1 SIL-Safety Instructions SM/FEX300/FEX500/SIL-EN Rev. C ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 Electromagnetic Flowmeter Information about functional safety Measurement made easy

2 Change from one to two columns Short product description Electromagnetic Flowmeter for flow measurement of liquid, pulpy or pasty measurement media with electrical conductivity. Further information Additional documentation on ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 is available to download free of charge at FEP300 FEP500 FEH300 FEH500 Manufacturer ABB Automation Products GmbH Measurement & Analytics Dransfelder Str Göttingen Germany Tel: Fax: Customer service center Tel.: Mail: automation.service@de.abb.com 2 SM/FEX300/FEX500/SIL-EN Rev. C ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500

3 Change from two to one column Contents 1 Acronyms and abbreviations Standards and definitions of terms Standard IEC (2010), Part 1 and Dangerous failure Safety-related system Safety function Other applicable documents and papers Determine the Safety Integrity Level (SIL) The Flowmeter as part of the safety function system Device specific data related to functional safety Prerequisites operating the device functional safety compliant Setup Analog output Locking / Unlocking the configuration level Hardware write protection Configuration of the flowmeter transmitter Proof Test Calibration On-site test, performed by ABB service personnel ScanMaster Verification Repair SIL 2 certificate ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 SM/FEX300/FEX500/SIL-EN Rev. C 3

4 Change from one to two columns 1 Acronyms and abbreviations Abbreviation Designation Description HFT Hardware Fault Tolerance Hardware fault tolerance of the unit. Ability of a functional unit (hardware) to continue to perform a required function when faults or errors are prevailing. MTBF Mean Time Between Failures Mean time between failures. MTTR Mean Time To Restoration Mean time between the occurrence of an error in a unit or in a system and its repair. PFD Probability of Dangerous Failure on Demand Probability of hazardous failures for a safety function on demand. PFD AVG Average Probability of Dangerous Failure on Average probability of hazardous failures for a safety function on demand. Demand SIL Safety Integrity Level The international standard IEC defines four discrete Safety Integrity Levels (SIL 1 to SIL 4). Each level corresponds to a range of probability for the failure of a safety function. The higher the Safety Integrity Level of the safety-related systems, the lower the probability that they will not perform the required safety function. Low Demand Mode Low Demand Mode of operation Measurement type with low request rate. Measurement type for which the request rate for the safety-related system is not more than once a year and not greater than twice the frequency of the retest. DCS Distributed Control System Control system used in industrial applications to monitor and control decentralized units. HMI Human Machine Interface In this case, the HMI is a combined module consisting of an LCD display with or without a local keyboard. DTM Device Type Manager A DTM is a software module that supports specific functions for accessing device parameters, the setup and the operation of devices, and diagnostics. The DTM is not executable software. It requires an FDT container program in order to be activated. LRV Device Configuration Lower Range Value of the measurement range. URV Device Configuration Upper Range Value of the measurement range. DC Diagnostic Coverage Fraction of dangerous failures covered by cyclical diagnosis functions on runtime. Multidrop Multidrop Mode In Multidrop Mode, up to 15 field devices are connected in parallel to a single wire pair. The analog current signal simply serves to supply power to the devices in two-wire technology with a fixed current of 4 ma. 4 SM/FEX300/FEX500/SIL-EN Rev. C ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500

5 2 Standards and definitions of terms 2.1 Standard IEC (2010), Part 1 and 2 English Functional safety of electrical / electronic / programmable electronic safety-related systems (Target group: Manufacturers and Suppliers of Devices). German Funktionale Sicherheit sicherheitsbezogener elektrischer / elektronischer / programmierbarer elektronischer Systeme (Zielgruppe: Hersteller und Lieferanten von Geräten). 2.2 Dangerous failure A failure that has the potential to place the safety-related system in a dangerous state or render the system inoperative. 2.3 Safety-related system A safety-related system performs the safety functions that are required to achieve or maintain a safe condition, e.g., in a plant. Example: pressure meter, logics unit (e.g., alarm signalling unit) and valve form a safety-related system. 3 Other applicable documents and papers The following documentation must be available for the flowmeter. These documents include details about functional specifications of the analog output and how to operate and configure the device. Document name CI/FEX300/FEX500 OI/FEX300/FEX500 Document type Commissioning Instruction Operating Instruction For devices in explosion-proof design, the Safetey Instructions must also be observed. Document name SM/FEX300/FEX500 Document type Safety Instructions 2.4 Safety function A specified function that is performed by a safety-related system with the goal, under consideration of a defined hazardous incident, of achieving or maintaining a safe condition for the plant. Example: limit pressure monitoring ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 SM/FEX300/FEX500/SIL-EN Rev. C 5

6 4 Determine the Safety Integrity Level (SIL) The achievable Safety Integrity Level for a device certificated according EN route 2S and 2H is determined by the following safety-related parameters: Average probability of hazardous failures for a safety function on demand (PFD AVG ) Hardware Fault Tolerance (HFT) Table below shows the achievable Safety Integrity Level (SIL) based on the Average Probability of Failure on Demand (PFD AVG ) for the complete safety function system consisting of the Flowmeter, the Logics Unit and the Actuator. Safety Integrity Level (SIL) PFD AVG (low demand mode) < < < < 10-1 Table below shows the achievable Safety Integrity Level (SIL) for the complete safety-related system for type B systems depending on the Hardware Fault Tolerance (HFT). Type B systems are, for example, sensors with complex components such as microprocessors (see IEC 61508, Part 2). Hardware Fault Tolerance (HFT) SIL 1 SIL 3 SIL 4 SIL 2 (low demand mode) SIL 2 (high demand mode / continuous mode) NOTICE ProcessMaster and HygienicMaster flowmeter fulfill HFT = 0 and are applicable for safety-related systems as per table above. In low demand mode the demand rate for the safety-related system is not more than once a year and not greater than double the frequency of the periodic test. 6 SM/FEX300/FEX500/SIL-EN Rev. C ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500

