FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual"

Transcription

1 Fire Safety FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ Brampton, Ontario L6T 5E4 CN P/N (447290)

2 Table of Contents INTRODUCTION...1 CONTROL UNIT LIMITATIONS...1 PREFACE...2 DESCRIPTIONS...3 SYSTEM DESCRIPTION...3 HARDWARE CONFIGURATION...3 MINIMUM CONTROL UNIT CONFIGURATION...4 Power Supply...4 Addressable Device Circuit...4 Notification Appliance Circuits...4 RS485 Communications Circuit...4 Status Relays...4 OPTIONAL CONTROL UNIT CONFIGURATION...4 Municipal Tie Board...4 RS232 Communication Board...4 DACT Board...4 BATTERY SETS...5 AUXILIARY MODULES...5 Remote LCD Annunciator...5 Serial Relay Unit and Serial Relay Extender...5 Serial Annunciator Unit and Serial Annunciator Extender...5 ADDRESSABLE DEVICES...5 Siemens Addressable Detectors...5 Variable Thresholds...5 Operator Alerts...6 Other Siemens Addressable Devices...6 Heat Detectors...6 Addressable Modules (Monitor and Control)...6 Manual Stations...6 PROCESSOR CONTROLLED OUTPUT ZONES...6 Output Sounding Patterns...6 Control of Audible Silencing...6 Audible Silence Inhibit...6 EVENT HISTORY...7 GENERAL DESIGN FEATURES...8 Environmental...8 Power Limiting...8 Ground Fault Detection...8 Transient Protection...8 Security Functions...8 REGULATORY STANDARDS...8 Federal Communications Commission...8 Underwriters Laboratories...8 GENERAL SPECIFICATIONS...9 Environmental...9 Primary Supply...9 Secondary and Trouble Power Supply...9 Auxiliary Power Outputs...9 Status Relays...9 Notification Appliance Circuits...9 RS485 Communications Circuit...10 P/N i

3 Addressable Device Circuit...10 Municipal Tie (Optional Municipal Tie Board Model FS-MT)...10 RS232 Output (Optional RS232 Board Model FS-232)...10 DACT Circuit (Optional DACT Board Model FS-DACT)...11 CONTROL UNIT OPERATION...12 OPERATION INSTRUCTIONS...12 A. Standby Condition...12 B. Alarm Condition ) Waterflow Alarms ) Positive Alarm Sequence (PAS) ) Pre-Signal...12 C. Trouble Condition...13 D. Supervisory Condition...13 E. Maintenance...13 ADDITIONAL OPERATING PROCEDURES...14 A. Lamp Test...14 B. Drill...14 C. Recall...14 D. Pre-Alarm...14 E. General Alarm...14 F. Tornado...14 G. History...15 FS-100 OPERATING INSTRUCTIONS...16 FS-RD OPERATING INSTRUCTIONS...17 CONTROL UNIT INSTALLATION...18 PARTS SUPPLIED...18 CAUTION...18 CONTROL UNIT LOCATION...18 ENCLOSURE MOUNTING...18 A. Surface Mounting Instructions...19 B. Semi-Flush Mounting Instructions...20 C. Knock-Outs...21 D. Main Board Installation...21 E. AC Supply Connection...21 F. Transformer Installation...22 G. Front Plate Assembly...22 H. Front Plate Mounting...22 I. Door Assembly...23 J. Battery Installation...23 K. Powering the Control Unit...23 L. Checking Supervised Circuits...24 M. Optional Modules...24 N. System Wiring...24 O. Check System Operation...24 SYSTEM WIRING...25 CONTROL UNIT WIRING OVERVIEW...25 WIRING SEPARATION...25 WIRING SEPARATION...26 PRIMARY AND SECONDARY POWER WIRING...26 STATUS RELAYS AND AUXILIARY POWER OUTPUTS WIRING...27 System Power Requirement Calculations...27 Auxiliary Power Supply...27 Battery Size Calculations...27 NAC WIRING...28 P/N ii

4 RS485 COMMUNICATIONS CIRCUIT...29 Remote Device Power...29 Remote Device Data...29 ADDRESSABLE DEVICE CIRCUIT...30 Addressable Device Wiring Diagrams...30 Addressable Detectors...33 FS-DPT Photoelectric Detector with Thermal...33 FS-DT Thermal Detector...33 FS-DP Photoelectric Detector...33 DB-11, ADBX-11 and DBX-11RS Detector Bases...33 AD-11P and ADX-11PR Air Duct Housing...33 LIM-1 Line Isolator Module...33 Addressable Modules...34 Transmit & Receive Interface Modules...34 FS-CZM Conventional Zone Module...34 PROGRAMMING THE CONTROL UNIT...35 MAIN BOARD JUMPER...35 KEYPAD PROGRAMMING...35 PROGRAMMING SECURITY...35 MAINTENANCE...36 GENERAL...36 QUICK TEST (WALK TEST)...37 APPENDIX A- REFERENCE INFORMATION...38 WIRE SELECTION GUIDES...38 Resistance of Solid Copper Wire...38 Notification Appliance Circuit Wire Selection Guide...38 Addressable Device Circuit Wire Selection Guide...39 BATTERY SIZE CALCULATIONS...40 APPENDIX B- COMPATIBLE DEVICES...42 DEVICES FOR ADDRESSABLE DEVICE CIRCUITS...42 FS-100 Addressable Modules...42 FS-100 Addressable Detectors...42 FS-100 Detector Bases...42 FS-100 Accessories...42 DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS...42 APPENDIX C: TROUBLES HOOTING...43 DEFINITIONS FOR EVENT HISTORY ENTRIES...43 A. General...43 B. System Troubles...44 C. System Events...45 APPENDIX-D: INSTALLATION INSTRUCTIONS...46 APPENDIX-E: GLOSSARY...47 P/N iii

5 INTRODUCTION CONTROL UNIT LIMITATIONS This control unit must be installed with compatible initiating devices (smoke detectors, etc.) and notification devices (horn, lights, etc.) connected to it. Electrical ratings of the initiation and notification appliances must be compatible with the electrical ratings of the control unit and must be properly interconnected. The wiring used for interconnection must be large enough to carry the total current for all appliances without excessive voltage drop. The control unit must be connected to a dedicated primary electrical source that has a high degree of reliability and adequate capacity for this control unit. The only means of disconnecting this power source shall be available only to authorized personnel and clearly marked "Fire Alarm Circuit Control". The control unit must also have connected to it a battery set (24v) that has enough capacity to properly operate the system for 24 or 60 (depending on system type) hours standby and 5 minutes alarm per NFPA 72 (chapter 1). These batteries do lose capacity with age. Batteries must be replaced when they fail to provide the control unit with the required standby and alarm power or after 4 years, whichever happens first. These batteries must be checked for performance at least two (2) times a year or more often if local requirements dictate. Fire alarm control units cannot last forever. Even though this control unit was made to last for the expected life of the fire alarm system, any part could fail at any time. Therefore a regular test program should be followed and documented to make sure that each part of the system is tested as in Chapter 7 of NFPA 72 or more often if dictated by local code requirements. Malfunctioning units must be replaced or repaired immediately by factory authorized service personnel. NOTE: This control unit is designed to show an alarm condition when the initiating devices connected to it detect specific conditions. These conditions may or may not represent a life-threatening condition. Also, evacuation of a building or area unnecessarily may subject individuals to an unnecessary hazard. Therefore, it is most important that the building owner, manager, or representative promulgate, distribute, and/or post instructions describing steps to be taken when the fire alarm control unit signals any alarm condition. These instructions should be developed in cooperation and conformance with representatives of the local authority having jurisdiction. As a backup or precautionary measure, it is strongly suggested that one of these steps should be to notify the local fire department of an abnormal condition even where the DACT option (or similar device) is included in the system. P/N

