Effective Date: October 2016 Void After: October Product: Air Admittance Valves File No. C-3803

Size: px
Start display at page:

Download "Effective Date: October 2016 Void After: October Product: Air Admittance Valves File No. C-3803"

Transcription

1 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the requirements of applicable codes and standards. This activity is coupled with periodic surveillance of the supplier's factory and warehouses as well as the assessment of the supplier's Quality Assurance System. This listing is subject to the conditions set forth in the characteristics below and is not to be construed as any recommendation, assurance or guarantee by IAPMO Research and Testing, Inc. of the product acceptance by Authorities Having Jurisdiction. The most updated information on this Certificate of Listing is available online at pld.iapmo.org Effective Date: October 2016 Void After: October 2017 Product: Air Admittance Valves File No. C-3803 Issued To: IPS Corporation 202 Industrial Park Lane Collierville, TN Identification: Manufacturer's name or trademark, model designation, and the C/IAPMO triangular certification mark. Characteristics: Air admittance valves designed to permit air to enter the drainage system when the pressure within the system drops below atmospheric pressure. To be installed in accordance with the manufacturer's instructions. The device shall be installed in an accessible location which shall permit free (unobstructed) movement of air into the device. The device shall be insalled in a vertical and upright orientation not to exceed 15 degrees from the vertical plumb. Products listed on this certificate have been tested by an IAPMO R&T recognized laboratory. This recognition has been granted based upon the laboratory's compliance to the applicable requirements of ISO/IEC Products are in compliance with the following standard(s): ASSE This listing period is based upon the last date of the month indicated on the Effective Date and Void After Date shown above. Any change in material, manufacturing process, marking or design without having first obtained the approval of the Product Certification Committee, or any evidence of non-compliance with applicable codes and standards or of inferior workmanship, may be deemed sufficient cause for revocation of this listing. Production of or reference to this form for advertising purposes may be made only by specific written permission of IAPMO Research and Testing, Inc. Any alteration of this certificate could be grounds for revocation of the listing. This document shall be reproduced in its entirety.

2 Page 2 Void After: October 2017 Product: Air Admittance Valves File No. C-3803 Issued To: Ips Corporation MODELS: Note: Model number on the product is an internal identification number for IPS in reference to the packaging size or bulk quantity. Studor Maxi-Vent Mini-Vent Redi-Vent Tec-Vent

3 Page 3 Void After: October 2017 Product: Air Admittance Valves File No. C-3803 Issued To: Ips Corporation ADDITIONAL COMPANY INFO: Hajoca Corporation Brigade TM / Mainline TM Model No. BR10464/ML10464 BR10465/ML10465 BR10466/ML10466 BR10469/ML10469 BR10470/ML10470 Description Maxi Vent PVC Mini Vent PVC adaptor Mini Vent ABS adaptor Redi Vent PVC adaptor Redi Vent ABS adaptor

4 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the requirements of applicable codes and standards. This activity is coupled with periodic surveillance of the supplier's factory and warehouses as well as the assessment of the supplier's Quality Assurance System. This listing is subject to the conditions set forth in the characteristics below and is not to be construed as any recommendation, assurance or guarantee by IAPMO Research and Testing, Inc. of the product acceptance by Authorities Having Jurisdiction. The most updated information on this Certificate of Listing is available online at pld.iapmo.org Effective Date: March 2016 Void After: March 2017 Product: STACK AIR ADMITTANCE VALVES File No. C-7729 Issued To: Ips Corporation 202 Industrial Park Lane Collierville, TN Identification: Manufacturer's name or trademark, model designation, and the C/IAPMO triangular certification mark. Characteristics: Air admittance valves designed to permit air to enter the drainage system when the pressure within the system drops below atmospheric pressure. To be installed in accordance with the manufacturer's instructions. Products listed on this certificate have been tested by an IAPMO R&T recognized laboratory. This recognition has been granted based upon the laboratory's compliance to the applicable requirements of ISO/IEC Products are in compliance with the following standard(s): ASSE This listing period is based upon the last date of the month indicated on the Effective Date and Void After Date shown above. Any change in material, manufacturing process, marking or design without having first obtained the approval of the Product Certification Committee, or any evidence of non-compliance with applicable codes and standards or of inferior workmanship, may be deemed sufficient cause for revocation of this listing. Production of or reference to this form for advertising purposes may be made only by specific written permission of IAPMO Research and Testing, Inc. Any alteration of this certificate could be grounds for revocation of the listing. This document shall be reproduced in its entirety.

5 Page 2 Void After: March 2017 Product: STACK AIR ADMITTANCE VALVES File No. C-7729 Issued To: Ips Corporation MODELS: Maxi-Vent Mini-Vent Redi-Vent Tec-Vent

6 Page 3 Void After: March 2017 Product: STACK AIR ADMITTANCE VALVES File No. C-7729 Issued To: Ips Corporation ADDITIONAL COMPANY INFO: Hajoca Corporation BR10469 / ML10469 BR10470 / ML10470 BR10465 / ML10465 BR10466 / ML10466 BR10464 / ML10464 (Redi Vent PVC) (Redi Vent ABS) (Mini Vent PVC) (Mini Vent ABS) (Maxi Vent PVC)

7 ICC-ES Report PMG-1025 Reissued 02/2016 This report is subject to renewal 02/2017 EVALUATION SUBJECT: STUDOR AIR ADMITTANCE VALVES DIVISION: PLUMBING SECTION: AIR ADMITTANCE VALVE Report Holder: STUDOR, INC., DIVISION OF IPS CORPORATION 500 DISTRIBUTION PARKWAY COLLIERVILLE, TN 38017

8 ICC-ES PMG Listing PMG-1025 Effective Date: February 2016 This listing is subject to re-examination in one year. (800) (562) A Subsidiary of the International Code Council CSI: DIVISION: PLUMBING Section: Air Admittance Valve Product certification system: The ICC-ES product certification system includes testing samples taken from the market or supplier s stock, or a combination of both, to verify compliance with applicable codes and standards. The system also involves factory inspections, and assessment and surveillance of the supplier s quality system. Product: Studor Air Admittance Valves: Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent, Trap-Vent Listee: Studor, Inc., Division of IPS Corporation 500 Distribution Parkway Collierville, Tennessee Additional listees: Hajoca (Mainline brand) 1942 Airport Road Monroe, NC Compliance with the following codes: 2015, 2012 and 2009 International Plumbing Code (IPC) 2015, 2012 and 2009 International Residential Code (IRC) 2012 and 2009 National Standard Plumbing Code (NSPC)* *National Standard Plumbing Code is a copyrighted publication of Plumbing-Heating-Cooling-National Association Compliance with the following standards: ASSE , Performance Requirements for Stack Air Admittance Valves for Sanitary Drainage Systems ASSE , Performance Requirements for Individual and Branch Type Air Admittance Valves for Sanitary Drainage Systems- Fixture and Branch Devices NSF Standard , Plastic Piping System Components and Related Materials Listings are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the listing or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this listing, or as to any product covered by the listing. Copyright 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 6

