ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan.
|
|
- Cecil Baldwin
- 6 years ago
- Views:
Transcription
1 ADDENDUM NO. 1 for MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140 Marquette, Michigan December 12, 2016 TO: ALL BIDDERS OF RECORD This addendum forms a part of the contract documents and modifies the original specification and bid proposal as noted below. Acknowledge receipt of this addendum by attaching a copy to the Bid Proposal Form. Failure to do so may subject bidder to disqualification. This addendum consists of seven (7) pages plus sheet E1. A. General Items: a. The Addendum replaces all prior communication. b. The Owner has original blue-line drawings dated January 24, 1968 which include architectural, structural, plumbing, mechanical, electrical, fire protection and fire alarm which are available for the contractor s review. The drawings are also available in pdf format. c. See the attached sign-in sheet from the December 5, 2016 pre-bid meeting. d. The bid due date remains Tuesday, December 20 th at 10am. If bids are to be delivered via FedEx or UPS ensure the receipt indicates delivery by Tuesday, December 20 th at 10am in case of any delivery delays. e. The contract length will be revised to allow for six months of construction. The six months will begin after all shop drawing submittals and plan reviews have been completed.
2 Page 2 of 6 f. Refer to Section Wage Rates. The General Decision Number MI dated 09/09/2016 which is included within the Project Manual does NOT include a rate for Electrician for Building Construction Type. All bidders to use as a minimum the rate included for Residential Construction Type, summarized below. ELEC /01/2014 ALGER, LUCE, MACKINAC & MARQUETTE COUNTIES Rates Fringes ELECTRICIAN $ g. Refer to Section Form of Bid to be Used. Add the following as item 10: 10. Base Bid Breakdown Base Bid Breakdown a. Material: $ b. Labor: $ c. Base Bid Total (a+b): $ h. The contractor will be allowed to use the building s restroom facilities. The contractor will also be given access to an area within the building where they can break or eat. i. Work hours are Monday Saturday, 8am to 6pm. The contractor is not required to work Saturdays. j. No smoking is allowed within the building. Any smoking must be 25 feet from the building. Chewing tobacco is allowed but related refuse must be properly disposed of. k. Refer to the Asbestos Survey dated September 10, 2009 by Lakeshore Environmental at the following link from the Marquette Housing Commission web site: l. All on-site contractors, subcontractors or suppliers are required to wear identification, examples of which include badges or clothing emblazoned with the company logo. This identification is in addition to the written verification regarding Criminal Background check and exclusion on any registered Sex Offender listed in paragraph 8.D of Section Architect s Supplemental Instructions to Bidders page 2. m. The contractor will be required to submit regular schedules to the Owner. 48 hour written tenant notification is required for all work within apartment units. The Owner will give the written notice to the tenants based upon the contractor s schedule. n. Refer to specifications A.2.b and B. NICET Level IV for is required for design. NICET Level IV is required for final programming, commissioning, testing, and training of the final system.
3 Page 3 of 6 B. Drawings: a. See revised sheet E1 Lower Level. i. There are two occurrences of the telephone symbol T outside of the building footprint; north of the Maintenance Garage and north of Stair 2. Disregard the two symbols. ii. The new Fire Alarm Control Panel to be located adjacent to the existing panel scheduled to be removed in the Electrical Room as shown but not noted. C. Response to Questions: Q1: Note on sheet E1 states Design shall include capacity for ½ the units on each floor to be converted to hearing impaired unit. Is this a requirement? A1: Yes, final design to have the capacity for 50% of the apartment units on each floor to be converted to hearing impaired units in the future. Q2: Specification section 2.14 requires a Listed printer. Is a network card, specifically the SafeLINC by Simplex, acceptable? A2: Yes, a network card which provides electronic documentation meeting code is acceptable. Q3: Is the elevator shaft sprinkled? A3: Contractor to verify but original drawings do not indicate suppression in the shafts. Q4a: Specification section 2.4 Manual Fire Alarm Boxes lists requirement of Indoor Protective Shield. Is this required for all pull stations? It will add depth. A4: No, Indoor Protective Shields are not required. Q4b: A4b: Specification section 2.4 states to supply manufacturer s surface back box at surface mounted stations. Is there a known quantity? Existing building is block wall construction at corridors. It can be assumed that all devices will be surface mounted except for areas where there is a drop ceiling, limited to minimal areas at the first and ground level floors. Q5: Specification says no more than 50 addressable devices per SLC. Is it ok to isolate per floor rather than per device count? This would save on field or panel mounted isolators and installation. A5: Isolation per floor is required. More than 50 is acceptable.
