Conventional Fire Detection

Size: px
Start display at page:

Download "Conventional Fire Detection"

Transcription

1 SECTI 4: page 1 Section 4: Conventional Fire Detection Contents System Architecture Control Panel Automatic & Manual Detection Manual Call Points Smoke Detectors Heat Detectors Beam Smoke Detectors Duct Smoke Detector Alarm Devices S3 Electronic Sounders / Strobes S3 Voice Enhanced Sounders Ancillary Equipment Electronic Bells Door Release Relays Power Supplies Miscellaneous System Loading Calculator S3 Electronic Sounders / Strobes Sound Patterns S3 Voice Enhanced Sounders Sound Patterns

2

3 SECTI 4: page 3 4.1: conventional fire detection Xenex System Architecture Dual RX/TX Beam with reflector Beam Transmitter Beam Receiver End of Line Call Point Smoke Detector Smoke Detector 24V 3 Core Cable End of Line Control Unit Extend PSU Extend PSU Required (24V required) End of Line Call Point Smoke Detector Smoke Detector Heat Detector Call Point Duct Detector End of Line Control Panel (also 1,2,4,8 zone versions) Class Change Repeat Panel 1 N/O, 1 N/C relay contacts to auxiliary equipment such as door holders or manned centre link. Alarm Sounder Voice Enhanced Sounder End of Line Sounder Strobe Voice Enhanced Sounder Strobe End of Line Polarised Relay (to switch 230V equipment eg. door holders) Sounders Circuits Sounder Strobe

4 SECTI 4: page 4 4.1: conventional fire detection Xenex Control Panel The Xenex panel complies fully with the European standard EN 54 Parts 2 & 4 and can be used on installations meeting BS Each panel contains its own integral power supply and battery support for up to eight alarm sounder circuits, two auxiliary relay contacts, a zone disablement facility and a one man test and commission facility, all simplifying system design, installation and commissioning. Xenex Control Panel No. of Zones Maximum Load per Zone 3mA 3mA 3mA 3mA No. of Sounder Circuits Max. Sounder Circuit Load 500mA per circuit max 1A combined 500 ma per circuit Max 1.5A combined Batteries (seperate) 2 x 12V, 2.1 Ah 2 x 12V, 2.8 Ah Battery Standby Aux. Relay Contacts Approx Weight (with batteries) 72 hours plus 0.5 hours alarm load 1 N/O and 1 N/C pair, 1A at 24V 5.1 Kg 5.1 Kg 6.6 Kg 6.6 Kg Relevant Standard EN 54 Parts 2 & 4 Approvals LPCB approved to EN54: Parts 2 & 4 Cable Type Operating Temperature Class Change Facility BS 6387, 2 core, min 1.5mm 2 CSA Indoor, 0-40 o C Volt free contact max distance 100m Note: Maximum of 1, 8 zone repeat panel per system. Note: For maximum system loading table see page 16. Dimensions of all panels (inc Repeat panel) (mm) Zone LB 2 Zone LB 4 Zone LB 8 Zone LB Zone Repeat Panel LB Flush Surround Fire Fault Relay XEN-FFR (Batteries to be ordered seperatly) For flush mounting, aperture size 378mm x 245mm x 60mm

5 SECTI 4: page 5 4.2: Automatic & Manual DETECTI Manual Call Points Manual call points are manufactured from ABS with plastic covered push break glasses for safe and simple operation. No hammer is required. A polycarbonate cover version is available for applications susceptible to inadvertent operation, such as sports halls. Manual Call Point Nominal Voltage 24Vdc Ingress Protection IP43 (IP55 with cover) Approx Weight 0.11 Kg Operating Temperature -20 o C to +70 o C Relevant Standard EN Approvals LPCB pending Alarm Current 30mA (max) Colour Red (Similar to RAL 3020) Surface Mounted c/w Backbox IP44 New EN54 Pt11 version EN Surface Mounted with Cover and Backbox New EN54 Pt11 version EN Key Operated, Surface Mounted c/w Backbox Surface Mounted New EN54 Pt11 version EN Dimensions (mm) MCP Surface 87 Removable Terminalblock Weather Resistant Kit EN BS/EN Front Conversion Kit with Glass New EN54 Pt11 version EN-KIT Spare Square Glasses, pack of 10 New EN54 Pt11 version EN Hinged Cover with drilled front moulding EN54 Pt11 version EN 87 Pack of 10 Plastic Test Keys for EN and MCP MCP Weatherproof Enclosure for MCP S * Normally Open / Normally Close

6 SECTI 4: page 6 4.2: Automatic & Manual DETECTI Smoke Detectors Optical smoke detectors are ideal at detecting visually smoky fires which are likely to be slow, smouldering fires. ABS casing with red LED fire indicator. Optical Detector Special feature The use of the diode base allows monitoring of a removed detector to comply with BS N.B. Maximum of 20 per zone. Type Optical Nominal Voltage 9-28V dc Quiescent Current 60μA Ingress Protection IP30 Approx Weight 0.11 Kg Operating Temperature -10 o C to +50 o C Relevant Standards EN 54 7 Approvals LPCB approved Optical Common Base Dimensions (mm) 104 Common Base with Diode Base less Diode (surface cabling) Base with Diode (surface cabling) Remote LED module Remote Relay module with base