6 PREFACE Along with the use of this instruction manual, the appropriate following standards and the manufacturer's instructions for initiating and notification devices should be used to install and maintain a functioning fire alarm signaling system. NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 101 Life Safety Code For other standards that may apply contact the authority having jurisdiction. For NFPA publications, contact: National Fire Protection Association Batterymarch Park Quincy, Massachusetts P/N

7 DESCRIPTIONS SYSTEM DESCRIPTION The FS-100 is an advanced modular fire alarm control unit. It features addressable/analog detection, programming, and memory capability. Its base configuration includes one addressable device circuit, with four conventional notification appliance circuits. The basic FS-100 control unit mounts in a 14-3/8" x 14-3/8" back-box with overall cover size of 14-3/4" x 14-21/32". Operating controls and indicators are mounted inside a secure door. An 80-character LCD display provides specific indications for addressable devices while LEDs indicate general panel status. Semi-flush mounting kits are available for the enclosure. HARDWARE CONFIGURATION The main board mounts in the rear of the enclosure. The power supply is physically contiguous with the main board. The FS-100 main board provides the interface for external analog system connections, for the addressable device circuit, four notification appliance circuits, remote signaling and indicating interfaces, and connection of the main system power supply. Optional boards mount on the main board. The display board mounts on the front plate, allowing it to carry the controls and displays which must be accessible. All normal operation is controlled from the front of the control unit via push-button switches. Displays are provided by an 80-character, alphanumeric, backlit LCD display and by discrete LED indicators for major control unit functions. The 80-character LCD display is used to display event data, including alarms and troubles, identification of zone or device, and presentation of history. The display is controlled by a set of four push-button switches commanding the control processor. A back light is included in the display to assure visibility in low light, but to conserve power, it is only activated during a reported event or on operation of a display control switch. Individual LEDs on the panel are provided to indicate SYSTEM ALARM, PREALARM, SUPERVISORY, ALARM SILENCED, SYSTEM TROUBLE and AC POWER ON. Direct push-button controls are provided for ALARM SILENCE, TROUBLE SILENCE/ACKNOWLEDGE, MENU and SYSTEM RESET. P/N

8 MINIMUM CONTROL UNIT CONFIGURATION Power Supply A 3A, 24V nominal power supply provides all operating power to the control unit for both standby and alarm conditions. Sufficient battery charging capability is available to charge sealed lead-acid batteries within code requirements for 60 hour quiescent plus 5 minutes alarm. The cabinet will hold batteries only up to 7 AH. The back-up battery is 24V, maintained by floating on the power supply. The power supply is physically contiguous with the main board. Addressable Device Circuit The FS-100 control unit has one addressable device circuit that is programmed for connection to Siemens addressable devices. The addressable device circuit drives up to 60 addressable initiating devices, detectors and/or modules. Each detector and module can support one output device. Notification Appliance Circuits The FS-100 control unit has four independent notification appliance circuits (NACs). Each circuit can be selected to give continuous output or one of eight sounding patterns available in the control unit. There is also a system coder capable of zone coded operation. All of the NACs are power limited and can be wired for Class A (Style Z) or Class B (Style Y) operation. RS485 Communications Circuit The FS-100 control unit has an RS-485 Communications Circuit that will drive up to 16 remote LCD annunciators and 8 Serial Relay Units and Serial Annunciator Units on the RS485 communication line. Status Relays Three dry relay contacts are provided. These contacts are dedicated to alarm, trouble and supervisory indications. The relay contacts are form C and are rated 28VDC resistive. OPTIONAL CONTROL UNIT CONFIGURATION A maximum control unit configuration can include all of the minimum configuration items plus additions as noted below. Details of these accessories are given in Appendix D. Municipal Tie Board The Siemens Model FS-MT municipal tie board provides local energy and polarity reversal connections. The polarity reversal connections provide a trouble circuit and an alarm circuit with optional trouble output. RS232 Communication Board The Siemens Model FS-232 RS-232 communication board will allow event data to a serial printer or terminal. DACT Board The Siemens Model FS-DACT Digital Alarm Communication Transmitter board will send control unit status data to a remote receiving station. P/N

9 BATTERY SETS The FS-100 control unit is designed to use only sealed lead-acid or equivalent batteries for back-up power. The system enclosure can house 7 AH, 24VDC battery sets, Model BT-33. AUXILIARY MODULES Remote LCD Annunciator The Siemens FS-RD remote LCD annunciator consists of a backlit 80 character LCD alphanumeric display, 4 menu buttons, 4 dedicated buttons for operator interaction, 6 LED indicators, and a security key-switch. The display and controls on the annunciator are the same as those on the front of the control unit, including a key-switch for security. The back light operates only when the data are being accessed, to conserve power. Up to sixteen annunciators may be addressed by the communications circuit, but some may require auxiliary power supplies, depending on the total accessory power loading. Serial Relay Unit and Serial Relay Extender The Siemens FS-RU includes a processor board and a relay board. The processor board receives commands from the control unit for activating the relays and transmits supervision and control functions to the control unit. The processor board can control up to 3 FS-RE8 relay boards. Each relay board provides 8 relays with form C contacts. The control unit can address up to 8 FS-RU Serial Relay Units and/or FS-SAU Serial Annunciator Units. Auxiliary power supplies will be required to power units beyond the control unit capability. Serial Annunciator Unit and Serial Annunciator Extender The Siemens FS-SAU includes a processor board and an annunciator driver board. The processor board receives commands from the control unit for activating the outputs and transmits supervision and control functions to the control unit. The processor board can control up to 4 FS-SAE16 annunciator driver boards. Each driver board provides 16 supervised outputs for LEDs or incandescent lamps. The control unit can address up to 8 FS-RU Serial Relay Units and/or FS-SAU Serial Annunciator Units. Auxiliary power supplies will be required to power units beyond the control unit capability. ADDRESSABLE DEVICES Siemens Addressable Detectors The control unit processor sends the sensitivity and pre-alarm settings to the detectors and polls the detectors as to their status. The detector determines normal, trouble, pre-alarm or alarm conditions and relays the status to the control unit. Variable Thresholds The obscuration level for alarm can be adjusted from the control unit on a permanent or time-variable basis. This facility also means that the control unit can display information on individual points for maintenance or service. P/N