4 Page 4 of 6 Q6: Page 10 from 2.7 Notification Appliances states: A. General Requirements for Notification Appliances: Individually addressed, connected to a signaling line circuit, equipped for mounting as indicated and with screw terminals for system connections. Does Individually Addressed require truly addressable notification? A6: Yes, the design intent is for addressable notification, detection and monitoring. Voluntary alternate may be provided outside of base bid. Q7: Section 2.3 Fire Alarm Control Unit part K states: K. Voice/Alarm Signaling Service: Central emergency communication system with redundant microphones, preamplifiers, amplifiers, and tone generators provided in a separate cabinet located in the fire command center. A7: The main Fire Alarm Control Panel is intended to be in the basement, adjacent to (replacing) the existing fire alarm panel, see revised sheet E1. A spare of each on site is acceptable if it meets minimum code requirements. If the Fire Command Center does not increase in size, it is acceptable to have the main Fire Alarm Control Panel in the Fire Command Center. Q8: Please confirm the date of the first complete annual inspection required with the bid. Please advise whether paper or electronic reports of the results are required. A8: Provide a complete inspection including testing of all addressable devices per NFPA 72 one year after the date of substantial completion. Provide Owner electronic i.e. pdf results of the testing. Q9: Please detail the FCC, Fire Command Center. A9: The command center is required for high rise buildings and is required to have monitoring and overrides for the following: Elevator, fire pump, transfer switches, generator, smoke evacuation, (if installed), to allow for managed control of the building from the single location. This includes the voice communication along with all of the building s associated documentation to allow the fire department full knowledge of possible threats during a fire or active event at the site. Q10: The bid form has the alternate wireless system as a deductive alternate. Is that correct? A10: Yes, the wireless system is a deductive alternate. Refer to section Alternates. Base bid is a wired telephone system which includes all of the stairwell and elevator lobby hardwired phones. The alternate provides a wireless system in lieu of the wired system and to include the communication system booster to allow for appropriate signal strength for the fire department in the building. Q11: What is Smoke EVAC sequence of operation? A11: Contractor to verify existing system and provide monitoring of status, manual override, and automatic operation per NFPA72. Coordinated documentation to be provided with delegated design submittal.
5 Page 5 of 6 Q12: What is Voice EVAC sequence of operation? A12: Contractor shall provide sequence of operation matrix per NFPA 72. Shall include individual messages per floor with evacuation of the floor above and below dependent upon coordination with fire marshal requirements. Coordinated documentation to be provided with delegated design submittal. Q13: Are there stairwell pressurization fans? A13: Contractor to verify but Owner states there are no stairwell pressurization fans. Q14: Are there existing duct detectors and dampers in the chase? A14: Field verify and confirm, per plans. Plan on worst case scenario. Q15: What is the voltage and current draw on the existing dampers if they do existing? A15: Contractor to field verify. Q16: Is the evacuation going to be general evacuation of the whole building or is the system partial evacuation with defend in place? A16: Design intent is for partial evacuation. Q17: If partial evacuation is being used is the EOR requiring Circuit Integrity cable between floors and the panel? A17: Yes Q18: Are protective guard required at each manual station as noted in A.3? A18: No. Q19: Spec section call for 4 wire smoke detectors. Addressable detectors are not 4 wire detectors. Please clarify. A19: All devices shall be addressable. Provide base plate style units per specifications. Q20: Are all detectors to have integral heat detectors as indicated in spec section b? A20: Unable to verify specification section. Smoke detectors shall have sensitivity adjustment but not smoke and heat detection. Q21: Spec section 2831a1-2.5.C.3 requires weather proof duct detectors. Is this a requirement for the detectors inside of the building? A21: This requirement is for duct detectors requiring weatherproof enclosures. Standard enclosure is acceptable for installation inside in a dry location. Q22: Spec section 2831a1-2.7.A call for addressable notification appliances. This requirement will drive up the cost of the project significantly. A22: All devices shall be addressable. Contractor may provide voluntary alternate for review.
