring codes. Installations in the UK must adhere to the current edition of the IEE Wiring regulations (BS 7671) and to the recommendations of BS : 2002+A2:2008 Fire detection and fire alarm systems for buildings. Code of practice for system design, installation, commissioning and maintenance. ALL CABLING MUST ENTER THE PANEL THROUGH THE 5 ENTRIES IN THE BOTTOM OF THE CASE OR VIA THE RECTANGULAR SLOT IN THE BACK. DO NOT DRILL YOUR OWN ENTRY POINTS IN THE CASING AND ROUTE THE CABLING ACROSS THE INTERNAL AERIAL CONNECTORS OR RADIO CIRCUITRY. CABLING SHOULD BE ROUTED SO THAT IT DOES NOT GO VERTICALLY UPWARDS UNTIL IT IS AT LEAST 1 METRE FROM THE PANEL IN ANY DIRECTION. THIS INCLUDES BEHIND THE PANEL SO DO NOT TAKE CABLES THROUGH THE WALL AND THEN UP BEHIND THE PANEL. IT IS ALSO RECOMMENDED THAT THE 1 METRE EXCLUSION ZONE IS APPLIED AT ALL OTHER SERVICES IN THE BUILDING. Never carry out insulation tests on cables while they are connected to equipment. Do not over tighten connector terminal screws. Always use the correct type of cable specifically designed for in fire detection and alarm systems. Always observe the polarity throughout the system. Non colour coded conductors should be permanently identified. Figure 5 9

10 CONTROL PANEL INSTALLATION 3.5 MAINS SUPPLY Connection to the mains supply must be via an isolating device, such as an un-switched fuse unit, with a fuse rating of 3A. This supply must be reserved solely for the fire alarm system; the cover should be red and labelled: If the circuit is fed from the live side of the main isolator and additional warning label should be added reading: The main isolator should also be labelled: If the isolating device for the fire alarm supply is taken from the switched side of the main isolating device, a label should be fixed to the main isolator reading: The mains supply should enter the control panel at the bottom left and kept segregated from all other circuits entering the enclosure. 10

11 CONTROL PANEL INSTALLATION 3.6 OTHER EXTERNAL CIRCUITS Alarm Sounders Two alarm circuits are provided to operate conventional audible and visual alarm devices to be controlled directly from the control panel. The outputs are designed to work with polarised alarm devices so the polarity of the connections must be observed at all times. For Circuit monitoring a 6K8 end of line (EOL) resistor is supplied, this should be fitted into the last device on each circuit. The circuit must be wired in a radial with no spurring or T connections. If no wired audible or visual alarms are to be used then the resistor should be fitted into the panel terminals to suppress fault warnings. The total alarm load across the two circuits is limited to 1.5A. The load should be distributed evenly across both circuits. DO NOT exceed the rated output current. If connecting to existing circuits, check the loading on each circuit and ensure that there are no existing wiring faults. Note: any hard wired sounders should have a similar tone to the wireless sounders used elsewhere on site Auxiliary Relay The control panel has a volt free (SPCO) contact which operates when a fire condition is indicated. The contacts remain operated until the fire condition is reset. The contact is rated at 1A 24Vdc. DO NOT exceed this current rating Fault Output There is a 12Vdc output from the terminals when the control panel is healthy, i.e. no faults are displayed. If a fault is present the output will drop to 0Vdc. The output is monitored and must have a 6K8 resistor fitted at the end of the circuit. If the output is not used the resistor must be connected into the panel terminals to suppress fault warnings. The output is limited to 30mA. DO NOT exceed this current rating. 11

12 CONTROL PANEL INSTALLATION 3.7 PANEL CONNECTION Figure 6 12

13 CONTROL PANEL INSTALLATION 3.8 NETWORKING Up to 10 control panels may be linked together to operate as a single networked system. To achieve this each panel must be fitted with an additional network card. When operating as a network all fire and fault events are displayed at each panel and when suitably configured, silencing and resetting of alarms can be achieved from any of the panels on the network, Figure 7 Figure 8 13

14 CONTROL PANEL INSTALLATION Cable screen continuity must be maintained throughout the entire network, including each junction point. The screen should only be earthed at one end usually the first control panel. The cable screen and drain wire are NOT to be treated as a safety earth and therefore should not be connected to any terminals marked with an earth symbol except in the control panel. Protective green and yellow earth sleeve should be used. Where a network cable passes between buildings, screen continuity should not be maintained from building to building, but a network booster unit must be used at some point regardless of cable length. The cable screen should be connected to one panel only in each building. A terminator resistor should be fitted at the beginning and end of the network. If the network length exceeds 1Km then a network booster should be used. The network booster requires a 24Vdc supply which can be obtained from the local control panel. Figure 9 Figure 10 Using the cable specified above, the maximum distance between network boosters is 1Km. Once the maximum cable length is reached another network booster must then be fitted which allows a further 1km of cable. A maximum of 3 network boosters can be used. 14

