Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Size: px
Start display at page:

Download "Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings"

Transcription

1 Fire Science and Technorogy Vol.24 No.4(2005) Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research Institute Obayashi Corporation, Japan 2 Disaster Prevention Research Institute, Kyoto University, Japan ABSTRACT This paper proposes simple equations for predicting the smoke filling time in the room of fire origin, which may be practically used to evaluate the performance of evacuation safety design of building. The simple equations were developed for the typical types of design fires, i.e. constant, t-square and their combination. Also these equations can be used for rooms having irregular ceilings, whose horizontal section areas change with height. Their prediction capabilities were verified by comparison with the predictions by BRI2002, a two-layer zone model often used as a tool for evacuation safety design. These simple equations are found to have prediction capability almost equivalent to BRI2002 for smoke filling in the room of origin. Keywords: Smoke Filling Time, Simple Equations, t 2 fire, Irregular Ceiling, Evacuation Safety design 1. INTRODUCTION In the context of performance-based fire safety designs of buildings, it is a common practice that the performance of evacuation safety in fire is evaluated by means of comparing the required safe egress time (RSET) with the available safe egress time (ASET), i. e. the time when fire-induced conditions within an occupied space become untenable [1]. Although heat, toxic gases, visibility etc. in smoke are involved in the untenable conditions, the assessment of the available safe egress time in the room of origin in fire safety design practices is most often based on the smoke filling time to the critical height [2]. If all the occupants have escaped from the room before the interface of the smoke layer descends to their height, it follows that they are not exposed to the smoke so it is not necessary to care complicated conditions of tenability. This is of course a bit conservative but a very convenient safety criterion for practical building designs. The smoke filling time is influenced by the configuration of the fire room and the behavior of the fire growth. It is true that the behaviors of fire growth of real world combustible items, such as chairs, wardrobes, trash baskets and beds, are complicated and differ from one to another. So their burning behaviors are experimentally investigated using furniture calorimeters based on oxygen consumption heat release rate measurement method [3],[4]. From such experimental measurements, it has been found that heat release rates at initial stage of many burning items can be empirically Received 22 July 2005 Accepted 6 February 2006

2 166 J.YAMAGUCHI and T.TANAKA approximated in the form of Q= α t 2 letting Q be the heat release rate, t be the time and α be a constant associated with the item [3]. This type of fire is now being used extensively as the design fires in evacuation safety and smoke control designs of actual buildings [5], [6]. The purpose of predicting fire behavior in fire safety design of a building is to verify the fire safety performance of the building under some appropriately conservative assumption but not to analyze the fire behavior as accurately as possible. What design fire is to fire safety design is just like what design load is to structural design of building. It does not necessary represent a realistic fire behavior but it is an artificial fire condition that is so determined that somewhat severer result than most of real fire cases is predicted [7]. As long as the fire behavior in a building is predicted at safer side for fire safety design, the simpler the design fire the easier the calculation for safety verification. However, too severe design fire condition may claim unbearably expensive fire safety measures. So the design fire of which the heat release rate grows proportionally to t-square at the initial stage and then levels off at the maximum heat release rate for a while until the available fuel has been depleted is often employed [8]. Currently, three types of design fires are most frequently used in fire safety design practices, i. e., constant, t-square, and their combination. Smoke filling time etc. in complex conditions have been predicted often using two layer zone smoke transport models, such as BRI2 in Japan [9], ASET[10] and CFAST[11] in USA and many others [12]. On the other hand, for the prediction of the smoke filling in a fire room with simple geometry, simple prediction equations are provided as practical FSE tools [5], [6], [8]. The advantages of such simple equations in fire safety design practices are as follows: 1) Easy to grasp the relation between design conditions and smoke filling behavior. 2) Easy to understand the effect of fire parameters, such as heat release rate, on smoke filling behavior. 3) Easy to use for designers, who are not fire experts. 4) Can be calculated promptly responding to change of design conditions In addition, simple calculation equations in general have a function as an educational tool of fundamental fire physics for designers etc. since such equations explicitly show what parameter how much affects the fire behavior. In this study, for the purpose of expanding the applicability of such simple smoke filling equations, the simple equations which can apply to several typical design fires and rooms with somewhat complex ceiling geometries were developed.

