Model CV-1F Grooved End Swing Check Valves. General Description. Technical Data. Installation. Page 1 of 6 FEBRUARY 2016 TFP1550. Worldwide Contacts

Size: px
Start display at page:

Download "Model CV-1F Grooved End Swing Check Valves. General Description. Technical Data. Installation. Page 1 of 6 FEBRUARY 2016 TFP1550. Worldwide Contacts"

Transcription

1 Worldwide Contacts Model CV-F Grooved End Swing Check Valves General Description The TYCO Model CV-F Grooved End Swing Check Valves are compact and rugged swing-type units that allow water flow in one direction and prevent flow in the opposite direction. A resilient elastomer seal facing on the spring-loaded clapper ensures a leaktight seal and non-sticking operation. The Model CV-F Check Valves are designed to minimize water hammer caused by flow reversal. The Model CV-F Grooved End Swing Check Valves are furnished with grooved ends and can be installed using GRINNELL Grooved Couplings or GRINNELL Figure 7 Flange Adapters. The Model CV-F Check Valves have been designed with a removable cover for ease of field maintenance. These valves can be installed horizontally (with cover in the upward position) or vertically with the flow in the upward direction (Ref. Figure ). A check valve maintenance kit is available to allow backflushing through a fire department connection without removing the Model CV-F Grooved End Swing Check Valve from the riser. Refer to technical data sheet TFP. Model CV-F is a re-designation for Central Figure 90F and GRINNELL Figure 90F Grooved End Swing Check Valves. NOTICE The TYCO Model CV-F Grooved End Swing Check Valves described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protection Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. Never remove any piping component nor correct or modify any piping deficiencies without first de-pressurizing and draining the system. Failure to do so may result in serious personal injury, property damage, and/or impaired device performance. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions. Technical Data Approvals Compliance with CE Pressure Equipment Directive (PED) and Standards of Engineering Practice to (DN0 to DN00): UL and C-UL Listed, FM Approved, Bureau Veritas -/ to 0 (DN to DN0): VdS Approved Certificate No. G4000 Sizes to (DN0 to DN00) Maximum Working Pressure UL/FM - 00 psi (0,7 bar) VdS - bar Valve Assembly Finish Red, non-lead paint For fire protection pressure rating, listing and approval information, contact your TYCO representative. Installation The Model CV-F Grooved End Swing Check Valves are to be installed in accordance with this section: Step. The arrow cast on the body must point in the direction of the flow. Step. Valves installed vertically must be positioned with the flow in the upward direction. Step. Valves installed horizontally must be positioned with the cover facing up (Ref. Figure ). Step 4. Grooved end pipe couplings used with the Model CV-F Grooved End Swing Check Valves must be installed in accordance with manufacturer s instructions. Note: Valves should be installed a reasonable distance downstream from pumps, elbows, expanders, reducers, or other similar devices to extend the valve life. Standard piping practices call for a minimum of five () times the pipe diameter for general use. Page of FEBRUARY 0 TFP0

