11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies
|
|
- Silvester Kennedy
- 6 years ago
- Views:
Transcription
1 11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies
2
3 Visible Signals Agenda 1. Physics 2. Installation Considerations 3. Application Specific Engineering 4. Technician Perspective
4 We are going to analyze three different ways of measuring light intensity. 1. Peak Candlepower 2. Candela 3. Foot Candles or Lumens
5 Candlepower (abbreviated as cp) is an obsolete scientific unit of luminous intensity based on the light emitted from a candle made to a specified formula. The candlepower as a scientific measure was replaced in 1948 by the international unit (SI) known as the candela. Measures only the PEAK Candlepower and Candela have an equal ratio 1:1 PEAK AREA Peak Candlepower measures only the peak
6 Effective candela rating is calculated by the total area under the light intensity curve and includes all of its light energy. Light Intensity Curve CANDELA
7 CANDELA DEFINITION USED TODAY The candela is the luminous intensity, in a given direction, of a source that emits monochromatic radiation of frequency 540 x 1012 hertz and that has a radiant intensity in that direction of 1/683 watt per steradian.
8
9 Measures the intensity in Candela and the distance from the light source. This is called illumination and can be calculated by the following formula. INTENSITY OF LIGHT SOURCE DIVIDED BY THE DISTANCE SQUARED
10 1. Peak Candlepower measures only the peak and looks at the performance over a short period of time. 2. Effective Candela measures the total light energy, but does not take into consideration the distance from the light source. 3. Illumination (Lumens or Foot-Candles) takes both factors into consideration by measuring the power of the light and the distance from the light source.
11 ADA (Americans with Disabilities Act) required a minimum light intensity of 75 candela, for use out to a distance of 50 feet 75 CANDELA 50 FEET
12 NFPA 72 & 101 ANSI ADAAG UL1971 ADA requirements were incomplete ADA did not look at different candela ratings; Polarity distribution of light; Room size dimensions and Synchronization The industry got together and expanded ADA s requirements to Harmonize with other standards. For Example (NFPA 72, UL 1971, ANSI & ADAAG 2-2) Equivalent Facilitation was born and allowed for other designs and technologies to be used as long as they met or exceeded these other requirements CAN/ULC-S & CAN/ULC-S incorporates most of these standards (Emulated Copied - Plagiarized) Now we will look at an example of how Equivalent Facilitation works
13 DISTANCE FROM STROBE
14 DISTANCE FROM STROBE
15 DISTANCE FROM STROBE
16 Equivalent Facilitation Therefore, utilizing a visible signal less than 75 Candela in a smaller room is equivalent to a larger Candela strobe in a larger room; by providing greater luminance per square foot. (.0375) In the United States the minimum calculated illumination is required to be at least lumens or foot candles at any point within the covered area ULC-S Table 5 (Wall Mounting) meets or exceeds this requirement It is ironic that we do not follow Equivalent Facilitation in Canada, but we meet it in most cases
17 POLAR LIGHT DISTRIBUTION
18 CAN/ULC-S HORIZONTAL DISPERSION (WALL) Degrees % Candela Rating 0 100% Compound Top View Wall Example is based on a 75 Candela Strobe 15 Candela would need to meet the following
19 CAN/ULC-S VERTICAL DISPERSION (WALL) Degrees % Candela Rating 0 100% Side View
20 CAN/ULC-S VERTICAL DISPERSION (CEILING) Degrees % Candela Rating 0 100% 90 0 Ceiling
21 Intensity of light source? Distance from light source? Ambient lighting? Lens color? Size? Flashing or continuous output? Duration of output? Location in the visual field? Reflected light?
22 White 100% Amber % Blue 35-70% Red 25-40%
23 The recommended light source for visual appliances is clear unless another colour is required for the application or by AHJ. Example: Chemical Agent Release may require a different colored lens
24 Visible Signals Agenda 1. Physics 2. Installation Considerations 3. Application Specific Engineering 4. Technician Perspective
25 What do panel manufacturers print on the control panel circuit board where you would normally connect a strobe to? Bell cct Signal cct Notification cct NAC cct Output cct Indicating cct They all mean the same thing!!
