1 Fire Protection in High-rise Buildings By: Dante B. Verano 1.0 General Design Approach 1.1 All fire protection and detection systems design and installation shall be in accordance with local Authority Having Jurisdiction (AHJ) by laws, regulations, orders, codes, requirements and to International Standards such as NFPA. 1.2 When a conflict between the various code requirements exist, the most stringent/conservative standard shall apply. 1.3 Occupancy hazard fire control approach in combination with the density/area method is the common method to determine the water demand requirements. 2.0 Building Height Categories Building Categories Height Low - rise Mid - rise High - rise Super high - rise up to 15 meters between 15 meters to 23 meters between 23 meters to 90 meters more than 90 meters 3.0 Occupancy Classification 3.1 Light Hazard The areas and occupancies which and contain low quantity and low combustible materials which are expected to release low heat release rates during fire condition shall be classified as light hazard occupancies. Occupancies considered as light hazard may include: a) Residential - Residential buildings, Apartments, Staff Accommodation b) Assembly, Group B & Group C - Mosques, Churches, museums, amusement parks, Airport Terminal Buildings, Restaurant seating areas, Food court seating areas c) Detention and Correctional Facilities d) Animal Housing, Group A & Group C Pet Shops, Animal market, Zoo e) Industrial Group C metal products fabrication assembly, brick and masonry fabrication, telephone exchanges and GSM switching stations. 3.2 Ordinary Hazard, Group 1 The areas and occupancies which contains medium quantity and moderate combustible materials and the storages up to 2.4 meters which are expected to release moderate heat release rates during fire condition shall be classified as Ordinary Hazard Group-1. Occupancies considered as ordinary hazard are: a) Hotel, Group A & Group B & Group C - Hotels, Hotel Apartments, Dormitories, Motels, Lodging House, Resorts... b) Mercantile, Group A, Group B Department Stores, Supermarkets, Hardware Stores c) Storage, Group C - Parking garages, Frozen food, dairy products d) Industrial, Group B Appliances, Athletic equipment, automobiles, bakeries, boat building a) Assembly, Group A Night Clubs, Banquet Halls, Restaurant with more than 50 people, Pubs, Bars, Theater, Concert Halls, Cinemas
2 3.3 Ordinary Hazard, Group 2 The areas and occupancies which are used for commercial & industrial uses and contain medium quantity and moderate to high combustible materials and the storages up to 3.6 meters which are expected to release moderate heat release rates and the storages up to 2.4 meters which are high heat release rates during fire condition shall be classified as Ordinary Hazard Group-2, such as: a) Animal Housing, Group B - Stables, Animal Sheds, Livestock Shelters and slaughterhouses. b) Malls, Group A Covered Malls c) Industrial, Group B Repair Garages, textile Manufacturing, Printing and Publishing, Wood machining and wood product assembly 3.4 Extra High Hazard, Group 1 The areas and occupancies which are used for industrial uses and contains high quantity and very high combustible material which will support fast development of fire and are expected to release very high heat release rates during fire condition and having less or no combustible or flammable liquid & gases shall be classified as Extra High Hazard Group 1, such as: a) Storage / Industrial, Group B - Storage and activities involving aircraft hanger, leather, linoleum, and motor vehicle repair garages 3.5 Extra High Hazard, Group 2 The areas and occupancies which are used for industrial uses and contain moderate to high quantity of flammable & combustible liquids and gases, which will support rapid growth of fire and expected to release very high heat release rates during fire condition shall be classified as Extra High Hazard Group 2, such as: a) Storage / Industrial, Group A - Storage and activities involving explosives, detonators, pyrophoric materials, fireworks, pyrotechnic material, flammable spraying b) Group B Plastics c) Group C Plastics d) Combustible & Flammable Liquids e) Parking, Group B Robotic and Mechanical Parking f) Commodities 4.0 Fire Protection Systems High-rise building having building height of more than 23m but less than 90m, of any occupancy classification shall be provided with the following fire protection systems; 4.1 Automatic Sprinkler System (AS) Sprinkler shall be provided throughout the building including basements and podium (open as well as closed). 4.2 Wet Riser System (WRS) Class III Hose System shall be provided. The maximum pressure anywhere in the wet riser system shall not exceed 24bars with a fire pump set to cut-off at 140% of the rated operational pressure. When the vertical wet riser system pressure exceeds 12 bar with a fire pump set to cut-off at 140% of the rated operational pressure, or when most remote landing valve is located at a height 45m from the fire pump location, the risers shall be zoned in to High Zone and Low Zone.
