Operating Instructions

Size: px
Start display at page:

Download "Operating Instructions"

Transcription

1 Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 DE Güglingen Telefon: +49(0) Service: +49(0) Telefax: +49(0) Internet: Operating Instructions Alarm unit for oil, petrol and grease separators Type: WGA 06 WGA 06 Part No.: WGA-ÖW probe Part No.: WGA-AS probe Part No.: Oil-on-water alarm or overflow alarm Read instructions before using device! Observe all safety information! Keep instructions for future use! Version: ID No.:

2 Contents 1 This instruction manual Precautions Explanation of symbols and typeface Safety Intended use Predictable incorrect application Safe handling Staff qualification Modifications to the product Usage of spare parts and accessories Liability information Product description Specifications Transportation and storage Mounting and commissioning Mounting the evaluation unit Mounting the probes Mounting the junction box Operation Factory settings Test Altering the factory settings Maintenance Troubleshooting Shutting down and disposal Spare parts and accessories Warranty Copyright Customer satisfaction Addresses Appendix Approval documents Auswerteeinheit Approval documents probes Declaration of conformity WGA 06

3 1 This instruction manual 1.1 Precautions This instruction manual This instruction manual is part of the product. Read this manual before using the product. Keep this manual during the entire service life of the product and always have it readily available for reference. Always hand this manual over to future owners or users of the product. WARNING TERM Type and source of the danger is shown here. Precautions to take in order to avoid the danger are shown here. There are three different levels of warnings: Warning term DANGER WARNING CAUTION Meaning 1.2 Explanation of symbols and typeface Symbol Immediately imminent danger! Failure to observe the information will result in death or serious injuries. Possibly imminent danger! Failure to observe the information may result in death or serious injuries. Dangerous situation! Failure to observe the information may result in minor or serious injuries as well as damage to property. Meaning Prerequisite for an activity Activity consisting of a single step 1. Activity consisting of several steps Result of an activity Bulleted list Text Highlighting Indication on a display Highlighting WGA 06 3

4 Safety 2 Safety 2.1 Intended use The WGA 06 alarm unit consists of an evaluation unit and a capacitance probe (WGA-ÖW or WGA-AS). With the probe WGA-ÖW the WGA 06 alarm unit is exclusively suitable for detection of accumulations of oil in separator sumps or shafts. With the probe WGA-AS the WGA 06 alarm unit is exclusively suitable for detection of maximum levels in separators or retention tanks. Any use other than the use explicitly permitted in this instruction manual is not permitted. 2.2 Predictable incorrect application The WGA 06 alarm unit must never be used in the following cases: Using the evaluation unit in hazardous areas (ex) If the device is operated in hazardous areas, sparks may cause deflagrations, fires or explosions 2.3 Safe handling The WGA 06 alarm unit represents state-of-the-art technology and is made according to the pertinent safety regulations. Each device is subjected to a function and safety test prior to shipping. Operate the WGA 06 alarm unit only when it is in perfect condition. Always observe the operating instructions, all pertinent local and national directives and guidelines as well as the applicable safety regulations and directives concerning the prevention of accidents. 2.4 Staff qualification The product may only be mounted, commissioned, operated, maintained, shut down and disposed of by qualified, specially trained staff. Electrical work may only be performed by trained electricians qualified in accordance with the local and national directives. 2.5 Modifications to the product Changes or modifications made to the product by unauthorised persons may lead to malfunctions and are prohibited for safety reasons. 4 WGA 06

5 Product description 2.6 Usage of spare parts and accessories Usage of unsuitable spare parts and accessories may cause damage to the product. Use only genuine spare parts and accessories of the manufacturer (refer to chapter 11, page 25). 2.7 Liability information The manufacturer shall not be liable for direct or consequential damage resulting from failure to observe the technical instructions, guidelines and recommendations. The manufacturer and the sales company shall not be liable for costs or damages incurred by the user or by third parties in the usage or application of this device, in particular in case of improper use of the device, misuse or malfunction of the connection, malfunction of the device or of connected devices. The manufacturer or the sales company shall not be liable for damages resulting from any use other than the use explicitly permitted in this instruction manual. The manufacturer shall not be liable for misprints. 3 Product description Fig. 1: Evaluation unit Fig. 2: WGA-ÖW capacitance probe Fig. 3: WGA-AS capacitance probe Included in delivery are as per your order the evaluation unit and one WGA-ÖW or WGA-AS capacitance probe, a junction box and installation material. WGA 06 is a one-channel alarm unit. Typical applications are high level and low level alarms in liquid tanks, condensed water alarms, level control and alarms in oil, sand and grease separators. WGA 06 5

6 Product description Fig. 4: Application examples WGA-ÖW is a floating probe, which provides an alarm of at least 15 mm thick oil or hydrocarbon layer on water. The most common applications are for example inspection shafts and different kind of basins with altering liquid level. WGA-AS is a level detector for high level, low level and e.g. leak detection. Typical applications are oil separators and grease traps where oil/water interface or water/air interface need to be detected. The probes are an apparatus of equipment group II, category 1 G (Directive 94/9/EC). The probes can be installed in zone 0/1/2 hazardous area. The evaluation unit must not be installed in hazardous area. 1 LED indicator for mains 2 LED indicators of alarm and fault 3 Test button 4 Reset button for alarm and fault 5 Connector for one WGA level probe [EEx ia] Fig. 5: Evaluation unit front view 6 Potential-free relay outputs for monitoring and control purposes 6 WGA 06

7 4 Specifications Evaluation unit Table 1: Specifications evaluation unit Parameter General specifications Dimensions (W x H x D) Mounting holes (Ø) Material enclosure Operational delay relays Ex-classification Special conditions (X) Electrical parameters Value 175 x 125 x 75 mm 4.5 mm Polycarbonate Operating temperature range Ambient 25 C to +50 C Specifications 5 or 30 s. Relays de-energize at trigger point. Operation mode selectable for increasing or decreasing level. II (1) G [EEx ia] IIC VTT 05 ATEX 005X (Ta = -25 C to +50 C) U o = 14.7 V; I o = 55 ma; P o = 297 mw; R = 404 Ohm C o = 608 nf; L o = 10 mh; L o /R o = 116,5 µh/ohm C o = 3.84 nf; L o = 30 mh; L o /R o = 466 µh/ohm Characteristic curve of the output voltage is trapezoidal. Refer to table 2, page 8. Supply Supply voltage AC 230 V ± 10 % The device is not equipped with a mains switch Power consumption 2 VA Fuse 125 ma T, 5 x 20 mm (EN /3) Impedance of the current Max. 75 Ohm loop between the control Refer to table 3, page 9. unit and a probe WGA 06 7

