Developing a Healthcare Facility Fire Door Inspection Program

Size: px
Start display at page:

Download "Developing a Healthcare Facility Fire Door Inspection Program"

Transcription

1 Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1

2 POLLING There will be occasional interactive poll questions Developing a Healthcare Facility Fire Door Inspection Program WEBINAR SERIES Two (2) sessions Approximately 90 minutes each Handouts and survey tools available Completion certificate On demand access 2

3 SESSION ONE AGENDA Background Qualifications Applicable Doors Session One Creating an Inventory Survey Process SESSION TWO AGENDA Door Components Survey Criteria Documentation Session Two Survey Tools Common Findings WEBINAR OBJECTIVES Upon completion, participants will have the ability to: Establish an inspection program Determine applicable doors Develop a door inventory Inspect fire rated door assemblies and smoke door assemblies Develop inspection documentation 3

4 BACKGROUND 2000 Life Safety Code (NFPA 101) 2012 Life Safety Code (NFPA 101) Adopted July 2016 Instituted November 2016 CODE PATH: 2012 LIFE SAFETY CODE Chapter 19 Reference to Chapter 7 Chapter Reference NFPA 80 & NFPA 105 NFPA 80 & 105 NFPA 80 (Standard for Fire Doors and Other Opening Protectives) NFPA 105 (Standard for the Installation of Smoke Door Assemblies and Other Opening Protectives) CODE PATH: REFERENCED STANDARDS NFPA 101 (2012 Edition) NFPA 80 (2010 Edition) NFPA 105 (2010 Edition) 4

5 AUTHORITIES HAVING JURISDICTION CMS Developed K 363 No additional guidance The Joint Commission EC EP25 Recent clarifications in EC News and Perspectives Other Accrediting Agencies / State Survey Agencies QUALIFICATIONS NFPA 80 Language Functional testing of the fire door and window assemblies shall be performed by individuals with knowledge and understanding of the operating components of the type of door being subject to testing No reference to certified QUALIFICATIONS NFPA Definition Qualified A person who, by possession of a recognized degree, certificate, professional standing, or skill, and who, by knowledge, training, and experience, has demonstrated the ability to deal with the subject matter, the work, or the project Focus on professional standing, skill, knowledge, training, and /or experience 5

6 QUALIFICATIONS Internal Staff Staff Carpenter General Maintenance / Physical Plant Staff External Vendor Certified Fire Door Inspector Life Safety Consultant Licensed Carpenter External Vendor Support to Train Internal Staff DEVELOPING AN INVENTORY WHAT DOORS? Determining what doors to survey Fire barriers Smoke barriers Hazardous areas Chutes and shafts DEVELOPING AN INVENTORY WHAT DOORS? Fire Barrier Doors Building separations Occupancy separations Stairwell enclosures *check your life safety drawings to determine barriers 6

7 DEVELOPING AN INVENTORY WHAT DOORS? Smoke Barrier Doors Separate smoke compartments May or may not be labeled fire doors Don t include courtesy doors *check your life safety drawings to determine barriers DEVELOPING AN INVENTORY WHAT DOORS? Hazardous Area Enclosures Non sprinklered spaces New construction Generally 45 minute doors in 1 hour rated enclosures *check your life safety drawings to determine hazardous area enclosures DEVELOPING AN INVENTORY WHAT DOORS? Chute and Shaft Doors Trash chutes (inlet and outlet) Linen chutes (inlet and outlet) Shaft access doors *check your life safety drawings to determine chute and shaft locations 7

8 DEVELOPING AN INVENTORY WHAT DOORS? Unique Situations Rated patient / resident room doors Rated doors that are not part of a rated barrier DEVELOPING AN INVENTORY WHAT DOORS? Patient / Resident Room Doors Not required to be rated May be rated anyway Not a true fire door assembly since door closer not required Joint Commission not required to be included CMS no guidance *RPA suggestion do not include in inventory or inspection. Still must meet corridor door requirements. DEVELOPING AN INVENTORY WHAT DOORS? Misc. Rated Doors (not part of a rated enclosure) Not required to be rated May be rated anyway Joint Commission not required to be included CMS no guidance 8

