Type TEC, Transformer Electronic Control System

Size: px
Start display at page:

Download "Type TEC, Transformer Electronic Control System"

Transcription

1 Type TEC, Transformer Electronic Control System Technical, installation, operating, maintenance and service manual for TEC cabinet and sensors 1ZSC en, Rev. 3,

2 We reserve all rights in this documents and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. Copyright 2004 ABB

3 Contents 1 Technical manual Scope System architecture TEC functionality Hardware Cabinet Electronic boards and terminals Power supply Processor Analogue input 4-20 ma Temperature input Pt Digital input Control and output Motor relay TC Alarm box Display Performed tests EMC (Electro Magnetic Compability) tests Mechanical tests, vibration and seismic Climate tests Trip, alarm and warning output from TEC Output signals from TEC cabinet Alarm/Warning output options Trip output options Connection of devices in parallel both traditionally and to TEC Ordering data Load test 34 2 Installation manual Connection table Sensors Air temperature Oil temperature Use of TEC bottom oil sensor Current transducer Hydrogen gas in oil Moisture in oil sensor Cables and earthing Pt ma and Digital In RS Fibre optic Cable entry and Roxtec PC 40

4 3 Operating manual Start sequence Display on cabinet Status light Warning, Alarm and Trip signal TEC during transformer test Sensor failure Sensor failures influence on functions Other back-ups in case of failures 44 4 Maintenance and service manual Loading of new program in TEC Hardware needed and connections Trouble-shooting Replacement of board Spare part list 47 5 Contact list ZSC en, Rev. 2

5 1 Technical manual 1.1 Scope This manual describes all aspects of the Control IT Transformer Electronic Control (TEC), version The information is grouped into two manuals: one covering TEC cabinet with sensors, and one covering the interface. This means that information on a specific item, such as a temperature sensor, is given in several places. Information that is needed at a specific occasion is in some cases gathered in a separate section, but it is recommended that all users have a general knowledge of TEC functions and read through both manuals. 1.2 System architecture Transformer Cabinet and Sensors TEC CABINET ON CABINET Di splay ALARM WARNING NORMAL Standard 3 dry contacts for: Trip Alarm Warning TEC CABINET TEC CABINET ON CABINET TEC Display CABINET ALARM ON CABINET WARNING TEC Display CABINET ALARM ON CABINET NORMAL WARNING Display ALARM ON CABINET NORMAL WARNING Display ALARM NORMAL WARNING NORMAL Fibre Optic Bus Option Relay box with 6 dry contacts to distinguish between Alarms TEC PC in station Electric Bus TCP/IP Remote PC with Internet Explorer Connections LAN (standard) Modem (special option) SCADA Data from all sensors on a transformer are collected by TEC. The sensors are grouped in four types: Temperature sensors for oil and ambient air (Pt 100) Analogue sensors to measure quantities such as load current or amount of hydrogen gas in oil (4-20 ma) Digital sensors indicating an on-off status, e.g. contacts of a sudden pressure relay Position sensor (resistor bridge) for tap-changer position. The sensor information is brought into the processor via input cards, one card for each of the three sensor types. The processor contains a detailed mathematical model of the transformer including measured data at the heat run test. Taking actual oil temperature and load conditions into account, TEC calculates the hot-spot temperature. As a result of the temperature calculations, TEC starts and stops the coolers and even prepares for rapid load increases. This is done with a separate board with small relays. This board is placed in connection with the cooler contactors in the transformer control cabinet and communicates with the TEC processor via a data bus in order to simplify the wiring. TEC can be connected to a traditional control system and operate contacts in those circuits, e.g. to give a trip signal. 1ZSC en, Rev. 2 5

6 A status light on front of the TEC cabinet indicates the status of the transformer and the most important measured and calculated values are also displayed there. However, the major user interface is via a PC, normally located in the station control room. The monitoring and control functions run continuously in the processor independently of the connection to the PC user interface. The PC stores all historical data about the transformer and it is possible to analyse the transformer condition in detail, e.g. accumulated ageing of the insulation and time to next service of the tap-changer. The PC also contains simulation programs for overload and other emergency situations. Remote access to TEC and connection of TEC to a superior control system will be possible in the future, as the PC has an OPC server. 1.3 TEC functionality The following functionality is available in TEC version 1: Hot-spot calculation Winding hot-spot will be calculated to fulfil both IEC and IEEE. Calculations can be made for 3 windings simultaneously: high voltage, low voltage and tertiary windings. The calculations are made according to: ON (Oil Natural) cooled transformers Θ h = Θ o + Hg r K y OF (Oil Forced) and OD (Oil Directed) cooled transformers Θ h = Θ b + 2[ Θ imr - Θ br ]K y + Hg r K y It should be noted that under certain load conditions the top oil temperature can be higher then the hot-spot temperature. Correction on OD-cooled transformers Θ h = Θ h (Θ h - Θ hr ) For an OD-cooled transformer a correction has been applied to the result of the OFequation in case of Θ h - Θ hr >0 In IEC the criteria is K>1. (In case of loads exceeding 100 % rated current) The intention of this must however been to correct when the actual hot-spot temperature exceeds the one measured during test. Θ o = Top oil temperature Hg r = Hot-spot to top-oil gradient K = Load factor (load current/rated current) y = Winding exponent Θ imr = Average oil rise (rated conditions) Θ br = Bottom oil rise (rated conditions) Θ b = Bottom oil temperature = Rated hot-spot temperature Θ hr The hot-spot values are shown on the TEC cabinet display. If an interface exists, the values will be stored and shown there. (See the manual for the interface.) 6 1ZSC en, Rev. 2

7 Transformer top and bottom oil temperature The top and bottom oil temperature will be shown on the TEC cabinet display. If an interface exists, the values will be stored and shown there. (See the manual for the interface.) Cooling Control The cooling will be controlled from - Top oil temperature - Hot-spot temperature - Forecast on the hot-spot made from actual load and ambient temperature. The cooling control aims to keep the transformer at a fairly constant temperature. Up to 6 independent cooling groups can be controlled. A logic control that all cooler groups are evenly used. All cooler groups are started at least each week. There is a delay (10 seconds) between start of cooler groups to avoid that all start at the same time that can create a pressure pulse in the transformer or a peak consumption of power. If TEC of some reason stops to work or the connection between TEC and the motor relay is broken all cooling will start. A traditional top oil thermometer will start all cooler groups if the TEC system for some other reason does not work. Service prediction cooling equipment The time each cooling group has been in operation is measured and displayed in the station interface. It can be used to predict when service is needed. A log is also available to see events related to the cooling equipment. Ageing The ageing from the warmest winding hot-spot is calculated during service according to IEC if normal craft paper is used in the winding or according to IEEE if thermally upgraded paper is used. The actual ageing speed is displayed in %. The accumulated ageing is also calculated and displayed in years. The calculations are made in the TEC processor and the accumulated ageing is also stored there. (See the manual for the interface.) The accumulated ageing and the ageing speed are displayed in the interface. (See the manual for the interface.) 1ZSC en, Rev. 2 7