15 4 COMMISSIONING 4.1 INTRODUCTION After the wireless control panel has been powered and any faults remedied the commissioning process for the system can use either three methods. The method chosen will depend on the size and complexity of the site and to some extent on personal preference. Automatic Commissioning learns the devices onto the control panel (or booster) in the order in which they are powered up and automatically assigns addresses consecutively. This method does not use the handheld Survey/Commissioning tools and is best suited to small to medium installations. Manual Commissioning uses the handheld Survey/Commissioning tool to select the device which is to be commissioned on to the control panel. The devices must still be commissioned in sequence as per the site plan as the control panel will automatically assign addresses consecutively. This method allows the devices to be learnt onto the control panel after being fully installed into a building and powered up. Soft Addressing uses the handheld Survey/Commissioning tool to manually assign an address to each device in any order. The control panel is then placed into System Rescan mode to find the addressed devices. Both automatic and manual methods can be used on the same site as circumstances demand. It is not recommended to use the automatic or manual mode with the soft addressing mode on the same site. Device and Zone labelling, cause and effect programming can be set using the touch screen on the control panel, but this can be time consuming with complex systems. It is more convenient to setup the system using a laptop running Site Installer software. These instructions cover only basic system setup using the control panel s touch screen. Site Installer instructions are supplied with the software. 15

16 4.2 SUGGESTED ORDER OF WORK Power Panel Rectify Panel Faults Set-up Panel o Change pass codes o Set time and date o Set number of panels (if networked) o Set Panel number (if networked) o Set system frequency and ID o Hard reset the panel (wait 5 minutes for boot-up to complete) o Wireless/Wired Synchronisation Commission Devices to Panel/Booster: o Automatic method Devices are not powered. Devices are powered to instigate commissioning. Panel automatically assigns an address to each device. o Manual method Devices are already powered. Survey tool is used to wakes up devices and instruct them individually to commission to the panel. Panel automatically assigns an address to each device. o Soft Addressing method Devices are already powered. Survey tool is programmed with Panel/Booster commissioning parameters. Survey tool is used to wake up devices and commission them to a manually selected address. Panel is placed into system rescan mode to find all the pre-addressed devices. o Hard reset the panel on completion(wait 5 minutes for boot-up to complete) Wait 15 minutes for any wireless device faults Rectify Wireless Device Faults Add device text Add zone text Select alarm tone 16

17 4.3 POWERING THE PANEL 1) Fit the two 4Ah batteries into the control panel and fix the clamp. 2) Connect the battery cables (so the batteries are in series) and ensure that the plug is securely fixed into the socket on the PCB. Figure 11 3) Connect the AC mains supply a. The panel will run through a self test routine during which the LED indications will illuminate and the LCD display will also illuminate. b. The display will briefly show and initialisation screen, after which it will default to the home screen with a company logo displayed. If there are any faults on the system these will be listed and must be rectified before proceeding. Figure 12 4) Before commissioning ensure that the following data is entered into the panel (see pages 23 to 37): a. Pass codes for access to the menus b. Time and date c. Panel number (if networked) d. Number of panels (if networked) e. System frequency f. System ID 17

18 4.4 SCREEN COVER During the commissioning process it is likely that the internal buzzer of the control panel will sound frequently. To simply the silencing of the buzzer, a feature called Screen Cover can be installed so that the home screen is changed to include a Mute Buzzer button as shown below. This button can be used without first entering the Supervisor or Engineer pass code. If the following screen is displayed then follow the instructions below for activating the screen cover. 1. On the home screen press the Supervisor button to open the access screen. 2. Enter the engineers code (default is ) and press OK. 18

19 1. Press the Commission button to display the commissioning options. 2. Press the Screen Cover button to change the setting. 3. Press the Installed button to change the home screen to the screen cover mode. 4. The screen will briefly show Saving before returning to the commission menu options. 19

20 4.5 FAULTS If one or more faults are present the home screen will automatically show the faults list. Figure 13 For instructions on how to view the faults refer to the relevant section in the Quick Start Guide supplied. The internal buzzer of the Panel will operate continuously and a combination of Fault LEDs will illuminate. For instructions on how to mute the panel buzzer refer to the relevant section of the Quick Start Guide supplied. The LEDs provide a quick indication of what the faults are without having to examine the faults list. The fault LEDs provide the following fault indications: Power Fault: System Fault: General Fault: There is a problem with the mains supply, the batteries or the battery charger. There is a critical problem with the panel or the watchdog reset switch was pressed. Wireless device faults (all device types) or any other fault not covered by the other fault LEDs. Once the faults have been corrected the panel must be reset to clear the fault indications. For instructions on how to perform a soft reset refer to the relevant section of the Quick Start Guide. 20

21 4.6 ACCESS TO PANEL MENUS The control panel has three levels of access, two of which are pass code protected. Failure to enter the correct pass code 3 times will result in access being denied and the system will return to the home screen ACCESS LEVEL 1(USER) Public access does not require a pass code and allows anyone to view the system status and messages from the home screen. Figure ACCESS LEVEL 2(SUPERVISOR) This is a restricted access level that requires a valid pass code entry to gain access to key panel functions such as Evacuate, Silence Alarms and Soft Reset. The default pass code for this level is It is highly recommended that a different pass code is set during commissioning to prevent unauthorised access. To access this level press the Supervisor button in the top left hand corner then enter the supervisor pass code and press the OK button. Figure 15 21

