1 SECTION CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where card insertion into a reading device is not required and will also be capable to function as an alarm and contact monitoring system. B. Related Sections: Finish Hardware Closed Circuit television System Intrusion Detection System Raceways and Conduits Wire and Cable Outlet, Pull, and Junction Boxes Grounding Fire Alarm and Detection System SYSTEM DESCRIPTION A. One designated door at each of the following locations shall be controlled by a card reader: 1. Entrance to administration. 2. Entrance to physical education office and storage. 3. Entrance from kitchen exterior at receiving (Truck loading area). 4. Entrance to media center. 5. Additional doors as indicated on Drawings SUBMITTALS A. Shop Drawings: 1. Submit riser and connection diagrams, schedules showing location and function of each device, and specification data sheets. 2. Supply a proposed acceptance test procedure. 3. Submittals showing typical riser diagrams and specification data sheets are not acceptable. 4. Submit 10 copies each. 5. Indicate card access locations on plans. Project No. SPECIFICATION GUIDELINES
2 1.04 QUALITY ASSURANCE A. The system supplier shall have a minimum of 5 years system design, engineering supervision, and installation experience in the alarm or access control industry. B. Any equipment, device, system component, or part provided or installed by contractor containing or using date processing shall be Year 2000 (Y2K) compliant. Before substantial completion, contractor shall provide a manufacturers statement of Year 2000 compliance and manufacturers and contractors warranty against daterelated failures. C. The Contractor shall provide a factory-trained technician to assist and advise installing personnel. Final connections shall be the sole responsibility of the Contractor WARRANTY A. The entire installation, except access cards, shall carry a 2-year guarantee after acceptance of the system by the Board. B. Access Card: 5 year warranty, all inclusive, for deterioration with age or damage due to reasonable flexing. C. Contractor shall guarantee all devices against defects in material or quality of construction. D. Electrical Contractor shall guarantee conduit, wire, and electrical installation labor for 2 years. E. Allied trades shall guarantee installation, material, and labor provided under this section of work. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Card Access Control Systems: 1. Checkpoint. 2. Simplex. 3. Westinghouse Security Electronics MATERIALS A. Provide electrical transient protection according to Project No. SPECIFICATION GUIDELINES
3 manufacturer's requirements. B. Include all necessary tools, equipment, material, and labor to furnish, install, and verify correct operation. C. The system shall consist of a central command center, UPS system, microprocessor based terminal controllers, input/output boards as required, proximity card readers, magnetic door position monitor contacts, and door strikes as required. D. Provide a modem according to manufacturers requirements and compatible with M-DCPS District Communications Management (DCOM). E. Provide a dedicated UPS system of 800 va or larger to provide backup power for the card access control headend. F. Remote power supplies for terminal controllers, magnetic locks, and door strikes connected to the card access system shall be provided with battery backup capacity to maintain complete system operation for 24 hours and be supervised for power failure EQUIPMENT A. Human Interface: 1. The system shall be capable of supporting a local or remote command center (terminal and printer). The interface is enabled by a menu-driven full text character set. This device shall be any industry standard ASCII terminal with a serial output. The human interface must accept as a minimum, a user-defined auto-logoff routine selectable from 0 to 240 minutes. This function shall be provided by the system controller. B. Network Components: 1. The distributed architecture requires the interface of various intelligent controllers. These controllers shall have operating environments to allow complete functionality at a temperature range of 0 to 50 degrees C and a relative humidity of 90 percent (noncondensing). C. System Controller: 1. The System Controller shall be microprocessor-based Project No. SPECIFICATION GUIDELINES
4 with onboard time and data generation and battery to allow a minimum of 48 hours data integrity. This device shall be responsible for maintaining the data communications between the terminal controllers attached and the ASCII terminal. 2. This device shall maintain the operating system parameters to include the definitions of, but not limited to, the following: a. Doors. b. Inputs. c. Outputs. d. Access Levels. e. Time Zones. f. Users. g. Operators. h. Dial-up communications. i. Auto Log-Off. j. Classify Events. 3. The definitions of these parameters shall be in full English text. Abbreviated text or code shall not be acceptable. 