10 Operator Alerts The control unit can trigger an alarm or trouble automatically on the occurrence of a number of conditions of the detector. These include: Maintenance alert Pre-alarm alert No response Incorrect response Other Siemens Addressable Devices Heat Detectors Addressable heat sensing detectors may be intermixed on the circuit for locations where heat sensing may be the most effective detection mode. Addressable Modules (Monitor and Control) In addition to detectors, the circuit can communicate with addressable modules, allowing initiating devices or notification appliances with local power sources, and supervising the power sources. Manual Stations Addressable manual stations may be intermixed on the circuit with proper response programmed into the control unit. PROCESSOR CONTROLLED OUTPUT ZONES While the notification appliance circuits are essentially hardware circuits, the fact that the outputs are commanded and controlled by the processor does provide more versatility than in a total hardware system. All functional selections are included in the control unit programming process. Output Sounding Patterns The notification appliance circuits are operable in different sounding patterns. Any circuit is selectable to any of eight software-generated patterns or continuous sounding. For convenience, three of the patterns are preprogrammed for March Time, Temporal, and Californian patterns. Control of Audible Silencing It is possible to select an auto-silence mode, adjustable from 0 to 255 minutes. Each notification appliance circuit programmed for alarm silence sequence, will be silenced upon time-out of the autosilence timer. The alarm silenced LED will flash, indicating the auto-silence time-out. Audible Silence Inhibit In addition to designation of waterflow zones, the entire control unit may be programmed to inhibit audible silence for 0, 1, 3, or 6 minutes from the last alarm. System reset may also be inhibited. P/N

11 EVENT HISTORY The control unit includes a non-volatile memory recording up to 500 system events. Identified alarm, trouble, supervisory trouble, and other significant events will be recorded along with the date and time of occurrence, and can be inspected by operating front panel push buttons. Events recorded in the history are: Alarm, Trouble, or Supervisory conditions. Drill, Tornado, Recall and General Evacuation. Activation of NACs or modules used for sounders or strobes. Unit used for command functions. (Silence, acknowledge, reset, etc.) PAS_INHIBIT switch activation. Alarm silence (manual and automatic). System reset. Power up. Entry to Programmer Mode. Secondary configuration edited. Validity check on backup configuration. (Errors detected or no errors detected) Running of comparison function. (Same or different) Replacement of primary configuration. Execution of Auto-program. Exit from Programmer Mode. System time or date change. Input point disable/enable. Start and stop of walk test. Expiration of Walk Test Timer. Expiration of re-ring timer. Alarm/trouble/supervisory Acknowledgment. Trouble/supervisory restored to normal. Alarm verification counter rollover. Pre-alarm activation. Pre-alarm acknowledgment/restore. Alarm of zone with no outputs. Activation of points defined for logging. Sensor maintenance alerts P/N

12 GENERAL DESIGN FEATURES Environmental All hardware is suitable for use in an interior or protected location. Power Limiting The AC power and battery wiring are not power limited. All other circuits leaving the control unit are power limited, provided the proper installation rules are maintained. Ground Fault Detection The control unit provides ground fault detection and a ground fault will trigger the common fault buzzer and system trouble LED. Transient Protection Transient protection devices are provided where needed to meet the requirements of UL864. Security Functions Processor control and addressing allow inclusion of several functions to assure security of the system. Multi-level password protection of programming functions prevents unauthorized configuration changes. Device type supervision: If the type reported by an addressable sensor or module, does not agree with the configuration, the system reports a trouble. Device address supervision: The system checks that all configured devices on the addressable device circuit and the RS485 circuit responds to an address poll. If a configured device is missing, the system reports a trouble. The system also polls unused addresses periodically. If a device responds to such a poll of a non-configured device, the system reports a trouble. Two devices addressed the same also cause a trouble to be reported. REGULATORY STANDARDS The FS-100 control unit meets the requirements of industry and government regulatory agencies as noted. Federal Communications Commission The FS-DACT meets the requirements of the Code of Federal Regulations (CFR 47), Part 68, for connection of equipment to the public switched telephone network. Underwriters Laboratories The FS-100 Fire Alarm control unit is listed under UL Standard 864 for compliance to NFPA Standard 72 for fire service P/N

13 GENERAL SPECIFICATIONS Operating specifications for the FS-100 are as follows: Environmental Operating temperature F (0-49 C) Relative humidity Up to 86 F (30 C) Primary Supply Primary Input Voltage: 120 VAC (60 Hz) nominal (FS ) Maximum primary input current: 1.3A at 120 VAC Secondary and Trouble Power Supply 24 volt lead-acid battery set: Maximum Charge Voltage: 27.8 VDC Maximum Charge Current: 1.0 A Maximum Input Current: 3.5A Battery capacity: 7-38 A.H. (over 7 A.H. requires separate enclosure) Auxiliary Power Outputs Current: 0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards 0.4 amp maximum per power output Non-Resettable Power Outputs Power limited Voltage: 24 VDC nominal Ripple: 1.5 VAC maximum Resettable Power Output Power limited Voltage: 24 VDC nominal Ripple: 1.5 VAC maximum Status Relays Includes alarm, supervisory and trouble relays. Contact Rating: 1 A, 28 VDC maximum, resistive Form C Contact Notification Appliance Circuits Four Class A, Style Z/Class B, Style Y circuits Power limited Supervised Maximum Standby Current: 3.4mA Alarm Voltage: 24 VDC nominal Maximum Alarm Current per circuit: 1.5 A Total Maximum Alarm Current (all circuits): 2.5 A Maximum Ripple: 16 VAC Maximum Loop Drop Voltage: 1.0 VDC P/N

14 RS485 Communications Circuit Power limited Supervised Voltage: 24 VDC nominal Current: 0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards 0.4 amp maximum for RS485 circuit Maximum wire loop resistance: 25 ohms/line Communications: RS485 Addressable Device Circuit Power limited Supervised Voltage: 24 VDC nominal Maximum Current (shorted): 0.25A Maximum wire loop resistance: 20 ohms/line One Style 4 or 6 circuit 60 detectors and modules max. 1 accessory output per device Municipal Tie (Optional Municipal Tie Board Model FS-MT) CA CT LE Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation Power limited Supervised by receiver for short or open circuit. Supervised by control unit for grounded circuit. Voltage: 24 VDC nominal Current: 0.020A maximum (normal or trouble) Current: 0.025A maximum (shorted) Ripple: 1.5 VAC maximum Reverse Polarity: Programmable for Trouble or Supervisory or either operation Power limited Supervised by receiver for short or open circuit. Supervised by control unit for grounded circuit. Voltage: 24 VDC nominal Current: 0.020A maximum (normal or alarm) Current: 0.025A maximum (shorted) Ripple: 1.5 VAC maximum Local Energy Not power limited Supervised for open or grounded circuit by control unit. Voltage: 24 VDC nominal Standby Current: 0.007A maximum Alarm Current: 0.400A maximum Ripple: 1.5 VAC maximum Maximum wire loop resistance: 30 ohms Trip coil impedance: 14.5 ohms RS232 Output (Optional RS232 Board Model FS-232) Power limited Not supervised Voltage Range: -15 VDC to +15 VDC Maximum Current (shorted): 0.050A Baud Rate: 4800 Maximum wire loop resistance: 25 ohms P/N

15 DACT Circuit (Optional DACT Board Model FS-DACT) Power limited Supervised for short or open circuit Maximum Voltage: 60 VDC P/N