26 Strobe/Horn Panel Connections Before Sync Most Fire Alarm Panels would have two circuits for signaling, one for strobes which would be a constant voltage and one for Horn/Bell which would pulse a code such as temporal for EVAC, or Alert at 20 spm. FACP FACP FIRE FIRE FIRE FIRE FIRE FIRE
27 The problem is the strobes will flash at different rates FACP FACP FIRE FIRE FIRE FIRE FIRE FIRE
28 Synchronization ADAAG (American with Disabilities Act Accessibility Guidelines) Technical Bulletin #2, states that 5 flashes per second or more is the trigger point for photosensitive epileptic seizures. This means if 4 strobes in a room are flashing 2 times per second, the combined flash rate could exceed the 5 flashes per second; potentially causing a seizure. ADA recommends that a composite flash rate of 5 Hz be avoided for multiple strobes. The strobe flash rate must be a minimum of 1 Hz across the listed voltage range. (Increasing or lowering the operating voltage will affect the flash rate).
29 Synchronization Requirements In Canada Two or more visible signaling devices in corridors or rooms in the same field of view shall flash in synchronization. Performance tests to verify flash rate between 1 and 2 flashes per second. Synchronization feature to flash within 0.01 sec for 2 hours.
30 Strobe/Horn Panel Connections With Sync Synchronization can be accomplished in two ways The first is using an external sync module (this is for both strobes and horns) FACP Nac circuit 1 Sync Module Nac circuit 2
31 Strobe/Horn Panel Connections With Sync Some Fire Alarm Panels use two NAC circuits in order for the horns to be silenced and strobes to have continuous operation. FACP Nac circuit 1 Nac circuit 2
32 Strobe/Horn Panel Connections With Sync The second method is the panel having the sync protocol built into the panel. The external module is not required. FACP
33 Visible Signals Agenda 1. Physics 2. Installation Considerations 3. Application Specific Engineering 4. Technician Perspective
34 Visible Signals Codes & Standards CANADA ULC-S VISIBLE SIGNAL DEVICES FOR FIRE ALARM SYSTEMS, INCLUDING ACCESSORIES ULC S provides installation requirements for strobes in Canada NBC 2005 (National Building Code) OBC 2006 (Ontario Building Code) Other Provincial Building Codes UNITED STATES NFPA 72 &101 provides additional guidance for strobe applications in large volume open spaces ADA has its own guidelines UL 1971 AADAG ANSI 117.1
35 Where are Strobes Required? OBC & NBC require strobes in the following areas.
36 Where are Strobes Required? Where Ambient Sound Levels Exceed 87dB Example - Noisy manufacturing plants or diesel generator areas
37 Where are Strobes Required? Where ear protection is worn
38 Where are Strobes Required? Sound insulated or audiometric booths (Recording Studios or Sound Testing Rooms)
39 Where are Strobes Required? Entertainment areas where sound levels may exceed 100dB (Night Clubs & Concert Halls)
40 Where are Strobes Required? Building or portions of a building for persons with hearing impairment
41 Where are Strobes Required? Minimum 10% of rooms in Hotel (NEW)
42 OBC NEW REQUIREMENTS Based on Occupancy Class
43 New Requirements Based on Occupancy Class (OBC) Installation of strobes in public corridors for B Occupancy (Health Care)
44 OBC New Requirements Based on Occupancy Class - Strobes in public corridors D Occupancy (Office)
45 OBC New Requirements Based on Occupancy Class - Strobes in public corridors E Occupancy (Mercantile)
46 OBC New Requirements Based on Occupancy Class Strobes permitted in lieu of audible signals in compartments including operating rooms and recovery areas such as ICU and CCU
47 OBC New Requirements Based on Occupancy Class A Occupancy (Assembly Areas) Strobes are required in corridors used by the public, and also floor areas where public may congregate
48 OBC EXCEPTIONS FOR USE OF STROBES Not Required In classrooms (A Occupancy) Group B Div 3 care occupancy for up to 10 persons In C Occupancies - Residential