4. There shall be a maximum capability of 8 terminal controllers attached to any one system controller. The system shall be capable of accepting one system controller. This controller shall be modem compatible for communications over standard 3002 voice grade telephone lines. D. Terminal Controller: 1. The terminal controller shall be microprocessor based with onboard time date generation and battery to allow a minimum of 48 hours of data integrity. This device shall be responsible for all access control decision and alarm monitoring detection in the system. 2. It shall also be responsible for all output responses to alarm detection and create the appropriate response through its processor logic. This controller shall be capable of maintaining a buffer of a minimum of 2800 event transactions when communication is lost with the system controller. 3. System shall work with fail-safe and fail-secure locking hardware. 4. The terminal controller shall have all necessary provisions to implement access control for 2 doors. The capacity shall be present for 2 door contacts, to request to exit devices and 2 door strike outputs. These strike outputs shall control locking power and Project No. SPECIFICATION GUIDELINES
5 are to be rated at a minimum of 1 amp at 24 VDC or 0.5 amps at 120 VAC. Strike outputs that only supply voltage are unacceptable. These devices shall be connected to the terminal controllers through snap-in Buchanan type plugs. These controllers shall be labeled to insure the correct wire coding is followed and the appropriate devices are wired in the correct locations. 5. The terminal controllers shall provide additional alarm points and outputs. The contacts shall be voltage-free Form "C" while the monitor points shall provide 4 conditions of status, normal, abnormal, cut, and short. There shall be 2 of each type of point available per controller and expanded to a capacity of 16 alarm points and 16 outputs total through use of an alarm interface module. E. I/O Expansion Board: 1. The system shall provide the interface of the I/O Board to be directly interfaced to any terminal controllers for a total of eight (128 inputs/128 outputs) in the system. Equipment supplied that requires alarm monitoring devices having their own address and take away from the systems total reader or address capacity is not acceptable. 2. The I/O board shall be logic driven by the connected terminal controller and allow the alarm points and output control specified above. These abilities shall exist whether the terminal controller is on-line or off line to the system controller. 3. Each of the 14 alarm points shall have supervision capabilities and shall allow a 500 foot, 22 gage wire run to each alarm device. 4. Each of the 14 control outputs shall be single pole, double throw (SPDT) Form C relays. These devices shall be rated for 1 amp at 24VDC or 0.5 amps at 120VAC. All outputs shall be made to allow for any of the following states to be programmed. Outputs shall be configured to close momentarily or set to follow the state of the corresponding inputs. These states shall also work with outputs being managed under time zones. F. Network Wiring: 1. The communications network shall be made up of a primary and secondary bus. The communications protocol used shall be RS485. Networks using 20 mil current loop or RS232 will not be acceptable. The secondary bus shall use a dual twisted pair, Beldon #8723 (22 AWG) cable and be capable of a distance of 4000 feet, total Project No. SPECIFICATION GUIDELINES
6 wire. This network shall be wired in any configuration needed. 2. Reader cabling shall use a 5-conductor West Penn #3280 (18 AWG) overall shield. Readers requiring coaxial cable will not be acceptable. A reader shall be wired a minimum of 500 feet without wire size change. Readers requiring a wire size change or special adapters to drive signal this distance are not acceptable. G. The system communications shall be supervised for integrity. If communications are detected as failed, the system shall report the loss and automatically enable the buffer of the non-communicating terminal controller(s) in the network. A system that does not buffer event information upon lost communications is not acceptable. H. Proximity Card Readers: 1. The proximity card reading sensor shall be a sealed unit with no moving parts that connects to the terminal controller via a 5-conductor cable. a. It shall detect the coded information in the access cards and send the information to the terminal controller for processing. b. As a minimum, it shall detect access card codes when a card is within 2 inches of its surface. 2. The reader design shall allow operation behind nonmetallic surfaces and to be surface mounted on virtually any surface (including glass) without requiring cutouts or mounting bolts. 3. Any reader may be used in a normal mode or antipassback mode without changes to the reader. 4. The readers shall be designed to operate properly within the temperature range of -50 degrees F. to +180 degrees F. (-45 degrees C. to 82 degrees C.) and within a relative humidity range of 0 to 100 percent. 5. No special housing nor treatment shall be required for outdoor use. 6. Unit shall be water and vandal resistant. 7. Physical damage including breaking open of the reader housing shall not allow a perpetrator access to any circuitry that would allow the system to be compromised. Transmission of any frequency or set of frequencies into the sensor at any power level shall not compromise the system. 8. Presentation of an invalid set of frequencies (such as would occur if a perpetrator were attempting to "pick" the system) shall temporarily disable the reader, thus Project No. SPECIFICATION GUIDELINES
