Renovate MCRC Facilities Great Lakes, IL

Size: px
Start display at page:

Download "Renovate MCRC Facilities Great Lakes, IL"

Transcription

1 6. ENGINEERING SYSTEMS REQUIREMENTS D50 ELECTRICAL SYSTEM DESCRIPTION The electrical repair work includes the design and construction of the electrical distribution system for the B3200 Marine Corps Reserve Center and B8200 Vehicle Maintenance Facility. The electrical system for each area of work shall be designed after thorough site investigation and meeting with the local Electrical Utility Department and the Users, and shall be in accordance with the most current editions of the following: NFPA-70 National Electrical Code NFPA-70E Standard for Electrical Safety in the Workplace NFPA 101 Life Safety Code IEEE, ANSI, NEMA, and UL Standards IES, Lighting Reference Guide and Application Guide UFC , Electrical Engineering UFC , Interior Electrical Systems UFC , Design: Interior and Exterior Lighting and Controls UFC , Exterior Electrical Power Distribution UFC , Telecommunication Building Cabling Systems Planning and Design UFC , Navy Marine Corps Intranet (NMCI) Standard Construction Practices UFC , Electronic Security Systems Design and Construction Requirements-Energy Policy Act 2005 Provide an upgrade to the interior and exterior electrical systems consisting of Distribution and Lighting Panelboards, Dry Type Transformers, Conduits, Feeder and Branch Circuits, Motor Control Equipment, Lighting and Branch Wiring, Communications (also called Telecommunications), Security and Alarm Systems, Emergency Lighting and EXIT signs, Grounding, including accessories and devices as necessary and required for a complete and usable system. This section covers installations out to the building 5 foot (1.5 meter) line. Provide detailed circuit analysis, load calculations, design and installations of the existing and new electrical distribution systems. The distribution systems should meet the requirements for the existing and the new additional anticipated electrical loads for the Marine Corps Reserve Center Building B3200 and the VMF, B8200. The interior distribution system shall consist of copper insulated conductors in conduit, including an insulated green equipment grounding conductor. The conduit shall not be considered the equipment PART 3 - CHAPTER 6 / ESR D50 - Page 1

2 grounding conductor. GENERAL SYSTEM REQUIREMENTS Provide an Electrical System complete in place, tested and approved, as specified throughout this RFP, as needed for a complete, usable and proper installation. All equipment shall be installed per the criteria of PTS Section D50 and the manufacturer s recommendations. Where the word "should" is used in the manufacturer s recommendations, substitute the word "shall". D5010 ELECTRICAL SERVICE AND DISTRIBUTION D MAIN TRANSFORMERS Main transformer(s) are defined in Section G40, Site Electrical Utilities. B3200 has an existing 500KVA, 280Y/120V, 3PH-4W pad-mount transformer. B8200 has an existing 225KVA, 208Y/120V, 3PH-4W pad-mount transformer. B8201 does not have a dedicated transformer, but is fed from a separate 500KVA, 208Y/120V, 3PH-4W transformer located southwest of B3200. B8201 has a 42-pole, 208Y/120V, 3PH-4W, 225A MCB panelboard and is separately metered. D SERVICE ENTRANCE EQUIPMENT All service rated entrance equipment shall remain for re-use. Provide additional feeder breakers and feeder circuits as required for new branch panelboards to accommodate the additional loading. All service into and from the facility(ies) shall be underground. D INTERIOR DISTRIBUTION TRANSFORMERS Provide energy efficient dry type transformers to step down secondary voltages for general purpose outlets and other low voltage equipment. Transformers shall be sized with a minimum of 25% spare capacity for future load. Step down transformers shall have copper windings. Transformers rated up to and including 75KVA shall be rated for 115 DEG C rise. Transformers rated at 112.5KVA and larger shall be rated for 80 DEG C rise. D PANELBOARDS The main distribution panelboard, shall be circuit breaker type with single main disconnect switch and distribution feeder breakers. The main breaker is anticipated to be rated. Main distribution panelboard and branch circuit panels will be installed to serve the electrical loads. As a minimum, panelboards shall be 30 poles and 100A, and have a minimum of 20% space and 20% spare breakers for future use. (Regardless of their loading, size feeders to equal the panel s amperage rating.) Panelboards shall be balanced to the maximum extent possible, so no phase shall be less than 80 percent or more than 120 percent of the average load. Panelboards not within sight of the feeder over current protection shall have a main circuit breaker; molded case breaker will suffice. Recessed panelboards shall have front door with lock. Surface mount panelboards shall PART 3 - CHAPTER 6 / ESR D50 - Page 2