6 Page 6 of 6 Q23: Where is the location of the new fire alarm control panel? There is a key note on E1 but I cannot find it on the actual drawing. A23: New main panel to be located adjacent to existing panel in basement. Q24: Spec section C.c call for 1 SLC circuit per floor. Is this intent? A24: (1) Minimum per floor, per specifications. Q25: Spec section C.d limits the number of addressable devices to 50 most system have 250 or more addresses available on a SLC circuit. Is this truly intent or are isolation module an acceptable alternative? A25: See response A5. Isolation per floor is minimum requirement. More than 50 per floor is acceptable. Q26: If a printer is required I do not see a location for the printer indicated on the drawings. A26: Printer location would be in Fire Command Center. See response to Question 2 for alternative to printer. Q27: Spec section M.2 call for the system to be designed assuming all candela ratings are a minimum of 110cd. Is that the intent on this project? This adds extra expense. A27: Yes, this is the intent. Q28: The drawing indicated that symbol [10] is a combination smoke detector and A/V. These will be separate devices. Are the devices in the bedroom the only location for the 177cd strobes? A28: Separate is acceptable. See plans for locations. Q29: Does this project have a Seismic requirement as stated in spec section B.1 A29: All areas are seismic. The system shall be installed per the seismic rating of the area. END OF ADDENDUM
7 PRE-BID SIGN-IN: Project Name: Marquette Housing Commission Fire Alarm Replacement Date: December 5, 2016 Time: 1:00 p.m. Attendee s Name Company Name Phone No. Address Kathleen Waters M. C. Smith Associates kwaters@mcsagroup.com Sharon Maki Marquette Housing Commission x11 smaki@mqthc.org Scott Nielson SimplexGrinnell snielson@simplexgrinnell.com Dallas Barrow Master Electric dallas@masterelectricinc.net Denny Fleming First Contracting, Inc bill@firstcontracting.net Jason Niemi J & N Electric jasonniemi@ymail.com Jack Leadbetter Leadbetter Electric jleadbetter.leco@gmail.com Tom Parent VanErt Electric tparent@vanert.com Mike Parent VanErt Electric mparent@vanert.com Page - 1 -
8 ELECTRICAL KEYNOTES: 1. FIRE PUMP CONTROLLER, FTA1000-AA40H-AM-BY-P-R, TO REMAIN. INTEGRATE INTO ALARM SYSTEM. ELECTRICAL GENERAL SCOPE OF WORK NOTES: PROVIDE NEW SURFACE MOUNTED RACEWAY THROUGHOUT ALL PUBLIC SPACES. CONCEAL IN CONDUIT ABOVE LOCATIONS WITH A DROP CEILING. NEW SURFACE MOUNTED RACEWAY SHALL BE WHITE. RACEWAY SHALL HAVE CLIPS TO RETAIN CONDUCTORS, 3' ON CENTER, AND SHALL BE MOUNTED PER UL LISTING. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. REUSE OF CONDUIT IN NON-PUBLIC SPACES IS ACCEPTABLE. CONDUIT IN BACK OF HOUSE EXPOSED LOCATIONS SHALL BE PAINTED TO MATCH. REUSE OF EXISTING FLOOR TO FLOOR PENETRATIONS/ WIREWAYS IS ACCEPTABLE. CONTRACTOR TO REMOVE ALL EXISTING FIRE ALARM CONDUCTORS, COMPONENTS, RACEWAY, AND CONDUITS THAT ARE NOT NOTED AS ACCEPTABLE TO REMAIN. EXISTING SYSTEM TO REMAIN ACTIVE DURING INSTALLATION OF NEW SYSTEM. CONTRACTOR TO PROVIDE ALL FIRE WATCH REQUIREMENTS IN BASE SCOPE OF WORK. CONTRACTOR TO PATCH, REPAIR, AND PAINT ALL AREAS WHERE EXISTING CONDUIT AND WIREWAY IS TO BE REMOVED. PAINT TO MATCH EXISTING CEILING/ WALL. PATCH TO BE CLEAN OF BURRS, SMOOTH, AND MINIMALLY VISIBLE. CONTRACTOR TO FIRE CAULK ALL WALL AND FLOOR PENETRATIONS ASSOCIATED WITH DEMOLITION OF EXISTING AND INSTALLATION OF NEW FIRE ALARM SYSTEM. FINISH SMOOTH AND PAINT TO MATCH WALL/CEILING IN ALL EXPOSED LOCATIONS. CONTRACTOR TO REPLACE ANY DAMAGED CEILING TILE OR GRID DAMAGED DUE TO WORK BEING PERFORMED. CONTRACTOR TO PROVIDE NEW TUBES AND HOUSINGS FOR DUCT DETECTION AND REMOVE EXISTING. PATCH AND REPAIR EXISTING DUCT. FIELD VERIFY AND PROVIDE ALL REQUIRED FLOW SWITCH, TAMPER SWITCH, FIRE DAMPER, AND SMOKE DAMPER MONITORING BASED ON EXISTING DEVICES. PROVIDE NEW DETECTION FOR ALL SMOKE DAMPERS. TO BE PROVIDED IN BASE SCOPE OF WORK. SCOPE TO INCLUDE UPGRADES TO EXISTING ELEVATORS TO MEET CURRENT CODE REQUIREMENTS FOR ELEVATOR