2 TFP0 Page of Nominal Pipe Size Valve Size (DN) Pipe O.D. Nominal Dimensions A B C D E F J Cover Bolt Torque Lbs.-ft. (Nm) Approx. Weight Lbs. (kg) (0) -/ 7, mm (0) 4 (00),7 mm () (), mm (0) (0) (00) 0 (0) (00).7 (0,). (7,0) (7,).0 (,9) 4.0 (4,).0 (,7). (4,).0 (,). (,). (9,) 0.7 (7,).7 (,9).7 (7,).00 (0,).00 (0,).7 (,) 9. (44,) 0.0 (,7) 0.0 (,7).0 (9,).0 (9,) 4.00 (,).00 (47,).00 (,4).9 (49,). (,7). (,7).7 (4,). (9,7) 7.40 (,0) 7.40 (,0).00 (0,).00 (0,) 0.4 (7,). (4,) 4. (,7).9 (49,). (,7). (,7). (7,4).0 (9,) 4.4 (,) 4.4 (,) 4. (7,) 4. (7,).7 (9,4). (,9) 9.9 (,).7 (,).09 (7,).09 (7,). (4,). (9,) 4. (04,9) 4. (04,9) 4.0 (4,) 4.0 (4,). (40,).4 (,) 7.7 (4,7). (,).7 (9,).7 (9,).7 (9,) 4. (,4) 4.90 (4,) 4.90 (4,).00 (7,0).00 (7,0).4 (,7) 7.0 (90,) 7. (9,) 4.7 (0,7).7 (49,).7 (49,).7 (49,) 7. (,) 7.0 (90,) 7.0 (90,) 7.0 (9,0) 7.0 (9,0).4 (4,9) 0.0 (,7) 0. (9,7). (4,). (4,7). (4,7). (4,7).4 (4,7).7 (44,).7 (44,). (47,0). (47,0). (4,) (7,).7 (9,9) () (4) (4) (4) 0 (9) (4) (4) 0 () 0 () 0 (4) 0 (7) 0 (7) 9.0 (4,) 0.0 (4,) 0.0 (4,).0 (,0).0 (,) 9.0 (,) 9.0 (,) 47.0 (,) 47.0 (,).0 (9,9) 09.7 (49,4).0 (,0) B A C O.D. D Care and Maintenance The TYCO Model CV-F Grooved End Swing Check Valves must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection /" NPT FIGURE MODEL CV-F GROOVED END SWING CHECK VALVES NOMINAL DIMENSIONS system from the proper authorities and notify all personnel who may be affected by this decision. After placing a fire protection system in service, notify the proper authorities and advise those responsible for monitoring proprietary and/or central station alarms. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards F E J /" NPT of the National Fire Protection Association (e.g., NFPA ), in addition to the standards of any authority having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Any impairments must be immediately corrected. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.

3 TFP0 Page of No. Part Material Qty. Body Ductile Iron Cover Ductile Iron Cover Gasket 4 Hex Cap Screw Clapper, "-" (DN0-00) Clapper, 0"-" (DN0-00) Nitrile Rubber, Zinc Plated 4, Ductile Iron AR SEE VIEW A No. Part Material Qty. Clapper Facing 7 Spring Hinge Shaft 9 Retaining Ring Retention Bolt Retaining Disc 7 EPDM Grade "E" 9 SEE DETAIL B AR " - " (DN0-DN00) No. Part Material Qty. 4 Locknut Plug /" NPT Adhesive Cast Iron Thread Sealer AR 7 Nameplate Aluminum Rivet 9 Spacer 7 " - " (DN0-DN00) FIGURE MODEL CV-F GROOVED END SWING CHECK VALVES ASSEMBLY DETAIL B 9 7 0" - " (DN0 - DN00) VIEW A 4, 0" - " (DN0 - DN00), 9 NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI) INCH (DN0) -/ INCH (DN) INCH (DN0) FLOW RATE IN LITERS PER MINUTE (LPM) ( GPM =,7 LPM) 4 INCH (DN00) INCH (DN) INCH (DN0) INCH (DN00) FLOW RATE IN GALLONS PER MINUTE (GPM) 0 INCH (DN0) GRAPH A MODEL CV-F GROOVED END SWING CHECK VALVES NOMINAL PRESSURE LOSS VS. FLOW INCH (DN00) ,0 0,0 0,0 0,09 0,0 0,07 0,0 0,0 0,04 NOMINAL PRESSURE DROP IN BAR ( PSI = 0,09 BAR)