8 Specifications Parameter Relay outputs Insulation level, probe/ mains supply voltage Electrical safety Value Two potential-free relay outputs, 250 V, 5 A, 100 VA 375 V (EN 50020) Electrical safety EN Class Protection IP 65 Category II/III (EN ) Electromagnetic compatibility (EMC) Noise suppression EN Noise immunity EN II Due to non-linear characteristics of the probe voltage, the interaction of both, capacitance and inductance, must be taken into account. The table below indicates the connecting values in explosion groups IIC and IIB. In explosion group IIA the values of the group IIB can be followed. Table 2: Connecting values in explosion groups IIC and IIB Maximum permissible value Interaction of capacitance and inductance Ca La Ca La IIC 608 nf 10 mh 568 nf 458 nf 388 nf 328 nf 258 nf IIB 3,84 µf 30 mh 3,5 µf 3,1 µf 2,4 µf 1,9 µf 1,6 µf Lo/Ro = 116,5 µh/ohm (IIC) and 466 µh/ohm (IIB) 0,15 mh 0,5 mh 1,0 mh 2,0 mh 5,0 mh 0,15 mh 0,5 mh 1,0 mh 2,0 mh 5,0 mh 8 WGA 06

9 Specifications Maximum length of the probe cable is determined by the resistance (max. 75 Ohm) and other electrical parameters (Co, Lo and Lo/Ro) of the probe circuit. Table 3: Example: Determing the maximum cable length Parameter Condition Influence of resistance Value Instrument cable with following characteristics is used: DC resistance of a twin wire at +20 C is approx. 81 Ohm/km Inductance is approx. 3 µh/m Capacitance is approx. 70 nf/km Estimate for additional resistances in the circuit is 10 Ohm. The maximum length of the cable is then ( 75 10) Ohm = 800 m. 81 Ohm / km Influence of inductance Influence of capacitance Total inductance is 0,8 km x 3 µh/m = 2,4 mh. The sum value of the cable and e.g. WGA-AS probe [Li = 30 µh] is 2.43 mh. L/R ratio is 2,4 mh = 37 µh/ohm (75 10) Ohm which is less than the maximum allowed value 116,5 µh/ohm. Die Kapazität des Kabels beträgt 0,8 km x 70 nf/km = 56 nf. Die Summe der Werte für das Kabel und z. B. eine Sonde WGA-AS [Ci = 3 nf] beträgt 59 nf. Cable capacitance is 0,8 km x 70 nf/km = 56 nf. Combined value of the cable and the e.g. WGA-AS probe [Ci = 3 nf] is 59 nf. When compared to the values in table 2, we can summarize that above values do not limit the use of this particular 800 m cable in explosion groups IIB or IIC. Feasibility of other cable types and probes for different distances can be calculated accordingly. WGA 06 9

10 Specifications WGA-AS probe (overflow alarm) Table 4: Specifications WGA-AS probe Parameter General specifications Dimensions (L x Ø) Material enclosure Operational principle Cable Ex-classification Electrical parameters Value 81 x 82 mm AISI 316, PVC Capacitive Operating temperature range Ambient 25 C to +60 C Supply Supply voltage Electrical safety Protection IP 68 Electromagnetic compatibility (EMC) Noise suppression EN Noise immunity EN Shielded, oil-proof instrumentation cable 3 x 0.5mm². Standard length is 5 m. II 1 G EEx ia IIA T5 VTT 05 ATEX 008X U i = 18 V; I i = 66 ma; P i = 297 mw; C i = 3 nf; L i = 30 µh; Un = 9-18 V Approx. DC 12 V of the evaluation unit The probe can be installed in zone 0/1/2 hazardous area with the following special conditions: The ambient temperature is between 25 C and +60 C The probe cable can be extended with the AFRISO junction box type LJB or LJB The junction box is of light metal so there may be sparks if the box is subjected to friction or impact. The box shall be grounded. 10 WGA 06

11 Specifications WGA-ÖW probe (oil-on-water alarm) Fig. 6: Dimensions Table 5: Specifications WGA-ÖW probe Parameter Value General specifications Material enclosure AISI 316, PVC Cable Shielded, oil-proof instrumentation cable 3 x 0.5 mm². Standard length is 5 m. Can also be delivered according to the order with a maximum 15 m long cable. The cable can be extended with a similar instrumentation cable. The maximum pair resistance of the cable should not exceed 75 Ohm. Operational principle Capacitive Ex-classification II 1 G EEx ia IIA T5 VTT 05 ATEX 008X Electrical parameters U i = 18 V; I i = 66 ma; P i = 297 mw; C i = 3 nf; L i = 30 µh; U n = 9-18 V Operating temperature range Ambient 25 C to +60 C Electrical safety Protection IP 68 Electromagnetic compatibility (EMC) Noise suppression EN WGA 06 11

12 Transportation and storage Parameter Value Noise immunity EN The probe can be installed in zone 0/1/2 hazardous area with the following special conditions: The ambient temperature is between 25 C and +60 C The probe cable can be extended with the junction box type LJB or LJB The junction box is of light metal so there may be sparks if the box is subjected to friction or impact. The box shall be grounded. 5 Transportation and storage CAUTION Damage to the device due to improper transportation. Do not throw or drop the device. CAUTION Damage to the device due to improper storage. Protect the device against shock when storing it. Store device in a clean and dry environment. 6 Mounting and commissioning The evaluation unit must not be installed in hazardous area. Probes connected to the evaluation unit may be installed in explosive atmosphere zone 0,1 or 2. In case of installations in explosive atmospheres the national requirements and relevant standards as EN and EN must be taken into account. If electrostatic discharges can cause hazards in the operating environment, the device must be connected into equipotential ground according to requirements with regards to explosive atmospheres. Equipotential grounding is made by connecting all conductive parts into same potential e.g. at the cable junction box. Equipotential ground must be earthed. The device does not include a mains switch. A two pole mains switch (AC 250 V, 1 A), which isolates both lines (L1, N) must be installed in the main power supply lines in the vicinity of the unit. This switch 12 WGA 06