LOBBY SMOKE DETECTION AND ELEVATOR SMOKE/ HEAT DETECTION. -ELECTRICAL CONTRACTOR SHALL INCLUDE ELEVATOR CONTRACTOR FEE IN THEIR SCOPE OF WORK. -CONTACT - OTIS ELEVATOR - STEVE KAPE SCOPE TO INCLUDE NEW COMMUNICATION SYSTEM INSIDE OF ELEVATOR CAR. ALL WALL MOUNTED DEVICES SHALL BE RED WITH WHITE LETTERING. CEILING DEVICES SHALL BE WHITE WITH RED LETTERING. UNITS 101, 207, 310, 508, AND 810 SHALL BE PROVIDED FOR PROVISIONS FOR HEARING IMPAIRED. DESIGN SHALL INCLUDE CAPACITY FOR 1/2 THE UNITS ON EACH FLOOR TO BE CONVERTED TO HEARING IMPAIRED UNIT. ALTERNATE: SEE SPECIFICATIONS FOR ALTERNATE WIRELESS SYSTEM. 2. EXISTING FIRE ALARM CONTROL PANEL TO BE DEMOLISHED. 3. NEW MAIN FIRE ALARM CONTROL PANEL. 4. EXISTING EMERGENCY TRANSFER SWITCH AND PANELS, TO REMAIN. P:\2016\ Pine Ridge Marquette MI - Fire Alarm\Working Drawings\ E1.dwg, 12/9/2016 2:35:02 PM, mdelora, Classic Engineering
Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.
Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationRE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan
ADDENDUM NO. 2 RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan TO: All Bidders Gentlemen: You are hereby directed to make the following changes in the Project Manual and/or
More informationPROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS
SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationBrighton Area Fire Authority
615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following
More informationLake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 283111 A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationFIRE AND SAFETY PROJECT REVIEW REPORT
1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationHinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.
More informationDIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM
DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationLEA COUNTY NEW MEXICO Page 1 of 8 JUDICIAL COMPLEX RFP NO.: 03-(16-17)
LEA COUNTY NEW MEXICO Page 1 of 8 JUDICIAL COMPLEX RFP NO.: 03-(16-17) ADDENDUM #3 This addendum forms part of the Contract Documents and modifies the original Contract Documents. All other parts of the
More informationFire Alarm, Water Flow Alarm & Signaling Systems
Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving
More informationThe following information shall become and form part of the contract documents.
October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More information2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This
More informationCITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1
CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device
More informationSECTION FIRE ALARM SYSTEMS
SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work
More informationSECTION : FIRE ALARM & DETECTION SYSTEMS
SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction
More informationAddendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017
Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor
More informationCOUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III
SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationDONALD H. BERG, ARCHITECT
DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationOSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM
OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,
More informationM001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings
1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationSECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS
SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 28 work shall, in addition to all division 1 specification sections, comply with all of
More information1.3 REFERENCE STANDARDS
SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises
More informationValuation: # of Plans Submitted: # of pages: Type of Work (select one): New Addition Existing System/Modification Project Name: Scope of Work:
PERMIT FEE: $ 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the following information. Please PRINT).