7 eliminating the possibility of "sweeping" the system and finding a valid combination. I. Access Cards: 1. The access card shall be credit card size, not deteriorate with age, and shall be capable of reasonable flexing without damage. 2. Twenty access cards shall be supplied with the system. Each card shall be encoded with a code that is different from all other system codes. Supply the Board a list of all access codes for programming into memory. J. Related Door Hardware Requirements: 1. Electro-magnetic lock: Von Duprin Series 4000, 24VDC conductors to jamb header. Belden 8461, 18 gage, stranded. 2. Medeco Lock No installed at secondary means of egresses. 3. Electro-magnetic locks, power supplies, and Medeco locks shall be provided by door hardware supplier and wired under this section. 4. Emergency manual release device: See Life Safety Code S C K. The system and terminal controller and local modem will be enclosed in a metal cabinet with a door hinged on the side with key lock. L. Provide and install manufacturer specified and compatible modem to interface with M-DCPS District Communications Management (DCOM). Contact DCOM at for assistance and testing. PART 3 EXECUTION 3.01 INSPECTION A. Do not proceed with the work of this section until conditions detrimental to the proper and timely completion of the work have been corrected in an acceptable manner PREPARATION A. Coordinate and inform other trades of locations of all pieces of equipment to be installed under this section for proper functional interface with other equipment or hardware to avoid any interference or delay in the progress Project No. SPECIFICATION GUIDELINES
8 of the work. B. Conduit and wiring installation shall be according to Sections 01043, 16112, and other parts of this Section. C. In case of discrepancies, consult with A/E before proceeding with the work. Failure to comply will make the Contractor responsible for any cost involved in the proper execution of the work INSTALLATION A. System equipment and wiring installation shall be by the properly licensed company, either the original equipment manufacturer or the factory distributor for the brand of equipment used. Furnish wiring diagrams and wire runs for the raceway system installed by the licensed electrical contractor, under Division FIELD QUALITY CONTROL A. After installation, the system shall be under complete control of DCOM and perform system controls as specified without the services of the manufacturer. B. The following is a list of minimum acceptable DCOM initiated management functions: 1. Add cards to memory with ability to define where and when the cardholder may use the card. On a door-by-door basis, valid access times shall be definable. 2. Group load cards with the same access control privileges using any reader. 3. Delete access cards from memory. 4. Modify access control privileges of individual cards. 5. Define certain cards as "night" (privileged) cards allowing access to "night" readers when the alarm system is in the "night" mode. 6. Define primary and alternate facility code for cards. 7. Define the system configuration data (i.e., which doors are active IN and OUT doors, relationship of doors and contact points, etc.). 8. Define which doors will have request-to-exit (alarm shunt) implemented. 9. Define which monitored doors will alarm when "forced" open and during what time such alarms will take place. 10. Select card controlled areas that are to operate in an anti-passback mode and whether contact closure is required to change anti-passback status. 11. Manually unlock locks from the terminal. Project No. SPECIFICATION GUIDELINES
9 12. Define up to 15 access codes (groups of doors with up to 4 time codes associated with each door). 13. Define up to 32 holidays. 14. Automatically unlock and relock selected locks by time code. 15. Define which readers are "night" mode (Building Closed) sensors. 16. Define which readers are "switch" sensors that can enable or disable the "night" mode of operation (i.e. enable and disable the alarm system). 17. Select sensors that will generate an alert message when cardcodes selected for traces are used. 18. Obtain hard copy listings of cardcodes by any combination of access code, time period, location (IN or OUT), privileged (night mode), and trace status. 19. Obtain hard copy listings of the definitions of any door sensor or monitor point. 20. Obtain hard copy listings of each report type. Define pass-codes and up to 6 levels of access for operator entry into system command mode. 21. Obtain hard copy report of current system status. 22. Select access and monitor point activity messages that are output to the system printer. 23. Determine if valid access reporting is required only at certain hours of the day and week for selected sensors. 