13 Mounting and commissioning facilitates maintenance and service operations and it has to be marked to identify the unit. When executing service, inspection and repair in explosive atmosphere, the rules in standards EN and EN about instructions of Ex-devices must be obeyed. 6.1 Mounting the evaluation unit Mount the evaluation unit to the wall. The mounting holes are located in the base plate of the enclosure, beneath the mounting holes of the front cover. The connectors of the external conductors are isolated by separating plates. The plates must not be removed. Install the plate covering the connectors back after executing cable connections. The cover of the enclosure must be tightened so, that the edges touch the base frame. Only then do the push buttons function properly and the enclosure is tight. 6.2 Mounting the probes Probe WGA-AS (overflow alarm) In case of installations in explosive atmospheres the national requirements and relevant standards EN and EN must be taken into account. The probe shall not be installed into a space where caustic vapour, gas or liquid, such as aromatic and chlorinated hydrocarbons or strong alkalis or acids, can damage the equipment. WGA-AS is equipped with a shielded 3-wire cable. The wires 1 and 2 shall be connected to the corresponding connectors (1 = +, 2 = ) in the evaluation unit. Wire 3 shall be connected to equipotential ground together with the shield of the cable. Install the WGA-AS probe according to fig. 7, page 14. WGA-AS causes an alarm, when the probe is immersed ¼ to ¾ in oil or when the probe is 5 to 10 mm in water. The trigger level can be adjusted by SENSITIVITY within the evaluation unit (refer to chapter 7.3, page 20). The probe can be mounted loose-hanging at the cabel from the top side of the oil separator. For the proper installation hight also refer to the operations instructions of the separator. WGA 06 13

14 Mounting and commissioning Fig. 7: Connection for WGA-AS probe 1 Cover plate 2 Safe area 3 Hazardous area 4 Supply voltage, L1 = phase conductor, N = neutral conductor 5 Mains switch 6 Fuse 14 WGA 06

15 7 Relay 1 (alarm relay) 3 = common pole 4 = opening pole when alarm 5 = closing pole when alarm 8 Relay 2 (operating relay) 6 = common pole 7 = opening pole when alarm 8 = closing pole when alarm 9 Channel 1 9 = auxiliary connection (SHD) 10 = [+] supply pole to probe 11 = [-] supply pole to probe 10 4 separating plates of the connectors 11 Shield of the probe cable 12 Channel 1 13 Junction box LJB Pair shield 15 To equipotential ground Mounting and commissioning Relays are in alarm position, when the mains voltage ist off. Connect all shields and excess wires to the same point. WGA 06 15

16 Mounting and commissioning Probe WGA-ÖW (oil-on-water-alarm) The probe shall not be installed into a space where caustic vapour, gas or liquid, such as aromatic and chlorinated hydrocarbons or strong alkalis or acids, can damage the equipment. Install the WGA-ÖW probe according to fig. 8. Fig. 8: Connection for WGA-ÖW probe a Evaluation unit d Equipotential ground b Junction box e Extension cable shield c Probe cable shield Relays are in alarm position, when the mains voltage ist off. Connect all shields and excess wires to the same point. WGA-ÖW is equipped with a shielded 3-wire cable. The wires 1 and 2 shall be connected to the corresponding connectors (1 = +, 2 = -) in the control unit. Wire 3 shall be connected to equipotential ground together with the shield of the cable. Ground connector of the float frame shall be connected to equipotential ground. The cable can be shortened or, when the evaluation unit is located further away from the probe, the cable can be extended with the junction box, which is included in the delivery. The probe floats freely on the liquid. Therefore, please use long enough a cable to avoid hanging in the air in critical situations (e.g. when the liquid level decreases). When installing WGA-ÖW probe into an explosion hazardous zone (0/1/2), the following standards need to be followed: EN and EN WGA 06

17 Operation 7 Operation 6.3 Mounting the junction box If the probe cable must be extended or there is need for equipotential grounding, it can be done with the cable junction box. The cabling between the WGA 06 control unit and the junction box should be done with a shielded twisted pair instrument cable. In fig. 7, page 14, the shields and excess wires have been connected to the same point in galvanic contact with metallic frame of the junction box. This point can be connected to equipotential ground thru the ground terminal. Other components of the system that need to be grounded can also be connected to the same ground terminal. LJB2 junction box enables cable extension in potentially explosive atmospheres. The wire used for equipotential grounding must be min. 2.5 mm² mechanically protected or, when not protected, the minimum cross section is 4 mm². 7.1 Factory settings Make sure, that the cable between the evaluation unit and the probe does not exceed maximum connection values (refer to chapter 4, page 7). Junction box of type LJB2 include light alloy parts. When installing in explosive atmosphere, make sure, that the junction box is located so, that it can not be mechanically damaged or it will not be exposed to external impacts, friction etc. causing ignition of sparks. Make sure, that the junction box is closed properly. Normal mode no alarms Mains LED indicator is on. Other LED indicators are off. Relays 1 and 2 are energized. Oil-on-water alarm/overflow alarm Mains LED indicator is on. Alarm LED indicator is on. Buzzer on after 5 s delay. Relays de-energize after 5 s delay. WGA 06 17

18 Operation 7.2 Test Fault alarm Probe cable break, short circuit or a broken probe. Too low or too high probe signal current. Mains LED indicator is on. Probe cable Fault LED indicator is on after 5 s delay. The relays de-energize after 5 s delay. Buzzer is on after 5 s delay. Resetting of an alarm Pressing the Reset push button. Buzzer will go off. Relay 1 energizes. Relay 2 will stay de-energized until the actual alarm or fault is off. If the operation is not as described here, check the factory settings (refer to chapter 7.3, page 19) or contact the manufacturer. Before pressing the Test button, make sure that the change of relay status does not cause hazards elsewhere. Simulating an oil-on-water alarm (WGA-ÖW probe) Lift up the WGA-ÖW probe totally in the air. An alarm occurs. Simulating an overflow alarm (WGA-AS probe) Lift and immerse the WGA-AS probe few times into the liquid. An alarm occurs. Testing at normal mode 1. Press and hold the Test push button. Alarm and Fault LED indicators are immediately on. Buzzer is immediately on. Relays de-energize after 2 sec of continuous pressing. 2. Release the Test push button. LED indicators and buzzer go immediately off. Relays energize immediately. 18 WGA 06