7 5 The Flowmeter as part of the safety function system Fig. 1: Safety function (e.g. min / max flowrate monitoring) with flowmeter as a sub-system a ProcessMaster or HygienicMaster b Notebook with configuration Tool such as SMART VISION c FSK-Modem d Handheld terminal e Automation System, Logic-Unit, PLC, alarm signalling unit, etc. f Actuator The Flowmeter transmitter generates an analog signal ( ma) proportional to the flowrate. The analog signal is fed to a downstream logics unit such as a PLC or an alarm signalling unit, and is monitored for exceeding a specified maximum or minimum value. NOTICE The safety-related signal is the ma analog output signal of the flowmeter transmitter. All safety functions refer exclusively to this analog output (terminals 31 / 32) Device specific data related to functional safety Term Value DeviceType ProcessMaster FEP300, FEP500, HygienicMaster FEH300, FEH500 Firmware Level from to Hardware Level Electronics compartment Part number D674A903U01 Rev. 05 to 13 Par tnumber D674A904U01 Rev. 05 to 13 Part number D674A905U01 Rev. 05 to 13 Part number D674A906U01 Rev. 05 to 13 Type of Assessment Proven in Use Assessment according IEC route 2S Hardware Fault Architecture Route 2H according to IEC Tolerance SIL capability SIL2 (Low demand mode) HFT 0 Component Type B Failure Rates SIL Detector OFF ON DC 71.1 % 82.6 % PFD AVG after 10 years with Proof Test Interval 2,65E-03 1,51E-03 of 1 year and Proof Test Coverage of 90 % (valid for FEX311, FEX511, FEX315, FEX515, FEX325, FEX525) PFD AVG after 6 years with Proof Test Interval of 2,09E-03 1,20E-03 1 year and Proof Test Coverage of 90 % (valid for FEX321, FEX521) λ SD 0 FIT 0 FIT λ SU 943 FIT 943 FIT λ DD 937 FIT 1070 FIT λ DU 317 FIT 181 FIT NOTICE The configuration menu of the device includes a parameter called SIL Detector. To assure PFD value as per table above, the Detector has to be set accordingly. ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 SM/FEX300/FEX500/SIL-EN Rev. C 7

8 NOTICE The listed failure rates λ SD, λ SU, λ DD and λ DU depend on the meter design (standard or high temperature design). The listed failure rates λ SD, λ SU, λ DD and λ DU are valid for ambient temperatures up to 45 C. For higher ambient temperatures up to 60 C, the failure rates and the PFD AVG must be multiplied with a factor of 2.5. See diagram below C 45 C 25 C Prerequisites operating the device functional safety compliant The analog signal of the transmitter can be considered to be safe after 30 minutes (warm up time). A dangerous error is an error during which the output analog output of the transmitter no longer responds to the input signal or deviates by more than 2 % from the maximum flowrange Q max DN. For Q max DN see device nameplate or refer to instruction manual. The maximum reaction time of the device on error is less than 3 hours. The response time of the current output depends on the parameterization (Noise Filter settings and Damping) and is less than 5 Minutes. 90 C 130 C 2 G11926 Fig. 2: Standard temperature design 1 Ambient temperature 2 Fluid temperature 3 Failure rates and PFD AVG to be multiplied with a factor of Failure rates and PFD AVG as per table 1 60 C 3 45 C 4 25 C 140 C 180 C 2 G11927 Fig. 3: High temperature design 1 Ambient temperature 2 Fluid temperature 3 Failure rates and PFD AVG to be multiplied with a factor of Failure rates and PFD AVG as per table 8 SM/FEX300/FEX500/SIL-EN Rev. C ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500

9 Change from two to one column 6 Setup 6.1 Analog output The status of this analog output (4 20 ma output) during alarm conditions, can be configured either to go to a high alarm level or to a low alarm level. (See instruction manual). For high alarm level, a range from ma can be assigned to the analog output. For low alarm level, a range from ma can be assigned to the analog output. NOTICE The safety function of the automation system must be able to detect errors that result in high alarm level as well as those that result in low alarm level. The analog output signal of the transmitter can be configured as active mode or as passive mode. With the analog output configured passive mode, the external supply power of the 20mA loop must be capable to provide the required voltage level even in case of a high alarm level. NOTICE After completion of the parameter configuration, the safety function has to be checked. The transmitter software menu allows for simulation of the analog output. See Instruction manual. Behavior during operation and failure is described in the operating instructions. 6.2 Locking / Unlocking the configuration level WARNING Unauthorized changes of the parameter settings may affect the safety function. This device can be configured through the local Keypad or using HART communication. During configuration and in case of simulation and driving the device in HART Multidrop Mode, the device is not safety compliant. Once configuration is completed, the device must be protected against unauthorized access. Refer to Instruction manual set hardware write switch to ensure the keypad is locked and write protection through HART is enabled too. With the hardware write protection switched to ON, try to alter a parameter to make sure the write protection mechanism is enabled properly. To lock the device access menu Device Setup / Access Control and set the password of the corresponding log in level. Menu / parameter Value range Description Device Setup /...Access Control Standard Password Alphanumeric Enter the password for the "Standard" access level. Advanced Password Alphanumeric Enter the password for the "Advanced" access level. Read Only Switch Display only (ON / OFF) Display the setting of the configuration of the Read Only switch (BR902 - hardware write protection) ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 SM/FEX300/FEX500/SIL-EN Rev. C 9

10 6.2.1 Hardware write protection In addition to the software password protection, it is possible to enable a hardware write protection. 2 A 1 B 2 A 1 B Fig. 4: Jumper for hardware write protection A Integral mount design B Remote mount design a Housing cover b Jumper (BR902) for hardware write protection G Switch off power supply. 2. Open the housing cover. 3. Remove the mounting screws for the transmitter electronics unit. 4. Pull out the transmitter electronics unit. 5. Set jumpers on backplane in accordance with the following table. Jumper Number Function BR902 Read only Hardware write protection active 6. Reinstall the transmitter electronic unit in reverse order. 10 SM/FEX300/FEX500/SIL-EN Rev. C ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500