4 TFP0 Page 4 of Valve Size (DN) (0) -/ 7, mm (0) 4 (00),7 mm () (), mm (0) (0) (00) 0 (0) (00) Pipe O.D..7 (0,). (7,0) (7,).0 (,9) 4.0 (4,).0 (,7). (4,).0 (,). (,). (9,) 0.7 (7,).7 (,9) Part Number TABLE A MODEL CV-F GROOVED END SWING CHECK VALVES PART NUMBER SELECTION Valve Size (DN) (0) -/ 7, mm (0) 4 (00),7 mm () (), mm (0) (0) (00) 0 (0) (00) Pipe O.D..7 (0,). (7,0) (7,).0 (,9) 4.0 (4,).0 (,7). (4,).0 (,). (,). (9,) 0.7 (7,).7 (,9) Cover Gasket Part Number Clapper Facing Part Number Clapper Assembly Part Number Americas Only EMEA/APAC Americas Only EMEA/APAC Americas Only EMEA/APAC EPDM 900EPDM 97700A EPDME 90EPDM 970A EPDME 90EPDM EPDME 900EPDM 970A EPDME 9040EPDM A EPDME 900EPDM EPDME 900EPDM 970A EPDME 900EPDM EPDME 900EPDM 9740A EPDME 900EPDM 9790A EPDM 900EPDM 97900A EPDM 90EPDM A TABLE B MODEL CV-F GROOVED END SWING CHECK VALVES REPLACEMENT VALVE PARTS PART NUMBER SELECTION

5 COVER INLET OUTLET INLET VERTICAL ORIENTATION COVER FLOW FLOW HORIZONTAL ORIENTATION OUTLET FIGURE MODEL CV-F GROOVED END SWING CHECK VALVES PROPER ORIENTATION Limited Warranty For warranty terms and conditions, visit Ordering Procedure TFP0 Page of Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Model CV-F Check Valve Specify: Model CV-F Grooved End Swing Check Valve, size (specify), P/N (specify per Table A) Replacement Valve Parts Refer to Figure to identify Parts. Cover Gasket Specify: Model CV-F Grooved End Swing Check Valve, Cover Gasket, size (specify), P/N (specify per Table B) Clapper Facing Specify: Model CV-F Grooved End Swing Check Valve, Clapper Seal Facing, EPDM Grade E, size (specify), P/N (specify per Table B) Clapper Assembly Includes items,, -4, and 7-9. Specify: Model CV-F Grooved End Swing Check Valve, Clapper Assembly, size (specify), P/N (specify per Table B)

6 TFP0 Page of GLOBAL HEADQUARTERS 400 Pennbrook Parkway, Lansdale, PA 944 Telephone Copyright 0 Tyco Fire Products, LP. All rights reserved.

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950 Technical Services 00--9 +-0--0 www.tyco-fire.com Model CV-FR Riser Check Valves to Inch (DN0 to DN00) General Description The TYCO Model CV-FR Riser Check Valve is a compact and rugged swingtype unit

More information

Technical Data. Sizes 2 in. (DN50) to 16 in. (DN400) Approvals UL and ULC Listed FM Approved

Technical Data. Sizes 2 in. (DN50) to 16 in. (DN400) Approvals UL and ULC Listed FM Approved Worldwide Contacts www.tyco-fire.com Model TJR Resilient-Seated Gate Valves Outside Screw and Yoke General Description TYCO Model TJR Resilient-Seated Gate Valves are used in Fire Protection Systems for

More information

Care and Maintenance

Care and Maintenance Worldwide Contacts www.tycofire.com GRINNELL GFIRE Figure 71 Flange Adapters 2 to 12 Inch (DN50 to DN300) General Description The GRINNELL GFIRE Figure 71 Flange Adapters allow a direct transition from

More information

Worldwide Contacts. Technical Data

Worldwide Contacts.  Technical Data Worldwide Contacts www.tyco-fire.com Model BFV- Butterfly Valve Wafer Style General Description The TYCO Model BFV- Wafer Style Butterfly Valves are indicating type valves designed for use in fire protection

More information

Technical Data. Sizes: ANSI Inches (DN) 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250)

Technical Data. Sizes: ANSI Inches (DN) 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250) Worldwide Contacts www.tyco-fire.com Model BFV-/BFV-C Butterfly Grooved End General Description The TYCO Models BFV- (Normally Open) and BFV-C (Normally Closed) Grooved End Butterfly s are indicating type

More information

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, Dual-Purpose Water Supply, Domestic and Fire Sprinkler System General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, Dual-Purpose Water Supply, Domestic and Fire Sprinkler System General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, Dual-Purpose Water Supply, Domestic and Fire Sprinkler System General Description The TYCO RAPID RESPONSE Model