49 Key Installation Requirements in ULC-S ULC Table 7 - Corridor ULC Table 5 - Wall ULC Table 6 - Ceiling a) ULC Tables will specify the strobe intensity and the number of strobes required for each specific room size b) Now we will look at installation examples using all of the tables
50 CORRIDOR SPACING
51 CORRIDOR SPACING FOR CEILING OR WALL MOUNTED VISIBLE SIGNAL DEVICES (ULC- (ULC-S TABLE 7) Corridor Length (m) 6m less in width Minimum # of 15 Candela Strobes
52 MOUNTING HEIGHT Wall mounted (Room Area and Corridor) Entire lens is not less than 2m and not more than 2.4m above the finished floor
53 INSTALLATION EXAMPLES CORRIDORS meter corridor 4.6 m 4.6 m 30 m 15 Candela Strobe for corridor installations Strobe must be located no more than 4.6m from end of corridor Additional strobes placed not more than 30m apart
54 INSTALLATION EXAMPLES CORRIDORS m 40.8 m 50 meter corridor 20.4m 4.6 m 4.6 m 40.8m Strobe must be located no more than 4.6m from end of corridor Additional strobes placed not more than 30m apart
55 INSTALLATION EXAMPLES CORRIDORS 4.6m m 38m 4.6m 4.6m 4.6m 22m Where there is an interruption of the concentrated viewing path, such as a fire door, an elevation change, or any other obstruction, the area shall be treated as a separate corridor
56 WALL MOUNTED VARIOUS ROOM SIZES
57 CAN/ULC-S (Table 5) LIGHT OUTPUT FOR WALL-MOUNTED VISIBLE SIGNAL DEVICES FOR VARIOUS ROOM SIZES Maximum Area Coverage in (m) 1 Strobe per area 2 Strobes per area 4 Strobes per area 6.10 X N/A N/A 8.53 X N/A 9.14 X N/A 12.2 X X X X X X X X X
58 Room Spacing Example 6 m 5 m? Intensity
59 Room Spacing Example Application: 6m X 5m Room ULC-S Table 5 for wall mounted devices requires a 15 Candela strobe for a maximum room size of (6.10m X 6.10m) Since our room size falls below 6.10m X 6.10m; a 15 Candela Strobe will meet this application Maximum Room size in (m) 1 Strobe per area 2 Strobes per area 4 Strobes per area 6.10 X N/A N/A 8.53 X N/A
60 Room Spacing Example Long Side Coverage? Short Side Coverage? 5 m 6 m 15 Candela Installation Tip - Spacing allocation for wall mounted strobes are to be located (at the mid-point of the longest side of the area served) NFPA 72 The mid-point of the longest side is the preferred method Do we mount the strobe on the short or long side of the wall?
61 Correct & Incorrect Allocation Methods Application - Four 15 Candela Strobes in a 12.2m X 12.2m Room 12.2 m 12.2 m In this example, we are meeting minimum Candela rating (illumination) but the strobe allocation is incorrect Area Coverage of each appliance is not maximized Moreover, if these were (Horn/Strobe or Speaker Strobe) combination units the result may be conflicting sound waves or sound cancellation
62 Correct & Incorrect Allocation Methods The correct method is by following clause in CAN/ULC-S Subdivide the room into multiple squares (6.1m x 4) ULC-S Table 5 - room size of 6.1m X 6.1m requires a 15 candela strobe Install four 15 candela strobes (one for each 6.1m area) 6.1m 12.2 m 12.2 m 6.1m 6.1m Utilize Maximum Area Coverage 6.1m
63 Correct & Incorrect Allocation Methods Application Room size is 14m X 28m Solution is to divide the room into two 14m X 14m rooms Using ULC S Table 5 (wall mounting) requires a 94 Candela strobe in a 15.2m X 15.2m room (One in each subdivided room) Two 60 Candela or four 30 Candela strobes can be substituted Please note that the two visible signal devices are located on opposite walls If they were located on the same wall and both were within the same field of view then synchronization would be required 14 m 28 m 14 m 14 m
64 Wall Mount Not Centered Application 7m X 5m Room Wall Appliance Not Centered In rooms with visible signal devices not centered on a wall, the effective intensity (candela) from one wall-mounted visible signal device shall be determined by maximum room size dimensions obtained either by measuring the distance to the furthest wall or by doubling the distance to the furthest adjacent wall, whichever is greater 7m 6m 5m One 60 Candela Two 30 Candela Four 15 Candela In this scenario, the greater distance is obtained by doubling the distance to the farthest adjacent wall (6m x 2 = 12m) In table 5, a 12m X 12m room requires a 60 candela strobe.