3 have door-in-door (hinged) trim for easier maintenance access; front door with lock. Wall(s) for recessed panels shall be 6 stud and coordinated with the Architect. Panelboards supplying power to non-linear loads (Electronic equipment affected by electrical noise, Computers, Printers, Fax Machines, Copiers, etc.) shall have an isolated ground bus. The isolated ground bus shall be insulated from the panel and raceway grounding and be connected directly to the transformer service ground. The panelboard serving the computer and IT equipment loads shall have 200 % rated neutral busses. Panelboards shall have copper bussing, copper ground and neutral bars. The use of double-tub panelboards shall be allowed. Panelboards shall have bolt-on type circuit breakers throughout the facility to serve electrical loads. Voltage surge protection shall be provided at the incoming main service panelboard. D ENCLOSED CIRCUIT BREAKERS Upgrade or repair defeative enclosed circuit breakers and provide new circuit breakers and wiring as needed. D MOTOR CONTROL CENTERS Provide motor control center(s), combination motor starters (fusible shall be provided for short-circuit protection short circuit values greater than 10,000 amps), individual motor starters with disconnect switches, reduced voltage starters, manual motor starters and variable speed drives for motor controls by mechanical equipment in accordance to NEC. Provide all circuits and connections for motors and other mechanical equipment. 120-volt motors will be specified to have integral thermal overload protection when available. If integral thermal overload protection is not available, provide manual thermal overload starters. Provide combination motor starter-disconnect controllers for poly-phase motors. Provide reduced voltage starters for motors over 25 HP. Coordinate type with motor design and starting torque requirements. Provide horsepower-rated manual starters for 120-volt motors with integral thermal overload protection. The manual starter may serve as the disconnect means for 120-volt motors without integral thermal overload protection when properly located to meet the within sight as stated in the NEC and properly labeled. Combination motor starter-disconnect controllers may serve as the disconnect means for poly-phase motors when properly located. Provide additional fused or non-fused disconnect switches (depending upon its AIC rating) within sight of the motor when the starter disconnect cannot be placed within sight of the motor. D OTHER SERVICE AND DISTRIBUTION Provide an external transient voltage surge suppressors (TVSS) at the service entrance. Provide 120V, 20A TVSS duplex receptacles for telecommunications equipment. For all tele-communication rooms, provide quantity of receptacles and circuits per UFCs. NOTE: If the telecommunications rack or cabinet requires a 30A receptacle, provide a twist-lock. Within the rack/cabinet, provide the TVSS duplex receptacles. In B8200, Supply Room Provide heavy duty electrical receptacle for electric forklift. This receptacle shall be power from a new panelboard, located on the East of the adjacent room. Panelboard shall PART 3 - CHAPTER 6 / ESR D50 - Page 3

4 be powered from the building s main switchboard; provide feeder breaker and feeder circuit. Panelboard shall be 225A and 42 poles. Provide light fixture and switch under the mezzanine. D5020 LIGHTING AND BRANCH WIRING Provide lighting and general-purpose receptacles throughout all spaces within and outside the buildings. All general purpose receptacles shall be 20 amps. NEMA WD 1. Receptacles for general purpose shall be circuited such that no more than six duplex (or three quad duplex) receptacles are placed on the one 20 amp, single-pole breaker. Receptacles dedicated for computer loads shall be circuited such that no more than three quad-duplex receptacles are placed on one (1) 20 amp, single pole breaker (three computers per circuit). Quad-duplex receptacles in communications rooms shall be circuited such that one quad-duplex receptacle is placed on one 20 amp, single pole breaker. Provide dedicated receptacles for all ancillary office equipment such as faxes, printers, plotters, shredders, or copiers. This equipment shall be circuited such that no more than one duplex receptacles is place in one 20 amp, single pole breaker. A dedicated circuit shall also be required for refrigerators, water coolers, microwaves, and vending machines. Each receptacle homerun shall have a dedicated neutral, multi-wire branch circuits (shared neutrals) shall not be used. Provide ground fault circuit interrupting receptacles per National Electrical Code. Provide a minimum of one general-purpose receptacle on each wall of individual offices, conference and break rooms. In offices where walls exceed 12 feet, provide an additional duplex receptacle for each additional 12 feet of wall or fraction thereof. Corridors spacing every 40 feet minimum 2 per wall. General-purpose receptacle spacing shall not exceed 12 feet. Provide receptacles and/or hardwired power connections for any special equipment or furnishings. Provide receptacles for all equipment, devices, etc. NOTE: Due to the extensive HVAC work/renovation within B3200, this contractor shall provide or replace in all effected spaces the ceiling mount occupancy sensor(s) with new dual-technology occupancy sensors with an integral isolation relay. Contractor shall also provide power to new or additional HVAC equipment and if required provide new feeder breakers, conductors in conduit, and panelboards to feed the HVAC equipment. D BRANCH WIRING All branch wiring shall be per UFC At a minimum, provide conductors with type THHN/THWN insulation for conductor sizes #12 AWG through #1/0 AWG, and type XHHW insulation for conductor sizes #2/0 AWG and larger. All conductors shall be copper and shall be routed in EMT conduit, unless otherwise required. All conductor sizes shall be #12 AWG minimum. All branch wiring shall be insulated conductors in conduit. Provide connection to elevator sump pump (no GFI). Provide GFI outlets at elevator pit and hoistway. Provide disconnect switches for elevator power and lights. Provide elevator disconnecting means inside of elevator machine room. D LIGHTING EQUIPMENT Provide a complete lighting system including exit and emergency lighting, LED exit lights, and emergency egress lighting (see D509090). Refer to part D for detailed emergency lighting requirements. Building lighting shall consist of induction, LED and fluorescent lighting including PART 3 - CHAPTER 6 / ESR D50 - Page 4