19 Operation Testing during a oil-on-wat alarm or overflow alarm 1. Press and hold the Test push button. Fault LED indicator is immediately on. Alarm LED indicator of the channel which activated the alarm remains on. The corresponding relay will remain de-energized. Alarm LED of the other channel is on and the relay will deenergize. Buzzer remains on. If it has been reset earlier, it will return to be on. If relay 1 was already reset, it will de-energize again after 2 s. Test will not affect relay 2, because it is already in alarm status. 2. Release the Test push button. The device returns without delay to the preceding status. Testing during a fault alarm Press the Test push button. The device does not react to the test at all. WGA 06 19

20 Operation 7.3 Altering the factory settings If the factory settings described in chapter 7.1, page 17, differ from the specifications, check if the settings match with the specifications in fig. 9. If necessary the factory settings can be altered. The following settings can be altered. Operating direction: High level or low level function (increasing or decreasing level). Operation delay: 5 or 30 seconds Trigger level: Trigger point of an alarm in the probe s sensing element. Fig. 9: Altering the factory settings 1 The settings of channel 1 3 Serial number are made with switches S1 4 Probe selection (channel 1) and S2 and potentiometer in the left 5 WGA-AS/WGA-ÖW probe 2 Type plate In fig. 9, the switches are as set in the factory. The following tasks must only be executed by a person with proper education and knowledge of Ex-i devices. We recommend, that when altering the settings the mains voltage is off or the device is initialized before the installation is executed. 20 WGA 06

21 Operation Operating directions (MODE) Switch S1 is used to set the operating direction. When the switch is in its low position, Alarm LED indicator as well as buzzer is on and relays de-energize when the liquid level is beneath the trigger level of the probe (low level mode, probe WGA-AS).This setting is also used, when an alarm of an oil-layer on water is required. When the switch is in its high position the Alarm LED indicator as well as buzzer will be on and relays de-energize when the liquid level is above the probe s trigger level (high level mode, probe WGA-AS). 1 Alarm when level below trigger level 2 Alarm when level above trigger level 3 Trigger level Fig. 10: Operating directions Setting the operational delay (DELAY) Switch S2 is used to set the operational delay of the device. When the switch is in low position relays operate and buzzer is on after 5 seconds after the level reaches trigger level, if the level still remains on the same side of the trigger level.when the switch is in high position, the delay is 30 seconds. Delays are operational in both directions (energizing, de-energizing). 1 Verzögerung 5 Sekunden 2 Verzögerung 30 Sekunden Fig. 11: Funktionsverzögerung einstellen Alarm LED follows the probe current value and trigger level without delay. Fault LED has a fixed delay of 5 seconds. WGA 06 21

22 Operation Setting the trigger level (SENSITIVITY) 1 WGA-AS/WGA-ÖW capacitance probe 2 When rotating the trimmer clockwise the trigger level moves upwards 3 When rotating the trimmer anti-clockwise the trigger level moves downwards Fig. 12: Setting the trigger level Adjusting the switching point for WGA-AS probe: 1. Immerse the probe into the liquid on the designated hight. 2. Rotate the potentiometer until the alarm LED will go on and the relay de-energizes. Consider the delay. 3. Check the function by lifting and immersing the probe few times into the liquid. Adjusting the switching point for WGA-ÖW probe: 1. Let the probe float freely on the water. 2. Lift up the probe as much as there is assumed to be oil or hydrocarbon layered on the water in alarm situation (the layer that should generate an alarm). 3. If the evaluation unit does not operate, adjust the SENSE trimmer slowly until the desired switching point is reached. The sensitivity can also be decreased by adjusting the position of the sensor lower in the floating construction. Too sensitive settings cause unnecessary alarms if there are waves in the liquid. 22 WGA 06

23 8 Maintenance Table 6: Maintenance times When Min. alle 6 Monate und nach jeder Entleerung des Abscheiders Nach jedem Schichtdickenalarm Activity Maintenance Funktionstest durchführen, siehe Kapitel 7.1, Seite 17. Sonden reinigen. Sonden reinigen. Die Netzsicherung kann durch eine andere EN /3-konforme Glasrohrsicherung mit 5 20 mm/125 ma T ausgetauscht werden. Zum Reinigen der Sonden kann eine milde Reinigungslösung (z. B. Spülmittel) und eine Bürste verwendet werden. Alle sonstigen Reparatur- und Wartungsarbeiten am Gerät dürfen ausschließlich von einer im Umgang mit Ex-i-Geräten geschulten und vom Hersteller autorisierten Person durchgeführt werden. 9 Troubleshooting Repair work may only be performed by qualified, specially trained staff. Table 7: Troubleshooting Problem Possible reason Repair Mains LED indicator is off. Fault LED indicator is on. Supply voltage too low. Fuse is blown. Transformer or mains LED indicator is faulty. Current in probe circuit too low (cable break) or too high (cable in short circuit). Probe is broken. Check if the two pole mains switch is off. Check the fuse. Measure the voltage between poles N and L1. It should be AC 230 V + 10 %. Make sure, that the probe cable has been connected correctly to the evaluation unit. Measure the voltage separately between the poles 10 and 11. The voltages should be between 10,5 and 12 V (WGA-ÖW probe). If the voltages are correct, measure the probe current. See below. WGA 06 23

24 Troubleshooting Problem Possible reason Repair Other malfunctions. Send the device to the manufacturer. Measuring the probe current 1. Disconnect probe s [+] wire from probe connector (pole 10). 2. Measure short circuit current between [+] and [-] poles. 3. Connect ma-meter as in fig 13, page 24. If the probe is located in an explosive atmosphere, the multimeter must be Exi-approved. 4. Make a comparison to the values in table 8, page Connect the wire back to the connector. a b WGA 06-Sondenanschluss Zur Sonde Fig. 13: Measuring the probe current Table 8: Probe current WGA-AS, Pole 10 [+] and 11 [-] WGA-ÖW, Pole 10 [+] and 11 [-] Short circuit ma ma Probe in air 5-7 ma 5-6 ma Probe in oil 9-12 ma 9-11 ma Probe in water ma ma 24 WGA 06

25 Shutting down and disposal 10 Shutting down and disposal 1. Switch off mains voltage. 2. Dismount the device (see chapter 6, page 12, reverse sequence of steps). 3. To protect the environment, this device must not be disposed of together with the normal household waste. Dispose of the device according to the local conditions and directives. This device consists of materials that can be reused by recycling firms. The electronic inserts can be easily separated and the device consists of recyclable materials. If you do not have the opportunity to dispose of the used device in accordance with environmental regulations, please contact us for possibilities to dispose of it or to return it. 11 Spare parts and accessories Part Part No. Event reporting system Phone Alarm SD Event reporting system GSM Alarm Event reporting system EMS Event reporting system EMS Warranty The warranty of the manufacturer for this product is 24 months after the date of purchase. This warranty shall be good in all countries in which this device is sold by the manufacturer or its authorised dealers. 13 Copyright The manufacturer retains the copyright to this manual. This manual may only be reprinted, translated, copied in part or in whole with the prior written consent of the manufacturer. We reserve the right to technical modifications with reference to the specifications and illustrations in this manual. 14 Customer satisfaction Customer satisfaction is our prime objective. Please get in touch with us if you have any questions, suggestions or problems concerning your product. WGA 06 25