65 Wall Mount Not Centered The Intent 7m 6 m 5m 12m 6 m 12m Since we cannot centre the appliance, we create an imaginary room size to centre the device (12m x 12m) Then we select the appropriate strobe intensity to cover those dimensions - ensure full room area coverage
66
67 CEILING MOUNTED
68 Room Spacing for Ceiling Mounted Visible Devices CAN/ULC-S (Table 6) Maximum Area Size Maximum Mounting Height One Strobe Light (Rated Candela) 6.10 X X X x X X X x X X X x
69 Ceiling mounted strobes have a different polar distribution than wall mounted versions. The strobe s reflector has to be designed to disperse the light 180 degrees. Most Manufacturers now offer separate models for ceiling mounted applications. 180 Degrees Distribution
70 Ceiling Mounted Example Application 9.14 X meter Ceiling Height Ceiling Appliance Centered ULC-S Ceiling Mount Table 6 requires a 30 Candela Strobe for room size 9.14m X 9.14m At 6m ceiling height, a 45 Candela is required At 9m ceiling height, a 75 Candela is required Please refer to Table 6 Ceiling Height Data 9.14 m 9.14 m 30 Candela 3m height
71 Ceiling Mounted Not Centered Application 9m X 4.5m 3 meter Ceiling Height Ceiling Appliance Not Centered We have a 7m distance from device to the furthest wall - Doubling the distance gives us 14m. The next closest room size is 15.2m X 15.2m. The table shows that a 95 candela strobe is required 9 m 7m 4.5 m One 95 or 2 60 Candela Strobes can be used Where the ceilingmounted visible signal device is not located at the centre of the room, the effective intensity (candela) shall be determined by doubling the distance from the device to the farthest wall to obtain the maximum room size.
72 Visible Signals Agenda 1. Physics 2. Installation Considerations 3. Application Specific Engineering 4. Technician Perspective
73 Compatibility Most people in the fire industry are aware devices like smoke detectors are required to be compatible with the Fire Alarm Panel but now we must ensure the signaling devices are as well. Each manufacturer has a unique sync protocol.
74 Compatibility So what if? What if you install a new sync type horn/strobe on a non sync circuit? In most cases the devices are designed to work, but not always!! At least once when I tested a horn/strobe the horn did not operate.
75 Compatibility So what if? What if you install a horn/strobe on a different manufacturers sync module or protocol? It may work but probably won t!!! I tested three different manufacturers devices on each others sync modules with the following results.
76 Compatibility Test Results (Note: this was a very unscientific test) Using Manufacturer A s Sync Module To Manufacturer B device - No Strobe or Horn sync To Manufacturer C device -Strobe sync but Horn no sync Using Manufacture B Sync Module To Manufacturer A device- No Strobe or Horn sync To Manufacturer C device- Strobe and Horn sync Using Manufacture C Sync Module To Manufacturer A device - Strobe Sync but no Horn sync To Manufacturer B device - No Strobe or Horn sync Note in almost all cases silencing the horn cct and keeping the strobe operational did not work.
77 Compatibility Conclusions Depending on the type of sync protocol, mixing devices from difference manufacturers may or may not work. Odds are they won t work!!
78 APPLICATION CONSIDERATIONS When designing systems requiring strobes, you need to consider the following Current draws NAC output Additional Power Supplies Larger batteries Appropriate wire sizes Synchronization if two or more are in the field of view
79 Strobe Current Requirements Traditional signaling devices such bells and horns require relatively small amount of current compared to strobe. A typical bell is 20 ma vs. a 75 cd strobe at 190 ma. Manufacturers offer strobe products with multi-candela settings. Before installation please confirm current draws for selected products. This can made a big difference! A 15 cd strobe may only require 60ma but a 110 cd can require 220 ma. When designing or installing a system check the maximum current specification of the control equipment. Anticipate the requirement for additional Power Supply Boosters.
80 Strobe Current Requirements Example A system requires 14 strobes set at 75 cd. The strobe selected at this setting requires.19 amps. The alarm current required is.19 x 14 = 2.66 amps. Note: Most panels on the market today have NAC circuits with a max between 1.5 and 2 amps. Therefore at least two circuits will be required. If we use 2 NAC circuits each circuit would have a load of 1.33 meaning that number 12 or 14 gauge wire will be required, depending on the distance required.
81 Voltage Drops All wire has internal resistance. Distance will reduce the voltage available to power the appliance. All appliances have a minimum voltage rating that will affect their operation. (Stop functioning) System designers need to look at how distance, wire size and battery will affect the operation of the appliance. (This should include their minimum operating voltage.)
82 Voltage Drops Batteries should be sized to meet the appliance s minimum voltage. In other words; making sure the battery will deliver the appropriate number of amps down to its end voltage. (Example: Appliance has a minimum operating voltage of 18 volts: In this case the battery should be sized to deliver the appropriate number of amps before its voltage drops to 18 volts. (The battery s voltage decreases during discharge.)
83 (Audible & Visual Signals) Wiring Chart Total Signal Load Maximum Wiring Run To Last Device (ELR) Max Loop Resistance 18 AWG 16 AWG 14 AWG 12 AWG Amps ft m ft m ft m ft m Ohms Maximum voltage drop should not exceed 1.8 volts and this table assumes total load at end of line
84 Verification Requirements So what are we required to do for strobes? Do we measure the output with a meter to ensure that it meets Building code requirements?