More information

Technical Data. Sizes 2 12 Inch (DN50 DN300)

Technical Data. Sizes 2 12 Inch (DN50 DN300) Worldwide Contacts www.tyco-fire.com Model BFV- Butterfly Valve Wafer Style General Description The TYCO Model BFV- Wafer Style Butterfly Valves are indicating type valves designed for use in fire protection

More information

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations Worldwide Contacts www.tyco-fire.com AQUAMIST Mist Control Center (MCC) Pump Skid Unit General Description Center (MCC) Pump Skid Unit is a preassembled, self-contained, control center for Ultra Low Flow

More information

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts Worldwide Contacts www.tyco-fire.com AQUAMIST Mist Control Center (MCC) Pump Skid Unit General Description Center (MCC) Pump Skid Unit is a preassembled, self-contained, control center for the Ultra Low

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry Type Pendent Sprinklers (TY7229)

More information

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description Worldwide Contacts www.tyco-fire.com Model AV--00 Alarm Valve With and Without Model RC- Retard Chamber European Conformity Valve Trim General Description The TYCO Model AV--00 Alarm Valves DN, DN0, DN0,

More information

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations Worldwide Contacts www.tyco-fire.com AQUAMIST Mist Control Center (MCC) Pump Skid Unit General Description Center (MCC) Pump Skid Unit is a preassembled, self-contained, control center for Ultra Low Flow

More information

Technical Data. Outlet Connections (Ref. Figure 2) ISO 7-Rc 3/8 1/2 inch NPT 3/4 inch NPT. Nominal Assembly Lengths Ref. Table A

Technical Data. Outlet Connections (Ref. Figure 2) ISO 7-Rc 3/8 1/2 inch NPT 3/4 inch NPT. Nominal Assembly Lengths Ref. Table A Worldwide Contacts www.tyco-fire.com FASTFLEX Model YN25, YB25, and YB28 Flexible Hose Europe, Middle East, and Africa Only General Description The TYCO FASTFLEX Flexible Hose is a unique sprinkler drop

More information

Sprinkler Identification Number (SIN)

Sprinkler Identification Number (SIN) Worldwide Contacts www.tyco-fire.com Series DS-3 Dry-Type Sprinklers 11.2K Horizontal Sidewall Standard Response, Extended Coverage General Description TYCO Series DS-3 Dry-Type Sprinklers, 11.2K Horizontal

More information

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description Worldwide Contacts www.tyco-fire.com Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description TYCO Series DS-1 Stainless

More information

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar) Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description Worldwide Contacts www.tyco-fire.com Series TY-FRL 5.6 and 8.0 K-factor Extended Horizontal Sidewall s Quick & Standard (Light Hazard) General Description The Series TY-FRL, 5.6, and 8.0 K-factor, Extended

More information

Worldwide Contacts.

Worldwide Contacts. Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description Worldwide Contacts www.tyco-fire.com Model ESFR-17 16.8 K-factor Dry Type Pendent s Early Suppression, Fast Response General Description TYCO Model ESFR-17 Dry Type Pendent s are Early Suppression, Fast

More information

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Worldwide Contacts www.tyco-fire.com Series EC-8 8.0 K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Pendent Sprinklers are decorative glass bulb sprinklers

More information

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description TYCO Series EC-11 and EC-14 Extended

More information

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description. Technical Services: Tel: (00) 31-9312 / Fax: (00) 91-5500 Customer Service/Sales: Tel: (1) 50-5000 / (00) 55-523 Fax: (1) 50-5010 / (00) -1295 Model A Pipe Line Strainer 3,,, & 10 Inch (DN0, DN100,, DN200

More information

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description Worldwide Contacts www.tyco-fire.com Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description The Series TY-B, 5.6 and 8.0 K-factor Upright

More information

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems General Description The TYCO RAPID RESPONSE Series

More information

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description The TYCO RAPID RESPONSE Series LFII

More information

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry

More information

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types: Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Preaction Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window

More information

RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems General Description The TYCO RAPID RESPONSE Series