11 6.3 Configuration of the flowmeter transmitter Note Some parameter settings may affect the safety function. Changing these parameters, the safety function has to be checked again. Refer to Commissioning Instruction (CI/FEX300/FEX500) and Operating Instruction (OI/FEX300/FEX500) for Settings and Installation Instructions. Menu / parameter Description Action Diagnostics /...Diagnosis Control / Sil Detection Sil Detection To assure PFD value as per table in chapter 2.1, the Detector has to be set accordingly. Check Safety Function. Easy Setup Q [units] Select the engineering unit for flowrate indication in the display. Qmax Select the flow range for forward and reverse flow. Default setting: 1 x QmaxDN. Damping Select the damping. The setting relates to 1 Τ (Tau). The damping affects the analog output response time. Default setting: 1 second. Iout at Alarm Status of the analog output during error conditions can be configured either to go to a high alarm level or to a low alarm level. (See instruction manual). Default setting: High. Low Alarm Value Analog output Low alarm level. A range from 3,5 to 3,6mA can be assigned to the analog output. Default setting: 3.5 ma. High Alarm Value Analog output High alarm level. A range from 21 to 23mA can be assigned to the analog output. Default setting: 21.8 ma. System Zero Manual adjustment of the system zero. Cable length Enter the signal cable length between the transmitter and the flowmeter sensor. For devices with a compact design (FEP311, FEH311, FEP315, FEH315) 0.01 m must be entered. Device Setup /...Sensor Qmax2 See Qmax. Range Mode Manual switchover between flow range Qmax and Qmax2. ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 SM/FEX300/FEX500/SIL-EN Rev. C 11

12 Menu / parameter Description Action Device Setup /...Transmitter /...Units Custom Vol. Type Select whether the user-defined flow unit is displayed as a mass flow (with density) or volume flow (without density). Check Safety Function. When a mass flow unit is selected, the corresponding density must be set. Custom Vol. Factor Enter the factor for a user-defined flow unit. The factor relates to the flow per liter. Check Safety Function. Device Setup /...Transmitter Density To show the flowrate in massflow units a fixed density must be configured to convert the volume flowrate into mass flowrate. Device Setup /...Transmitter /...Low Flow Cut Off Flow Cut Off Level Threshold for low flowrate monitoring. Check Safety Function. If the flowrate is below threshold, the flow is not measured. The current output is set to zero. Hysteresis Set the hysteresis for the low flow cut off. Check Safety Function. Device Setup /...Transmitter /...Operating Mode Meter Mode Measuring direction for the flowmeter. Forward only : The device measures only forward flow direction. Forward and Reverse : The device measures both directions. Check Safety Function. Device Setup /...Transmitter / Noise Reduction Noise Reduction Enables noise filtering. Filtering increases the response time of the SIL relevant ma output. Input/Output /...Current Output Iout at EP Alarm Iout at Flow >103% Iout Mode Status of the analog output during empty pipe condition. Off: Error is not output at the current output. Q = 0 %: The current output assumes the value for No flow. High Alarm: The current output assumes the value for High Alarm. Low Alarm: The current output assumes the value for Low Alarm. Default setting: Off. Status of the analog output when flowrate exceededs 103 % of the flow range end value set. Off: Error is not output at the current output. High Alarm: The current output assumes the value for High Alarm. Low Alarm: The current output assumes the value for Low Alarm. Default setting: Off. Select the operating mode for the current output ma - 4 ma = No flow - 20 ma = Maximum flow ma - 4 ma = Maximum reverse flow - 12 ma = No flow - 20 ma = Maximum forward flow 12 SM/FEX300/FEX500/SIL-EN Rev. C ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500

13 Change from one to two columns Menu / parameter Description Action Process Alarm /...Group Masking Maintenance Required Alarm messages are divided into 3 groups. Masking is not allowed for Function Check Out of Specification Maintenance, Function Check and Out of Spec. Masking of a group results in no error message any longer for errors belonging to this group. parameter setting for a Functional Safety application. Parameter has to be switched to OFF. Process Alarm /...Individual Masking Min Flowrate Alarm Individual alarm messages can also be masked. Max Flowrate Alarm These alarms are not included in the masking of a group such a Maintenance. Flow >103% Masking of an individual alarm results in no error message any longer for this Com Controller Alarm alarm. Empty Pipe Detector completed Process Alarm / Alarm Simulation Simulation Mode Manual simulation of measured values. The output values correspond to the simulated flowrate entered. The Configuration information is displayed in the lower line of the display. Restore the Simulation mode to Off once The values in the Value range column can be simulated. Make sure Simulation mode is switched to Off once Diagnostics /...Diagnosis Control /...Empty Pipe Detector Manual Adjust EP Manual adjustment of the Empty Pipe Detector function. Flow Cut Off Level Threshold of the empty pipe detection. Diagnostics /...Diagnosis Control /...Sensor Measurements Coil R. Max Alarm Set the maximum limit value for the coil resistance. Exceeding this limit results in an alarm. Coil R. Min Alarm Set the minimum limit value for the coil resistance. Exceeding this limit results in an alarm. ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 SM/FEX300/FEX500/SIL-EN Rev. C 13