22 4.6.3 ACCESS LEVEL 3 (ENGINEER) This is a restricted access level that requires a valid pass code entry to gain access to configuration and engineering functions. The default pass code for this level is It is recommended that a different pass code is set during commissioning to prevent unauthorised access. To access this level press the Supervisor button in the top left hand corner then enter the engineer pass code and press the OK button. Figure 16 22

23 4.7 CHANGING PASS CODES Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the Configure button to show the configurable options. 23

24 5. Press the Change Passcode button to show the pass code selection screen. 6. Press the pass code button you wish to change. 7. The pass code entry screen will be displayed. 8. Enter the current pass code (DO NOT PRESS OK). 9. Press underneath New Code: so the cursor appears. 10. Enter your new pass code (DO NOT PRESS OK). 11. Press underneath Verify New Code: so the cursor appears 12. Enter your new pass code again and then press OK. 24

25 13. Press the OK button. The new pass code is now active. 25

26 4.8 SETTING TIME AND DATE Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the Configure button to show the configurable options. 26

27 1. Press the Change Date/Time button to show the time and date entry screen. 2. Press the top 6 buttons to adjust the time by the increments shown. 3. Press the bottom 6 buttons to adjust the date by the increments shown. 4. Press the OK button to save the adjusted time and date. 27

28 4.9 SETTING NUMBER OF PANELS (NETWORKING) Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the Commission button to show the wireless options. 28

29 5. Press the Number of panels in Network button to show the entry screen. 6. Enter the total number of panels that will be networked together. 7. Press the OK button to save the parameter. 29

30 4.10 SETTING PANEL NUMBER (NETWORKING) Screen Cover Installed 8. If the backlight is off press the top right of the screen to activate the backlight. 9. Press the Supervisor button to open the access screen. No Screen Cover Installed 10. Enter your ENGINEER code (default is ) and press OK. 11. Press the Commission button to show the wireless options. 30

31 12. Press the Change Panel Number button to show the entry screen. 13. Enter the number that identifies this panel on the network. 14. Press the OK button to save the parameter. 31

32 4.11 SETTING SYSTEM ID Screen Cover Installed 15. If the backlight is off press the top right of the screen to activate the backlight. 16. Press the Supervisor button to open the access screen. No Screen Cover Installed 17. Enter your ENGINEER code (default is ) and press OK. 18. Press the RF button to show the wireless options. 32

33 19. Press the System ID button to show the entry screen. 20. Enter a unique System ID between 1 and 255 (0 is not a valid ID). Each Panel and Booster should be assigned a unique ID; none of them should be the same. 21. Press the OK button to save the system ID. 33

34 4.12 SETTING SYSTEM FREQUENCY Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the RF button to show the wireless options. 34

35 5. Press the System frequency button to show the entry screen. 6. Enter a unique System Frequency between 0 and 14. Each Panel and Booster should be assigned a unique frequency; none of them should be the same. 7. Press the OK button to save the system frequency. 35

36 4.13 FREQUENCY CHANNEL SELECTION GUIDE Certain channels cannot be used together as they will interfere with each other. Use the following tables in conjunction with the survey results to reduce the possibility of interference between systems. It is highly recommended to always use wired or wireless synchronisation on multiple panel sites to give the optimum radio performance. 36

37 4.14 HARD RESET 1. Once the System ID and System Frequency have been set to the correct values then press the hard reset for the new settings to take effect. 2. Wait 5 minutes for the system to stabilise before proceeding. 37

38 4.15 PANEL SYNCHRONISATION WIRED SYNCHRONISATION 1. If there are multiple Control Panels on the site and they are not in radio range of each other but their wireless devices are, then a wired sync connection is required. 2. Connect one end of a 2-core cable to the SYNC OP+ and OP- terminals of the Master Panel. 3. Connect the other end of the 2-core cable to the SYNC IP+ and IP- terminals of the 1 st Slave Panel;, making sure the polarity is correct (+ to +, - to -). 4. Connect 2-core cables from the SYNC IP+/- of each Slave Panel to the SYNC IP+/- of each Slave Panel, making sure the polarity is correct (+ to +, - to -), to create a daisy chain. 5. If you re at the Auto Learn menu then jump to step If you re at the home screen press the Supervisor button to open the access screen. 7. Enter the engineer code as previously shown. 38

39 8. Press the RF button at the bottom of the screen. 9. Press RF sync master. 10. Select Yes for Master mode. 11. Select No for Slave mode NOTE: A hard reset will be required to configure the Panel in the mode selected. 39

40 WIRELESS SYNCHRONISATION Screen Cover Installed 1. If there are multiple Control Panels on the site and they are in radio range of each other then a wireless synchronisation is required. 2. If the backlight is off press the top right of the screen to activate the backlight. No Screen Cover Installed 3. Press the Supervisor button to open the access screen. 4. Enter your ENGINEER code (default is ) and press OK. 5. Press the RF button to show the wireless options. 40

41 NOTE: THIS OPTION IS ONLY AVAILABLE WHEN THE PANEL IS CONFIGURED AS THE MASTER 6. Press the RF Synchronisation button to show the entry screen. 7. Press the Yes button if you want to start a wireless synchronisation scan. 8. Press the No button to return to the menu screen. 9. The Panel will now scan all available system channels (excluding its own channel) looking for another system in range to synchronise with, 10. Once the scan is complete the display will return to the menu screen. 11. Every subsequent system power-up or hard reset the Panel will synchronise with the other Panel. This will prevent the Panels interfering with each other. 41