More information

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,

More information

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential 4.9 K-factor Pendent Sprinkler Wet Pipe and Dry Pipe Systems General Description TYCO RAPID RESPONSE Series Recessed Pendent

More information

Submittal Packages Detailed with Items and Reviewers

Submittal Packages Detailed with Items and Reviewers Submittal Packages Detailed with Items and Reviewers Tenochca Upgrades Project # 2351 San Diego State University 5500 Campanile Drive San Diego, CA 92182 Tel: 619-594-3740 Fax: 0050-211000-0 Fire Protection

More information

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential 4.9 K-factor Pendent Sprinkler Wet Pipe and Dry Pipe Systems General Description TYCO RAPID RESPONSE Series Recessed Pendent

More information

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN) Worldwide Contacts www.tyco-fire.com Model ESFR-25 25.2 K-factor Pendent Sprinkler Early Suppression, Fast Response General Description TYCO Model ESFR-25 Pendent Sprinklers are Early Suppression, Fast

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description LFII Residential Horizontal Sidewall

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2524)

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2234) are

More information

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

Technical Data. Installation

Technical Data. Installation Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems Customer Service/Sales: Tel: (15) 6-0700 / (800) 5-651

More information

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage Worldwide Contacts www.tyco-fire.com Series 2.8,.2, 5.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description IMPORTANT Always refer to Technical

More information

Sprinkler Identification Numbers. TY3351 Horizontal TY3451 Vertical. Technical Data

Sprinkler Identification Numbers. TY3351 Horizontal TY3451 Vertical. Technical Data Worldwide Contacts www.tyco-fire.com Series TY-B 5.6 K-factor Standard Response, Standard Coverage General Description described in this data sheet are standard response - standard coverage, decorative

More information

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary Sprin klers, Standard

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems General Description LFII Residential Flush Horizontal Sidewall

More information

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series TY-B 2.8,.6, 8.0 K-factor Upright, Pendent, Recessed Pendent Sprinklers Stard Response, Stard Coverage General Description TYCO Series TY-B, 2.8,.6, 8.0 K-factor,

More information

Worldwide Contacts.

Worldwide Contacts. Worldwide Contacts www.tyco-fire.com Series Multiple Jet Controls DN20, DN25, DN40, and DN50, 2 bar BSPT Inlet & Outlets Threads General Description The TYCO Series Multiple Jet Controls are control valves

More information

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series TY-B 5.6 K-factor Standard Response, Standard Coverage General Description described in this technical data sheet are standard response, standard coverage decorative

More information

ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

ESCUTCHEON PLATE SEATING 3/4 NPT SURFACE. 1-1/2 (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 6.9 K-factor, Pendent/Recessed Pendent/Concealed, NFPA 13 Optimized Wet Pipe Systems General Description The TYCO

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 K-factor Horizontal Quick Response, Standard Coverage General Description IMPORTANT Always refer to Technical Data Sheet TFP700 for the INSTALLER

More information

Series TY-FRB 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 K-factor Horizontal Quick Response, Standard Coverage General Description described in this data sheet are quick response -standard coverage, decorative

More information

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description The TYCO Series TY-FRL,

More information

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series ELO-231 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description Response, Standard Coverage Upright and Pendent

More information

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types: Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Preaction Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed

More information

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS * Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Quick Response General Description Intermediate Level Sprinklers are automatic

More information

Technical Data. to the physical properties of

Technical Data. to the physical properties of Worldwide ontacts www.tyco-fire.com G-FIRE Figure 579 d Rigid oupling 2 Inch to 8 Inch (N50 to N200) General escription he GRINNELL G-FIRE Figure 579 d Rigid ouplings provide a rigid joint by firmly gripping

More information

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description Worldwide Contacts www.tyco-fire.com 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description TYCO 5.6K Institutional Pendent and

More information

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco. TN-25 Tunnel Fire Protection System Safer. Smarter. Tyco. Expert Fire Protection for Tunnels Tyco provides a complete fire protection solution to protect the infrastructure of tunnels. Whether it is rail,

More information

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

WRENCH FLATS 1/2 NPT. 7/16 (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems General Description The TYCO RAPID RESPONSE Series

More information

FIGURE 1 MODEL RFIII ECLH CONCEALED HSW SPRINKLER ASSEMBLY AND FEATURES. 5/16" (7,9 mm) MIN. 9/16" (14,3 mm) MAX.