9 PMG-1025 Most Widely Accepted and Trusted Page 2 of 6 Identification: Installation: Models: Conditions of listing: The Studor Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent must be identified by molded lettering on the lid, indicating the name of the product, the manufacturer s name, manufacturing location (Ellington, Connecticut), and the ICC-ES PMG listing mark. Studor Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent must be installed in accordance with the manufacturer s installation instructions and the conditions of this listing. The Studor Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent are air admittance valves conforming to ASSE 1050, ASSE 1051 and NSF 14. The Mini-Vent and Redi-Vent are designed for pipe sizes of 1 1 / 2 inches through 2 inches (38 mm through 51 mm). The Maxi-Vent is designed for pipe sizes of 3 inches through 4 inches (76 mm through 102 mm). The Tec-Vent is designed for 1 1 / 2 inch pipe (38mm). The Trap-Vent is designed for 1 ¼ inches through 1 ½ inches pipe. The Studor air admittance valves are used as a vent termination for individual vents, common vents, circuit vents and branch vents. Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent are also permitted to be used as the vent termination for a vent stack or stack vent with six branch intervals or less. 1. The Studor Mini-Vent and Redi-Vent are supplied with a connector which enables the valve to be solvent cemented onto 1 1 / 2 -inch- or 2-inch-diameter (38 mm or 51 mm) pipes or screwed into 1 1 / 2 - inch (38 mm) I.P.S. threads. The Tec-Vent has 1 1 / 2 (38mm) I.P.S. threads and does not come with a connector. 2. The Studor Maxi-Vent is supplied with a synthetic rubber connector which enables the valve to be push fitted into a 4-inch-diameter (102 mm) PVC, cast iron or ABS pipe. It may also be installed on a 3-inch-diameter (76 mm) PVC, cast iron or ABS pipe in accordance with the manufacturer s instructions. 3. The use of Studor Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent is limited to systems subject to siphonage conditions and a maximum pressure condition of 1-inch (25 mm) water column. 4. Each Studor Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent must be located a minimum of 4 inches (102 mm) above the horizontal branch drain or fixture drain being vented when providing trap seal protection for fixtures or branches. When serving as vent terminals for stack vents or vent stacks, they must be a minimum of 6 inches (152 mm) above the flood level rim of the highest fixture served. 5. Each Studor Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent must be accessible for replacement if required. 6. The Studor Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent must be located to allow adequate air to enter the valve. When the products are located in a wall space or attic space, ventilation openings must be provided into the space. When in an attic space, the vents must be located a minimum of 6 inches (152 mm) above any ceiling insulation. 7. The air-admittance valve must be installed in the vertical upright position. The maximum offset from the vertical upright position must not exceed 15 degrees. 8. Each vent must connect to the drain with a vertical connection to maintain an unblocked opening in the piping to the air admittance valves.

10 PMG-1025 Most Widely Accepted and Trusted Page 3 of 6 9. A minimum of one vent stack or stack vent must extend outdoors to the open air for every building plumbing drainage system unless specifically engineered. 10. The Studor Mini-Vent, Maxi-Vent, Redi-Vent, Tec-Vent and Trap-Vent are permitted to be installed as the vent termination for a vent stack or stack vent with six branch intervals or less or as a branch vent terminal for fixtures on the same floor. 11. The air admittance valves must be installed after the drainage system has been pressure tested. 12. When a horizontal branch connects to a stack more than four branch intervals from the top of the stack, a relief vent must be provided. The relief vent must be located between the connection of the branch to the stack and the first fixture connecting to the branch. The relief vent may also serve as a vent for a single fixture. The relief vent must connect to the vent stack or stack vent and extend to the open air outside the building. 13. The air admittance valves shall not be installed in non-neutralized special waster systems as described in chapter 8 of IPC. 14. The air admittance valves shall not be located in spaces utilized as supply or return air plenums. 15. The air admittance valves without an engineered design (See Figure 11) shall not be utilized to vent sumps or tanks of any type. 16. The Studor Mini-Vent, Maxi-Vent, Redi-Vent and Tec-Vent are produced in Ellington, Connecticut; the Studor Trap-Vent is produced in Darul Eshan, Malaysia under annual surveillance audits by ICC-ES. TABLE 1 AIR ADMITTANCE VALVE MODELS NUMBERS OF STUDOR/IPS NAME ONLY DESCRIPTION Mini Vent w/ PVC adaptor Mini Vent w/ ABS adaptor Maxi Vent USA PVC Redi Vent - w/ PVC adaptor Redi Vent - w/ ABS adaptor Tec Vent Trap Vent TABLE 2 AIR ADMITTANCE VALVE CROSS REFERENCE OF MODEL NUMBERS, STUDOR AND HAJOCA STUDOR/IPS PART NO. DESCRIPTION HAJOCA CORP. (BRIDAGE / MAINLINE BRAND) MODEL NO Maxi Vent USA PVC (25 pack) BR10464 / ML X-Pack Mini Vent-PVC (40 pack) BR10465 / ML X-Pack Mini Vent-ABS (40 pack) BR10466 / ML Redi Vent-PVC (120 pack) BR10469 / ML Redi Vent-ABS (120 pack) BR10470 / ML10470 The following diagrams are examples of acceptable designs using the Mini-Vent, Maxi-Vent, Redi-Vent and Tec-Vent

11 PMG-1025 Most Widely Accepted and Trusted Page 4 of 6 TRAP-VENT TRAP-VENT

12 PMG-1025 Most Widely Accepted and Trusted Page 5 of 6

13 PMG-1025 Most Widely Accepted and Trusted Page 6 of 6 Figure 11

14 0 ICC-ES Report ICC-ES (800) (562) Most Widely Accepted and Trusted PMG-1099 Valid: 10/15 to 10/16 DIVISION: PLUMBING SECTION: AIR ADMITTANCE VALVES REPORT HOLDER: IPS CORPORATION 500 DISTRIBUTION PARKWAY COLLIERVILLE, TENNESSEE EVALUATION SUBJECT: STUDOR AIR ADMITTANCE VALVE BOX Look for the trusted marks of Conformity! 2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2015