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationSECTION WET-PIPE SPRINKLER SYSTEMS
SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition
More informationBULLETIN. Temperature Controls (VAV) (3/11/2010)
BULLETIN Temperature Controls (VAV) (3/11/2010) This bulletin is to advise you of the fees and responsibilities associated with Tenant s temperature controls. Tenant Responsibility: 1. Unit power is by
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationMANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO
MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationChanges to this Division since the last issuance are indicated with yellow highlighted text.
Table of Contents 28 10 00 ELECTRONIC ACCESS CONTROL AND INTRUSION DETECTION... 2 A. GENERAL... 2 B. DESIGN REQUIREMENTS... 2 C. CONSTRUCTION REQUIREMENTS... 3 28 20 00 ELECTRONIC SURVEILLANCE... 4 A.
More informationArchitect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition
PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.
More informationPROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE
PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated
More informationSECTION FIRE DETECTION AND ALARM
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 46 00 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the VA ENGINEERING GUIDE FOR FIRE PROTECTION DESIGN which provides fire alarm system criteria that
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationAdditions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401
Henry L. Chauvin, Architect, LLC 9429 Highway 941 Gonzales, Louisiana 70737 (225) 612-0707 Fax: (224) 612-4565 Email: henry.chauvin@outlook.com Additions & Alterations to Ascension Parish Library Galvez
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationSTANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018
STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition
More informationCOMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.
4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationTenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1
12/4/2017 Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant
More informationIN2 Digital, Addressable Fire-alarm System
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Digital, Addressable Fire-alarm System Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More informationSECTION ADDRESSABLE FIRE ALARM SYSTEM
SECTION 16723 ADDRESSABLE FIRE ALARM SYSTEM 1 PART 1 GENERAL 1.1 DESCRIPTION A. This section outlines the requirements for the installation, programming and configuration of Addressable Fire Alarm System
More informationCITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST
CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:
More informationBULLETIN. Temperature Controls (10/2013)
BULLETIN Temperature Controls (10/2013) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. This applies to Phase I & II only. Tenant Responsibility:
More informationFire Permit Application
Fire Permit Application FOR STAFF USE ONLY Case Permit Number: Plan Number: Related permits: Project #: Responsibility for information Although designated Department staff members will help you with general
More informationSECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101
More informationSECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM
SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat
More informationCity of La Puente REQUEST FOR PROPOSAL ADDENDUM NO. 1
City of La Puente REQUEST FOR PROPOSAL ADDENDUM NO. 1 BID TITLE: Facility Access Control and Security System REQUESTING DEPARTMENT: Development Services RELEASE DATE: July 12, 2016 DUE DATE: August 4,
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More informationDivision 28 - Electronic Safety and Security
Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm
More informationPrinceton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors
Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors 1. SUMMARY AND BACKGROUND: Princeton Joint Unified School District located in Princeton
More informationUniversity Design Standard Fire Alarm Systems
1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationSECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM
SECTION 2 8 31 00 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Request For Proposal apply to this Section.
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationFollowing are the systems proposed as per NBC & Local Fire Authority:
1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building
More informationWHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS
WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge
More informationBULLETIN. Temperature Controls (Chilled Water) Phase III only (3/11/2010)
BULLETIN Temperature Controls (Chilled Water) Phase III only (3/11/2010) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant Responsibility:
More informationDIGITAL, ADDRESSABLE FIRE ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationD. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe
More informationProject No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10
Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction
More informationElectronic Safety and Security
28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions
More informationSTUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017
STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationEnvironmental Health & Safety
Environmental Health & Safety Oklahoma State University ADDRESSABLE FIRE ALARM SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu
More informationMinimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016
1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.