3 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings THE SMOKE FILLING TIME IN THE FIRE ROOM 2.1 e fundamental equations of smoke filling Simple equations for smoke filling have already been proposed for some simple cases [5] and validated with full-scale smoke filling experiment in a large scale space [13]. The outline of the method is summarized as follows. In order to predict the smoke filling behavior, it is, in principle, necessary to solve the conservation of mass and the conservation of heat, at least. However, to derive the simple smoke filling equation, only mass conservation is considered, i.e. (1) where, ρ and V are the density and the volume of the smoke layer, respectively. m p is the flow rate of the fire plume. As shown in Figure 1, considering a rectangular room with constant ceiling height, the volume of the smoke layer, V, can be expressed as (2) where A r is the floor area of the room, H r is the ceiling height, z is the smoke layer interface height. Using Equation 2 into Equation 1 is given as follows (3) It is assumed here that the plume mass flow rate is given by the following formula by Zukoski et. al.[14]. (4) where C m is the plume coefficient, for which Zukoski proposed C m= Incidentally, the smoke layer interface height, z, should be measured from the virtual point of heat source distance. However, the virtual point of heat source distance is ignored for convenience. Using Equation 4 into Equation 3 yields (5) Equation 5 is the basis for the following discussions in this paper. Figure 1 Schematic of calculation model

4 168 J.YAMAGUCHI and T.TANAKA 2.2 e heat release rate of design fire and the ceiling geometry of fire room As stated already, the design fires most frequently used in fire safety design practices of actual buildings are illustrated in Figure 2 in terms of the heat release rates. Namely, the heat release rates of such design fire sources are (a) constant with time (constant fire) (b) proportional to time-square (t 2 fire) (c) proportional to time-square in the beginning, then constant (t 2 -constant fire) (a) constant fire (b) t 2 fire (c) t 2 -constant fire Figure 2 The heat release rate of the design fire In fire safety design practices, smoke filling calculations are frequently required for not only simple rectangular rooms but also somewhat complex spaces whose horizontal section areas vary with height, atria for example. Figure 3 illustrates the ceiling geometries of fire room consideration in this paper. (A) regular ceiling space (B) irregular ceiling space Figure 3 The ceiling geometries of the fire room 2.3 e smoke filling for constant fire For a constant fire, the heat release rate of Equation 5, Q f, is substituted by the constant heat release rate Q c, i.e. (6) Regular ceiling space For rooms of regular ceiling height, the smoke filling equation with a constant fire have been already available [2], i.e., the smoke layer interface height as a function of time is given by (7)

5 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings 169 Reversely, the smoke filling time as a function of the smoke layer interface height is given by (8) Irregular ceiling space Equation 7 and 8 can be extended to irregular ceiling space, such as a dome and a sloped ceiling atrium etc., if the space geometry is modeled into a combination of rectangular space elements as illustrated in Figure 4. It is not so difficult to derive the smoke filling equation in such a configuration as shown in Figure 4. That is, by slightly modifying the equation demonstrated in [16], the smoke filling time as a function of smoke layer interface height is given as (9) where n is number of rectangular space elements, A i is horizontal section area of rectangular space elements and H i is ceiling height of rectangular space elements. And the smoke layer interface height, z, needs to satisfy z H n. It is interesting note that Equation 9 is given by making summation of smoke filling time calculated by Equation 8 regarding each part of the space with different ceiling height. Figure 4 Dividing the room vertically Reversely, as an identical equation, the smoke layer interface height is given as a function of time as follows: (10) where the time, t, in Equation 10 needs to satisfy the following condition: (11)

6 170 J.YAMAGUCHI and T.TANAKA 2.4 e smoke filling for t 2 fire In case of t 2 fire, the heat release rate of Equation 5, Q f, is expressed as follows (12) where α is the fire growth rate coefficient. Using Equation 12 into Equation 5 yields (13) Equation 13 can be integrated as (14) where z 0 is the smoke layer interface height at time t Regular ceiling space For a simple rectangular space whose ceiling height is regular, using (t 0,z 0)=(0,H r), at the time of fire ignition, into Equation 14 yields the equation for the smoke layer interface height as a function of time as follows: (15) Reversely, the smoke filling time as a function of smoke layer interface height is as follows: (16) Irregular ceiling space In an irregular ceiling space, a simple smoke filling equation with t 2 fire has not yet been proposed. This can be derived as follows: First, the smoke filling time to fill the height ceiling part, i.e., the smoke filling time to the height which changes the cross-section area, t 1, can be calculated as, using A r=a 1, H r=h 1 and z=h 2 in Equation 16 as (17) Next, the time for the smoke layer interface height descends to height between H 2 and H 3, i.e. H 3 z < H 2, is given using A r=a 1+A 2 and (t 0,z 0)=(t 1,H 2) in Equation 14 as (18)