3 The wet risers shall be interconnected both at the lowest level and highest level of each zone. When the vertical wet riser system pressure exceeds 24 bars with fire pump set to cut-off at 140% of the rated operational pressure, or when the most remote landing valve is located at a height of 90 meters from the fire pump location, the second set of fire pumps and dedicated water tanks shall be provided to feed such risers from that level. 4.3 Yard Hydrant Systems (YHS) All new developments with Plot Area greater than 20,000 m² shall be provided with private yard hydrant system. 4.4 Auxiliary rooms and various areas of the building shall be protected by other acceptable fire protection systems, such as; Other Fire Protection Systems Fire Hose Reel / Rack System (FHS) Dry Riser System (DRS) Pre-action Sprinkler System (PSS) Water Spray System (WSS) Water Mist System (WMS) Water Deluge System (WDS) Foam Sprinkler System (FSS) Foam Monitor System (FMS) Foam Injection System (FIS) Clean Agent Based Fire Protection System Dry Chemical System (DCS) Wet Chemical System (WCS) Portable Fire Extinguisher (FE) 5.0 Water Demand (Total Demand) The water requirements for a sprinklers building are based on sprinkler system and inside and outside hose streams demands. 5.1 Sprinkler Demand:
4 5.2 Hose Demand: Two (2) numbers of landing valves on top most point of the hydraulically most unfavorable wet riser proving 250gpm flow at 6.9bar (7bar) per outlet and one landing valve outlet on the topmost point of the adjacent wet risers providing 250gpm flow at 7bar outlet. If a horizontal wet riser system provides supply for 3 or more landing valve outlets in a floor, the hydraulic calculation shall be based on 3 numbers of landing valve at remotes point of the hydraulically most unfavorable wet riser pipe providing 250gpm flow at 7bar per outlet and one landing valve outlet at the topmost point of each adjacent wet riser pipes providing 250gpm flow at 7bar per outlet. 5.3 Hydrant Demand: The minimum flowrate for each fire hydrant shall be 500 gallons per minute at 250gom per outlet. Two (2) number of fire hydrants shall be considered for hydraulic demand calculations which is a total flow requirement of 1000gpm per single yard hydrant system. The minimum pressure required for the most remote fire hydrant in the system loop is 6.9bars. 5.4 Combined Fire Water Tank Capacities Without Yard Hydrants shall have a capacity of 60 minutes of operation With Yard Hydrants shall have a capacity of 90 minutes of operation
5 6.0 Fire Pump Sizing Formula: 1) WHP = Q x TDH ) BHP = WHP Ɛff. 3) Motor HP = BHP Ɛff. Where: WHP = Water Horse Power BHP = Brake Horse Power Motor HP = Motor Horse Power Ɛff. = Efficiency Q = Total Water Demand, GPM TDH = Total Dynamic Head, FT 7.0 Reference Code and Standards 7.1 UAE Fire and Life Safety Code of Practice NFPA 1 : Fire Code 7.3 NFPA 13: Standard for Installation of Sprinkler Systems 7.4 NFPA 14: Standard for the Installation of Standpipe and Hose System 7.5 NFPA 5000: Building Construction and Safety Code Ending thoughts; Sharing will enrich everyone with more knowledge. Ana Monnar If you have knowledge, let others light their candles in it. Margaret Fuller A candle loses nothing by lighting another candle. Father James Keller
PLAN REVIEW CHECKLIST
PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD STANDPIPE SYSTEMS PURPOSE This standard outlines the general requirements for the installation of standpipe systems. CODE REFERENCES
More informationHigh Ceiling Protection
High Ceiling Protection High Ceiling Protection An Investigation of Automatic Sprinkler Protection of Buildings with Non-Storage Occupancies and High Clearances Company Confidential 2 Background New architectural
More informationORDINANCE NUMBER
ORDINANCE NUMBER 2010-2 AN ORDINANCE AMENDING THE ORDINANCE 2007-4 REQUIRING THE INSTALLATION OF AUTOMATIC FIRE SUPPRESSION SYSTEMS IN CERTAIN STRUCTURES IN THE CITY OF STARKVILLE, OKTIBBEHA COUNTY, MISSISSIPPI
More informationFIRE EXTINGUISHER SPACING & INSTALLATION GUIDELINES
FIRE EXTINGUISHER SPACING & INSTALLATION GUIDELINES Town of Brighton Office of the Fire Marshal October 2018 Fire Extinguisher Spacing & Installation Guidelines Scope The Fire Code of New York specifies
More informationFire Suppression Introduction Contact Information
Contact Information Jeffrey Mayers Fire Safety Engineering Manager Georgia State Fire Marshal s Office 404-617-8515 E-mail: jmayers@sfm.ga.gov 1 Goal of This Seminar: Hierarchy of Codes List reference
More informationBUILDING/FIRE CODE REFERENCES 2006 EDITION
BUILDING/FIRE CODE REFERENCES 2006 EDITION This document provides a cross reference with the International Building Code and NFPA 1/Uniform Fire The IBC references the IFC in 97 Code sections. This document
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationThe following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101):
The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): 1.1.1 Title. NFPA 101, Life Safety Code, shall be known as the Life Safety Code, is cited as such, and shall
More informationRequirements. This Toolbox Talk has been created to assist you, and the user to assess the building Occupancy and classification.
This Toolbox Talk has been created to assist you, and the user to assess the building Occupancy and classification. We all know that the user s guide for placement, and quick inspection of their equipment
More informationSprinkler Permit Applications
REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations
More information1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)
1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors) 1. What is the minimum diameter for a non-hydraulically calculated Class III fire standpipe that is part of a combined
More informationFIRE PROTECTION SYSTEMS IN BURJ KHALIFA. By NAFFCO Fire Protection
FIRE PROTECTION SYSTEMS IN BURJ KHALIFA By NAFFCO Fire Protection 8 September 2015 Company Introduction NAFFCO ( National Fire Fighting Manufacturing FZCO ) an ISO 9001:2008 certified company with its
More informationPLACES OF ASSEMBLY CHAPTER 17
CHAPTER 17 PLACES OF ASSEMBLY SECTION 1701 GENERAL 1701.1 Scope. Places of assembly, including trade shows and exhibitions, outdoor assembly events, outdoors mazes, special amusement buildings and special
More informationMoving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design
Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System Part 1: Concept Design 2 Amy L. Porter, P.E. (TX,VA, NM) AND Michael Wojcik, P.E. (AZ, CO, MA,
More informationAmerican Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.