7 SECTI 4: page 7 4.2: Automatic & Manual DETECTI Heat Detectors Heat detectors respond to changes in temperature and are better suited to smoky, dusty or steamy environments than smoke detectors. A comprehensive range of fixed, high temperature and rate of rise devices are available, making the range suitable for areas where the temperature fluctuates for natural reasons or due to certain industrial processes. Heat Detector ABS casing with red LED fire indicator. Type Fixed Temp. Rate of Rise High Fixed Temp. Nominal Voltage 28V dc 28V dc 24V dc Quiescent Current 30μA 30μA 30μA Ingress Protection IP30 IP30 IP30 Approx Weight 0.07 Kg 0.07 Kg 0.07 Kg Operating Temperature -10 o C to +50 o C Relevant Standards EN 54 Part 5 EN 54 Part 5 EN 54 Part 8 Approvals LPCB LPCB - Trigger Temperature 58 o C NA (Factory preset 58 o C) 85 o C Sensitivity Grade 1 Grade 1 Grade 2 Dimensions (mm) Fixed Temperature Rate of Rise High Fixed Temperature Common Base Common Base with Diode Base less Diode (surface cabling) Base with Diode (surface cabling) Remote LED module Remote Relay module

8 SECTI 4: page 8 4.2: Automatic & Manual detection Beam Smoke Detectors Optical beam smoke detectors are suitable for large open areas where installation of single point detectors may be difficult or uneconomical. Beam detectors can be installed with separate transmitter and receiver or combined transceiver unit and reflector. Note: An additional 24V dc power supply is required. Dual Ended Beam Single Ended Reflective Beam Type Dual Ended Beam Combined Reflective Beam Nominal Voltage 24V dc 24V dc Quiescent Current Receiver: - 8mA Receiver: <4mA Transmitter: - 5mA Approx Packaged Weight 3.2 Kg 0.67 Kg Ambient Temperature -10 o C to 50 o C -30 o C to 55 o C Relevant Standards BS Beam Length 10m - 100m 50m - 100m Dimensions (mm) Separate Beam Smoke Detector Reflective Beam Detector Width: 130mm Height: 210mm Depth: 120mm Beam Detector Reflective Beam Power Supply EN

9 SECTI 4: page 9 4.2: Automatic & Manual detection Duct Smoke Detector The duct detector kit is comprised of a conventional detector and duct detector housing. The duct detector is mounted on the outside of the air duct. A venturi tube protrudes into the duct and draws a sample of the air which passes over the sensor and returns back into the duct. Duct Detector When the smoke density in the sampled air reaches the trigger level of the smoke detector an alarm will be signalled on the fire alarm control panel. Ingress Protection Operating Temperature Approx Weight Finish Air Velocity Quiescent Current IP54-10 o C to +60 o C 0.7Kg ABS plastic (Grey) 1M/S to 20M/S 90μA Dimensions (mm) Duct Detector Includes Venturi tube and Duct Kit Mounting Remote Relay Module Optical Smoke Detector

10 SECTI 4: page : ALarm devices S 3 Electronic Sounders / Strobes The S-cubed range of alarm sounders incorporate sound, speech and strobe effects all in one range of alarm devices. The range offers all variants in the choice of 2 colours, red or white, with either a shallow base version sealed to IP31 or a deep base version sealed to IP55. All the low profile sounders have the option of an integral strobe. As an aid to commissioning there is the option to use the HandiLink IR remote control to select sounder tones and adjust the volume remotely. This means physical access is not required to make this adjustment. This facility is only active when the sounders are turned on from the fire alarm panel. Low Profile Sounder 100 dba IP65 Electronic Sounder Red C3IP-SN-R IP65 Electronic Sounder White C3IP-SN-W IP31 Electronic Sounder Red C3-SN-R Technical specification 1.0. sounders and strobes Type Sounder Sounder/Strobe Strobe Only Sound Output at 1m See Tone Table See Tone Table N/A Strobe Flash Rate See Tone Table See Tone Table Variable Strobe Output N/A Equivalent to a 3w Xenon Strobe Equivalent to a 3w Xenon Strobe Average Current See Tone Table See Tone Table 6 24V Synchronisation Sound & Strobe synchronisation better than ±30mS over 20 minutes with all units powered from the same circuit Operating Voltage Range 10.8V 28.8V 10.8V 28.8V 10.8V 28.8V Ingress Protection IP55C with the Deep Base IP31C with the Shallow Base Approx Weight 0.3Kg 0.3Kg 0.3Kg Operating Temperature -10 o C to 50 o C -10 o C to 50 o C -10 o C to 50 o C Relevant Standards (Sounder only) IR Control Operating Distance Standards EN54-3 EN54-3 N/A 3m 3m N/A Complies with EN54 Pt3 IP31 Electronic Sounder White C3-SN-W Low Profile Sounder and Strobe 100 dba IP65 Electronic Sounder/Strobe Red C3IP-SN-ST-RR IP65 Electronic Sounder/Strobe White C3IP-SN-ST-WR IP31 Electronic Sounder/Strobe Red C3-SN-ST-RR IP31 Electronic Sounder/Strobe White C3-SN-ST-WR Conventional Strobe IP65 Ultra Low Current Strobe (5mA) Red Body/Red Lens C2IP-ST-RR Very low power consumption means more sounders and strobes per circuit The strobe option is equivalent to a standard 3w xenon strobe and uses 1/20th of the power 32 sounder tones are available Voice enhanced sounders are available in the range 4 voice phrases and a bell sound are available as standard All sound and strobe signals are synchronised to better than +/- 30mS over 20 minutes Sounders and Strobes are compatible with 12V and 24V systems A third wire option allows the selection of 2 alternative sounds. Ideal for class change applications Products incorporate innovative design features for which multiple patents have been granted Please note all strobes are red except where listed