9 DEVELOPING AN INVENTORY WHAT DOORS? May do Nothing May Include in Inventory & Inspection May Remove Labels If the labels are removed, consider retaining the labels and documenting where they came from Consider checking with your local AHJ May Replace Doors DEVELOPING AN INVENTORY WHAT DOORS? Doors Not to Include WON doors Fire or Smoke shutters Smoke Curtains or other smoke containment devices *These doors/curtains are covered in separate sections/standards for inspection, testing, and maintenance. DOOR CATEGORIES Eleven (11) categories of doors Fire rated door assemblies (fire barriers) Doors to hazardous areas (rated enclosures) Shaft access doors (rated shaft enclosures) Trash chute inlet Trash chute discharge Linen chute inlet Linen chute discharge Smoke doors (new nonrated) Smoke doors (new rated) Smoke doors (existing nonrated) Smoke doors (existing rated) 9

10 SURVEY CHECKLIST SURVEY TOOLS SURVEY CHECKLIST SURVEY TOOLS SURVEY CHECKLIST SURVEY TOOLS 10

11 DEVELOPING AN INVENTORY PHASES Phase I Identify door assemblies to be included Document door ID, location, type and rating Consider a spreadsheet Identify door locations on a drawing DEVELOPING AN INVENTORY PHASES DEVELOPING AN INVENTORY PHASES 11

12 DEVELOPING AN INVENTORY PHASES DEVELOPING AN INVENTORY PHASES Door Components 12

13 DEFINITIONS Labeled: Equipment or materials to which has been attached a label, symbol, or other identifying mark of an organization that is acceptable to the AHJ and concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer indicates compliance with appropriate standards or performance in specified manner. A fire door with a label is a labeled component of a listed assembly Listed: Equipment, materials, or services included in a list published by an organization that is acceptable to the AHJ and concerned with evaluation of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, material, or service meets appropriate designated standards or has been tested and found suitable for a specified purpose. A fire stop system is part of a listed (barrier) assembly (approved for use, but no label is present) DEFINITIONS Fire Door Assembly: Any combination of a fire door, a frame, hardware, and other accessories that together provide a specific degree of fire protection to the opening. Classification: Fire doors and fire windows shall be classified by designating a required fire protection rating expressed in hours or fractions thereof. Fire door assemblies have fire rating durations expressed as 20,30,45,60,90,and 180 minutes. May also be expressed as 1/3, 1/2, 3/4, 1, 1 1/2, 3 hours DEFINITIONS Builder s hardware: Individual listed or labeled hardware products are usually suitable for fire door assemblies of any construction or hourly rating. Fire Door Hardware: Door hardware furnished for swinging and sliding fire doors by the door manufacturer as a component part of the listed door assembly Smoke Door Assembly: Any combination of a door, frame, hardware, and any other accessories that together restrict smoke movement through door openings by limiting the amount of air that can pass through the assembly. Does not include smoke partitions or corridor doors 13

14 DEFINITIONS WINDOWS AND GLAZING Fire Resistance Rated Glazing Tested as part of a fire resistance rated wall assembly in accordance with the Standard for Fire Tests of Building Construction and Materials DEFINITIONS WINDOWS AND GLAZING Fire Protection Rated Glazing Fire protection rated glazing materials are intended for installation in fire windows, fire doors, and fire door frames with transoms and/or sidelights that are provided with suitable glazing frame members. Unless otherwise indicated in the individual Classifications, these materials have not been investigated by UL to determine compliance with safety glazing requirements. DEFINITIONS WINDOWS AND GLAZING NFPA Table:

15 DEFINITIONS WINDOWS AND GLAZING NFPA Table: DEFINITIONS WINDOWS AND GLAZING NFPA Table: DEFINITIONS WINDOWS AND GLAZING NFPA Table:

16 COMPONENTS (APPURTENANCES) Components (Appurtenances) all must bear a label OR meet the specifications for that particular component Astragals Sweeps Closers COMPONENTS (APPURTENANCES) Door Bottoms Door ends COMPONENTS (APPURTENANCES) Hardware Hinges Latches Locks 16

17 COMPONENTS (APPURTENANCES) Lights (side lights) Louvers Vision Panels The Inspection DOOR CATEGORIES Eleven (11) categories of doors Fire rated door assemblies (fire barriers) Doors to hazardous areas (rated enclosures) Shaft access doors (rated shaft enclosures) Trash chute inlet Trash chute discharge Linen chute inlet Linen chute discharge Smoke doors (new nonrated) Smoke doors (new rated) Smoke doors (existing nonrated) Smoke doors (existing rated) * Rated doors that are not required to be rated 17