14 Change from two to one column 7 Proof Test In accordance with IEC61508, the safety function of the measuring device must be checked at appropriate time intervals. The operator must determine the checking interval and take this into account when determining the probability of failure PFDavg of the flowmeter. The test must be carried out in such a way that it verifies correct operation of the device. Testing the device can be performed in the following steps: 7.1 Calibration Calibrating the device in a certified calibration rig checking the analog output safety function results in a > 98 % diagnostic coverage detecting undetected failures. 7.2 On-site test, performed by ABB service personnel An on-site test, performed by ABB service personnel results in a > 90 % diagnostic coverage detecting undetected failures. 8 Repair To ensure the safety related function, repairs have to be performed by ABB. Replacing modular components by original ABB spare parts is permitted if personnel was trained by ABB for this purpose. The "Declaration of contamination and cleaning" must be enclosed when returning the defective device. Refer to instruction manual for further details. Adress: ABB Automation Products GmbH Measurement & Analytics Dransfelder Str Goettingen Germany Tel: Fax: ScanMaster Verification Performing a ScanMaster Verification results in a > 50 % diagnostic coverage detecting undetected failures. If the test is not passed, the device may no longer be used as part of a protective system. The influence of systematic faults on the safety function are not covered by the test and must be examined separately. Systematic faults can be caused, for example, by medium properties, operating conditions, build-up or corrosion. 14 SM/FEX300/FEX500/SIL-EN Rev. C ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500

15 9 SIL 2 certificate ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 SM/FEX300/FEX500/SIL-EN Rev. C 15

16 Notizen Contact us ABB Limited Measurement & Analytics Howard Road, St. Neots Cambridgeshire, PE19 8EU UK Tel: +44 (0) Fax: +44 (0) Mail: ABB Inc. Measurement & Analytics 125 E. County Line Road Warminster, PA USA Tel: Fax: Note We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB. Copyright 2017 ABB All rights reserved 3KXF231304R4801 SM/FEX300/FEX500/SIL-EN Rev. C ABB Automation Products GmbH Measurement & Analytics Dransfelder Str Goettingen Germany Tel: Fax: Mail: vertrieb.messtechnikprodukte@de.abb.com ABB Engineering (Shanghai) Ltd. Measurement & Analytics No. 4528, Kangxin Highway, Pudong New District Shanghai, , P.R. China Tel: +86(0) Fax: +86(0) Mail: china.instrumentation@cn.abb.com

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy ABB MEASUREMENT & ANALYTICS SIL-SAFETY MANUAL TTH300, TTF300 Temperature transmitter Additional instructions for IEC 61508 compliant devices Measurement made easy TTH300 TTF300 Introduction TTH300, TTF300

More information

Pressure Transmitter cerabar M PMC 41/45 cerabar M PMP 41/45/46/48 with Output Signal ma/hart

Pressure Transmitter cerabar M PMC 41/45 cerabar M PMP 41/45/46/48 with Output Signal ma/hart Safety Manual SD 172P/00/en 71036063 Pressure Transmitter cerabar M PMC 41/45 cerabar M PMP 41/45/46/48 with Output Signal 4...20 ma/hart Functional Safety Manual Application Pressure measurement (e.g.

More information

Thermal Mass Flowmeter Sensyflow FMT500-IG

Thermal Mass Flowmeter Sensyflow FMT500-IG Pos: 1 /Titelblätter / Copyright/SIL/Durchfluss/SIL-Handbuch Sensyflow FMT500-iG Analog / HART @ 22\mod_1222423613156_3101.doc @ 218417 @ Pos: 2 /Titelblätter / Copyright/Copyright-Seite @ 32\mod_1247732119296_3101.doc

More information

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma Functional Safety Manual Deltapilot S FMB70 Level and Pressure Measurement with Output Signal 4...20 ma Application Use for process pressure measurement in aggressive and non-aggressive gases, vapours

More information

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions Introduction 1 General safety instructions 2 SITRANS Temperature transmitter Device-specific safety instructions 3 Appendix List of Abbreviations/Acronyms A B Product Information Supplement to Operating

More information

Proservo NMS5- / NMS7-

Proservo NMS5- / NMS7- Functional Safety Manual Proservo NMS5- / NMS7- Tank gauge for Liquid level measurement with 4 to 20mA Output or with Alarm Relay Contact Output Application Operating minimum (e.g. dry run protection),

More information

Cerabar S PMC71, PMP71, PMP75

Cerabar S PMC71, PMP71, PMP75 Functional Safety Manual Cerabar S PMC71, PMP71, PMP75 Process Pressure and Level Measurement with Output Signal 4...20 ma Application Use for process pressure measurement (e.g. limit pressure monitoring)

More information

Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with ma output signal

Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with ma output signal Safety Manual SD 159P/00/en Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with 4...20 ma output signal Functional safety manual Application Pressure measurements (e.g. limit pressure

More information

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal Safety Manual SD 158P/00/en Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with 4...20 ma output signal Functional safety manual Application Overspill protection or

More information

ProcessMaster, HygienicMaster FEX300, FEX500

ProcessMaster, HygienicMaster FEX300, FEX500 SM/FEX300/FEX500/ATEX/IECEX-EN ProcessMaster, HygienicMaster FEX300, FEX500 ATEX / IECEx Zone 1, 2, 21, 22 Safety instructions for electrical apparatus in potentially explosive areas, in accordance with

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Detcon FP-700 Combustible Gas Sensor Customer: Detcon The Woodlands, TX USA Contract No.: DC 06/08-04 Report No.: DC 06/08-04 R001 Version V1, Revision

More information

Functional Safety Manual June pointek CLS500/LC500

Functional Safety Manual June pointek CLS500/LC500 Functional Safety Manual June 2009 pointek CLS500/LC500 Introduction 1 Level Switch Pointek CLS500 SITRANS LC500 SIL Safety Manual Supplement to device manual General safety instructions 2 Device-specific

More information

Soliphant M with electronic insert FEM52

Soliphant M with electronic insert FEM52 Functional safety manual Soliphant M with electronic insert FEM52 Level Limit Measuring System Application Overfill protection or operating maximum detection of all types of solids in tanks to satisfy

More information

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017 STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT-25-05 Revision 4 September 2017 Honeywell Process Solutions Copyrights, Notices and Trademarks Copyright

More information

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS) SAFETY MANUAL Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS) Sensor Module (GTS) Transmitter (GTX) Detector (GT3000) SAFETY CERTIFIED GT3000