11 SECTI 4: page : Alarm Devices S 3 Voice Enhanced Sounders Technical specification 1.1 Voice enhanced sounders & strobes Type Voice Enhanced Sounder Voice Enhanced Sounder/Strobe Sound Output at 1m See Table 3 See Table 3 Strobe Flash Rate See Table 3 See Table 3 Strobe Output Equivalent to a 3w Xenon Strobe Average Current See Table 3 See Table 3 Synchronisation Sound & Strobe synchronisation better than ± 30mS over 20 minutes with all units powered from the same circuit Message and Attention Tone Period Seconds Seconds Operating Voltage Range 10.8V 28.8V 10.8V 28.8V Maximum Reverse Monitoring Voltage Ingress Protection 30V/20μA 30V/20μA IP55C with the Deep Base IP31C with the Shallow Base Approx Weight 0.3 Kg 0.3 Kg Operating Temperature -10 o C to 50 o C -10 o C to 50 o C IR Control Operating Distance 3m 3m How to select a speech message and attention tone 1. Select the required speech message and tone from the signal 1 column of table 3 referring to table 1 and 2 for message and tone descriptions. 2. If the third wire option is used the two alternative messages and ones for your first selection are shown on the right hand side of table After making a selection set the switch SW1 as shown in the SW1 column of table 3. Conventional Speech Sounder and Strobe Table 1 Message No. Speech Message M1 Attention please this is an emergency please leave the building by the nearest available exit. (Female voice) M2 An incident has been reported in this building please await further instructions. (Female voice) M3 This is a test message no action is required. (Female voice) M4 This is a fire alarm! Please leave the building immediately by the nearest available exit. (Male voice) Complex Tone No. CTO Table 2 Tone Tone 1 Description of Tone Alarm Bell (equivalent to 8 Solenoid Bell) 12V 1m with strobe 14.2mA (without strobe 4.5mA) 24V 1m with strobe 12mA (without strobe 4.5mA) Standard messages and complex tones (Audio File - PA020001) Description Alternating tone 800/ 2Hz FP Telecoms Graphical representation Tone 2 Intermittent tone LF back up alarm BS 5839: Part 1 Tone 3 Intermittent tone 970Hz 0.25s on, 1s off BS 5839: Part 1 Tone 4 970Hz - BS 5839: Part 1 Tone 5 Fast sweep 800Hz 7Hz BS 5839: Part 1 Tone 6 Medium sweep 800Hz BS 5839: Part 1 Tone 7 Tone 8 Tone 9 Tone 10 Tone 11 Tone 12 Tone 13 Tone 14 Sweep 1200Hz - with 10ms silence German DIN tone evacuate Alternating tone 440Hz / 2Hz Turn out Sweden Intermittent tone Local warning Sweden Intermittent Tone 700Hz 4s On, 4s Off Industrial alarm Germany Fast whoop 500Hz 7Hz US temporal tone LF US temporal tone HF Define during manufacture default is a fast siren Low Profile Voice Enhanced Sounder and Strobe 100 dba IP31 Voice Sounder/Strobe Red C3-VP-ST-RR IP31 Voice Sounder/Strobe White C3-VP-ST-WR Remote Control Note: Only the messages and complex tones specified in table 1 are applicable to this S-cubed product. Note: The nominal sound frequencies stated in the table are based on the resonance frequency of the transducer. HandiLink IR Remote Control for the S-Cubed range of Sounders S3-CTROL

12 SECTI 4: page : Ancillary Equipment Electronic Bells An electronic bell for a wide range of uses. Metal casing available in red or grey finish. Suitable for semi flush or surface mounting. Bell Type 24V dc 230V ac Ingress Protection Standard IP40 Standard IP41 Special IP55 Special IP55 Approx Weight 1.1 Kg 1.25 Kg Operating Temperature Indoor, -10 o C to +50 o C Sound Output at 1m 93dB(A) 96dB(A) Current at Nominal Voltage 30mA 30mA Relevant Standard EN 54-3 Dimensions (mm) IP40 24V dc Electronic Bell Red 30mA M IP41 220/240V ac Electronic Bell Grey 30mA IP55 24V dc Weather Resistant Electronic Bell Red 30mA

13 SECTI 4: page : Ancillary Equipment Door Release To ensure fire doors close in an emergency and prevent the spread of fire and smoke. Moulded ABS and steel enclosure capable of floor or wall mounting. Complies with BS Door Holder Wall Mounted Wall Mounted Floor Mounted Type 24V dc 230V ac 24V dc Approx Weight Door plate, 0.07 Kg Door holder, 0.53 Kg Current Consumption 21mA 12mA 45mA Operating Temperature Indoor/Outdoor, -10 o C to + 50 o C Nominal Magnetic Pull 112 Newton 200 Newton Relevent Standard BS Finish Moulded ABS Dimensions (mm) Door Holders, Closers, Batteries and Chargers Magnet Door Holder 24V dc 22mA Magnet Door Holder 240V ac 17.5mA dia Door Holder Floor Plate Door Plate Assembly (Spare) Magnet Door Holder Floor Mounted 24V dc 45mA Power Supply Units for 24V dc Door Holders 23 Transformer Rectifier 24V dc 0.5A Transformer Rectifier 24V dc 1.5A

14 SECTI 4: page : Ancillary Equipment Relays Relay enclosure to house applications involving switching and timers. All purpose polycarbonate construction. Suitable for activating class change or start work signals. Low Profile Enclosure Coil Voltage Coil Current Contact Rating 240V ac Contact Rating 24V dc Profile Max. Capacity Ingress Protection Operating Temperature 24V dc 50mA 6A 5A High 4 mini relays IP67 Indoor/Outdoor, 0-40 o C 24V dc DPCO Relay c/w High Profile Enclosure V dc Relay Base and Diode Dimensions (mm) 50 Timer Octal Base 2-32 Secs. DOE 24V dc c/w Base Enclosures and Accessories for Relays High Profile Enclosure with DIN Rail 125x125x100mm

15 SECTI 4: page : Ancillary Equipment Power Supplies To supply additional standby power for control panels or relays. Protected against over-voltage and reverse polarity connections. Fault monitoring to comply with BS Power Supply Unit Mains Input 230V ac 230V ac Output Current 4A 1A Output Voltage 27.5V dc Operating Temperature -10 o to +40 o C -10 o to +50 o C Max. Battery Capacity 2 x 12V/24Ah 2 x 12V/7Ah Approx Weight 8.5 Kg 7.5Kg Power Supply Units (less cells) 24V, 6.0A charger EN 24V, 1A Charger