18 DOOR CATEGORIES Requirements vary based upon category of door See Inspection Criteria Tool Approximately 25 total inspection criteria DOOR INSPECTION COMPONENTS I. Latching hardware operates and secures the door when it is in the closed position. 18

19 II. The self closing device is operational, that is, the active door completely closes when operated from the full open position. III. No open holes or breaks exist in surfaces of either the door or frame IV. Door labels are clearly visible and legible V. Frame labels are clearly visible and legible 19

20 VI. Signage affixed to a door meets the requirements listed in NFPA 80 SIGNAGE Signage requirements per NFPA 80 Total area of attached signs shall not exceed 5 percent of the area of the face of the door Signs shall be attached to fire doors by use of an adhesive. Screws or nails shall not be permitted. Signs shall not be installed on glazing material in fire doors. Shall not impair or otherwise interfere with the proper operation of the fire door. In accordance with Manufacturer Listings Fire Door Informational Signage Door Width (in inches) Door Height (in inches) Maximum area of sign(s) permitted (in square inches) NFPA ed Sign Width (in inches) Sign Height (in inches) Area of sign(s) (in square inches) 20

21 VII. The door, frame, hinges, hardware, and noncombustible threshold are secured, aligned, and in working order with no visible signs of damage. VIII. No field modifications to the door assembly have been performed that void the label. IX. Corridor doors do not exceed a one (1) inch clearance at the bottom of the door 21

22 X. Door clearances at the door edge to the frame, on the pull side of the door, are not excessive bottom (3/4 ) and between (1/8 ) HOW TO FIX EXCESSIVE FIRE DOOR CLEARANCES Door undercut vs clearance Install door bottoms listed for that purpose 22

23 HOW TO FIX EXCESSIVE FIRE DOOR CLEARANCES Door undercut vs clearance Install door bottoms listed for that purpose HOW TO FIX EXCESSIVE FIRE DOOR CLEARANCES Side gaps Gasketing for the frame/door gap Meeting edges of door gaps Install door ends to minimize gap XI. No parts are missing, broken or damaged 23

24 XII. The door is free of nonrated protective plates >16" above the bottom of the door XIII. Vision panels are installed properly with a legible rating label XIV. Chute inlet doors positively latch 24

25 XV. Door is equipped with astragal, rabbet or bevel XVI. If a coordinator is installed, the inactive leaf closes before the active leaf. XVII.Vision panels and glazing beads are intact and securely fastened in place, if so equipped 25

26 XVIII.Automatic flush bolts in place and properly working on inactive door leafs XIX. Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame. XX. Fusible links in place and not damaged 26

27 XXI. Gasketing and edge seals, where required, are inspected to verify their presence and integrity. XXII. There are not gaps around the door frame or the frame is not secured to the wall. XXIII.Center mullion does not restrict door opening or closing. 27

28 XXIV.New smoke barrier doors swing in opposite directions and have vision panels XXIV.Fire exit hardware in place where required Inspection Documentation 28

29 DOCUMENTATION PHASE Document inspection findings via the data collection tool (spreadsheet) Reference the appropriate checklist based on door type Determine any failing inspection components via the failure mode list (items 1 25) Document on the Findings Report (Phase II) DOCUMENTATION PHASE DOCUMENTATION PHASE Phase II Result: Pass or Fail Failure Mode Other Comments 29

30 Building Floor Location Door Number Leaves: Single or Double Barrier Type Door Type (See inspection checklist for criteria inspected to) Door Rating (in minutes) Result: Pass or Fail North 11 Rm Stair 26 F11101 Single 2hr Fire Fire Rated Door Assembly 90 Fail 3 6 Remove label North 11 Rm Stair 26 F11102 Single 2hr Fire Fire Rated Door Assembly 90 Fail 5 6 North 11 Rm Stair 28 F11120 Single 2hr Fire Fire Rated Door Assembly 90 Fail 3 10 North 10 Rm Stair 28 F10120 Single 2hr Fire Fire Rated Door Assembly 90 Fail 3 10 North 10 North 10 North 10 North 10 Rm Mechanical Rm Mechanical Rm Mechanical Rm Mechanical F10100 Single 2hr Fire Fire Rated Door Assembly 90 Pass F10101 Single 2hr Fire Fire Rated Door Assembly 90 Fail 6 7 F10102 Single 2hr Fire Fire Rated Door Assembly 90 Fail F10103 Single 2hr Fire Fire Rated Door Assembly 90 Fail 3 Failure Mode Comments Summary: Maintain, Repair, Replace, Date Repaired and/or Result: Remove Label, Remove Verified Complete Pass or Fail Rating 4/21/2017 DOCUMENTATION PHASE Phase II Result: Pass or Fail Failure Mode Other Comments Pass Fail 5 6 Fail 3 10 Fail 3 10 Pass Fail 6 7 Fail DOCUMENTATION PHASE Sample Medical Center Fire / Smoke Barrier Door Assembly Report of Findings and Management Tool Phase I Phase II Phase III Other DOCUMENTATION PHASE 30