American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals
More informationFONTANA FIRE PREVENTION DISTRICT USER FEE LIST 2015 DEVELOPMENT SERVICES FEES PLANNING APPLICATION FEES Administrative Site Plan 516 Conditional Use
FONTANA FIRE PREVENTION DISTRICT USER FEE LIST 2015 DEVELOPMENT SERVICES FEES PLANNING APPLICATION FEES Administrative Site Plan 516 Conditional Use Permit Review 460 Design Review Project 802 Fuel Modification
More information*HB0217* H.B. 217 H.B STATE FIRE CODE ACT AMENDMENTS. LEGISLATIVE GENERAL COUNSEL 6 Approved for Filing: C.R. Gilbert :11 PM 6
LEGISLATIVE GENERAL COUNSEL 6 Approved for Filing: C.R. Gilbert 6 6 02-04-13 2:11 PM 6 H.B. 217 1 STATE FIRE CODE ACT AMENDMENTS 2 2013 GENERAL SESSION 3 STATE OF UTAH 4 Chief Sponsor: James A. Dunnigan
More informationBUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007
BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith
More informationFire protection for buildings
Fire protection for buildings HI-FOG high-pressure water mist Ghelamco Group Protecting people, property and business continuity A fire in a building can lead to serious consequences. Even a harmless fire
More informationMODULE 2. Water-Based Suppression System Basics
MODULE 2 Water-Based Suppression System Basics Based on the Ohio Building Code (OBC) National Fire Protection Association (NFPA) & Ohio Fire Code (OFC) 1 WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE
More informationPROJECT: NITESH PALO Bangalore FIRE SAFETY MEASURES
PROJECT: NITESH PALO ALTO @ Bangalore FIRE SAFETY MEASURES System Description 1 Firewater pumping system 2 Wet riser system and hose reel system. 3 Automatic sprinkler system 4 Yard hydrant system 5 Pressurization
More informationINSPECTOR I SKILLS ADMINISTRATION
INSPECTOR I SKILLS ADMINISTRATION 1- Prepare inspection reports so that the report is clear and concise and reflects the findings of the inspection in accordance with the applicable codes and standards..
More informationARTICLE XVIII C 1 CENTRAL BUSINESS DISTRICT
ARTICLE XVIII C 1 CENTRAL BUSINESS DISTRICT SECTION 1. INTENT AND PURPOSE OF DISTRICT: The C 1 Central Business District is intended for the purpose of grouping retail merchandising activities into a concentrated
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationOklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:
Oklahoma 310:451-1-3. Adopted references The Board of Health hereby incorporates by reference the International Code Council (ICC) 2006 (IBC) Edition International Building Code; the 2007 Edition Standard
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationCity of Santa Monica Fee Schedule Effective July 1, 2012
Fire Prevention Preliminary Review $176.17 Over the Counter Plan Check $176.17 Standard and Complex Plan Check New Buildings - Except One and Two Family Dwellings 1st 2,500 square feet $379.38 Over 2,500
More informationNOTICE TO PROSPECTIVE BUSINESSES STATEMENT OF INTENDED USE
COUNTY OF LOS ANGELES FIRE DEPARTMENT FIRE PREVENTION DIVISION East Region - Irwindale Office 5200 Irwindale Avenue #210, Irwindale, CA 91706 Form 30 (9/16) Office (626) 430-3050 Fax (626) 337-0788 Hours
More informationTHE BASICS OF BUILDING FIRE PROTECTION DESIGN. RES Symposium April 18, 2017
THE BASICS OF BUILDING FIRE PROTECTION DESIGN RES Symposium April 18, 2017 PRESENTER S BACKGROUND Ted Sherwood, PE, CFPS, LEED AP 5 years as a Code Enforcement Official and Division Head supervising all
More informationAircraft Hangers. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409
Aircraft Hangers DESCRIPTION Considering the value of commercial and military aircraft, it has become extremely important to have a reliable fixed fire protection system in aircraft storage, servicing,
More informationEXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5
UNIT PRICING IS A "NOT TO EXCEED" PRICE EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 Unit Pricing to perform all required Test
More informationSUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%
210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent
More informationFire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY
Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE
More informationAircraft Hangars DESCRIPTION. A single fire area not larger than 40,000 sq. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409
Aircraft Hangars DESCRIPTION Considering the value of commercial and military aircraft, it has become extremely important to have a reliable fixed fire protection system in aircraft storage, servicing,
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS > SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation,