5 manual, multi-level and step-dimming switches and automatic controls (occupancy sensors, lighting control panels and daylight sensors). All lighting control design, fixture layout, luminaire wattage requirements, lighting power allowance, etc. shall be in compliance with ASHRAE and UFC Lighting design at a minimum shall consist of a combination of recessed parabolic (3 inch luminaires) 12 cell for 2-lamps and 18 cell for 3-lamps, 85% plus efficient fluorescent low-profile fixture with small lens, fluorescent high bays, minimal fluorescent industrials with 0-10% up-light, compact fluorescent and/or LED down lights, suspended direct/indirect fixtures to meet the required foot-candle levels needed for the desired areas. Note: If 18 cell parabolics are employed, provide a second ballast cover. Lighting methods and foot-candle levels shall be in accordance with the Illuminating Engineering Society of North America (IESNA) or applicable UFC. Design to highest recommended foot candle level. Illumination shall meet the requirements of the visual tasks being performed. General illumination requirements shall be determined in a plane of 30 inches above the floor. Fluorescent fixtures shall utilize T8, 4100 Deg K, CRI = 83 or higher, lamps and electronic energy efficient, high frequency ballasts. Design shall employ multi-lamp standard ballasts with total harmonic distortion less than 10 percent. High-bay fixtures shall use high temperature ballasts with power factor of 1.10 or higher. LED light fixtures shall have a color temperature to match. Automatic shut-off systems - lighting control panels, dual-technology occupancy sensors with isolated relay or a combination of both shall be used to help reduce energy costs. Dimming ballasts, bi-level (or step-dimming) switching or multi-level switching, and daylight sensors shall also be considered. At a minimum, occupancy sensors shall be installed in conference rooms, classrooms, offices with one to six person occupancy and restrooms. Contractor shall coordinate all possible light fixture types and layout designs along with any controls design requirements with the user and applicable design guides. Provide lighting at elevator pit, min 20 fc in all pit areas. Provide lighting at elevator machine room, min 30 fc in all areas. D5030 COMMUNICATIONS AND SECURITY The Room Requirements Section identifies locations for communications and security systems and equipment, unless noted otherwise in the following sub-elements. D TELECOMMUNICATIONS SYSTEMS Provide a complete building entrance facility, backbone distribution system, and horizontal distribution system including, but not necessarily limited to, all wiring, pathway systems, grounding, backboards, connector blocks, protectors for all copper service entrance pairs, patch panels, fiber optic distribution panels, terminators for all fiber optic cables, outlet boxes, telephone jacks, data jacks cover plates. Telecommunications design must be performed and stamped by a Registered Communications Distribution Designer (RCDD). Contractor shall be responsible for providing all copper, fiber and infrastructure into the building and coordinating with the utility companies. MARFORRES (MFR) should be able to come into the building and hook their equipment in the DEMARC room. The contractor shall be responsible for PART 3 - CHAPTER 6 / ESR D50 - Page 5