31 DOCUMENTATION PHASE DOCUMENTATION PHASE DOCUMENTATION PHASE 31

32 Building Floor Location Door Number Leaves: Single or Double Barrier Type Door Type (See inspection checklist for criteria inspected to) Door Rating (in minutes) Result: Pass or Fail North 11 Rm Stair 26 F11101 Single 2hr Fire Fire Rated Door Assembly 90 Fail 3 6 Remove label North 11 Rm Stair 26 F11102 Single 2hr Fire Fire Rated Door Assembly 90 Fail 5 6 North 11 Rm Stair 28 F11120 Single 2hr Fire Fire Rated Door Assembly 90 Fail 3 10 North 10 Rm Stair 28 F10120 Single 2hr Fire Fire Rated Door Assembly 90 Fail 3 10 North 10 North 10 North 10 North 10 Rm Mechanical Rm Mechanical Rm Mechanical Rm Mechanical F10100 Single 2hr Fire Fire Rated Door Assembly 90 Pass F10101 Single 2hr Fire Fire Rated Door Assembly 90 Fail 6 7 F10102 Single 2hr Fire Fire Rated Door Assembly 90 Fail F10103 Single 2hr Fire Fire Rated Door Assembly 90 Fail 3 Failure Mode Comments Summary: Maintain, Repair, Replace, Date Repaired and/or Result: Remove Label, Remove Verified Complete Pass or Fail Rating 4/21/2017 CM46 Making The Repairs REPAIRS Sample Medical Center Fire / Smoke Barrier Door Assembly Report of Findings and Management Tool Phase I Phase II Phase III Other REPAIRS Summary: Maintain, Repair, Replace, Remove Label, Remove Rating Phase III Date Repaired and/or Verified Complete Result: Pass or Fail 32

33 Slide 94 CM46 add information about pieces/parts allowed for making the repairs. Colin McKay, 3/29/2017

34 REPAIRS WHO DOES IT Internal Staff Carpenter General Maintenance, Facilities, Physical Plant Staff External Vendor Certified Fire Door Inspector / Firm Licensed Carpenter REPAIRS WHEN TO DO IT Repairs shall be made, and defects that could interfere with operation shall be corrected without delay Consider ILSMs in accordance with your organization s policy REPAIRS MATERIAL & PRODUCTS Damaged glazing must be replaced with labeled glazing (not wired glass) Broken components shall be: Repaired with labeled parts or parts obtained from the original manufacturer. Tested to ensure emergency operation and closing upon completion of the repairs. 33

35 REPAIRS MATERIAL & PRODUCTS When holes are left in a door or frame due to changes or removal of hardware or plant ons, the holes shall be repaired by the following methods: (1) Install steel fasteners that completely fill the holes (2) Fill the screw or bolt holes with the same material as the door or frame If repairs cannot be made with labeled components or parts obtained from the original manufacturer or retrofitted in accordance with Section 5.3, the fire door frame, fire door assembly, or appurtenances shall be replaced. REPAIRS FIELD MODIFICATIONS Where a field modification to a fire door or a fire door assembly is desired, the listing lab shall be contacted and a description of the modifications shall be presented to that laboratory. If the laboratory finds that the modifications will not compromise the integrity and fire resistance capabilities of the assembly, the modifications shall be permitted to be authorized by the laboratory without a field visit from the laboratory. Common Findings 34