26 Addresses 15 Addresses The addresses of our worldwide representations and offices can be found on the Internet at 16 Appendix 16.1 Approval documents Auswerteeinheit 26 WGA 06

27 Appendix WGA 06 27

28 Appendix 28 WGA 06

29 Appendix 16.2 Approval documents probes WGA 06 29

30 Appendix 30 WGA 06

31 Appendix 16.3 Declaration of conformity WGA 06 31

SET Installation and Operating Instructions. Level switch for one sensor

SET Installation and Operating Instructions. Level switch for one sensor Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel.: +358 29 006 260 Fax: +358 29 006 1260 7.11.2013 Internet: www.labkotec.fi 1/14 SET-1000 Level switch for one sensor Copyright 2013 Labkotec Oy

More information

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use! Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 74363 Güglingen Telefon +49 7135-102-0 Service +49 7135-102-211 Telefax +49 7135-102-147 info@afriso.de

More information

OilSET-1000 (12 VDC)

OilSET-1000 (12 VDC) Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

OilSET Installation and Operating Instructions. Oil Separator Alarm Device Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec

More information

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000

More information

SET-2000 Hi Level/Oil

SET-2000 Hi Level/Oil Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve

More information

SET-2000 Oil/Sludge 12 VDC

SET-2000 Oil/Sludge 12 VDC Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 12.2.2015 Internet: www.labkotec.fi 1/14 SET-2000 Oil/Sludge 12 VDC Alarm Device for Oil Separators with

More information

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...

More information

Instruction Manual. Electronic gas and smoke detector GRM

Instruction Manual. Electronic gas and smoke detector GRM Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 DE-74363 Güglingen Telefon +49(0)7135-102-0 Service +49(0)7135-102-211 Telefax +49(0)7135-102-147 E-Mail

More information

AND INSTALLATION MANUAL

AND INSTALLATION MANUAL Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel. +358 29 006 260 Fax +358 29 006 1260 Internet: www.labkotec.fi 10.10.2013 SET/DM3AL Level sensor OPERATION AND INSTALLATION MANUAL 1(5) SYMBOLS

More information

Instruction Manual. Automatic fuel oil de-aerator SMART-FLO 3/K B100 COMPATIBLE

Instruction Manual. Automatic fuel oil de-aerator SMART-FLO 3/K B100 COMPATIBLE Sid Harvey s 605 Locust Street Garden City, NY 11530 Instruction Manual Automatic fuel oil de-aerator SMART-FLO 3/K Read manual before use! Observe all safety information! Keep manual for future use! 05.2015

More information

MANUAL Oil Level Sensor

MANUAL Oil Level Sensor PROCESS AUTOMATION MANUAL Oil Level Sensor KVF-104-PF ISO9001 0102 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products

More information

Inductive slot sensor

Inductive slot sensor 0102 Model Number Features 2 mm slot width Technical Data specifications Switching function Normally closed (NC) Output type NAMUR Slot width 2 mm Depth of immersion (lateral) 5... 7 mm, typ. 6 mm Output

More information

SolarSET GSM SolarSET GSM with a Beacon

SolarSET GSM SolarSET GSM with a Beacon Labkotec Oy Myllyhaantie 6 FI-33960 Pirkkala FINLAND Tel. +358 29 006 260 Fax +358 29 006 1260 13.08.2009 Internet: www.labkotec.fi SolarSET GSM SolarSET GSM with a Beacon Solar Powered Oil Separator Alarm

More information

Operating instructions

Operating instructions Operating instructions Level switches Minimelder, Maximelder Minimelder-R (with relay) Maximelder-R (with relay) Read instructions before using product! Observe all safety information! Keep instructions

More information

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0)

OSA 3. Level alarm for oil separator. Afriso Ema AB. Kilvägen 2 SE Arlöv Sweden T +46-(0) F +46-(0) Level alarm for oil separator CONTENTS: Functional description... 2 Component parts... 3 Spare parts... 5 Safety regulations... 6 Checklist... 7 Installation... 8 Commissioning... 11 Operation... 14 Maintenance...

More information

Sensor module. Operating instructions. Sensor module, Type 17-51P2-... Document No P2-7D0001 Version: 17 May 2011/Rev. 0

Sensor module. Operating instructions. Sensor module, Type 17-51P2-... Document No P2-7D0001 Version: 17 May 2011/Rev. 0 Sensor module Operating instructions Sensor module, Document No. 11-51P2-7D0001 Version: 17 May 2011/Rev. 0 Operating Instructions Sensor-Module Type: 17-51P2-. Document no.: 11-51P2-7D0001 Version: 17.

More information

OPTIBAR P 1010/2010 C Supplementary instructions

OPTIBAR P 1010/2010 C Supplementary instructions OPTIBAR P 1010/2010 C Supplementary instructions Pressure transmitter Equipment category II 1G / Ga, II 1D / Da in protection type intrinsic safety Exi KROHNE CONTENTS OPTIBAR P 1010/2010 C 1 Safety instructions

More information

Operating instructions

Operating instructions Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 74363 Güglingen Telefon +49 7135 102-0 Service +49 7135-102-211 Telefax +49 7135-102-147 info@afriso.de

More information

MANUAL Overflow sensor NVF-104/34-PF

MANUAL Overflow sensor NVF-104/34-PF PROCESS AUTOMATION MANUAL Overflow sensor NVF-104/34-PF ISO9001 0102 Overflow sensor NVF-104/34-PF With regard to the supply of products, the current issue of the following document is applicable: The

More information

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS INSTALLATION AND MAINTENANCE INSTRUCTIONS 2251EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2,

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-i Edition 09/2018 CONTENTS 1 Safety instructions 3 1.1 General notes... 3 1.2 EU conformity... 3 1.3 Approval according to the IECEx scheme...