More informationWILLIAM HICKS. MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI. Associate Professor Eastern Kentucky University
Foam Systems WILLIAM HICKS MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI Associate Professor Eastern Kentucky University William.Hicks@eku.edu Objectives Classify high, medium, and lowexpansion
More informationNFPA 45 NFPA 211 NFPA 1600
NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA
More informationOCFA Planning and Development Section Fees Effective September 28, 2015
Description (IFP) PLANNING & SITE DEVELOPMENT PR0 PR4 PR5 California Environmental Quality Act (CEQA), Environmental Impact Report (EIR), Notice of Preparation (NOP), Advance Planning requests for information
More informationCLOVERDALE FIRE PROTECTION DISTRICT FEE SCHEDULE
MISCELLANEOUS FIRE FEES: Aerosol Products Retail Operation $ 242.00 Aircraft Refueling Vehicle $ 222.00 Fire Alarm: New System Plan Check $ New System Inspection $ 480.00 Major Modification Plan Check
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationSpecial Occupancy Requirements
Special Occupancy Requirements CHAPTER 2 0 AVIATION FACILITIES CHAPTER 2 1 DRY CLEANING CHAPTER 2 2 COMBUSTIBLE DUST-PRODUCING OPERATIONS Special Occupancies The objective of this module is to make the
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities
More informationCOMMERCIAL PLAN SUBMITTAL CHECK LIST Mercantile / Business / Educational / Storage / Factory Industrial / Hazardous / Institutional
COMMERCIAL PLAN SUBMITTAL CHECK LIST Mercantile / Business / Educational / Storage / Factory Industrial / Hazardous / Institutional Two (2) Complete sets of plans and One (1) disk in PDF format including:
More informationCITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS
CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS Fire Protection Systems includes the following: Alternate Fire Suppression Systems Atrium Fire Protection Systems Automatic Fire Sprinkler
More informationDIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION
DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation
More informationFire Protection Coffee Break Training May 2016
Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers
More informationERRATA TO THE 2000 INTERNATIONAL FIRE CODE. Fourth Printing, January 2002 Updated March 29, 2002
ERRATA TO THE 2000 INTERNATIONAL FIRE CODE Fourth Printing, January 2002 Updated March 29, 2002 Table 2306.2 General Fire Protection and Life Safety Requirements In column 2 (Size of High Piled Storage
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved;
More informationLOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION
CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...
More informationTRI-LAKES MONUMENT FIRE PROTECTION DISTRICT
TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter
More informationSprinkler Standards Proposed Technical Changes
Sprinkler Standards 2002-2007 Proposed Technical Changes Featuring Speaker Bob Caputo Consolidated FireProtection, Inc August 9, 2006 1 1 SPEAKER Bob Caputo Consolidated FireProtection, Inc Bob Caputo
More informationRetain. Retain. Retain. Board Advisory. Board Advisory. Retain. Disposition. (Statute, Rule, FBC, Industry)
Florida Specific Amendment Code Reference NFPA 101 Anytime a reference is made to NFPA 1 or NFPA 101 within this Code, it shall be 1.1.1.1 the Florida specific version of NFPA 1 and NFPA 101. The Florida
More informationItem Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15
N/A N/A 2015 International Fire Code 2015 International Building Code Codes Jurisdictions for Fire and Building Codes Source of Information Building Fire Plumbing Mechanical Electrical Energy Code Accessibility
More informationSOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21
SOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21 ARTICLE I FIRE PREVENTION CODE 21-1. Statutory authority 21-2. Adoption of standards 21-3. Definitions 21-4. Exceptions to Fire Prevention Code
More informationAutomatic Fire Sprinkler Systems New Construction Matrix
Automatic Fire Sprinkler Systems New Construction Matrix September 2012-2009 I-Codes For additional information contact: Fire Prevention Division Building Safety Division (785) 832-3174 (785) 832-7700
More informationAutomatic Fire Sprinkler Systems New Construction Matrix
Automatic Fire Sprinkler Systems New Construction Matrix May 2013-2012 I-Codes For additional information contact: Fire Prevention Division Building Safety Division (785) 832-3174 (785) 832-7700 cking@lawrenceks.org
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationINDEPENDENT FIRE EXTINGUISHER SALES & SERVICES. Your First Line of Defense Since 1971
