1 /9308 External Battery Chargers Installation Instructions Introduction This publication describes the installation procedure for an External Battery Charger used with the 4100U or 4100ES System. IMPORTANT: Verify FACP System Programmer, Executive, and Slave Software compatibility when installing, or replacing system components. Refer to the Technical Support Information and Downloads website for compatibility information. In this Publication This publication discusses the following topics: Topic See Page # Cautions and Warnings 2 General Description 3 Configuring the External Battery Charger 6 Locating and Wiring the External Battery Charger SimplexGrinnell LP. All rights reserved. Specifications and other information shown were current as of publication and are subject to change without notice. Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license Rev. D

2 Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper installation. DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED- Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier. ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or authorized agent of your local Simplex product supplier. EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output of this device may exceed eye safety limits. Do not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device. STATIC HAZARD - Static electricity can damage components. Handle as follows: Ground yourself before opening or installing components. Prior to installation, keep components wrapped in anti-static material at all times. FCC RULES AND REGULATIONS PART 15 - This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be tested in accordance with NFPA , Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. 2

3 General Description Introduction The external battery charger (XBC) consists of the battery charger PC board bracket assembly and the external battery cabinet. The external battery charger (XBC) is a communicating slave in a 4100U/4100ES System. A micro controller monitors all input and output functions on the charger and is capable of reporting all board statuses to the system CPU via a 4100-style communications channel. The XBC monitors and reports the following statuses: Battery charger status Battery status Positive earth fault Negative earth fault AC fail Both the battery cabinet and charger are shown in Figure 1. Battery Cabinet Bracket Assembly Batteries (shipped separately) Battery Charger PC Board Figure 1. Battery Cabinet and External Charger Continued on next page 3

4 General Description, Continued Charging Batteries The XBC can re-charge 55Ah 110Ah batteries per UL 864 and S527 requirements. When completely discharged, the batteries will demand a high current. As the battery charges, the rate of charge will decrease. The table below shows specific voltage and current information for both the supply and output of the battery charger. Table 1. System Voltage Ratings Voltage Range, Amps Supply Current At 120VAC, 4A Max. At 220/230/240VAC, 2A Max. Output Float Voltage *27.4V DC 20 High Voltage Output up to 7A (charger voltage determined by battery charge state) *temperature compensated at 24mV/ C (-5 C 50 C) **no temperature compensation Note: If the AC line drops below 85% of nominal (brownout or AC fail), the XBC will no longer charge the batteries. It will continue to operate and communicate to the system CPU, however. The XBC is a temperature compensated battery charger. It has no field adjustment. The charger voltage is higher when the temperature in the cabinet is low and lower when the temperature in the cabinet is high. A warmer environment than that noted in the table above will result in a lower output float voltage (see Table 1). The High Voltage Output shown above relates to the battery charger s dual rate ability. The high voltage output kicks in when the batteries are discharged. This allows battery capacity to be restored more quickly. When the batteries become close to full, the current will drop and the charger will switch back to the float voltage. Continued on next page 4

5 General Description, Continued Indicators The charger controller board contains three LED indicators for signaling various troubles with the operation of the system. They are used to indicate communications status, power supply status, and AC power status respectively. The tables below explain the trouble conditions of each LED. Table 2. LED 1 COMMS Status LED On Yellow Indication Lost communication with CPU or OFFLINE (if SW1 is set that way) Table 3. LED 2 Power Supply Status LED Off Single Blink Double Blink Triple Blink Quadruple Blink Indication Normal POS. Earth NEG. Earth Battery Trouble Charger Trouble Table 4. LED 3 AC Power LED On Green Indication Indicates charger running from AC Mains Environmental Requirements Normal Operating Temperature (Ambient Conditions Outside the Cabinet): -5 C to 50 C Humidity: normal operation under non-condensing humidity conditions up to 93% (ULC) relative 38 C (FM spec). 5