36 TOP 10 FINDINGS IFDIA 1. Painted or missing fire door labels. 2. Excessive clearances around the perimeter of the door in the closed position. 3. Kick down door holders. 4. Auxiliary hardware items that interfere with the intended function of the door (barrel bolts and dead bolts, etc.) 5. Fire doors blocked in the open position. 6. Areas surrounding the fire door assembly blocked by furniture, equipment and/or boxes. Top 10 Findings IFDIA 7. Broken, defective or missing hardware items (latch bolts, and/or strike plates, closer arms, cover plates, etc.) 8. Fire exit hardware installed on doors that are not labeled for use with fire exit hardware. 9. Missing or incorrect fasteners. 10. Bottom flush bolts that do not project ½ into the strike. RPA s TOP 10 FINDINGS Rank Item # % Failure % Door or frame has open holes or breaks 2 10 Door clearances exceed clearances listed in NFPA (3/4 undercut) and NFPA 80 28% (1/8 gap) % Parts are missing or broken % Latching hardware does not operate or secures when it is in the closed position % Door frame rating label is not present and/or legible % Door has non rated protective plates 16+" % The self closing device is not operational % Signage affixed to a door does not meet the requirements listed in (Max 5% of area of door, not affixed with fasteners, not installed on vision panels) % Door rating label is not present and/or legible % Hardware is not appropriate for the door (No fire exit hardware) NOTE: More than 1 failure on a door is possible. In fact, 55% have more than 1 problem. 35

37 WHAT IFS? NUANCES What if the labeled door is in a non rated wall/barrier? What if in years past door sweeps were added on the bottom of their doors, and now those sweeps are not good enough? What if a vision panel has wired glass without a rating label? CM53 WHAT IFS? NUANCES What about hospital frames? How do we address other occupancies: An attached Business Occupancy? Ambulatory Occupancy across the street? MOB across the street? ADDITIONAL INFO CERTIFICATIONS International Fire Door Inspector s Association (IFDIA) Door & Hardware Institute s Fire and Egress Door Assembly Inspection (FDAI) 36

38 Slide 107 CM53 as time allows Colin McKay, 3/30/2017

39 QUESTIONS THANK YOU Paul Dzurinda, Colin McKay & Dave Hood 37

NFPA 80 Overview January 21, 2016

NFPA 80 Overview January 21, 2016 NFPA 80 Overview January 21, 2016 Kristin Bigda, P.E. Senior Fire Protection Engineer National Fire Protection Association Presenter Kristin Bigda, P.E. Senior Fire Protection Engineer, NFPA Building Fire

More information

WHAT TO EXPECT DURING A FIRE DOOR INSPECTION

WHAT TO EXPECT DURING A FIRE DOOR INSPECTION WHAT TO EXPECT DURING A FIRE DOOR INSPECTION Basic Fire Door Inspections 1. Fire door basic function 2. Understanding codes 3. Responsibility of end user 4. Common fire door deficiencies 5. What your door

More information

Fire Rated Door Assemblies: Compliant Designs

Fire Rated Door Assemblies: Compliant Designs Fire Rated Door Assemblies: Compliant Designs Steel Door Institute www.steeldoor.org AIA Provider #G389 Course #: SDIFIRE 1 HSW CE hour 1 Credit(s) earned on completion of this course will be reported

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

Swinging Egress and Fire Doors

Swinging Egress and Fire Doors Presented by: AHCA Seminar: Inspecting and Maintaining Swinging Egress and Fire Doors Current State CMS Memorandum July 28, 2017 Tuesday May, 3, 2016 CMS issued the final rule adopting the 2012 Life Safety

More information

About the Instructor & Presenter:

About the Instructor & Presenter: About the Instructor & Presenter: Paul G. Baillargeon, AHC, FDAI Vice President, Technical Consulting Door Security & Safety Foundation A noted veteran in the door and hardware industry, Mr. Baillargeon

More information

Fire and Smoke Door Inspections Qualified Training 02/03/17

Fire and Smoke Door Inspections Qualified Training 02/03/17 Fire and Smoke Door Inspections Qualified Training 02/03/17 Basis of Requirements NFPA 101 requires annual fire and smoke door inspections (Section 18/19.2.2.2.1) Sections 18/19.2.2.1 require compliance

More information

Laura Frye, AHC, CSI, CCS, FDAI Technical Director, DSSF Director of Certification, DHI

Laura Frye, AHC, CSI, CCS, FDAI Technical Director, DSSF Director of Certification, DHI Laura Frye, AHC, CSI, CCS, FDAI Technical Director, DSSF Director of Certification, DHI Inspecting Swinging Fire Doors with Builders Hardware A Practical Guide for AHJs and Facility Management Personnel

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance 2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance Will begin at 1 pm Housekeeping Announcements Problems during the call? Press *0

