TrueAlarm Addressable Fire Alarm Control Panels

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "TrueAlarm Addressable Fire Alarm Control Panels"

Transcription

1 FIRE FIRE SUPERVISORY PREVIOUS MENU NEXT SUPV SUPERVISORY PREVIOUS MENU NEXT SUPV SILENCED SILENCE DISABLE ENABLE FUNCTION EXIT CLEAR ENTER SILENCED SILENCE DISABLE ENABLE FUNCTION EXIT CLEAR ENTER AC POWER RESET AC POWER RESET GHI ABC JKL DEF MNO PQRS TUV WXYZ GHI ABC JKL DEF MNO PQRS TUV WXYZ DISCONNECT BATTERY AND A. C. POWER DISCONNECT BATTERY AND A. C. POWER TrueAlarm Addressable Fire Alarm Control Panels UL, ULC Listed; FM, CSFM, Model 4008 Fire Alarm Control Panel for IDNet Addressable and MEA (NYC) Approved* Devices and TrueAlarm Addressable Smoke Detection Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient panel status information Operation is programmable using a multi-function keypad and the panel LCD or via service computer (PC) RS-232 service port provides upload/download PC access for panel configuration and event history logs Software updates are via PC download Convenient library of standard custom label terms Standard on-board DACT provides: Contact ID, 3/1, 4/2, BFSK, and SIA formats WALKTEST silent or audible system test** Voltage and current for both the battery charger and the battery can be displayed at the front panel LCD Addressable Devices: Using IDNet communications, up to 200 addressable TrueAlarm detection points or addressable device points are available (see page 3 for details)** Two Standard Notification Appliance Circuits (NACs): Class A or Class B outputs with solid state overcurrent protection per NAC, each rated for 2 A Selectable for Simplex SmartSync two-wire horn/strobe control or synchronized strobe control** Standard Power Supply: Provides 3 A nominal 24 DC Automatic input power selection operates with 120 VAC or 240 VAC, 50 or 60 Hz On-board temperature compensated battery charger for up to 12.7 Ah batteries in cabinet (UL and ULC) and up to 25 Ah batteries in separate cabinet (UL only) Additional standard features: Two auxiliary relays NACs, Relay outputs, and communications circuits are power limited per NFPA 72 (AC input, battery circuits, and City Circuit Module outputs are non-power limited) UL listed to Standard UL 864, 9th Edition Available option modules: Door mounted 24 LED annunciator (standard on ULC model) 3 A Expansion Power Supply with two on-board 2 A NACs that operate the same as standard NACs City Interface Module and Auxiliary Relay Module Remote LCD and LED/Switch Annunciators Standard Control Panel Fire Alarm Annunciator Control Panel with 24 LED Annunciator (required for ULC applications) Description For areas requiring up to 200 addressable input devices and up to 4 NACs, the Simplex 4008 Series fire alarm control panels provide flexible initiating circuit monitoring, extensive programmable control capability, and LCD annunciated circuit-specific 20 character custom labels. * See page 2 for additional ULC and MEA information. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section of the California Health and Safety Code. See CSFM Listing :318 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Additional listings may be applicable, contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. ** TrueAlarm analog smoke detection is protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683; 5,543,777. IDNet addressable communications are protected by U.S. Patent No. 4,796,025. IDNet duplicate device detection is protected under U.S. Patent No. 6,034,601. WALKTEST system test is protected under US Patent No. 4,725,818. SmartSync horn/strobe operation is protected under U.S. Patent No. 6,281,789. Two-wire synchronization circuit operation is protected by U.S. patent No. 5,559, CAUTION BEFORE SERVICING CAUTION BEFORE SERVICING S /2005

2 Standard Feature Details Addressable operation is provided by an IDNet signaling line circuit (SLC) capable of communicating to up to 200 addressable devices (points). Addressable devices include: TrueAlarm smoke detection, heat detection, and duct detection; supervised addressable modules for single and multiple contact monitoring, manual stations, isolation modules, and a remote signal module (see list on page 4.) (Please note that this panel provides a limited TrueAlarm operation feature set. For larger applications that require the full complement of TrueAlarm features, contact your local Simplex product supplier.) Two, 2 A On-Board NACs provide conventional reverse polarity operation, selectable as Class A or Class B, with electronic control and overcurrent protection. Operation is selectable for synchronized strobe or SmartSync horn/strobe two wire operation. Horn control can be selected at the panel for: Temporal pattern coding, Steady On, Slow March Time (20 beats per minute), or Fast March Time (120 beats per minute). Note: When selected for SmartSync horn/strobe control, March Time produces 60 beats per minute. The 24 VDC Auxiliary output provides up to 500 ma for system use. (Auxiliary output current is counted for total power supply capacity.) Standard Auxiliary Relay Outputs. Two relay outputs are available, selectable as normally open or normally closed, rated 2 30 VDC per below: Aux Relay 1 is normally assigned to General Alarm operation but is programmable (see page 7) Aux Relay 2 (Trouble) is energized when Normal and is de-energized with a Trouble condition. Product Selection Standard Feature Details (Continued) On-Board Dual Line DACT. Operation can be selected for Contact ID, SIA, 3/1, 4/2, and BFSK formats. Reporting includes Alarm, Supervisory, Trouble, and AC Failure. Operation includes automatic 24 hour test and programmable power fail report delay. Power Supply and Battery Charger. DC power output is 3 24 VDC for panel use. The temperature compensated battery charger (sealed lead-acid batteries only) is rated for up to 25 Ah batteries per UL 864 and up to 12.7 Ah per ULC-S527. (Up to 12.7 Ah batteries fit in the cabinet, larger batteries require an external cabinet.) Panel electronics can measure and display voltage and current for the power supply, batteries and the battery charger (standard and expansion power supply). Depleted battery trouble is monitored and annunciated and depleted battery cutout can be selected. Active battery status monitor supervises charger operation. Optional Feature Details Expansion Power Supply. Provides 3 A 24 VDC, two additional 2 A NACs, and an additional auxiliary power output of 500 ma. Output operation is the same as on the standard power supply. Expansion Relay Module. Provides three relays, one each for Alarm, Supervisory, and Trouble conditions. Each is jumper selectable as N.O. or N.C. Contacts are rated 2 30 VDC. Location is the same as for the City Circuit Modules. City Circuit Modules. These modules are available with or without on-board disconnect switches, depending on local requirements (either type can be disconnected through the front panel under password control). Connections are for Remote Station (reverse polarity) or Municipal Master (local energy). Reporting includes Alarm, Supervisory, and Trouble. Control Panel Model Description Listings Box Depth Standard Features Standard fire alarm control panel MEA 4-1/4 (108 mm) Fire alarm control panel with LED Annunciator on front door Option Modules Model Description UL, FM, & CSFM ULC 4-5/8 (117 mm) Red cabinet; SLC with 200 addressable points, 2 Class B/Class A NACs, 3 A power supply with battery charger; on-board DACT; for input voltage of 120/240 VAC, 50/60 Hz (autoselect) Expansion Power Supply; 3 A, with 2 NACs, 120/240 VAC, 50/60 Hz Select one if required Expansion Relay Module; 3 relays selectable as either N.O. or N. C * City Circuit Modules with disconnect switch Select one if required * City Circuit Modules without disconnect switch * These City Circuit modules are also used on the 4006 Series control panels. Accessories Model Description Red Semi-Flush Trim; 1-7/16 wide (37 mm) Beige External Battery Cabinet for up to 25 Ah batteries; mounts close-nippled to control panel cabinet; dimensions = 16-1/4 W x 13-1/2 H x 5-3/4 D (413 mm x 343 mm x 146 mm) [depth increased for 25 Ah effective 7/2005] Batteries, 12 Volt (select one battery model per system standby requirements; order quantity of two) Model Size Model Size Location Model Size Location Ah Ah Ah Requires External Battery For cabinet mount Ah Ah Cabinet (UL listed only) 2 S /2005