FIGURE 1 MODEL RFIII ECLH CONCEALED HSW SPRINKLER ASSEMBLY AND FEATURES. 5/16 (7,9 mm) MIN. 9/16 (14,3 mm) MAX. Worldwide Contacts www.tyco-fire.com Model RFIII 8.0 K-factor Flat Plate Concealed Horizontal Extended Coverage Quick Response Light Hazard Sidewall Sprinkler General Description Response Sprinkler is

More information

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description The TYCO VIZOR Electronic Dry Pipe Accelerator (EDPA) is

More information

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Worldwide Contacts www.tyco-fire.com Series EC-8 8.0 K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Pendent Sprinklers are decorative glass bulb sprinklers

More information

Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description

Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description Worldwide Contacts www.tyco-fire.com Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description The Model TY-FRFS, TY-FS Special, and

More information

Technical Data. to the physical properties of

Technical Data. to the physical properties of Worldwide ontacts www.tyco-fire.com G-FIRE Figure 579 d Rigid oupling 2 Inch to 8 Inch (N50 to N200) General escription he GRINNELL G-FIRE Figure 579 d Rigid ouplings provide a rigid joint by firmly gripping

More information

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description The TYCO RAPID RESPONSE

More information

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description The TYCO RAPID RESPONSE Series LFII

More information

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

WRENCH FLATS NPT 1/2 7/16 (11,1 mm) NOMINAL MAKE-IN. 1-1/2 (38,1 mm) 2-3/16 (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN. Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and

More information

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

WRENCH FLATS 1/2 NPT. 7/16 (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.4 K-factor Horizontal Sidewall Wet Pipe Systems General Description LFII Residential Horizontal Sidewall Sprinklers

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2235)

More information

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS Worldwide Contacts www.tyco-fire.com Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description The Series TY-B, 5.6 and 8.0 K-factor Upright

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2235)

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description Extended Coverage and Pendent Sprinklers

More information

Sprinkler Identification Number. Page 1 of 6 AUGUST 2018 TFP288. Worldwide Contacts.

Sprinkler Identification Number. Page 1 of 6 AUGUST 2018 TFP288. Worldwide Contacts. Worldwide Contacts www.tyco-fire.com Model EC-HS 80 K-factor, Quick Response Extended Coverage Horizontal Sidewall Sprinklers Installations per VdS CEA 400, Annex E, LH/OH General Description The Model

More information

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16 (42,7 mm) CROSS SECTION Worldwide Contacts www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K and Pendent Extended Coverage Light and Ordinary Hazard General Description Extended Coverage and Pendent Sprinklers

More information

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description TYCO Series DS-1 Dry-Type Sprinklers,

More information

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are

More information

TECHNICAL DATA. Wet 26a. February 22, 2009

TECHNICAL DATA. Wet 26a. February 22, 2009 February 22, 2009 Wet 26a 1. DESCRIPTION The Viking Alarm Check Valve serves as a check valve by trapping pressurized water above the clapper and preventing reverse flow from sprinkler piping. The valve

More information

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series.8,.,.6, 8.0 K-Factor Upright,, Sprinklers Quick Response, Stard Coverage General Description The TYCO Series.8,.,.6, 8.0 K-factor Upright,, Sprinklers described

More information

G3/8" DIN ISO 228 THREAD SHOULDER AND DUST CAP MATING SURFACE. STYLE H ESCUTCHEON (SEPARATELY ORDERED) 85 mm DIA. (3-3/8")

G3/8 DIN ISO 228 THREAD SHOULDER AND DUST CAP MATING SURFACE. STYLE H ESCUTCHEON (SEPARATELY ORDERED) 85 mm DIA. (3-3/8) Worldwide Contacts www.tyco-fire.com Model FSC 80 K-factor Flush Sprinkler, Pendent Quick Response, Standard Coverage General Description The TYCO Model FSC 80 K-factor Flush Sprinkler is a quick response

More information

Safer. Smarter. Tyco. I wish I had a flexible FM Approved Water Mist Solution to fit any industrial oil cooker.