16 SECTI 4: page : miscellaneous System Loading Calculator Zone Loading To calculate the zone loading of any system complete the table below and ensure that the grand total does not exceed system limits (Xenex is 3mA per zone). Optical Smoke Detector 60 Fixed Temperature Heat Detector Rate of Rise Heat Detector 30 High Temperature Heat Detector 30 Notes: No. (a) Quiescent Load (µa) (b) Total Load (µa) (a x b) 30 Grand Total 1. If detector removal monitoring is required to comply with BS 5839, a detector base with diode should be used and the maximum number of detectors should not exceed 20 per zone. 2. Any number of manual call points may be included in zone calculations. 3. Beam detectors will require a separate power supply. Sounder Circuit Loading To calculate the maximum sounder loading complete the table below and ensure that the grand total does not exceed system limits. (For Xenex; maximum load per circuit is 0.5A. Total load maximum 1A). S-Cubed Sounders and Strobes No. (a) Operating CURRENT (ma) (b) Sounder Base 18 24V dc Bell 30 S 3 Sounder (no Strobe) S 3 Sounder (with Strobe) *See tone table for specific operating currents (page 17 section 4). * 2-6 (depending on tone) 5-12 (depending on tone) Total Load (ma) (a x b) Grand Total

17 SECTI 4: page : miscellaneous S 3 Electronic Sounders / Strobes Tone Table for sounder only and sounder / strobe variants Signal 1 Strobe Description SW1 Switch Tone 1 Tone 2 Tone 3 Tone 4 Tone 5 0.8Hz Alternating tone 800/ 2Hz - FP Telecoms BS 5839: Part 1 Alternating tone 800/ - BS 5839: Part 1 Intermittent tone LF back up alarm - BS 5839: Part 1 Intermittent tone HF back up alarm - 2nd tone BS 5839: Part 1 Intermittent tone 970Hz 0.25s - on, 1s off - BS 5839: Part 1 Graphical representation 12V Operating Current With Strobe ma Without Strobe ma 24V Operating Current With Strobe ma Without Strobe ma Signal 2 Strobe Signal 3 Strobe Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone 5 0.8Hz Tone Tone 3 0.5Hz Tone Tone 2 0.5Hz Tone 6 Tone 6 970Hz - BS 5839: Part 1 Tone 7 Tone 8 Tone 9 0.5Hz Slow sweep 300Hz- 1200Hz over 2s - Vds2300 Signal Fast sweep 800Hz - 7Hz - BS 5839: Part 1 Medium sweep 800Hz - - BS 5839: Part 1 Tone Hz Tone 11 Sweep 7Hz Tone 12 Sweep Tone 13 Tone Hz Slow whoop 500Hz Hz over 3s with 0.5s off Sweep 1200Hz - with 10ms silence - German DIN tone evacuate Tone 15 Alternating tone 2400/ 2Hz Tone 16 Tone 17 Alternating tone 554Hz for 100mS then 440Hz for 400ms - French AFNOR tone Alternating tone 440Hz / 2Hz - Turn out Sweden Tone 18 Continuous 700Hz - All clear Sweden Tone 19 Tone 20 Tone 21 Tone 22 Tone 23 Tone 24 Tone 25 6s - On 12s - Off 4s - On 4s - Off Sync. pulses Intermittent tone 700Hz 6s On 12s Off - Pre- vital message Sweden Intermittent tone - Local warning Sweden Rising 1s, constant 4s, fall 1000Hz - Industrial alarm Germany Intermittent tone 700Hz 4s On, 4s Off - Industrial alarm Germany Emergency evacuation to ISO ISO 8201 Tone Slow whoop 500Hz Hz over 4.5s - Evacuate Netherlands Siren (ramp up from 500Hz Hz in 3s then ramp down 1200Hz - 500Hz in 3s) Tone 26 Fast whoop 500Hz - 7Hz Tone 27 Tone 28 Sync. pulses Sync. pulses US temporal tone LF US temporal tone HF Tone 29 LF buzz 800Hz- 50Hz Tone 30 Alternate 2500/ 2Hz - Security alarm Tone 31 Alternate 2500 / 4Hz Tone 32 Define during manufacture - default is a fast siren Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone Hz Tone Tone 3 0.5Hz Tone Tone Hz Tone Tone 1 0.5Hz Tone Tone Hz Tone Tone Hz Tone Tone 3 0.5Hz Tone Tone Hz 6s - On 12s - Off Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone Hz Tone Tone 3 0.5Hz Tone Tone 4 0.5Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone Tone 3 0.5Hz Tone 6 4 Note: The current data in the table is for Red strobe only. The nominal sound frequencies stated in the table are based on the resonance frequency of the transducer. Tone 1 is the factory default setting

