CARD ACCESS CONTROL SYSTEM

Size: px
Start display at page:

Download "CARD ACCESS CONTROL SYSTEM"

Transcription

1 SECTION CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where card insertion into a reading device is not required and will also be capable to function as an alarm and contact monitoring system. B. Related Sections: Finish Hardware Closed Circuit television System Intrusion Detection System Raceways and Conduits Wire and Cable Outlet, Pull, and Junction Boxes Grounding Fire Alarm and Detection System SYSTEM DESCRIPTION A. One designated door at each of the following locations shall be controlled by a card reader: 1. Entrance to administration. 2. Entrance to physical education office and storage. 3. Entrance from kitchen exterior at receiving (Truck loading area). 4. Entrance to media center. 5. Additional doors as indicated on Drawings SUBMITTALS A. Shop Drawings: 1. Submit riser and connection diagrams, schedules showing location and function of each device, and specification data sheets. 2. Supply a proposed acceptance test procedure. 3. Submittals showing typical riser diagrams and specification data sheets are not acceptable. 4. Submit 10 copies each. 5. Indicate card access locations on plans. Project No. SPECIFICATION GUIDELINES

2 1.04 QUALITY ASSURANCE A. The system supplier shall have a minimum of 5 years system design, engineering supervision, and installation experience in the alarm or access control industry. B. Any equipment, device, system component, or part provided or installed by contractor containing or using date processing shall be Year 2000 (Y2K) compliant. Before substantial completion, contractor shall provide a manufacturers statement of Year 2000 compliance and manufacturers and contractors warranty against daterelated failures. C. The Contractor shall provide a factory-trained technician to assist and advise installing personnel. Final connections shall be the sole responsibility of the Contractor WARRANTY A. The entire installation, except access cards, shall carry a 2-year guarantee after acceptance of the system by the Board. B. Access Card: 5 year warranty, all inclusive, for deterioration with age or damage due to reasonable flexing. C. Contractor shall guarantee all devices against defects in material or quality of construction. D. Electrical Contractor shall guarantee conduit, wire, and electrical installation labor for 2 years. E. Allied trades shall guarantee installation, material, and labor provided under this section of work. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Card Access Control Systems: 1. Checkpoint. 2. Simplex. 3. Westinghouse Security Electronics MATERIALS A. Provide electrical transient protection according to Project No. SPECIFICATION GUIDELINES

3 manufacturer's requirements. B. Include all necessary tools, equipment, material, and labor to furnish, install, and verify correct operation. C. The system shall consist of a central command center, UPS system, microprocessor based terminal controllers, input/output boards as required, proximity card readers, magnetic door position monitor contacts, and door strikes as required. D. Provide a modem according to manufacturers requirements and compatible with M-DCPS District Communications Management (DCOM). E. Provide a dedicated UPS system of 800 va or larger to provide backup power for the card access control headend. F. Remote power supplies for terminal controllers, magnetic locks, and door strikes connected to the card access system shall be provided with battery backup capacity to maintain complete system operation for 24 hours and be supervised for power failure EQUIPMENT A. Human Interface: 1. The system shall be capable of supporting a local or remote command center (terminal and printer). The interface is enabled by a menu-driven full text character set. This device shall be any industry standard ASCII terminal with a serial output. The human interface must accept as a minimum, a user-defined auto-logoff routine selectable from 0 to 240 minutes. This function shall be provided by the system controller. B. Network Components: 1. The distributed architecture requires the interface of various intelligent controllers. These controllers shall have operating environments to allow complete functionality at a temperature range of 0 to 50 degrees C and a relative humidity of 90 percent (noncondensing). C. System Controller: 1. The System Controller shall be microprocessor-based Project No. SPECIFICATION GUIDELINES