6 coordinating the telephone and NMCI services to the building and into the DEMARC room. NMCI shall be installed per UFC Provide NMCI labels. Also refer to Part 6 Attachments: Cable label NMCI ISP cabling specifications with MFR updates and MFR site requirements summary. Provide Category 6 Unshielded Twisted Pair (UTP) copper cable for horizontal voice and data cables. Use colored cables for voice and data per NMCI Inside Cable Plant Installation Standards. Provide a minimum of one telecommunication outlet/drop on each wall of individual offices (and an additional telecommunication outlet/drop per workstation with multiple workstations), and break rooms. In spaces where walls exceed 12 feet, provide an additional telecommunications outlet/drop for each additional 12 feet of wall or fraction thereof. Refer to Room Requirements for more information. Secret Internet Protocol Router Network (SIPRNET) is a project requirement. Provide a Protected Distribution System (PDS) as required. Provide outlets in accordance with the Room Requirements and UFCs. SIPRNET REQUIREMENTS: 1. Provide 0.75 in. conduit from DEMARC/NMCI room to SIPRNET room. 2. Provide a single copper line and shall run from DEMARC to SIPRNET through 0.75 in. conduit. 3. Provide electrical power for the Rack two 120V, 30Amp. Duplex outlets. 4. NMCI/Phone System a. Provide surface mounted lighting fixtures. b. Provide standard duplex outlets one for each wall. c. Provide Data (NMCI)/Voice (Phone) outlet at desk area. 5. IDS Security System a. Provide dedicated circuit for electrical outlet for IDS system. b. Provide a dedicated analog phone line. c. IDS control panel shall be mounted on wall on the lock at side of door, not the hinge provide power here. IDS Control Panel and Keyboard to be installed by ADT/Tyco. STE Phone need analog phone line located near the desk. D PUBLIC ADDRESS SYSTEMS See D40 for Mass Notification System requirements. D INTERCOMMUNICATIONS SYSTEMS Provide an Intercommunication System as part of the telephone network to allow two-way communications between all office spaces, locker rooms, storage areas, Department Heads, Commanding Officer, Executive Officer, Officers Ready Rooms, Maintenance Control Rooms, Administration Offices and Maintenance Administration Offices. PART 3 - CHAPTER 6 / ESR D50 - Page 6

7 Provide separate intercom system with audible and visual from the front vestibule to the main administration office See Part 3, Chapter 6 / ESR G40. D TELEVISION SYSTEMS Provide a complete CATV system to be owned and maintained by the Government including all interior equipment required to provide high quality TV signals to all outlets with a return path for interactive television and cable modem access. System shall include, but is not necessarily limited to, head end amplifier, amplifiers, splitters, combiners, line taps, cables, outlets, tilt compensators, TV brackets (swivel type) and all other parts, components, and equipment necessary to provide a complete and usable system Conduct CATV testing at each of the following points in the system: At each outlet and at the Head and distribution amplifier inputs and outputs. D SECURITY SYSTEMS Provide modifications to or upgrade the existing ADT security system for the building to accommodate a card reader for Gate Access and card readers at the doors on both the North and South sides. The new Gate access will be located on the South East side of B3200. The system shall also include additional devices throughout the facility as mentioned below. An Electronic Security System (ESS) is the integrated electronic system that encompasses one or more of the following subsystems; access control system (ACS), intrusion detection system (IDS), and closed circuit television (CCTV) systems for assessment of alarm conditions. The ESS for this project shall meet requirements of UFC , Electronic Security Systems and SECNAV M Department of Navy Information Security Program and consist of an ACS and an IDS. A CCTV system is not a project requirement. Provide an ESS consisting of empty raceways with pull strings, outlet and back boxes, cover plates and associated power circuit(s) to enable the system. Full installation is by the ESS supplier. Provide raceways and boxes for an Intrusion Detection System (IDS) to detect intruders or unauthorized personnel in protected areas/zones. Raceways and boxes for: point sensors on all windows, doors, and man-passable openings; volumetric sensors within secure/protected areas to detect movement within the area. Provide raceways and boxes for: balanced magnetic switches, door contacts, electric strikes, card readers and request to exit on all exterior doors. Coordinate with door hardware schedules along with door closers/reclosers. Provide raceways and boxes for: sufficient motion sensors to provide coverage in all spaces, but not limited to, corridors, offices, restrooms, tool rooms, parts rooms, communication rooms, and storage rooms. Provide raceways and boxes (for future wiring) from switches and sensors to the ESS panel. Wireless transmission between sensors and the panel is not authorized. Balance magnetic switches and motion sensors will be wired to a panel located at (TBD by the DOR). PART 3 - CHAPTER 6 / ESR D50 - Page 7