18 SECTI 4: page : miscellaneous S 3 Voice Enhanced Sounders table 3 Tone / voice Table for voice and voice / strobe variants Signal 1 Message Strobe Attention Tone SW1 Switch 12V With Strobe ma Decibel (dba) and current (ma) values Without Strobe ma 24V With Strobe ma Without Strobe ma Signal 2 Message Strobe Intermittent 1S On and 1S Off Attention Tone Signal 3 Message Strobe Attention Tone Tone only Attention tone followed by speech messages M1 Tone 1 M1 Tone 6 M1 Tone 11 M1 Tone 5 M1 Tone 8 M1 Tone 7 M1 Tone 12 M1 Tone 14 M4 Tone 1 M4 Tone 6 M4 Tone 11 M4 Tone 5 M4 Tone 8 M4 Tone 7 M4 Tone 12 M4 Tone 14 M1 CT0 M1 CT1 M1 CT2 M1 CT3 M1 CT4 M1 CT5 M1 CT6 M1 CT7 - CT0 - CT1 - CT2 - CT3 - CT4 - CT5 - CT6 - CT M2 0.5Hz Tone 2 M3 Tone M2 0.5Hz Tone 3 M3 Tone Tone 5 0.8Hz Tone 6 M3 Tone Tone 3 0.5Hz Tone 6 M3 Tone Tone 2 0.5Hz Tone 6 M3 Tone Tone 3 0.5Hz Tone 1 M3 Tone Tone 3 0.5Hz Tone 6 M3 Tone Tone 3 0.5Hz Tone 6 M3 Tone Tone 3 0.5Hz Tone 6 M6 Tone Tone 3 0.5Hz Tone 6 M6 Tone Tone Hz Tone 10 M6 Tone Tone 3 0.5Hz Tone 10 M6 Tone Tone 3 0.5Hz Tone 6 M6 Tone Tone 3 0.5Hz Tone 6 M6 Tone 4 Refer to decibel (dba) and current (ma) values stated in Table 1. Tone Hz Tone 10 M6 Tone 4 Tone 3 0.5Hz Tone 6 M3 Tone 14 Tone Hz Tone 18 M3 CT0 Tone 1 0.5Hz Tone 3 M3 CT1 Tone Hz Tone 18 M3 CT2 Tone Hz Tone 25 M3 CT3 Tone 3 0.5Hz Tone 6 M3 CT4 Tone Hz 6s - On 12s - Off Tone 6 M3 CT5 Tone 3 0.5Hz Tone 6 M3 CT6 Tone 3 0.5Hz Tone 6 M3 CT7 Tone 3 0.5Hz Tone 6 - CT0 Tone Hz Tone 25 - CT1 Tone 3 0.5Hz Tone 6 - CT2 Tone 4 0.5Hz Tone 6 - CT3 Tone 3 0.5Hz Tone 6 - CT4 Tone 3 0.5Hz Tone 31 - CT5 Tone 3 0.5Hz Tone 8 - CT6 Tone 3 0.5Hz Tone 6 - CT7 Note: Only the complex tones (CTn) and speech messages (Mn) specified in Table 1 are valid. The highlighted row in this table shows the factory default setting of the S-cubed unit.

Xenex Conventional Fire Detection & Alarm System

Xenex Conventional Fire Detection & Alarm System SECTI 4: page 1 Section 4: Xenex Conventional Fire Detection & Alarm System SECTI 4: page 3 Xenex system architecture Beam Transmitter Beam Receiver End of Line Call Point Smoke Detector Smoke Detector

More information

four Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1

four Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1 four Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1 ANALOGUE FIRE DETECTION VIGILON COMPACT FEATURES & BENEFITS four Keep it Simple All Vigilon devices connect onto the same 2

More information

VTG-32E Spatial Sounder 24Vdc EN54 part 3 approved

VTG-32E Spatial Sounder 24Vdc EN54 part 3 approved The VTG32E family of sounders have been designed to cover a wide spectrum of applications. The 24 volt EN543 approved version is for use with conventional fire alarm systems including SAVWIRE two wire

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

AP200 SERIES INTELLIGENT ALARM DEVICES

AP200 SERIES INTELLIGENT ALARM DEVICES Tech Data Sheet D0170GB Fire Detection /01 AP00 SERIES INTELLIGENT ALARM DEVICES Intelligent AP00 series alarm devices for FX fire detection system The intelligent AP00 series alarm devices are used in

More information

AP200 SERIES INTELLIGENT ALARM DEVICES

AP200 SERIES INTELLIGENT ALARM DEVICES Tech Data Sheet D017GB1 Fire Detection /01 AP00 SERIES INTELLIGENT ALARM DEVICES Intelligent AP00 series alarm devices for FX NET fire detection system The intelligent AP00 series alarm devices are used

More information

EFBW series - BiWire Ultra control panel

EFBW series - BiWire Ultra control panel 4.2 Control panels and repeater panels EFBW series - BiWire Ultra control panel Eaton s new BiWire Ultra fire detection system is unlike any other standard conventional system as the panel, conventional

More information

ELECTRONIC SOUNDER STROBE Model : AVD-C407

ELECTRONIC SOUNDER STROBE Model : AVD-C407 ELECTRONIC SOUNDER STROBE Model : AVD-C407 MULTRON range of combination Electronic Sounders with Strobe Lights are designed to complement our Fire Alarm products both technically and aesthetically as an

More information

4 wire conventional alarm system

4 wire conventional alarm system Scimitar 4 wire conventional alarm system from Channel Safety Systems Scimitar 4 wire conventional alarm system The Scimitar Fire Alarm Control System is a comprehensive range of high specification conventional

More information

Conventional Leaflets

Conventional Leaflets Conventional Leaflets Panels Last updated October 1999 Make leaflet selection by clicking on appropriate bookmark Return to Menu Installation and Basic Commissioning guide for the range of 1,2,4 and 8

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd THE NANO SYSTEM The revolutionary analogue addressable control panel Nano, the revolutionary control panel from Gent Nano is the latest fire detection control panel from Gent by Honeywell. It s a single

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

The complete conventional fire warning system

The complete conventional fire warning system The complete conventional fire warning system www.espuk.com MAG2P 2 Zone Fire Panel 2 programmable zones Active end of line monitoring and head removal 30 fire detectors per zone Unlimited number of call

More information

Fire Signalling. Signalling Solutions

Fire Signalling. Signalling Solutions Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

(68.52) X. June 2000 supersedes February vigilon ADVANCED FIRE DETECTION & ALARM SYSTEMS

(68.52) X. June 2000 supersedes February vigilon ADVANCED FIRE DETECTION & ALARM SYSTEMS (68.52) X June 2000 supersedes February 2000 vigilon ADVANCED FIRE DETECTION & ALARM SYSTEMS VIGILON SYSTEM ARCHITECTURE Repeat Panel Spur Manual Call Point T-breaker Alarm Sounder Max loop length 1000m

More information

Signaling Devices. Acoustic Signaling Devices 298. Optical Signaling Devices 309. Bosch Security Systems B.V.