15 ICC-ES PMG Listing PMG-1099 Effective Date: October 2015 This listing is subject to re-examination in one year. (800) (562) A Subsidiary of the International Code Council CSI: DIVISION: PLUMBING Section: Air Admittance Valves Product certification system: The ICC-ES product certification system includes testing samples taken from the market or supplier s stock, or a combination of both, to verify compliance with applicable codes and standards. The system also involves factory inspections, and assessment and surveillance of the supplier s quality system. Product: Listee: Studor Air Admittance Valve Box IPS Corporation 500 Distribution Parkway Collierville, Tennessee Compliance with the following codes: 2015, 2012 and 2009 International Plumbing Code (IPC) 2015, 2012 and 2009 International Residential Code (IRC) 2015, 2012 and 2009 Uniform Plumbing Code (IAPMO UPC)* *Uniform Plumbing Code is a copyrighted publication of the International Association of Plumbing and Mechanical Officials Compliance with the following standards: Identification: Installation: Models: IAPMO PS a Material and Property Standard for Metallic and Plastic Utility Boxes The Studor Air Admittance Valve Box described in this listing must be permanently and legibly marked with manufacturer s name or trade mark and the ICC-ES PMG listing mark. Studor Air Admittance Valve Box may vary in dimensions of height, width and depth. Installation must be in accordance with manufacturer s published installation instructions and correct plumbing practices contained in the current edition of the International Plumbing Code, Uniform Plumbing Code and International Residential Code. Studor Air Admittance Valve Box Model Series is a utility box manufactured from a High Impact Polystyrene that meets the requirements of IAPMO Standard PS-54. Listings are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the listing or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this listing, or as to any product covered by the listing. Copyright 2015 Page 1 of 2

16 PMG-1099 Most Widely Accepted and Trusted Page 2 of 2 Conditions of Listing: 1. Studor Air Admittance Valve Box recognized in the listing must be installed in accordance with the manufacturer s published installation instructions and the applicable codes. 2. Studor Air Admittance Valve Box is manufactured by IPS Corporation in Collierville, Tennessee under a quality control program with annual surveillance inspections by ICC-ES.

17 Report prepared for: Spec Direct (Free User) on 11/4/ :57:25 AM LISTING INFORMATION OF Studor Air Admittance Valves Models Mini-Vent, Maxi-Vent & REDI-VENT SPEC ID: IPS Corporation (TN) 202 Industrial Park Lane Collierville, TN This report is for the exclusive use of Intertek s Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. IPS Corporation (TN) Rev: Aug :24AM Uncontrolled Copy Page 1 of 2

18 Report prepared for: Spec Direct (Free User) on 11/4/ :57:25 AM Product Type: Fitting - Air Admittance Valve Model Name: Mini-Vent Sizes: 1-1/4" (32 mm), 1-1/2" (38 mm) and 2" (50 mm). Model Name: Maxi-Vent Sizes: 3" (75 mm) and 4" (100 mm). Model Name: REDI-VENT Sizes: 1-1/2" and 2". EVALUATED TO THE FOLLOWING: ASSE 1050 Performance Requirements for AIr Admittance Valves for Plumbing DWV Systems - Stack type Devices ASSE 1051 Air Admittance Valves for Plumbing Drainage Systems - Fixture and Branch Devices IDENTIFICATION: All required marking must be permanent, legible and visible after manufacture. Markings consist of the WHI Certification Mark and the Markings required by the relevant standard(s). Attribute Value Criteria ASSE 1051 (2002) Criteria ASSE 1050 (1991) CSI Code Plumbing Fixtures Intertek Services Certification Listed or Inspected LISTED Listing Section PLUMBING FITTINGS & ACCESSORIES Report Number ; /99 Edition 4 Spec ID Test Original Issue Date September 3, 1999 IPS Corporation (TN) Rev: Aug :24AM Uncontrolled Copy Page 2 of 2

19 11/4/2016 Listing Category Search Page NSF International The Public Health and Safety Organization NSF Product and Service Listings These NSF Official Listings are current as of Friday, November 04, 2016 at 12:15 a.m. Eastern Time. Please contact NSF International to confirm the status of any Listing, report errors, or make suggestions. Alert: NSF is concerned about fraudulent downloading and manipulation of website text. Always confirm this information by clicking on the below link for the most accurate information: NSF/ANSI 14 Plastics Piping System Components and Related Materials Click here for a list of End Use Code Designations. Click on Product Standards or footnote in blue to view the referenced document Studor Inc. 500 Distribution Parkway Collierville, TN United States Visit this company's website ( Facility : Somers, CT Drain, Waste, and Vent Pipe and Fittings Product Type Material Type Trade Name Product Standard Air Admittance Valve ABS MINI VENT ASSE /2", 2" Air Admittance Valve ABS MINI VENT ASSE /2", 2" Product is authorized to bear the cnsf and/or the cnsfus Mark. 1/3

20 11/4/2016 Listing Category Search Page NSF International Air Admittance Valve ABS MAXI VENT ASSE ", 4" Air Admittance Valve ABS MAXI VENT ASSE ", 4" Product is authorized to bear the cnsf and/or the cnsfus Mark. Air Admittance Valve ABS REDI VENT ASSE /2", 2" Air Admittance Valve ABS REDI VENT ASSE /2", 2" Product is authorized to bear the cnsf and/or the cnsfus Mark. Air Admittance Valve PC TEC VENT ASSE /2", 2" Air Admittance Valve PC TEC VENT ASSE /2", 2" Product is authorized to bear the cnsf and/or the cnsfus Mark. NOTE: Only products bearing the NSF Mark are Certified. Facility : Collierville, TN Drain, Waste, and Vent Pipe and Fittings Product Type Material Type Trade Name Product Standard Air Admittance Valve PP CHEM VENT ASSE /2", 2" Product is authorized to bear the cnsf and/or the cnsfus Mark. NOTE: Only products bearing the NSF Mark are Certified. 2/3

21 11/4/2016 Listing Category Search Page NSF International Facility : Shahalam, Selangor, Malaysia Drain, Waste, and Vent Pipe and Fittings Product Type Material Type Trade Name Product Standard Air Admittance Valve ABS Trap ASSE Vent* 1051 * Tailpieces and adapters were not tested or Listed by NSF International for this production location. Product can also come with white cladding, model Number of matching Manufacturers is 1 Number of matching Products is 10 Processing time was 0 seconds 3/3