More information

Liquiphant S, Nivotester FDL60/61, FTL670

Liquiphant S, Nivotester FDL60/61, FTL670 Functional Safety Manual Liquiphant S, Nivotester FDL60/61, FTL670 Level limit measuring system FTL670 s Application Overfill protection or maximum detection of all types of liquids, to meet the particular

More information

United Electric Controls One Series Safety Transmitter Safety Manual

United Electric Controls One Series Safety Transmitter Safety Manual United Electric Controls One Series Safety Transmitter Safety Manual OneST-SM-02 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented

More information

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL SAFETY MANUAL PointWatch Eclipse Infrared Hydrocarbon Gas Detector SIL 2 Certified Model PIRECL Safety Certified Model PIRECL PointWatch Eclipse IR Gas Detector This manual addresses the specific requirements

More information

100 & 120 Series Pressure and Temperature Switches Safety Manual

100 & 120 Series Pressure and Temperature Switches Safety Manual 100 & 120 Series Pressure and Temperature Switches Safety Manual MECH-SM-01 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented

More information

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications SAFETY MANUAL Intelligent Sensors for H 2 S Gas Applications The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

Gammapilot M FMG60. Functional safety manual. Radiometric measurement technology Maximum point level detection

Gammapilot M FMG60. Functional safety manual. Radiometric measurement technology Maximum point level detection Functional safety manual Gammapilot M FMG60 Radiometric measurement technology Maximum point level detection Application Overfill protection or maximum point level detection of all types of liquids and

More information

Certification Report of the ST3000 Pressure Transmitter

Certification Report of the ST3000 Pressure Transmitter Certification Report of the ST3000 Pressure Transmitter Revision No.: 1.0 Date: Report Number: Product: Customer: Order Number: Authority: Responsible: 2006-Dec-12 SAS-128/2006T ST3000 Pressure Transmitter

More information

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update Technical Paper Functional Safety Update IEC 61511 Edition 2 Standards Update Functional Safety Update Table of Contents 1.0 Introduction 2.0 IEC 61511-1 changes 3.0 IEC 61511-2 changes 4.0 IEC 61511-3

More information

Certification Report of the ST 3000 Pressure Transmitter with HART 6

Certification Report of the ST 3000 Pressure Transmitter with HART 6 Certification Report of the ST 3000 Pressure Transmitter with HART 6 Revision No.: 2.4 Date: Report Number: 2010-Mar-18 SAS-190/2006T Product: ST 3000 Pressure Transmitter with HART 6 Customer: Order Number:

More information

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No User s Manual YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters Manual Change No. 16-045 Please use this manual change for the manuals listed below. 1. Applicable manuals, revised item, revised

More information

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300 Failure Modes, Effects and Diagnostic Analysis Device Designation: KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300 Pepperl+Fuchs GmbH Mannheim Germany Mannheim norm sheet 1 of 16 Released EDM checkout

More information

Functional Safety Manual Oil Leak Detector NAR300 System

Functional Safety Manual Oil Leak Detector NAR300 System SD01357G/08/EN/01.14 71255416 Products Solutions Services Functional Safety Manual Oil Leak Detector NAR300 System Application This system is designed to be installed in a pit, dike, plant, or sump pit

More information

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany FMEDA and Proven-in-use Assessment Project: Transmitter Supply Isolators KF**-CRG-*** Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 02/11-01 Report No.: P+F 02/11-01 R012 Version V2,

More information

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators Rev 0, November 17 2015 Page 1 of 9 Table of Contents 1 INTRODUCTION 3 1.1 Terms and abbreviations 3 1.2 Acronyms 4 1.3

More information

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

SAFETY MANUAL. Multispectrum IR Flame Detector X3301 SAFETY MANUAL Multispectrum IR Flame Detector X3301 SAFETY-CERTIFIED MODEL X3301 MULTISPECTRUM INFRARED DETECTOR This manual addresses the specific requirements and recommendations applicable to the proper

More information

Safety in the process industry

Safety in the process industry Products Solutions Services Safety in the process industry Simply reliable Table of contents Endress+Hauser: At home in the process safety Smart devices and concepts for hazardous areas Introduction to

More information

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland Scully Intellitrol Safety Manual Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options TÜVRheinland Functional Safety Type Approved FS IEC 61508 Certified SIL 2 / SIL

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Fireye Flame Sensor Module CE Flameswitch, model MBCE-110/230FR Company: Fireye Derry, NH USA Contract Number: Q09/10-26 Report No.: FIR 09/10-26

More information

PPA Michaël GROSSI - FSCE PR electronics

PPA Michaël GROSSI - FSCE PR electronics Functional Safety Component selection according to IEC61511 Title 2 Presentation Michaël GROSSI: Ex / SIL Product manager @ Degree in Instrumentation & Measurement More than 10 years experience in Functional

More information

SIPART. Electropneumatic positioner Functional safety for SIPART PS2. Introduction. General safety instructions 2. Device-specific safety instructions

SIPART. Electropneumatic positioner Functional safety for SIPART PS2. Introduction. General safety instructions 2. Device-specific safety instructions Introduction 1 General safety instructions 2 SIPART Electropneumatic positioner Device-specific safety instructions 3 Appendix List of Abbreviations/Acronyms A B Product Information Supplement to the manuals

More information

User Guide OI/FEX100HART EN Rev. A. WaterMaster FEX100 HART Field Device Specification

User Guide OI/FEX100HART EN Rev. A. WaterMaster FEX100 HART Field Device Specification User Guide OI/FEX100HART EN Rev. A WaterMaster FEX100 The Company We are an established world force in the design and manufacture of measurement products for industrial process control, flow measurement,

More information

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY-CERTIFIED Flame DETECTORs This manual addresses the specific requirements and recommendations applicable to the proper

More information

Proof Testing Level Instruments

Proof Testing Level Instruments Proof Testing Level Instruments Partial proof testing of level instruments can save millions of dollars while maintaining required safety ratings By Bill Sholette, Level Product Business Manager Endress+Hauser