8 tec_0086 Ageing graph Example: Winding hot-spot temperature 98 C F IEC = 1 Ageing speed 100 % If the hot-spot temperature increases 18 C to 116 C F IEC = 8 Ageing speed 800 %. The ageing speed is eight times faster compared to the one at 98 C. If the hot-spot temperature decreases 18 C to 80 C F IEC = Ageing speed 12.5 %. The ageing speed is 12.5 % of the one at 98 C. Hydrogen equivalent detection This function will received a signal from a hydrogen detector which is a gas-in-oil detector that is sensitive to H 2, CO, C 2 H 2 and C 2 H 4. The resulting value is an H 2 - equivalent ranging from ppm. The result will be shown in the display. Electrical data will be stored in the interface. (See the manual for the interface.) Tap-changer contact wear The contact wear function will keep track on how many operations has been done on each contact, and calculate the wear. The wear on the contacts are stored in the TEC processor. From that information it will calculate the number of operations and time to next service/ contact exchange. As those events are approached there will be warnings, and if actions not are taken in due time for the contact exchange there will be alarms. This function provides prediction and a reminder when overhaul and contact exchange are needed. The results are shown in the interface. (See the manual for the interface.) The warning and alarm signal will also appear on the cabinet status lights. Transformer temperature balance (optional) The transformer temperature balance function will keep track on the temperature in the transformer and compare with the theoretically calculated temperature. The default setting is that, if the average transformer temperature becomes more than 15 ºC higher than expected for 24 h, there will be an alarm. The function can indicate a cooling problem at lower load conditions before the problem gives a warning due to high top oil temperature. The calculated temperatures shall be used as references to the actual temperatures over a longer time. Note that the temperature balance does not support all types of cooler configurations. (See ordering data help.) 8 1ZSC en, Rev. 2

9 Tap-changer temperature balance (optional) This function calculates if there is excessive heat generation in the tap-changer. At normal conditions there is a known balance between the theoretical calculated losses in the tap-changer and the heat transferred from the tap-changer to its surroundings. The default setting is that, if the average temperature in the tap-changer is more then 15 ºC above the calculated value for 24 h there will be an alarm. Moisture in transformer oil detection This function will receive a signal from a moisture sensor. The value in ppm will be shown in the TEC display and in the PC interface. It is possible to set a warning and alarm level for the moisture content in the order data sheet. Overload capacity (optional) A prediction of the maximum allowed load under the existing ambient conditions is displayed in the main interface. At this loading the top oil and hot-spot temperature should not exceed preset values in the order data sheet. Voltage measurement The voltage on the high voltage side can be displayed. The values will be shown in TEC Monitor. Historical values can also be displayed in TEC Monitor. Tap-changer temperature The temperature in the tap-changer is measured and stored. This temperature can easily be compared to the transformer and outdoor temperature, to see that the situation is stable. In the same graph the load can be displayed. Some rules are also described in the chapter about operations. The temperature in the tap-changer(s) is measured and shown on the TEC display. Tap-changer position This function displays the tap-changer position on the cabinet display as a number. In the station interface it is optionally possible to convert into another format. (See the manual for the interface.) Cabinet conditions This function reads the temperature and the relative humidity on the processor board in the cabinet. The readings will be available both as a conditions at the present time, but also as a histogram showing the frequency of the different temperatures and humidities. Load forecasts In the station interface it is possible to do load forcasting on hot-spot and top oil temperatures. (See the interface manual.) Event log (See the interface manual.) Documentation (See the interface manual.) Provided on a CD. Tap-changer service videos (See the interface manual.) 1ZSC en, Rev. 2 9

10 1.4 Hardware Cabinet tec_0097 Power supply Universal VAC, 50/60 Hz, and VDC. It is recommended to connect both AC as main supply and DC from station battery as spare supply. It is also possible to connect 2 different AC supplies. TEC will automatically switch without interruption in case of outage on any of them. Front panel Push button to control the LCD display Rolling LCD display showing top-oil temperature, up to three hot-spot temperatures, bottom oil temperature, load, tap-changer position, tap-changer temperature and hydrogen content (if applicable). Temperatures are displayed in both Celsius and Fahrenheit Status light with three lamps (green/yellow/red) 10 1ZSC en, Rev. 2

11 Environmental Operation temperature to +55 C (-40 to 122 F) Degree of protection... IP 54, according to IEC Temperature cycling tested to +70 C, 90% humidity according to IEC , -2,-3 and -5 Dimensions (mm)... Width 500, Height 600, Depth 300 Weight kg EMC compliance... IEC or higher Vibration tested... IEC ,-2, -3 and IEC , -27, -29 Temperature cycling... IEC Max cable area to terminals mm² Max cable area to temperature input Pt mm² Input parameters 8 insulated analogue 4-20 ma via terminals, for current transformers, sensors etc. 4 insulated Pt100 direct inputs, for temperature sensors 12 insulated digital input via terminals, for fan motor status, alarm / trip signals etc. Input tap-changer position transmitter R tot 80 W Amount of input signals can be increased Output parameters 3 outputs for alarm, warning and trip signals 6 outputs to start cooler groups (fans) Permitted load breaking capacity on output terminals AC 250 V 8 A, DC 125 V 0.1 A L/R=7ms, DC 30 V 5 A Fibre optic cable The connection between TEC and the station computer is made via optic cable. 1ZSC en, Rev. 2 11

12 Extra roof Status lights Display Lamps Space for extra boards Electronic boards 24 V power supply Standard terminals Heater Space for extra terminals tec_0045 Cable entry Status light Red indicates Alarm or Trip Yellow indicated Warning Green indicates Normal 12 1ZSC en, Rev. 2

13 Display on cabinet tec_0063, tec_0073 Displayed information A TOP OIL B1HOT-SPOT HV B2HOT-SPOT LV C BOTTOM OIL D LOAD E OLTC POSITION F OLTC TEMP1 G HYDROGEN H2 MOISTURE TRAFO MOISTURE OLTC Heater The heater in the cabinet is connected to TEC s AC supply. It is designed for an AC supply of V. Depending on the temperature in the cabinet it can give a heating power between W. (At -30 C the heating power is 135 W.) Lamp The 2 lamps in the cabinet are standard lamps for lorries 24V, 10W. 24V power supply The 24 V power supply is only intended to supply the lamps. 1ZSC en, Rev. 2 13

14 Standard terminals tec_0046 Power supply Data communication Analogue input Digital input Control and output Cable between TEC and transformer cabinet The cable is supplied to make an easy connection between the transformer cabinet and TEC. It is up to the transformer manufacturer to use the the provided cabling as they see fit. The shielded cable A is intended to use for the RS 485 connection to the motor board. There are 2 more shielded cables and 24 single conductors in the cable. Connection to transformer control cabinet. Hole PG29 (D = 38 mm) tec_0047 Connection to TEC cabinet 14 1ZSC en, Rev. 2

15 For cable Ø mm (5x) Cable sealing (option) For cable Ø mm (14x) Connection to transformer control cabinet Optic fibre Ø 9 1) Standard cable entrance plate Earthing terminal M A M A tec_ ) Mounting holes on the transformer. 25 1ZSC en, Rev. 2 15

16 1.4.2 Electronic boards and terminals The electronic boards are mounted on a back-plane providing internal communication and power supply between the boards. Connection to external power and signal sources is normally done via the terminals at the bottom of the cabinet. A sign with the connection table is placed on the inside of the TEC cabinet door. The boards are placed in the following order from left to right: Power supply board, TC 110 Processor board, TC 121 Analogue input 4-20 ma board, TC 130 Temperature input Pt 100 board, TC 140 Digital input board, TC 150 Control and output board, TC 160 To the right of these standard boards, there are three extra slots for temperature input Pt 100 boards and/or digital input boards. The standard set-up also comprises: Motor relay board, TC 180, in the transformer control cabinet Alarm box 1, TC 181 Alarm box 2, TC 182 Display board, TC 170, at the front of the TEC cabinet Power supply TEC can work with either AC or DC power supply. It is recommended to connect both AC as main supply and DC from the station battery as back-up. It is also possible to connect 2 different AC supplies. The power supply board will automatically switch between the two supplies without interruption if one fails. The power consumption of the electronic boards is <20 W plus the consumption of sensors. The cabinet heater element is connected to the input AC supply and it has a current peak of approximately 8 A for some seconds each time it starts. It is recommended to have at least a 10 A fuse. The terminals can be disconnected by moving the orange part downwards V AC (or DC) input via terminal group X V DC (or AC) input via terminal group X2 24 V DC output via terminal group X3 to TEC display and current transducers tec_0048 tec_ ZSC en, Rev. 2