24. Acknowledge alarm conditions. 25. Select which monitor points are to be monitored at all times and which are monitored only during selected time periods. 26. Select which doors and monitor points will actuate output contacts. 27. Select which monitor points are to generate a latched alarm and which are to report for information purposes only. 28. Define under what circumstances the system will "dial up" and report to DCOM. 29. Define up to 4 telephone numbers for dial-up use. 30. Define how many attempts (up to 10) will be made to communicate via dial-up. 31. Define when the system will report that building closure is overdue. 32. Define a 24-character name for each monitor point. 33. Define a 12-character name for each sensor. 34. Define a 12-character name for each employee. 35. Define a 12-character name for each operator. 36. Select card controlled areas that are to be monitored for "Forced" and "Door Held Open" alarms, and whether such alarms will be generated at all times or only when system is in "night" mode. Project No. SPECIFICATION GUIDELINES
10 C. All system activity messages to the operator shall be printed in plain language, English text. Mnemonic type, or transaction-code type operator messages are not acceptable. D. A complete operator's manual shall also be supplied. 1. The system shall use passwords. A password must be used by an operator to gain access to system commands. Each password shall be assigned to one of 6 command levels. A command level is a set or subset, of all system commands. It shall be possible to define up to 8 passwords. E. Central console equipment necessary for full system operation shall be furnished as part of the initial installation. F. A final test before substantial completion shall be performed by the Contractor. G. After substantial completion, Contractor shall provide complete detailed Record Drawings (6 sets), written operation instructions and manuals. H. Wiring Requirements: All wiring incidental to the protection system shall be provided by the low voltage electrical contractor. Detailed wiring diagrams and necessary job site supervision shall be provided by the low voltage electrical contractor. The term "wiring" shall include furnishing of wire, conduits, miscellaneous materials and labor as required for connecting the system equipment DEMONSTRATION A. Training: Conduct a minimum one day course for system operators and users. END OF SECTION Project No. SPECIFICATION GUIDELINES
SECTION INTRUSION DETECTION SYSTEM
SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing
More informationControl Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2
Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...
More informationSECTION INTRUSION DETECTION
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION
More informationB. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator.
SECTION 281300 - ACCESS CONTROL SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Minimum standards for Access Control Systems. B. Related Requirements: 1. Section 087100 Door Hardware. 1.2 REFERENCES
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if
More informationPWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More informationB. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).
SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover
More informationDIVISION 28 ELECTRONIC SAFETY AND SECURITY
281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationControl/Communicator
Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality
More informationCONSULTANT PROCEDURES & DESIGN GUIDELINES ACCESS CONTROL SYSTEM
GENERAL: To provide minimum standards for Access Control Systems. PART 1 Common Work Results for Access Control System 1.1 Owner will provide server and software for connecting control panels through the
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationCardax System Comparison
System Comparison Hardware FT Series 5 Syst Com 131102 Syst Com 131102 2 Contents 1. Introduction... 5 2. System Diagrams... 7 3. Hardware Comparison... 10 4. Comparison... 11 Syst Com 131102 3 Syst Com
More informationTAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE
TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means
More informationThe system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events.
0BThe System The Security Management System should be capable of Controlling and Monitoring Access through the doors, Monitor and control Inputs and Outputs, include an Integrated Video Badging, Integrate
More informationHRX Technical Manual. Version 1.2
HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire
More informationDOOR MONITORING/DURESS SYSTEM
SECTION PART 1 - GENERAL 1.1 RELATED SECTIONS A. Comply with the requirements of Section 27 05 00 Common Work Results for Communications. 1.2 DEFINITIONS A. Not used. 1.3 DESCRIPTION OF SYSTEM: A. Provide
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC
More informationUNC100 Integra Manual
UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant
More informationFIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200
FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.