More information

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB 2CMT2016-005511 rev

More information

Digital EPIC 2 Safety manual

Digital EPIC 2 Safety manual Safety manual Before installation these instructions must be fully read and understood Table of contents Safety manual... 1 1. Introduction... 1 1.1 Terms and abbreviations... 2 1.2 Acronyms... 2 1.3 Product

More information

Functional safety manual Liquiphant M/S with FEL57 and Nivotester FTL325P

Functional safety manual Liquiphant M/S with FEL57 and Nivotester FTL325P T T SD00231F/00/EN/14.14 71271294 Products Solutions Services Functional safety manual Liquiphant M/S with FEL57 and Nivotester FTL325P [Ex ia] [Ex ia] FTL325N FTL325N CH2 CH3 CH2 CH3 Level Limit Measuring

More information

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations

More information

SLG 700 SmartLine Level Transmitters Guided Wave Radar Safety Manual 34-SL Revision 4.0 December 2017

SLG 700 SmartLine Level Transmitters Guided Wave Radar Safety Manual 34-SL Revision 4.0 December 2017 SLG 700 SmartLine Level Transmitters Guided Wave Radar Safety Manual 34-SL-25-05 Revision 4.0 December 2017 Honeywell Process Solutions Copyrights, Notices and Trademarks Copyright 2017 by Honeywell, Inc.

More information

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. February Valves

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. February Valves Valves Guidelines Safety Integrity Level - SIL - Valves and valve actuators February 2009 VDMA German Engineering Federation Valves Manufacturers Association Chairman: Prof.-Dr.-Ing. Heinfried Hoffmann

More information

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511 TÜV Rheinland International Symposium in China Functional Safety in Industrial Applications October 18 19, 2011 in Shanghai China Safety Integrity Verification and Validation of a High Integrity Pressure

More information

Functional Safety Solutions

Functional Safety Solutions Demand Moore Reliability IEC 61508/61511 Solutions Line Card Functional Safety Solutions for Your Safety Instrumented System www.miinet.com Functional Safety Products Designed and Built for your Process

More information

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA Failure Modes, Effects and Diagnostic Analysis Project: 2088 Pressure Transmitter Customer: Rosemount Inc. Chanhassen, Minnesota USA Contract No.: ROS 06/10-18 Report No.: ROS 06/10-18 R001 Version V1,

More information

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark Failure Modes, Effects and Diagnostic Analysis Project: 9203 Solenoid / Alarm Driver Customer: PR electronics A/S Rønde Denmark Contract No.: PR electronics 06/03-19 Report No.: PR electronics 06/03-19

More information

FUNCTIONAL SAFETY MANUAL

FUNCTIONAL SAFETY MANUAL f u n c t i o n a l S a f e t y M a n u a l FUNCTIONAL SAFETY MANUAL Gassonic Surveyor and Gassonic Observer Ultrasonic Gas Leak Detectors The information and technical data disclosed in this document

More information

ABB MEASUREMENT & ANALYTICS DATA SHEET. C50 1/16 DIN controller / alarm unit

ABB MEASUREMENT & ANALYTICS DATA SHEET. C50 1/16 DIN controller / alarm unit ABB MEASUREMENT & ANALYTICS DATA SHEET C50 1/16 DIN controller / alarm unit 2 C50 1/16 DI N CON TROLL ER / AL ARM U NIT DS/C 50-E N RE V. M Measurement made easy C50 the 1/16 DIN controller to suit your

More information

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440) Safety Temperature Limiter STL 50 Certified to DIN EN 14597 (replaces DIN 3440) Features M For use as: STB Protection - temperature limiter ASTB Exhaust gas - protection - temperature limiter STW Protection

More information

FUNCTIONAL SAFETY MANUAL. Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector

FUNCTIONAL SAFETY MANUAL. Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector FUNCTIONAL SAFETY MANUAL Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector The information and technical data disclosed in this document may be used and disseminated only for the purposes

More information

Rosemount 2140:SIS Level Detector

Rosemount 2140:SIS Level Detector Rosemount 2140:SIS Level Detector Functional Safety Manual Manual Supplement Manual Supplement Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual..................................

More information

HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual

HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual Document No. SIL0008 Version 1.7 17/04/2018 1. Revision History: Revision Author Reviewed Approved Update Details Date 0.1 Klaus Lorentschitsch

More information

GMA200-MW4. User Manual. Gas detection controller for wall mounting

GMA200-MW4. User Manual. Gas detection controller for wall mounting User Manual GMA200-MW4 Gas detection controller for wall mounting GfG GESELLSCHAFT FÜR GERÄTEBAU MBH KLÖNNESTRASSE 99 44143 DORTMUND, GERMANY TEL. +49 / (0)231 / 564 00 0 FAX +49 / (0)231 / 516 313 INFO@GFG-MBH.COM

More information

Technical Manual for the Manual Alarm Call Point BG

Technical Manual for the Manual Alarm Call Point BG Technical Manual for the Manual Alarm Call Point BG Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, however, accept responsibility for damage, loss

More information

CoriolisMaster FCM2000

CoriolisMaster FCM2000 CI/FCM2000-EN CoriolisMaster FCM2000 EN English Commissioning Instruction Mass Flowmeter CoriolisMaster FCM2000 P R O F I PROCESS FIELD BUS B U S Neu Contents Mass Flowmeter CoriolisMaster FCM2000 Commissioning

More information

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors SAFETY MANUAL FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent

More information

Safety Manual. XNXTM Universal Transmitter. Fault Diagnostic Time Interval Proof Test Proof Testing Procedure

Safety Manual. XNXTM Universal Transmitter. Fault Diagnostic Time Interval Proof Test Proof Testing Procedure XNXTM Universal Transmitter Safety Manual Table of Contents SIL 2 Certificates Overview Safety Parameters Fault Diagnostic Time Interval Proof Test Proof Testing Procedure Revision 2 Table of Contents