85 Strobe Verification Requirements Currently we are required to do the following Inspect and test each device to correct field terminations and wire size. Test for operation, supervision and ensure that it is clearly visible from all points throughout the area served by the device. Note: It is not required to make any test measurements using a meter. Test the device at the electrically furthest point of each circuit to ensure it receives the rated power (voltage) as per the manufacturer s specifications.
86 Strobe Verification Requirements Ensure the strobe is compatible with the control panel or the sync module. Ensure that the device is correctly located and its output settings match the engineering design for the area. This requires the tech to have a copy of the approved drawings with the correct candela settings indicated.
87 Visible Signals Agenda 1. Physics 2. Installation Considerations 3. Application Specific Engineering 4. Technician Perspective
88 Helping to provide a brighter future. Improving Life Safety Through Education
SELECT-A-HORN/STROBE SERIES
SELECT-A-HORN/STROBE SERIES Features Description Mircom s Select-A-Strobe/Horn Series is designed to comply with the Americans with Disability Act (ADA) and meet UL standard 1971 requirements for emergency
More information08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor
s Data Sheet Fire Safety & Security Products 08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor AS-MC-CW AS-MC-R AH-W AH-R Product Overview
More informationPROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-02-07 Ontario-NBC CODE REFERENCE: Division B / 3.2.4.22. and 3.2.4.23. DESCRIPTION
More informations Notification Appliances
s Notification Appliances Data Sheet Fire Safety Products AS & AH Audible Horn Strobe / Audible Horn Appliances Application: Indoor / Outdoor AS-MC-CW AS-MC-R AH-R AH-W Product Overview Fast installation
More informationTrueAlert Multi-Candela Notification Appliances
UL, ULC Approved* TrueAlert Multi-Candela Notification Appliances Non-Addressable Visible Only Amber Lens Strobes for Emergency Communications Features Visible only (V/O) 24 VDC wall mount notification
More informationTrueAlert Multi-Candela Notification Appliances
TrueAlert Multi-Candela Notification Appliances UL, ULC, CSFM Listed; FM Approved* Features 24 VDC high intensity notification appliance common features: Xenon strobe with intensity selectable as 135,
More informationField Configurable Horns and Strobes
Vigilant Catalog Strobes, Horns, Bells, Chimes Field Configurable Horns and Strobes Genesis Series MNEC appliances available with clear or amber lenses. Pending Overview The Genesis line of fire alarm
More informationField Configurable Horns and Strobes
EDWARDS Catalog u Strobes, Horns, Bells, Chimes LIFE SAFETY & INCIDENT MANAGEMENT Field Configurable Horns and Strobes Genesis Series ECS/MNS appliances available with clear or amber lenses. S218, S5389,
More informationTrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions
TrueAlert NonAddressable, MultiCandela Notification Appliances Installation Instructions PRODUCT IDENTIFICATION REFERENCE (See Page 4 for Detailed Product Specifications) Type Mount Model Color Operation
More informationTrueAlert Notification Appliances
TrueAlert Notification Appliances UL Listed; FM, CSFM and MEA (NYC) Approved* Non-Addressable Audible/Visible Notification Appliances with SmartSync Operation of Strobes and Horns Features Wall mount audible/visible
More informationMEA. SpectrAlert Series Horns, Strobes, and Horn/Strobes GENERAL
March 30, 2000 Section: Audio/Visual Devices G-250 SpectrAlert Series Horns, Strobes, and Horn/Strobes GENERAL System Sensor SpectrAlert Series strobes, horns, and combination horn/strobes are UL listed
More informationGenesis LED G1 Series
EDWARDS Catalog u Strobes, Horns, Bells, Chimes LIFE SAFETY INCIDENT MANAGEMENT Genesis LED G1 Series Compact Notification Devices S218, S5389 7125-1657:0506 7135-1657:0502 Overview Genesis LED G1 Series
More information1 Watt Supervised Self-Amplified Strobe Speakers Round Flush Grille with 75cd Strobe
273 Branchport Avenue Long Branch, N.J. 07740 (800) 631-2148 Thank you for using our products. www.wheelockinc.com INSTALLATION INSTRUCTIONS SUPERVISED SELF-AMPLIFIED STROBE SPEAKERS Use this product according
More informationInstallation Guide for AL800UL-ADA. NAC Power Extender. Rev
Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA
More informationTrueAlert Addressable Notification Appliances
UL, ULC Listed* TrueAlert Addressable Notification Appliances Audible/Visible Notification Appliances; Multi-Tone Horn/Strobe with 520 Hz Output Features Individually addressed and controlled multi-tone
More informationAL800ULADA. NAC Power Extender. Installation Guide
AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery
More informationPotter Wall Mount Select-A-Strobe
104 Kenran Industrial Dr. Potter Wall Mount Select-A-Strobe SL-1224 SERIES SELECT-A-STROBE Call for additional listings 12 VDC with 15, 35 or 60 cd setting 24 VDC with 15, 35, 60, 5, 95 or 110 6 distinct
More informationELECTRONIC SOUNDER STROBE Model : AVD-C407