42 4.16 PRE-COMMISSIONING 1. Ensure the sit e plan is available so that the location of all Boosters, Sounder/Beacons, Call Points, Detectors and I/O units are clearly identified. 2. Install any Boosters at their required locations as per the site plan. 3. Fit the first fit components, i.e. Sounder/Beacon back boxes, Call Point back boxes, Detector mounting plates 42

43 4.17 AUTOMATIC COMMISSIONING COMMISSIONING DEVICES TO PANEL Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the Commission button to display the commissioning options. 43

44 5. Press the Auto Learn button to display the commissioning modes. 6. Press the Commission to panel button to place the Panel into commissioning mode. 44

45 7. After a few moments the screen will display Please commission device now. 8. This mode will automatically assign the next free address to a device being commissioned. It is recommended to commission the devices in address order as per the site plan. 9. To commission a Booster either power-cycle it or press its hard reset button. 10. To commission any other device, simply insert the 3 AA lithium batteries supplied. 11. After approximately 10 seconds the LED on the device (not Boosters) will illuminate to show that it has been locked to the Panel, the LED will turn off after approximately 5 seconds. 12. The Panel will show that the device has been locked by displaying the address assigned to the device and its device type. 13. Fit the Device (not Boosters) to its mounting plate, base or box. 14. Repeat the process for each device in order of the site plan. 15. Pressing the Finish button at any time will save the data and return you to the auto learn menu. This allows you to switch between Commission to Panel and Commission to Booster modes as and when the site plan dictates. NOTE: If the LED on the device illuminates in a couple of seconds then this device is already commissioned and cannot be commissioned again. If the device has not been commissioned to this or another Panel/Booster on this site then this device can only be used after being hard decommissioned using a decommissioning tool. NOTE: Call Points will turn there LEDs back on again after commissioning. This is normal as the call point is registering an alarm. A soft reset at the end of commissioning is required to clear these alarm conditions. 45

46 COMMISSIONING DEVICES VIA A BOOSTER Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the Commission button to display the commissioning options. 46

47 5. Press the Auto Learn button to display the commissioning modes. 6. Press the Commission to booster button to place the Panel and Booster into commissioning mode. 7. A list of all Boosters commissioned to the Panel will be shown. 8. Select the Booster you wish the devices to be commissioned to as per the site plan. 47

48 9. The display will ask for confirmation that this is the correct Booster. 10. If it is simply press the Yes button to start commissioning devices to the Booster. 11. If it is not then press the No button to return to the Booster list. 12. After a few moments the screen will display Please commission device now. 13. This mode will automatically assign the next free address to a device being commissioned. It is recommended to commission the devices in address order as per the site plan. 14. To commission a device, simply insert the 3 AA lithium batteries supplied. 15. After approximately 10 seconds the LED on the device (not Boosters) will illuminate to show that it has been locked to the Panel, the LED will turn off after approximately 5 seconds. 16. The Panel will show that the device has been locked by displaying the address assigned to the device and its device type. 17. Fit the Device to its mounting plate, base or box. 18. Repeat the process for all devices on this Booster in order of the site plan. 19. Pressing the Finish button at any time will save the new data and return you to the auto learn menu. This allows you to switch back to Commission to Panel mode or select a different Booster in Commission to Booster mode as and when the site plan dictates. NOTE: Boosters CANNOT be commissioned to Boosters. 48

49 4.18 MANUAL COMMISSIONING COMMISSIONING DEVICES TO PANEL 1. Follow steps 1 through 8 in COMMISSIONING DEVICES TO PANEL to place the panel into commission to panel mode. 2. The survey/commissioning tool needs to be in Via Panel mode, refer to survey tool manual for more details. 3. Follow the commissioning instructions as outlined in the survey tool manual. 4. Repeat the process for each device directly on the panel, in order of the site plan. 5. Pressing the Finish button at any time will save the data and return you to the auto learn menu. This allows you to switch between Commission to Panel and Commission to Booster modes as and when the site plan dictates. 49

50 COMMISSIONING DEVICES VIA A BOOSTER 1. Follow steps 1 through 13 in COMMISSIONING DEVICES TO PANEL to place the panel into commission to booster mode. 2. The survey/commissioning tool needs to be in Via Panel mode, refer to survey tool manual for more details. 3. Follow the commissioning instructions as outlined in the survey tool manual. 4. Repeat the process for each device directly on the Booster, in order of the site plan. 5. Pressing the Finish button at any time will save the data and return you to the auto learn menu. This allows you to switch between Commission to Panel and Commission to Booster modes as and when the site plan dictates. 50

51 4.19 SOFT ADDRESSING COMMISSIONING COMMISSIONING DEVICES TO PANEL 1. The survey/commissioning tool needs to be in Via Programmer mode and programmed with the Panel s serial number, system ID and system frequency, refer to survey tool manual for more details. 2. Follow the commissioning instructions as outlined in the survey tool manual. 3. Repeat the process for each device on the Panel (including Boosters) and manually assign them a soft address as per the site plan COMMISSIONING DEVICES VIA A BOOSTER 4. The survey/commissioning tool needs to be in Via Programmer mode and programmed with the Booster s serial number, system ID and system frequency, refer to survey tool manual for more details. 5. Follow the commissioning instructions as outlined in the survey tool manual. 6. Repeat the process for each device on the Booster and manually assign them a soft address as per the site plan. 7. Repeat from step 1 for all Boosters on the system. 51