6 Configuring the External Battery Charger Introduction The External Battery Charger (XBC) is configured as part of a 4100 system in two steps. It must be programmed as part of the system. Use the PC-based 4100U or 4100ES Programmer to add the XBC to the system configuration. This will assign a system address used when communicating with the XBC. Refer to the ES Panel Programmer s Manual ( ) for instructions on adding the XBC to the system software configuration. Adding the XBC is similar to adding any other communicating slave to the system. The physical configuration of the board must be set. This includes setting the card address and positioning the hardware jumpers on the card. This section explains how to configure the battery charger and includes an illustration referring to the different components on the battery charger controller card. Address Switch LEDs 4100 Communications Connections Jumper R49 (Remove for S527) Battery Connector Jumper P3 Bridge Rectifier Connection Figure 2. External Battery Charger Controller Card Continued on next page 6

7 Configuring the External Battery Charger, Continued Jumpers The External Battery Charger has two options that are jumper selectable: the Earth Fault Monitor Jumper and the Depleted Battery Cutout Jumper. Their functions are explained below. Earth Monitor The XBC can be configured to monitor for earth faults. When the XBC is not located with an SPS or RPS, it should be configured to monitor for earth faults. Set jumper P3 at positions 1 and 2 to enable the monitoring of earth faults Set jumper P3 at positions 2 and 3 to disable the monitoring of earth faults When earth monitor is enabled, the XBC will detect earth faults on equipment that is connected to the same OV as the XBC. When RUI communications are used, OV points between cabinets are isolated. In those cases, a battery charger, SPS or RPS at a remote location is configured to monitor for earth faults for modules at that location. Depleted Battery Cutout Some jurisdictions require system cutout when a depleted battery condition is detected and AC has failed. You can set your system up to remove power from the XBC when the AC has failed and the batteries are depleted. Note: This is different than inhibiting alarms that occur after the batteries are already depleted. This operation shuts the system off. To activate this feature, Low Battery Cutout option must be selected in the Programmer. Refer to Appendix C in manual Also, a specific jumper must be removed from each power module in the system to activate depleted battery cutout operation. The XBC has one such jumper. If depleted battery cutout is desired, remove jumper R49. The jumper is labeled remove for S527 as this operation is specified in S527, the Canadian standard for fire alarms. This removes power from the XBC when AC fails and batteries are depleted. Note: Systems with this jumper removed will not power-up from battery power. Continued on next page 7

8 Configuring the External Battery Charger, Continued Address Switch The card address assigned to the XBC in the Programmer must also be set physically using the Address Switch located on the XBC s printed circuit board. The switch is 8 positions, with 7 positions used to set the address and 1 used to set the card either on or off line. SW8 SW2 are used to set card addresses. SW8 is the least significant bit (LSB). SW2 is the most significant bit (MSB). Each switch has a different weight. The sum of the weights of the switches turned OFF is the address setting. Valid addresses are in the range of 1 to 119. Two cards cannot occupy the same address. Table 5. Switch Weights Switch SW8 SW7 SW6 SW5 SW4 SW3 SW2 Weight Add 1 to card address if OFF Add 2 to card address if OFF Add 4 to card address if OFF Add 8 to card address if OFF Add 16 to card address if OFF Add 32 to card address if OFF Add 64 to card address if OFF The card is set either on or off-line with SW1. SW1 in the on position sets the card on-line. If SW1 is off, the card is off-line and will not communicate to the system CPU. LED 1 (yellow) on indicates that the card is off-line or when communications are otherwise inhibited. 8