More information

DB5 Intrinsically Safe Sounder Type DB-5

DB5 Intrinsically Safe Sounder Type DB-5 Operating Instructions RTK Instruments Limited DB5 Intrinsically Safe Sounder Type DB-5 Description The DB5 Sounder is a strong, lightweight warning sounder, CENELEC certified to Ex II 1G EExia IIC T4

More information

PROTECT SRB 200EXi-1A

PROTECT SRB 200EXi-1A 2 Installation up to zone 1/21 J S L1 0V X1 X3 S11 S12 S21 S22 Installation up to zone 2 A1 F1 F2 U B U EXi U i 0V S12 S22 X1 X3 K1 Logic K2 K1 K2 13 23 U EXi SRB 200EXi U B -1A U i K1 K2 PA PA A1 A2 13

More information

Translation of the assembly instructions with operating instructions and technical appendix

Translation of the assembly instructions with operating instructions and technical appendix BA Ex-SBU Switch box type SBU-x(1,2,3)x Translation of the assembly instructions with operating instructions and technical appendix In accordance with EU ATEX Directive 2014/32/EU In accordance with EU

More information

SITRANS T. SITRANS T Explosion protected temperature sensor. General information. Marking of the degree of protection. Range of uses.

SITRANS T. SITRANS T Explosion protected temperature sensor. General information. Marking of the degree of protection. Range of uses. General information 1 Marking of the degree of protection 2 SITRANS T SITRANS T Explosion protected temperature sensor Operating Instructions Range of uses 3 Installation 4 Assembly and disassembly 5 Commissioning

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 8 mm non-flush Stainless steel housing Usable up to SIL2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 8 mm

More information

RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION

RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION Special Safety Instruction en RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION Contents TankRadar Pro European ATEX Directive Information............................... 2 ATEX marking and Ex Certification

More information

Battery Powered Separator Alarm Type Standalone Unit. Installation, Operation & Maintenance

Battery Powered Separator Alarm Type Standalone Unit. Installation, Operation & Maintenance Battery Powered Separator Alarm Type 17200 Standalone Unit Installation, Operation & Maintenance Battery Powered Separator Alarm Type 17200 Contents Declaration of Conformity 3 IMPORTANT 3 General Description

More information

OPTIWAVE X500 Supplementary Instructions

OPTIWAVE X500 Supplementary Instructions OPTIWAVE X500 Supplementary Instructions OPTIWAVE 3500 C OPTIWAVE 6500 C OPTIWAVE 7500 C Supplementary Instructions for ATEX applications KROHNE CONTENTS OPTIWAVE X500 1 General safety information 4 1.1

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 5 mm flush Usable up to SIL2 acc. to IEC 61508 Accessories EXG-18 Quick mounting bracket with dead stop BF 18 Mounting flange, 18 mm Technical Data specifications Switching element

More information

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm 0102 Model Number Features 4 mm non-flush Accessories BF 12 Mounting flange, 12 mm Technical Data specifications Switching element function NAMUR, NO Rated operating distance s n 4 mm Installation non-flush

More information

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm 0102 Model Number Features 5 mm non-flush Usable up to SIL2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 5 mm Installation non-flush

More information

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document 1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-nA Edition 08/207 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features Comfort series 50 mm non-flush Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 50 mm Installation non-flush Output polarity NAMUR

More information

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor DSF xx15.xx xhv Ex-Atex Product ID Type # Product # Drawing # DSF 1215.01 SHV Ex-atex (5m) 304Z-05197 113216 DSF 1415.01 AHV Ex-atex S148 304Z-05256 113351 DSF 1615.01 SHV Ex-atex (5m) 304Z-05196 113214

More information

SEPARIX. Technical Documentation. SEPARIX-C/-T and SEPARIX-Control CT. Edition: Version: 5 Art. no.:

SEPARIX. Technical Documentation. SEPARIX-C/-T and SEPARIX-Control CT. Edition: Version: 5 Art. no.: Technical Documentation SEPARIX SEPARIX-C/-T and SEPARIX-Control CT Edition: 2018-05 Version: 5 Art. no.: 207105 FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Tel.: +49 / 40 / 39 82 07-0 Fax: +49

More information

VERSAFLOW VORTEX Supplementary instructions

VERSAFLOW VORTEX Supplementary instructions VERSAFLOW VORTEX Supplementary instructions Vortex flowmeter Equipment category II 2G CONTENTS VERSAFLOW VORTEX 1 Safety instructions 3 1.1 General notes... 3 1.2 EC conformity... 3 1.3 Approval according

More information

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm 0102 Model Number Features 5 mm flush Usable up to SIL 3 acc. to IEC 61508 Application Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs,

More information

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content 8 Appendix 8.1 Wiring examples...4 8.2 Start configuration...4 8.3 Sensor configuration...4 8.4 Actuator configuration...5 Operating instructions.............pages 1 to 6 Original 9 EU Declaration of conformity

More information

ExDetector HC-100. Data Sheet. Gas Measuring and Alarm Systems

ExDetector HC-100. Data Sheet. Gas Measuring and Alarm Systems HC-100 Gas Measuring and Alarm Systems HC-100 Application / Construction The HC100 series of measuring probes, used in conjunction with evaluation systems, have the following functions: Measurement and

More information

Manual Isolating Barrier D461 (Revision 05)

Manual Isolating Barrier D461 (Revision 05) D461 Manual Isolating Barrier D461 (Revision 05) Product Manual Original Instructions valid for models D461.11 with 1x signal input into 1x isolated signal output D461.12 with 1x signal input into 2x isolated

More information

PEPPERL+FUCHS GmbH

PEPPERL+FUCHS GmbH Comfort series 1.5 mm embeddable M8x1 4 25 16 13 LED Switching element function NAMUR NC Rated operating distance s n 1,5 mm Installation embeddable Assured operating distance s a 0... 1,215 mm Reduction

More information

Manual Isolating Barrier D461R1 (Revision 01)

Manual Isolating Barrier D461R1 (Revision 01) D461R1 Manual Isolating Barrier D461R1 (Revision 01) Product Manual Original Instructions valid for models D461R1.11 with 1x signal input into 1x isolated signal output D461R1.12 with 1x signal input into

More information

Technical Data. General specifications. Rated operating distance s n 5 mm

Technical Data. General specifications. Rated operating distance s n 5 mm 0102 Model Number Features 5 mm non-flush Usable up to SIL 2 acc. to IEC 61508 Technical Data specifications Switching function Normally closed (NC) Output type NAMUR Rated operating distance s n 5 mm