More information

Hands On Training for Fire Door Products and Fire Door Assemblies

Hands On Training for Fire Door Products and Fire Door Assemblies 2017 NFPA Conference & Expo Hands On Training for Fire Door Products and Fire Door Assemblies Presented by: Paul M. Goldense, FDAI Goldense Building Products, Inc. Jeffery S. Batick, FDAI Allegion Why

More information

Iowa State Fire Marshal

Iowa State Fire Marshal Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards

More information

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments

More information

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30 Life Safety Services, LLC TXMAS Schedule Contract Number: TXMAS-12-03FAC030 Passive Fire Protection Services Authorized Federal Supply Schedule Price List Quantity of Dampers to Inspect Per Damper to Survey

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet

Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet This document is used for frequently cited Life Safety Code violations. This is not an all-inclusive list and is intended for reference only.

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

Design, Installation, Inspection, and Maintenance

Design, Installation, Inspection, and Maintenance Presents: Swinging Fire Door Assemblies with Builders Hardware Design, Installation, Inspection, and Maintenance About the Instructor & Presenter: Paul Baillargeon, AHC, FDAI A 40 year veteran in the Door

More information

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH) The following represents a review of the Life Safety chapter of the new 2018 Joint Commission CAMH manual for

More information

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2

More information

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL

More information

Basic Fire Door Requirements

Basic Fire Door Requirements TECHNICAL DATA SERIES S D I 118-05 Basic Fire Door Requirements 2009 Steel Door Institute STEEL DOOR INSTITUTE 30200 DETROIT ROAD CLEVELAND, OHIO 44145 Technical Data Series SDI 118-2005 Basic Fire Door

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General

More information

AHCA Seminar: Inspecting and Maintaining Swinging Egress and Fire Door Assemblies

AHCA Seminar: Inspecting and Maintaining Swinging Egress and Fire Door Assemblies AHCA Seminar: Inspecting and Maintaining Swinging Egress and Fire Door Assemblies Today s Speakers Joseph A. Glaski, MBA, FASHE 20+ years as Director/VP of Facilities and Engineering Currently Director

More information

Barrier Management- Defending the Safety of Patients, Visitors, & Staff

Barrier Management- Defending the Safety of Patients, Visitors, & Staff Barrier Management- Defending the Safety of Patients, Visitors, & Staff About Your Speaker Rick Tinsley: 3 Years as Healthcare Construction Electrician 38 Years in Healthcare Facility Maintenance 13 Years

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012) 1. K62 Automatic Sprinkler Systems - Automatic sprinkler systems are continuously maintained in reliable operating condition and are inspected and tested periodically. 18.7.6, 19.7.6, 4.6.12, NFPA 13,

More information

Page 1 of 31 Second Revision No. 1-NFPA 80-2014 [ Section No. 2.3.2 ] 2.3.2 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A36/A36M,

More information

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control 11-27-12 This document is designed as a summary guide using IFC requirements for the provisions associated with exiting,

More information

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities Fire & Life Safety Code Compliance Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities LTC, Skilled Nursing Facilities COMMON LIFE SAFETY DEFICIENCIES

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

TIPS FOR BETTER JOINT COMMISSION SURVEYS

TIPS FOR BETTER JOINT COMMISSION SURVEYS TIPS FOR BETTER JOINT COMMISSION SURVEYS Washington Society for Healthcare Engineering September 21, 2011 Yakima, Washington The BASICS Most Failed Standards. Scoring. Electronic S. O. C. I.L.S.M. Building

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies

More information

The Physical Environment Portal: Module 5, LS Leadership

The Physical Environment Portal: Module 5, LS Leadership The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings

More information

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99

More information

AHC Meeting #7 July 12-13, Occupancy WG Report

AHC Meeting #7 July 12-13, Occupancy WG Report AHC Meeting #7 July 12-13, 2012 Part 1: CTC public comments on I-1/I-2 Condition designations..page 1 Part 2; AHC public comments on I-2 Condition designations Page 6 Part 3: Approved code change G244

More information

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1 Building Codes & Standards for Healthcare Building Codes and Standards AHJs Codes Defend in Place Walls Sprinklers Fire Alarm Important Dates for Healthcare Facilities 7/5/16 NFPA Life Safety Code 101

More information

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com 1 Wis Professional Engineer Experienced Facility Director Experienced AHJ WHEA Code