9 Locating and Wiring the External Battery Charger Guidelines The external battery charger must be within 20 feet of the Fire Alarm Panel to which it supplies battery backup. All wiring to the external battery charger from the Fire Alarm Panel must be in conduit. All power and comm. wiring is in compliance with the requirements specified in NFPA 70, Article (1), Exception No.2 (b) (1). Connect AC Power AC power connects to the XBC at an off-board terminal block. There are two versions of the XBC: the 120V/60Hz and the 220/230/240V 50/60Hz model. For the 120V version, three connections are made: 1. Connect the HOT wire to the terminal marked 120V. 2. Connect the NEUTRAL wire to the terminal marked NEU. 3. Connect the safety ground to the ground stud marked with the EARTH symbol. For the 220/230/240V version, the same three connections are made only there are three different choices for input voltage. Therefore, the HOT wire should be connected to the appropriate terminal for the operating voltage being used. Connect the Battery The XBC connects to the batteries through a battery block. A two-conductor harness from the battery block snaps into a keyed connector on the XBC circuit board. The RED wire is +24V and the BLACK wire is OV. The harness does not carry the alarm load. It carries the current to the batteries only, which is about 7A maximum. The battery block can accept very large wire (up to 2AWG) in order to minimize the voltage drop to the equipment. When choosing the wire gauge to be used, consideration must be given to the details of each application. A system with a high worst-case load requires careful planning of the distance from the batteries to the system, wire gauge choice, and worst-case battery voltage. It is always best to use the largest gauge wire possible and to keep the distance to a minimum. Using 12 AWG wire results in a voltage drop of about 4mV/Ampere/foot. The drop is quite significant (see example). Example: Wire gauge = 12 AWG System with 3 Power Supplies = potential load of 27A Battery Cabinet distance from System = 20ft. Therefore, Voltage Drop =.004V * 27A * 20ft. = 2.16V If the battery discharge curves with an end voltage of 21V were used, the voltage to the system would be too low to provide the required notification. The system must be planned to avoid situations such as those described in the example. Generally, locate the battery cabinet as close to the FACP cabinet as possible and use as large a wire gauge as possible. Note: Another way to reduce voltage drop is to use multiple cabinets when current demand is high. Running a pair of wires to each cabinet reduces the overall voltage drop since each pair of wires carries a lower current. Continued on next page 9

10 Locating and Wiring the External Battery Charger, Continued 4100 Communications The communications (comms) harness, , is connected from a close-nippled 4100U/4100ES cabinet. The harness is constructed with type FPL cable to allow routing with the other connections to the XBC (refer to NFPA 70, Article (1), exception no. 2 (b) (1)). The harness is keyed for easy connection and plugs into connector P1 on the XBC. The other end gets connected to any of the four-position connectors on the PDI or CPU motherboard in the host system. This harness is long enough to allow for the maximum distance of 20 feet between the Fire Alarm Panel and the External Battery Charger. Connect the Bridge Rectifier Use harness number to connect H1 and H2 to the bridge rectifier. H1 +Bridge Rectifier (red wire) H2 -Bridge Rectifier (black wire) Rev. D

Network Display Unit Installation Instructions

Network Display Unit Installation Instructions Network Display Unit Installation Instructions Introduction This publication describes the installation procedures for the optional Network Display Units (NDUs). This product is compatible with both the

More information

Class A and Expansion NAC Modules Installation Instructions

Class A and Expansion NAC Modules Installation Instructions Class A and Expansion NAC Modules Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-1245 Flex Amplifier Expansion NAC (XNAC) 4100-1246

More information

Panel Message Memory Expansion Cards Installation Instructions

Panel Message Memory Expansion Cards Installation Instructions Panel Message Memory Expansion Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-1241 Audio Message Memory Expansion Card (4 Megabytes

More information

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES 579-685 Rev. B ii iii Cautions and Warnings Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

Instruction Manual. CMP-12/24 Fire Alarm Control Panel. 12 Clintonville Road, Northford, CT DOCUMENT /11/96 REV: D1

Instruction Manual. CMP-12/24 Fire Alarm Control Panel. 12 Clintonville Road, Northford, CT DOCUMENT /11/96 REV: D1 12 Clintonville Road, Northford, CT 06472 Instruction Manual CMP-12/24 Fire Alarm Control Panel DOCUMENT 15819 3/11/96 REV: D1 P/N 15819:D1 ECN 96-047 Installation Precautions - Adherence to the following

More information

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Part Number P84748 Assembly Number A84749 Revision C Revision A Copyright 2006 Printed in U.S.A. All rights reserved.