4 with onboard time and data generation and battery to allow a minimum of 48 hours data integrity. This device shall be responsible for maintaining the data communications between the terminal controllers attached and the ASCII terminal. 2. This device shall maintain the operating system parameters to include the definitions of, but not limited to, the following: a. Doors. b. Inputs. c. Outputs. d. Access Levels. e. Time Zones. f. Users. g. Operators. h. Dial-up communications. i. Auto Log-Off. j. Classify Events. 3. The definitions of these parameters shall be in full English text. Abbreviated text or code shall not be acceptable. 4. There shall be a maximum capability of 8 terminal controllers attached to any one system controller. The system shall be capable of accepting one system controller. This controller shall be modem compatible for communications over standard 3002 voice grade telephone lines. D. Terminal Controller: 1. The terminal controller shall be microprocessor based with onboard time date generation and battery to allow a minimum of 48 hours of data integrity. This device shall be responsible for all access control decision and alarm monitoring detection in the system. 2. It shall also be responsible for all output responses to alarm detection and create the appropriate response through its processor logic. This controller shall be capable of maintaining a buffer of a minimum of 2800 event transactions when communication is lost with the system controller. 3. System shall work with fail-safe and fail-secure locking hardware. 4. The terminal controller shall have all necessary provisions to implement access control for 2 doors. The capacity shall be present for 2 door contacts, to request to exit devices and 2 door strike outputs. These strike outputs shall control locking power and Project No. SPECIFICATION GUIDELINES

5 are to be rated at a minimum of 1 amp at 24 VDC or 0.5 amps at 120 VAC. Strike outputs that only supply voltage are unacceptable. These devices shall be connected to the terminal controllers through snap-in Buchanan type plugs. These controllers shall be labeled to insure the correct wire coding is followed and the appropriate devices are wired in the correct locations. 5. The terminal controllers shall provide additional alarm points and outputs. The contacts shall be voltage-free Form "C" while the monitor points shall provide 4 conditions of status, normal, abnormal, cut, and short. There shall be 2 of each type of point available per controller and expanded to a capacity of 16 alarm points and 16 outputs total through use of an alarm interface module. E. I/O Expansion Board: 1. The system shall provide the interface of the I/O Board to be directly interfaced to any terminal controllers for a total of eight (128 inputs/128 outputs) in the system. Equipment supplied that requires alarm monitoring devices having their own address and take away from the systems total reader or address capacity is not acceptable. 2. The I/O board shall be logic driven by the connected terminal controller and allow the alarm points and output control specified above. These abilities shall exist whether the terminal controller is on-line or off line to the system controller. 3. Each of the 14 alarm points shall have supervision capabilities and shall allow a 500 foot, 22 gage wire run to each alarm device. 4. Each of the 14 control outputs shall be single pole, double throw (SPDT) Form C relays. These devices shall be rated for 1 amp at 24VDC or 0.5 amps at 120VAC. All outputs shall be made to allow for any of the following states to be programmed. Outputs shall be configured to close momentarily or set to follow the state of the corresponding inputs. These states shall also work with outputs being managed under time zones. F. Network Wiring: 1. The communications network shall be made up of a primary and secondary bus. The communications protocol used shall be RS485. Networks using 20 mil current loop or RS232 will not be acceptable. The secondary bus shall use a dual twisted pair, Beldon #8723 (22 AWG) cable and be capable of a distance of 4000 feet, total Project No. SPECIFICATION GUIDELINES

6 wire. This network shall be wired in any configuration needed. 2. Reader cabling shall use a 5-conductor West Penn #3280 (18 AWG) overall shield. Readers requiring coaxial cable will not be acceptable. A reader shall be wired a minimum of 500 feet without wire size change. Readers requiring a wire size change or special adapters to drive signal this distance are not acceptable. G. The system communications shall be supervised for integrity. If communications are detected as failed, the system shall report the loss and automatically enable the buffer of the non-communicating terminal controller(s) in the network. A system that does not buffer event information upon lost communications is not acceptable. H. Proximity Card Readers: 1. The proximity card reading sensor shall be a sealed unit with no moving parts that connects to the terminal controller via a 5-conductor cable. a. It shall detect the coded information in the access cards and send the information to the terminal controller for processing. b. As a minimum, it shall detect access card codes when a card is within 2 inches of its surface. 2. The reader design shall allow operation behind nonmetallic surfaces and to be surface mounted on virtually any surface (including glass) without requiring cutouts or mounting bolts. 3. Any reader may be used in a normal mode or antipassback mode without changes to the reader. 4. The readers shall be designed to operate properly within the temperature range of -50 degrees F. to +180 degrees F. (-45 degrees C. to 82 degrees C.) and within a relative humidity range of 0 to 100 percent. 5. No special housing nor treatment shall be required for outdoor use. 6. Unit shall be water and vandal resistant. 7. Physical damage including breaking open of the reader housing shall not allow a perpetrator access to any circuitry that would allow the system to be compromised. Transmission of any frequency or set of frequencies into the sensor at any power level shall not compromise the system. 8. Presentation of an invalid set of frequencies (such as would occur if a perpetrator were attempting to "pick" the system) shall temporarily disable the reader, thus Project No. SPECIFICATION GUIDELINES