7 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings 171 Using Equation 17 into Equation 18 yields as follows: (19) where H 3 z < H 2. The similar process, Equation 17 through Equation 19, can be repeated to yield the equation for smoke filling time to arbitrary height z as (20) where z H n. Reversely, the smoke layer interface height can be given as a function of time as follows: (21) where the time, t, in Equation 21 needs to satisfy the following condition: (22) Note that the smoke filling time for t 2 fire is again given by the summation of the filling times in the spaces fictitiously divided corresponding to different ceiling height. 2.5 e smoke filling for t 2 -constant fire In this section, the simple equations in t 2 -constant fire, as shown in Figure 2(c), is considered. In this case, the heat release rate of Equation 5, Q f, is given as follows (23) where t c is the time at which the initial heat release of the growth fire reaches the constant value, i.e. (24) Regular ceiling space During the initial growing stage, i.e. 0<t t c, is given by Equation 15, therefore the smoke layer interface height H c at time t c is (25)

8 172 J.YAMAGUCHI and T.TANAKA Figure 5 The schematic of the smoke layer interface height After the transition to constant fire, i.e. t>t c, the simple equations constant fire, Equation 7 and Equation 8, can be invoked. Using t=t-t c, H r=h c in Equation 7 yields (26) where t t c. Hence, the smoke layer interface height in Equation 26 can be obtained by calculating the smoke layer interface height at the transition time, H c, and then using Equation 26. Or we may obtain a single equation, by using Equation 25 into Equation 26, as follows: (27) Equation 26 can be solved for t to yield the smoke filling time as a function of the smoke layer interface height as follows: (28) or identically (29) 3. COMPARISON OF SIMPLE EQUATION AND BRI 2002 PREDICTIONS 3.1 Calculation conditions In order to examine the level accuracy of the simple equations for smoke filling in this paper, comparisons of prediction results are made between the simple equation and BRI2002, a smoke transport zone computer model, for 3 sample cases shown Table 1. Two types of room geometries as shown in Figure 6 (a), i.e. Type1: irregular ceiling space, and (b), Type 2: regular ceiling space, are considered. Incidentally, the reason that each room has an opening in the lower part of wall is that BRI2002 needs a certain opening for room pressure calculation. Unlike BRI2002, the smoke layer density ρ is not calculated by the simple equations, so ρ is assumed as ρ=1, in these case studies.

9 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings 173 Table 1 Calculation conditions CASE 1 CASE 2 CASE 3 Heat Release Rate[kW] t 2 fire t 2 -constant fire Ceiling Geometry irregular ceiling space (Type 1) Figure 6(a) regular ceiling space (Type 2) Figure 6(b) irregular ceiling space (Type 1) Figure 6(a) (a) Type1: irregular ceiling space (b) Type 2: regular ceiling space Figure 6 The schematic of room geometries 3.2 Comparison of prediction results (1) CASE 1 Figure 7(a) and (b) shows the comparison of the predictions for CASE 1 by BRI2002 [15], which is the revised version of BRI2 smoke transport model, and the simple equations. The calculations by BRI2002 were made for two different locations of the fire source, i.e. in Area 1: high ceiling part and in Area 2: low ceiling part, of which results are shown in Figure 7(a) and (b), respectively. The smoke filling predictions by the simple equations are slightly faster than the predictions by BRI2002, particularly when the fire source is in Area 2. However, the simple equations can be said to be sufficiently accurate as tool used for smoke filling prediction in usual fire safety design practices.

10 174 J.YAMAGUCHI and T.TANAKA (a) The fire source location is in Area 1 (b) The fire source location is in Area 2 Figure 7 Comparison of the predictions by BRI2002 and the simple equations for CASE 1 (2) CASE 2 Figure 8 shows the comparison for CASE 2, in which t 2 -constant fire was assumed in a regular ceiling space. As can be seen in this comparison, the agreement of the predictions is very good between the simple equation and BRI2002. Figure 8 Comparison of the predictions by BRI2002 and the simple equations for CASE 2 (3) CASE 3 Figure 9 shows the comparison for CASE 3, in which t 2 -constant fire was assumed in a irregular ceiling space. The fire source location for prediction by BRI2002 is in Area1. As can be seen in this comparison, the agreement of the predictions is very good between the simple equation and BRI2002.