ELECTRONIC SOUNDER STROBE Model : AVD-C407 MULTRON range of combination Electronic Sounders with Strobe Lights are designed to complement our Fire Alarm products both technically and aesthetically as an
More information'08 Series Notification A liances
SIEMENS Data Sheet Fire Safety & Security Products '08 Series Notification A liances AS I AH & AS - Audible Strobe Appliances and AH Audibles AS-MC-CW AS-MC-R AH-W AH-R Product Overview - Fast installation
More informationAL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated
More informationL-Series, Indoor Strobes and Horn Strobes
Notification Appliances L-Series, Indoor Strobes and Horn Strobes Indoor Selectable-Output Strobes/Horn Strobes for Ceiling Applications General The L-Series audible visible notification products offer
More informationHorn/Strobe Compliance Reference Guide
Horn/Strobe Compliance Reference Guide Table of Contents INTRODUCTION...1 WHAT IS THE COVERAGE AND ENFORCEMENT OF THE ADA?...2 WHAT IS THE ADAAG?...3 WHAT IS PUBLIC MODE VS. PRIVATE MODE OPERATION?...4
More informationTrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed, FM Approved TrueAlert Addressable Notification Appliances Audible/Visible Notification Appliances, Wall Mount Multi-Candela Horn/Strobe, Model Series 49AV Features Individually addressed
More informationCSH24CH. Colored Light Strobe/Horn Series High Candela. Description. Features. Ceiling/Wall Mount Patent Pending. Ordering Information
OF FIRE CS24C Colored Light Strobe/orn Series igh Candela Ceiling/Wall Mount Patent Pending Description AMSECO's UL listed Colored Light Strobe CS24C series is designed to provide audible and visual signals
More informationCanadian Fire Alarm Association (CFAA)
An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems Canadian Fire Alarm Association (CFAA) CAN/ULC - S524-01 STANDARD FOR THE INSTALLATION OF FIRE ALARM SYSTEMS Installation
More informationWheelock RSS & RSSP Series
Wheelock RSS & RSSP Series Single- and Multi-Candela Strobes and Strobe Plates DF-51780:A G-520 General Wheelock s patented Series RSS Strobe Appliances and Series RSSP Strobe Plates have lower current
More informationL-Series, Emergency Communication Devices
Notification Appliances L-Series, Emergency Communication Devices Description The L-Series Emergency Communications devices and accessories combine application versatility with all of the same time-saving
More informationL-Series, Indoor Strobes and Horn Strobes
Notification Appliances L-Series, Indoor Strobes and Horn Strobes Indoor Selectable-Output Horns, Strobes and Horn Strobes for Wall Applications General The L-Series audible visible notification products
More informationPerformance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide. Ernesto Vega Jánica, EE, MSc, MEng
Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide Ernesto Vega Jánica, EE, MSc, MEng 1 Performance Based Design Introduction Change on Philosophy 1999-2002-2007-2010-2013
More informationAL600ULADA. NAC Power Extender. Installation Guide
AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery
More informationSpectrAlert Advance. Field-Selectable Mass Notification Devices. Description. An ISO Company SIGNALING. MEA Approved E
SpectrAlert Advance Description System Sensor SpectrAlert Advance offers a variety of devices designed for mass notification, including plain devices for non-fire applications, amber lens strobes and speaker
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationFort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS
HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable
More informationChapter 7. Communication Elements and Features
Chapter 7. Communication Elements and Features Chapter 7. Communication Elements and Features 701 General 701.1 Scope. Communications features and elements required to be accessible by the scoping provisions
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationGenesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet
Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet Table 1: Models Description Low frequency (520 Hz) horn, white housing, no FIRE marking, standard output clear strobe light Low frequency (520
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationLifeAlarm Fire Alarm Controls
UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity
More informationCFAA Technical Seminar Ontario Building Code Updates to 2015
CFAA Technical Seminar Ontario Building Code Updates to 2015 October 28, 2015 2015 Fire Alarm Updates Ontario Building Code Glenn Somerton P.Eng. Senior Code Specialist Morrison Hershfield Limited gsomerton@morrisonhershfield.com
More informationData Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906
s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones
More information3.1 Introduction. 3.1 Introduction
DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationAL602ULADA AL802ULADA AL1002ULADA
AL602ULADA AL802ULADA AL1002ULADA NAC Power Extenders Application Guide (See Installation Guide for additional information) Rev. 031703 1. General Information (Use this in conjunction with respective Installation
More informationMR-2602 Two Zone Fire Alarm Control Panel
MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...