3 TrueAlarm Smoke Detection TrueAlarm Addressable Detection. IDNet addressable device compatibility includes Simplex TrueAlarm photoelectric smoke and temperature sensors. The 4008 fire alarm control panel provides a subset of the complete analog TrueAlarm features. TrueAlarm sensors appear to the panel essentially as addressable detectors and that term is used for 4008 documentation. Approximately every four seconds the addressable smoke detectors transmit an output value based on their smoke chamber condition. The panel CPU internally maintains a current value, peak value, and an average value for each detector s output. Status is determined by comparing the current value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity. Alarm Determination. Photoelectric detection sensitivity is 2.5%/ft obscuration. All detectors can be selected for a reduced sensitivity detection mode that satisfies the city of Boston requirements. Addressable heat detectors provide a fixed temperature alarm at 135 F (57 C) and may be individually selected to also provide rate-of-rise alarm of 15 F (8.3 C) per minute where applicable. Diagnostics and Default Device Type Status Monitoring TrueAlarm operation provides the ability to automatically indicate when an addressable detector is dirty or excessively dirty. The NFPA 72 (National Fire Alarm Code) requirement for a test of the sensitivity range of the detectors is fulfilled by the TrueAlarm ability to maintain the sensitivity level of each addressable detector. Modular Addressable Detector/Base Combination. Modular TrueAlarm addressable detectors use the same base which allows different detector head types (photoelectric smoke, or heat) to be easily interchanged to meet specific application requirements. This feature also allows intentional detector (sensor head) substitution during building construction. When conditions are temporarily dusty, instead of covering the smoke detectors (causing them to be disabled), heat detector heads may be installed without reprogramming the control panel. Although the control panel will indicate an incorrect detector type, the heat detector will operate at a default setting to provide heat detection for building protection at that location. Keyboard Reference FIVE STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset 2 X 20 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions, provides up to 20 characters for custom label information FIRST DISPLAY: Operation can be selected for maintained display of first alarm until acknowledged THREE PROGRAMMABLE LEDs provide custom labeling (labels insert into a pocket), the top two LEDs are selectable as red or yellow, the bottom LED is selectable as green or yellow CONTROL PANEL VIEW with door closed FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET RESET restores control panel to normal when all alarmed inputs are returned to normal acknowledges a Fire Alarm condition, logs the acknowledge, silences the operator panel and all annunciator tone-alerts, and steps through the active Alarm list SUPV acknowledges system supervisory conditions, logs the acknowledge, silences the operator panel and all annunciator tone-alerts, and steps through the active Supervisory list FIVE NAVIGATION KEYS: MENU selects the on-screen programming menu; left and right arrows moves the position on the screen, and PREVIOUS and NEXT navigate screen selections PREVIOUS MENU NEXT acknowledges system troubles, logs the acknowledge, silences the operator panel and all annunciator tone-alerts, and steps through the active Trouble list DISABLE ENABLE FUNCTION EXIT CLEAR ENTER 1 GHI 4 PQRS 7 ABC 2 JKL 5 TUV 8 0 DEF 3 MNO 6 WXYZ 9 ALPHANUMERIC KEYPAD provides programming entry of numbers and letters SILENCE causes audible notification appliances to be silenced, used after evacuation is complete and while alarm source is being investigated FOUR EXTENDED FUNCTION KEYS: ENTER confirms selections, EXIT/CLEAR backs out of the present screen menu and clears information that has not been entered, FUNCTION enables the active function menu, DISABLE/ENABLE toggles the function or circuit status as appropriate per the selected screen 3 S /2005

4 Compatible Simplex Peripherals (see specifications on page 5 for notification appliances) Detector Heads and Addressable Bases (refer to page 3 for 4008 detector/sensor terminology) Model Detector Head Type Compatible Addressable Base Data Sheet , Standard detector base , Base for remote LED or relay S Photoelectric , Features of and remote supervised relay Heat, 135 F (57 C) , Sounder base S , IDNet Isolator base S Photo and Heat Duct Detection , Dual address sounder base , Dual address standard base NOTE: These bases require two addresses S Model Description Data Sheet Addressable Duct Detector Housing with detector, no relay control S Addressable Duct Detector Housing with detector, with remote relay control Addressable Devices Model and Description Data Sheet Model and Description Data Sheet Model and Description Data Sheet Supervised IAM CL B ZAM Signal IAM S S S Supervised IAM CL A ZAM , , & Manual S Relay IAM S IDNet Isolator S Stations Compatible System Expansion Panels Model Type Description Data Sheet 4003 Series Voice Control Panel Provides a remote voice control panel with on-board NACs, internal microphone, and remote microphone input S Series Remote NAC Extender Provides remote NACs; includes power supply and battery charger; 4 extenders max/nac; 4008 uses NAC output to provide control S Note: Contact your local Simplex Product Supplier for additional compatible peripherals. Remote Annunciator Options The 4008 supports up to four annunciator options including: Door Mounted 24 LED Annunciator Remote LED/Switch Annunciators Remote LCD Annunciators Annunciators communicate at a rate of 9600 baud with power supplied by separate wiring LED Annunciator Features: 16 LEDs with programmable functions and dedicated LEDs for Alarm Silenced, Lost Communications, Trouble, and Power-on Keyswitch access controlled switches for nowledge, Alarm Silence, Reset, and Lamp Test Local tone-alert LCD Annunciator Features: LCD readout with two lines of 40 characters each and LED backlighting Wide viewing angle, super-twist design Keyswitch access controlled Control switches and status LEDs for: Alarm, supervisory, or trouble acknowledge Alarm silence and System Reset Three programmable LED indicators: Two LEDs are selectable as red or yellow One LED is selectable as green or yellow With provisions for custom labeling Fire Alarm Annunciator SILENCE SILENCED CONTROL ENABLE LOST COM RESET LAMP TEST FIRE SUPERVISORY SILENCED POWER ON CONTROL ENABLE POWER SUPV SILENCE RESET LED/Switch Annunciator LCD Annunciator 4 S /2005