Signaling Devices. Acoustic Signaling Devices 298. Optical Signaling Devices 309. Bosch Security Systems B.V. Signaling Devices Acoustic Signaling Devices 28 Optical Signaling Devices 30 26 Signaling Devices Acoustic Signaling Devices Acoustic Signaling Devices MSS300-SA SG 200 DS 10 LSN/GLT GLT GLT GLT Operating

More information

Product Manual Standard Asserta Sounder Range

Product Manual Standard Asserta Sounder Range Product Manual Standard Asserta Sounder Range Document Structure: Steve Martin - 18/09/08 Technical Information: Chris Anderson - 14/10/08 Cooper Fulleon Ltd Llantarnam Park Cwmbran South Wales NP44 3AW

More information

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology Fire-Cryer Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX Shaping Alarm Technology Fire-Cryer Plus The Fire-Cryer range of voice sounders was first introduced to the market by Vimpex in 1999.

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

XP95 Sounder VAD Base

XP95 Sounder VAD Base PP2478/2016/Issue 5 XP95 Sounder VAD Base FUNC TION The XP95 Sounder Visual Alarm Device (VAD) Bases incorporates a standard mouting base with a loop-powered sounder VAD. It is used to signal a fire alarm

More information

PRODUCT INFORMATION. Sounder SG 200. BDL F.01U A3.en / ST FIR/ PRM1 / zab. Page 1 of 10

PRODUCT INFORMATION. Sounder SG 200. BDL F.01U A3.en / ST FIR/ PRM1 / zab. Page 1 of 10 PRODUCT INFORMATION PI 38.43 Sounder SG 200 Page 1 of 10 Table of Contents 1. Product Description............................... 3 2. Features......................................... 3 3. Functional Description............................

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

MINERVA MX. 800 Series Ancillary Equipment

MINERVA MX. 800 Series Ancillary Equipment An extensive range of ancillary modules has been specifically designed for use with the MX range of Fire Controllers. The 800 range of ancillary modules provide the MX Fire Controller with a wide degree

More information

Nexus 120 DC Sounder Nexus 120 DC Sounder with 5J Xenon Beacon Nexus 120 DC Sounder with LED Beacon

Nexus 120 DC Sounder Nexus 120 DC Sounder with 5J Xenon Beacon Nexus 120 DC Sounder with LED Beacon Nexus 120 DC Sounder Nexus 120 DC Sounder with 5J Xenon Beacon Nexus 120 DC Sounder with LED Beacon Technical Specification 1. Sounder Supply Voltage Range 10-60V DC Current 0.12 0.55A* (Typ. 0.5A @ 24V,

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

Addressable and Conventional Fire Protection

Addressable and Conventional Fire Protection Addressable and Conventional Fire Protection Simply reliable F I R E P R O T E C T I O N The MAGPro and Fireline systems has been created to balance performance, reliability and aesthetics whilst being

More information

LS800S Intruder Alarm System. Engineering Manual

LS800S Intruder Alarm System. Engineering Manual LS800S Intruder Alarm System Engineering Manual Table of Contents Section 1 Overview of System 1.1 Kit Contents 1.2 Tools Required 1.3 System Features Section 2 Planning your installation 2.1 Location

More information

Industries. As a premier global manufacturing company, we believe that great brands are

Industries. As a premier global manufacturing company, we believe that great brands are JSB Fire Systems ONE COOPER Every day, thousands of people all over the world use products made by Cooper Industries. As a premier global manufacturing company, we believe that great brands are built on

More information

Analogue addressable devices

Analogue addressable devices Apollo XP95 Analogue addressable devices from Channel Safety Systems Apollo XP95 Analogue addressable devices The XP95 range of analogue addressable fire detectors is advanced in design, improved in performance

More information

Fire Signalling. Signalling Solutions

Fire Signalling. Signalling Solutions Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.

More information

INPUT / OUTPUT MINI MODULES

INPUT / OUTPUT MINI MODULES INPUT / OUTPUT MINI MODULES APPLICATION The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Fire Detection Pty Ltd Fire Detection - Addressable Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Fire Detection

More information

Intellia Sounder Bases and Sounder Beacon Bases

Intellia Sounder Bases and Sounder Beacon Bases Intellia Bases and Beacon Bases The Base and Beacon Base are a local-area alarm devices designed for indoor use. They can be connected only to detection systems using Intellia detectors and FX control

More information

VIMPEX BS Evacuation. Fire Alarms EN Banshee. Beacons. FlashDome. Electronic Sounders. Audible Alarm

VIMPEX BS Evacuation. Fire Alarms EN Banshee. Beacons. FlashDome. Electronic Sounders. Audible Alarm VIMPEX Sounder Range Fire Alarms Banshee Electronic Sounders FlashDome EN 54-3 Evacuation Audible Alarm BS 5839-1 Beacons The range of sounders, beacons, sounder beacons and accessories represents the

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Fire Detection - Addressable Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Fire Detection - Addressable Protec Protec Algo-TecTM

More information

Door Release Power Supply

Door Release Power Supply www.protectingpeople.co.uk Door Release Power Supply Engineer / Installation Manual Document: VI55.1 Protecting People Printed : 04/03/2004-1 - Ventcroft Ltd Door Release Power Supply Engineer / Installation

More information

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices. FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001

More information

Fire Signalling. Signalling Solutions

Fire Signalling. Signalling Solutions Fire Signalling Signalling Solutions Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place.