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

4007ES Fire Control Panels

4007ES Fire Control Panels UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved* 4007ES Fire Control Panels 4007ES Hybrid, Fire Detection and Control Panel with Addressable and/or Conventional Initiation Features Satisfies a variety

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations: F1! 44487023 These instructions cover the following parts: PS902 Power Supply Installation Instructions! DANGER: To avoid risk of electric shock, turn off AC power before installing or servicing PS902

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual INSTALLATION 10-175UL Power Supply 10-175UL Access Control Power Supply/Charger Installation and Specifications Manual Overview The 10-175UL is a power limited power supply/charger that will convert 115VAC

More information

Installation and Operating instructions for. C9900-U battery pack. Version: 2.0 Date:

Installation and Operating instructions for. C9900-U battery pack. Version: 2.0 Date: Installation and Operating instructions for C9900-U330-0010 battery pack Version: 2.0 Date: 2017-03-23 Table of contents Table of contents 1 Foreword 3 1.1 Notes on the Documentation 3 1.1.1 Liability

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

MMF Six Zone Interface Module

MMF Six Zone Interface Module Installation and Maintenance Instructions I56-900-005 MMF-0-6 Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage: 5- VDC Stand-By Current: ma Alarm Current: 40 ma (assumes all six LEDs solid

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3W FEATURES Transmits alarm information to a long range radio network Varitech Transmission Format Note: If automatic SIA is used in

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Harrington Signal HS-3100/3200 Fire Alarm Control Unit HARRINGTON SIGNAL INC. FIRE ALARM Harrington Signal HS-3100/3200 Fire Alarm Control Unit Installation Manual Revision 2 January 2009 Document # LT-2000HAR Table of Contents 1.0 Technical Information...

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Dual Input ph/orp Analyzer

Dual Input ph/orp Analyzer Instruction Sheet PN 51A-1055pH/rev.I February 2006 Model 1055 SOLU COMP II Dual Input ph/orp Analyzer Model Option 1055-22-32 For additional information, please refer to the Instruction Manuals CD shipped

More information

4100ES-S1 Fire Indicator Panel Installation & Maintenance

4100ES-S1 Fire Indicator Panel Installation & Maintenance Fire 4100ES-S1 Fire Indicator Panel Installation & Maintenance Australian Australian Installation & Manual Maintenance Manual LT0394 Issue 1.9 Copyrights and Trademarks 2006, 2014 Tyco Australia Pty Limited.

More information

RMS/RPX Reader. User Manual

RMS/RPX Reader. User Manual RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,

More information

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual 24 Viceroy Road Unit #6 & 7 Concord, Ontario L4K2L9 Phone (905) 660-7210 FAX: (905) 660-7204 MS-2410BC Conventional Fire Alarm Control Panel Programming, Installation, Maintenance and Operating Instruction

More information

HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual

HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual NOTICE All information, documentation, and specifications contained in this manual are subject to change without prior notice

More information

Dual Input ph/conductivity Analyzer

Dual Input ph/conductivity Analyzer Instruction Sheet PN 51A-1055pHC/rev.I January 2006 Model 1055 SOLU COMP II Dual Input ph/conductivity Analyzer Model Option 1055-22-30 For additional information, please refer to the Instruction Manuals

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter W A R N I N G Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. TM

More information

Fire Control Panels. Addressable Fire Detection and Control Basic Panel Modules and Accessories. UL, ULC Listed, FM Approved* Features