11 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings 175 As can be seen in this comparison the agreement between the simple equation is again very satisfactory. Figure 9 Comparison of the predictions by BRI2002 and the simple equations for CASE 3 4. CONCLUSION In this paper, simple predictive equations for smoke filling were developed for t-square fire source and a t-square and constant combined fire source, i.e. t-square fire at first and then constant fire at later stage, as shown in APPENDIX A. These equations are applicable not only to spaces with regular ceiling but also with irregular ceiling. It is very interesting to note that the smoke filling time in a irregular ceiling space can be calculated by fictitiously dividing the space corresponding to the different ceiling height, and adding up the smoke filling times calculated for each of the fictitiously rooms. The comparison of the predictions by the simple equations with those by BRI2002 demonstrates that the simple equations can be useful tools for smoke filling calculation in fire safety design practices. The simple equations developed in this study are summarized in Appendix. Incidentally, unlike a computer model such as BRI2002, the simple equations cannot predict smoke layer temperature so the density has to be assumed. It is desirable for better prediction to improve the model to enable to estimate the smoke layer temperature. REFERENCES 1. The SFPE Handbook of Fire Protection Engineering, 3rd Ed. Chapter 3, p For example, The verification method for evacuation safety of buildings, Ministry Order No. 1441, Ministry of Construction, JAPAN, Quintiere, J.: Principles of Fire Behavior, Delmar Publishers, p Gross, D.: Data Sources for Parameters Used in Predictive Modeling of Fire Growth and Smoke Spread, NBSIR , NBS, Tanaka, T. and Yamana, T.: Smoke Control in Large Scale Space ; (Part 1 Analytical theories for smoke control in large scale spaces), Fire Science and Technology, Vol. 5, No. 1, 1985

12 176 J.YAMAGUCHI and T.TANAKA 6. NFPA 92B: Smoke management System in Malls, Atria, and Large Areas, 1991 Edition, NFPA, Tanaka, T.: Concept and Framework of a Performance Based Fire Safety Design System for Building, J. of Applied Fire Science, Vol.3, No.4, Karlsson, B. and Quintiere, J. Q.: Enclosure Fire Behavior, CRC Press. 9. Tanaka, T.: A Model of Multiroom Fire Spread, NBSIR , NBS, Cooper, L. Y. and Stroup, D. W.: ASET - A Computer Program for Calculating Available Safe Egress Time, Fire Safety J., 9, Jones, W. W., Forney, G. P., Peacock, R. D. and Reneke, P. A.: A Technical Reference for CFAST: An Engineering for Estimating Fire and Smoke Transport, TN-1431, NIST, Friedman, R.: A Irnational Survey of Computer models for Fire and Smoke, J. of Fire Protection Engineering, 48(3), Yamana, T. and Tanaka, T. : Smoke Control in Large Scale Space ; (Part2 Smoke control experiments in a large scale space), Fire Science and Technology, Vol.5, No. 1, Zukoski, E.E., Kubota,T., Cetegen, B., : Entrainment in Fire Plume, Fire Safety Journal, Vol.3, , 1980/ Tanaka, T., Yamada S., : BRI2002 Two Layer Smoke Transport Model, Fire Science and Technology, Vol. 23, No. 1(special issue), Tanaka, T., : Introduction to Fire Safety Engineering of Buildings, The Building Center of Japan, pp , 2002(in Japanese) NOMENCLATURE LISTING A i horizontal section area of rectangular space elements (m 2 ) A r horizontal section area of fire room(m 2 ) c p specific heat of air(kj/kg.k) C m plume coefficient(kg/kj 1/3.m 5/3.s 2/3 ) H c H i H r m p n Q c Q f t t c smoke layer interface height with t c(m) ceiling height of rectangular space elements (m) ceiling height of fire room(m) flow rate of fire plume(kg/s) room division number heat release rate of constant fire(kw) heat release rate(kw) time(s) Transition time from t 2 -fire to constant fire(s) V smoke layer volume(m 3 ) z smoke layer interface height(m)