More information

INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder

INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder 1) Introduction The Appello tone and speech annunciation sounder has three different styles in AC and DC. A105NAPPX

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System. Fire Detection - Addressable Protec Protec Algo-Tec TM 6100 Interactive Digital Addressable Fire Control System ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE Protec Protec Algo-TecTM 6100 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

PATROL SOUNDERS 110/120 db(a) PA 10 / PA 20

PATROL SOUNDERS 110/120 db(a) PA 10 / PA 20 PRODUCTS AUDIBLE SIGNALING DEVICES PATROL SOUNDERS 110/120 db(a) PA 10 / PA 20 PATROL the new generation of sounders. Three dimensional innovation. Safe; an incorrect installation is virtually impossible.

More information

Addressable Detectors & Bases

Addressable Detectors & Bases Edwards Signaling Catalog u Intelligent Initiating Addressable Detectors & Bases Detectors: E-PD, E-PHD, E-HD Bases: B4U, RB4U, IB4U, SB4U Overview Edwards intelligent addressable detectors are meticulously

More information

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

FIREBETA EXTINGUISHING CONTROL PANEL (ECP) F I R E D E T E C T I O N A N D C O N T R O L FIREBETA EXTINGUISHING CONTROL PANEL (ECP) Three versions: 2 areas of detection and 1 area extinguishing 4 areas of detection and 1 area extinguishing 4 areas

More information

PATROL SOUNDERS 100/105 db(a) PA 1 / PA 5

PATROL SOUNDERS 100/105 db(a) PA 1 / PA 5 PRODUCTS AUDIBLE SIGNALING DEVICES PATROL SOUNDERS 100/105 db(a) PA 1 / PA 5 PATROL the new generation of sounders. Three dimensional innovation. Safe; an incorrect installation is virtually impossible.

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range Fire Detection MINERVA Marine MX T2000 Panel Range Features: Enhances fire detection and eliminates unwanted alarms using fuzzy logic Assists fire fighting and training by providing on-screen risk management

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules Application The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors and manual call points,

More information

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL CONTENTS 1. INTRODUCTION. 3 1.1 HANDLING THE PCBS 1.2 USING THIS MANUAL

More information

Protec. Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network. Fire Detection - Addressable

Protec. Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network. Fire Detection - Addressable Protec Protec Fire Detection Pty Ltd Protec Algo-Tec TM 6500 Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE CAUTION

More information

Protec. Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network

Protec. Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network Protec Protec Fire Detection plc Protec Algo-Tec TM 6500 Open Protocol Interactive Digital Addressable Fire Control System with Algo-Tec 6600 Bridging Network ADDRESSING SAFETY SYSTEMS WITH INTELLIGENCE

More information

intelligent solutions

intelligent solutions Alco is one of the leading intelligent solution providers of Fire Detection System. Security System and Public Addressing System in the United States of America. Based in California since 1992, we have

More information

Series 65 Product Guide MAN 3036

Series 65 Product Guide MAN 3036 Series 65 Product Guide MAN 3036 TABLE OF CONTENTS Page No. 1 Ionisation Smoke Detector... 1 1.1 Operating Principles:... 1 1.2 Product Codes... 2 1.3 Integrating Version:... 2 1.4 Options:... 2 1.5 Safety

More information

Emergi-Lite Orbis detectors

Emergi-Lite Orbis detectors Emergi-Lite Orbis detectors Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofire systems. Non-addressable (conventional) smoke and heat sensors respond

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

Solution F2. Fire Alarm Control Panels one step ahead.

Solution F2. Fire Alarm Control Panels one step ahead. Solution F2 Fire Alarm Control Panels one step ahead. Sicherheitstechnik Sicherheitstechnik GmbH GmbH The Fire Alarm Control Panel Solution F2 Solution F2 in B2 enclosure (B01090-00) The Concept The Solution

More information

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING GENERAL The VEC 25/50 is a state-of-the-art, compact, stand-alone or slave Emergency Voice Evacuation Control. The VEC 25/50 is offered in a self-contained, cost-effective design and includes a 25 Watt,

More information

MINERVA MZX125 Digital Addressable Fire Detection System

MINERVA MZX125 Digital Addressable Fire Detection System DATASHEET MINERVA MZX125 Digital Addressable Fire Detection System The Minerva MZX125 is a highly featured digital addressable panel with a comprehensive but easy to operate user interface. The system

More information

Precept Marine Control Panel Application Guide

Precept Marine Control Panel Application Guide Precept Marine Control Panel Application Guide Contents Page 1.0 Cabinet Specifications 2 2.0 Panel Hardware Specifications 5 3.0 Panel Configuration 8 4.0 Technical Specifications 8 5.0 Battery Sizes

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control File: S8485 Wiring Diagram This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control Panel. The operation of this product is intended for indoor

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation The most user friendly Contents Section 1 Overview of System 1.1 Kit Contents 1.2 Tools Required 1.3 System Features Security Alarm System L S 4 0 0 Section 2 Planning your Installation 2.1 Location of

More information

Industrial Signalling

Industrial Signalling Industrial Signalling Introduction Introduction Klaxon Signals manufactures the world s largest range of sound signalling equipment and solutions for the European and worldwide market place. Product Range

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

SISTEMAS DE SEGURIDAD MIRA, S.L. COMPANY & PRODUCT GUIDE

SISTEMAS DE SEGURIDAD MIRA, S.L. COMPANY & PRODUCT GUIDE SISTEMAS DE SEGURIDAD MIRA, S.L. COMPANY & PRODUCT GUIDE Sistemas de Seguridad Mira, S.L. focuses on the design, development and manufacture of advanced components for fire detection systems. To secure

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and Operating Manual BCU RANGE OF

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information

SAFE AREA AUDIBLE & VISUAL SIGNALLING PRODUCTS

SAFE AREA AUDIBLE & VISUAL SIGNALLING PRODUCTS SAFE AREA AUDIBLE & VISUAL SIGNALLING PRODUCTS Document No. Date Rev. STD-SEMCO-T-LA-0003 08/12-2011 1 www.semcomaritime.com Contents Contact sheet - Component Sales & Logistics... 3 Daily Support - DK...