More informationOKLAHOMA STATE UNIVERSITY
ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL
More informationTrueAlert Notification Appliances
TrueAlert Notification Appliances UL Listed; FM, CSFM and MEA (NYC) Approved* Non-Addressable Audible/Visible Notification Appliances with SmartSync Operation of Strobes and Horns Features Wall mount audible/visible
More informationSECTION INSPECTION AND TESTING OF WORK
SECTION 01455 PART I - GENERAL 1.01 SECTION INCLUDES A. Project Inspections and Procedures B. Scheduling Inspectors Notification requirements 1.02 RELATED SECTIONS A. Section 01310 COORDINATION B. Section
More informationDESIGN GUIDELINE SBA 5.11
GeneralScope DESIGN GUIDELINE SBA 5.11 FIRE COMMAND CENTER This design guideline clarifies how certain Michigan Building Code (MBC) requirements for Fire Command Centers are to be applied on University
More informationPurpose : Project Manager. Professional. Contractor: devices/system. compatibility
I. Title: Fire Alarm Systems Design, Construction and Commissioning II. Purpose : Define activities, identify stakeholders, and assign responsibilities as it relates to the installation of fire alarm devices
More informationSECTION FIRE DETECTION AND ALARM
SECTION 28 31 00 FIRE DETECTION AND ALARM SPEC WRITER NOTES: This specification addresses fire alarm systems installations of the following configurations/conditions: 1. A fully addressable fire alarm
More informationHARRIS COUNTY HOUSING AUTHORITY
HARRIS COUNTY HOUSING AUTHORITY 8933 Interchange Houston, Texas 77054 713.669-4514 P AMENDMENT OF SOLICITATION ADDENDUM # 3 DATE: 06-03-16 ISSUED BY: Harris County Housing Authority AMENDMENT TO SOLICITATION
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationSolicitation No.: The enclosed addendum amends the bid documents for the above referenced Project.
Date: September 14, 2018 Project: AlDEA/AEA Noise Control Tenant Improvement Solicitation No.: 19003 Addendum No. One TO ALL PLANHOLDERS: The enclosed addendum amends the bid documents for the above referenced
More informationADDENDUM NO. 1. PREPARED BY: Justin Scott DATE PREPARED: 05/25/2018. PROJECT: Centerville-Washington Park District Park Operations Facility
ADDENDUM NO. 1 PREPARED BY: Justin Scott DATE PREPARED: 05/25/2018 PROJECT: Centerville-Washington Park District Park Operations Facility PROJECT NO.: 2017-051 OWNERS REPS: Ken Carter Nick Meyer COPIES
More information1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.
PART 1 - GENERAL SECTION 28 31 11 STANDARD 1.1 FIRE ALARM SYSTEM REQUIREMENTS A. Contractor Requirements 1. The fire detection and alarm system (including the conduit) shall be a separate bid item and
More informationSurviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018
Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET
More informationSECTION FIRE DETECTION AND ALARM
PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation
More informationTrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description
TrueCom Building Communications Systems 5115-Series 5115-9001, -9002 Area of Rescue Communications System Description The Simplex 5115-9001 and -9002 Area of Rescue Communications System provides buildings
More informationWEST VIRGINIA UNIVERSITY
WEST VIRGINIA UNIVERSITY Environmental Health and Safety (SOP) WV State Fire Marshal (SFM) Project Plans Review Process & Procedures West Virginia University Environmental Health & Safety Page 1 of 10
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe
More informationSECTION (13900) - FIRE SUPPRESSION SYSTEMS
PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety
More informationPhotovoltaic (Solar) Array Installation Guide
Building & Safety Division Community Development Department 7351 Rosanna Street, Gilroy, CA 95020 Phone: 408 846-0451 Fax: 408 846-0429 Visit us: www.cityofgilroy.org Photovoltaic (Solar) Array Installation
More informationMar H: SUPPLEMENTAL FIRE DETECTION AND ALARM (16720-H)
2101 Commonwealth Blvd, Suite B Ann Arbor, MI 48105-5759 www.med.umich.edu/facilities/plan/ 283100-H: SUPPLEMENTAL FIRE DETECTION AND ALARM (16720-H) Related Sections Basis Guideline: 283100 - Fire Detection
More informationSECTION 907 FIRE ALARM AND DETECTION SYSTEMS
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing
More informationPART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:
PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,
More informationCommercial Application/Plan Review Submittal Checklist
Commercial Application/Plan Review Submittal Checklist The following checklist has been compiled to assist in expediting the commercial plan review and permit issuance process. Please take a moment to
More information