7 eliminating the possibility of "sweeping" the system and finding a valid combination. I. Access Cards: 1. The access card shall be credit card size, not deteriorate with age, and shall be capable of reasonable flexing without damage. 2. Twenty access cards shall be supplied with the system. Each card shall be encoded with a code that is different from all other system codes. Supply the Board a list of all access codes for programming into memory. J. Related Door Hardware Requirements: 1. Electro-magnetic lock: Von Duprin Series 4000, 24VDC conductors to jamb header. Belden 8461, 18 gage, stranded. 2. Medeco Lock No installed at secondary means of egresses. 3. Electro-magnetic locks, power supplies, and Medeco locks shall be provided by door hardware supplier and wired under this section. 4. Emergency manual release device: See Life Safety Code S C K. The system and terminal controller and local modem will be enclosed in a metal cabinet with a door hinged on the side with key lock. L. Provide and install manufacturer specified and compatible modem to interface with M-DCPS District Communications Management (DCOM). Contact DCOM at for assistance and testing. PART 3 EXECUTION 3.01 INSPECTION A. Do not proceed with the work of this section until conditions detrimental to the proper and timely completion of the work have been corrected in an acceptable manner PREPARATION A. Coordinate and inform other trades of locations of all pieces of equipment to be installed under this section for proper functional interface with other equipment or hardware to avoid any interference or delay in the progress Project No. SPECIFICATION GUIDELINES

8 of the work. B. Conduit and wiring installation shall be according to Sections 01043, 16112, and other parts of this Section. C. In case of discrepancies, consult with A/E before proceeding with the work. Failure to comply will make the Contractor responsible for any cost involved in the proper execution of the work INSTALLATION A. System equipment and wiring installation shall be by the properly licensed company, either the original equipment manufacturer or the factory distributor for the brand of equipment used. Furnish wiring diagrams and wire runs for the raceway system installed by the licensed electrical contractor, under Division FIELD QUALITY CONTROL A. After installation, the system shall be under complete control of DCOM and perform system controls as specified without the services of the manufacturer. B. The following is a list of minimum acceptable DCOM initiated management functions: 1. Add cards to memory with ability to define where and when the cardholder may use the card. On a door-by-door basis, valid access times shall be definable. 2. Group load cards with the same access control privileges using any reader. 3. Delete access cards from memory. 4. Modify access control privileges of individual cards. 5. Define certain cards as "night" (privileged) cards allowing access to "night" readers when the alarm system is in the "night" mode. 6. Define primary and alternate facility code for cards. 7. Define the system configuration data (i.e., which doors are active IN and OUT doors, relationship of doors and contact points, etc.). 8. Define which doors will have request-to-exit (alarm shunt) implemented. 9. Define which monitored doors will alarm when "forced" open and during what time such alarms will take place. 10. Select card controlled areas that are to operate in an anti-passback mode and whether contact closure is required to change anti-passback status. 11. Manually unlock locks from the terminal. Project No. SPECIFICATION GUIDELINES

9 12. Define up to 15 access codes (groups of doors with up to 4 time codes associated with each door). 13. Define up to 32 holidays. 14. Automatically unlock and relock selected locks by time code. 15. Define which readers are "night" mode (Building Closed) sensors. 16. Define which readers are "switch" sensors that can enable or disable the "night" mode of operation (i.e. enable and disable the alarm system). 17. Select sensors that will generate an alert message when cardcodes selected for traces are used. 18. Obtain hard copy listings of cardcodes by any combination of access code, time period, location (IN or OUT), privileged (night mode), and trace status. 19. Obtain hard copy listings of the definitions of any door sensor or monitor point. 20. Obtain hard copy listings of each report type. Define pass-codes and up to 6 levels of access for operator entry into system command mode. 21. Obtain hard copy report of current system status. 22. Select access and monitor point activity messages that are output to the system printer. 23. Determine if valid access reporting is required only at certain hours of the day and week for selected sensors. 24. Acknowledge alarm conditions. 25. Select which monitor points are to be monitored at all times and which are monitored only during selected time periods. 26. Select which doors and monitor points will actuate output contacts. 27. Select which monitor points are to generate a latched alarm and which are to report for information purposes only. 28. Define under what circumstances the system will "dial up" and report to DCOM. 29. Define up to 4 telephone numbers for dial-up use. 30. Define how many attempts (up to 10) will be made to communicate via dial-up. 31. Define when the system will report that building closure is overdue. 32. Define a 24-character name for each monitor point. 33. Define a 12-character name for each sensor. 34. Define a 12-character name for each employee. 35. Define a 12-character name for each operator. 36. Select card controlled areas that are to be monitored for "Forced" and "Door Held Open" alarms, and whether such alarms will be generated at all times or only when system is in "night" mode. Project No. SPECIFICATION GUIDELINES