5 Specifications (Refer to Installation Instructions for additional information) AC Input Input Voltage Input Current, Standard Input Current with Expansion Power Supply 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select 2 A 120 VAC input; 1.5 A 240 VAC input 4 A 120 VAC input; 3 A 240 VAC input Power Supply Output 3 A 24 VDC in alarm Battery Charger Temperature compensated charger is rated for up to 25 Ah per UL 864; up to 12.7 Ah per ULC-S527 Notification Appliance Circuits (NACs) (NOTE: Total DC current = 3 A maximum per power supply) General Rating Special Application Rating = 2 A per NAC Strobe synchronization is UL listed across all four system NACs for these 4906 Series appliances Regulated 24 VDC Rating = 1.5 A per NAC NOTE: Maximum strobe load on main power supply or expansion power supply is 1.35 A per power supply (2.7 A total); remainder of power supply rating is available for other loading 2 A 24 VDC, per NAC; available as Class A or Class B; Class B end-of-line resistor = 10 k, 1/2 W; Model (P/N ) Simplex 4901 Series (horns) and the following 4906 Series Multi-Candela: strobes, horn/strobes, and speaker/strobes (see data sheets S , S , & S ) All other UL Listed Notification Appliances; use associated external synchronization modules where required Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum per power supply) Auxiliary Power Output 500 ma 24 VDC Standard Auxiliary Relay Outputs Relay 1 Programmable operation Contacts rated 2 30 VDC, 0.35 power factor; Relay 2 Trouble operation jumper selectable as N.O. or N.C. Wiring Connections Terminals rated for 18 AWG to 12 AWG (0.82 mm 2 to 3.31 mm 2 ) IDNet Communications Quantity Up to 200 addressable devices (see list on page 4) Suppression For wiring external to building, use Overvoltage Protector at each end of the connection; refer to data sheet S for details Wire Size 18 AWG (0.82 mm 2 ) Wire Types Unshielded twisted pair (UTP) Shielded twisted pair (STP) Distance from Control Panel to Farthest Device Acceptable for most applications; not for use with wiring in conduit with either NAC or AC power wiring (or similar) Shielded wire may provide protection from unexpected sources of interference and may be required for some applications; review system with your local Simplex product supplier Up to 4000 feet (1219 m) with 125 devices; 32 Up to 2500 feet (762 m) with 200 devices; 51 Total Wire Length Allowed With T Taps for Class B Wiring Up to 10,000 ft (3 km) Total Capacitance Allowed 0.6 µf (600 nf) Annunciator Communications Quantity Supported Up to four annunciator modules per panel (see page 4 for details) Wiring Size and Type See description for IDNet wiring above Wiring Distances Bus-Style Wiring Up to 4000 ft (1219 m); 0.58 µf (580 nf) maximum capacitance; 35 max. T-Tap Wiring Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device Line Matching Resistor Bus-Style Wiring Connect one at panel 100, 1/2 W; ; T-Tap Wiring Connect one at panel and one at end of line (part number ) Suppression Use Overvoltage Protectors where wiring leaves and enters a building (refer to data sheet S ) Option Module Ratings Expansion Relay Contact Ratings 2 30 VDC, 0.35 power factor; jumper selectable as N.O. or N.C. Module Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm 2 to 3.31 mm 2 ) Environmental Ratings Operating Temperature Range 32 to 120 F (0 to 49 C) Operating Humidity Range Up to 93% RH, F (38 C) maximum 5 S /2005

6 Supervisory and Alarm Currents Model Module Supervisory Alarm Standard fire alarm control panel with 50 IDNet devices 175 ma 200 ma Control panel with 24 LED Annunciator 193 ma + 1 ma per IDNet device 250 ma+ 1 ma per IDNet device Expansion Power Supply 50 ma 60 ma Expansion Relay Module 10 ma per energized relay 10 ma per energized relay City Circuit Module with disconnect switch 30 ma 60 ma City Circuit Module without disconnect switch Remote LCD Annunciator (see data sheet S ) Remote LED/Switch Annunciator (see data sheet S ) 30 ma 60 ma 100 ma 150 ma 40 ma 70 ma (all LEDs and tone-alert on) ** Current Calculation Information: 1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads. 2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads and all auxiliary loads. Addressable Device Information The following addressable device types and hardware point types are provided. A combination of autoprogram, and either front panel or PC programming allows the operation to be selected per application. Available Fire Detection Device Types Device Description Options Photoelectric Addressable Detector Heat Detector TrueAlarm operation with sensitivity = 2.5%/ft Fixed temperature thermal detection at 135 F (57.2 C) Sounder base (selectable for single station operation) With relay output Sounder base (selectable for single station operation) With relay output With communications isolator Selectable for all detectors to be at city of Boston sensitivity of 3.7%/ft With communications isolator Individually selectable to add rate-of-rise heat detection of 15 F/minute (8.3 C/minute) Addressable Hardware Point Types Function Type Description Function Type Description FIRE Fire monitor device WSO Combination waterflow and water supervisory device WATER Waterflow monitor device SUPV Supervisory monitor HEAT Heat detector device UTIL Supervised utility monitor DUCT Duct detector device Trouble monitor PULL Manual (pull) station device VSMOKE Verified fire alarm; an alarm level causes the alarm verification cycle to start SMOKE Smoke detector device STYLEC Style C fire monitor SO Sprinkler Supervisory LATSUPV Latching supervisory monitor (supervisory latches until system is reset) 6 S /2005

7 Relay Operation Modes The following relay operations are selectable from either the front panel or the PC programmer. Common Fire Alarm Operations Function Type Relay Activates Upon Relay Deactivates Upon SRELAY General Alarm Silence RRELAY General Alarm Reset SUPV Supervisory condition Clear TRBL Trouble condition nowledged Special Functions Function Type UTILITY PRIMARY ALTERN DRESET DHOLDER Description Utility input in the same alarm group activates General alarm; relay is tied to Primary Elevator Recall contacts General alarm; relay is tied to Alternate Elevator Recall contacts Relay provides 24 VDC power to 4-wire addressable detectors; relay turns off for 5 seconds on System Reset Relay provides 24 VDC to larger door holder relay with separate power source; relay activates on general alarm to remove power to door holder relay and close doors Additional Programming Feature Details Function Custom labels Message Library History logs Autoprogram Alarm Groups WALKTEST Manual Control Passcode Protection (4-digit number) Details Up to 20 characters per point; a built-in message library provides for commonly used words for easy front panel programming For front panel label creation convenience, the following words can be selected as part of a custom label ( _designates a built-in space; typing the first letter of a word/number will select the closest word in alphabetical/numerical sequence) North South East West Front Center rear 5th Flr_1 Flr_2 Flr_3 Flr_4 Flr_5 RM_ Basement Floor Garage Hallway HVAC_Room Kitchen Lobby Office Patient upper lower main first 2nd 3rd 4th Boiler_RM Classroom Closet_ Corridor Elect_RM Elevator Entrance Restroom Room Stairway Storeroom Wing Zone Three separate logs: Alarm (100 entries), Supervisory (100 entries), and Trouble (300 entries); logs can be queried separately, or as a combined log; logs can be downloaded for printing or archiving using the RS-232 service port Automatically scans system for installed option modules and configures panel programming accordingly; modes are available to detect new modules only, recreate default programming and then add all modules found; Scans of addressable loop adds addressable devices, displays total added; checks for duplicate addresses and identifies errors Up to 99 alarm groups are available, any point may be in up to 3 alarm groups; this allows NAC and relay operation to be associated with inputs according to local response requirements Allows one person to perform system testing; alarm or trouble tests are followed by automatic reset; the alarm zone is sounded out by associated audible notification or the response is silently logged into the Alarm log Allows selection of individual relays or NACs for system testing Level 1 = nowledge, Silence, System Reset, View logs, View point information, and Lamp Test Level 2 = All Level 1 + Set Time/Date, Point Control, Enable/Disable points Level 3 = All Level 2 + Clear logs, Clear verification tallies, Custom label editing, and WALKTEST Level 4 = All Level 3 + Programming, Upload/Download; this is the Service access level 7 S /2005

