Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Size: px
Start display at page:

Download "Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel"

Transcription

1 Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes, United States INTRODUCTION Airport departure and arrival concourses are either grouped together to form a giant building, or located separately but connected through inter-concourse transit, such as train and bus, or through pedestrian walkway in the form of above-grade bridge or below-grade pedestrian tunnel. When compared with above-grade bridges, pedestrian tunnel is often a preferred and commonly adopted approach since it is able to avoid interference with normal functioning of the airfields. Currently, the typical length of a pedestrian tunnel varies from hundreds to thousands of feet. For instance, the pedestrian tunnels are about 250 meters (800 feet) long at Chicago O Hare International Airport, 280 meters (900 feet) long at Detroit Metropolitan Wayne County Airport, 300 meters (1,000 feet) long at Los Angeles International Airport (LAX), and 460 meters (1,500 feet) long at NYC John F. Kennedy International Airport (JFK). In the design of pedestrian tunnels, one of the key challenges is to ensure the emergency means of egress to comply with applicable code requirements. In accordance with most of current codes and standards, such as IBC [1], UBC [2] and NFPA 101 [3], the maximum allowable travel distance from any point to the nearest exit is limited to 76.2 meters (250 feet) or less, with an automatic sprinkler system provided throughout the tunnel. To comply with such code requirements, most of airport pedestrian tunnels need multiple exits in the middle of as well as at the end of the tunnels. However, it would be extremely difficult to provide such exits in the middle due to security reasons and airport normal operation policies. For example, exit stairs provided in the middle of a tunnel to discharge passengers to the ground of airfield would expose them to an unsafe environment as well as affect the airfield operation, such as airplane departure, landing and maintenance. Therefore, alternative solutions using passive methods are currently adopted to meet the means of egress requirements specified in the relevant codes. Passive methods refer to the approaches that use physical barriers to form physical compartments. Typical examples are area of refuge and horizontal exits. The former is to build a fire-safe area attached immediately to the tunnel to temporarily accommodate passengers during a fire emergency. The latter is to divide a tunnel into numerous physical compartments separated by fire doors (i.e. roll-down fire shutters, Wondoors, etc.) so the travel distance on the egress path is shortened to within the code limit. In some cases, a mechanical smoke exhaust system designed on the basis of air change method is also combined with the passive methods. However, these passive methods rely on distance

2 requirements only and do not invoke a time factor to reach exits. Furthermore, they do not help with maintaining a tenable environment within the zone of fire origin for safe evacuation or relocation of occupants. In order to maintain a safe egress environment within an airport pedestrian tunnel during a fire emergency, an alternate method of design utilizing engineered performance-based design approach, virtual compartment, is proposed in this paper. Instead of currently adopted physical compartment approach, the proposed virtual compartment approach is to create multiple virtual zones that are isolated through exhausting the virtual zone of fire origin and supplying makeup air from zones immediately adjacent to the fire zone. DESIGN METHODOLOGY Pedestrian Tunnel A pedestrian tunnel with dimensions of meters (50 feet) wide by meters (1,500 feet) long by 6.1 meters (20 feet) high is modeled for the analysis. The plan and section view of the modeled pedestrian tunnel in Figure 1 shows that a 3.66-meter (12 feet) security screen is provided at the center of the pedestrian tunnel to separate the departure and arrival. Throughout the tunnel is a ceiling height of 4.88-meter (16 feet). The entire pedestrian tunnel is equally divided into three compartments named as West, Central and East s, with a length of meters (500 feet) for each. Figure 1. Plan and Section View of Pedestrian Tunnel Occupant loads of the pedestrian tunnel are determined by occupancy classification and air-flight passenger flow. An occupant load of 750 persons is estimated based on the entire tunnel area of 6, m 2 (75,000 ft 2 ) and an occupant load factor of 9.3 m 2 /P (100 ft 2 /P). An air-flight

3 passenger flow of 2,400-3,400 persons ( for Airbus A380 [4] and for Boeing [5]) is projected based on an assumption of 4-flight (2 airplanes landing and 2 take-off) passengers using the tunnel simultaneously. Therefore, approximately 4,150 occupants are assumed to be located throughout the tunnel and an occupant load of 1,384 persons for each physical/virtual compartment is assumed in this analysis. Design Goal and Objective The goal of the virtual compartment approach is to maintain a tenable environment within the zone of fire origin along the egress path for the safe evacuation or relocation of occupants. Accordingly, the performance-based design objective is to slow the smoke layer descent for a period of time sufficient to allow the occupants to safely egress from the zone of fire origin. Evaluation Criteria The evaluation criteria are values with which the performance of the proposed design can be measured, compared and deemed successful (i.e., demonstrate equivalency to the code intent). Numerous tenability criteria have been suggested and used in published fire hazard analyses and test studies over the past two decades. This performance-based analysis only considers the effect of acute (short-term) exposures to toxic products; chronic (long-term) effects are not considered. Three conditions are analyzed to determine whether tenability is maintained: visibility, gas concentration within the breathing zone, and ambient temperature. Table 1 summarizes the evaluation criteria adopted in this analysis. These criteria are utilized to analyze the modeling simulation results for determination of the smoke layer interface (i.e., maintaining the height of the smoke layer at least six feet above the walking surface) in accordance with IBC [1], NFPA 101 [3] and NFPA 92 [6]. Parameter Temperature Visibility Carbon Monoxide (CO) Table 1 Performance-Based Design Evaluation Criteria Description of Criterion Limit temperature to a maximum of 60 C (140 F) at a height of 1.83 meters (6 feet) above the walking surface [7, 8] Maintain visibility of at least 10 meters (33 feet) to an exit sign at a height of 1.83 meters (6 feet) above the walking surface [9] Limit CO concentration to 220 ppm for 20 minutes and 150 ppm for 30 minutes at a height of 1.83 meters (6 feet) above the walking surface [7, 8, 10] Value of Criterion 60 C 10 meters ppm Note that the evaluation criteria may vary with projects and authority having jurisdictions (AHJs). The evaluation criteria adopted herein are to validate the proposed virtual compartment approach as an alternate method of design for means of egress in an airport pedestrian tunnel.