13 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings 177 Greek α fire growth coefficient(kw/s 2 ) ρ smoke layer density(kg/m 3 ) APPENDIX The simple equations for smoke filling Ceiling geometry Type of design fire regular ceiling space irregular ceiling space constant fire t 2 fire t 2 -constant fire

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

A Monte Carlo Approach for the Design of Thermal Fire Detection System

A Monte Carlo Approach for the Design of Thermal Fire Detection System A Monte Carlo Approach for the Design of Thermal Fire Detection System Walter W. Yuen Department of Mechanical & Environmental Engineering University of California at Santa Barbara California, USA and

More information

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE , Volume, Number 4, p.138-14, 23 EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE Yuanzhou Li, Ran Huo, Liang Yi and Guodong Wang State Key Laboratory of Fire

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

Potential Impact of New UL Fire Test Criteria

Potential Impact of New UL Fire Test Criteria Potential Impact of New UL Fire Test Criteria Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 7, 2014 Outline Background Recent History Task Group Progress

More information

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,

More information

Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building

Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building 5A-4 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building A. Sekizawa 1, S. Nakahama

More information

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS , Volume 3, Number 4, p.151-157, 2001 A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS F. Liu and X.Z. Fu Faculty of Urban Construction and Environmental Engineering Chongqing University, Chongqing

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES R. Huo a, Y. Li a, W. Fan a and W. Chow b a. State Key Laboratory of Fire Science, CHINA b. The Hong Kong Polytechnic University

More information

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM Mingjie Zheng Research Laboratory, SANKO AIR CONDITIONING CO., LTD. Nagoya, 450-0003, JAPAN ABSTRACT In large

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement First Revision No. 1-NFPA 259-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5865, Standard Test Method

More information

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Mohammed Mutafi 1, Mohammad Nasif 1*, William Pao 1 and

More information

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 2-NFPA 259-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D 5865, Standard Test Method

More information

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering Analysis of the influence of open door size on fire smoke diffusion law in protective engineering Abstract Zheli Xing a, Jinfeng Mao b, Chaofeng Li c and Jin Zhou d PLA University of Science and Technology,

More information

Advantages and Disadvantages of Fire Modelling

Advantages and Disadvantages of Fire Modelling Advantages and Disadvantages of Fire Modelling Dr Guillermo Rein School of Engineering University of Edinburgh & Imperial College London Dr Guillermo Rein 9 May 2012 Chief Fire Officers Association Annual

More information

Recent BRANZFIRE enhancements and validation

Recent BRANZFIRE enhancements and validation Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings 2014 Purdue Compressor/Refrigeration and Air Conditioning and High Performance Buildings Conference West Lafayette, IN, USA 14-17 July 2014 Heat Release Rate of an Open Kitchen Fire of Small Residential

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information

Keywords: slope stability, numerical analysis, rainfall, infiltration. Yu. Ando 1, Kentaro. Suda 2, Shinji. Konishi 3 and Hirokazu.

Keywords: slope stability, numerical analysis, rainfall, infiltration. Yu. Ando 1, Kentaro. Suda 2, Shinji. Konishi 3 and Hirokazu. Proceedings of Slope 25, September 27-3 th 25 SLOPE STABLITY ANALYSIS REGARDING RAINFALL-INDUCED LANDSLIDES BY COUPLING SATURATED-UNSATURATED SEEPAGE ANALYSIS AND RIGID PLASTIC FINITE ELEMENT METHOD Yu.

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS PROCEEDINGS, Fire and Evacuation Modeling Technical Conference 211 Baltimore, Maryland, August 15-16, 211 EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS Brian Salyers, Bevan Jones Holmes Fire 13 Sutter

More information

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME Elizabeth L. Milarcik, Stephen M. Olenick*, and Richard J. Roby Combustion Science & Engineering,

More information

Fire Test Evaluation using the Kerosene and Aviation Fuel

Fire Test Evaluation using the Kerosene and Aviation Fuel Fire Test Evaluation using the Kerosene and Aviation Fuel K. S. Bang, J.C. Lee, C. S. Seo, K. S. Seo, H. J. Kim* Korea Atomic Energy Research Institute, 15 Dukjin-Dong, Yuseung-gu, Daejeon, Korea 35-353