More informationAppendix 1 LACCD Districtwide Security Performance Requirements
Appendix 1 LACCD Districtwide Security Performance Requirements SECTION LISTING 28 01 10 Overview 28 13 00 Access Control System 28 13 01 Access Control System Installation 28 13 26 Access Control Remote
More informationHARDwired Installation/ Owner s Manual
HARDwired Installation/ Owner s Manual Use this manual for circuit - Revision L or higher. For Models:,, and Multi-Door Access Controller Wiegand Compatable --R-- Provides Access Control System to manage
More informationLOCK INTO THE ACSI ADVANTAGE LOCK INTO THE ACSI ADVANTAGE
LOCK INTO THE ACSI ADVANTAGE LOCK INTO THE ACSI ADVANTAGE MODIFICATIONS TO: ADAMS RITE ARROW CORBIN RUSSWIN DORMA DOROMATIC MONARCH PRECISION SARGENT VON DUPRIN YALE and more SERIES 1500 EXIT DEVICES CATALOG
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationARCHITECTURAL AND ENGINEERING SPECIFICATION
ARCHITECTURAL AND ENGINEERING SPECIFICATION Access Control System ACTpro Vanderbilt Industries, Clonshaugh Business and Technology Park, Dublin, D17 KV84, Ireland TABLE OF CONTENTS PART 1 GENERAL 1.1 System
More informationNetworked Access Control Panel. Installation Guide
XP2M Networked Access Control Panel V1.0X Installation Guide X P 2 M A C C E S S C O N T R O L S Y S T E M Installation Guide Document Ref: PLAN XP2M Installation Guide V4(G)2010 Access Control Services
More informationSection PERIMETER SECURITY SYSTEMS
Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security
More informationAIRPORTS. CARECALLER PowerfulSecuritySolutionsForSeriousSecurityNeeds
AIRPORTS CARECALLER PowerfulSecuritySolutionsForSeriousSecurityNeeds CARECALLER CARECALLER Emergency Call Systems are perfect for any Airport that is concerned with the safety and security of their employees.
More informationUBC Technical Guidelines Section Edition Access Control Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 28 05 00 Access Services: General Standards.2 Section 08 71 00 Door Hardware 1.2 Coordination Requirements.1 UBC Access Services 1.3 Description.1
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationCRC Technical Reference Manual P/N Rev NOV01
CRC Technical Reference Manual P/N 3100132 Rev 1.0 01NOV01 DEVELOPED BY COPYRIGHT NOTICE CREDITS Edwards Systems Technology 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 2001 Edwards
More informationDS7400Xi Addressable Control/ Communicator
DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems
More informationSECTION SECURITY TESTING AND COMMISSIONING
SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,
More informationACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F
II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy
More informationRFP Addendum 2 March 31, 2016
RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)
More informationSECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR
SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead
More informationARCHITECTURAL DOOR HARDWARE KEY PADS & CARD READERS CATALOG
ARCHITECTURAL DOOR HARDWARE KEY PADS & CARD READERS CATALOG January 1, 2017 v3 West Coast Office (800) 544-4422 East Coast Office (800) 225-6737 intldoorclosers.com Index KEY PADS & CARD READERS Heavy
More informationNetwork Display Unit Installation Instructions
Network Display Unit Installation Instructions Introduction This publication describes the installation procedures for the optional Network Display Units (NDUs). This product is compatible with both the
More informationInstallation Manual COPYRIGHT NOTICE
Installation Manual COPYRIGHT NOTICE Copyright 2007 by Quest Controls Inc (QUEST). The material discussed in this publication is the proprietary property of QUEST. QUEST retains all rights to reproduction
More informationAccess CONTROL. MANAGEMENT Software
Software Guide Access CONTROL MANAGEMENT Software Engineered to meet today s demands and tomorrow s challenges, Keyscan s System VII software delivers unique features to provide an access control solution
More information7638 Standish Place Derwood, MD Tel: (301) Fax: (301) Page 1 of 12. Website:
7638 Standish Place Derwood, MD 20855 Tel: (301) 760-4016 Fax: (301) 762-2253 Page 1 of 12 Website: www.rbtec.com E-Mail: info@rbtec.com Purpose The purpose of this document is to provide performance specifications
More informationTLS-300 UST Monitoring and Leak Detection System
Part 1 General System Requirements 1.1 Description TLS-300 UST Monitoring and Leak Detection System A. These Specifications are intended to provide information by which prospective bidders may understand
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationTable of Contents. Appendix A Special Characters 31
Table of Contents Introduction 2 Section 1: General System Operation 3 1.1 Getting to Know Your System... 3 1.2 How to Arm... 4 1.3 Alternate Arming Methods... 5 1.4 Disarming... 6 1.5 Alarm Memory...
More informationCOUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III
SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSpectron LSN (Life Safety Network) Suggested Specifications
1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without
More informationHugs Product Guide Specification
Stanley Healthcare Solutions 309 Legget Drive Ottawa, ON K2K 3A3, Canada Tel: 1.866.559-6275 Int l: +1 (613) 592.6997 Fax: (613) 592.4296 Web site: www.stanleyhealthcare.com E-mail: hugssupport@stanleyworks.com
More informationSECTION ENERGY MANAGEMENT SYSTEM (EMS)
SECTION 13810 ENERGY MANAGEMENT SYSTEM (EMS) PART 1 GENERAL 1.01 SUMMARY A. Section Includes: The energy management system (EMS) including the following major subsystems: HVAC temperature controls, HVAC
More information_5120_School_Intercom_Rack_Spec.doc 09/21/04
****************************************************************************************** 16720-3 Simplex TrueCom 5120 Inter Communication System Advanced 360 Station, Rack Mounted, Intercom / Paging
More informationSECTION FIRE ALARM SYSTEMS
SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationDS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel
DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection
More informationSPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION
1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Access Control System - CAAMS. Basis of Design
Basis of Design The section applies to the design, rough-in, and installation of automated access control systems for University facilities. These systems control access at building entrances and at the
More informationCard Access Control Specifications
1.0 Qualifications Card Access Control Specifications 1.01 Vendors must be pre-qualified for card access on the SHSU campus. 2.0 General Requirements and Notes 2.00 SHSU requires that all exterior doors
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationHinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.
More informationPowerWizard. Level 1.0 & Level 2.0 Control Systems Training
PowerWizard Level 1.0 & Level 2.0 Control Systems Training New Systems Current Systems Systems Comparison Level 1 Level 2 Level 3 Level 4 PowerWizard Level 3.0 PowerWizard Level 4.0 Overview Common parts
More information/ How To Order
84-800 / 85-800 How To Order SERIES 84 = 1.0A continuous (powers and controls 1 EExER device with signal output for 1 operator) 85 = 2.0A continuous (powers and controls EExER device for 1 pair of doors
More informationOJD ITB No Attachment E Duress Alarm Equipment Specifications
Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;
More informationACTIVE INFRARED BARRIER
Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology
More informationKT-100 Door Controller
WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully
More informationPEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K
PEGAsys Multi-Loop Intelligent Suppression Control System A UTC Fire & Security Company Effective: March 2007 K-76-028 FEATURES UL Listed CSFM Approved MEA Approved Peer-to-Peer Networking (to 32 nodes)
More informationSECTION AUTOMATIC TRANSFER SWITCHES
SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationD1255RB/D1256RB/D1257RB
D1255RB/D1256RB/D1257RB EN Installation Instructions Fire Keypads and Fire Alarm Annunciator D1255RB/D1256RB/D1257RB Installation Instructions Listings and Approvals Listings and Approvals UL 365 UL 609
More informationG SERIES: Security INTEGRATION as you want it. Greater expansion, communication, video integration, system resilience, and automation.
G SERIES: Security INTEGRATION as you want it Greater expansion, communication, video integration, system resilience, and automation. G Series Integrated Security Solution Fire Intrusion Access Greater
More informationPerimeter Product Overview. Effective protection for your business
Perimeter Product Overview Effective protection for your business The Gallagher difference Our innovation is driven by the desire to solve problems, meet your needs and provide real business value. We
More informationBi-Directional Barrier Arm Turnstile
ES831 *Custom model shown in stone and bronze Bi-Directional Barrier Arm Turnstile Model ES831 Optical Turnstiles > ES831 Series > Optical Turnstiles w/ Barrier Arms > Design Overview The ES831 bi-directional
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationDIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts.
DIVISION 14 - CONVEYING SYSTEMS I. GENERAL A. This division contains: 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts. B. Elevators in schools are for the disabled, furniture
More informationGG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual
GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationFiber Optic Cable Fence Disturbance Sensor
Architectural & Engineering Specification for Fiber Optic Cable Fence Disturbance Sensor Purpose of document This document is intended to provide performance specifications and operational requirements
More informationTYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM
2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40
More informationOSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM
OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,
More informationTrueAlarm Fire Alarm Systems
OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK
More informationLaptop / PC Programming Manual
Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup
More informationPROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS
SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationPro-Watch Software Suite. Architect and Engineering Specifications. January 9, 2002 Revision 3.4
Architect and Engineering Specifications Revision 3.4 SECTION 13800 BUILDING AUTOMATION AND CONTROL Part 1 GENERAL 1.0.1. GENERAL 1.0.2. REFERENCES 1.0.3. DEFINITIONS 1.0.4. SYSTEM DESCRIPTIONS 1.0.5.