INDEPENDENT FIRE EXTINGUISHER SALES & Your First Line of Defense Since 97 Suppression Sales i Installation i Service ABOUT IFESSAR In business since 97 Serve over 4000 customers Service Arkansas and Mississippi
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More information2010 FIRE CODE OF NEW YORK STATE
2010 FIRE CODE OF NEW YORK STATE CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 1401 GENERAL 1401.1 Scope. This chapter shall apply to structures in the course of construction, alteration,
More informationBOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015
Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC
More informationCITY OF INDUSTRY USE PERMIT SUPPLEMENT A
CITY OF INDUSTRY USE PERMIT SUPPLEMENT A Before any application for a can be accepted as complete, the applicant must obtain a Fire Department stamp of approval on this form. In order to obtain approval,
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationHI-FOG for buildings. Technical introduction. Protecting people, property and business continuity. Jussi Tiainen
HI-FOG for buildings Technical introduction Jussi Tiainen Protecting people, property and business continuity Contents Introduction to HI-FOG...3 How HI-FOG fights fire...4 Principles of HI-FOG system
More informationExplosion Protection Engineering Principles
Handbook of Fire and Explosion Protection Engineering Principles for Oil, Gas, Chemical and Related Facilities Second edition Dennis P. Nolan ELSEVIER AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD
More informationKELLER WILLIAMS COMMERCIAL
KELLER WILLIAMS COMMERCIAL BALLANTYNE AREA Uptown Land Opportunity +/- 1 acre Charlotte, NC Scott Greene 704.577.7344 scottgreene@kw.com Matthew Hagler 704.408.8867 mhagler@kwcommercial.com Scott Stevens
More informationSUPPRESSION SALES I INSTALLATION I SERVICE
SUPPRESSION SALES I INSTALLATION I SERVICE ABOUT FESSAR In business since 1973 Serve over 4000 customers Service Arkansas and Mississippi Trained and certified suppression technicians Technicians are Arkansas
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationPort of St Helens SIA Aircraft Hanger Scappoose, OR
Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance
More informationHAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 7 BOARDS CHAPTER 45.1 STATE FIRE COUNCIL STATE FIRE CODE
HAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 7 BOARDS CHAPTER 45.1 STATE FIRE COUNCIL STATE FIRE CODE Subchapter 1 Rules of General Applicability 12-45.1-1
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply
More informationESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised
Engine Module Page 1 of 5 SPRINKLER HEADS Types of Sprinkler Heads There are many different types of sprinkler heads utilized in fire protection systems. Most are equipped with a thermal detector that
More informationBP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6
BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 1. Purpose This policy sets forth requirements for preventing and detecting fires, sounding an alarm, and suppressing fires. Fire protection
More informationPA 256 of 2011 Michigan Fireworks Safety Act What We Need To Know
We will discuss PA 256 of 2011 Michigan Fireworks Safety Act What We Need To Know Fire Marshal Michael Evans, CFPS Novi Fire Department Documents to be familiar with Definitions of the types of fireworks
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International
More informationMichigan Fireworks. Mike Evans Instructor # 2062 Program approval # A, 1S, 1T
Michigan Fireworks Mike Evans 734.942.3736 Instructor # 2062 Program approval # 17506 1 A, 1S, 1T PA 256 of 2011 Michigan Fireworks Safety Act What We Need To Know We will discuss Documents to be familiar
More informationCorrosion in Fire Sprinkler Systems Increasing Your Liability, Increasing Your Costs, and Shortening System Life
Corrosion in Fire Sprinkler Systems Increasing Your Liability, Increasing Your Costs, and Shortening System Life Jeff Merwin Director of Business Development Fire Sprinkler Monitoring / OEM Controls jeffm@pottersignal.com
More informationFIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS
Department of Fire Rescue & Emergency Services Fire Marshal s Office Dania Beach District 103 West Dania Beach Blvd. Dania Beach, Florida 33004 Office: (954)342-4262 Fax: (954)342-4265 FIRE SPRINKLER SHOP
More informationDOUGLAS L. BARRY FIRE CHIEF
DEPARTMENT...... DEC 18 2007,,..?,.... ;, ': ' : ;;: :.,..,. :; L,,........,, :,
More informationRevision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.
SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems
More informationPART 2. Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s
PART 2 Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s Occupancy Classifications Y A - Assembly Y B - Business Y E - Educational Y F - Factory/Industrial Y H - Hazardous
More informationDIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses
PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned
More informationBuilding Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design
June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor
More informationFIRE STOP 200/30. High technology system for first attack of fire with high pressure nebulized water (Water mist) FD 907. Ed.
NCAGE A5009 CONFORM TO THE QUALITY SYSTEM STANDARD AQAP 2110 and ISO 9001:2008 FD 907 Ed. 07/2016 FIRE STOP 200/30 High technology system for first attack of fire with high pressure nebulized water (Water
More informationBuilding Permit Type & Sub-Type Definitions
Building Permit Type & Sub-Type Definitions New Any new commercial building and the tenant is known (e.g., New grocery store). Foundation only Allows foundation to be started while the building plans are
More informationThe Authoritative Source for Plumbing, Hydronics;
The Authoritative Source for Plumbing, Hydronics; Fire Protection and PVF Find us on Facebook & Twitter twitter.com/plumbingeng facebook.comlplumbingengineer renew your subscription to Plumbing :-:. Engineer..[!]
More informationROSELAND FEE SCHEDULE Fees Effective: July 1, 2016
ROSELAND FIRE PROTECTION DISTRICT 2016-2017 ROSELAND FEE SCHEDULE Fees Effective: July 1, 2016 Fire and Life Safety Division Plan Review and Inspection Fees Base Fee Duration Additional Re-Inspection -
More informationThose uses will be allowed which are compatible with these overall objectives. 4. Public and private parks and playgrounds.
CHAPTER 500. SECTION 503. ZONING STANDARDS A-C AGRICULTURAL DISTRICT 503.1. Purpose The purpose of the A-C Agricultural District is to preserve the rural and open character of various lands within the
More informationNational Fire Authority
National Fire Authority GUIDELINE SELECTION, INSTALLATION & MAINTENANCE OF PORTABLE FIRE EXTINGUISHERS AND FIRE BLANKETS. First Issued: 15 October, 2007 Version No: 1 Guideline No: GL-01 Prepared By: Structural
More informationSEMICONDUCTOR FABRICATION FACILITIES
CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply
More informationThe following are the Proposed Amendments to 2015 edition of the Fire Code (NFPA 1):
The following are the Proposed Amendments to 2015 edition of the Fire Code (NFPA 1): 1.1.2 Title. The title of this Code shall be NFPA 1, Fire Code, of the National Fire Protection Association (NFPA).
More informationAPPENDIX A FEES SECTION FC A01 CERTIFICATES A01.1
FEES SECTION FC A01 CERTIFICATES A01.1 Certificate fees. Applicants for certificates required pursuant to the provisions of this code or the rules shall pay the fees specified in this section. Fees for
More informationINDEX 2006 VIRGINIA STATEWIDE FIRE PREVENTION CODE INDEX-1
A ABANDONED PREMISES (see VACANT PREMISES) ABANDONMENT Flammable and combustible liquid tanks.................... 3404.2.13 ACCEPTANCE TESTING Fire protection system installations.. 901.5, 904.4 Fire pumps.........................
More informationFoam Systems U.S. Quick Reference Guide
Foam Systems U.S. Quick Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation
More informationGUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES
OFFICE OF THE FIRE MARSHAL Worcester County GOVERNMENT CENTER - ONE WEST MARKET STREET - ROOM 1003 SNOW HILL, MARYLAND 21863-1194 TEL: 410-632-5666 FAX: 410-632-5664 GUIDELINES FOR INSPECTING GROUND BASED
More informationSecond Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement
Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,
More informationEmergency Evacuation Plan. Tiffany Tower Plot W2 Jumeirah Lakes Towers
Emergency Evacuation Plan Tiffany Tower Plot W2 Jumeirah Lakes Towers September 2017 TABLE OF CONTENTS 1.0 I N T R O D U C T I O N... 1 2.0 B U I L D I N G I N F O R M A T I O N... 1 3.0 F I R E S Y S
More information