8 FIRE SUPERVISORY PREVIOUS MENU NEXT SUPV SILENCED SILENCE DISABLE ENABLE FUNCTION EXIT CLEAR ENTER AC POWER RESET Installation and Module Placement Reference Knockouts are located on top and sides Main board Box width 15-5/8" (397 mm) 11-1/4" (286 mm) (Top and side views are shown with door installed) Box depth = 4-1/4" (108 mm) standard 4-5/8" (117 mm) w/annunciator door Door thickness 5/8" (16 mm) 13-1/2" (343 mm) Display Assembly ABC DEF GHI JKL MNO PQRS TUV WXYZ Expansion Power Supply* 16" (406 mm) Main board AC Input Terminals Battery Area No conduit or wiring in this area City Module* or Expansion Relay Module* 13-1/4" (337 mm) * Indicates optional modules NOTE: For semi-flush mounting, cabinet must extend 1-1/2" (38 mm) minimum from wall surface Door LED Annunciator Details YELLOW LED RED LED 14 CUSTOM LABEL AREAS are available, typically for location identification and NAC annunciation (shown labeled for reference, blank labels are provided); dual LED locations have a Red LED (top) and a Yellow LED (bottom); labels insert into pockets behind the overlay; LED operation is programmable to track other monitored status conditions Fire Alarm Annunciator AREA 1 AREA 5 AREA 2 AREA 3 AREA 4 AREA 6 AREA 7 AREA 8 AREA 9 AREA 10 NAC 1 NAC 2 NAC 3 NAC 4 FOUR YELLOW LEDs provide default NAC Trouble annunciation (shown labeled as NAC 1-4) Tyco, Simplex, the Simplex logo, TrueAlarm, IDNet, WALKTEST, and SmartSync are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA). Tyco Safety Products Westminster Westminster, MA USA S / Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

9 Features TrueAlarm Fire Alarm Controls UL, ULC Listed; FM, CSFM, Model 4010 Fire Alarm Control Panel for TrueAlarm and MEA (NYC) Approved* Analog Sensors and IDNet Addressable Devices Standard features include: Up to 250 addressable TrueAlarm sensor or addressable device points using IDNet communications that operate with either shielded or unshielded twisted pair wiring** Four, 2 A notification appliance circuits (NACs) with solid state current protection Internal event reporting DACT module (standard on models , , & ) UL listed to Standard 864 Installation convenience features: Power-limited design with electronic modules contained on one-piece chassis Up-front terminal blocks for wiring access Compact NEMA 1 rated cabinet is available in beige or red and can be pre-shipped for early installation Setup, programming, and maintenance features: Device level ground fault search, locate and isolate Auto Program for general alarm operation TrueAlarm individual analog sensing with front panel information and selection access Dirty TrueAlarm sensor maintenance alerts, service and status reports including almost dirty Default TrueAlarm sensor device type operation Duplicate address error detection Front panel or PC programming TrueAlarm sensor peak value performance report WALKTEST silent or audible system test Software verification simulation mode Supports the following IDNet devices: Addressable manual stations Quad-state zone adapter modules (ZAMs) for initiating device monitoring IDNet ground fault/short circuit isolator base for TrueAlarm sensors Quad-state line powered individual addressable modules (IAMs) for initiating device monitoring and relay control Available option modules include: Door mounted 24 LED annunciator (std. on ULC models) Network, or Point Reporting DACT Class A NAC adapter module RS-232 ports for printer and maintenance PC Additional power supply; Auxiliary Relay Module or City Interface Equipment for Suppression Release Applications (refer to data sheet S ) Compatible with Simplex auxiliary panels: TrueAlert Addressable Controllers and NAC power extenders (IDNet controlled and conventional) 4003 Voice Control Panel 4081 Battery Cabinet with charger for 50 Ah batteries 4010 Fire Alarm Control Panel (with standard door) Description TrueAlarm fire alarm control panels have the ability to provide location accuracy for monitoring and control. When equipped with TrueAlarm analog sensing for smoke and heat detection, the processing power of the control panel also has the ability to analyze conditions at each location to provide accurate detection with significantly reduced maintenance costs. The 4010 TrueAlarm Fire Alarm Control Panel has been specifically designed to provide addressable operation and analog detection in a cost-effective package for application sizes that previously were considered only appropriate for conventional zoned monitoring. Installation and Service Ease. The 4010 mounts on a single chassis for quick installation and removal. Terminal blocks are large and up-front for easy access and inspection. Optional modules are easily and quickly installed and programmed as required. The 4010 cabinet provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting. Smooth cabinet surfaces are provided for locally cutting conduit entrance holes exactly where required cabinets and electronics can be ordered separately, allowing early cabinet installation. Ground Fault Assistance. Ground fault problems often occur during installation. The 4010 provides isolating circuitry and software-controlled sequencing to isolate ground faults to specific identified locations. This assistance helps the installer to accurately locate the wiring problem for quicker repair. * Refer to page 6 for listing details. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section of the California Health and Safety Code. See CSFM Listing :226 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use City of New York Department of Buildings MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. ** TrueAlarm analog smoke detection and IDNet addressable devices are protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683; 5,543,777; 5,400,014; 5,552,765; 5,552,763; DES. 377,460. WALKTEST system test is protected under U.S. patent # 4,725,818. S /2004

10 4010 Operator Control Summary Extensive Feature List. The 4010 Fire Alarm Control Panel provides access to an extensive feature list that includes: Providing easy and powerful operator information with a logical, menu-driven display Extensive and automatic diagnostics for maintenance reduction History Logs available from the LCD or capable of (optionally) being printed Software Verification, allowing detailed logic programming simulation to be conducted without activating connected outputs Control Panel (or service PC) label editing Password access control Auto Program Quick Configuration (Quick-CFIG) of connected modules and IDNet devices for general alarm operation to quickly get the system up and running 4010 Display Panel and Diagnostic Mode Convenient Status Information. With the locking door closed, a window allows viewing of the status display. The 4010 status panel provides a two line by 40 character, super-twist LCD information display and eight status LED indicators as shown in the illustration below. From this display, the LED indicators will describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door will provide access to the control switches and allow further inquiry by scrolling the display for additional detail. (Refer to control panel functional illustration below.) WALKTEST Diagnostic Operation Mode. The patented WALKTEST process allows a single person to perform system test. The system records test inputs such as intentional alarms or trouble and either logs the response (silent WALKTEST operation) or outputs a brief, recognizable audible notification signal (audible WALKTEST operation). Extended Operator Control Panel Functions FIVE STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset 2 X 40 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions, provides up to 40 characters for custom label information FIRST DISPLAY: Operation can be selected for maintained display of first alarm until acknowledged THREE PROGRAMMABLE LEDs provide custom labeling (labels insert into a pocket), the top two LEDs are selectable as red or yellow, the bottom LED is selectable as green or yellow CONTROL PANEL VIEW with 4010 door closed FIRE ALAR M ALAR MAC K SUPERVISORY SUPV AC K AC K ALAR M SILENCED ALAR M SILENCE A C POWER RESET RESET restores control panel to normal when all alarmed inputs are returned to normal DISABLE EXIT MENU FUNCTION ENTER ENABLE CLEAR PREVIOUS NEXT acknowledges a Fire Alarm condition, logs the acknowledge and silences the operator panel and all annunciator tone-alerts NINE EXTENDED FUNCTION KEYS (accessible with door open) select and scroll through display prompts for locating additional system information, performing maintenance functions, or for front panel programming SUPV acknowledges system supervisory conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts SILENCE causes audible notification appliances to be silenced, used after evacuation is complete and while alarm source is being investigated acknowledges system troubles, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts 2 S /2004