22 11/4/2016 Listing Category Search Page NSF International The Public Health and Safety Organization NSF Product and Service Listings These NSF Official Listings are current as of Friday, November 04, 2016 at 12:15 a.m. Eastern Time. Please contact NSF International to confirm the status of any Listing, report errors, or make suggestions. Alert: NSF is concerned about fraudulent downloading and manipulation of website text. Always confirm this information by clicking on the below link for the most accurate information: MP Mechanical Plumbing Products Studor Inc. 500 Distribution Parkway Collierville, TN United States Visit this company's website ( Facility : Shahalam, Selangor, Malaysia Product Type Material Type Trade Product Name Standard Air Admittance Valve ABS Trap ASME Vent* A * Tailpieces and adapters were not tested or Listed by NSF International for this production location. Product can also come with white cladding, model Number of matching Manufacturers is 1 Number of matching Products is 1 Processing time was 0 seconds 1/1

Effective Date: May Rev. 1/31/2018- Void After: May Product: Plumbing Fixtures (Stainless Steel) File No. 6088

Effective Date: May Rev. 1/31/2018- Void After: May Product: Plumbing Fixtures (Stainless Steel) File No. 6088 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

EVALUATION SUBJECT: CAST IRON SOIL PIPE AND FITTINGS EXTRA HEAVY OR SERVICE

EVALUATION SUBJECT: CAST IRON SOIL PIPE AND FITTINGS EXTRA HEAVY OR SERVICE ICC-ES Report PMG-1083 Reissued 05/2017 This report is subject to renewal 05/2018 EVALUATION SUBJECT: CAST IRON SOIL PIPE AND FITTINGS EXTRA HEAVY OR SERVICE DIVISION: 22 00 00 PLUMBING SECTION: 22 13

More information

MAXI-VENT Air Admittance Valve

MAXI-VENT Air Admittance Valve MAXI-VENT Air Admittance Valve Manufacturer: Studor, Inc. Connec on Size: 3 or 4 Model #: MAXI VENT Item #: 20302 An air admittance valve shall be acceptable as a vent termination for any individual vent,

More information

Effective Date: June 2017 Void After: June Product: Plumbing Fixture Fittings File No. 4995

Effective Date: June 2017 Void After: June Product: Plumbing Fixture Fittings File No. 4995 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

EVALUATION SUBJECT: DIVISION: HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: HYDRONIC PIPING.

EVALUATION SUBJECT: DIVISION: HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: HYDRONIC PIPING. ICC-ES Report Reissued 08/2016 This report is subject to renewal 08/2017 EVALUATION SUBJECT: UNIPIPE PEX-AL-PEX DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: 23 21 13 HYDRONIC

More information

Effective Date: October Rev. 5/21/2018- Void After: October Product: Plumbing Fixture Fittings File No. 5840

Effective Date: October Rev. 5/21/2018- Void After: October Product: Plumbing Fixture Fittings File No. 5840 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

EVALUATION SUBJECT: FIRE SUPPRESSION RANGE HOOD DIVISION: MECHANICAL SECTION: COMMERCIAL-KITCHEN HOODS.

EVALUATION SUBJECT: FIRE SUPPRESSION RANGE HOOD DIVISION: MECHANICAL SECTION: COMMERCIAL-KITCHEN HOODS. ICC-ES Report PMG-1293 Reissued 12/2016 This report is subject to renewal 12/2017 EVALUATION SUBJECT: FIRE SUPPRESSION RANGE HOOD DIVISION: 23 00 00 MECHANICAL SECTION: 23 38 13 COMMERCIAL-KITCHEN HOODS

More information

Effective Date: January 2018 Void After: January Product: Plumbing Fixture Fittings File No. 6354

Effective Date: January 2018 Void After: January Product: Plumbing Fixture Fittings File No. 6354 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

Effective Date: December 2017 Void After: December Product: Outlet Boxes (Washing Machine) File No. 2150

Effective Date: December 2017 Void After: December Product: Outlet Boxes (Washing Machine) File No. 2150 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

Effective Date: September 2017 Void After: September 2018

Effective Date: September 2017 Void After: September 2018 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

EVALUATION SUBJECT: DIVISION: PLUMBING SECTION: FACILITY WATER DISTRIBUTION INSTRUMENTATION AND CONTROL FOR PLUMBING

EVALUATION SUBJECT: DIVISION: PLUMBING SECTION: FACILITY WATER DISTRIBUTION INSTRUMENTATION AND CONTROL FOR PLUMBING ICC-ES Report PMG-1360 Reissued 10/2017 This report is subject to renewal 10/2018 EVALUATION SUBJECT: LOW LEAD - PRESSURE REDUCING VALVE, TEMPERATURE ACTUATED MIXING VALVE, WATER TEMPERATURE LIMITING DEVICE,

More information

EVALUATION SUBJECT: PLUMBING SUPPLY FITTINGS DIVISION: PLUMBING SECTION: INSTRUMENTATION AND CONTROL FOR PLUMBING.

EVALUATION SUBJECT: PLUMBING SUPPLY FITTINGS DIVISION: PLUMBING SECTION: INSTRUMENTATION AND CONTROL FOR PLUMBING. ICC-ES Report PMG-1367 Reissued 02/2018 This report is subject to renewal 02/2019 EVALUATION SUBJECT: PLUMBING SUPPLY FITTINGS DIVISION: 22 00 00 PLUMBING SECTION: 22 09 00 INSTRUMENTATION AND CONTROL

More information

EVALUATION SUBJECT: DIVISION: PLUMBING SECTION: FACILITY WATER DISTRIBUTION INSTRUMENTATION AND CONTROL FOR PLUMBING

EVALUATION SUBJECT: DIVISION: PLUMBING SECTION: FACILITY WATER DISTRIBUTION INSTRUMENTATION AND CONTROL FOR PLUMBING ICC-ES Report PMG-1360 Reissued 01/18/2018 This report is subject to renewal 10/2018 EVALUATION SUBJECT: LOW LEAD - PRESSURE REDUCING VALVE, TEMPERATURE ACTUATED MIXING VALVE, WATER TEMPERATURE LIMITING

More information

EVALUATION SUBJECT: DIVISION: PLUMBING SECTION: FACILITY WATER DISTRIBUTION INSTRUMENTATION AND CONTROL FOR PLUMBING

EVALUATION SUBJECT: DIVISION: PLUMBING SECTION: FACILITY WATER DISTRIBUTION INSTRUMENTATION AND CONTROL FOR PLUMBING ICC-ES Report PMG-1360 Reissued 10/2018 This report is subject to renewal 10/2019 EVALUATION SUBJECT: LOW LEAD - PRESSURE REDUCING VALVE, TEMPERATURE ACTUATED MIXING VALVE, WATER TEMPERATURE LIMITING DEVICE,