10 C. All system activity messages to the operator shall be printed in plain language, English text. Mnemonic type, or transaction-code type operator messages are not acceptable. D. A complete operator's manual shall also be supplied. 1. The system shall use passwords. A password must be used by an operator to gain access to system commands. Each password shall be assigned to one of 6 command levels. A command level is a set or subset, of all system commands. It shall be possible to define up to 8 passwords. E. Central console equipment necessary for full system operation shall be furnished as part of the initial installation. F. A final test before substantial completion shall be performed by the Contractor. G. After substantial completion, Contractor shall provide complete detailed Record Drawings (6 sets), written operation instructions and manuals. H. Wiring Requirements: All wiring incidental to the protection system shall be provided by the low voltage electrical contractor. Detailed wiring diagrams and necessary job site supervision shall be provided by the low voltage electrical contractor. The term "wiring" shall include furnishing of wire, conduits, miscellaneous materials and labor as required for connecting the system equipment DEMONSTRATION A. Training: Conduct a minimum one day course for system operators and users. END OF SECTION Project No. SPECIFICATION GUIDELINES

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator.

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator. SECTION 281300 - ACCESS CONTROL SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Minimum standards for Access Control Systems. B. Related Requirements: 1. Section 087100 Door Hardware. 1.2 REFERENCES

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY 281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES ACCESS CONTROL SYSTEM

CONSULTANT PROCEDURES & DESIGN GUIDELINES ACCESS CONTROL SYSTEM GENERAL: To provide minimum standards for Access Control Systems. PART 1 Common Work Results for Access Control System 1.1 Owner will provide server and software for connecting control panels through the

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Cardax System Comparison

Cardax System Comparison System Comparison Hardware FT Series 5 Syst Com 131102 Syst Com 131102 2 Contents 1. Introduction... 5 2. System Diagrams... 7 3. Hardware Comparison... 10 4. Comparison... 11 Syst Com 131102 3 Syst Com

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events.

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events. 0BThe System The Security Management System should be capable of Controlling and Monitoring Access through the doors, Monitor and control Inputs and Outputs, include an Integrated Video Badging, Integrate

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

DOOR MONITORING/DURESS SYSTEM

DOOR MONITORING/DURESS SYSTEM SECTION PART 1 - GENERAL 1.1 RELATED SECTIONS A. Comply with the requirements of Section 27 05 00 Common Work Results for Communications. 1.2 DEFINITIONS A. Not used. 1.3 DESCRIPTION OF SYSTEM: A. Provide

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

Appendix 1 LACCD Districtwide Security Performance Requirements

Appendix 1 LACCD Districtwide Security Performance Requirements Appendix 1 LACCD Districtwide Security Performance Requirements SECTION LISTING 28 01 10 Overview 28 13 00 Access Control System 28 13 01 Access Control System Installation 28 13 26 Access Control Remote

More information

HARDwired Installation/ Owner s Manual

HARDwired Installation/ Owner s Manual HARDwired Installation/ Owner s Manual Use this manual for circuit - Revision L or higher. For Models:,, and Multi-Door Access Controller Wiegand Compatable --R-- Provides Access Control System to manage

More information

LOCK INTO THE ACSI ADVANTAGE LOCK INTO THE ACSI ADVANTAGE

LOCK INTO THE ACSI ADVANTAGE LOCK INTO THE ACSI ADVANTAGE LOCK INTO THE ACSI ADVANTAGE LOCK INTO THE ACSI ADVANTAGE MODIFICATIONS TO: ADAMS RITE ARROW CORBIN RUSSWIN DORMA DOROMATIC MONARCH PRECISION SARGENT VON DUPRIN YALE and more SERIES 1500 EXIT DEVICES CATALOG