8 Contractor shall ensure adequate power is run to the alarm panel s location. Contractor shall provide an analog phone line to each main panel of the ESS. Provide 8 hours of emergency uninterruptable backup power. Backup power may be provided by batteries, an uninterruptable power supply or combination thereof. In addition to the ACS/IDS for the whole building, provide a dedicated ESS raceway and back boxes for the following spaces: Armory, EKMS Vault, I&I Office and S-2 (SIPRNET). Each system shall utilize the same devices and features as described above. Coordinate with Part 5 Room Requirements and coordinate with Part 3, Chapter 6, E D OTHER COMMUNICATIONS AND ALARM SYSTEMS At the front entrance, provide an ACS (Door Station) with two way communication (intercom) and video camera. Provide the second intercom box in main office. Second location shall have door release function and a 20 inch monitor. Provide all wiring in conduit and junction boxes. NOTE: In any room where meetings (ie. Conference Rooms), lectures (ie. Classrooms), or group settings are held AND these spaces contain, but not limited to, VTC (Video Tele-Conferencing), presentations with over-head projectors and monitors or screens, the contractor shall provide all raceways and junction boxes for all the power wiring and communication cabling from the table(s) to the wall and over to the control source (ie. podium(s)), from each projector to the podium(s), etc. Minimum conduit shall be 1 inch or an infloor system can be used. D5090 OTHER ELECTRICAL SERVICES D GENERAL CONSTRUCTION ITEMS (ELECTRICAL) Provide General Construction Items (Electrical) including, but not necessarily limited to, all connections, fittings, boxes and associated equipment needed by this and other sections of this RFP as required for a complete and usable system. Conduits, cable trays and busways that penetrate fire-rated walls, fire-rated partitions, or fire-rated floors shall be firestopped in accordance with Section C10, Interior Construction. D EMERGENCY LIGHTING AND POWER Provide power and wiring for emergency lights and exit lights throughout the facility to meet NFPA 101 and 70 requirements, particularly NEC Article Provide emergency lighting, but not limited to, in corridors, heads and interior rooms that do not have exposure to natural light, and at all EXIT access and EXIT discharge. Emergency lighting shall be powered by an internal emergency battery ballast (output of 1100 lumens per lamp and parallel operation), a remote battery (inverter), emergency battery units (EBUs) with MR-16, 12-watt (or greater) or LED lamp equivalent, or combination thereof. Arrange EGRESS fixtures to illuminate automatically upon loss of power. Exit signs shall be battery back-up, die-cast aluminum housing and LED type, color red. In corridors, provide night light/security lighting on each floor, minimum of 1 fixture for every feet. D GROUNDING SYSTEMS PART 3 - CHAPTER 6 / ESR D50 - Page 8

9 Provide a complete grounding system for the facility electrical and telecommunications systems. Grounding shall be per National Electrical Code (NEC) and include copper equipment grounding conductors run with branch and feeder circuits. Wire shall be copper conductors minimum size #12 AWG for branch wiring. Communication/Radio Repair Shop work shop work table(s) shall be statically grounded. D LIGHTNING PROTECTION Not applicable. D ELECTRIC HEATING Provide power wiring and connections as required for all electric heating systems and equipment. D ENERGY MANAGEMENT CONTROL SYSTEM Provide power wiring and connections as required for all systems and equipment including Plumbing and HVAC. D BUILDING PHOTOVOLTAIC SYSTEM Not applicable. D OTHER SPECIAL SYSTEMS AND DEVICES Provide power to Fire Pump. B3200 Elevator Upgrade/replace the circuit breakers for the elevator sump pump and replace the existing receptacles, lighting and other wiring. HVAC Provide disconnect switches, power and wiring as needed. Provide power wiring and connections for the following special systems: Mass Notification and Fire Alarm. --End of Section-- PART 3 - CHAPTER 6 / ESR D50 - Page 9

It is acceptable to place all required information in the main element (such as D5010) and delete the sub-elements provided in this template.

It is acceptable to place all required information in the main element (such as D5010) and delete the sub-elements provided in this template. 6. ENGINEERING SYSTEMS REQUIREMENTS D50 ELECTRICAL SYSTEMS REQUIREMENTS ELECTRICAL TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT Level 2 Group Elements.