More information

EVALUATION SUBJECT: PLUMBING SUPPLY FITTINGS

EVALUATION SUBJECT: PLUMBING SUPPLY FITTINGS ICC-ES Report PMG-1280 Reissued 10/2016 This report is subject to renewal 10/2017 EVALUATION SUBJECT: PLUMBING SUPPLY FITTINGS DIVISION: 22 00 00 PLUMBING SECTION: 22 40 00 PLUMBING FIXTURES SECTION: 22

More information

Effective Date: October Rev. 12/15/2017- Void After: October Product: Lead Free Plumbing Products File No. 6441

Effective Date: October Rev. 12/15/2017- Void After: October Product: Lead Free Plumbing Products File No. 6441 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

Effective Date: October 2018 Void After: October 2019

Effective Date: October 2018 Void After: October 2019 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

EVALUATION SUBJECT: DIVISION: PLUMBING SECTION: INSTRUMENTATION AND CONTROL FOR PLUMBING PLUMBING FIXTURES.

EVALUATION SUBJECT: DIVISION: PLUMBING SECTION: INSTRUMENTATION AND CONTROL FOR PLUMBING PLUMBING FIXTURES. ICC-ES Report PMG-1095 Reissued 08/2017 This report is subject to renewal 08/2018 EVALUATION SUBJECT: WATER CLOSET,VITREOUS CHINA WATER CLOSET WITH DUAL FLUSH DEVICE, VITREOUS CHINA LAVATORIES, VITREOUS

More information

EVALUATION SUBJECT: FIREPLACES DIVISION: SPECIALTIES SECTION: FIREPLACES AND STOVES. Report Holder:

EVALUATION SUBJECT: FIREPLACES DIVISION: SPECIALTIES SECTION: FIREPLACES AND STOVES. Report Holder: ICC-ES Report PMG-1290 Reissued 02/2017 This report is subject to renewal 02/2018 EVALUATION SUBJECT: FIREPLACES DIVISION: 10 00 00 SPECIALTIES SECTION: 10 30 13 FIREPLACES AND STOVES Report Holder: CF+D

More information

Effective Date: December Rev. 3/12/2018- Void After: December Product: Lead Free Plumbing Products File No. 6661

Effective Date: December Rev. 3/12/2018- Void After: December Product: Lead Free Plumbing Products File No. 6661 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

Fire Performance of Translucent Systems

Fire Performance of Translucent Systems Fire Performance of Translucent Systems ASTM E-108 Burning Brand Test on Quadwall Class A Approved Light Transmitting Plastics Fire Test Performance Meets Building Code Requirements: Self-Ignition ASTM

More information

EVALUATION SUBJECT: LOW LEAD - PLUMBING SUPPLY FITTINGS, FLEXIBLE WATER CONNECTOR

EVALUATION SUBJECT: LOW LEAD - PLUMBING SUPPLY FITTINGS, FLEXIBLE WATER CONNECTOR ICC-ES Report PMG-1368 Reissued 02/2018 This report is subject to renewal 02/2019 EVALUATION SUBJECT: LOW LEAD - PLUMBING SUPPLY FITTINGS, FLEXIBLE WATER CONNECTOR DIVISION: 22 00 00 PLUMBING SECTION:

More information

EVALUATION SUBJECT: PLUMBING SUPPLY FITTING

EVALUATION SUBJECT: PLUMBING SUPPLY FITTING ICC-ES Report PMG-1130 Reissued 04/2017 This report is subject to renewal 04/2018 EVALUATION SUBJECT: PLUMBING SUPPLY FITTING DIVISION: 22 00 00 PLUMBING SECTION: 22 40 00 PLUMBING FIXTURES 22 09 00 INSTRUMENTATION

More information

Effective Date: not available Void After: Product: Plumbing Fixture Fittings File No. 4079

Effective Date: not available Void After: Product: Plumbing Fixture Fittings File No. 4079 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

EVALUATION SUBJECT: OUTDOOR DECORATIVE GAS FIRE PIT AND FIREPLACES DIVISION: SPECIALTIES SECTION: FIREPLACE SPECIALTIES

EVALUATION SUBJECT: OUTDOOR DECORATIVE GAS FIRE PIT AND FIREPLACES DIVISION: SPECIALTIES SECTION: FIREPLACE SPECIALTIES ICC-ES Report PMG-1213 Reissued 06/2017 This report is subject to renewal 03/2018 EVALUATION SUBJECT: OUTDOOR DECORATIVE GAS FIRE PIT AND FIREPLACES DIVISION: 10 00 00 SPECIALTIES SECTION: 10 32 00 FIREPLACE

More information

EVALUATION SUBJECT: OUTDOOR DECORATIVE GAS FIRE PIT AND FIREPLACES DIVISION: SPECIALTIES SECTION: FIREPLACE SPECIALTIES

EVALUATION SUBJECT: OUTDOOR DECORATIVE GAS FIRE PIT AND FIREPLACES DIVISION: SPECIALTIES SECTION: FIREPLACE SPECIALTIES ICC-ES Report PMG-1213 Reissued 03/2018 This report is subject to renewal 03/2019 EVALUATION SUBJECT: OUTDOOR DECORATIVE GAS FIRE PIT AND FIREPLACES DIVISION: 10 00 00 SPECIALTIES SECTION: 10 32 00 FIREPLACE

More information

Effective Date: July 2017 Void After: July Product: Plumbing Fixture Fittings File No. 4472

Effective Date: July 2017 Void After: July Product: Plumbing Fixture Fittings File No. 4472 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

REPORT HOLDER: SMOKE GUARD, INC. 287 NORTH MAPLE GROVE ROAD BOISE, IDAHO EVALUATION SUBJECT:

REPORT HOLDER: SMOKE GUARD, INC. 287 NORTH MAPLE GROVE ROAD BOISE, IDAHO EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1136 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 07 00

More information

Effective Date: July Rev. 1/26/2018- Void After: July Product: Plumbing Fixture Fittings File No. 3474

Effective Date: July Rev. 1/26/2018- Void After: July Product: Plumbing Fixture Fittings File No. 3474 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: FIRE RETARDANT WOOD TREATMENT REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: FIRE RETARDANT WOOD TREATMENT REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2666 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 06 00