17 Terminal group X1 1 Input V AC 50/60 Hz line voltage. 2,3 Output AC line voltage. Connected to X1:1 and is always energized, even if the terminal disconnection bar is moved to the disconnected position. Can be used to supply special sensors with power. 4 Input AC neutral. 5, 6 Output AC neutral. Terminal group X2 1 Input V DC positive. 2 Input V DC negative. Dangerous voltage! WARNING Terminal group X3 1 Output 24 V DC positive from the power supply board. The display (1.6 W) is internally wired to this supply. Up to 3 current transducers can also be connected here. Maximum total load on this supply is 5 W. 2 Output 24 V DC negative from the power supply board. Up to 3 current transducers can also be connected here, 3 Input 24 V DC positive from a separate 24 V supply unit in the TEC cabinet (connected at delivery). This power feeds the cabinet light. 4 Output 24 V DC positive from X3:3. This terminal is used to energise 4-20 ma sensors. 5 Input 24 V DC negative. 6 Output 24 V DC negative from X3:5. 1ZSC en, Rev. 2 17

18 Processor LEDs: green and red RS 232 DIN connection for system administration (loading new code) Fibre optic input, ST connector from station PC Fibre optic output, ST connector to station PC RS 485 connection to display board and motor relay board via terminal group X11 tec_0096 tec_0050 Terminal group X Shall not be used (RS 422 connection) 5 RS 485 connection A to motor relay board. 6 RS 485 connection B to motor relay board. 18 1ZSC en, Rev. 2

19 Analogue input 4-20 ma 4-20 ma input via terminal group X11 tec_0034 tec_0050 The sensors are calibrated and assigned to their terminals at delivery, see sections 9.1 Ordering data and TEC. If a new calibration is needed, see TEC Monitor manual, 1ZSC The 3 current transducers can take the 24 V DC supply from X3:1 and 2. Power supply for other sensors that requires 24 V DC shall be provided by the transformer manufacturer. Terminal group X Current High Voltage 3 4 Current Low Voltage 5 6 Current Tertiary Voltage 7 8 Tap-changer temperature from moisture sensor (can have other power supply than 24 V DC) 9 10 Tap-changer moisture in oil sensor (can have other power supply than 24 V DC) Transformer temperature from moisture sensor (can have other power supply than 24 V DC) Hydrogen (can have other power supply than 24 V DC) Transformer moisture in oil sensor (can have other power supply than 24 V DC) 4-20 ma sensor 24 V tec_0015 1ZSC en, Rev. 2 19

20 Temperature input Pt 100 In order to improve the measuring accuracy, Pt 100 temperature sensors are connected directly to the front of the board, not via terminals at the bottom of the cabinet. This connection is designated Terminal group X31. If one or more extra boards are needed, they will be placed after the standard boards and the terminal groups will be designated X32, X33 etc. Pt 100 sensors are calibrated at delivery and need no recalibration. Terminal group X31 Pt Ω tec_0016 Current Feed Measure Top oil Bottom oil Air in shadow tec_0051 tec_0034 Position X Air in sun Terminal group X32 Pt Ω tec_0016 Current Feed Measure Tap-changer 1 Tap-changer 2 Tap-changer tec_0051 tec_0034 Position X Tap-changer 4/Core yoke 20 1ZSC en, Rev. 2

21 Digital input tec_0034 tec_0046 The digital input board interprets relay signals of two different types: Function confirmation that a device is running properly, where an open relay contact means that the device is not running and a closed contact indicates that it is running. Example: Oil flow indicator in a cooler circuit. In case of TEC cooling group control the feedback from each cooler group needs to be connected to TEC. The input shall be placed first of all input X41:1 and following. Warning, alarm and trip devices, where an open relay contact means a normal function and a closed contact shall release a warning, alarm or trip signal. Example: Sudden pressure relay. For each contact connected to the digital input board, the type is defined by data entered to the ordering data sheet. This information is then stored if an interface exists. (See the interface manual.) +24 V +24 V (+24 V) Neutral Test = Terminals Terminals and boards Sensor contacts tec_0012 1ZSC en, Rev. 2 21

22 Terminals 1-8 are available for warning and alarm contacts, e.g. the oil level detector and Bucholz relay (warning levels). Any of these eight terminals can also be used for function confirmation type contacts. In that case, the related contacts from each cooler group shall be connected in series to the same terminal, e.g. the auxiliary contact on a fan motor contactor and the oil flow indicator of the same cooler group. When TEC controls the coolers, each cooler group shall give a function confirmation signal to the digital input board. The digital input board feeds +24 V DC to the terminal and also measures the voltage at the terminal. As long as the sensor contact is open, the voltage is maintained and the status of warning/alarm signals is ok. The status of function signals is not running, which also is ok as long as the cooler group is not switched on. When a sensor contact is closed, the voltage supply from the board cannot maintain the 24 V, the measured voltage drops to zero and for warning/alarm inputs, an error signal is released. Function inputs change status to running. The warning/alarm signal is released (or the function changes to running ) when the measured voltage is below 8 V. +24 V +24 V Neutral +24 V (+24 V) Neutral Terminals and boards Trip relay coil tec_ V tec_ V Terminals 9-12 are available for sensor contacts which normally are used to trip the transformer, e.g. sudden pressure relay and Bucholz trip contacts. This example shows how two sensor contacts, a 110 V battery and the trip relay coil are connected. As long as all sensor contacts are open, the measured voltage is 110 V and the status is ok. If one contact closes, the 110 V circuit is closed, the current through the trip relay coil trips the transformer and the measured voltage at the terminal drops to zero. The battery voltage also disappears from the other terminals, but there the 24 V supply from the board maintains the measured voltage above 8 V. Any of the twelve terminals will activate a warning, an alarm or a trip signal from TEC via the output auxiliary relay contacts of the Control and output board, section If more than 8 warning/alarm/function or 4 trip sensors are used, one or more extra boards are needed. The terminal groups will be placed at the lower terminal row and designated X42, X43 etc. 22 1ZSC en, Rev. 2

23 Terminal group X41 Each sensor is connected to one of the terminals 1-12 and one of the neutral terminals Input warning/alarm and function sensor contacts Input trip sensor contacts Shall not be used Input neutral. Each terminal number represents two terminals, one at the upper side and one at the lower side. 25 Shall not be used. 26 Input positive DC from battery and trip relay coil according to sketch above. Voltages above +220 V DC and negative voltages are not permitted Shall not be used. 29 Input neutral from battery and trip relay coil. 30 Shall not be used. See chapter 1.6 for the trip and alarm/warning functionality. 1ZSC en, Rev. 2 23

24 Control and output tec_0048 tec_0046 This board is used to make relay signals. Terminal group X51 1 Output disconnectable terminal in series with terminal 14 (Disconnected in downwards position.) 2-3 Input voltage measurements. Nominal voltage V AC. Neutral on Input tap-changer position transmitter, 4 = max position, 5 = moving contact, 6 = min position. R tot 80 Ω. 7-9 Output. Not used in this version. 10, 12 Output dry contact for warning 11, 12 Output dry contact for alarm 13, 1 Output dry contact for trip. This output also have a contact that can be disconnecte at terminal 1. These contacts are wired to the digital board to get one trip output on X41:26 and tec_0017 Dangerous voltage! WARNING Permitted load (breaking capacity) on output terminals: AC 250 V 8 A DC 125 V 0.1 A L/R = 7 ms DC 30 V 5 A 24 1ZSC en, Rev. 2