52 SYSTEM RESCAN Screen Cover Installed 8. If the backlight is off press the top right of the screen to activate the backlight. 9. Press the Supervisor button to open the access screen. No Screen Cover Installed 10. Enter your ENGINEER code (default is ) and press OK. 1. Press the Commission button to display the commissioning options. 52

53 2. Press the Auto Learn button to display the commissioning modes. 3. Press the System Rescan button to place the Panel into commissioning mode. 4. The display will ask for confirmation before starting a system rescan. NOTE: The control panel starts a system rescan with an empty device list. 5. Press the Yes button to start the system rescan. 6. Press the No button to return to the auto learn menu. 53

54 7. The panel will request the type ID and soft address from ALL 250 possible addresses. 8. As each device responds to the request the Panel will save the device to the device list. 9. This process will take approximately 12 minutes to complete. 10. Once complete the screen will briefly show the number of devices found, and will then automatically exit ENDING COMMISSIONING 1. When new devices have been locked to the Panel the auto learn menu will change to show a Hard Reset button. 2. Once all devices have been commissioned press the Hard Reset button to allow all default cause and effect programming to take effect. 3. The Panel will start the normal boot-up cycle. 4. Wait 5 minutes after boot-up to allow the system to stabilise. 54

55 4.21 ADDING DEVICE TEXT Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the Configure button to display the configure options. 55

56 5. Press the Change Text button to display the text options. 1. Press the Change Address Text button to display the address list. 2. Select an address from the list to display the QWERTY keyboard so that the address text can be changed. 56

57 1. The address text can be entered by using the virtual keyboard displayed on the screen. Press the OK button once done and the display will show the saving prompt. 2. Once saved it will return to the previous screen. 3. It is recommended to use site installer to conduct more complex programming. 57

58 4.22 ADDING ZONE TEXT Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the Configure button to display the configure options. 58

59 5. Press the Change Text button to display the text options. 6. Press the Change Zone Text button to display the zone list. 1. Select a zone from the list to display the QWERTY keyboard so that the zone text can be changed. 59

60 1. The zone text can be entered by using the virtual keyboard displayed on the screen. Press the OK button once done and the display will show the saving prompt. 2. Once saved it will return to the previous screen. 3. It is recommended to use site installer to conduct more complex programming. 60

61 4.23 ADDING PANEL TEXT Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your ENGINEER code (default is ) and press OK. 4. Press the Configure button to display the configure options. 61

62 5. Press the Change Text button to display the text options. 6. Press the Change Panel Text button to display the QWERY keyboard so the panel text can be changed. 1. The panel text can be entered by using the virtual keyboard displayed on the screen. Press the OK button once done and the display will show the saving prompt. 2. Once saved it will return to the previous screen. 3. It is recommended to use site installer to conduct more complex programming. 62

63 MAINTENANCE 5 MAINTENANCE 5.1 SYSTEM MAINTENANCE All fire systems require regular inspection and maintenance. For systems installed in the UK the guidance given in BS should be followed. Wireless systems also require that the batteries in the field devices are changed periodically. 5.2 SYSTEM SHUT-DOWN It is recommended that if a control panel or booster needs to be shut-down for more than 12 hours that the field devices are also powered down to conserve battery life. Failure to follow this guideline could result in degraded battery life as the field devices will be attempting to regain communications with the control panel. 5.3 WIRELESS RECEPTION If a field device loses communications with the control panel or booster to which it is assigned, it is a requirement of the governing standards that it makes regular attempts to regain communications. A field device will regain communications with the panel by periodically listening for a broadcast from the control panel. Once synchronisation and communications is regained the field device will report its current status to the control panel. The control panel poll the system every 80 seconds to make sure all devices are still in communication with it. The control panel will resend the poll to any device that fails to respond every 20 seconds until the field device responds. If the unit fails to respond for a full 5 minutes then a device missing fault will register for this device. However, this does not mean that the device will not regain communications once the radio obstruction has cleared. 5.4 CHANGING BATTERIES The wireless system will give an automatic warning at the control panel when the capacity left in any set of batteries is running low. When the warning is given the batteries will still be able to operate the device for more than 30 days. In normal service, batteries will have a life of around 3 years. When replacing batteries only use approved types as listed on labels fixed to the devices. It is advisable to disable the devices concerned before changing their batteries. If the devices are not disabled, tamper faults will be generated by the device(s) and in the case of call points a fire will also be generated as the glass element will have been removed. The disable command can be applied to either an individual address or a zone. If several sets of batteries are to be changed it is recommended to use the disable zone option. Once all batteries have been replaced and the field units re-mounted, the control panel should be reset before enabling the addresses or zones. 63

64 MAINTENANCE DISABLING AN ADDRESS Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your SUPERVISOR code (default is 2214) and press OK. 4. Press the Enable/Disable button to display the enable/disable menu. 64