More information

VIRTUAL FIRES via COMPUTERS

VIRTUAL FIRES via COMPUTERS VIRTUAL FIRES via COMPUTERS Robert N. Meroney Wind Engineering Software Wind Engineering and Fluids Laboratory Civil and Environmental Engineering Colorado State University, Fort Collins, CO Paper prepared

More information

FIRE RESISTANCE LEVEL ASSESSMENTS AND DEVELOPMENT OF APPROPRIATE INPUT DATA

FIRE RESISTANCE LEVEL ASSESSMENTS AND DEVELOPMENT OF APPROPRIATE INPUT DATA FIRE RESISTANCE LEVEL ASSESSMENTS AND DEVELOPMENT OF APPROPRIATE INPUT DATA Andrew Barnett Fire Safety Engineer Scientific Fire Services Pty Ltd INTRODUCTION Co-authors: Mahmut Horasan, Scientific Fire

More information

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Marco Alexandre Onofre Dias This paper presents a model that was implemented

More information

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor 2C-1 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor Soo-Young Kim *, Eung-Sik

More information

TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS

TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS Arthur H. Gager III, PE and Gary Dominguez 1 Jensen Hughes agager@jensenhughes.com 2 Jensen Hughes gdominguez@jensehughes.com Abstract. FDS

More information

A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS

A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS V. BHOGESWARA RAO Research Scholar Email:pallivayala@gmail.com Dr. S. CHAKRADHAR GOUD Principal, Sri Sarada Institute of Science and Technology

More information

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing

More information

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL Reference : Spearpoint M J, Mowrer F W, McGrattan K. Simulation of a single compartment flashover fire using hand calculations, zone models and a field model. Proc. 3 rd International Conference on Fire

More information

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses

More information

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies MATEC Web of Conferences 13, 27 (214) DOI: 1.151/ matecconf/ 21413 27 C Owned by the authors, published by EDP Sciences, 214 Computer Simulation Investigation on the Effect of Channelled and Unchannelled

More information

Smoke Alarm Research at NIST

Smoke Alarm Research at NIST Smoke Alarm Research at NIST Thomas G. Cleary Fire Research Division National Institute of Standards and Technology Smoke Alarm Summit March 31, 2015 Outline Supporting ANSI/UL 217 268 Task Group on adding

More information

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 A. D. Parekh, P. R. Tailor Abstract The Montreal protocol and Kyoto protocol underlined the need of substitution

More information

Numerical Analysis of the Bearing Capacity of Strip Footing Adjacent to Slope

Numerical Analysis of the Bearing Capacity of Strip Footing Adjacent to Slope International Journal of Science and Engineering Investigations vol. 4, issue 46, November 25 ISSN: 225-8843 Numerical Analysis of the Bearing Capacity of Strip Footing Adjacent to Slope Mohammadreza Hamzehpour

More information

THE COMPARISON OF THE RESULTS OF A FULL SCALE EVACUATION TEST TO THE CALCULATION METHOD OF HUNGARIAN REGULATIONS AND TO THE PATHFINDER SOFTWARE

THE COMPARISON OF THE RESULTS OF A FULL SCALE EVACUATION TEST TO THE CALCULATION METHOD OF HUNGARIAN REGULATIONS AND TO THE PATHFINDER SOFTWARE Application of Structural Fire Engineering, 19-20 April 2013, Prague, Czech Republic THE COMPARISON OF THE RESULTS OF A FULL SCALE EVACUATION TEST TO THE CALCULATION METHOD OF HUNGARIAN REGULATIONS AND

More information

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,

More information

EVACUATION AND SMOKE MOVEMENT INTERACTIVE SIMULATION MODEL

EVACUATION AND SMOKE MOVEMENT INTERACTIVE SIMULATION MODEL EVACUATION AND SMOKE MOVEMENT INTERACTIVE SIMULATION MODEL S. Kakegawa and H. Notake Institute of Technology, Shimizu Corporation, 3-4-17, Etchujima, Koto, Tokyo, 135-853, Japan A. Sekizawa Department

More information

and vent height on mechanical smoke exhaust efficiency

and vent height on mechanical smoke exhaust efficiency Experimental investigation on influence of smoke venting velocity and vent height on mechanical smoke exhaust efficiency Ji Jie a, Li Kaiyuan b, Zhong Wei c, *, Huo Ran a a State Key Laboratory of Fire