More information

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT

More information

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT

More information

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets

More information

LABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES

LABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES LABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 3-4, 20 CODE CHANGES Issue : Clarification of when 703.6 can be used rather than 76. 76.2 --rated glazing. --rated

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Measures (ILSM) Process

Measures (ILSM) Process Managing the Interim Life Safety Measures (ILSM) Process 1 A Program for The Texas Association of Healthcare Facility Management Monday, April 30, 2012 Robert H. Bartels, CHFM CHSP CHEP SASHE President,

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 75 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K0100 - General Requirements - Other Title General Requirements - Other General Requirements - Other List in the REMARKS

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when

More information

2000 to 2012 Hospital K-tag crosswalk matrix for hospitals 2000 Tag #

2000 to 2012 Hospital K-tag crosswalk matrix for hospitals 2000 Tag # P Language 0 Language 2018 IBC/IFC Section Commentary N/A N/A N/A K100 2 General Requirements Other List in the REMARKS section, any LSC Section 18.1 and 19.1 General Requirements that are not addressed

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates Issued September 20, 2017 Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Home Care (OME) Accreditation

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

Safety Best Practices Manual

Safety Best Practices Manual CHAPTER 24 OSHA Compliance Checklist te: This is not a comprehensive checklist. It is designed for a typical corporate aviation maintenance department. You must consult the OSHA 1910 Regulations for specific

More information

Objectives. To review updated IBC and fire test requirements when designing for life safety.

Objectives. To review updated IBC and fire test requirements when designing for life safety. Objectives To review updated IBC and fire test requirements when designing for life safety. To understand the relationship of fire safety and human impact safety. To clarify the difference between fire

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 Sharon S. Gilyeat, P.E. Lauren Schrumpf August 8, 2018 Expertly Engineering

More information

Committee Input No. 1-NFPA [ Chapter 2 ]

Committee Input No. 1-NFPA [ Chapter 2 ] of 35 11/4/2016 6:18 PM Committee Input No. 1-NFPA 80-2016 [ Chapter 2 ] The committee will review and update the editions of the referenced publications to the correct edition at the Second Draft meeting.

More information

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY 08 70 00 PART 1 - GENERAL 1.01 SUMMARY A. Section includes the design and coordination for all necessary hardware and coordination for all doors. Hardware shall include but not necessarily be limited to

More information

Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form

Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form PART 1 GRAVITY CHUTES CHUTE DESIGN AND INSTALLATION INTAKE OPENINGS LIMITED ACCESS OFFSETS DIMENSIONS VENTING CONSTRUCTION

More information

E25 (D) Automatic controls for general means of egress lighting

E25 (D) Automatic controls for general means of egress lighting Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress

More information

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Section No. Subject Page No. 1 Authority and Purpose 10-1 2 Definitions

More information

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers, NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101

More information

EC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10

EC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10 MSL Healthcare Partners, Inc. Wild Card EPs Paraphrase K-tag # EC.02.04.03 EP 14 All other electrical K-920 equipment in patient care vicinity NFPA 992012, Chapter 10 K-924 K-928 K-931 K-tag Description

More information

2016 Joint Commission Update

2016 Joint Commission Update 2016 Joint Commission Update Bert M. Gumeringer, MBA, CHFM, FASHE Asst. Vice President-Facilities Operations Texas Children s Hospital August 12, 2016 11:30am-12:30pm Top 10 Findings Comparison-2015 vs.2016

More information

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters EC.01.01.01 EP3 Related to Life Safety Code Updates Hospital (HAP) Accreditation Program The hospital has a library

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common

More information

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY 08 70 00 PART 1 - GENERAL 1.01 SUMMARY A. Section includes the design and coordination for all necessary hardware and coordination for all doors. Hardware shall include but not necessarily be limited to

More information

Presentation Outline

Presentation Outline New Annual Fire Door Inspections NFPA 80 2007 Edition April 6, 2011 Presentation Outline What is NFPA 80 Why NFPA 80 is applicable Which States have adopted NFPA 80 What has changed Who can do the inspections

More information

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICA SERVICE Form Approved OMB Exempt FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

More information

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are

More information

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1 Interim Life Safety Measures Purpose of Interim Life Safety Management BASIC SAFETY: During renovations projects in healthcare occupancies, the basic level of protection for the occupants must be maintained