More informationUse this product according to this instruction manual. Please keep this instruction manual for future reference.
273 Branchport Avenue Thank you for using our products. Long Branch, NJ 07740 (800) 631-2148 INSTALLATION INSTRUCTIONS www.cooperwheelock.com E50 MULTI-CANDELA SPEAKER STROBES GENERAL: Use this product
More informationLife safety notification
LED Wheelock Exceder LED3 Life safety notification Meeting the latest codes with increased energy-efficiency in a compact design Wheelock Exceder LED3 Compliant, compatible, compact, and energy efficient
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationDimensions of the Optional Mounting Box (BB-400R/W)
Wall and Ceiling Notification Appliances This manual applies to the following models Horn only FH-400-WW and FH-400-RR - wall and ceiling mounted horn Strobe only FS-400-WW and FS-400-RR - wall mounted
More informationAddressable Fire Alarm Control Panel
PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT
More informationDIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,
More informationadvancedsolutions Advanced Design. We have engineered all SpectrAlert products to meet or exceed code today and tomorrow. We ve worked to standardize
advanced ideas advancedsolutions At System Sensor, Research and Development is more than a department. It s a way of life. Every day we work to design new products that utilize the most innovative technologies
More informationSECTION FIRE ALARM SYSTEMS
SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationAutonomous control unit
Supersedes October 2016 Autonomous control unit Description Eaton s Autonomous Control Unit (), part of the ALERiTY integrated MNS platform, is a supervised in-building emergency communications system
More informationXP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card
XP6-C Six Circuit Supervised Control Module and SYNC-1 Accessory Card General NOTIFIER s XP6-C six-circuit supervised control module provides intelligent alarm systems with supervised monitoring of wiring
More information30.45 Electric Release PDRP-2001
The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or
More informationPOWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)
PATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) NAC ETENDER SUPPLIES Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web
More informationInstallation Manual CFP-105. Fire Alarm Control Panel. Version 1.0
CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability
More information1. POWERPATH Operation
273 Branchport Avenue Long Branch, NJ 07740 (800) 631-2148 www.wheelockinc.com Thank you for using our products. INSTALLATION INSTRUCTIONS MODEL PS-12/24-6 POWERPATH Use this product according to this
More informationBritish Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety
Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These
More informationSAFEPATH SAFEPATH. Emergency communications system
SAFEPATH SAFEPATH Emergency communications system ALERiTY Integrated mass notification solutions by Eaton; designed to protect, alert and inform your most critical resources your people ALERiTY /a ler
More informationAL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).
More informationTrueAlert ES Addressable Notification Appliances
UL, ULC, CSFM Listed; FM Approved* TrueAlert ES Addressable Notification Appliances Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO Features Individually addressed
More informationTrueAlert Addressable Notification Appliances
UL, ULC Approved* TrueAlert Addressable Notification Appliances Audible Notification Appliances; Multi-Tone Horns with 520 Hz Output Features Individually addressed and controlled TrueAlert ES multi-tone
More information*15cd models are Listed at 15cd and meet 75cd on axis
273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 INSTALLATION INSTRUCTIONS www.wheelockinc.com MULTITONE STROBE APPLIANCES Use this product according to this
More informationPage 1 of 16 FLASH PUSLE WIDTH EFFECTIVENESS IN NOTIFICATION APPLIANCES
Page 1 of 16 FLASH PUSLE WIDTH EFFECTIVENESS IN NOTIFICATION APPLIANCES Ken Savage TYCO Safety Products January 25, 2011 Page 2 of 16 ABSTRACT Today s fire alarm system notification equipment standards
More informationSpeakers and Speaker Strobes
Kingfisher Company, inc. Speakers and Speaker Strobes Features: Approvals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshall (CSFM), Factory Mutual (FM), and
More informationgood things in small packages
FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with
More informationLifeAlarm Fire Alarm Control Panels
LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient
More informationSelectable Output Chimes and Chime/Strobes
Selectable Output Chimes and Chime/Strobes PRELIMINARY DN-60940:A Audio/Visual Devices General System Sensor L-Series selectable-output chimes and chime/ strobes are rich with features guaranteed to cut
More informationFire Alarm Intelligibility. Chris Nolan
Fire Alarm Intelligibility Chris Nolan chris.nolan@honeywell.com 416-525-9898 Fire Alarm Intelligibility Agenda Definition Codes Factors Design Test 2 What is Voice Intelligibility Definition: A measure
More informationAddressable NAC Output Module D327A
Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,
More informationTrueAlarm ES Analog Sensing
TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,
More informationEvacuate everyone Sonos Pulse & Nexus Pulse
Evacuate everyone Sonos Pulse & Nexus Pulse Available through distribution: www.discountfiresupplies.co.uk Tel: 01792 452 700 EN54-23 Fire Beacons In a fire, everyone matters. Sonos Pulse and Nexus Pulse
More informationStandard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment
NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationFigure 1. Figure 2. See notes 1 and 2 below.