More information

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015 Rosemount 2120 Functional Safety Manual Manual Supplement Manual Supplement Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual.................................. 1 1.2

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Type 95IR/95UV/95DS Flame Scanners Customer: FIREYE Derry, New Hampshire USA Contract No.: FIR 04/08-21 Report No.: FIR 04/08-21 R002 Version V1,

More information

IEC Functional Safety Assessment

IEC Functional Safety Assessment IEC 61508 Functional Safety Assessment Project: Detcon IR-700 Combustible Hydrocarbon Gas Sensor Customer: Detcon The Woodlands, TX USA Contract No.: Q13/06-003 Report No.: DC 13-06-003 R002 Version V1,

More information

FUNCTIONAL SAFETY CERTIFICATE

FUNCTIONAL SAFETY CERTIFICATE FUNCTIONAL SAFETY CERTIFICATE This is to certify that the X5000 & S5000 Fixed Gas Detector Range MSA The Safety Company manufactured by General Monitors 1000 Cranberry Woods Drive 26776 Simpatica Cir Cranberry

More information

Operating Guide Safe Torque Off

Operating Guide Safe Torque Off ENGINEERING TOMORROW Operating Guide Safe Torque Off VLT Frequency Converters vlt-drives.danfoss.com Contents Operating Guide Contents 1 Introduction 2 1.1 Purpose of the Manual 2 1.2 Additional Resources

More information

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74 AM54 Instruction Bulletin North American Installation Addendum Document Number PN25016 Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

More information

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System SAFETY MANUAL Open Path Hydrocarbon Gas Monitoring System The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

FUNCTIONAL SAFETY MANUAL

FUNCTIONAL SAFETY MANUAL FUNCTIONAL SAFETY MANUAL UltraSonic EX-5 Ultrasonic Gas Leak Detector The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent

More information

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA Failure Modes, Effects and Diagnostic Analysis Project: 3144P SIS Temperature Transmitter Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: ROS 04/08-19 Report No.: ROS 04/08-19 R003 Version V1,

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: 3144P 4-20mA HART Temperature Transmitter Device Label SW REV 1.1.X Customer: Rosemount Inc. (an Emerson Process Management company) Shakopee, MN

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Oldham OLCT 200 Transmitter Company: Industrial Scientific Corporation Oakdale, PA USA Contract Number: Q11/05-009 Report No.: IS 10/10-010 R001

More information

430128A. B-Series Flow Meter SIL Safety Manual

430128A. B-Series Flow Meter SIL Safety Manual 430128A B-Series Flow Meter SIL Safety Manual Copyrights and Trademarks Copyright 2016 Kurz Instruments, Inc. All rights reserved. No part of this publication may be reproduced or transmitted in any form

More information

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/ Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/09 Table Of Contents Interconnecting the HART Communicator with the Detector.... 1 HART Device Description Language.... 3 Detector Wiring.......................................

More information

Measurement of Safety Integrity of E/E/PES according to IEC61508

Measurement of Safety Integrity of E/E/PES according to IEC61508 Measurement of Safety Integrity of E/E/PES according to IEC61508 Mr. Chen Zhenkang TUV Rheinland Singapore 18. May. 2018 Singapore World Metrology Day 2018 1 Agenda 1. TÜV Rheinland: a Certification Body

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S Revised 04/13/16 SPECIFICATIONS - DETAILED PROVISIONS Section 17210 - Magnetic Flowmeters C O N T E N T S PART 1 - GENERAL... 1 1.01 GENERAL REQUIREMENTS... 1 1.02 PROJECT SPECIFIC REQUIREMENTS... 1 1.03

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: ST3000 pressure transmitter Customer: Honeywell International Inc. Fort Washington, Pennsylvania USA Contract No.: HON 06/05-18 Report No.: HON 06/05-18

More information

Functional Safety Manual Cerabar M PMC51, PMP51/55 Deltabar M PMD55 Deltapilot M FMB50/51/52/53

Functional Safety Manual Cerabar M PMC51, PMP51/55 Deltabar M PMD55 Deltapilot M FMB50/51/52/53 SD00347P/00/EN/03.16 71344568 Products Solutions Services Functional Safety Manual Cerabar M PMC51, PMP51/55 Deltabar M PMD55 Deltapilot M FMB50/51/52/53 Process pressure / Differential pressure, Flow

More information

Technical Report Proven In Use SITRANS P500

Technical Report Proven In Use SITRANS P500 Technical Report Proven In Use SITRANS P500, Industry Sector, Industry Automation Division, Sensors and Communication, PD PA PI R&D PM CRT Oestliche Rheinbrueckenstr. 50 76187 Karlsruhe, Germany Number:

More information

Simply reliable: Process safety from Endress+Hauser

Simply reliable: Process safety from Endress+Hauser Products Solutions Services Simply reliable: Process safety from Endress+Hauser Safety by choice, not by chance: Functional Safety Slide 1 Oil & Gas industry Hai-Thuy Industry Manager Oil & Gas Slide 2

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: 3144P SIS Temperature Transmitter Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: ROS 04/08-19 Report No.: ROS 04/08-19 R003 Version V2,

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Honeywell Temperature Transmitter STT650 with 4-20 ma Output Company: Honeywell International Inc. Field Products 512 Virginia Drive Fort Washington,

More information

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry 1. Introduction Author: Colin Easton ProSalus Limited ~ Independent Safety Consultants Within the United

More information

Safety Manual. XNX TM Universal Transmitter. Table of Contents SIL 2 Certificates Overview Safety Parameters

Safety Manual. XNX TM Universal Transmitter. Table of Contents SIL 2 Certificates Overview Safety Parameters XNX TM Universal Transmitter Safety Manual Table of Contents SIL 2 Certificates Overview Safety Parameters Fault Diagnostic Time Interval Proof Test Proof Testing Procedure Table of Contents 1 SIL 2 Certificate...3