25 Motor relay TC180 Power +24 V 0 RS 485 A RS 485 B Cooler group tec_ LEDs tec_0055 tec_0054 The motor relay board TC 180 is placed in the transformer control cabinet. All fans and pumps of one cooler group shall be connected so that they are started by one relay output. Up to six separate groups can be controlled. If the RS 485 connection to TEC is lost, all relays will close automatically one by one with 10 seconds intervals. It is recommended to supply the motor relay board with 24 V DC from the transformer cabinet to ensure that all motors start even if the entire connection to TEC is broken. If the power supply to TEC is disconnected the motor relay board starts all cooler groups. To avoid this when the transformer is out of service, first disconnect contact with the 24V supply to the motor board. The power supply to TEC should also be connected before the 24V power supply to the motor board to avoid that the coolers starts. A traditional top oil thermometer is also recommended to be used as a back-up together with this version of TEC. It shall be set to start all cooler groups 5 ºC above the highest start temperature in TEC. The permitted load on the relays is the same as on output terminals of the control and output board. 1ZSC en, Rev. 2 25

26 Alarm box Power +24 V 0 RS 485 A RS 485 B Alarm signals tec_ LEDs tec_0055 tec_0054 The alarm box can be used get dry contact output from specific alarms in TEC. The alarm box can be placed in the transformer cabinet. The two extra shielded cables in the big cable between TEC and the transformer cabinet. There are 2 different alarm boxes available. No connection should be made to the signals that not used. Permitted load (breaking capacity) on output terminals: AC DC DC 250 V8 A 125 V0.1 A L/R=7 ms 20 V 5 A Only one type of alarm relay box can be used. The alarm box, TC182, can either be placed in the TEC or in the transformer cabinet. The power suply can be taken from either the 24 V output from TC110 or any other 24 V source. The communication cables can be parallel wired with the communication to the cooler box. Closed relay is represented by a lit LED. 26 1ZSC en, Rev. 2

27 TC V 0 V On Common A Data communication 1 B Top-oil alarm 2 Hot-spot alarm 3 OLTC temperature 4 OLTC maintenance 5 Cooler error 6 Loss of com to TEC Top-oil alarm Hot-spot alarm OLTC temperature OLTC maintenance Cooler error Loss of comm. to TEC Top-oil temperature alarm Hot-spot temperature alarm OLTC temperature or OLTC temperature balance Exchange or service is needed Cooler problem or transformer temperature balance event No communication between alarm box and TEC (for example wiring, power or system failure of TEC). The relay is closed when the box have power but no communication to TEC. The other relays will be open. There is a 20 second delay Display The display board TC 170 is connected to the processor board at delivery. tec_0073 tec_0057 1ZSC en, Rev. 2 27

28 1.5 Performed tests EMC (Electro Magnetic Compability) tests Immunity according to EN :1999 Radiated RF field IEC/EN (1995), ENV50204 (1995) Conducted RF voltage IEC/EN (1996) Fast transient/burst IEC/EN (1995) Electrostatic discharge (ESD) IEC/EN (1995/96) Surge IEC/EN (1995) LF magnetic field 1 IEC/EN (1993) Additional immunity tests Damped Oscillatory Wave 1 IEC/EN (1995), SS Spark 1 SS Power voltage variations 1 IEC SC77AWG 6 (info. Annex) Emission according to EN :1993 Radiated emission CISPR 11 (1997), EN (1998) Conducted emission CISPR 11 (1997), EN (1998) 1) This method is not within the scope of the laboratory accreditation. Emission Port Class Limits Result 1 Radiated emission Enclosure A limits of EN increased by 10 db for 10 m measure distance in accordance with EN Passed Conducted emission AC mains A limits of EN Passed Immunity Immunity port Process I/O ports Mains port 1) Passed = Complied with the specification. Failed = Did not comply with the specification. See relevant chapter for details. Criteria, see chapter 4.4 Criteria for approval. Earth ports Result/ Criteria 1 Radiated RF fields 15 V/m Passed/A Conducted RF voltage - 10 V 10 V 10 V Passed/A Electrostatic discharge 8 kv contact 4 kv 4 kv 4 kv Passed/A 15 kv air Surge pulse - 4 kv (CM) 4 kv (CM) - Passed/A 2 kv (CM) Power frequency magnetic field 1000 A/m Passed/A Power voltage variations - - -/+ 10 %, 15 s - Passed/A Damped oscillatory wave- 2.5 kv 2.5 kv - Passed/A Fast transient/spark - 4 kv - 8 kv 4 kv - 8 kv - Passed/A 28 1ZSC en, Rev. 2

29 1.5.2 Mechanical tests, vibration and seismic The TEC unit manufactured by ABB in Sweden have been subjected to mechanical testing as specified in chapter 3. The results of the testing are given below: Test Specifications Severity Result Vibration IEC IEC Hz, 2 g, 20 sweep cycles OK Bump IEC IEC g, 16 ms, 6 x 1000 bumps OK Shock IEC IEC g, 11 ms, 6 x 3 shocks OK Seismic IEC IEC Hz, 7.5 mm/2 g, 1 sweep OK OK: No malfunctions was observed during the test and no damage was observed after the test Climate tests Test Severity Duration Standard Dry heat Operational +85 C 72 hours IEC , Test Bd Cold Operational -40 C 72 hours IEC , Test Ab Change of temperature Operational -40 to +70 C 3 cycles t = 2 h 3 C/min IEC , Test Nb Damp heat steady state Operational +40 C, >93 % non condensing 4 days IEC , Test Ca Damp heat cyclic Operational +25 to +55 C, >93 % condensing 6 cycles à 24 hours IEC , Test Dd 1ZSC en, Rev. 2 29

30 1.6 Trip, alarm and warning output from TEC Output signals from TEC cabinet Optic fibre, all information Sum Trip signal from X41 from all signals connected to X41 trip positions and the internal TEC trip from X51. The internal TEC trip can be disconnected. One Alarm signal from TEC X51. Top oil, hot-spot contact exchange, tap-changer temp etc. One Warning signal from TEC X51. Top oil, hot-spot, tap-changer service, tap-changer temp etc. Alarm box Relay box with 6 dry contacts to distinguish between Alarms Alarm/Warning output options Alarm/Warning option 1 From devices connected to TEC there will be one alarm signal from X51:11 and 12, and the warning signal from X51:10 and 12. Alarms and warnings from TEC functions will also be connected to these contacts. Via the optic fiber the interface PC will have the details about the alarm and warning signals from the devices and TEC in the event log. Option 1, TEC option Buchholz Device Connected to TEC Connected devices, hot-spot, top oil and other alarm and warnings from TEC Terminal X51 Substation Control 2 cables for Alarm and Warning from TEC Gets a Alarm or Warning from contacts Gets a Alarm or Warning from TEC Details found in TEC Warning output Alarm output 30 1ZSC en, Rev. 2