Fire Control Panels. Addressable Fire Detection and Control Basic Panel Modules and Accessories. UL, ULC Listed, FM Approved* Features Fire Control Panels UL, ULC Listed, FM Approved* Features Basic system includes: Capacity for up to 1000 addressable IDNet points, up to 127 VESDA Air Aspiration Systems interface points and up to 254

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

CMP-2401B/CMP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual

CMP-2401B/CMP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual 10 Whitmore Road Woodbridge, Ontario L4L 7Z4 Phone (905) 856-8733 FAX (905) 856-9687 CMP-2401B/CMP-2402B Fire Alarm Control Panel Installation, Maintenance and Operating Instruction Manual P/N 50907:A1

More information

MR3CCUHV Temperature/Defrost Control

MR3CCUHV Temperature/Defrost Control Master Catalog 125 Temperature Controls Section A Product/Technical Bulletin Issue Date 0401 MR3CCUHV Temperature/Defrost Control The MR3CCUHV Temperature/Defrost Control is designed to control the temperature

More information

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays AEGIS Conventional Fire Alarm-Suppression Control Unit FEATURES Agency Approvals FM Approved FM Approved to ANSI/UL 864, 9th edition FM Approved to ULC-S527-99 Other domestic U.S. approvals/listings pending/

More information

SEE DISCLAIMER ON REVERSE

SEE DISCLAIMER ON REVERSE BOLTEK CORPORATION Lightning Detection GSM-1 Text Message Notification for EFM-100C Electric Field Monitor User Guide SEE DISCLAIMER ON REVERSE BOLTEK LIGHTNING DETECTION GSM-1 Text Message Alert Dialer

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions

DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions QUICK LINKS Mounting Location Guidelines Open the Sensor Mount the Sensor Sensor Components and Settings Wire the Sensor Wiring

More information

TrueAlert Notification Appliances

TrueAlert Notification Appliances TrueAlert Notification Appliances UL Listed; FM, CSFM and MEA (NYC) Approved* Non-Addressable Audible/Visible Notification Appliances with SmartSync Operation of Strobes and Horns Features Wall mount audible/visible

More information

Fire Control Panels. Network Annunciator Panels Network Display Unit (NDU) UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features

Fire Control Panels. Network Annunciator Panels Network Display Unit (NDU) UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features FIRE PL ALARM DOWN FIRE PL ALARM DOWN Event Time Enable Arm Di sable E mergency Operating Instr uctions Al ar m or War ni ng Co ndi ti on System indicator f lashing. Tone. How to nowledge / View Events

More information

4007ES Fire Control Panels

4007ES Fire Control Panels UL, ULC, CSFM Listed; FM, NYC Fire Dept Approved* Features Flexible standard combination of addressable initiation and addressable notification 4.3 (109 mm) Diagonal color touchscreen display: Convenient

More information

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions 574-052 Rev. F This page intentionally blank Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

TrueAlarm ES Analog Sensing

TrueAlarm ES Analog Sensing TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN Field Charger/Power Supply FCPS-S6 FCPS-S8 Document #977 8/06/0 Revision: C PN: 977:C ECN 0-96 Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute

More information

Fire Control Units. Addressable Fire Detection and Basic Control Unit Modules and Accessories. UL, ULC Listed, FM Approved* Features

Fire Control Units. Addressable Fire Detection and Basic Control Unit Modules and Accessories. UL, ULC Listed, FM Approved* Features Fire Control Units UL, ULC Listed, FM Approved* Features Basic system includes: Capacity for up to 1000 addressable IDNet points, up to 127 VESDA Air Aspiration Systems interface points and up to 254 addressable

More information

Table 1: dba Ratings for AMT Multitone Signal Typical Anechoic dba at 10 Feet per CAN/ULC S525-07

Table 1: dba Ratings for AMT Multitone Signal Typical Anechoic dba at 10 Feet per CAN/ULC S525-07 273 Branchport Avenue Long Branch, NJ 07740 (800) 631-2148 (USA) Thank you for using our products. (800) 397-5777 (CANADA) www.coopernotification.com GENERAL: INSTALLATION INSTRUCTIONS AMT MULTITONE APPLIANCES