More information

Operating instructions

Operating instructions Operating instructions Leak detector LAG-14 ER BRL A part 1 (DIBt) Annex 15.24 Read instructions before using product! Observe all safety information! Keep instructions for future use! 05.2016 0 854.001.0153

More information

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74 AM54 Instruction Bulletin North American Installation Addendum Document Number PN25016 Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

More information

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon INSTRUCTION MANUAL Minialite Intrinsically Safe Round LED This instruction sheet describes installations which conform to EN60079:Part14:2008 Electrical Installation in Hazardous Areas. When designing

More information

IECEx Certificate of Conformity

IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate No. : Status: Date of Issue: Applicant:

More information

Labkotec SET. Labkotec separator alarm system protecting our environment. Measure your success

Labkotec SET. Labkotec separator alarm system protecting our environment. Measure your success Labkotec SET Labkotec separator alarm system protecting our environment Designed to comply EN858-1&2 and PPG3 norms Warns of excessive levels of oil, sludge & liquids Prevents pollution incidents Fail-safe

More information

Alarm system For oil-water separator

Alarm system For oil-water separator INSTRUCTIONS MANUAL Alarm system For oil-water separator Safety precautions Fitting, wiring, initial start-up and maintenance operations must be done by trained technicians. All European and local rules

More information

4) Intrinsic Safety Certification

4) Intrinsic Safety Certification INSTRUCTION MANUAL Minialert Intrinsically Safe Round Combined Unit Section Volume Control Tone Generator S2 S3 Tone Selection Switches Fig 1 Simplified block diagram The combined unit is CE marked for

More information

PROZESSAUTOMATION. Manual SEGMENT PROTECTOR R-SP-!12. Zone 1 Zone 2 / Div 2 FNICO

PROZESSAUTOMATION. Manual SEGMENT PROTECTOR R-SP-!12. Zone 1 Zone 2 / Div 2 FNICO PROZESSAUTOMATION Manual SEGMENT PROTECTOR R-SP-!12 FieldConnex TM Segment Protectors with overloaod protection and short-circuit current limitation for the connection of 12 field devices Zone 1 Zone 2

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 15 mm non-flush Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 15 mm Installation non-flush Assured operating distance s a 0...

More information

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI100EN 09/2017

More information

DSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor

DSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor Product ID Type # Product # Drawing # DSF 1210.00 SHV Ex-atex (2m) 374Z-05066 110428F1 DSF 1210.00 SHV Ex-atex (5m) 374Z-05176 110428F1 DSF 1210.00 SHV Ex-atex (10m) 374Z-05590 110428F1 DSF 1410.00 SHV

More information

Rosemount 3490 Series 4 20 ma + HART Compatible Controller

Rosemount 3490 Series 4 20 ma + HART Compatible Controller 00825-0200-4841, Rev AB Rosemount 3490 Series 4 20 ma + HART Compatible Controller Failure to follow safe installation guidelines could result in death or serious injury The Rosemount 3490 Series Control

More information

Installation and Operating Instruction

Installation and Operating Instruction Installation and Operating Instruction Automatic Fire Detectors Series 900 Ex (i) 9893 0.00 GB Technical changes reserved! 0 Installation and Operating Instruction Automatic Fire Detectors Series 900 Ex

More information

Operating Manual MS220DA

Operating Manual MS220DA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN

More information

Flameproof Manual Call Points

Flameproof Manual Call Points Operating instructions Additional languages www.r-stahl.com CS & Clifford & Snell Contents General Information.... Manufacturer.... Information regarding the operating instructions.... Further documents....

More information

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI200EN 09/2017

More information

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI500EN 09/2017

More information

Universal Tank Alarm Type Installation, Operation & Maintenance

Universal Tank Alarm Type Installation, Operation & Maintenance Universal Tank Alarm Type 14400 Installation, Operation & Maintenance Universal Tank Alarm Type 14400 Contents Declaration of Conformity 3 IMPORTANT 3 General Description 4 General Operation 4 Installation

More information

Manual Power relay SR853

Manual Power relay SR853 Manual Power relay SR853 Product types SR853.8.x.x, Rev. 1 SR853 manual page2 The symbols WARNING, CAUTION, NOTE This symbol warns of a serious hazard. Failure to observe this warning may result in death

More information

2CKA001473B System Manual Busch-Infoline. Handicapped toilet signal set 1510 UC

2CKA001473B System Manual Busch-Infoline. Handicapped toilet signal set 1510 UC 2CKA001473B9007 19.05.2017 System Manual Busch-Infoline Handicapped toilet signal set 1510 UC-... -101 Table of contents Table of contents 1 Notes on the instruction manual... 3 2 Safety... 4 2.1 Information

More information

Intrinsically Safe Solutions

Intrinsically Safe Solutions Intrinsically Safe Solutions INSTALLATION MANUAL 04/12/14 Rev D DOC-01-029 Documentation Feedback Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions

More information

Operating Instructions Edition 02/2007

Operating Instructions Edition 02/2007 Operating Instructions Edition 02/2007 Temperature Transmitter 7NG3214 with PROFIBUS PA 7NG3215 with FOUNDATION Fieldbus sitrans Introduction 1 General safety notes 2 SITRANS T Temperature transmitter

More information

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d. Additional Operating Instructions SITRANS F Vortex flowmeters Ex-d Edition 09/208 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4

More information

Operating Instructions

Operating Instructions Operating Instructions MSi-JM0100-USB R. STAHL HMI Systems GmbH Adolf-Grimme-Allee 8 D 50829 Köln Operating Instructions Version: 01.00.03 Issue date: 29.06.2017 Disclaimer Disclaimer Publisher and copyright

More information

EU DECLARATION OF CONFORMITY

EU DECLARATION OF CONFORMITY The Low Voltage Directive (LVD) 2014/35/EU and Electromagnetic Compatibility (EMC) Directive 2014/30/EU. Capacitive level sensor DLS 27N(T) Capacitive level sensor type DLS 27N(T) is designed to bistable

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

Inspection Light LED 6149/2. Operating instructions EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN

Inspection Light LED 6149/2. Operating instructions EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Inspection Light LED Operating instructions Additional languages www.stahl-ex.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information regarding the operating instructions...3 1.3 Conformity

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications Force Pressure Temperature Switch Pressure sensors Ex ia I / IIC T6 acc. to ATEX with internal diaphragm with front flush diaphragm Accuracy: 0,25% and 0,5 % Standard output: 4...20 ma; 2-wire system Description