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods 1. BASIC ELECTRICAL MATERIALS 1. All conduit and raceway must be 3/4" or larger. Exposed raceway in finished areas shall be in 700 or larger wiremold. Exception: runs to individual devices 10 or less,

More information

Construction Management at Risk Services. New North East Branch Library Project. August 3, 2018

Construction Management at Risk Services. New North East Branch Library Project. August 3, 2018 Construction Management at Risk Services New North East Branch Library Project ADDENDUM 01 August 3, 2018 1. The attendance sheets (4 pages) from the Pre-Bid Conference are attached. 2. The proposals may

More information

Division 26 ELECTRICAL TABLE OF CONTENTS

Division 26 ELECTRICAL TABLE OF CONTENTS Division 26 ELECTRICAL TABLE OF CONTENTS 26 1000 GENERAL... 33 A. CODE... 3 B. RELATED SECTIONS... 3 C. ABBREVIATIONS... 3 D. DEFINITIONS... 3 E. DRAWING REQUIREMENTS... 3 F. EQUIPMENT SERVICE ACCESS AND

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,

More information

CHAPTER 8 ELECTRICAL

CHAPTER 8 ELECTRICAL CHAPTER 8 ELECTRICAL 8.1 GENERAL... 3 8.2 REQUEST FOR PROPOSAL DEVELOPMENT... 3 8.3 DESIGN DEVELOPMENT... 3 8.3.1 CONCEPT (30%) DESIGN SUBMITTAL REQUIREMENTS... 3 8.3.1.1 Concept Design Analysis... 3 8.3.1.1.1

More information

Related Sections: TBD. Effective Date: January 1, 2016

Related Sections: TBD. Effective Date: January 1, 2016 Description: The purpose of the section is to highlight the current applicable UMCP Design Standards for the design, selection and, installation of lighting fixtures within buildings. Related Sections:

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2 Lindsay Frederick Lighting + Electrical Ron Dodson Faculty Advisor Native American Cultural Center Arizona Technical Report 2 Native American Cultural Center Technical Report 2 p. 2 Executive Summary The

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

*************************************************************************** SECTION D50 ELECTRICAL 02/18

*************************************************************************** SECTION D50 ELECTRICAL 02/18 NAVFAC PTS-D50 (February 2018) -------------------------------- Preparing Activity: NAVFAC SUPERSEDING PTS D50 (September 2016) PERFORMANCE TECHNICAL SPECIFICATION SECTION D50 ELECTRICAL 02/18 NOTE: This

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth Corbin Building Technical Assignment 2 Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth 10/26/2011 Technical Report II 1 Executive Summary The following report is an overview

More information

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations... Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

CHAPTER 8 ELECTRICAL

CHAPTER 8 ELECTRICAL CHAPTER 8 0 8.1 GENERAL... 3 8.2 REQUEST FOR PROPOSAL DEVELOPMENT... 3 8.3 DESIGN DEVELOPMENT... 3 8.3.1 CONCEPT (30%) DESIGN SUBMITTAL REQUIREMENTS... 3 8.3.1.1 Concept Design Analysis... 3 8.3.1.1.1

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.07 ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.07 It is expected that the electrical design professional will conform to accepted good engineering design practices.

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: SECTION 26 09 23 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices. SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance

More information

Page 1 of General

Page 1 of General Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3

HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3 HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California 95833 September 15, 2016 Woodland Joint Unified School District Spring Lake Area Elementary School HMC No. 3535003.000 DSA Appl.

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1 Page 1 TABLE OF CONTENTS 1 ELECTRICAL 2 Summary Sustainability Electrical Distribution Lighting Detection and Alarm Communication Systems Lightning Protection Clock Systems Access Control Housekeeping

More information

Electrical System (N) PANELBOARD "L1" VOLTAGE: 208/120 A, 3P :MAIN C/B PHASE: 3 A :BUSSING WIRE: 4 :MOUNTING

Electrical System (N) PANELBOARD L1 VOLTAGE: 208/120 A, 3P :MAIN C/B PHASE: 3 A :BUSSING WIRE: 4 :MOUNTING Electrical System After re-designing the lighting system for the children s computer, circulation and storytelling areas, the electrical system had to be redesigned as well. These are the new panel board

More information

13. ELECTRICAL - TECHNICAL

13. ELECTRICAL - TECHNICAL 13. ELECTRICAL - TECHNICAL 13.1 GENERAL REQUIREMENTS 1. Base the electrical design on providing the following features at the most economical cost, considering both investment and operating expenditures:

More information

SECTION LIGHTING CONTROL DEVICES

SECTION LIGHTING CONTROL DEVICES SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Currently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required.