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

ARCHITECTURAL AND ENGINEERING SPECIFICATION

ARCHITECTURAL AND ENGINEERING SPECIFICATION ARCHITECTURAL AND ENGINEERING SPECIFICATION Access Control System ACTpro Vanderbilt Industries, Clonshaugh Business and Technology Park, Dublin, D17 KV84, Ireland TABLE OF CONTENTS PART 1 GENERAL 1.1 System

More information

Networked Access Control Panel. Installation Guide

Networked Access Control Panel. Installation Guide XP2M Networked Access Control Panel V1.0X Installation Guide X P 2 M A C C E S S C O N T R O L S Y S T E M Installation Guide Document Ref: PLAN XP2M Installation Guide V4(G)2010 Access Control Services

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

AIRPORTS. CARECALLER PowerfulSecuritySolutionsForSeriousSecurityNeeds

AIRPORTS. CARECALLER PowerfulSecuritySolutionsForSeriousSecurityNeeds AIRPORTS CARECALLER PowerfulSecuritySolutionsForSeriousSecurityNeeds CARECALLER CARECALLER Emergency Call Systems are perfect for any Airport that is concerned with the safety and security of their employees.

More information

UBC Technical Guidelines Section Edition Access Control Page 1 of 5

UBC Technical Guidelines Section Edition Access Control Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 28 05 00 Access Services: General Standards.2 Section 08 71 00 Door Hardware 1.2 Coordination Requirements.1 UBC Access Services 1.3 Description.1

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

CRC Technical Reference Manual P/N Rev NOV01

CRC Technical Reference Manual P/N Rev NOV01 CRC Technical Reference Manual P/N 3100132 Rev 1.0 01NOV01 DEVELOPED BY COPYRIGHT NOTICE CREDITS Edwards Systems Technology 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 2001 Edwards

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy

More information

RFP Addendum 2 March 31, 2016

RFP Addendum 2 March 31, 2016 RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)

More information

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead

More information

ARCHITECTURAL DOOR HARDWARE KEY PADS & CARD READERS CATALOG

ARCHITECTURAL DOOR HARDWARE KEY PADS & CARD READERS CATALOG ARCHITECTURAL DOOR HARDWARE KEY PADS & CARD READERS CATALOG January 1, 2017 v3 West Coast Office (800) 544-4422 East Coast Office (800) 225-6737 intldoorclosers.com Index KEY PADS & CARD READERS Heavy

More information

Network Display Unit Installation Instructions

Network Display Unit Installation Instructions Network Display Unit Installation Instructions Introduction This publication describes the installation procedures for the optional Network Display Units (NDUs). This product is compatible with both the

More information

Installation Manual COPYRIGHT NOTICE

Installation Manual COPYRIGHT NOTICE Installation Manual COPYRIGHT NOTICE Copyright 2007 by Quest Controls Inc (QUEST). The material discussed in this publication is the proprietary property of QUEST. QUEST retains all rights to reproduction

More information

Access CONTROL. MANAGEMENT Software

Access CONTROL. MANAGEMENT Software Software Guide Access CONTROL MANAGEMENT Software Engineered to meet today s demands and tomorrow s challenges, Keyscan s System VII software delivers unique features to provide an access control solution

More information

7638 Standish Place Derwood, MD Tel: (301) Fax: (301) Page 1 of 12. Website:

7638 Standish Place Derwood, MD Tel: (301) Fax: (301) Page 1 of 12. Website: 7638 Standish Place Derwood, MD 20855 Tel: (301) 760-4016 Fax: (301) 762-2253 Page 1 of 12 Website: www.rbtec.com E-Mail: info@rbtec.com Purpose The purpose of this document is to provide performance specifications

More information

TLS-300 UST Monitoring and Leak Detection System

TLS-300 UST Monitoring and Leak Detection System Part 1 General System Requirements 1.1 Description TLS-300 UST Monitoring and Leak Detection System A. These Specifications are intended to provide information by which prospective bidders may understand

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Table of Contents. Appendix A Special Characters 31

Table of Contents. Appendix A Special Characters 31 Table of Contents Introduction 2 Section 1: General System Operation 3 1.1 Getting to Know Your System... 3 1.2 How to Arm... 4 1.3 Alternate Arming Methods... 5 1.4 Disarming... 6 1.5 Alarm Memory...