More information

A Brief on Performance- Based Design for Building Fire Safety

A Brief on Performance- Based Design for Building Fire Safety International Conference on Safety & Security Management and Engineering Technology 2009 (ICSSMET2009) 17-18 December 2009, Taiwan A Brief on Performance- Based Design for Building Fire Safety Professor

More information

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

'" Corresponding author (

' Corresponding author ( New Estimation of the Thermal Interface Height in Forced-Ventilation Enclosure Fires L. AUDOUIN '=I, B. TOURNIAIRE Institut de Protection et de Sfireti Nucleaire (IPSN) Dtpartement de Recherches en StcuritC

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite

More information

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment AKIHIKO HOKUGO Building Research Institute Ministry of Construction Tatehara I, Tsukuba-City 305, Japan DAVID YUNG and

More information

Residential Building Walls and Environment in Amman, Jordan

Residential Building Walls and Environment in Amman, Jordan Int. J. of Thermal & Environmental Engineering Volume 3, No. 2 (211) 1-7 Residential Building Walls and Environment in Amman, Jordan S. J. Sulaiman*, N. Beithou Department of Mechanical Engineering, Applied

More information

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate KEYWORDS: Steel-plate forming, Induction heating, Triangle heating, Transverse shrinkage,

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 504/220-7475 A CRITIQUE OF HUGHES ASSOCIATES, INC. PAPER TITLED: Analysis of the Performance of Ganged

More information

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS , Volume 11, Number 2, p.21-26, 212 SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS C.Y. Tso and W.K. Chow Research Centre for Fire Engineering,

More information

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-02-07 THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS March, 2007 Society of Fire Protection Engineers - 1 - Position

More information

ANALYSIS OF PERFORMANCE-BASED SMOKE MANAGEMENT SYSTEM DESIGN IN A SHOPPING MALL

ANALYSIS OF PERFORMANCE-BASED SMOKE MANAGEMENT SYSTEM DESIGN IN A SHOPPING MALL , Volume 1, Number 4, p.181-192, 2 ANALYSIS OF PERFORMANCE-BASED SMOKE MANAGEMENT SYSTEM DESIGN IN A SHOPPING MALL K.H. Yang and J.N. Lee Mechanical Engineering Department, National Sun Yat-Sen Uniersity,

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin Hypercube Sampling And CFAST

Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin Hypercube Sampling And CFAST Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin ypercube Sampling And CFAST Wanhong WANG a, Dahuan ZU b, ui BAO c, Yun GUO a, Changhong PENG a * a School

More information

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Experimental

More information

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea CONDUCTING A FULL-SCALE EXPERIMENT ON A RAIL PASSENGER CAR ABSTRACT N. White and V.P. Dowling CSIRO Fire

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION Fire Australia 2017 Fire Safety Engineering Stream - Quantification of Fire Safety AS/NZS 1668.1:2015 IS IT GOOD ENOUGH FOR PERFORMANCE-BASED SMOKE EXHAUST SYSTEM DESIGN ABSTRACT M.C. HUI and M. KHEDHER

More information

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology

More information

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED - 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company

More information

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology PO Box 310 North

More information

EVACUATION MODELLING IN ROAD TUNNEL FIRES

EVACUATION MODELLING IN ROAD TUNNEL FIRES Complex Underground Multipurpose Facilities: Safety Challenges and Solutions Workshop organised by the ITA-COSUF as part of the ITA-AITES World Tunnel Congress 2013 EVACUATION MODELLING IN ROAD TUNNEL

More information

Computer Models For Fire and Smoke

Computer Models For Fire and Smoke Computer Models For Fire and Smoke Model Name: JASMINE Version: 3.1 Classification: Very Short Description: CFD or Field A CFD or field model for predicting consequences of fire to evaluate design issues

More information

An Experimental Investigation of the Fire Characteristics of the University of Waterloo Burn House Structure

An Experimental Investigation of the Fire Characteristics of the University of Waterloo Burn House Structure An Experimental Investigation of the Fire Characteristics of the University of Waterloo Burn House Structure by Amanda J. Klinck A thesis presented to the University of Waterloo in fulfilment of the thesis