More information

BUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT

BUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT BUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT DATE OF AUTHORIZATION June 28, 2001 BMEC REFERENCE BMEC # 01-07-259 BMEC APPLICATION # BMEC #A 2001-10 OATEY CANADA INC. SURE-VENT AND

More information

EVALUATION SUBJECT: EPA WATERSENSE - PLUMBING SUPPLY FITTING DIVISION: PLUMBING SECTION: INSTRUMENTATION AND CONTROL FOR PLUMBING

EVALUATION SUBJECT: EPA WATERSENSE - PLUMBING SUPPLY FITTING DIVISION: PLUMBING SECTION: INSTRUMENTATION AND CONTROL FOR PLUMBING ICC-ES Report PMG-1132 Reissued 04/2018 This report is subject to renewal 04/2019 EVALUATION SUBJECT: EPA WATERSENSE - PLUMBING SUPPLY FITTING DIVISION: 22 00 00 PLUMBING SECTION: 22 09 00 INSTRUMENTATION

More information

EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS

EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS ICC-ES Report PMG-1004 Reissued 08/2017 This report is subject to renewal 08/2018 EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING (HVAC)

More information

Combined Hand-Washing Systems

Combined Hand-Washing Systems IAPMO IGC 127-20142018 PUBLIC REVIEW DRAFT Combined Hand-Washing Systems IAPMO Standard IAPMO IGC 127 20142018 Published: January 2014 Previous Editions: January 2014, July 2013, April 2013, April 2009,

More information

EVALUATION SUBJECT: EPA WATERSENSE PLUMBING SUPPLY FITTINGS DIVISION: PLUMBING SECTION: INSTRUMENTATION AND CONTROL FOR PLUMBING

EVALUATION SUBJECT: EPA WATERSENSE PLUMBING SUPPLY FITTINGS DIVISION: PLUMBING SECTION: INSTRUMENTATION AND CONTROL FOR PLUMBING ICC-E Report PMG-1410 Reissued 11/2017 This report is subject to renewal 11/2018 EVALUATION UBJECT: EPA WATERENE PLUMBING UPPLY FITTING DIVIION: 22 00 00 PLUMBING ECTION: 22 09 00 INTRUMENTATION AND CONTROL

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance Certificate: 1852750 Master Contract: 214418 Project: 2501914 Date Issued: February 27, 2012 Issued to: 11160 Grace Ave Fountain Valley, CA 92708 USA Attention: Hiroshi Ichikawa

More information

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS June 20, 2011 TO: PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS SUBJECT: New Acceptance Criteria for Fixed Condensed Aerosol Fireextinguishing Systems, Subject AC432-0611-R1

More information

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R

CHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R CHAPTER 31 VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R This page left intentionally blank. 426R 2003 INTERNATIONAL RESIDENTIAL CODE For SI: PIPE SIZE (inches) TABLE P3107.3 COMMON VENT SIZES

More information

Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC

Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC People Helping People Build a Safer World Methods of Venting Plumbing Fixtures and Traps in the 2018 IPC Installation, Flexibility and Opportunity for Savings Lee Clifton, Senior Director of PMG Resources,

More information

ENGINEERING EVALUATION

ENGINEERING EVALUATION ENGINEERING EVALUATION REPORT NUMBER: 100378137MID-002 ORIGINAL ISSUE DATE: April 26 th, 2011 REVISION AND DATE: Original EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Hanchett

More information

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1 REPORT NUMBER: 101145164COQ-005 ORIGINAL ISSUE DATE: April 25, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO udecor Inc.

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17065:2012

SCOPE OF ACCREDITATION TO ISO/IEC 17065:2012 SCOPE OF ACCREDITATION TO ISO/IEC 17065:2012 TEi-LISTING SERVICES 3455 S. 500 W. Salt Lake City, UT 84115 Mrs. Alona MacGregor (Authorized Representative) Phone: 801 262 1868 Email: alona@tei-test.com

More information

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: Page 1 of 10 TEST REPORT REPORT NUMBER: 102317918SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet

More information

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source TEST REPORT Kolay 5mm 20mil Wear Layer LVT with Fiberglass Core Project

More information

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy REPORT NUMBER: 100900037COQ-002 ORIGINAL ISSUE DATE: October 10, 2012 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, BC V3K 7C1 RENDERED TO Laminam S.P.A.

More information

STACKS AND STACK VENTS

STACKS AND STACK VENTS CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing

More information

Navigating The Product Certification Maze: Building Codes and Product Standards. AGENDA be Covered

Navigating The Product Certification Maze: Building Codes and Product Standards. AGENDA be Covered AGENDA be Covered Navigating The Product Certification Maze: Understanding the Product Testing & Certification Process and Certification Marks BSC Course No. 49-6664 Presenter: Lisa Reiheld, CSA Group

More information

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3 REPORT NUMBER: 101207560COQ-001b ORIGINAL ISSUE DATE: June 12, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Vipco Industries

More information

CHAPTER 9 VENTS SECTION

CHAPTER 9 VENTS SECTION CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing

More information

FLASHLIGHT ANSI STANDARDS

FLASHLIGHT ANSI STANDARDS FLASHLIGHT ANSI STANDARDS While Pelican was one of the first manufacturers to use quantifiable test procedures, the need was recognized to develop a common language that customers could use to select the

More information

Level I Chapter 1 Worksheet

Level I Chapter 1 Worksheet Chapter 1 Worksheet 1. For applicability requirements of the Plumbing Code, refer to: a. Building Code b. Administration and Enforcement Code c. Plumbing Code d. Residential Code 2. The provisions of the

More information

2009 IRC. and Fuel gas Provisions

2009 IRC. and Fuel gas Provisions 2009 IRC Q &A Plumbing, MechanICAl and Fuel gas Provisions TABLE OF CONTENTS PREFACE... vii ABOUT THE INTERNATIONAL CODE COUNCIL...viii PLUMBING PROVISIONS... 1 CHAPTER 25 PLUMBING ADMINISTRATION....3

More information

PLUMBING CODE REFERENCE Second Edition

PLUMBING CODE REFERENCE Second Edition PLUMBING CODE REFERENCE Second Edition Written by American Contractors Exam Services Published by /guides 1111135940 DeWalt Plumbing Reference_CS4.indd 1 6/25/10 10:24 AM DEWALT Plumbing Code Reference:

More information

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. ICP Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A 1 inch diameter faucet, where the inside edge of the spout opening is 2.5 inches away