11 CAUTION DISCONNECT POW ER BEFORE SERVICING FIRE ** IS NORMAL ** 12:02:15pm Mon 9-Sep-02 SUPERVISORY ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 SILENCED ZONE 9 ZONE 10 ZONE 11 ZONE 12 ZONE 13 ZONE 14 ZONE 15 ZONE 16 AC POW ER AL AR M SUPV SILENCE RESET ZONE 17 ZONE 18 ZONE 19 ZONE 20 ZONE 21 ZONE 22 ZONE 23 ZONE FIRE CONTROL CAUTION DISCONNECT POWER BEFORE SERVICING SIMPLEX TIME RECORDER CO RELAY IAM INSTAL. INSTR DATE CODE: CAUTI ON D ISCONNECT POWER BEFORE SERVIC ING IDNet Addressable Interface Overview. The 4010 provides IDNet addressable device communications. Using a two wire circuit, individual devices such as manual fire alarm stations, TrueAlarm sensors, and sprinkler waterflow switches can be directly connected (or interfaced) to the IDNet controller to communicate their identity and status. This addressability allows the location and condition of the connected device to be displayed on the 4010 panel LCD and on system annunciators. Additionally, control circuits (fans, dampers, etc.) may be individually controlled by using a relay IAM (individual addressable module). The 4009 IDNet NAC Extender or the TrueAlert Addressable controller can be controlled for local or remote notification appliance expansion. (Refer to individual device documentation for further details.) Capacity. A total of 250 addressable monitor and control points may be intermixed on the same pair of wires. By using Zone Adaptor Modules (ZAMs) or Individual Addressable Modules (IAMs), conventional initiating devices can be connected to the IDNet circuit. IDNet Addressable Operation. The IDNet controller continuously interrogates each addressable device on the communication channel for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuit for Class B (Style 4) operation. Wiring Requirements. Refer to the specifications chart below. Distances are for shielded or unshielded wire. Shielded wire may provide protection from unexpected sources of interference and may be required for some applications. Wiring Specifications Size 18 AWG minimum Wire Preferred Shielded twisted pair (STP) Acceptable Unshielded twisted pair (UTP) Farthest Distance from Control Panel to Device Total Wire Length Allowed With T Taps for Class B Wiring TrueAlarm Analog Sensors Up to 2500 feet (762 m) Up to 10,000 ft (3 km). TrueAlarm System Operation. IDNet communications are used for TrueAlarm smoke and temperature sensors. Every four seconds, smoke sensors transmit an output value based on their smoke chamber condition. The 4010 CPU maintains a current value, peak value, and an average value of each sensor's output. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity. Programmable Sensitivity. The sensitivity of each sensor can be field programmed at the 4010 Control Panel for different levels of smoke obscuration (in percent) or for specific heat detection levels. In order to evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read and compared to the alarm threshold directly in percent. TrueAlarm Analog Sensors (Continued) TrueAlarm heat sensors can be selected for rate-of-rise detection as either 15 F (8.3 C) or 20 F (11.1 C) per minute with an independent fixed limit of 135 F (57 C) or 155 F (68 C). TrueAlarm heat sensors can also be programmed as a utility device to monitor for temperature extremes in the range from 32 F to 155 F (0 C to 68 C). This feature can provide freeze warnings or alert to HVAC system problems. TM TrueAlert Addressable Controller TrueAlert Addressable Controller Supervised IAM FIRE PULL DOWN Addressable station Quick-Connect TrueAlarm sensor 4010 Fire Alarm Control Panel with annunciator door To additional IDNet devices, up to 250 total Modular TrueAlarm sensor with base Modular TrueAlarm sensor with IDNet isolator base Monitor ZAMs and Relay IAMs TM 4009 IDNet NAC EXTENDER 4009 IDNet NAC Extender 4010 Control Panel with Typical IDNet Devices Diagnostics and Default Device Type TrueAlarm operation gives the 4010 system the ability to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 (National Fire Alarm Code) requirement for a test of the sensitivity range of the sensors is fulfilled by the TrueAlarm ability to maintain the sensitivity level of each sensor. Modular TrueAlarm sensors use the same base and different sensor types (photoelectric smoke sensor, or heat sensor) can be easily interchanged to meet specific location requirements. This feature also allows intentional sensor substitution during building construction. When conditions are temporarily dusty, instead of covering the smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. Although the control panel will indicate an incorrect sensor type, the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location. 3 S /2004

12 FIRE ** IS NORMAL ** 12:02:15pm Mon 8-Mar-99 SUPERVISORY SILENCED AC POWER SUPV SILENCE RESET FIRE CONTROL CAUTION DISCONNECT POWER BEFOR E SER VIC IN G TrueAlarm Information Details True Alarm sensor data can be displayed on the system LCD, on a remote maintenance PC, or printed on a remote printer. With the proper operator access, a TrueAlarm Service Report can be generated to list the specific details of each TrueAlarm device. This report, as well as the Status Report can either be displayed on the remote maintenance PC or captured permanently by using a remote 80 character printer. The report samples below illustrate the format provided on either the remote maintenance PC or a printer. This information is available at the system LCD by identifying the specific point of interest and reading one point at a time. Model is a UL Standard 864 listed 80 column, 24 pin dot matrix printer (refer to data sheet S ). (Model , a 24 VDC, 40 column printer, is compatible with the 4010 for event printing only. Refer to data sheet S ) Printer (Simplex model ) 4010 Fire Alarm Control Panel Local maintenance computer One connection type per 4010, selected by module choice; max. wiring distance is 300 ft ( baud Remote authorized maintenance computer connected via dial-up Service Modem Connection RS-232 Connection Options (refer to module selection on page 6) TrueAlarm Status and Service Report Samples Simplex 4010 Fire Alarm System Page 1 REPORT 3 : TrueAlarm Status Report 2:43:03 pm Mon 18-Oct-04 Zone Name Custom Label Sensitivity Device Status Almost Dirty M1-1 ANALOG PHOTO CLEAN ROOM 0.5 % NORMAL M1-2 ANALOG ION CLEAN ROOM 1.3 % NORMAL M1-3 ANALOG PHOTO MAIN LOBBY 2.5 % NORMAL *YES* M1-4 ANALOG PHOTO CONFERENCE ROOM % NORMAL M1-10 HEAT DETECTOR GARAGE 135 F NORMAL M1-11 ANALOG PHOTO KITCHEN 3.7 % NORMAL *YES* END OF REPORT Typical TrueAlarm Status Report Information Printout and/or Maintenance PC Screen Simplex 4010 Fire Alarm System Page 1 REPORT 4 : TrueAlarm Service Report 2:56:09 pm Mon 18-Oct-04 Dev Num Custom Label Alarm at: Avg val Current/ % alarm Peak/ % alarm 1 ANALOG PHOTO - CLEAN ROOM 0.5/ / 1% 72/ 10% NOR 2 ANALOG ION - CLEAN ROOM 1.3/ / 2% 101/ 1% NOR 3 ANALOG PHOTO - MAIN LOBBY 2.5/ / 0% 125/ 42% NOR 4 ANALOG PHOTO - CONFERENCE ROOM 1 2.5/ / 0% 93/ 0% NOR 10 HEAT DETECTOR - GARAGE 135F/ /-67F 66/ 69F NOR 11 ANALOG PHOTO - KITCHEN 3.7/ / 1% 110/ 36% NOR END OF REPORT Typical TrueAlarm Service Report Information Printout and/or Maintenance PC Screen State 4 S /2004