More information

User s Manual YTA610 and YTA710 NEPSI Certification

User s Manual YTA610 and YTA710 NEPSI Certification User s Manual YTA60 and YTA70 NEPSI Certification [Option code: /NS, /NS5 and /NF] st Edition . INTRODUCTION Thank you for purchasing the YTA60 and YTA70 Temperature transmitters. This manual contains

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm 0102 Model Number Features Direct mounting on standard actuators EC-Type Examination Certificate TÜV99 ATEX 1479X Accessories BT32 BT32XS BT32XAS BT33 BT34 V1-G-N4-5M-PUR Female cordset, M12, 4-pin, NAMUR,

More information

Tank Gauging System Special Safety Instruction

Tank Gauging System Special Safety Instruction Tank Gauging System www.rosemount-tg.com Rosemount TankRadar REX Table of Contents Contents SPECIAL SAFETY INSTRUCTION........................ 1-1 1. GENERAL REQUIREMENTS....................... 1-2 1.1

More information

Technical Data. General specifications Switching element function Rated operating distance s n 8 mm

Technical Data. General specifications Switching element function Rated operating distance s n 8 mm 0102 Model Number Features 8 mm non-flush Usable up to SIL 3 acc. to IEC 61508 Application Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs,

More information

INSTRUCTION MANUAL. SIL 3 - SIL 2 IIB Group Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001C PSD1001C

INSTRUCTION MANUAL. SIL 3 - SIL 2 IIB Group Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001C PSD1001C PSD1001C INSTRUCTION MANUAL SIL 3 SIL 2 IIB Group Power Supply for Hazardous Area Equipment DINRail Model PSD1001C PSD1001C SIL 3 SIL 2 IIB Group Power Supply for hazardous Area Equipment ISM006510 General

More information

Labkotec automatic warning devices for separators protecting the environment

Labkotec automatic warning devices for separators protecting the environment Labkotec automatic warning devices for separators protecting the environment ENG Labkotec SET warning devices SolarSET S warning systems OMS-1 warning device for light liquid separators GA-1 and GA-2 warning

More information

Safety instructions VEGAPULS 64

Safety instructions VEGAPULS 64 Safety instructions Intrinsic safety "i" 4 20 ma/hart - two-wire Document ID: 53001 Contents 1 Area of applicability... 3 2 Important specification in the type code... 3 3 Different ignition protection

More information

Test Unit GTL 100 for Fire Detectors

Test Unit GTL 100 for Fire Detectors Test Unit GTL 100 for Fire Detectors Description and Operation Manual Zertifiziertes QM System Nach DIN EN ISO 9001 Description and Operation Manual Table of Contents 1. Instructions 1.1 General 1.2 Standards

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL Contents IMPORTANT... 3 General Description... 4 General Operation... 4 Changing Factory Settings... 4 Alarm Type... 4 Check Interval...

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200

Installation instructions and operating manual. Sauna control system FCU1000 / FCU1200 Series FCU1x00 Installation instructions and operating manual Sauna control system FCU1000 / FCU1200 only sauna FCU1000 additional humidity FCU1200 Doc-ID: B_M_FCU1xxx-A5_EN Version: V 1.06 certificated

More information

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR 7 783 DETACTOGYR Flame Safeguard The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil or gas burners or

More information

14300 MAINS SEPARATOR ALARM MANUAL

14300 MAINS SEPARATOR ALARM MANUAL Conder Environmental Solutions 14300 MAINS SEPARATOR ALARM MANUAL Separator and Alarm provided by: Alarm Installation, Commissioning & Servicing Support Please contact: www.envirotank.com.au www.envirotank.co.nz

More information

Connection. e. g. Pt100. reference limit. yellow Output I. Composition

Connection. e. g. Pt100. reference limit. yellow Output I. Composition Trip amplifiers for Pt1, Ni1 KFD2GREx1 Connection e. g. Pt1 Input EEx ia IIC 1+ 2 3 Hazardous area 1channel Input EEx ia IIC 2 switching points operate on 2 output relays High/low alarm can be selected

More information

YTA Series Temperature Transmitters [Style: S3] EN :2006, -11:2007, -26:2007. Supply circuit: Ui=30 V, Ii=165 ma,

YTA Series Temperature Transmitters [Style: S3] EN :2006, -11:2007, -26:2007. Supply circuit: Ui=30 V, Ii=165 ma, User s Manual YTA Series Temperature Transmitters [Style: S3] Manual Change No. 10-008 Please use the attached sheets in the following manuals when the product is with /KU2 option and EN60000 Series based

More information

OPTISENS TUR 2000 Technical Datasheet

OPTISENS TUR 2000 Technical Datasheet OPTISENS TUR 2000 Technical Datasheet Sensor for turbidity measurement in water and wastewater Rugged design for harsh applications Integrated transmitter with direct 4...20 ma output Near infrared light

More information

INSTALLATION GUIDE. AXIS A1001 Network Door Controller

INSTALLATION GUIDE. AXIS A1001 Network Door Controller INSTALLATION GUIDE AXIS A1001 Network Door Controller Liability Every care has been taken in the preparation of this document. Please inform your local Axis office of any inaccuracies or omissions. Axis

More information

RT FLOW RATE TOTALISER

RT FLOW RATE TOTALISER Universal Mount Series RT FLOW RATE TOTALISER I N S T R U C T I O N M A N U A L S U P P L E M E N T for I N T R I N S I C A L L Y S A F E F L O W R A T E T O T A L I S E R ATEX & IECEx approvals The name

More information

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - USER GUIDE DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER - II CONTENTS 1. SYMBOLS AND WARNINGS... 5 2. GENERAL INFORMATION... 6 3. WARNINGS... 7 4. GENERAL DESCRIPTION... 8 5. INSTALLATION...

More information

Physikalisch-Technische Bundesanstalt

Physikalisch-Technische Bundesanstalt (1) EC-TYPE-EXAMINATION CERTIFICATE (Translation) (2) Equipment and Protective Systems intended for Use in Potentially Explosive Atmospheres Directive 94/9/EG (3) EC-type-examination Certificate Number:

More information

Hazardous Area Zirconia Oxygen Systems

Hazardous Area Zirconia Oxygen Systems Operating Instructions IM/EXGP-INT_7 Hazardous Area Zirconia Oxygen Systems Interface Electronics Unit ABB The Company We are an established world force in the design and manufacture of instrumentation

More information

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products 7 418 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of small to medium capacity (without fan) in intermittent operation. The LGA... and this

More information