Currently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required. Executive Summary The current electrical system is functional but requires some understanding in order to avoid overloading circuits. Certain outlets can be used for space heaters while others cannot and

More information

Technical II Report Electrical Systems

Technical II Report Electrical Systems Technical II Report Electrical Systems Kelly Chan Consultant: Prof T. Dannerth, P.E. Part A Drawings Drawings needed for single-line diagram EE1.01 title sheet (electrical drawings) EE2.09 penthouse/roof

More information

Building Electrical System Overview

Building Electrical System Overview Philip Mackey L/E Dr. Mistrick Holy Cross Hospital North Addition Silver Spring, MD 0/3/05 Building Electrical System Overview Executive Summary: The following report describes the existing emergency power

More information

Chang Liu Lighting + Electrical M.A.E./B.A.E. Integrated Degree. Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson

Chang Liu Lighting + Electrical M.A.E./B.A.E. Integrated Degree. Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson M.A.E./B.A.E. Integrated Degree Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson Renzo Museum of American Art Executive Summary This report provides an analysis of the electrical

More information

SECTION EXTERIOR LIGHTING

SECTION EXTERIOR LIGHTING SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

Lord Stirling Community School Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004

Lord Stirling Community School Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004 Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004 Table of Content: Page 1 ~ Single Line Diagram 1 2 ~ Electrical System Narrative 2-3 3 ~ Lamp

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:... 2 2. EMERGENCY POWER... 3 B. LIGHTING...4 1. GENERAL... 4 2. AVERAGE MAINTAINED

More information

Electrical Inspection Lighting & Power

Electrical Inspection Lighting & Power 0921 Light Fixtures & Controls Fixtures, controls, conduit, wiring, etc. Interior classroom and corridor lighting consists of T12 fluorescent lamps with magnetic ballasts. In the classrooms the luminaires

More information

SECTION INTERIOR AND EXTERIOR LIGHTING FIXTURES

SECTION INTERIOR AND EXTERIOR LIGHTING FIXTURES SECTION 26 50 00 INTERIOR AND EXTERIOR LIGHTING FIXTURES PART 1: GENERAL 1.1 WORK INCLUDED: A. Interior lighting fixtures and accessories B. Exterior lighting fixtures and accessories C. Emergency battery

More information

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical

More information

SECTION POWER SUPPLIES AND DISTRIBUTION

SECTION POWER SUPPLIES AND DISTRIBUTION SECTION 17460 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for Power Supplies and Power Distribution for Station communications. 1.02 REFERENCE STANDARDS A. American National Standards

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xiii How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Technical Report 2: Electrical Systems Criteria and Existing Conditions

Technical Report 2: Electrical Systems Criteria and Existing Conditions Technical Report 2: Electrical Systems Criteria and Existing Conditions Princeton Theological Seminary Library Princeton, NJ Stephanie Deckard Lighting Electrical Faculty Advisor Dr. Kevin Houser 10/12/2012

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

CT CABINET AND UTILITY METERING WELL AND BOOSTER PUMP CONTROL 12"x12" WIREWAY 200A MCB 200A, 120/208V, 3Ø, 4W BOARD TVSS CIA ALARM 400A, DOUBLE-THROW SWITCH PORTABLE GENERATOR CONNECTION ENCLOSURE EXISTING

More information

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

DIVISION 13 - SPECIAL CONSTRUCTION

DIVISION 13 - SPECIAL CONSTRUCTION DIVISION 13 - SPECIAL CONSTRUCTION I. GENERAL A. This division contains the following elements: 1. Relocatable Buildings. 2. Telephone and Data Systems. 3. Intercom and Clock/Bell System. 4. Wiring and

More information

SECTION INTERIOR LIGHTING

SECTION INTERIOR LIGHTING SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION (16140) - WIRING DEVICES

SECTION (16140) - WIRING DEVICES SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -

More information

WINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016

WINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016 SECTION 26 2030 - LIGHTING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Special Conditions and Division 1 Specification Sections,

More information

Technical Report Two

Technical Report Two Technical Report Two Yale Sculpture Building Advisors: Ted Dannerth Richard Mistrick Date: October 31, 2006 Electrical Systems Existing Conditions and Building Load Summary Report Executive Summary: This

More information

SECTION INTERIOR LIGHTING

SECTION INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:...2 2. EMERGENCY POWER...3 B. LIGHTING...4 1. GENERAL...4 2. AVERAGE MAINTAINED

More information

Electrical Inspection Service & Distribution

Electrical Inspection Service & Distribution 0911 Distribution Panels & Switchgear Equipment, conduit, feeders, and grounding 480 Volt Switchboard: This switchboard contains the utility meter and two main, service, circuit breakers. One circuit breaker

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION 265100 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior lighting fixtures, lamps, and ballasts. 2. Emergency lighting units. 3. Exit signs. 4.