More information

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001 SLATE Sub-Base Module R8001S9001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform

More information

AFP-100 Intelligent Fire Panel

AFP-100 Intelligent Fire Panel One Fire-Lite Place Northford, CT 06472 (203) 484-7161 (203) 484-7118 (Fax) AFP-100 Intelligent Fire Panel Installation, Programming and Operating Manual Document 51010 A 12/15/98 Revision PN 51010:A ECN

More information

Remote Booster Power Supply Technical Reference Manual

Remote Booster Power Supply Technical Reference Manual E Security Fire & Life Safety Remote Booster Power Supply Technical Reference Manual P/N 3100485 RE 3.0 ISS 06JUL07 Copyright Copyright 2007 E Security, Inc. ll rights reserved. This document may not be

More information

NetworX NX-548E Receiver Installation Instructions

NetworX NX-548E Receiver Installation Instructions NetworX NX-548E Receiver Installation Instructions Content Introduction... 1 Internal mounting... 1 External mounting... 2 Wiring... 3 DIP switch settings... 3 Power up... 3 Programming... 4 Testing and

More information

SYSTEM ENHANCEMENT MODULE

SYSTEM ENHANCEMENT MODULE SYSTEM ENHANCEMENT MODULE DSC PowerSeries INSTALLATION GUIDE INSTALL WIZARD AVAILABLE AT ALARM.COM/SEMPOWERSERIES OVERVIEW The System Enhancement Module (SEM) can be used with DSC PowerSeries PC1616, PC1832,

More information

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual Annunciators, 8 LED D7030X, D7030X-S2, and D7030X-S8 en Installation Manual Annunciators, 8 LED Notices en 3 1 Notices These instructions cover the installation of the D703X, D7030X-S2, and D7030X-S8

More information

R Series Remote Annunciators and Expander Installation and Operation Guide

R Series Remote Annunciators and Expander Installation and Operation Guide GE Security R Series Remote Annunciators and Expander Installation and Operation Guide P/N 3100969 REV 1.0 ISS 15JUL08 Copyright Copyright 2008 GE Security, Inc. All rights reserved. This document may

More information

4100U-S1 Fire Indicator Panel Installation & Maintenance

4100U-S1 Fire Indicator Panel Installation & Maintenance Fire 4100U-S1 Fire Indicator Panel Installation & Maintenance Australian Australian Installation & Manual Maintenance Manual LT0394 Iss 1.4 Copyrights and Trademarks 2006 Tyco Safety Products Christchurch,

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES MBD-00 FEBRUARY 00 MBUV-00D, MBUVS-00D MBIR-00D, MBFR-00D DIN RAIL MOUNT FLAMEWORX MODULES APPROVED Year 000 Compliant in accordance with BSI document DISC PD000-I:998 DESCRIPTION Fireye offers a complete

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

SECTION POWER SUPPLIES AND DISTRIBUTION

SECTION POWER SUPPLIES AND DISTRIBUTION SECTION 17460 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for Power Supplies and Power Distribution for Station communications. 1.02 REFERENCE STANDARDS A. American National Standards

More information

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand 5U Compact System Installation Manual V1.0 Manufactured by Enatel Ltd. 321 Tuam Street PO Box 22-333 Christchurch New Zealand Phone +64-3-366-4550 Fax +64-3-366-0884 Email sales@enatel.net www.enatel.net

More information

HPFF8(E)/HPFF8CM(E) NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

HPFF8(E)/HPFF8CM(E) NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL HPFF8(E)/HPFF8CM(E) NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL P/N 53499:B3 ECN 16-562 10/5/2016 Fire Alarm & Emergency Communication System Limitations While a life safety