31 Alarm/Warning option 2 No devices connected to TEC. Alarms and warnings from TEC functions will have the alarm signal from X51:11 and 12, and the warning signal from X51: 10 and 12. Via the optic fiber the interface PC will have the details about the alarm and warning signals from TEC in the event log. Option 2, TEC option with traditional contacts Buchholz Top oil Hot-spot Customer connects in cabinet Hot-spot, top oil and other alarm and warnings from TEC Terminal X51 Substation Control 2 cables for Alarm and Warning from TEC Cables from all protection devices Gets a Alarm or Warning from TEC TEC gives details from TEC Alarm/Warnings Warning output Alarm output Trip output options Trip option 1 No trip devices connected to TEC. Trip from TEC functions gives signal from X41:26 and 29. The customer connects this signal as any other device. Via the optic fiber the interface PC will have the details about the trips from TEC in the event log. Trip option 2 No trip devices connected to TEC. Trip from TEC functions not used. No information about the trips in TEC event log. Option 1 with TEC trip device from TEC Traditionally but with the trip from TEC hot-spot and top oil added as an extra device. Option 2 as today on transformer Buchholz Pressure relay Relief vent Top oil Hot-spot Buchholz Pressure relay Relief vent TEC top oil and hot-spot trip Customer connections X41 X X51 14 Customer connections Substation Control 1 cables for Trip from TEC (option 1) Cables from all protection devices TEC gives details from TEC Trip (option 1) 1 Output disconnectable terminal in series with terminal 14. 1ZSC en, Rev. 2 31

32 Trip option 3 From trip devices connected to TEC there will be one trip signal from X41:26 and 29. If the TEC trip is disconnected at terminal X51:1 this signal will not be integrated in the trip sum signal. Via the optic fiber the interface PC will have the details about the trip signals from the devices and TEC in the event log. Trip option 4 From trip devices connected to TEC and the internal TEC there will be one trip signal from X41:26 and 29. Via the optic fiber the interface PC will have the details about the trip signals from the devices and TEC in the event log. Option 3 TEC solution Option 4 TEC solution with TEC trip device Resistor Device Resistor Device 1 Top oil Device 2 Hot-spot 13 1 TEC X51:1 disconnected + - Connected in TEC cabinet, trip traditional way to customer, but all devices connected. TEC Hot-spot & top oil trip + - Connected in TEC cabinet, trip traditional way to customer, but all devices connected. Substation Control 1 cables for Trip from TEC TEC gives details for all Trip Substation Control 1 cables for Trip from TEC TEC trip included TEC gives details for all Trip Connection of devices in parallel both traditionally and to TEC Alarm/Warning devices Below figure shows how alarm/warning devices can be connected the traditional way in parallel with TEC. If the voltage in the station alarm/warning circuit is >24V no diode is needed in the traditionally alarm/warning circuit. Same common as in Trip circuit 24V 24V TEC Alarm/Warning device 1 Alarm/Warning device 2 If V > 24V no diode is needed V V Traditional connection, but sometimes with diode 32 1ZSC en, Rev. 2

33 Trip devices Below figure shows how warning/alarm devices can be connected the traditional way in parallel with TEC. Observe that a diode is needed in the traditionally trip circuit. If devices are connected both to TEC and the traditional way Same common as in Alarm/Warning circuit 24V 24V TEC Trip device 1 Trip device 2 Traditional connection, but always with diode Extra to TEC to get out one sum Trip signal even if TEC is dead 1ZSC en, Rev. 2 33

34 1.7 Ordering data The transformer manufacturer specifies TEC on an ordering data sheet with embedded guidance. The folders in the Excel sheet that should be filled in are: Order data 1, Functions Hardware Order data 2, Protection Sensors Order data 3, Software Order data 4, Cooling control Cells with a red mark in the corner contain help. Part of page 1 is shown here, page 2 with data on sensors is shown in 2.1. Additional data from the transformer design database are also used to configurate a mathematical model of the transformer in the TEC system software. tec_ Load test In case data from the heat-run test of the transformer deviate from calculated values given in section 1.7 Ordering data, the new values shall be added to the model of the transformer in TEC. In version 1.0, this is done by sending a revised ordering data sheet to ABB, where the program code can also be updated. (See the interface manual.) 34 1ZSC en, Rev. 2

35 2 Installation manual 2.1 Connection table Already from the Excel order data sheet under Order data 2 Protection Sensors it is possible to see how the sensors shall be connected. The other connections can be found in section Electronic boards and terminals. tec_0089 A similar table will also be sent with the order confirmation. 1ZSC en, Rev. 2 35

36 2.2 Sensors Sensors are normally included in the delivery, see 1.7 Ordering data. Connection of the cable shield is described in 2.3 Cables Air temperature Pt 100 sensor for air temperature in sun and shadow. The sensor in the shadow must not be influenced by the radiated heat from the transformer. A Pt 100 sensor that is replaced, automatically starts to work after approximately 30 seconds. The bushing that is included in the delivery is for cable diameter 4 8 mm. If a larger cable diameter is used, it should be provided by the customer. Height with cover: 44 Ø 4.5 (2x) Temperature input Pt T ( C) Pt 100(Ω) Shadow sensor Sun sensor tec_ ZSC en, Rev. 2

37 2.2.2 Oil temperature 7/8-14UNF2 88 D=12.21± KR D=14 tec_0059 Pt 100 sensor for oil temperatures at the transformer top and bottom and in the tapchanger. The thermometer pocket is included in the delivery of the temperature sensor. Order sensor for the tap-changer together with the tap-changer. Recommendations about placement of the thermometer: - Should be placed in level of the lower spacer ring (to avoid the cooler non moving bottom oil). - Should be placed not to far away from the cooler /radiator outlet (to measure in moving oil) Use of TEC bottom oil sensor The TEC bottom oil sensor should not be used in the calculations from the heat run test but the temperature should be noted. The calculation of average oil temperature etc. should be carried out in the normal way. TEC will for OF- and OD-cooled transformers in service calculate the hotspot from the TEC bottom oil thermometer and the calculated values from the heat run test. The bottom oil sensor shall be assembled at a position where the reading represents the temperature of the oil entering the windings Conductor no. in Temperature input Pt 100 tec_0060 1ZSC en, Rev. 2 37

38 2.2.3 Current transducer The current transducer is a 4-20 ma sensor that is connected on the cable from the transformer CT (current transformer). The sensor requires a 24 V DC supply to be connected in series with the signal. The 24 V DC power supply from X3:1 and 2 can be used. The cable from the CT should sometimes make more then one-turn trough the current transducer. The amount of turns can be found on the order data sheet or on the sign inside of the cabinet door. The current transducer can be calibrated from the interface. (See the interface manual.) If only one current transducer is used, the two current transducers should be placed on the same CT for backup purposes. Examples on CT locations in the transformer I I TEC Current transducer in the transformer cabinet I TEC = c I ma c = combined ratio of the current transformers tec_ tec_ Hydrogen gas in oil HYDRAN is a suitable sensor for hydrogen gas. Other sensors giving a 4-20 ma signal can also be used. The Hydran detector gives a signal proportional to the hydrogen equivalent in the transformer oil. The hydrogen equivalent includes the content of hydrogen (H 2 ) and fractions of the hydrocarbons (C 2 H 2, C 2 H 4, etc.) and carbon monoxide (CO) in the transformer oil. If needed, the sensor reading can be calibrated from the interface. (See the interface manual.) Moisture in oil sensor Moisture in oil sensor giving an output of 4-20 ma can be used. The output can be ppm, water activity or RH %. If the output is in ppm, the temperature output (4-20 ma) from the sensor does not need to be connected to TEC. 38 1ZSC en, Rev. 2