13 Standard Panel Features N2 Communications for Serial Annunciator Control. Control for up to 6 remote Simplex Annunciator products including 24 Point I/O Module, and LCD Annunciator. Includes extensive troubleshooting diagnostics. Access Port. RS-232 service port for connecting PC tools for service diagnostics and for programming the CPU Flash EPROM memory. IDNet Addressable Communications Channel. Addressable channel provides communications for up to 250 remote addressable devices, including TrueAlarm analog sensors and isolator bases (see descriptions on page 3). Four NACs. Class B output is standard, rated for 2 24 VDC nominal, with solid state current protection. Class A operation is optional with the addition of an adapter module. NAC operation can be selected for on-until-silence or on-until-reset, and can be Temporal pattern, 20 or 120 bpm March Time pattern, or continuous. Each NAC is also individually selectable to control Simplex synchronized visible notification appliances and to control audible notification appliances using SmartSync control, allowing separate audible and visible appliance operation using a common 2-wire circuit. (Class A, Style Z, SmartSync circuits require SmartSync Control Module , refer to data sheet S for details.) Two Auxiliary Output Circuits. Operation is programmable for trouble, alarm, supervisory, or other fire response functions. Output is one Form C dry contact each, rated 2 24 VDC. An optional relay kit is available for switching up to 1/2 A at 120 VAC. Power Supply. Standard output is 4 28 VDC, filtered, non-regulated. Internal system power is provided separately, allowing the 4 A to be available for NAC and auxiliary power tap functions. Over-current protection is solid state and self-resetting. Auxiliary Power Tap. Provides up to 1/2 A of the standard power supply voltage, over-current protected. Battery Charger. Capable of charging up to 25 Ah sealed lead-acid batteries (4010 cabinet mounted). A recharge time of 24 hours is typical with stable 120 VAC input. For applications requiring larger batteries, external charger/cabinet assemblies are available. A depleted battery cutout feature is programmable to advise and/or to reduce current when battery voltage is low. Optional Expansion Slot Modules (The 4010 is available with a Simplex Network Interface points can be declared public. ) Network Interface, Fixed Media. Available for wired applications. Network Interface, Modular Media. Available for wired connections or fiber optic. Require separate media modules. May be both wired, both fiber optic, or one of each. DACT, Point Reporting Module. Provides serial output information that can send location details to a remote receiving station. Optional Expansion Slot Modules (Cont d) DACT, Event Reporting Module. For applications where simple event status information is required (Alarm, Trouble, Supervisory, and AC power failure). Dual RS-232 Module. Available for interfacing to a printer and a maintenance PC. Single RS-232 Module with Service Modem Connection. Provides one port dedicated for connection to a printer, and a second port dedicated for dial-in from a service computer, typically located off-site. With an off-site computer, programming changes and system diagnostics can be performed remotely, reducing service time for repair or reprogram. Security is maintained by password protection. Optional Chassis Mount Modules Standard 4 A Expansion Module provides two taps of 2 A each, 28 VDC, filtered, non-regulated, similar to the standard power supply capacity. Suppression Release Power Supply provides two taps of 2 A each, regulated at 24 VDC ± 10%. May also be used for other applications requiring regulated voltage. Use for suppression release requires a front panel mounted release appliqué that is provided with this power supply and also may be ordered separately. Battery Meter Module provides panel mounted ammeter and voltmeter for power supply monitoring. Dual Circuit Class A NAC Adapter Module mounts on the main 4010 printed circuit assembly and provides the additional circuitry needed for Class A operation. Dual Circuit City Connect Module provides the interface required for direct wired reporting to conventional city connection circuits. (Available with or without disconnect switches.) Expansion Power Distribution Module provides two additional termination points for the 1/2 A auxiliary power output, or for one tap of the expansion power supply. Relay Option Module. Provides three relays, one each for Alarm, Supervisory, and Trouble. Relay contacts are selectable for normally open or normally closed and are rated 2 32 VDC maximum. N2 Communications Modules Up to six of the following modules may be connected to the Simplex N2 serial communications bus LCD Annunciators provide remote acknowledge, reset, and alphanumeric status display. (Refer to data sheet S ) 24 LED Annunciator Doors are standard on ULC listed models and are available as door-only assemblies for electronics only packages or other aftermarket applications. This option uses the 24 Point I/O module with all points pre-assembled as LED outputs, with individual labels and each LED is selectable as red or yellow Series 24 Point I/O Modules are available for remote mounting and provide 24 points that can be programmed as either general purpose switch inputs or system controlled outputs. Typical applications are for remote annunciators and monitoring and control of other related processes. (Refer to data sheet S ) 5 S /2004

14 4010 Fire Alarm Control Selection Chart and Module Location Rules (refer to diagrams on page 8) Category Model Description Voltage Color Beige UL Listed 4010 Fire Alarm Control Panel with: door, cabinet, power 120 VAC supply/battery charger, IDNet interface, 4 NACs, 2 auxiliary relays, and Red external N2 communications interface; and Beige include internal common event reporting DACT 240 VAC Control Panel Red Assembly C English ULC Listed 4010 Fire Alarm Control Panel; same as above 120 VAC Beige (select one) CF French except: with 24 LED Annunciator door; and without DACT UL Listed C ULC English CF Listed French 4010 Fire Alarm Control Panel electronics only, for pre-shipped cabinets, requires door and cabinet ordered separately; has event reporting DACT Optional Expansion Slot Features (two slots are available, select modules as required) 120 VAC NA Category Model Description DACT Module (Common Event Reporting) Reporting and Includes two, 7 ft (2.1 m) long RJ45 cables DACT Module (Point Reporting) Network Modules (select one) Network Interface Module with fixed, wired connections Network Interface Module, Modular; requires 2 (In/Out) media modules (see below) RS Dual RS-232 Interface Module Communications (select one) Single RS-232 Interface Module with Service Modem connection Network Wired Media Module Media modules mount on the module Media Modules Network Fiber Optic Media Module without impact to slot allocation space. Chassis Mounted Expansion Modules (select as required) Category Model Description VAC input Additional 4 A Expansion Power Supply VAC input Power Supply (select one) 120 VAC input (CF) Optional Features (select one) Optional Features (select as indicated) Accessories Suppression Release Power Supply; 4 24 VDC, regulated ± 10%; includes front panel suppression appliqué; CF suffix selects French Battery Meter Module (ammeter and voltmeter) 240 VAC input 24 VDC Expansion Power Distribution Module, provides two additional termination points for an expansion power supply tap or the auxiliary power output Dual Circuit Class A (Style Z) NAC Adapter Module, two maximum Dual Circuit City Connect Module * Dual Circuit City Connect Module w/o disconnect switches Relay Option Module Select one maximum Category Model Description VAC Auxiliary Relay Kit, allows one auxiliary relay to control up to 1/2 VAC, select as required; 2 maximum Optional Features (CAF) Suppression Release Appliqué, required for suppression release applications; suffix CAF selects a French appliqué Semi-flush trim, beige, 1-7/16 (37 mm) wide Semi-flush trim, red, 1-7/16 (37 mm) wide Batteries Ah Battery, 12 VDC (required if Ah Battery, 12 VDC batteries are internal; select one Ah Battery, 12 VDC size; two batteries Ah Battery, 12 VDC; NOTE: This battery size will not allow bottom entry conduit are required) Ah Battery, 12 VDC Cabinets (select one if pre-shipped) Doors (select one if pre-shipped or for use with ) Red Cabinet (CF) Beige Cabinet; CF suffix has French labels Red Door with dress panel (CF) Beige Door with dress panel; CF has French labels Dimensions: 22 H x 18 W x 5-3/8 D (559 mm x 457 mm x 137 mm) Dimensions: 22 H x 18 W x 5/8 D (559 mm x 457 mm x 16 mm) Beige Door with 24 LED Annunciator and dress panel; Dimensions: 22 H x 18 W x (CAF)* CAF suffix selects French for ULC applications 1-23/32 D (559 mm x 457 mm x * Red Door with 24 LED Annunciator and dress panel 44 mm) [see also S ] * As of document revision date: is not ULC listed; and are listed by UL and ULC and approved by CSFM and FM; CAF is ULC listed and FM approved only. 6 S /2004