More information

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES

More information

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition

More information

Internal Use Only INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

Internal Use Only INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR ELECTRICAL OR HIGH-DENSITY MAGNETIC ANTI-SCALE OR WATER CONDITIONING APPLIANCE IGC 91-2009 1. PURPOSE 1.1 The purpose

More information

Declaration of Conformity

Declaration of Conformity Declaration of Conformity We, Paradox Security Systems Ltd. (manufacturer's name) 780 Industrial Boulevard, St. Eustache, Quebec, Canada, J7R 5V3 (manufacturer's address) declare under our responsibility

More information

UL TEST REPORT AND PROCEDURE

UL TEST REPORT AND PROCEDURE Issue Date: 2010-12-01 Page 1 of 16 Report Reference # E252373-A31-UL UL TEST REPORT AND PROCEDURE Standard: Certification Type: CCN: Product: Model: Rating: UL 60950-1, 2nd Edition, 2014-10-14 (Information

More information

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630 REPORT 58 COMMERCENTRE DRIVE, LAKE FOREST, CA 93 Project No. G138456 Date: April, 16 REPORT NO. 138456LA-51 TEST OF ONE CYCLORAMA WALL WASH LUMINAIRE MODEL NO. TVL CYC RGBW RENDERED TO ACCLAIM LIGHTING

More information

UL TEST REPORT AND PROCEDURE

UL TEST REPORT AND PROCEDURE Issue Date: 2011-01-24 Page 1 of 18 Report Reference # E183863-A17-UL UL TEST REPORT AND PROCEDURE Standard: Certification Type: CCN: UL 60950-1, 2nd Edition, 2007-03-27 (Information Technology Equipment

More information

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630 REPORT 58 COMMERCENTRE DRIVE, LAKE FOREST, CA 963 Project No. G119188 Date: March 13, REPORT NO. 119188LAX-4 TEST OF ONE LED WASH MODEL NO. COLOUR CHORUS 4 RENDERED TO ELATION PROFESSIONAL 61 S. EASTERN

More information

SIGMADEK, LTD. FIRE TEST REPORT

SIGMADEK, LTD. FIRE TEST REPORT SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

Test Code: 8117 / Version 1

Test Code: 8117 / Version 1 Pennsylvania Customized Assessment Blueprint Plumbing Technology/Plumber PA Test Code: 8117 / Version 1 Copyright 2012. All Rights Reserved. General Assessment Information Plumbing Technology/Plumber PA

More information

ProVent Systems Plumbing Fundamentals. Educational Literature. Comparison of ProVent Design Rules and The International Plumbing Code

ProVent Systems Plumbing Fundamentals. Educational Literature. Comparison of ProVent Design Rules and The International Plumbing Code ProVent Systems Plumbing Fundamentals Educational Literature Comparison of ProVent Design Rules and The International Plumbing Code Guide to Contents Topics and Descriptions Page Interior views of the

More information

CHAPTER 9 VENTS. run undiminished in size and as directly as possible from the building drain through to the open air above the roof.

CHAPTER 9 VENTS. run undiminished in size and as directly as possible from the building drain through to the open air above the roof. CHAPTER 9 VENTS SECTION 90 GENERAL run undiminished in size and as directly as possible from the building drain through to the open air above the roof. 90. Scope. The provisions of this chapter shall govern

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS MATERIAL AND PROPERTY STANDARD FOR

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS MATERIAL AND PROPERTY STANDARD FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS MATERIAL AND PROPERTY STANDARD FOR EARLY-CLOSURE REPLACEMENT FLAPPERS OR EARLY-CLOSURE REPLACEMENT FLAPPER WITH MECHANICAL ASSEMBLIES IAPMO

More information

FUNDERMAX GMBH FIRE TEST REPORT

FUNDERMAX GMBH FIRE TEST REPORT FUNDERMAX GMBH FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON 19 MM MAX COMPACT REPORT NUMBER I0002.02-121-24 TEST DATE 01/29/18 ISSUE DATE 02/16/18 RECORD RETENTION END DATE 01/29/22 PAGES 10 DOCUMENT

More information

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630 REPORT 58 COMMERCENTRE DRIVE, LAKE FOREST, CA 963 Project No. G67677 Date: June 6, 4 REPORT NO. 67677LAX- TEST OF ONE FULL ON AT 9 BEAM ANGLE MODEL NO. RAZOR Q ZOOM RENDERED TO ELATION PROFESSIONAL 6 S.

More information

Plumbing Lesson Four: Plumbing System Plan. Student Handouts

Plumbing Lesson Four: Plumbing System Plan. Student Handouts Plumbing Lesson Four: Plumbing System Plan Student Handouts Building Basics was paid for under an EL Civics grant from the U. S. Department of Education administered by the Virginia Department of Education.

More information

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. The minimum air gap for a fixture with an effective open of 1/2", located away from a

More information

Trap Seal Primers and Water Hammer Arrestors TSP-2015 Go to for the most current product specification sheets.

Trap Seal Primers and Water Hammer Arrestors TSP-2015 Go to  for the most current product specification sheets. www.mifab.com TSP-2015 Go to www.mifab.com for the most current product specification sheets. Trap Seal Primers and Water Hammer Arrestors LIT-062, Inc. 1321 West 119th Street, Chicago, Illinois 60643-5109,

More information

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI TECHNICAL MANUAL for FIRE TAPE E-Z TAPING SYSTEM PO BOX 10887 GREEN BAY, WI 54307 800-721-8273 http://www.e-ztape.com Table of Contents Product Description... 3 Fire Tape Manufacturer... 3 Fire Tape Listed

More information

Manufactured specifically for Acid Waste systems. NSF certified to meet all performance standard of ASSE 1051

Manufactured specifically for Acid Waste systems. NSF certified to meet all performance standard of ASSE 1051 CHEM-VENT VENT The CHEM-VENT VENT Manufactured specifically for Acid Waste systems Material is NSF 014 and ASTM D-4101 compliant NSF certified to meet all performance standard of ASSE 1051 Designed and

More information

IPC CODE AND COMMENTARY

IPC CODE AND COMMENTARY 2012 IPC CODE AND COMMENTARY 2012 International Plumbing Code Commentary First Printing: March 2012 ISBN: 978-1-60983-070-0 (soft-cover) COPYRIGHT 2012 by INTERNATIONAL CODE COUNCIL, INC. ALL RIGHTS RESERVED.