16 CONTROL UNIT OPERATION OPERATION INSTRUCTIONS A. Standby Condition In normal standby operation, the green AC POWER ON LED should be illuminated and no other indicator operating. The display will show the system name, System Normal announcement and the current date, day, and time. B. Alarm Condition 1) GENERAL ALARMS a) In case of alarm, the system alarm LED will operate in a flashing mode and the buzzer will sound. Local audible and visual signals and remote alarm signals will operate, and the LCD panel display will indicate the zone or point initiating the alarm. b) On receipt of an alarm, proceed in accordance with the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department. c) To silence the audible after evacuation, where permitted by the codes and control unit programming, press ALARM SILENCE. The alarm audible will be silenced, the alarm silence LED will be illuminated and a system trouble indicated. Operating the ACKNOWLEDGE button will silence the local buzzer and change the LED alarm indicator from flashing to steady. 2) Waterflow Alarms Alarms detected on zones designated waterflow indicate sprinkler operation and the audible alarms cannot be silenced in this condition. Operation of alarm silence will produce no effect. 3) Positive Alarm Sequence (PAS) a) Activation of a point programmed for PAS, including two-stage manual stations, activates the Alarm LED, display and buzzer (pulsing), but delays all other outputs (system and user) for 15 seconds. b) Operation of the ACKNOWLEDGE button within 15 seconds will add 165 seconds to the timer value, to make the total delay 180 seconds. c) If an ALARM SILENCE button is pressed or the sensor returns to a normal reading before the extended PAS delay time, the alarm sequence is aborted. d) An alarm condition on a sensor programmed for direct alarm response (such as the key switch on a manual station) will over-ride the PAS timer and activate the outputs. 4) Pre-Signal a) A point activated by a PRE-SIGNAL alarm activates the alarm relay, alarm DACT, city tie, alarm LEDs and buzzers, and all user programmed outputs normally, but does not activate any NACs. b) Operation of the ALARM SILENCE button less than 180 seconds after initiation of the alarm prevents operation of the NACs. c) Failure to act within 180 seconds will result in activation of the NACs. d) Receipt of another pre-signal or standard alarm during the delay period immediately sounds the NACs. e) A SYSTEM RESET is required to return the zone and input point to normal, whether or not the NACs were activated. NOTE: Do not reset the system until the alarm condition has been cleared. The LCD display on the will indicate the area in which the alarm was detected. The detector initiating the alarm will display a light. If more than one zone is in alarm, the last zone to be alarmed will be indicated on the display. P/N

17 f) When the alarm condition has been corrected, return the system to standby operation by pressing the SYSTEM RESET button. C. Trouble Condition a) In case of a trouble condition, the system trouble LED and any programmed trouble LEDs will be flashing, the LCD display will identify the problem, and the buzzer will sound. Refer to the applicable section of the system manual to determine the probable cause of the trouble and the action to be taken. b) When a trouble has been noted, the buzzer may be silenced by pressing the ACKNOWLEDGE button. The trouble LEDs will change to a continuous display. If the trouble has not been corrected when the trouble re-ring timer expires, the trouble display will revert to its original condition and the buzzer resound. c) If the control unit is programmed for trouble acknowledge required, when the indicated trouble condition has been cleared, the system will revert to standby condition after the ACKNOWLEDGE button is pressed. Note: Some trouble conditions require a system reset to restore the control unit. D. Supervisory Condition Supervisory conditions are indicated similar to regular system trouble conditions except that when a supervisory condition is cleared, the cleared condition continues to be indicated until it is acknowledged. E. Maintenance In order to insure continued safe and reliable operation of the fire alarm system, periodic inspection and testing should be performed in accordance with applicable NFPA 72 standards. CAUTION: If the system has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and/or notify the remote monitoring station before performing test operations. For any required service, refer to the system manual or contact a factory authorized representative. P/N

18 ADDITIONAL OPERATING PROCEDURES In addition to the basic fire alarm instructions above, several features are included to facilitate maintenance and increase the versatility of the system. Following are procedures to call up these functions. A. Lamp Test To operate the lamp test, press the MENU button. The LCD display will change to a MENU screen. Press the button next to the More indication twice. Then press the button by the Lamp Test indication. All lamps on the unit being operated will then light. Operating the button next to Esc will then return the control unit to normal display. Note that the lamp test operates the indicators only on the unit being operated, and no record is reported to system history. B. Drill To activate a fire alarm drill, proceed as follows: 1. Press "MENU". 2. On the MENU display, select "More". 3. At the next screen, select "DRILL". 4. At the next screen, select "Yes". 5. Operate ALARM SILENCE to terminate drill signal. C. Recall To signal recall after a drill, proceed as follows: 1. Press "MENU". 2. At the next screen, select "More". 3. Select "RECALL". 6. At the next screen, select "Yes". 4. Operate ALARM SILENCE to terminate recall signal. D. Pre-Alarm 1. A pre-alarm condition is annunciated by Pre-alarm LEDs and buzzers on the control unit and RS485 LCD Annunciators and RS485 Remote Processors. The LEDs flash and buzzers are on steady until acknowledgment. 2. Acknowledging the Pre-alarm condition puts LEDs on steady and buzzers off. 3. If pre-alarm has been acknowledged and restores to normal, the condition clears. If the system proceeds into an alarm condition, the pre-alarm condition clears whether or not it has been acknowledged and is replaced by alarm. E. General Alarm To activate a general alarm, proceed as follows: 1. Press "MENU". 2. On the MENU display, select "GENERAL ALARM". 3. At the next screen, select "Yes". 4. Silence and reset the system as with any alarm. F. Tornado To activate a tornado alarm, proceed as follows: 1. Press "MENU". 2. On the MENU display, select "TORNADO". 3. At the next screen, select "Yes". 4. Operate ALARM SILENCE to terminate tornado signal. P/N

19 G. History The last 500 system events are time-tagged and recorded for review in the user level event history. This history is available to anyone with the door key, but may be erased only at the maintenance security level. 1. Operation of history: a) New events overwrite old when filled. b) Printer (if used) records all events. c) For more information see the event history section 2. Access to history: To recall past events, proceed as follows: a) Press MENU button. b) Operate button identified as "More". c) Operate button identified as "More". d) Operate button identified as "View History". e) Operate upper left button for previous event display. f) Operate lower left button for next event display. g) Operate upper right button to exit to MENU DISPLAY. P/N

20 FS-100 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the System Alarm LED flashes, LCD will display alarm conditions and the panel buzzer sounds. Local audible and visual signals and remote alarm signals operate. When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department. Authorized Personnel Only To silence the alarm: To silence the notification appliances after evacuation, where permitted, press the Alarm Silence switch. The notification appliances and panel buzzer will be silenced, and LED indications will change from flashing to continuous. The Alarm Silenced LED will be lit. Note: Do not reset the panel until the alarm has been cleared. Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a predetermined time. To reset panel after alarm: When the alarm condition is corrected, return the panel to normal standby operation by pressing the System Reset switch. Trouble is indicated by: System Trouble LED flashes LCD will display trouble conditions Panel buzzer sounds Trouble Operation To silence the trouble buzzer: Press the Trouble Silence switch. The Trouble Silenced LED lights and the specific trouble LED(s) may change to continuous display. When the trouble condition has been cleared, you may need to reset the panel to restore to a normal standby condition. Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to initiate a fire alarm sequence Normal Standby Condition The green AC Power On LED will be lit and no other indicators on. For service, contact: Telephone Number: Frame these instructions and mount them near the control unit for operator reference. P/N