39 2.3 Cables and earthing Pt 100 Fibre optic cable and cables to the sensors are normally included in the TEC delivery with lengths as specified in 9.1 Ordering data. All cable shields shall be connected to the TEC cabinet earth in one of the following ways: With a Roxtec sealing system at the entrance of the cabinet. With an EMC cable gland at the entrance of the cabinet. At the common earth bar in the cabinet. The length of the strand from the cable/ shield to the earth bar shall not be more than 50 mm. The sensor cable shields shall be connected to earth at one point only and thus not be connected to earth at the sensors. Shielded cable with four conductors in twisted pairs. One pair to feed current and one pair to measure resistance / voltage drop. Recommended conductor area 0.5 mm 2 (max 1.5) ma and Digital in RS 485 Shielded cable with two conductors in twisted pairs. Recommended conductor area 0.5 mm 2 (max 2.5). Shielded cable with two conductors in twisted pair. Recommended conductor area 0.5 mm Fibre optic The TEC cabinet is connected to the station PC with a double fibre optic cable. Cable diameter 62.5 / 125 µm with ST contacts. Cable length up to 1 km with max attenuation 4 db/km. The cable shall be handled with care: Max. allowable tensile load (N) during installation 3000 in service 1500 Min. bending radius (mm) during installation 130 in service 80 Crush resistance (N/cm) briefly 400 permanently 200 Impact resistance (impacts) Wp=4.41 Nm/r=25 mm 30 Temperature range ( C) during installation -10 to +50 in service -25 to +70 in storage -40 to +70 1ZSC en, Rev. 2 39

40 2.3.5 Cable entry and Roxtec Cables enter the cabinet at the bottom via a flange that is drilled and provided with cable glands at the transformer assembly, or via a Roxtec sealing system. Dimensions are given in Cabinet. Use the original manual for guidance at installation work. tec_ PC The PC is normally part of the TEC delivery. See the interface manual, if existing. tec_ ZSC en, Rev. 2

41 3 Operating manual 3.1 Start sequence The TEC processor starts automatically when it is connected to voltage. (The power supply to TEC should be connected before the 24 V power supply to the motor board to avoid that the coolers start immediately.) The TEC PC should be started after the TEC processor. (See the interface manual.) 3.2 Display on cabinet A status light, a display and a push-button are assembled on the front of the cabinet. One push at the button wakes up the display and the information scrolls slowly. A second push stops the scroll and subsequent pushes advances the information step by step. Press the button for three seconds to return to automatic scrolling. Five minutes after the last push, the display turns off. tec_0063, tec_0073 tec_ tec_0071 A TOP OIL Top oil temperature B1 HOT-SPOT HV Hot-spot temperature high voltage winding B2 HOT-SPOT LV Hot-spot temperature low voltage winding C BOTTOM OIL Bottom oil temperature D LOAD I/ Irat Load I/I rated (highest of LV and HV) E OLTC POSITION Tap-changer position (numbers from 1-n) F OLTC TEMP1 Temperature of first tap-changer G HYDROGEN H2 Hydrogen gas In oil Moisture in trafo Moisture in oil in the transformer Moisture in OLTC Moisture in oil in the tap-changer E, F, G and moisture readings are only displayed when applicable. 1ZSC en, Rev. 2 41

42 3.2.1 Status light Red, alarm or trip Yellow, warning Green, normal The same colour code is used in the station interface 3.3 Warning, Alarm and Trip signals TEC can give a warning, alarm and trip signal. The warning signal could be seen as an early alarm signal. The alarm signal should be similar to the normal alarm signal The trip signal created by TEC is only the top oil and hot-spot trip. This trip signals can be disconnected at the terminal. 3.4 TEC during transformer test TEC can be connected during test of the transformer. If it is switched off, the coolers will be started automatically unless their power supply is also switched off. 3.5 Sensor failure There is a sensor back-up in TEC in the case of a sensor failure. If the reading from a Pt100 sensor is out of range ( C) for 1 minute a back-up will take place described below. A warning signal on the status lights and in the station PC. If the Pt 100 sensor is replaced it will start to work after approximately 30 seconds. A 4 20mA sensor that is out of range if the reading is <3 ma or >22 ma - then it will be a warning signal on the status lights and in the station PC. The false sensor reading will not be displayed. If the sensor is replaced it will start to work after 30 seconds. For the current sensors, see also the logic below. Top oil thermometer failure If the sensor fails, the top oil is calculated based on the bottom oil temperature. At stable conditions the calculated temperature will be rather close to the real one. Although at rapid load increase the calculated top oil temperature will increase much quicker then the real temperature. To avoid a to early trip in this case the top oil trip is disabled, although alarm and warning will still work. There will be a warning for sensor failure. Θ Top = Θ Bot + 2[ Θ imr - Θ br ]K y Bottom oil thermometer failure If the sensor fails, the bottom oil is calculated based on the top oil temperature. There will be a warning for sensor failure. Θ Bot = Θ Top - 2[ Θ imr - Θ br ]K y 42 1ZSC en, Rev. 2

43 Both top and bottom oil thermometer fails If both sensors fail, there will be an alarm for sensor failure in TEC. Ambient air thermometer failure If the shadow sensor fails, the value from the sun sensor will be displayed and used for the calculations. If the sun sensor fails, the value from the shadow sensor will be displayed. If one sensor fails there will be a warning. If both sensors fail there will still be a warning but the output from the sensors will be the latest readings before failure. Current sensors There are three different types of behaviour in case of sensor errors. A two-winding transformer sensor error will be compensated by calculation of the faulty current, based on the other current sensor. The calculation is based on the remaining current, the transformer ratio and the tap-changer. For all other connection types there will not be any current calculation. The faulty sensor will display 0. For autotransformers a current sensor failure on the series winding will result in a current reading of 0 from both current sensors. If the current sensor on the LV side or common winding fails the output from this sensor will be 0, but the output from the series current sensor will be correct. If one current sensor fails there will be a warning. If both sensors fail there will be an alarm Sensor failures influence on functions Hot-spot temperature calculation The hot-spot temperatures for the high-voltage and low-voltage winding is always calculated. If a thermometer or current transformer sensor fails the lost value will be calculated by the formulas in the previous sections and will be used for the hot-spot calculations. Ageing If the hot-spot temperature of the hottest winding cannot be calculated, e.g. because of a current transformer failure, the second hottest winding will be used for the ageing calculation. Cooling control If the hot-spot temperature of the hottest winding cannot be calculated, e.g. because of a current transformer failure, the second hottest winding will be used for the cooling control. 1ZSC en, Rev. 2 43

44 3.5.2 Other back-ups in case of failures PC problem If the PC is switched off or stops working the consequences are: No historical data will be stored Alarms and warnings can t be reset. The TEC cabinet functionality is not affected except for the small correction of the TEC clock. Cooling control back-up If the TEC for some reason stops working or the connection between TEC and motor board is disconnected the consequences are: The motor control board will start all cooling, with a 10 sec time delay between each of them If the 24V power supply to the motor board or the motor board stops working. The traditional top oil thermometer will start all coolers 44 1ZSC en, Rev. 2

45 4 Maintenance and service manual No routine maintenance on TEC is needed 4.1 Loading of new program in TEC See COM TEC Application and parameter load instruction. (The product information is attached in the station interface TEC documentation file.) Hardware needed and connections Connecting the PC to the TEC TC120 board according to figure. Monitoring cable. Contacts on monitoring cable. Contact Connection of the cable to the TC120 board. The other end of the cable should be connected to the COM port in the PC. 1ZSC en, Rev. 2 45

Type TEC, Transformer Electronic Control System

Type TEC, Transformer Electronic Control System Type TEC, Transformer Electronic Control System Technical Guide 1ZSC000857-AAB en, Rev. 2, 2006-06-15 Declaration of conformity The manufacturer ABB Power Technologies AB Components SE-771 80 LUDVIKA Sweden

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Galaxy Pulsar Plus Digital Battery Plant Controller

Galaxy Pulsar Plus Digital Battery Plant Controller Galaxy Pulsar Plus Digital Battery Plant Controller Features Supports up to 60 Power Modules rectifiers and converters Supports dual voltage plants, with rectifiers and converters Auto-sensing dual voltage

More information

User Guide

User Guide ABS control panel CP 112 212 ON ON ON ON ON ON User Guide www.absgroup.com ii ABS CONTROL PANEL CP 112 212, USER GUIDE Copyright 2008 ABS Group. All rights reserved. This manual, as well as the software

More information

S304 and S305 Dust Emission Monitors. User Manual. Distributor

S304 and S305 Dust Emission Monitors. User Manual. Distributor S304 and S305 Dust Emission Monitors User Manual Distributor Version 6.4 30/5/2012 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 Principle of operation... 4 2. INSTALLATION...