65 MAINTENANCE 5. Press the Enable/Disable Address button to display the address list. 6. Press the up and down arrows to scroll through the address list. 7. To disable a device press the Enabled button at the side of the address, this will change to Disabled. The General Disable LED will turn on. 8. To enable device press the Disabled button the side of the address, this will change to Enabled. The General Disable LED will turn off if there are no other disablements. 65

66 MAINTENANCE DISABLING A ZONE Screen Cover Installed 1. If the backlight is off press the top right of the screen to activate the backlight. 2. Press the Supervisor button to open the access screen. No Screen Cover Installed 3. Enter your SUPERVISOR code (default is 2214) and press OK. 4. Press the Enable/Disable button to display the disable address list. 66

67 MAINTENANCE 5. Press the Enable/Disable Zone button to display the zone list. 6. Press the up and down arrows to scroll through the zone list. 7. To disable a zone press the Enabled button at the side of the zone, this will change to Disabled. The General Disable LED will turn on. 8. To enable zone press the Disabled button the side of the zone, this will change to Enabled. The General Disable LED will turn off if there are no other disablements. 67

68 CWC950 Call Point PRODUCT DATA SHEETS 6 PRODUCT DATA SHEETS 68

69 CWSB980 Sounder / Beacon PRODUCT DATA SHEETS 69

70 CWD910 Detector / CWDB920 Detector Sounder Beacon PRODUCT DATA SHEETS 70

71 PRODUCT DATA SHEETS 71

72 CWIF930 Wireless 3 Channel I/O PRODUCT DATA SHEETS 72

73 73

74 PINST: CW9000 Document Drg Ref: PR

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

ZERIO PLUS EDA-Z5008, Z5020 & Z5100 ZERIO PLUS EDA-Z5008, Z5020 & Z5100 USER MANUAL Revision 1.00 EDA-Z5008, Z5020 & Z5100 User Manual 0359 Electro Detectors Limited Electro House Edinburgh Way Harlow, Essex CM20 2EG, UK 14 0359 CPR 00226

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual BiWire Flexi BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual Contents Contents 1. INTRODUCTION... 4 1.1 Purpose...4 2. THE BIWIRE FLEXI FIRE DETECTION & ALARM

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

Electro-Detectors Page 2. Revision History. EDA-Z Installation and Operation Manual

Electro-Detectors Page 2. Revision History. EDA-Z Installation and Operation Manual EDA-Z1000 Radio Fire Alarm System Operation and Installation Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2TP UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections. ISSUES ISSUE DATE RELEASED DETAILS OF CHANGE AUTHOR 4 Rev 2 September 2004 Changes for 4000 series. DB 4 Rev 3 April 2005 Screen shots updated and other minor changes K.Z. 4 Rev 4 September 2006 4 Rev

More information

Networked Access Control Panel. Installation Guide

Networked Access Control Panel. Installation Guide XP2M Networked Access Control Panel V1.0X Installation Guide X P 2 M A C C E S S C O N T R O L S Y S T E M Installation Guide Document Ref: PLAN XP2M Installation Guide V4(G)2010 Access Control Services

More information

SOLO Single Loop Addressable Fire Control Panel

SOLO Single Loop Addressable Fire Control Panel Solo Single Loop Analogue Addressable Fire Control Panel Apollo Protocol Installation, Commissioning & Operating Manual Issue 03 June 1999 CONTENTS Section... Page 1. Introduction...1 2. Safety...2 3.

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

ZSC100 Gas Detection and Alarm System Controller

ZSC100 Gas Detection and Alarm System Controller ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2

More information

ZITON RADIO LOOP MODULE

ZITON RADIO LOOP MODULE ZITON RADIO LOOP MODULE PROGRAMMING MANUAL Table of Contents Section Page No 1.0 INTRODUCTION...3 1.1 System Design...3 1.2 Handling Precautions...3 1.3 Packaging:...3 2.0 MENU STRUCTURE...4 2.1 Menu Structure

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj Control Equipment Limited 32 Zone, 40 Character Discovery Panel, Voyager Panel and Integra Network Repeater Installation, Commissioning

More information

14300 MAINS SEPARATOR ALARM MANUAL

14300 MAINS SEPARATOR ALARM MANUAL Conder Environmental Solutions 14300 MAINS SEPARATOR ALARM MANUAL Separator and Alarm provided by: Alarm Installation, Commissioning & Servicing Support Please contact: www.envirotank.com.au www.envirotank.co.nz

More information

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL The LeakStopper Multizone detects the presence of water in environments where it is not supposed to be. Should water

More information

CTPR3000 TOUCHSCREEN REPEATER PANEL INSTALLATION MANUAL

CTPR3000 TOUCHSCREEN REPEATER PANEL INSTALLATION MANUAL CTPR3000 TOUCHSCREEN REPEATER PANEL INSTALLATION MANUAL Cooper Fire Systems Security House, Vantage Point Business Village Mitcheldean Gloucester GL17 0SZ United Kingdom TEL: +44(0)1594 541900 FAX: +44(0)1594

More information

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1 INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation

More information

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

Operating instructions SENTRI4 Control panel based Fire detection and alarm system 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