More information

Chapter 2: Definitions

Chapter 2: Definitions FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter

More information

For additional information regarding R-3.1 residential care facilities please contact (951)

For additional information regarding R-3.1 residential care facilities please contact (951) Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las

More information

Accreditation Program: Hospital

Accreditation Program: Hospital ccreditation Program: Hospital Life Safety 2008 The Joint ommission on ccreditation of Healthcare Organizations ccreditation Program: Hospital hapter: Life Safety Standard LS.0001 The [organization] designs

More information

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway AIA Healthcare Group Introductions Presenters Coffman Engineers Scott M. Twele, P.E. Operations Manager,

More information

INSPECTOR I SKILLS ADMINISTRATION

INSPECTOR I SKILLS ADMINISTRATION INSPECTOR I SKILLS ADMINISTRATION 1- Prepare inspection reports so that the report is clear and concise and reflects the findings of the inspection in accordance with the applicable codes and standards..

More information

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only) 2007 & CFC Residential Care Facility Requirements (24 hour care only) Occupancy Construction Smoke Barrier I-1 Bedridden 7+non- Ambs Or bed- Ridden R-4 7+ambs (May have 6 nonambs or 6 bedridden) R-3.1

More information

SECTION INTEGRATED DOOR ASSEMBLIES

SECTION INTEGRATED DOOR ASSEMBLIES SECTION 08 17 10 INTEG DOOR ASSEMBLIES SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Integrated

More information

Are You Prepared? The impending impact of Code on Servicing Security Systems

Are You Prepared? The impending impact of Code on Servicing Security Systems Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems Siemens AG 2015 All rights reserved. usa.siemens.com/infrastructure-cities

More information

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of

More information

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in

More information

CODE SUMMARY REQUIREMENTS (NEW CONSTRUCTION/TENANT IMPROVEMENT (TI))

CODE SUMMARY REQUIREMENTS (NEW CONSTRUCTION/TENANT IMPROVEMENT (TI)) Code Summary Handout - Last revised 09/30/2014 CODE SUMMARY REQUIREMENTS WASHINGTON COUNTY OREGON (NEW CONSTRUCTION/TENANT IMPROVEMENT (TI)) NOTE: Washington County Building Services requires all commercial

More information

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary

More information

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Issued June 28, 207 Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Nursing Care Center (NCC) Accreditation Program Standard

More information

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting. Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic

More information

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD. Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 47 10/21/2015 9:37 AM First Revision No. 5041-NFPA 101-2015 [ Global Input ] Throughout the document, change electrically controlled egress door assemblies to door hardware-release of electrically locked

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

What's New January 2017 Release

What's New January 2017 Release Comprehensive Accreditation Manual for What's New January Release What s New is intended to help you understand the substantive changes in the most recent E-dition release. Please refer to the following

More information

ASHE Advocacy Team. Q4 ASHE Advocacy Liaison Webinar 12/7/16 12/7/16. Tim Adams, FASHE, CHFM, CHC Director of Leadership Development

ASHE Advocacy Team. Q4 ASHE Advocacy Liaison Webinar 12/7/16 12/7/16. Tim Adams, FASHE, CHFM, CHC Director of Leadership Development Q4 ASHE Advocacy Liaison Webinar 12/7/16 ASHE Advocacy Team Chad E. Beebe, AIA, CHFM, CFPS, CBO, SASHE Deputy Executive Director of Advocacy cbeebe@aha.org Tim Adams, FASHE, CHFM, CHC Director of Leadership

More information

Life Safety Crosswalk

Life Safety Crosswalk The Life Safety 2008 2009 Crosswalk is an easy-to-use reference tool that crosswalks The Joint Commission s 2009 Life Safety with the 2008 and National Fire Protection Association s This crosswalk excerpt

More information

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010) CHAPTER 1 SCOPE AND ADMINISTRATION 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 47 and such codes and standards shall

More information

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101

More information

Copyright Information

Copyright Information 1 Copyright Information Copyright 2013 HCPro, Inc. The Adopting the 2012 Life Safety Code : Prepare for Fire Safety Equipment Testing and Inspection Changes materials package is published by HCPro, Inc.

More information

LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT

LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT LIFE SAFETY CODE ESSENTIALS PRESENTED BY: LARRY VIGIL, RISK CONSULTANT INTRODUCTION 2007-11 5,690 Structure fires 75 Civilian Deaths $83 Million Direct Property Damage 71% in Nursery, Elementary, Middle

More information