More information

Audible warning devices for external alarm

Audible warning devices for external alarm VdS SCHADENVERHÜTUNG VdS Publisher: Gesamtverband der Deutschen Versicherungswirtschaft e.v. (GDV) Büro Schadenverhütung Publishing house: VdS Schadenverhütung Rules for Intruder Alarm Systems Audible

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Continuous, real-time detection, alarming and analysis of partial discharge events

Continuous, real-time detection, alarming and analysis of partial discharge events DMS PDMG-R Partial discharge monitor for EHV GIS Continuous, real-time detection, alarming and analysis of partial discharge events Automatic PD fault classification Robust design allows for reliable operation

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System SF6 Gas Density Monitoring System Description Introduction As a result of recent European legislation on the control of greenhouse gasses, utilities and manufacturers alike

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Rules for Intruder Alarm Systems

Rules for Intruder Alarm Systems Rules for Intruder Alarm Systems Opening detectors (Magnetic contacts) Part 1: Requirements VdS 2120en 03/96 (03) Subject 44 1 General; 2 Terms and definitions; 3 Classification 1 General 1.1 Scope These

More information

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE isocket Smart Relay is a complex Smart House system which is installed in the fuse cabinet (electric cabinet) in the house. We therefore assume that

More information

FT702LT Turbine control wind sensor gives durability a new meaning FT702LT. series

FT702LT Turbine control wind sensor gives durability a new meaning FT702LT. series FT702LT Turbine control wind sensor......gives durability a new meaning FT702LT series Proven High Availability The FT702LT ultrasonic anemometer is the result of FT Technologies 10 years of experience

More information

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning

More information

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply   - Tel: Systems Index Systems - Systems Systems...1 -.16 General information Description...1 System description...2 Overview...3 Ordering details Arc monitor with detectors...4 Current sensing unit...5 Technical

More information

Models 4623, 4628 & 5999/980 USP<645> Conductivity Analyzers

Models 4623, 4628 & 5999/980 USP<645> Conductivity Analyzers Data sheet USP Conductivity Analyzers A conductivity system designed to meet USP for the Pharmaceutical Industry incorporating automatic Stage 1 test Meets USP requirements ensures compliance

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller Wallace & Tiernan s & Analysers ChemTrim Disinfection Introduction The ChemTrim Disinfection is a modern, dedicated controller incorporating the latest advanced electronics and process control application

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

RAYCHEM NGC-30 COMPONENTS

RAYCHEM NGC-30 COMPONENTS PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM PRODUCT OVERVIEW CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

DEB71. Earth Leakage Monitoring Relay. Benefits. Description Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional

More information

Rules for Classification and Construction Additional Rules and Guidelines

Rules for Classification and Construction Additional Rules and Guidelines VI Rules for Classification and Construction Additional Rules and Guidelines 7 Guidelines for the Performance of Type Approvals 7 Test Requirements for Statical Converters with Semi-Conductors Edition

More information

PTE0705 Electric Fence Monitor

PTE0705 Electric Fence Monitor PTE0705 Electric Fence Monitor The JVA logo is a registered trademark of JVA Technologies. JVA Technologies. TABLE OF CONTENTS DESCRIPTION... 2 QUICK START GUIDE... 3 FEATURES... 4 EXPLANATION OF TERMS...

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc flash detection units. Product picture Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize

More information

Sintrol Snifter A2 EX. Manual. Version 1.2.3

Sintrol Snifter A2 EX. Manual. Version 1.2.3 Sintrol Snifter A2 EX Manual Version 1.2.3 Table of Contents 1 INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 How does it work?... 4 2 INSTALLATION... 4 2.1 Selecting the installation

More information

Universal fault annunciator for panel mounting

Universal fault annunciator for panel mounting Universal fault annunciator for panel mounting Communication over Ethernet USM - Universal-fault annunciator for panel mounting Low depth housing for panel mounting Versions with 8, 16, 32 or 48 inputs

More information

M2000 Engine Controller

M2000 Engine Controller M2000 Engine Controller Integrated control and protection of diesel and gas engines for all purposes Especially suited for auxiliary generator sets 1 IN OPERATION 1 2 STARTFAIL 2 3 OVERSPEED RPM FAIL 3

More information

Annunciator Unit SACO 16 D1. Product Guide

Annunciator Unit SACO 16 D1. Product Guide Issued: Aprill 1999 Status: Updated Version: C/20.03.2006 Data subject to change without notice Features Flexible, field-customizable 16-channel annunciator unit Alarm channels activated by normally open

More information

Specification for On-Line UPS Battery Monitoring and Data Management System

Specification for On-Line UPS Battery Monitoring and Data Management System 1 Scope This specification defines the minimum requirements for a predictive on-line Battery Monitoring BMDMS with test, analysis, and remote monitoring control capabilities. Unless noted otherwise, the

More information

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number Worldwide Supplier of Safety Solutions GfG Instrumentation 1194 Oak Valley Drive #20 Phone: 734-769-0573 Fax: 734-769-1888 E-Mail: info@gfg-inc.com Internet: www.gfg-inc.com GMA 301 Operation Manual Part

More information

Analog Annunciator Unit SACO 16 A3. Product Guide

Analog Annunciator Unit SACO 16 A3. Product Guide Issued: Aprill 1999 Status: Updated Version: C/20.03.2006 Data subject to change without notice Features Powerful, flexible and field-customizable 16-channel analog input signal annunciator unit A full

More information

Table of Contents. Page Quick Set-up Instructions 1. Theory of Operation 2. Specifications 3. TM 1003W Controls and Connections 4

Table of Contents. Page Quick Set-up Instructions 1. Theory of Operation 2. Specifications 3. TM 1003W Controls and Connections 4 Table of Contents Page Quick Set-up Instructions 1 Theory of Operation 2 Specifications 3 TM 1003W Controls and Connections 4 1. Power Source Connector 5 2. Alarm Output Connector 5 3. Variation Detection

More information

Series Temperature Controller Instruction Sheet

Series Temperature Controller Instruction Sheet Series Temperature Controller Instruction Sheet Thank you very much for purchasing DELTA A Series. Please read this instruction sheet before using your A series to ensure proper operation and please keep

More information

EL-USB-1-LCD Temperature Data Logger with LCD

EL-USB-1-LCD Temperature Data Logger with LCD 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 EL-USB-1-LCD Temperature Data Logger with LCD Visit us at www.testequipmentdepot.com ORDERING INFORMATION Standard Data

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET Control Systems Transmitters Sensors Accessories Wall, 19 Rack or Panel Mounting Units 110/230V 50/60Hz AC operation 250 Addressable devices as: Relays, 4-20 Inputs or Gas Detectors

More information

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01 PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Warnings and Notices WARNING - To reduce the risk of fire or electric shock, do not expose this product