More information

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI TECHNICAL MANUAL for FIRE TAPE E-Z TAPING SYSTEM PO BOX 10887 GREEN BAY, WI 54307 800-721-8273 http://www.e-ztape.com Table of Contents Product Description...3 Fire Tape Manufacturer...3 Fire Tape Listed

More information

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630 REPORT 58 COMMERCENTRE DRIVE, LAKE FOREST, CA 96 Project No. G85 Date: April 6, 5 REPORT NO. 85LAX- TEST OF ONE WALL BRACKET JELLY JAR MODEL NO. H-CGU--B LED MODEL NO. BRIDGELUX BXRC-E-C-X DRIVER MODEL

More information

ETSI TS V1.2.1 ( )

ETSI TS V1.2.1 ( ) TS 100 783 V1.2.1 (2004-08) Technical Specification Transmission and Multiplexing (TM); Passive optical components; Fibre optic fusion splices for single-mode optical fibre transmission systems for indoor

More information

XRRS Specification Fire Ready Hood

XRRS Specification Fire Ready Hood XRRS Specification Fire Ready Hood ************************************************************************************************************************ Note to User: This document is subject to copyright

More information

Australian Standard. Smoke alarms. AS (Incorporating Amendment Nos 1, 2, 3 and 4) AS 3786

Australian Standard. Smoke alarms. AS (Incorporating Amendment Nos 1, 2, 3 and 4) AS 3786 AS 3786 1993 (Incorporating Amendment Nos 1, 2, 3 and 4) AS 3786 Australian Standard Smoke alarms This Australian Standard was prepared by Committee FP-002, Automatic Fire Detection and Alarm Systems.

More information

Effective Date: August Rev. 12/22/2017- Void After: August Product: Plumbing Fixture Fittings File No. 4318

Effective Date: August Rev. 12/22/2017- Void After: August Product: Plumbing Fixture Fittings File No. 4318 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

Installation Instructions

Installation Instructions Installation Instructions Type B Gas Vent Model E/R 3" 8" ECCO TYPE B GAS VENT AND ACCESSORIES ARE FOR USE ONLY WITH LISTED CATEGORY 1 GAS-FIRED APPLIANCES OR APPLIANCES LISTED FOR USE WITH TYPE B GAS

More information

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-02-14 FIRE EXTINGUISHERS TABLE OF CONTENTS 0780-02-14-.01 Definitions 0780-02-14-.09 Restrictions 0780-02-14-.02 Standards

More information

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5 REPORT NUMBER: 3189147COQ-002 ORIGINAL ISSUE DATE: September 30, 2009 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Radial Engineering

More information

Tube Clamp Submittal Information Revision A: July 25, 2013

Tube Clamp Submittal Information Revision A: July 25, 2013 Tube Clamp Revision A: July 25, 2013 Polypropylene (PP) Tube Clamps secure ½" and ¾" Uponor crosslinked polyethylene (PEX-a) tubing products. Suspension Standard Description Part Number A B C Weight Tube

More information

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015 REPORT NUMBER: 101960325MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 TEST REPORT

More information

Matrix of changes for the National Standard Plumbing Code July 2013

Matrix of changes for the National Standard Plumbing Code July 2013 Matrix of changes for the National Standard Plumbing Code July 2013 Item # Section Number Person Submitting Change Committee Action 10-77 10.20.8 and Table 3.1.3 XI Certification 10-82 12.16 Size and Lengths

More information

MATERIALS Traps TRAPS. No. IPC IRC Description

MATERIALS Traps TRAPS. No. IPC IRC Description MATERIALS Traps TRAPS MAX " MAX 0" No. IPC IRC Description 00. P0.6 00. P0.6 00. P0. 00. () P0.6 Exc. Vertical distance from fixture to the trap weir can not exceed ". Horizontal distance from the fixture

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 3500.4:2003 (Incorporating Amendment Nos 1 and 2) AS/NZS 3500.4:2003 Australian/New Zealand Standard Plumbing and drainage Part 4: Heated water services AS/NZS 3500.4:2003 This Joint Australian/New

More information

Sanitary Drainage Systems

Sanitary Drainage Systems 11.1 MATERIALS See Section 3.1. Sanitary Drainage Systems 11.2 BUILDING SEWERS AND BUILDING DRAINS 11.2.1 Sewer or Drain in Filled Ground Chapter 11 Building sewers or building drains that are installed

More information

PLUMBING REQUIREMENTS

PLUMBING REQUIREMENTS PLUMBING REQUIREMENTS This handout is a compilation of the standard requirements based on the State Plumbing Code and City Ordinance for projects of this type. This information sheet does not contain all

More information

Avigilon Control Center System Integration Guide

Avigilon Control Center System Integration Guide Avigilon Control Center System Integration Guide with Velocity INT-HIRSCH-A-Rev3 Copyright 2013 Avigilon. All rights reserved. No copying, distribution, publication, modification, or incorporation of this

More information

PLUMBING INSTALLATIONS

PLUMBING INSTALLATIONS PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT PLUMBING INSTALLATIONS A homeowner guide to plumbing requirements for single-family dwellings November 2017 contents Permit Requirements... 3 Inspection Requirements...

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61169-42 Edition 1.0 2013-01 colour inside Radio-frequency connectors Part 42: Sectional specification for CQN series quick lock RF coaxial connectors IEC 61169-42:2013(E) THIS

More information

Ecodrain V1000. Selection and Installation Guide for Residential Applications TM MC TM

Ecodrain V1000. Selection and Installation Guide for Residential Applications TM MC TM Ecodrain V1000 Selection and Installation Guide for Residential Applications TM MC TM PRECISION ENGINEERING LEADS TO HIGH PERFORMANCE 2 3 WHAT S INCLUDED IN THE BOX Lead Free Brass Cast Manifold, with

More information

CLASSIFICATION Constructional Data Report (CDR)

CLASSIFICATION Constructional Data Report (CDR) CLASSIFICATION Constructional Data Report (CDR) 1.0 Reference and Address Report Number 100358381SAT-001 Original Standard(s) Fire Test for Heat and Visible Smoke Release for Discrete Products and Their

More information

CodeNotes. Solar Water Heating Systems Based on the 2018 International Solar Energy Provisions (ISEP ) Introduction OFFICIAL

CodeNotes. Solar Water Heating Systems Based on the 2018 International Solar Energy Provisions (ISEP ) Introduction OFFICIAL CodeNotes is provided courtesy of the ICC PMG Official Membership Council OFFICIAL CodeNotes Solar Water Heating Systems Based on the 2018 International Solar Energy Provisions (ISEP ) Introduction Solar

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information