21 FS-RD OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the System Alarm LED flashes, LCD will display alarm conditions and the buzzer sounds. Local audible and visual signals and remote alarm signals operate. When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department. Authorized Personnel Only To silence the alarm: To silence the notification appliances after evacuation, where permitted, turn the Button Enable keyswitch to the ON position and press the Alarm Silence switch. The notification appliances and buzzer will be silenced, and LED indications will change from flashing to continuous. The Alarm Silenced LED will be lit. Note: Do not reset the panel until the alarm has been cleared. Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a predetermined time. To reset panel after alarm: When the alarm condition is corrected, return the panel to normal standby operation by turning the Button Enable keyswitch to the ON position and then pressing the System Reset switch. Trouble is indicated by: System Trouble LED flashes LCD will display trouble conditions Buzzer sounds Trouble Operation To silence the trouble buzzer: Turn the Button Enable keyswitch to the ON position and press the Trouble Silence switch. The System Trouble LED changes from flashing to continuous display. When the trouble condition has been cleared, you may need to reset the panel to restore to a normal standby condition. Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to initiate a fire alarm sequence Normal Standby Condition The green Power On LED will be lit and no other indicators on. For service, contact: Telephone Number: Frame these instructions and mount them near the annunciator for operator reference. P/N

22 CONTROL UNIT INSTALLATION PARTS SUPPLIED Back-box Assembly (black or red) Door Assembly (black or red) Transformer Assembly (120VAC) #6-32 Locking Nuts (6) Front Plate Assembly #6-32 x 1/4 Screws (16) Main Board #8-32 Self-tapping Screw, (4) Display Board 24K Ohm 1/2W Resistor (4) Cable Assembly, 16 Pin Screwdriver Clear Lexan Window Owner s Manual Overlay Operating Instructions Programming Keypad 120 Ohm 1/2W Resistor (2) The fire alarm control unit must be mounted in a properly accessible location as required by applicable codes. Any auxiliary battery box or other accessory not connected through a protective device or a circuit designed for remote connection must be within the same room and connected through electrical conduit. Installation is to be done only by qualified personnel who have thoroughly read and understood these instructions. CAUTION It is recommended that the printed circuit boards be removed for any procedure that may cause dust, metal shavings, grease or any such matter that may affect the circuit boards and/or parts. There may be several sources of power into the control unit. Each source must be disconnected prior to installing or removing modules, connecting or disconnecting wiring, and programming jumpers. CONTROL UNIT LOCATION The control unit should be located near an exit at ground level, where the normal ambient temperature is maintained within the control unit specification (See General Specifications in Section III). The unit should be in an area that is free of dust, vibration, moisture and condensation. ENCLOSURE MOUNTING Follow the appropriate instructions for surface or semi-flush mounting. P/N

23 A. Surface Mounting Instructions To mount the enclosure: 1. Mount the enclosure at a convenient height for viewing indicators and operating switches. 2. Use four #10 lag screws (not supplied) to secure the control unit to the wall. The screw type and length must support the control unit, options and battery set. Note: You may need a different screw type, depending on the wall material. 3. Any auxiliary power supply or battery enclosure may be mounted immediately below the main enclosure, close nipple, allowing a minimum of 1 inch in between the enclosures for clearance between the doors. Keeping the wire run to the control unit short will keep the voltage drop to a minimum. P/N

24 B. Semi-Flush Mounting Instructions To mount the enclosure: 1. Mount the enclosure at a convenient height for viewing indicators, and operating switches. 2. Use four #10 lag screws (not supplied) to secure the control unit to the wall. The screw type and length must support the control unit, options and battery set. Note: You may need a different screw type, depending on the wall material. 3. The back-box can be mounted up to 3 1/2 inches into the wall. Place the semi-flush trim around the back-box and affix to the wall with four #10 x 3/4 inch wood screws (provided with trim). Note: You may need a different screw type, depending on the wall material. 4. Any auxiliary Power Supply or battery enclosure may be mounted immediately above or below the main enclosure, close nipple, allowing a minimum of 3 inches in between the enclosures for clearance between the semi-flush trims. Keeping the wire run to the control unit short will keep the voltage drop to a minimum. P/N

25 C. Knock-Outs 1. To prepare the enclosure for electrical wiring, break out the appropriate conduit entry points. Note the wiring diagram requirements for non-power limited and power limited wiring separation. 2. Attach conduit (if required) and run wires as required. Label each field cable for future reference. D. Main Board Installation 1. Secure the board to the back of enclosure using six of the provided #6-32 x 1/4 screws. E. AC Supply Connection 1. Wire the AC supply to terminal block TB2 on the main board. The supply should originate from a separate, fused circuit. It should be provided with a breaker or other means of isolation. 2. Observe the wiring order -- the bottom terminal is ground and must be wired back to the electrical panel ground (earth) bonding point or another good ground acceptable to the authority having jurisdiction and the electrical inspector. The neutral wire must be taken back to the electrical panel neutral distribution bar and must not be grounded. /!\ Dangerous voltages will be present on this terminal block and on other components surrounding it and the transformer when the AC supply is turned on. Do not touch. P/N

26 F. Transformer Installation 1. Place the transformer assembly over the studs on the left side of the enclosure. Mounting the transformer can be accomplished before mounting the enclosure if desired. 2. Secure the transformer using four #6-32 locking nuts. 3. Plug the transformer assembly into connector P5 on the Main Board. G. Front Plate Assembly 1. Secure Display Board to Plate Assembly using ten #6-32x1/4 screws. 2. Apply Overlay to Plate Assembly. H. Front Plate Mounting 1. Plug the Cable Assembly into connector P4 of the Display Board and to connector P1 of the Main Board. 2. Secure the Front Plate Assembly to backbox using four #8-32 self-tapping screws. P/N

27 I. Door Assembly 1. Secure the Lexan window to door assembly using four #6-32 locking nuts. 2. Place the Door Assembly onto hinges of the Back-box Assembly. J. Battery Installation Warning: Improper battery connections or shorting battery terminals may damage the system and/or batteries and may cause personal injuries. Place the batteries in the space provided in the bottom of the back-box. If larger than 7 AH battery set is required, a separate enclosure must be used. The Siemens Model BB-55 may be used for battery sets 55 AH and smaller. The FS-100 battery charging circuitry can only support systems requiring up to 38 AH battery sets. The control unit uses a 24V battery set. Connect the two 12V batteries (or four 6V batteries) in series with #12 AWG wire, minimum. Route the battery leads to the left of the enclosure and up to the battery termination block, TB5. The battery leads are not power-limited. Observe polarity. Connect the B- terminal from the main board into the black or - terminal of the battery set and the B+ terminal from the main board into the red or + terminal of the battery set. K. Powering the Control Unit Apply AC power to the control unit. AC POWER ON LED, SYSTEM TROUBLE LED, and the trouble buzzer should be on. P/N