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

Hugs Product Guide Specification

Hugs Product Guide Specification Stanley Healthcare Solutions 309 Legget Drive Ottawa, ON K2K 3A3, Canada Tel: 1.866.559-6275 Int l: +1 (613) 592.6997 Fax: (613) 592.4296 Web site: www.stanleyhealthcare.com E-mail: hugssupport@stanleyworks.com

More information

SECTION ENERGY MANAGEMENT SYSTEM (EMS)

SECTION ENERGY MANAGEMENT SYSTEM (EMS) SECTION 13810 ENERGY MANAGEMENT SYSTEM (EMS) PART 1 GENERAL 1.01 SUMMARY A. Section Includes: The energy management system (EMS) including the following major subsystems: HVAC temperature controls, HVAC

More information

_5120_School_Intercom_Rack_Spec.doc 09/21/04

_5120_School_Intercom_Rack_Spec.doc 09/21/04 ****************************************************************************************** 16720-3 Simplex TrueCom 5120 Inter Communication System Advanced 360 Station, Rack Mounted, Intercom / Paging

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Access Control System - CAAMS. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Access Control System - CAAMS. Basis of Design Basis of Design The section applies to the design, rough-in, and installation of automated access control systems for University facilities. These systems control access at building entrances and at the

More information

Card Access Control Specifications

Card Access Control Specifications 1.0 Qualifications Card Access Control Specifications 1.01 Vendors must be pre-qualified for card access on the SHSU campus. 2.0 General Requirements and Notes 2.00 SHSU requires that all exterior doors

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training PowerWizard Level 1.0 & Level 2.0 Control Systems Training New Systems Current Systems Systems Comparison Level 1 Level 2 Level 3 Level 4 PowerWizard Level 3.0 PowerWizard Level 4.0 Overview Common parts

More information

/ How To Order

/ How To Order 84-800 / 85-800 How To Order SERIES 84 = 1.0A continuous (powers and controls 1 EExER device with signal output for 1 operator) 85 = 2.0A continuous (powers and controls EExER device for 1 pair of doors

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

KT-100 Door Controller

KT-100 Door Controller WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K PEGAsys Multi-Loop Intelligent Suppression Control System A UTC Fire & Security Company Effective: March 2007 K-76-028 FEATURES UL Listed CSFM Approved MEA Approved Peer-to-Peer Networking (to 32 nodes)

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

D1255RB/D1256RB/D1257RB

D1255RB/D1256RB/D1257RB D1255RB/D1256RB/D1257RB EN Installation Instructions Fire Keypads and Fire Alarm Annunciator D1255RB/D1256RB/D1257RB Installation Instructions Listings and Approvals Listings and Approvals UL 365 UL 609

More information

G SERIES: Security INTEGRATION as you want it. Greater expansion, communication, video integration, system resilience, and automation.

G SERIES: Security INTEGRATION as you want it. Greater expansion, communication, video integration, system resilience, and automation. G SERIES: Security INTEGRATION as you want it Greater expansion, communication, video integration, system resilience, and automation. G Series Integrated Security Solution Fire Intrusion Access Greater

More information

Perimeter Product Overview. Effective protection for your business

Perimeter Product Overview. Effective protection for your business Perimeter Product Overview Effective protection for your business The Gallagher difference Our innovation is driven by the desire to solve problems, meet your needs and provide real business value. We

More information

Bi-Directional Barrier Arm Turnstile

Bi-Directional Barrier Arm Turnstile ES831 *Custom model shown in stone and bronze Bi-Directional Barrier Arm Turnstile Model ES831 Optical Turnstiles > ES831 Series > Optical Turnstiles w/ Barrier Arms > Design Overview The ES831 bi-directional

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

DIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts.

DIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts. DIVISION 14 - CONVEYING SYSTEMS I. GENERAL A. This division contains: 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts. B. Elevators in schools are for the disabled, furniture

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Fiber Optic Cable Fence Disturbance Sensor

Fiber Optic Cable Fence Disturbance Sensor Architectural & Engineering Specification for Fiber Optic Cable Fence Disturbance Sensor Purpose of document This document is intended to provide performance specifications and operational requirements

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Pro-Watch Software Suite. Architect and Engineering Specifications. January 9, 2002 Revision 3.4

Pro-Watch Software Suite. Architect and Engineering Specifications. January 9, 2002 Revision 3.4 Architect and Engineering Specifications Revision 3.4 SECTION 13800 BUILDING AUTOMATION AND CONTROL Part 1 GENERAL 1.0.1. GENERAL 1.0.2. REFERENCES 1.0.3. DEFINITIONS 1.0.4. SYSTEM DESCRIPTIONS 1.0.5.

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

SECTION DOOR HARDWARE

SECTION DOOR HARDWARE McClellan Blakemore Architects New Warehouse Facility for SECTION 08710 DOOR HARDWARE PART 1 GENERAL 1.01 SECTION INCLUDES A. Hardware for wood and hollow steel doors. B. Hardware for fire-rated doors.

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

BL 53 Security Barrier ENGINEERING SPECIFICATIONS

BL 53 Security Barrier ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS BL 53 Security Barrier SECTION 08 34 56 Security Gates SECTION 28 13 00 Access Control SECTION 34 71 13 Vehicle Barriers SECTION 34 75 13 Operable Roadway Equipment PART I GENERAL

More information

ARCHITECTURAL SPECIFICATIONS

ARCHITECTURAL SPECIFICATIONS 1 G4.1 Entrance System Page 1 of 6, August 2017 DIVISION 10 - SPECIALTIES SECTION 10450 PEDESTRIAN CONTROL DEVICES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements.

More information

BLG77 Rising Fenced Barrier

BLG77 Rising Fenced Barrier BLG77 Rising Fenced Barrier 1/8 ENGINEERING SPECIFICATIONS BLG77 Rising Barrier PART I GENERAL SECTION 08 34 56 Security Gates SECTION 11 12 33 Parking Gates SECTION 28 13 00 Access Control SECTION 34

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

UBC Technical Guidelines Section Edition Door Hardware Page 1 of 7

UBC Technical Guidelines Section Edition Door Hardware Page 1 of 7 Page 1 of 7 1.0 GENERAL 1.1 Related UBC Guidelines.1 Division 26.2 Division 28.3 Section 08 00 10 Openings General Requirements.4 Section 28 05 00 Common Work Results for Electronic Safety and Security.5

More information

Intelligent 2 & 4 Loop Fire Alarm Control Panels

Intelligent 2 & 4 Loop Fire Alarm Control Panels Intelligent 2 & 4 Loop Fire Alarm Control Panels Advanced has combined the latest technology with many years of fire experience, to create the Axis AX Series Intelligent Fire Alarm Control Panels. The

More information

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..

More information

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information: RDM LOCK G-1 1400 Series Electromagnetic Lock The patented 1400 Series Electromagnetic Lock is universal for all types of applications, including outdoor use. The innovative design will reduce installation

More information

Access Control (card access)

Access Control (card access) Access Control (card access) This page should be read in conjunction with security systems - general requirements. Aesthetic Cabling Unless cabling is to be in purpose built conduits within walling, which

More information

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description TrueCom Building Communications Systems 5115-Series 5115-9001, -9002 Area of Rescue Communications System Description The Simplex 5115-9001 and -9002 Area of Rescue Communications System provides buildings

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide

IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide Product Overview The IntelliKnight 5820XL is an intelligent addressable fire alarm control panel designed for flexibility and reliability.

More information

SL-3 Vibration Sensor line A&E Specifications Page 1 of 12 SL-3 AE v doc

SL-3 Vibration Sensor line A&E Specifications Page 1 of 12 SL-3 AE v doc SL-3 Vibration Sensor line A&E Specifications Page 1 of 12 SL-3 AE v2.0 05-14.doc Purpose The purpose of this document is to provide performance specifications and operational requirements for the RBtec

More information

GE TLC Softwired Contactor TM Guideform Specification

GE TLC Softwired Contactor TM Guideform Specification GE TLC Softwired Contactor TM Guideform Specification If you have any questions at all regarding this specification, please contact your local GE Lighting Control representative, or call the GE Lighting

More information

TTSIM-1 Sensor Interface Module

TTSIM-1 Sensor Interface Module R Sensor Interface Module Installation/Operation Guide General Information Please read these instructions and keep them in a safe place. These instructions must be followed carefully to ensure proper operation.

More information