More information

Mobrey Magnetic Level Switches

Mobrey Magnetic Level Switches Horizontal Float Switch Mobrey Magnetic Level Switches www.mobrey.com Horizontal Float Switch Contents Introduction Scope and Purpose of the Safety Manual...page 3 Skill Level Requirement...page 3 Terms,

More information

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition International Symposium in China Functional Safety in Industrial Applications 18 19 October 2011, Shanghai - China Functional safety according to IEC 61508 / IEC 61511 Important user information Major

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Phoenix Type 85UVF/IRF Flame Scanner Company: FIREYE Derry, New Hampshire USA Contract Number: Q08/04-57 Report No.: FIR 08/04-57 R001 Version V2,

More information

Engineering Guideline. pac- Carriers Type Universal

Engineering Guideline. pac- Carriers Type Universal Engineering Guideline pac- Carriers Type 9195 Universal Integration of conventional process automation interfaces pac- Carrier The pac- Carrier reflects the intention of R. STAHL to provide state-of-the-art

More information

Procedure for the Approval of New Fire Detection and Alarm Technologies

Procedure for the Approval of New Fire Detection and Alarm Technologies VdS Guidelines for Automatic Fire Detection and Fire Alarm Systems VdS 3469en Procedure for the Approval of New Fire Detection and Alarm Technologies VdS 3469en : 2016-01 (01) Publisher and publishing

More information

FUNCTIONAL SAFETY: A PRACTICAL APPROACH FOR END-USERS AND SYSTEM INTEGRATORS

FUNCTIONAL SAFETY: A PRACTICAL APPROACH FOR END-USERS AND SYSTEM INTEGRATORS FUNCTIONAL SAFETY: A PRACTICAL APPROACH FOR END-USERS AND SYSTEM INTEGRATORS TINO VANDE CAPELLE 1, Dr. MICHEL HOUTERMANS 2, 3 1- HIMA Paul Hildebrandt GmbH + Co KG, Brühl, GERMANY 2 Risknowlogy, Brunssum,

More information

Operating Manual MS220DA

Operating Manual MS220DA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN

More information

Functional Safety of Machinery: EN ISO Stewart Robinson. Overview of the presentation. References. TÜV SÜD Product Service

Functional Safety of Machinery: EN ISO Stewart Robinson. Overview of the presentation. References. TÜV SÜD Product Service Functional Safety of Machinery: EN ISO 13849-1 Stewart Robinson Overview of the presentation Defining Safety Functions Avoidance of Systematic Failures Defining Performance Levels Required Verifying Performance

More information

OPTISENS TUR 2000 Technical Datasheet

OPTISENS TUR 2000 Technical Datasheet OPTISENS TUR 2000 Technical Datasheet Sensor for turbidity measurement in water and wastewater Rugged design for harsh applications Integrated transmitter with direct 4...20 ma output Near infrared light

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-nA Edition 08/207 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4

More information

Safety instrumented systems

Safety instrumented systems Safety instrumented systems SIL2 / SIL3 rated vibronic point level measurement devices for overfill protection Typical tank farm Liquid level limit detection switch Liquiphant Chemical plant A white paper

More information

PROCESS AUTOMATION PROTECTING YOUR PROCESS THE DEFINITION FOR INTRINSIC SAFETY K-SYSTEM K-SYSTEM THE MOST TRUSTED NAME.

PROCESS AUTOMATION PROTECTING YOUR PROCESS THE DEFINITION FOR INTRINSIC SAFETY K-SYSTEM K-SYSTEM THE MOST TRUSTED NAME. PROCESS AUTOMATION K-SYSTEM THE MOST TRUSTED NAME PROCESS AUTOMATION PROTECTING YOUR PROCESS THE SYSTEM ELECTRONICS Availability: Power feed modules for a simplex or redundant supply on Power Rail Transmission

More information

Safety Instrumented Systems

Safety Instrumented Systems Safety Instrumented Systems What is a Safety Instrumented System? A Safety Instrumented System SIS is a new term used in standards like IEC 61511 or IEC 61508 for what used to be called Emergency Shutdown

More information

Endura AZ40 Oxygen and carbon monoxide equivalent (COe) analyzer

Endura AZ40 Oxygen and carbon monoxide equivalent (COe) analyzer ABB MEASUREMENT & ANALYTICS OPERATING INSTRUCTION SUPPLEMENT COM/AZ40/MOD-EN REV. A Endura AZ40 Oxygen and carbon monoxide equivalent (COe) analyzer Communications supplement Measurement made easy Oxygen

More information

IEC61511 Standard Overview

IEC61511 Standard Overview IEC61511 Standard Overview Andre Kneisel Instrumentation Engineer Chevron C.T. Refinery SAFA Symposium 2011 August 5 th, 2011 Presentation Overview Provide some understanding of the key aspects of Functional

More information

Models 4623, 4628 & 5999/980 USP<645> Conductivity Analyzers

Models 4623, 4628 & 5999/980 USP<645> Conductivity Analyzers Data sheet USP Conductivity Analyzers A conductivity system designed to meet USP for the Pharmaceutical Industry incorporating automatic Stage 1 test Meets USP requirements ensures compliance

More information

Automation, Software und Informationstechnologie

Automation, Software und Informationstechnologie Automation, Software und Informationstechnologie Report on the type approval of the Adjustable Frequency AC Drives PowerFlex 753 and 755 of Rockwell Automation Inc. Bericht-Nr.: 968/EZ 334.00/08 Datum:

More information

Operating Instructions. Electromagnetic Flowmeter Flowcont FN Hygienic version Flowcont LN

Operating Instructions. Electromagnetic Flowmeter Flowcont FN Hygienic version Flowcont LN Operating Instructions Electromagnetic Flowmeter Flowcont FN Hygienic version Flowcont LN Blinder Text 2 Contents 1 Safety... 8 1.1 General information and notes for the reader... 8 1.2 Intended use...

More information