28 L. Checking Supervised Circuits To check the supervised circuits of the control unit: 1. Place a 24K ohm resistor (color-coded: red, yellow, orange) across each set of NAC terminals. 2. Push SYSTEM RESET button. 3. The SYSTEM TROUBLE LED, and the trouble buzzer should be off. 4. Discard 24K ohm resistors after initial testing is complete M. Optional Modules Follow the installation instructions provided in Appendix D. N. System Wiring Before connecting the field wiring, check the wiring for opens, shorts, grounds and stray voltages. Warning: Damage may result if a high voltage insulation tester is used on wiring while connected to the control unit. Terminate the field wiring to the main board in accordance with the diagrams in Section V and the system design documents. NOTE: All wiring must be in accordance with local codes and the National Electrical Code. Use only FPL, FPLR and/or FPLP as described in Article 760 of the National Electric Code. O. Check System Operation Check for proper operation of all the system functions. See Section II for Operation Instructions. P/N

29 SYSTEM WIRING Basic system wiring and detector siting must be in accordance with NFPA 72 or other instructions from the appropriate local authority. Unit connections and limitations are as indicated on the wiring diagram included below. Devices that may be satisfactorily used with the control unit are shown in the compatible device listing in Appendix B. Wire reference data are included in Appendix A. CONTROL UNIT WIRING OVERVIEW The overall arrangement of boards in the control unit is shown in the following diagram * 1. Main Board 2. FS-DACT board or FS-MT board * (Note: When using FS-DACT, the FS-232 cannot be used) 3. FS-232 RS-232 Interface Board P/N

30 WIRING SEPARATION All high voltage and non-power limited wiring must be kept separate from power limited wiring. A ¼ separation must be maintained, with high voltage and non-power limited wiring running in separate conduit openings from power limited wiring. A C 1 3 E 2* F A. Non-power limited - High Voltage (AC power) or B B. Non-power limited - High Voltage (AC power) or A C. Power limited D. Non-power limited (Battery If external enclosure required) E. Non-power limited (Phone line or local energy box) F. Power limited or G G. Power limited or F B D G PRIMARY AND SECONDARY POWER WIRING The AC main connections and the battery connections must be made along the left-hand side of the board. Route all high voltage and non-power limited wiring together and away from power limited wiring. 120VAC 60Hz 1.3A max., Supervised Non-Power Limited AC N GND Keep All Non-Power Limited Wiring Separate from Power Limited Wiring 24V Battery Set (7 to 38AH) Supervised Non-Power Limited P/N

31 STATUS RELAYS AND AUXILIARY POWER OUTPUTS WIRING The right lower edge of the main board provides for connection of contacts and auxiliary power connections. Relay Designation: A Common O Normally Open C Normally Closed ALARM SUPERVISORY TROUBLE A O C A O C A C O R Status Relay Contacts (Shown in normal standby condition) max., Resistive For Power Limited Source, Unsupervised Auxiliary Power Outputs 0.4A nominal Unsupervised, Power Limited (Maximum current of all auxiliary outputs, RS485 Circuit and option boards is 0.5A.) System Power Requirement Calculations Device Item Max.(Amps) Total (Amps) FS-100 Control Unit Addressable Device Circuit Power # of Devices X Amps Auxiliary Power Outputs * Depends on devices installed FS-MT Municipal Tie Board FS-232 RS232 Communication Board FS-DACT Dialer Communicator Board FS-RD Remote LCD Annunciator * FS-RU/RE8 Serial Relay Unit * FS-SAU/SAE16 Serial Annun. Unit * Total must not exceed 0.75 Amps Auxiliary Power Supply * Connect a UL Listed auxiliary supply when the power requirement calculation indicates that an additional source is required. Battery Size Calculations For calculation of battery size requirements see appendix A. P/N

32 NAC WIRING At the right hand side of the main board the terminal blocks are used for the connection of notification appliances. Four individual NACs marked A through D are provided and the polarity shown is when the NAC is activated. 24K 1/2W Notification Appliance Circuit - Style Y, Class B + Supervised, Power Limited See P/N for Compatible Devices Polarity shown in activated condition Notification Appliance Circuit - Style Z, Class A + Supervised, Power Limited See P/N for Compatible Devices See Typical Wiring above See Typical Wiring above NAC Rating: Alarm Voltage: 24VDC nominal Max. Alarm Current: 1.5A Max. Ripple: 16VAC Max. Wire Voltage Drop: 1.0VDC Max. Standby Current: 1.0mA NOTE: The maximum current for all NACs is 2.5A. P/N

33 RS485 COMMUNICATIONS CIRCUIT The RS485 communication circuit can address up to 16 standard annunciators and/or 8 remote processors to drive graphic annunciation or relay modules. Devices on the circuit may be connected up to 4000 feet from the control unit. At the top of the main board the terminal blocks are used for the connection of remote serial devices. Serial Interface Circuit 24VDC nominal, 0.4A max. Wire Resistance-25 ohms/line (4000 max) Wire Type-Twisted Pair for data Supervised, Power Limited See Installation & Operation Manual Appendix D for Compatible Devices Remote Device Power When connecting devices on the RS485 communications circuit, a limited amount of current is available from the control unit. If more current supply is required for the connected devices, auxiliary power must be provided to each insufficiently powered device. Each address on the circuit must be fully powered from either control unit or auxiliary power (no combined source can be configured). Remote Device Data When connecting devices on the RS485 communications circuit, the data wires must be daisy chained and with no T-taps to preserve the integrity of the data. Each end (two places) must be terminated with a 120 ohm termination resistor. The following diagrams show typical examples using the proper wiring. P/N

34 ADDRESSABLE DEVICE CIRCUIT The basic configuration of the FS-100 control unit includes one addressable device circuit. The devices are polled by the control unit every few seconds and input or output functions communicated to determine device status or function. The control unit monitors all device addresses for alarm and trouble conditions. Addressable Device Circuit Style 4 or 6/7 Operation (set jumper P1 for proper style) 24VDC nominal Wire Resistance-20 ohms/line Supervised, Power Limited See Installation & Operation Manual Appendix B for Compatible Devices Style 6/7 4 Addressable Device Wiring Diagrams Proper connections for UL Listed compatible addressable devices are indicated below. Refer also to the instruction sheets packed with each device. Detectors and modules may be wired together according to several NFPA defined wiring styles. The wiring style that is appropriate for your installation should be determined from the relevant building codes and the Authority Having Jurisdiction. P/N

35 Style 4 wiring permits branching of circuit connections. The control equipment supervises modules because they are active and must respond periodically to the control unit s interrogation. ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA STYLE 4 SUPERVISED, POWER LIMITED TO OPTIONAL BRANCH(ES) OF LOOP CIRCUIT Note: Addressable Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 60 devices per addressable device circuit. Maximum of 20 devices per Isolator Module. Maximum of 12 Isolator Modules per addressable device circuit. P/N

36 Style 6 provides redundant communication paths. ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA STYLE 6 SUPERVISED, POWER LIMITED Note: Addressable Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 60 devices per addressable device circuit. Maximum of 20 devices between Isolator Modules. Maximum of 12 Isolator Modules per addressable device circuit. P/N