More information

Effects of Smoke on Evacuation Martin Lopušniak 1, a

Effects of Smoke on Evacuation Martin Lopušniak 1, a Advanced Materials Research Online: 2014-02-27 ISSN: 1662-8985, Vol. 899, pp 539-542 doi:10.4028/www.scientific.net/amr.899.539 2014 Trans Tech Publications, Switzerland Effects of Smoke on Evacuation

More information

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces ZHENKUN WU 1,2, HAIHANG LI 1, YAPING HE 3, DECHUANG ZHOU 1, JIAN WANG 1 1 State Key Laboratory of Fire Science, University of

More information

Simulation of Full-scale Smoke Control in Atrium

Simulation of Full-scale Smoke Control in Atrium Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 608 613 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Simulation of Full-scale Smoke Control in

More information

Global Journal of Engineering Science and Research Management

Global Journal of Engineering Science and Research Management EXPERIMENTAL AND THEORETICAL STUDY OF MINIATURE VAPOR COMPRESSION CYCLE USING MICROCHANNEL CONDENSER Issam M. Ali Aljubury*, Ahmed Q. Mohammed, Marwa S. Neama * Mechanical Eng. Dept. College of Engineering,

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

The Study of Evacuation Times from the Multiplex Theatres

The Study of Evacuation Times from the Multiplex Theatres American Journal of Applied Sciences 9 (3): 321-326, 2012 ISSN 1546-9239 2012 Science Publications The Study of Evacuation Times from the Multiplex Theatres 1 Khanitha Songsakulchai, 2 Supat Patvichaichod

More information

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University Scientific Principals and Analytical Model Charcoal Cooler Lisa Crofoot MECH 425, Queens University 1.0 Scientific Principles Evaporative cooling is based on the principle that water requires heat energy

More information

Probabilistic-deterministic modelling of fire spread

Probabilistic-deterministic modelling of fire spread European Journal of Environmental and Safety Sciences 2014 2(2): 79-83 ISSN 1339-472X European Science and Research Institute (Original Research Paper) Probabilistic-deterministic modelling of fire spread

More information

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System A D Parekh, and P R Tailor Abstract Because of damaging effect of CFC refrigerants on stratospheric

More information

Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium

Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium Ramisetti Sairam Department of Building Technologies &Services, School of Planning and Architecture, JNA&FAU Hyd E-mail :

More information

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Conceptual Design of a Better Heat Pump Compressor for Northern Climates Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1976 Conceptual Design of a Better Heat Pump Compressor for Northern Climates D. Squarer

More information

Performance of an Improved Household Refrigerator/Freezer

Performance of an Improved Household Refrigerator/Freezer Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical

More information

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array International Journal of Modern Studies in Mechanical Engineering (IJMSME) Volume 4, Issue 1, 2018, PP 11-16 ISSN 2454-9711 (Online) DOI: http://dx.doi.org/10.20431/2454-9711.0401002 www.arcjournals.org

More information

BR-BO Adopted June 1, Evacuation Safety Performance Evaluation Manual

BR-BO Adopted June 1, Evacuation Safety Performance Evaluation Manual BR-BO-07-01 Adopted June 1, 2000 Evacuation Safety Performance Evaluation Manual Article 1: Scope of Application This manual applies to the following types of performance evaluations: (1) Performance evaluations

More information

Tenability criteria for design of smoke hazard management systems

Tenability criteria for design of smoke hazard management systems Tenability criteria for design of smoke hazard management systems By Dr Weng Poh M.AIRAH Associate director, principal fire engineer, Umow Lai Pty Ltd ABSTRACT In the design of smoke hazard management

More information

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team Jeremiah Crocker and Dr. Bin Xiao New Technology Team Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved. The products and specifications published herein are for general evaluation

More information

Construction Innovation Center Building 186

Construction Innovation Center Building 186 Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview

More information

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation

More information

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator 18 R. Saidur et al./journal of Energy & Environment, Vol. 6, May 2007 Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator R. Saidur, M. A. Sattar, M.

More information

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011 Performance evaluation of two stage indirect/direct evaporative cooler with alternative shapes and cooling media in direct stage Kulkarni.R.K 1, Rajput S.P.S 2 1 SVPM College of Engineering, Malegaon(bk),

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area

On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area 2005 Asia-Pacific Conference on Risk Management and Safety 1-22 December 2005, Hong Kong On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area 20 min Presentation Professor W.K.

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

26 June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

26 June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1002 26 June 2001 GUIDELINES ON ALTERNATIVE

More information