More informationSyncro AS. Analogue Addressable Fire Control Panel. User Manual
Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level
More informationMODEL B2 INSTALLATION MANUAL
RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and
More informationSECTION DOOR HARDWARE
McClellan Blakemore Architects New Warehouse Facility for SECTION 08710 DOOR HARDWARE PART 1 GENERAL 1.01 SECTION INCLUDES A. Hardware for wood and hollow steel doors. B. Hardware for fire-rated doors.
More informationDIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,
More informationBL 53 Security Barrier ENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS BL 53 Security Barrier SECTION 08 34 56 Security Gates SECTION 28 13 00 Access Control SECTION 34 71 13 Vehicle Barriers SECTION 34 75 13 Operable Roadway Equipment PART I GENERAL
More informationARCHITECTURAL SPECIFICATIONS
1 G4.1 Entrance System Page 1 of 6, August 2017 DIVISION 10 - SPECIALTIES SECTION 10450 PEDESTRIAN CONTROL DEVICES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements.
More informationBLG77 Rising Fenced Barrier
BLG77 Rising Fenced Barrier 1/8 ENGINEERING SPECIFICATIONS BLG77 Rising Barrier PART I GENERAL SECTION 08 34 56 Security Gates SECTION 11 12 33 Parking Gates SECTION 28 13 00 Access Control SECTION 34
More informationAcross-the-Line SERIES MP300 Combined Manual and Automatic
Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps
More informationUBC Technical Guidelines Section Edition Door Hardware Page 1 of 7
Page 1 of 7 1.0 GENERAL 1.1 Related UBC Guidelines.1 Division 26.2 Division 28.3 Section 08 00 10 Openings General Requirements.4 Section 28 05 00 Common Work Results for Electronic Safety and Security.5
More informationIntelligent 2 & 4 Loop Fire Alarm Control Panels
Intelligent 2 & 4 Loop Fire Alarm Control Panels Advanced has combined the latest technology with many years of fire experience, to create the Axis AX Series Intelligent Fire Alarm Control Panels. The
More informationGASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL
GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..
More informationRDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:
RDM LOCK G-1 1400 Series Electromagnetic Lock The patented 1400 Series Electromagnetic Lock is universal for all types of applications, including outdoor use. The innovative design will reduce installation
More informationAccess Control (card access)
Access Control (card access) This page should be read in conjunction with security systems - general requirements. Aesthetic Cabling Unless cabling is to be in purpose built conduits within walling, which
More informationMichigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE
PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationTrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description
TrueCom Building Communications Systems 5115-Series 5115-9001, -9002 Area of Rescue Communications System Description The Simplex 5115-9001 and -9002 Area of Rescue Communications System provides buildings
More informationFire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63
Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.
More information1.3 REFERENCE STANDARDS
SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises
More informationIntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide
IntelliKnight 5820XL Addressable Fire Alarm Control System Sales Guide Product Overview The IntelliKnight 5820XL is an intelligent addressable fire alarm control panel designed for flexibility and reliability.
More informationSL-3 Vibration Sensor line A&E Specifications Page 1 of 12 SL-3 AE v doc
SL-3 Vibration Sensor line A&E Specifications Page 1 of 12 SL-3 AE v2.0 05-14.doc Purpose The purpose of this document is to provide performance specifications and operational requirements for the RBtec
More informationGE TLC Softwired Contactor TM Guideform Specification
GE TLC Softwired Contactor TM Guideform Specification If you have any questions at all regarding this specification, please contact your local GE Lighting Control representative, or call the GE Lighting
More informationTTSIM-1 Sensor Interface Module
R Sensor Interface Module Installation/Operation Guide General Information Please read these instructions and keep them in a safe place. These instructions must be followed carefully to ensure proper operation.
More information