37 Addressable Detectors Each detector uses an address between 01 and 60 on the addressable device circuit. All device addresses are programmed into the device using the FS-DPI Device Programmer Unit. When installed, the device is regularly scanned by the control unit and checked for its current sensor status. The control unit will interpret and respond to the analog data as programmed. Each time the device is scanned the integral green visible LEDs will flash. In the event of an alarm condition the red LEDs will flash at a faster rate. FS-DPT Photoelectric Detector with Thermal The FS-DPT Photo/Thermal Detector allows programmable analog sensitivity with fixed thermal temperature of 135 F. It requires a DB-11, DB-X11RS, ADBX-11, AD-11P, or ADX-11PR base. FS-DT Thermal Detector The FS-DT Thermal Detector is a fixed 135 F detector. It requires a DB-11, DB-X11RS, ADBX-11, AD- 11P, or ADX-11PR base. FS-DP Photoelectric Detector The FS-DP Photoelectric Detector allows programmable analog sensitivity. It requires a DB-11, DB- X11RS, ADBX-11, AD-11P, or ADX-11PR base. DB-11, ADBX-11 and DBX-11RS Detector Bases The DB-11 base is a standard base designed for use with all FS-Series addressable and all 11-Series conventional detectors. The DB-11 provides connection to an optional remote LED lamp (RLI-1 or RLI-2 lamp). The ADBX-11 audible detector base is designed for use with all FS-Series addressable detectors. The ADBX-11 provides means to obtain a local audible alarm at the specific detector location. The integral horn on the ADBX-11 will sound when either the detector installed in the base has latched into the alarm state, or when criteria developed through logic programming is met. It will remain on until the detector is successfully reset, or the logic criteria are no longer met. A separate 24VDC power source is required to operate the integral horn. The DBX-11RS relay detector base is designed for use with all FS-Series addressable detectors. The DBX-11RS provides a local Form C relay at the specific detector location. The relay on the DBX-11RS will energize when either the detector installed in the base has latched in the alarm state, or when criteria developed through logic programming is met. It will remain energized until the detector is successfully reset, or the logic criteria are no longer met. The contact is rated at 3A, 120VAC, or 3A, 30VDC resistive. AD-11P and ADX-11PR Air Duct Housing The AD-11P Air Duct Housing and the ADX-11PR Air Duct Housing are used with the FS-DP addressable photo detector. Both housings provide a means to mount the FS-DP in an air duct for proper operation of the detector in an air stream. The ADX-11PR also has an integral Form C contact that operates similarly to the DBX-11RS relay base. LIM-1 Line Isolator Module The LIM-1 Line Isolator Module is designed for use with FS-Series addressable detectors and provides short circuit isolation on the indicating device circuit. Each LIM-1 can support up to 20 devices. The system is limited to 12 LIM-1s on the circuit. P/N

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual P/N 315-049353-1 Siemens Building Technologies Fire Safety TABLE OF CONTENTS INTRODUCTION... 1 CONTROL PANEL

More information

MPC-6000 / MPC-7000 / RND-2

MPC-6000 / MPC-7000 / RND-2 MPC-6000 / MPC-7000 / RND-2 Fire Alarm System Control Unit Installation, Operation and Maintenance Manual Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014 January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,

More information

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system s Data Sheet Fire Safety & Security Products Cerberus TM PRO Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

Desigo TM Fire Safety System A comprehensive fire-protection system

Desigo TM Fire Safety System A comprehensive fire-protection system s Desigo TM Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the 252- point and 504-point systems One (1) or (2)

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2003-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2003-12NDS Network Fire Alarm Control Unit offers modular components to meet a

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays AEGIS Conventional Fire Alarm-Suppression Control Unit FEATURES Agency Approvals FM Approved FM Approved to ANSI/UL 864, 9th edition FM Approved to ULC-S527-99 Other domestic U.S. approvals/listings pending/

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

SECTION FIRE ALARM SYSTEM PART 1 GENERAL

SECTION FIRE ALARM SYSTEM PART 1 GENERAL SECTION 16720 - FIRE ALARM SYSTEM PART 1 GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and

More information

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual FA-1000 SERIES Microprocessor-Based Fire Alarm Control Panel Installation and Operation Manual LT-600 Rev. 19 May 2017 Table of Contents 1.0 Introduction 8 1.1 About this Manual... 8 1.2 About the FA-1000...

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK

More information

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11 Fire Safety Installation Instructions Model ADBX11 Audible Base INTRODUCTION Model ADBX11 The SIEMENS Model ADBX11 Audible Base consists of a standard Series 11 base combined with an audible device. All

More information

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual 24 Viceroy Road Unit #6 & 7 Concord, Ontario L4K2L9 Phone (905) 660-7210 FAX: (905) 660-7204 MS-2410BC Conventional Fire Alarm Control Panel Programming, Installation, Maintenance and Operating Instruction

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL INSTALLATION & OPERATION MANUAL GAMEWELL P/N 71810 60 PLEASANT STREET ISSUE 3, 10/04/2000 ASHLAND, MA 01721 FIRMWARE VER. 7 THIS PAGE INTENTIONALLY

More information

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 Corporate Headquarters 800.845.6692

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL Fire Alarm Control Panel ESL

E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL Fire Alarm Control Panel ESL E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL 2501 Fire Alarm Control Panel ESL a product A PRODUCT of OF SENTROL sentrol Sentrol 1-800-547-2556 1 2 Sentrol 1-800-547-2556 TABLE

More information

Installation Instructions Model HZM

Installation Instructions Model HZM Installation Instructions Model Remote Conventional Zone Module INTRODUCTION The Model from is an intelligent device that connects a single zone of conventional devices to a DLC (FireFinder-XLS System)

More information

Installation Instructions Model SSD-C-REM

Installation Instructions Model SSD-C-REM Installation Instructions Model SSD-C-REM Remote System Status Display with Control ON ALARM SUPERVISORY SECURITY TROUBLE AUDIBLES SILENCED INTRODUCTION The SIEMENS Model SSD-C-REM is an optional FireFinder

More information

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview Edwards Signaling atalog u Fire Alarm ontrol Panels E-FS onventional Fire Alarm ontrol Panels Overview The E-FS fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA90621-2268

More information

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels GE Security EST Life Safety & ommunications onventional Small Building Solutions Overview The FireShield Plus fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

ARCHITECT AND ENGINEER SPECIFICATIONS

ARCHITECT AND ENGINEER SPECIFICATIONS s Desigo Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the 252- point and 504-point systems One (1) or (2) two-heightunit

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3 Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone: Cookson Company 1901 South Litchfield Road Goodyear, AZ 85338 Phone: 800-294-4358 www.cooksondoor.com O W N E R S M A N U A L MODEL FIREFLY III EXTENDED PERFORMANCE RELEASE DEVICE TABLE OF CONTENTS INTRODUCTION

More information

The MS-4412B/MS-4424B(E) FIRE ALARM CONTROL PANELS

The MS-4412B/MS-4424B(E) FIRE ALARM CONTROL PANELS The MS-4412B/MS-4424B(E) FIRE ALARM CONTROL PANELS 12 Clintonville Road, Northford CT 06472 DOCUMENT 15125 06/24/97 Rev: F1 ECN 97-192 Installation Precautions - Adherence to the following will aid in

More information

Conventional Fire Alarm Control Panel

Conventional Fire Alarm Control Panel Conventional Fire Alarm Control Panel INSTALLATION and OPERATION MANUAL NOTICE All information, documentation, and specifications contained in this manual are subject to change without prior notice by

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Harrington Signal HS-3100/3200 Fire Alarm Control Unit HARRINGTON SIGNAL INC. FIRE ALARM Harrington Signal HS-3100/3200 Fire Alarm Control Unit Installation Manual Revision 2 January 2009 Document # LT-2000HAR Table of Contents 1.0 Technical Information...