More information

FTP-1000 Touchpad/Display Installation Manual

FTP-1000 Touchpad/Display Installation Manual FTP-1000 Touchpad/Display Installation Manual A B 1 2 3 4 5 6 7 8 9 0 * # Stay Away Disarm Quick Exit C D P/N 466-2231 REV B January 2011 Copyright Disclaimer Trademarks and patents Manufacturer Intended

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

4010 Fire Alarm PC Programmer Installation and Programming Instructions

4010 Fire Alarm PC Programmer Installation and Programming Instructions 4010 Fire Alarm PC Programmer Installation and Programming Instructions 574-187 Rev. C Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights reserved. Printed in the United States

More information

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack Master Catalog 125 Temperature Controls Section A Product/Technical Bulletin Issue Date 1098 MR4PMUHV Electronic Temperature/Defrost Control with Relay Pack The MR series temperature controls are designed

More information

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy

More information

Fire Alarm Control Panels MS-2 & MS-4 MS-2E & MS-4E. Instruction Manual. Document /6/2014 Rev: G3 P/N 51512:G3 ECN

Fire Alarm Control Panels MS-2 & MS-4 MS-2E & MS-4E. Instruction Manual. Document /6/2014 Rev: G3 P/N 51512:G3 ECN Fire Alarm Control Panels MS-2 & MS-4 MS-2E & MS-4E Instruction Manual Document 51512 8/6/2014 Rev: G3 P/N 51512:G3 ECN 14-523 Fire Alarm & Emergency Communication System Limitations While a life safety

More information

RC802/ B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual

RC802/ B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual RC802/804-240B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual Raisecom Technology Co., Ltd. (04/2005) 1. Cautions Please read the following notices carefully before installing and using the device,

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

Albeo TM LED Luminaire Accessory (Emergency Battery Backup Module)

Albeo TM LED Luminaire Accessory (Emergency Battery Backup Module) E Lighting Installation uide Albeo TM LED Accessory (Emergency attery ackup Module) EFOE YOU EI ead these instructions completely and carefully. ead and follow appropriate Lumination LED Installation uide

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

FIRE STROBE 2000 INSTALLATION INSTRUCTIONS

FIRE STROBE 2000 INSTALLATION INSTRUCTIONS FIRE STROBE 2000 INSTALLATION INSTRUCTIONS I. SITE INSPECTION FOR INSTALLATION A.P.I voice: (858) 292-1561 web: http:// www.firestrobe.com 1. Carefully inspect the area where the Fire Strobe 2000 will

More information

The RPT-485W/RPT-485WF

The RPT-485W/RPT-485WF 12 Clintonville Road Northford, CT 06472 203/484-7161 FAX: 203/484-7118 The RPT-485W/RPT-485WF EIA-485 Annunciator Loop Repeater for Twisted Pair Wiring/Fiber Optic Cable Document 15640 08/13/97 Revision:

More information

GE Security Fire & Life Safety F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet

GE Security Fire & Life Safety F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet GE Security Fire & Life Safety F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet Description The F-DACT(F) is a digital alarm communicator transmitter for F-series fire alarm control

More information

R-Series Remote Annunciators and Expanders Installation and Operation Guide

R-Series Remote Annunciators and Expanders Installation and Operation Guide R-Series Remote Annunciators and Expanders Installation and Operation Guide P/N 3100969-EN REV 05 ISS 06MAY13 Copyright Trademarks and patents Manufacturer Version FCC compliance Contact information 2013

More information

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification Dual Technology Wall Switch Occupancy Sensor Manual & Specification PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL ELECTRICAL CODES Douglas Lighting Controls Page 1 November 19, 2014 1. INTRODUCTION

More information

HARDwired Installation/ Owner s Manual

HARDwired Installation/ Owner s Manual HARDwired Installation/ Owner s Manual Use this manual for circuit - Revision L or higher. For Models:,, and Multi-Door Access Controller Wiegand Compatable --R-- Provides Access Control System to manage