Temporary wireless battery operated fire system from Channel Safety Systems

Temporary wireless battery operated fire system from Channel Safety Systems Temporary wireless battery operated fire system from Channel Safety Systems CHANNEL SAFETY SYSTEMS t: 0845 884 7000 Petersfield Business Park f: 0845 884 6000 Bedford Road Petersfield Hampshire e: sales@channelsafety.co.uk

More information

Control Panel User Guide (TO BE RETAINED BY THE USER)

Control Panel User Guide (TO BE RETAINED BY THE USER) Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement

More information

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above Surveyor Excel Fire Alarm Control Equipment Network version Programming Manual VERSION 14.0 and Above MASTER MANUAL Drawing S1606. PCB Layout guide for XLK range of control panels FCPXLK-2/4/6/8 & FCPXLK2/4/6/8TW

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual VoCALL - CFVCC5 Compact 5 Line Exchange Unit Installation & Commissioning Manual Introduction A VoCALL Emergency Voice Communications System (EVCS) is a fixed, secure, bi-directional, full duplex voice

More information

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL Contents IMPORTANT... 3 General Description... 4 General Operation... 4 Changing Factory Settings... 4 Alarm Type... 4 Check Interval...

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V1.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-1028 Issue 2 Fike s policy is one of continual

More information

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0) Overview of the Water Detection System 2 Components of a System 4 Design & Planning 5 System Installation Notes 7 Control Panel Installation - HSCPI-K3000 8 Control Panel Commissioning HSCPC-K3000 11 Front

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-5:2000+A1:2002 EN54-25:2008 0359 Electro Detectors Ltd. Electro House Edinburgh

More information

Operating instructions Vigilon panel and Network node Fire detection and alarm system

Operating instructions Vigilon panel and Network node Fire detection and alarm system Healthy 15:45 Fault Power Fault Vigilon Fire System GENT 2015 Designed to EN54 Pt 2 & 4 System Fault Operating instructions Vigilon panel and Network node Fire detection and alarm system Test Fire Fault/Dis

More information

RP1r-Supra / VSN-RP1r+ / ESS-RP1r-Supra Extinguishing Control Panel User Manual. HLSI-MN-103I v.06 September 2017

RP1r-Supra / VSN-RP1r+ / ESS-RP1r-Supra Extinguishing Control Panel User Manual. HLSI-MN-103I v.06 September 2017 / VSN-RP1r+ / ESS-RP1r-Supra Extinguishing Control Panel HLSI-MN-103I v.06 September 2017 Note Nota: This manual is valid for the following control panel models: RP1r-Supra VSN-RP1r+ (no touch screen)

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

2200 and 2200L ALARM CONTROL SYSTEMS

2200 and 2200L ALARM CONTROL SYSTEMS 2200 and 2200L ALARM CONTROL SYSTEMS OPERATING INSTRUCTIONS MODELS: 2200 (fitted software 3.4 or later) 2200L (fitted software 3.9L or later) Castle Care-Tech Ltd. 2200/2200L Alarm System Operating Manual

More information

Zerio. Electro-Detectors EDA-Z1000. Radio Fire Alarm System. Operation and Installation Manual

Zerio. Electro-Detectors EDA-Z1000. Radio Fire Alarm System. Operation and Installation Manual Zerio EDA-Z1000 Radio Fire Alarm System Operation and Installation Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2TP UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Door Release Power Supply

Door Release Power Supply www.protectingpeople.co.uk Door Release Power Supply Engineer / Installation Manual Document: VI55.1 Protecting People Printed : 04/03/2004-1 - Ventcroft Ltd Door Release Power Supply Engineer / Installation

More information

ID2000. operating manual

ID2000. operating manual ID2000 operating manual 997-434-000-2, Issue 2 Contents ID2000 Series Operating Manual Contents 1 Introduction 1 1.1 Associated Documents 1 1.2 The ID2000 Panels 1 1.3 Cleaning 2 2 Panel Controls and Indicators

More information

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Australia Issue 01 April 2012 Contents 1 Introduction 3 2 Safety 3 3 Installation 4 3.1 Mounting the Cabinet 4 4 Specifications

More information

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system SenTRI ONE panel-based Fire detection and alarm system one 042bc/14 4188-978 issue 2_04-10_SenTRI ONE system oper Part of Document pack 2535-235 issue 2 1 Contents User responsibility - - - - - - - - -

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

Installation guide. Wireless room thermostat with hot water control (DHW & single zone CH)

Installation guide. Wireless room thermostat with hot water control (DHW & single zone CH) Installation guide Wireless room thermostat with hot water control (DHW & single zone CH) Logic Heat H / Logic Max Heat H / Logic System S / Logic Max System S / Vogue System / Vogue Max System Ideal Touch

More information

Document No Issue 02 operation & installation manual. ZXr-A ZXr-P

Document No Issue 02 operation & installation manual. ZXr-A ZXr-P ZXr-A ZXr-P Document No. 996-144 Issue 02 operation & installation manual MORLEY-IAS ZXr-A / ZXr-P Repeaters Table of Contents 1 INTRODUCTION... 3 1.1 NOTICE... 3 1.2 WARNINGS AND CAUTIONS... 3 1.3 NATIONAL

More information

FIRE CONTROL PANEL. Revision 1.1 January 1997 USER MANUAL. Emergi-Lite Safety Systems Ltd Bruntcliffe Lane Morley Leeds LS27 9LL

FIRE CONTROL PANEL. Revision 1.1 January 1997 USER MANUAL. Emergi-Lite Safety Systems Ltd Bruntcliffe Lane Morley Leeds LS27 9LL FIRE CONTROL PANEL Revision 1.1 January 1997 USER MANUAL Emergi-Lite Safety Systems Ltd Bruntcliffe Lane Morley Leeds LS27 9LL Tel: 0113 281 0600 Fax: 0113 281 0601 C O N T E N T S PAGE INTRODUCTION...