More information

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

PART 4 ELECTRICAL STANDARDS

PART 4 ELECTRICAL STANDARDS PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve

More information

ELECTRICAL DESIGN GUIDELINES SECTION GUIDELINE SPECIFICATIONS-DUVAL COUNTY PUBLIC SCHOOL

ELECTRICAL DESIGN GUIDELINES SECTION GUIDELINE SPECIFICATIONS-DUVAL COUNTY PUBLIC SCHOOL The design guidelines, which follow, are intended to supplement the Educational Specifications and State Requirements for Educational Facilities (SREF). All electrical service (temporary, new, disconnection

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

Attendees/Absentees. Derek Gallagher DG. Delano Secondary School Additions and Renovations June 6, 2016 Technology User Group Meeting Minutes

Attendees/Absentees. Derek Gallagher DG. Delano Secondary School Additions and Renovations June 6, 2016 Technology User Group Meeting Minutes MEMORANDUM To: From: Attendees/Absentees Derek Gallagher DG Date: June 14, 2016 Comm. No: 152235 Subject: Independent School District #879 Delano Secondary School Additions and Renovations June 6, 2016

More information

National Electrical Code

National Electrical Code National Electrical Code 409.30 Disconnecting Means Disconnecting means that supply motor loads shall comply with Part IX of Article 30. 410.81 Control (A) Disconnection Luminaires (fixtures) or lamp installation

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

IN2 Lighting Control Devices

IN2 Lighting Control Devices Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section Wiring Devices for wall-box dimmers and manual light switches. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND

More information

RFP Addendum 2 March 31, 2016

RFP Addendum 2 March 31, 2016 RFP Addendum 2 March 31, 2016 For Best Value Procurement Option Three Security Upgrades Ph 1 UT Health Science Center SBC No. 540/013-04-2015 This Addendum forms a part of the Request for Proposals (RFP)

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets

More information

DOOR MONITORING/DURESS SYSTEM

DOOR MONITORING/DURESS SYSTEM SECTION PART 1 - GENERAL 1.1 RELATED SECTIONS A. Comply with the requirements of Section 27 05 00 Common Work Results for Communications. 1.2 DEFINITIONS A. Not used. 1.3 DESCRIPTION OF SYSTEM: A. Provide

More information

Spring Test 6 due 04/26/2013

Spring Test 6 due 04/26/2013 Spring Test 6 due 04/26/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. The article that covers TV wiring installations in residences

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

The following narrative outlines a conceptual electrical Scope of Work for converting the Phase 2 TRW Building to an Exhibition Hall.

The following narrative outlines a conceptual electrical Scope of Work for converting the Phase 2 TRW Building to an Exhibition Hall. The following narrative outlines a conceptual electrical Scope of Work for converting the Phase 2 TRW Building to an Exhibition Hall. Demolition: The area of work shall be a complete gut ; removing all

More information

STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES

STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES Articulation Agreement Identifier: ELT 118 (2005-1) Identifier is the postsecondary course prefix followed by Plan-of-Instruction

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

Charleston excellence is our standard County SCHOOL DISTRICT

Charleston excellence is our standard County SCHOOL DISTRICT Charleston excellence is our standard County SCHOOL DISTRICT FACILITY SECURITY ACCESS CONTROL, INTRUSION DETECTION, AND SURVEILLANCE DESIGN SPECIFICATIONS FOR NEW CONSTRUCTION, ADDITIONS, AND MAJOR RENOVATIONS

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and

DEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and DEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and equipment), and discussions with maintenance personnel

More information

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School MOUNT PLEASANT MIDDLE SCHOOL HVAC M-01 Heating Plant: The existing boilers have recently been upgraded. (3) steam boilers (8660 mbh each) manufactured by Weil- McLain have been installed. Newer hot water

More information

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations ELECTRICAL STANDARDS DESIGN CHECKLIST

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations ELECTRICAL STANDARDS DESIGN CHECKLIST ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations ELECTRICAL STANDARDS DESIGN CHECKLIST February 01, 2006 2 Project Name: Architect: Electrical Engineer: Completed By:

More information

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Nameplates and labels B. Wire and cable markers C. Conduit markers 1.2 REFERENCES A. NFPA 70 - National Electrical

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes

More information

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect 1 Site Summary Address 7200 Bluff Springs Road Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 2014 Total Campus Building Area (combined) 25,314 SF Introduction The

More information

DIVISION 16 ELECTRICAL

DIVISION 16 ELECTRICAL DIVISION 16 ELECTRICAL This division contains the following elements: 1.1 General Electrical Requirements. 1.2 Electrical Distribution System. 1.3 Power Distribution System. 1.4 Lighting System. 1.5 Emergency

More information