More information

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing Control Panels Control Panels for Commercial Applications Control panels provide the central processing and logic for an integrated system. In a typical system, there are four major functions: inputs,

More information

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) PATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) NAC ETENDER SUPPLIES Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web

More information

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual RAM-5-LCD Remote Annunciator Installation and Operation Manual LT-9 Rev. July Table of Contents. Introduction 6. Contact Us... 6. Mechanical Installation 8. Mounting Dimensions... 8. Configuring the Main

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TBLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Inputs 4 Outputs 4 LED Indications 4 User Keypad Functions 5 Engineer Keypad Functions 6

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE Cornell 100 Elmwood Ave. Crestwood Industrial Park Mountaintop, PA 18707 tel 800.233.8366 fax 800.526.0841 cornell@cornelliron.com O W N E R S M A N U A L M O D E L S F I R E G A R D B B FIREGARD BV EXTENDED

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..

More information

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08 GasScanner 4C Four Channel Monitor Operator s Manual MINT-0280-XX Rev. A 02/25/08 Product Warranty Matheson Tri-Gas., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

Installation Manual Premier 412/816/832. Issue 10

Installation Manual Premier 412/816/832. Issue 10 Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

Intelligent Single Loop Fire Alarm Control Panel

Intelligent Single Loop Fire Alarm Control Panel Intelligent Single Loop Fire Alarm Control Panel The CAX-CTL-1L Intelligent Single Loop Fire Alarm Control Panel is a member of the industry leading Axis AX Series Intelligent Fre Alarm Control Panels

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111 NETWORK FIRE ALARM CONTROL PANEL FX-2009-12NDS Description FX-2009-12NDS in a BB-5008R enclosure. Mircom s FleX-Net Series is a powerful intelligent networkable fire alarm solution designed with many levels

More information

CMP-2401B/CMP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual

CMP-2401B/CMP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual 10 Whitmore Road Woodbridge, Ontario L4L 7Z4 Phone (905) 856-8733 FAX (905) 856-9687 CMP-2401B/CMP-2402B Fire Alarm Control Panel Installation, Maintenance and Operating Instruction Manual P/N 50907:A1

More information

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX Page 1 of 10 Model 10807800 January 2014 ACCURATE ELECTRONICS INC PO BOX 1654 97075-1654 8687 SW HALL BLVD 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 WWW.ACCURATE.ORG Practice Section 10807800

More information

D1255RB/D1256RB/D1257RB

D1255RB/D1256RB/D1257RB D1255RB/D1256RB/D1257RB EN Installation Instructions Fire Keypads and Fire Alarm Annunciator D1255RB/D1256RB/D1257RB Installation Instructions Listings and Approvals Listings and Approvals UL 365 UL 609

More information

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE SAFE A N D SECURE Cornell 100 Elmwood Ave. Crestwood Industrial Park Mountaintop, PA 18707 Tel 800.233.8366 Fax 800.526.0841 Email: cornell@cornelliron.com O W N E R S M A N U A L M O D E L F I R E G A

More information

SFC-200 SERIES LCD FIRE ALARM PANEL

SFC-200 SERIES LCD FIRE ALARM PANEL SFC-200 SERIES LCD FIRE ALARM PANEL INSTALLATION INSTRUCTIONS LT-906SUM Rev.1 SFC-200 Series LCD Version Installation and Operation Manual Contents Industry Canada and FCC Notice... 1 Introduction...

More information

HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual

HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual NOTICE All information, documentation, and specifications contained in this manual are subject to change without prior notice

More information

CFP-2410B. Programming, Installation, Maintenance and Operating Manual. Conventional Fire Alarm Control Panel.

CFP-2410B. Programming, Installation, Maintenance and Operating Manual. Conventional Fire Alarm Control Panel. Conventional Fire Alarm Control Panel CFP-2410B Programming, Installation, Maintenance and Operating Manual Document 50974 2/18/04 Rev: B P/N 50974:B ECN 02-253 Fire Alarm System Limitations While a fire

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

Instruction Manual. CMP-12/24 Fire Alarm Control Panel. 12 Clintonville Road, Northford, CT DOCUMENT /11/96 REV: D1

Instruction Manual. CMP-12/24 Fire Alarm Control Panel. 12 Clintonville Road, Northford, CT DOCUMENT /11/96 REV: D1 12 Clintonville Road, Northford, CT 06472 Instruction Manual CMP-12/24 Fire Alarm Control Panel DOCUMENT 15819 3/11/96 REV: D1 P/N 15819:D1 ECN 96-047 Installation Precautions - Adherence to the following

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Intelligent 2 & 4 Loop Fire Alarm Control Panels

Intelligent 2 & 4 Loop Fire Alarm Control Panels Intelligent 2 & 4 Loop Fire Alarm Control Panels Advanced has combined the latest technology with many years of fire experience, to create the Axis AX Series Intelligent Fire Alarm Control Panels. The

More information

QA16 Addressable System

QA16 Addressable System QA16 Addressable System Operating Manual HORING LIH INDUSTRIAL CO., LTD. www.horinglih.com QA16 System Characteristics Each loop can connect with 250 devices. Easy system programming through PC to panel.

More information

AFP-100 Intelligent Fire Panel

AFP-100 Intelligent Fire Panel One Fire-Lite Place Northford, CT 06472 (203) 484-7161 (203) 484-7118 (Fax) AFP-100 Intelligent Fire Panel Installation, Programming and Operating Manual Document 51010 A 12/15/98 Revision PN 51010:A ECN

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS MXL-IQ Advanced Life Safety System ENGINEER AND ARCHITECT SPECIFICATIONS FirePrint Application Specific Fire Detection Capacity for up to 240 Intelligent Analog Detectors Expandable Up to a Stand Alone

More information

Installation Instructions Model DLC

Installation Instructions Model DLC Installation Instructions Model DLC Device Loop Card INTRODUCTION OPERATION The SIEMENS Model DLC Device Loop Card is the interface for connection of FireFinder-XLS smoke detectors, manual stations, monitor

More information

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE The Door Switch 11772 Westline Industrial Drive St. Louis, Mo 63146 (877) 998-5625 www.thedoorswitch.com Patent No. RE42,991 and RE44,039 CONTROL PANEL TRANSFORMER (SUPPLIED WITH CONTROL PANEL) NOTIFICATION

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

MIR2. System Operations Manual. P/N Rev 1.5 OCT98

MIR2. System Operations Manual. P/N Rev 1.5 OCT98 MIR2 System Operations Manual P/N 270676 Rev 1.5 OCT98 DEVELOPED BY COPYRIGHT NOTICE Mirtone, Inc. 90 Fieldstone Court Cheshire, CT USA 06410-1212 Tel: 1-(888) 649-9827 Fax: 203-250-1931 Copyright 1998

More information

D2071A. Operation & Installation Guide Fire Alarm Control Panel

D2071A. Operation & Installation Guide Fire Alarm Control Panel D2071A EN Operation & Installation Guide Fire Alarm Control Panel D2071A Operations & Installation Guide Contents Contents 1.0 Overview... 4 1.1 Communicator... 4 1.2 RFI and Lightning Protection... 4

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information