273 Branchport Avenue Long Branch, N.J. 07740 (800) 631-2148 Thank you for using our products. www.wheelockinc. com INSTALLATION INSTRUCTIONS HORN SPEAKER WITH AMPLIFIER Use this product according to this
More informationAL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X
AL1002ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).
More informationSignature Series Auto-Sync Output Module (CC1S)
Signature Series Auto-Sync Output Module (CC1S) Product description Mounting The Signature Series can be mounted in a North American 2-1/2 in (64 mm) deep 2-gang box or a standard 4 in square box 1-1/2
More informationSP40S-D. Kingfisher Company, inc. Features: Description:
Kingfisher Company, inc. SP40S-D Features: Multi-use applications The system can function as an evacuation system, an emergency messaging system, and an employee notification system Fire code applications
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationFrequently Asked Questions
Frequently Asked Questions For Life Safety System Designers, Building Owners, and Installers P/N 85000-0395 Introduction Provisions in NFPA 72 (The National Fire Alarm and Signaling Code) now require low
More informationAL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev
Altronix Corp. 140 58th St. Brooklyn, NY AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 052313 Agency Listings: UL Listed for Control Units for
More informationModel PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual
Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationAL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X
AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed for Control Units for Fire Protective Signaling Systems (UL
More information12/14/2013. Fire alarm and emergency power SPRINKLER HEAD
Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector
More informationAND ARCHITECT SPECIFICATIONS
SXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 4 Zones Expandable to 8 Zones Microprocessor Based Control Factory Programmed Field Configurable 2 Style Y Notification
More informationMultiple Input and Output Modules
Kingfisher Company, inc. Multiple Input and Output Modules Features: Removable 12 to 18 AWG plug-in terminal blocks Individual LED indicators Unused addresses may be disabled Rotary address switches Class
More informationInstallation Instructions Model ABHW-4S
Installation Instructions Model ABHW-4S Intelligent Audible Base for Sleeping Area with 520Hz Low Frequency Sounder Introduction Application note The Model ABHW-4S audible base from Siemens Industry, Inc.
More informationSAFEPATH Mass Notification System (SPMNS)
Supersedes February 2016 SAFEPATH Mass Notification System (SPMNS) SP40S SPB-320 SPB-80/4 SPB-160 PS-8-LP SPMNS-MIC SP4Z-A/B Contents Page SPMNS.... 2-4 SPMNS-MIC...3 Expansion Options SAFEPATH 2-zone
More informationUniversity Design Standard Fire Alarm Systems
1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationProject No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10
Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction
More informationDesign Considerations of LED based Visible Notification Appliances. Johnny K. W. Siu, Ph.D. - Light Engine Limited I. INTRODUCTION
Design Considerations of LED based Visible Notification Appliances Johnny K. W. Siu, Ph.D. - Light Engine Limited I. INTRODUCTION Solid state light emitters, Light Emitting Diodes, LEDs have been widely
More informationCONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA
CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with
More informationFire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11
Fire Safety Installation Instructions Model ADBX11 Audible Base INTRODUCTION Model ADBX11 The SIEMENS Model ADBX11 Audible Base consists of a standard Series 11 base combined with an audible device. All
More informationConcerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3
Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June
More informationSAFEPATH DoD facility communications system & expansion options
Supersedes September 2011 SAFEPATH DoD facility communications system & expansion options SP40S-D SPB-320 SPB-80/4 SPB-160 SP4-TZC SPRM SP4Z-A/B SP-SVC Contents Description Page SP40S-D Communications
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More information