4007ES Fire Control Panels

4007ES Fire Control Panels UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved* 4007ES Fire Control Panels 4007ES Hybrid, Fire Detection and Control Panel with Addressable and/or Conventional Initiation Features Satisfies a variety

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK

More information

TrueAlarm ES Analog Sensing

TrueAlarm ES Analog Sensing TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

Fire Control Panels. Addressable Fire Detection and Control Basic Panel Modules and Accessories. UL, ULC Listed, FM Approved* Features

Fire Control Panels. Addressable Fire Detection and Control Basic Panel Modules and Accessories. UL, ULC Listed, FM Approved* Features Fire Control Panels UL, ULC Listed, FM Approved* Features Basic system includes: Capacity for up to 1000 addressable IDNet points, up to 127 VESDA Air Aspiration Systems interface points and up to 254

More information

4007ES Fire Control Panels

4007ES Fire Control Panels UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved* Features Flexible standard combination of addressable initiation and addressable notification 4.3 (109 mm) Diagonal color touchscreen display: Convenient

More information

TrueAlert Notification Appliances

TrueAlert Notification Appliances TrueAlert Notification Appliances UL Listed; FM, CSFM and MEA (NYC) Approved* Non-Addressable Audible/Visible Notification Appliances with SmartSync Operation of Strobes and Horns Features Wall mount audible/visible

More information

Fire Control Units. Addressable Fire Detection and Basic Control Unit Modules and Accessories. UL, ULC Listed, FM Approved* Features

Fire Control Units. Addressable Fire Detection and Basic Control Unit Modules and Accessories. UL, ULC Listed, FM Approved* Features Fire Control Units UL, ULC Listed, FM Approved* Features Basic system includes: Capacity for up to 1000 addressable IDNet points, up to 127 VESDA Air Aspiration Systems interface points and up to 254 addressable

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

Network Display Unit Installation Instructions

Network Display Unit Installation Instructions Network Display Unit Installation Instructions Introduction This publication describes the installation procedures for the optional Network Display Units (NDUs). This product is compatible with both the

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 574-052 Rev. F This page intentionally blank Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights

More information

user manual Document No , Revision 03 November 2015

user manual Document No , Revision 03 November 2015 user manual Document No. 996-202-600-3, Revision 03 November 2015 Contents 1 Introduction...1 1.1 Notice...1 1.2 Models...1 2 User Control Levels...2 2.1 Level Definition...2 2.2 User Passwords...2 3 Controls

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES 579-685 Rev. B ii iii Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

Document No Issue 4 user manual

Document No Issue 4 user manual DX Document No. 996-148-000-4 Issue 4 user manual Dimension Series Table of Contents 1 INTRODUCTION... 5 1.1 NOTICE... 5 1.2 MODELS... 5 1.3 WARNINGS AND CAUTIONS... 7 1.4 NATIONAL APPROVALS... 7 1.5 EN54

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Fire Safety FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

Multi-Application Peripherals and Accessories

Multi-Application Peripherals and Accessories ON UL, ULC Listed FM Approved MultiApplication Peripherals and Accessories Communicating Devices Communications Individually Addressable Devices FEATURES Individually addressable communications over a

More information

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays AEGIS Conventional Fire Alarm-Suppression Control Unit FEATURES Agency Approvals FM Approved FM Approved to ANSI/UL 864, 9th edition FM Approved to ULC-S527-99 Other domestic U.S. approvals/listings pending/

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

Fire Control Panels. Network Annunciator Panels Network Display Unit (NDU) UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features

Fire Control Panels. Network Annunciator Panels Network Display Unit (NDU) UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features FIRE PL ALARM DOWN FIRE PL ALARM DOWN Event Time Enable Arm Di sable E mergency Operating Instr uctions Al ar m or War ni ng Co ndi ti on System indicator f lashing. Tone. How to nowledge / View Events

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3 Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

MPC-6000 / MPC-7000 / RND-2

MPC-6000 / MPC-7000 / RND-2 MPC-6000 / MPC-7000 / RND-2 Fire Alarm System Control Unit Installation, Operation and Maintenance Manual Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600

More information

Intelligent 2 & 4 Loop Fire Alarm Control Panels

Intelligent 2 & 4 Loop Fire Alarm Control Panels Intelligent 2 & 4 Loop Fire Alarm Control Panels Advanced has combined the latest technology with many years of fire experience, to create the Axis AX Series Intelligent Fire Alarm Control Panels. The

More information

4010 Fire Alarm PC Programmer Installation and Programming Instructions

4010 Fire Alarm PC Programmer Installation and Programming Instructions 4010 Fire Alarm PC Programmer Installation and Programming Instructions 574-187 Rev. C Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights reserved. Printed in the United States

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

Fire Detection and Alarm

Fire Detection and Alarm Fire Detection and Alarm Overview of Products Our fire systems are designed and manufactured to provide the highest levels of reliability, survivability, and flexibility to meet or exceed local regulatory

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual P/N 315-049353-1 Siemens Building Technologies Fire Safety TABLE OF CONTENTS INTRODUCTION... 1 CONTROL PANEL

More information

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels GE Security EST Life Safety & ommunications onventional Small Building Solutions Overview The FireShield Plus fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,

More information

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

Intelligent Single Loop Fire Alarm Control Panel

Intelligent Single Loop Fire Alarm Control Panel Intelligent Single Loop Fire Alarm Control Panel The CAX-CTL-1L Intelligent Single Loop Fire Alarm Control Panel is a member of the industry leading Axis AX Series Intelligent Fre Alarm Control Panels

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system s Data Sheet Fire Safety & Security Products Cerberus TM PRO Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA90621-2268

More information

SECTION FIRE ALARM SYSTEM PART 1 GENERAL

SECTION FIRE ALARM SYSTEM PART 1 GENERAL SECTION 16720 - FIRE ALARM SYSTEM PART 1 GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and

More information

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2003-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2003-12NDS Network Fire Alarm Control Unit offers modular components to meet a

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Fire Alarm Systems UL, ULC, CSFM Listed; FM Approved* Features TrueSite Incident Commander provides 4100ES mounting for the Simplex TrueSite Workstation: All-in-one touchscreen computer/monitor

More information

Desigo TM Fire Safety System A comprehensive fire-protection system

Desigo TM Fire Safety System A comprehensive fire-protection system s Desigo TM Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the 252- point and 504-point systems One (1) or (2)

More information

R Series Remote Annunciators and Expander Installation and Operation Guide

R Series Remote Annunciators and Expander Installation and Operation Guide GE Security R Series Remote Annunciators and Expander Installation and Operation Guide P/N 3100969 REV 1.0 ISS 15JUL08 Copyright Copyright 2008 GE Security, Inc. All rights reserved. This document may

More information

E3 Series Broadband System

E3 Series Broadband System Voice Evacuation E3 Series Broadband System Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System General The, E3 Series Broadband System is a modular design and

More information

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014 January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM. Features

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM. Features INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM Description Mircom s FleX-Net TM Series Network Fire Alarm Control Panels offer modular components to meet a wide variety of applications. Designed for peerto-peer