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

WALLACE & TIERNAN CONTROLLERS & ANALYSERS CHEMTRIM DISINFECTION CONTROLLER PRODUCT SHEET

WALLACE & TIERNAN CONTROLLERS & ANALYSERS CHEMTRIM DISINFECTION CONTROLLER PRODUCT SHEET WALLACE & TIERNAN CONTROLLERS & ANALYSERS CHEMTRIM DISINFECTION CONTROLLER PRODUCT SHEET INTRODUCTION The ChemTrim Disinfection Controller is a modern, dedicated controller incorporating the latest advanced

More information

Operation and use. Functions and characteristics

Operation and use. Functions and characteristics Operation and use Function Vigirex relays measure the earth-leakage current in an electrical installation via their associated toroids. Vigirex relays may be used for: b residual-current protection (RH10,

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2017-01-25 2001-2017 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

QPM21 Series Duct CO 2 and Air Quality Sensors

QPM21 Series Duct CO 2 and Air Quality Sensors Document No. CE1N1962 QPM21 Series Duct CO 2 and Air Quality Sensors Description Features Application The Carbon Dioxide (CO 2 ) Duct Sensors are directly wired to the controller via twisted pair and/or

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2018-07-06 2001-2018 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

REMOTE CONTROL FOR CHILLER MYCHILLER

REMOTE CONTROL FOR CHILLER MYCHILLER REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with,,,, 0 and signal inputs Storage of the last state of inputs and sequence in the case

More information

Operating Manual MS220DA

Operating Manual MS220DA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

C-Bus Four Channel Analogue Output Unit Installation Instructions

C-Bus Four Channel Analogue Output Unit Installation Instructions C-Bus Four Channel Analogue Output Unit Installation Instructions 5504AMP Series REGISTERED PATENT Table of Contents Section... Page 1.0 Product Range...3 2.0 Description...3 3.0 Capabilities...3 4.0 Wiring

More information

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER MODEL AL3 7 5 - AL3000 series conforming to CE, UL and CSA are 100mm multi-point type hybrid recorders with a simultaneous display of multi-channel

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

ABB MEASUREMENT & ANALYTICS DATA SHEET. C50 1/16 DIN controller / alarm unit

ABB MEASUREMENT & ANALYTICS DATA SHEET. C50 1/16 DIN controller / alarm unit ABB MEASUREMENT & ANALYTICS DATA SHEET C50 1/16 DIN controller / alarm unit 2 C50 1/16 DI N CON TROLL ER / AL ARM U NIT DS/C 50-E N RE V. M Measurement made easy C50 the 1/16 DIN controller to suit your

More information

Incident resolution workflow

Incident resolution workflow Incident resolution workflow Code Alarm Reason for shutdown Description 0001H Grid frequency Grid frequency out of The measured grid frequency is outside the specified limits out of range range 0002H Grid

More information

VdS SCHADENVERHÜTUNG. VdS-Rules for Intruder Alarm Systems

VdS SCHADENVERHÜTUNG. VdS-Rules for Intruder Alarm Systems VdS SCHADENVERHÜTUNG VdS Publisher: Gesamtverband der Deutschen Versicherungswirtschaft e.v. (GDV) Büro Schadenverhütung Publishing house: VdS Schadenverhütung. All rights reserved. VdS-Rules for Intruder

More information

Original operating instructions Photoelectric safety sensors (safety light curtain / safety light grid) Protected area width (range) 0...

Original operating instructions Photoelectric safety sensors (safety light curtain / safety light grid) Protected area width (range) 0... Original operating instructions Photoelectric safety sensors (safety light curtain / safety light grid) Protected area width (range) 0...12 m OY UK 704555 / 05 02 / 2018 Contents 1 Preliminary note...4

More information

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM Card Rack Modules CABLE DUCT MAIN SWITCH 800 mm USER INTERFACE TERMINAL PRODUCT OVERVIEW The nvent

More information

C-Bus Four Channel General Input Unit Installation Instructions

C-Bus Four Channel General Input Unit Installation Instructions C-Bus Four Channel General Input Unit Installation Instructions 5504GI Series REGISTERED DESIGN REGISTERED PATENT Table of Contents Section...Page 1.0 Product Range... 3 2.0 Description... 3 3.0 Capabilities...

More information

3500/61E & 3500/67E Temperature Monitor

3500/61E & 3500/67E Temperature Monitor 3500/61E & 3500/67E Temperature Monitor Bently Nevada* Asset Condition Monitoring Description The 3500/61E and 3500/67E modules provide six channels and two channel of temperature monitoring. Both monitors

More information

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504 Remote Monitor PTE0700 SECURITY ELECTRONICS User Manual PTE0700 V2 Series Remote Monitor Pakton Technologies Pty Ltd ABN 66 405 694 842 16 Ferrier Road, Narangba Qld 4504 PO Box 408, Narangba QLD 4504

More information

Knürr RMS Compact II. Knürr RMS Compact II 2.81

Knürr RMS Compact II. Knürr RMS Compact II 2.81 Knürr RMS Compact II Knürr RMS Compact II 2.82 to 2.85 2.81 Knürr RMS Compact II Damage prevention with checks and controls System and network management requirements mean the systems ambient conditions

More information

BC3250. Blowdown Controller

BC3250. Blowdown Controller Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Instruction Manual August sitrans CU 02

Instruction Manual August sitrans CU 02 Instruction Manual August 2005 sitrans CU 02 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET Wed : www.saenchotesei.com WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 920 - Wall, 19 Rack or Panel Mounting Units - 110/230V 50/60Hz AC operation - 250 Addressable

More information

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits Arc Protection 01 VAmP 120 Arc Flash Protection Units Customer benefits Personnel Safety A fast and reliable arc protection unit may save human lives in case of an arc fault arising in a switchgear during

More information

Annunciator unit. Application

Annunciator unit. Application Issued: April 1999 Status: April 1999 Version: B/09.11.2001 Data subject to change without notice Features Flexible, field-customizable 16-channel annunciator unit Alarm channels activated by normally

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 INTRODUCTION Thank you for purchasing the Hokkim Integrated Automatic Mains Failure Control Board model HAMF- 8 or HAMF-4. We shall

More information

Networked Access Control Panel. Installation Guide

Networked Access Control Panel. Installation Guide XP2M Networked Access Control Panel V1.0X Installation Guide X P 2 M A C C E S S C O N T R O L S Y S T E M Installation Guide Document Ref: PLAN XP2M Installation Guide V4(G)2010 Access Control Services

More information

Speed and Frequency Seite 1 von 7

Speed and Frequency Seite 1 von 7 Speed and Frequency Seite 1 von 7 E16 Systems for High Safety Speed ing, all with Triple Modular Redundancy. A choice of versions to meet various demands. Compliant with SIL3 / IEC 61508 and/or API 670.

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

Module Features are-configurable, no module jumpers to set

Module Features are-configurable, no module jumpers to set December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

QD-ENG-68 Controller for Thermoelectric Thermal Management

QD-ENG-68 Controller for Thermoelectric Thermal Management INSTALLING THE CONTROLLER QD-ENG-68 Controller for Thermoelectric Thermal Management The Ice Qube TMS controller is shipped complete with mounting hardware and electrical cables for easy installation.

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009 STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009 Introduction Honeywell s STT 3000 family of microprocessor based transmitters covers the full

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5

More information

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual ANALOX 5001 ANALOX 5001 Carbon Dioxide Monitor User Manual Analox Sensor Technology Ltd 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT T: +44 (0)1642 711400 F: +44 (0)1642 713900

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

Fiber Optic Cable Fence Disturbance Sensor

Fiber Optic Cable Fence Disturbance Sensor Architectural & Engineering Specification for Fiber Optic Cable Fence Disturbance Sensor Purpose of document This document is intended to provide performance specifications and operational requirements

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information