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

Code 542 Peltier Rack User's Guide

Code 542 Peltier Rack User's Guide Code 542 Peltier Rack User's Guide LT2544/ 1999 Gilson, Inc. All rights reserved June 1999 Table of Contents page Introduction...1-1 Unpacking...1-2 Customer Service...1-3 Technical Specifications...1-4

More information

Installation Instructions

Installation Instructions Installation Instructions S E C U R I T Y S Y S T E M Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations

More information

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual

HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual HCA Series Conventional Fire Alarm System (HCA-2, HCA-2D, HCA-4, HCA-4D, HCA-8, HCA-8D) Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA90621-2268

More information

PowerLogic Branch Circuit Power Meter (BCPM)

PowerLogic Branch Circuit Power Meter (BCPM) PowerLogic Branch Circuit Power Meter (BCPM) Panel Board Monitoring System Installation Guide Branch Circuit Power Meter (BCPM) HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and

More information

as required for residential sprinklers intended for use in dry pipe systems.

as required for residential sprinklers intended for use in dry pipe systems. Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Residential Dry Pipe System General Description The TYCO RAPID RESPONSE Residential Dry Pipe System provides a normally dry system for areas subject

More information

Wireless ShatterPro Acoustic Sensor Installation Instructions

Wireless ShatterPro Acoustic Sensor Installation Instructions Wireless ShatterPro Acoustic Sensor Installation Instructions Introduction This is the Wireless ShatterPro Acoustic Sensor Installation Instructions for models (3 V) and (9 V). The sensor is designed to

More information

D2071A. Operation & Installation Guide Fire Alarm Control Panel

D2071A. Operation & Installation Guide Fire Alarm Control Panel D2071A EN Operation & Installation Guide Fire Alarm Control Panel D2071A Operations & Installation Guide Contents Contents 1.0 Overview... 4 1.1 Communicator... 4 1.2 RFI and Lightning Protection... 4

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

INSTALLATION GUIDE. AXIS A1001 Network Door Controller

INSTALLATION GUIDE. AXIS A1001 Network Door Controller INSTALLATION GUIDE AXIS A1001 Network Door Controller Liability Every care has been taken in the preparation of this document. Please inform your local Axis office of any inaccuracies or omissions. Axis

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

# amp # amp 12/24 VDC POWER SUPPLY INSTALLATION MANUAL. 4202/4MA, Rev. E 0804

# amp # amp 12/24 VDC POWER SUPPLY INSTALLATION MANUAL. 4202/4MA, Rev. E 0804 #4202 2 amp #4204 4 amp 12/24 VDC POWER SUPPLY INSTALLATION MANUAL 4202/4MA, Rev. E 0804 4202/4204 Power Supply Fused 115 V Input Low Battery Indicator DC Output Adjustable 0.7 to 3.7 Volts from nominal

More information

Fire Alarm Control/Communicator

Fire Alarm Control/Communicator Fire Alarm Control/Communicator Operation and Installation Guide Power Alarm Trouble Silenced Radionics FIRE CONTROL/COMMUNICATOR R 31499F Page 2 2000 Radionics. Contents Contents 1.0 Notices... 9 1.1

More information

META SMK-9000 EXHAUST GAS MONITORING SYTEM FOR IN-LINE ENGINES (12 CYLINDERS)

META SMK-9000 EXHAUST GAS MONITORING SYTEM FOR IN-LINE ENGINES (12 CYLINDERS) 1 META SMK-9000 EXHAUST GAS MONITORING SYTEM FOR IN-LINE ENGINES (12 CYLINDERS) 2 COPY RIGHT AND TRADEMARK STATEMENT 1998 META -IMPROVING TECHNOLOGIES - LTD. ALL RIGHTS RESERVED No part of this manual

More information

Remote Relay Module (RRM)

Remote Relay Module (RRM) Remote Relay Module (RRM) Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like

More information