Safer. Smarter. Tyco. I wish I had a flexible FM Approved Water Mist Solution to fit any industrial oil cooker. I wish I had a flexible FM Approved Water Mist Solution to fit any industrial oil cooker. I wish I could protect my industrial fryer installation with a fire protection solution that helps minimize collateral

More information

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series TY-B.6 K-factor Standard Response, Standard Coverage General Description The TYCO Series TY-B,.6 K-factor, described in this technical data sheet are standard

More information

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description TYCO 5.6K Institutional Pendent and Horizontal Sidewall (HSW) Sprinklers

More information

Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description

Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description Worldwide Contacts www.tyco-fire.com Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description The Model TY-FRFS, TY-FS Special, and

More information

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description. Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description The TYCO RAPID RESPONSE Model RCP-1 Residential

More information

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts.

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts. Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 6.9 K-factor, Pendent/Recessed Pendent/Concealed, NFPA 13 Optimized Wet Pipe Systems General Description The TYCO

More information

Solutions at every turn.

Solutions at every turn. Solutions at every turn. GROOVED PIPING SYSTEMS HVAC INDUSTRY www.grinnell.com HVAC GROOVED PIPING SYSTEMS PROS TURN TO GRINNELL PRODUCTS GRINNELL Mechanical Products, a premier brand of Tyco International,

More information

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Series RFII 5.6 K-factor Royal Flush II Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General Description The

More information

* Temperature rating is FIGURE K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS

* Temperature rating is FIGURE K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS Worldwide Contacts www.tyco-fire.com Series TY-FRB.6 K-factor Horizontal Quick Response, Standard Coverage General Description The Series TY-FRB,.6 K-factor, Horizontal described in this data sheet are

More information

Series 759 FireLock Alarm Check Valve

Series 759 FireLock Alarm Check Valve R IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS 10.70 Series 759 FireLock Alarm Check Valve Grooved Grooved PRODUCT DESCRIPTION U L FM U L C See Victaulic publication 10.01 for details. The Victaulic

More information

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) SECTIONS General Description.... 1 Warnings.... 2 Technical

More information

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage General Description

More information

Simple On The Outside...

Simple On The Outside... Safer. Smarter. Tyco. Simple On The Outside... ...Effective On The Inside Tyco Fire Protection Products is the leading manufacturer and distributor of water-based fire suppression systems and components,

More information

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

More information

Discontinued Product

Discontinued Product SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS The Victaulic Series 759 alarm check valve works as a check valve by preventing the reverse flow of water from the system piping to the water supply. The valve

More information

UL/FM Fire Protection Products. Reliable fire protection products for your commercial, industrial, or institutional property.

UL/FM Fire Protection Products. Reliable fire protection products for your commercial, industrial, or institutional property. UL/FM Fire Protection Products Reliable fire protection products for your commercial, industrial, or institutional property. Reliable UL/FM Fire Protection Products Markets Power Institutional Company

More information

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs) Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Series DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description TYCO Series

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2284) are decorative, fast response, fusible solder sprinklers

More information

as required for residential sprinklers intended for use in dry pipe systems.

as required for residential sprinklers intended for use in dry pipe systems. Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Residential Dry Pipe System General Description The TYCO RAPID RESPONSE Residential Dry Pipe System provides a normally dry system for areas subject

More information

UL/FM Fire Protection Products Setting the Standard

UL/FM Fire Protection Products Setting the Standard UL/FM Fire Protection Products Setting the Standard Markets Power Institutional Company Overview Mueller Co. is a leader in high-quality commercial and institutional fire protection products, offering

More information

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description The Tyco ILLUSION,

More information

UL/FM Fire Protection Products

UL/FM Fire Protection Products UL/FM Fire Protection Products Setting the Standard Markets Power Industrial Company Overview Since 1857, the Mueller name has been associated with dependable Water and Gas distribution products around

More information