More information

NetSOLO Broadband. Voice Evacuation. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

NetSOLO Broadband. Voice Evacuation. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System Voice Evacuation NetSOLO Broadband Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System General The NetSOLO Broadband is a revolutionary advance in fire detection

More information

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview Edwards Signaling atalog u Fire Alarm ontrol Panels E-FS onventional Fire Alarm ontrol Panels Overview The E-FS fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Addressable Detectors & Bases

Addressable Detectors & Bases Edwards Signaling Catalog u Intelligent Initiating Addressable Detectors & Bases Detectors: E-PD, E-PHD, E-HD Bases: B4U, RB4U, IB4U, SB4U Overview Edwards intelligent addressable detectors are meticulously

More information

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111 NETWORK FIRE ALARM CONTROL PANEL FX-2009-12NDS Description FX-2009-12NDS in a BB-5008R enclosure. Mircom s FleX-Net Series is a powerful intelligent networkable fire alarm solution designed with many levels

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Fire Alarm Control/Communicator

Fire Alarm Control/Communicator Fire Alarm Control/Communicator Operation and Installation Guide Power Alarm Trouble Silenced Radionics FIRE CONTROL/COMMUNICATOR R 31499F Page 2 2000 Radionics. Contents Contents 1.0 Notices... 9 1.1

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

R-Series Remote Annunciators and Expanders Installation and Operation Guide

R-Series Remote Annunciators and Expanders Installation and Operation Guide R-Series Remote Annunciators and Expanders Installation and Operation Guide P/N 3100969-EN REV 05 ISS 06MAY13 Copyright Trademarks and patents Manufacturer Version FCC compliance Contact information 2013

More information

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND

More information

1. Buildings on the Pullman campus are monitored by a Simplex 4120 FDA Network or a Siemens XLS Network.

1. Buildings on the Pullman campus are monitored by a Simplex 4120 FDA Network or a Siemens XLS Network. 28 31 00 PART 1 - GENERAL 1.01 SCOPE A. Background: Washington State University has agreements with Simplex- Grinnell and Siemens Industry, Inc. to provide Fire Detection and Alarm (FDA) systems for the

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

ADR Analog Addressable Fire Alarm Control Panel. Technical Manual. Control Panels. 3000En. En pdf

ADR Analog Addressable Fire Alarm Control Panel. Technical Manual. Control Panels. 3000En. En pdf Control Panels Analog Addressable Fire Alarm Control Panel Technical Manual TELEFIRE FIRE & GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel: 972 3 970 0400 Fax: 972 3 921 1816 email: Web: info@telefire.co.il

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 Corporate Headquarters 800.845.6692

More information

All-In-One Wireless Security System V1.0. Model #: MG-6060

All-In-One Wireless Security System V1.0. Model #: MG-6060 All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual DRAFT Table of Contents Introduction... 5 About Magellan and this Manual... 5 Conventions... 5 Specifications...

More information

KFP-AF Series Fire Alarm Control Panel Installation Manual

KFP-AF Series Fire Alarm Control Panel Installation Manual KFP-AF Series Fire Alarm Control Panel Installation Manual P/N 501-405103-1-20 REV 2.0 ISS 03MAR11 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL The FireNET 427 control panel is an analog addressable fire alarm panel containing 2 or 4 SLC loops with each loop supporting 27 devices of

More information

ZP2 Series Operation Manual

ZP2 Series Operation Manual ZP2 Series Operation Manual P/N 501-405203-2-31 REV 03.10 ISS 07NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire & Security.

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

D1255RB/D1256RB/D1257RB

D1255RB/D1256RB/D1257RB D1255RB/D1256RB/D1257RB EN Installation Instructions Fire Keypads and Fire Alarm Annunciator D1255RB/D1256RB/D1257RB Installation Instructions Listings and Approvals Listings and Approvals UL 365 UL 609

More information

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing Control Panels Control Panels for Commercial Applications Control panels provide the central processing and logic for an integrated system. In a typical system, there are four major functions: inputs,

More information

D2071A. Operation & Installation Guide Fire Alarm Control Panel

D2071A. Operation & Installation Guide Fire Alarm Control Panel D2071A EN Operation & Installation Guide Fire Alarm Control Panel D2071A Operations & Installation Guide Contents Contents 1.0 Overview... 4 1.1 Communicator... 4 1.2 RFI and Lightning Protection... 4

More information

Agent Release Control Panel

Agent Release Control Panel Agent Release Control Panel System Capacity Annunciators: 8 Electrical Specifications RP-2002 (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66 amps RP-2002E (FLPS-7 Power Supply): 240 VAC, 50 Hz, 2.085 amps

More information

E3 Series Broadband. Description. Features. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

E3 Series Broadband. Description. Features. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System Broadband Description Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System The Broadband System includes the Net- SOLO Broadband System. Like the NetSOLO Broadband

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Analogue Addressable Fire Panels FP1500. Manual for Installation, Configuration and Commissioning

Analogue Addressable Fire Panels FP1500. Manual for Installation, Configuration and Commissioning Analogue Addressable Fire Panels FP1500 Manual for Installation, Configuration and Commissioning Version 2.1 / November 2003 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) PATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) NAC ETENDER SUPPLIES Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web

More information

E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL Fire Alarm Control Panel ESL

E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL Fire Alarm Control Panel ESL E S L I N S T A L L A T I O N A N D O P E R A T I O N S M A N U A L ESL 2501 Fire Alarm Control Panel ESL a product A PRODUCT of OF SENTROL sentrol Sentrol 1-800-547-2556 1 2 Sentrol 1-800-547-2556 TABLE

More information

/9308 External Battery Chargers Installation Instructions

/9308 External Battery Chargers Installation Instructions 4081-9306/9308 External Battery Chargers Installation Instructions Introduction This publication describes the installation procedure for an External Battery Charger used with the 4100U or 4100ES System.

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

FX-350/351/353 SERIES

FX-350/351/353 SERIES FX-350/351/353 SERIES Analog/Addressable Fire Alarm Panel Programming Manual LT- 1040 Rev 3.1 January 2017 FX-350/351/353 Series Programming Manual Table of Contents System Configuration... 1 Panel Configuration...

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL

IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL IDENTIFLEX 610 ANALOG / ADDRESSABLE FIRE ALARM CONTROL PANEL INSTALLATION & OPERATION MANUAL GAMEWELL P/N 71810 60 PLEASANT STREET ISSUE 3, 10/04/2000 ASHLAND, MA 01721 FIRMWARE VER. 7 THIS PAGE INTENTIONALLY

More information

CHERRY POINT BOQ B-487 CHERRY POINT, NC. Fire Alarm System Equipment Data Submittal February 4, Dividend Loop Myrtle Beach, SC 29577

CHERRY POINT BOQ B-487 CHERRY POINT, NC. Fire Alarm System Equipment Data Submittal February 4, Dividend Loop Myrtle Beach, SC 29577 CHERRY POINT BOQ B-487 CHERRY POINT, NC Fire Alarm System Equipment Data Submittal February 4, 2013 1578 Dividend Loop Myrtle Beach, SC 29577 THIS PAGE INTENTIALLY LEFT BLANK Project: Cherry Point Boq

More information

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Harrington Signal HS-3100/3200 Fire Alarm Control Unit HARRINGTON SIGNAL INC. FIRE ALARM Harrington Signal HS-3100/3200 Fire Alarm Control Unit Installation Manual Revision 2 January 2009 Document # LT-2000HAR Table of Contents 1.0 Technical Information...

More information