More information

Digital Electronic Thermostat With RF

Digital Electronic Thermostat With RF RT300RF Manual:89 6/7/10 12:52 Page 1 Digital Electronic Thermostat With RF Instruction Manual Model No RT300RF 2 RT300RF Manual:89 6/7/10 12:52 Page 2 2 RT300RF INSTRUCTION MANUAL RT300RF Manual:89 6/7/10

More information

GAS SUPRESSION CONTROL PANEL:

GAS SUPRESSION CONTROL PANEL: GAS SUPRESSION CONTROL PANEL: MODEL NAME: COMPANY: DELTA 437/2, Main Road, Mandwali Fazalpur, Delhi-110092 Page 1 ABOUT THE PRODUCT ASES is very proud of to introduce DELTA the completely digital microprocessor

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

SCS311 / SCS317 Installation Instructions

SCS311 / SCS317 Installation Instructions SCS311 / SCS317 Installation Instructions SCS311 or SCS317 Wireless Programmable Room Thermostat Programmable room thermostats are widely recognised as one of the best ways in which to control central

More information

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices. FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel. Application Guide

Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel. Application Guide Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-7:2000+A1:2002+A2:2006 EN54-25:2008 0359 Electro Detectors Ltd. Electro

More information

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

Radio fire warning panel SRC 3000

Radio fire warning panel SRC 3000 Radio fire warning panel SRC 3000 6 zone radio fire warning panel Operating instructions Version 1.2 Art. 32487 detectomat GmbH Headquarter: Phone: +49 (0) 4102-2114-60 An der Strusbek 5 Fax: +49 (0) 4102-2114-670

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0)

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

SRT321 User and Installation Instructions

SRT321 User and Installation Instructions SRT321 User and Installation Instructions Electronic Room Thermostat & Temperature Sensor (Tx) - Z-Wave 1 2 The SRT321 is a wireless electronic battery powered room thermostat that uses interoperable two-way

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone

More information

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1 ViewMatrix Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels Version: 2.0 Revision: 0.1 CONTENTS 1. Introduction...3 2. Keyboard...5 2.1 POWER indication - Normal Operation...5

More information

USER GUIDE Wireless room thermostat with hot water control (DHW & single zone CH)

USER GUIDE Wireless room thermostat with hot water control (DHW & single zone CH) USER GUIDE Wireless room thermostat with hot water control (DHW & single zone CH) Logic Heat H / Logic Max Heat H / Logic System S / Logic Max System S / Vogue System / Vogue Max System Contents Introduction...

More information

SYSTEM 5000 USER MANUAL

SYSTEM 5000 USER MANUAL SYSTEM 5000 USER MANUAL Table of Contents Section Page No 1 Introduction: -... 3 1.1 Procedure:... 3 1.2 Warnings and Cautions:... 3 2 User Control Levels:... 4 3 User Passwords:... 4 4 Controls and Displays:

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 PREMIER EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 USER MANUAL Approved Document No: GLT.MAN-132 INDEX Extinguishing

More information

Digital Electronic Thermostat With RF

Digital Electronic Thermostat With RF Digital Electronic Thermostat With RF Instruction Manual Model No RT300RF PRODUCT COMPLIANCE This product complies with the essential requirements of the following EC Directives: Electro-Magnetic Compatibility

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

CPA6. Installation & User Guide. Intelligent Security & Fire Ltd. Compatible Equipment

CPA6. Installation & User Guide. Intelligent Security & Fire Ltd. Compatible Equipment Installation & User Guide Compatible Equipment CPA6 OM - Output Module 9040 - Loudspeaker DC54/58 - Digital Communicators (Stand Alone Only) 496524 Issue A 1 of 16 CPA6 Overview Introduction Facilities

More information

Thermostat install guide

Thermostat install guide Thermostat install guide 74_Hive Thermostat Install Guide_97mmx97mm_v3.indd 1 23/11/2015 14:0 Install Guide For Hive Active Heating the thermostat, receiver and hub are installed together so heating and

More information

Salamander User Guide

Salamander User Guide SYSTEM USER GUIDE Introduction Salamander User Guide Salamander is a radio-controlled, battery-powered system for holding open fire doors. Before installation, a thorough radio survey will have been conducted

More information

LEAKSTOPPER 1 Single zone water leak detection system

LEAKSTOPPER 1 Single zone water leak detection system LEAKSTOPPER 1 Single zone water leak detection system WHAT DOES THE PRODUCT DO? The LeakStopper 1 detects the presence of water in environments where it is not supposed to be. Should water be detected

More information

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V2.00) Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0959

More information