More information

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF DETECTOR TYPE ED816 ZE 1 ZE 2 ZE 3 ZE 4 ZE 5 ZE 6 ZE 7 S ZE 8 CIRCUIT 1 ZE 9 ZE 10 ZE 11 ZE 12 ZE 13 ZE 14 ZE 15 ZE 16 CIRCUIT 1 POWER POWER SUPPLY GENERAL MENT DC GENERAL SYSTEM ALARM DELAYED ALARM RESOUND

More information

X10 Mini, Midi & Maxi

X10 Mini, Midi & Maxi Industrial Sounder, Sounder Beacon X0 Mini, Midi & Maxi Installation Manual EAT X0 Mini, Midi & Maxi Installation Manual (90F) Contents Overview and purpose... Product assembly... Select wiring method......

More information

L-Series, Emergency Communication Devices

L-Series, Emergency Communication Devices Notification Appliances L-Series, Emergency Communication Devices Description The L-Series Emergency Communications devices and accessories combine application versatility with all of the same time-saving

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TBLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Inputs 4 Outputs 4 LED Indications 4 User Keypad Functions 5 Engineer Keypad Functions 6

More information

An introduction to... Sigma

An introduction to... Sigma An introduction to... Sigma XT+ Sigma XT+ Overview The Sigma XT+ 21000 series are the latest additions to the Sigma family of control equipment from Kentec Electronics Limited. The Sigma XT+ range combines

More information

Intelligent addressable fire alarm control panel

Intelligent addressable fire alarm control panel Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity

More information

Evolution Analogue Addressable Fire System

Evolution Analogue Addressable Fire System Addressable Fire System optimum fire safety systems solutions High speed FSK protocol, uniquely resistant to noise Up to 254 addresses per loop for flexible system design Built to exceptional marine standards

More information

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 PREMIER EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 USER MANUAL Approved Document No: GLT.MAN-132 INDEX Extinguishing

More information

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware

More information

SOUNDER CONTROL MODULE SCM-AS4

SOUNDER CONTROL MODULE SCM-AS4 1 of 9 INTRODUCTION DESCRIPTION The forms part of the Nittan (UK)'s SENSORTEC-ANALOGUE range of Analogue Addressable Devices. This module is designed to control a group of bells or sounders from the detection

More information

INSTRUCTION MANUAL A121APPX, AL121APPX & MV121 APPELLO Alarm Tone and Voice Annunciation Sounder

INSTRUCTION MANUAL A121APPX, AL121APPX & MV121 APPELLO Alarm Tone and Voice Annunciation Sounder AUTHORIZED DISTRIBUTOR ControlSystemsUSA.com Houston, Texas USA sales@controlsystemsusa.com 832-615-3588 INSTRUCTION MANUAL A121APPX, AL121APPX & MV121 APPELLO Alarm Tone and Voice Annunciation Sounder

More information

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features 990-052, Issue 6 20 March 2006 ID50 Series Single Loop Intelligent Fire Alarm Panels Section: Intelligent Fire Alarm Panels GENERAL The NOTIFIER ID50 series single loop intelligent fire alarm panels, has

More information

CONTENTS NBM-06 Bell (6") Page 1

CONTENTS NBM-06 Bell (6) Page 1 CONTENTS NBM-06 Bell (6") - - - Page 1 NBM-08 Bell (8") - - - Page 1 LFB-24 Sounder Banshee - Page 2 VCT--NT Base Version Sounder Page 2 VCT--NT Wall Version Sounder Page 2 VRS1-R or W Bedhead Sounder

More information

Apollo Accreditation. Need further information? Visit

Apollo Accreditation. Need further information? Visit Product Catalogue 2016/2017 Apollo Accreditation Apollo products are certified in a global arena to meet the most exacting standards set by both our customers, and the dynamic and challenging environments

More information

MINERVA MZX125. Digital Addressable Fire Detection System

MINERVA MZX125. Digital Addressable Fire Detection System A C C E S S C O N T R O L C C T V E A S R F I D F I R E P R O T E C T I O N I N T R U D E R A L A R M S DATA SHEET MINERVA MZX125 Digital Addressable Fire Detection System Features: Long term service and

More information

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

Conventional Audible Visual Range

Conventional Audible Visual Range Conventional Audible Visual Range Visual Devices Non-Addressable Audible Visual Devices Base Sounder Honeywell s conventional audible visual devices operate over a wide input voltage range of 9 to 33VDC

More information

L-Series, Indoor Strobes and Horn Strobes

L-Series, Indoor Strobes and Horn Strobes Notification Appliances L-Series, Indoor Strobes and Horn Strobes Indoor Selectable-Output Horns, Strobes and Horn Strobes for Wall Applications General The L-Series audible visible notification products

More information

Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel. Application Guide

Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel. Application Guide Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware

More information

SECURIT 700L PLUS ENGINEERING MANUAL

SECURIT 700L PLUS ENGINEERING MANUAL SECURIT 700L PLUS ENGINEERING MANUAL C & K Systems Ltd 13/03/97 C031-096-02 NEW ENHANCED FEATURE SET Securit 700L PLUS Engineering instructions INTRODUCTION The Securit 700L is a microprocessor intruder

More information

SIRENS PROGRAMMABLE MULTI-SOUND SIGNAL by Tomar Electronics

SIRENS PROGRAMMABLE MULTI-SOUND SIGNAL by Tomar Electronics by Tomar Electronics SIRENS POWER ALARM PROGRAMMABLE MULTI-SOUND INDUSTRIAL SIGNALS The POWER ALARM siren is a heavy duty industrial audible alarm designed to operate under adverse industrial conditions

More information