4 Fire Dynamics Simulator (FDS) [11] developed by National Institute of Standards and Technology (NIST) is utilized to evaluate the toxic and thermal threat to which tunnel occupants are exposed. Design Determination Design Fires Smoke production generated by a design fire is the basis for analyzing accumulation and movement of smoke and hot gases. Design fires should consider factors such as characteristics of the fuel, fuel load, fuel spacing, and fuel configuration, fire growth, etc. In addition, the analysis above should consider heat release and sprinkler effectiveness. However, since the intent of this analysis is to demonstrate if the proposed virtual compartment method is an efficient approach as an alternate method of design for the means of egress in an airport pedestrian tunnel, the factors of design fires are not the focus of this analysis. To simplify the analysis, an unsteady sprinkler-controlled design fire of 642 KW (609 Btu/sec) with a fast T- square fire growth rate is used in the FDS simulation based on assumptions of a quick-response sprinkler system provided throughout the tunnel [1, 6, 12]. Key Design Assumptions In addition to the evaluation criteria and design fire size, the following assumptions are included in the analysis. A smoke exhaust airflow capacity of m 3 /s (84,000 ft 3 /min) is provided for the virtual compartment in fires and the makeup air supply is sized at approximately 95- percent of the smoke exhaust airflow capacities. All smoke exhaust and makeup air supply points are located at the ceiling of the tunnel. The soot yield (i.e., the fraction of mass converted into smoke particulate) is assumed to be approximately 5% to accommodate mixed combustible materials (wood and plastics) that may be present in the tunnel. The Carbon Monoxide (CO) yield is assumed to be approximately 4% for the mixed combustible materials. A default visibility factor of 3 for non-illuminated objects (i.e., light-reflecting signs) is used in the fire modeling evaluation per Mulholland, SPFE Handbook [9]. Design Fire Scenarios In this analysis, two cases, Central (middle compartment) and West (end compartment), are examined. In each case, we compare the virtual compartment approach with the physical compartment approach, as shown in Table 2.

5 Case No. Case 1: Central Case 2: West Table 2 Proposed Design Fire Scenarios Fire Location Center of Virtual Center of Physical Center of Virtual Center of Physical Sprinkler Controlled Yes Yes Yes Yes Fire Growth Rate Fast, T-Square Unsteady Fast, T-Square Unsteady Fast, T-Square Unsteady Fast, T-Square Unsteady Max. HRR (kw) Smoke Exhaust 642 Yes 642 No 642 Yes 642 No RESULTS AND DISCUSSION Timed Egress Analysis The most current codes and handbooks require and recommend that a smoke control system operate to maintain a tenable environment for the duration (ASET) longer than the required safe egress time (RSET). The RSET typically consists of the following components [1, 13]. RSET = td + tn (tp-e + te) Where: td = Time from fire ignition to detection (detection time) tn = Time from detection to notification of occupants of a fire emergency (notification time) te = Time from notification until evacuation commences (pre-movement time) tm = Time from start of evacuation movement until safety is reached (movement time) A detection time of 60 seconds is obtained from the FDS modeling analysis based on area smoke detectors placed at a meter (30 feet) spacing throughout the modeled pedestrian tunnel. In accordance with 2013 edition NFPA 72 [14], actuation of alarm appliances should occur within 10 seconds after the activation of an initiating device, but can have an alarm investigation phase up to 3 minutes (positive alarm sequence). From airport operation standpoints, the positive alarm sequence is adopted and the notification time is 3 minutes (180 seconds). The SFPE Handbook presents a study conducted by the British Standards Institute in 1997 [15]. This study gives several different times for the pre-movement time to start based on the type of notification system in the building. The first time (W1) is less than 1 minute for buildings with live directives through a voice communication system and trained, uniformed staff. The second time (W2) is 3 minutes for buildings with nondirective voice messages and trained staff. The third time (W3) is greater than 4 minutes for buildings with a fire alarm signal and staff with no

6 relevant training. Since airports are typically provided with live directives through a voice communication system and trained staff, a pre-movement time of 1 minute (W1) is assumed. The movement time includes travel time to an exit component, flow time through that exit component, time of the last person to egress to safety and all associated queuing times. The traveling speed of occupants is calculated using the equation below [13]: S = k - akd Where: S = Speed along the line of travel (m/s) k = Constant ( m/s (200 feet/min) for concourses per 2014 NFPA 130 [16]) a = Constant, D = Population density in persons per unit area (person/m 2 ) A maximum travel distance from the most remote location of compartments is 76.2 meters (250 feet) [1, 3]. The flow time of occupants passing through an exit component is determined in the following equation [13]: Fc = Fs We Where: Fc = Calculated flow (persons/minute) Fs = Specific flow (82 persons/m/min (25 persons/feet/min) per 2014 NFPA 130 [16]) We = Effective width of the component being traversed (a typical reduction of meters (6 inches) from each side of doors and meters (18 inches) for concourses [13]), four m doors assumed to be provided for each physical compartment, and about meters (42 feet) width of the tunnel assumed to be effective width at nonended sides and two m doors at ended sides for virtual compartments The passage time for the last occupant passing through an exit component is calculated using the occupant load at an exit component divided by the calculated flow. The movement time is the sum of the travel time to an exit component and the time to egress through that exit component. Tables 3 and 4 summarize the calculated movement time and the RSET based on two cases, total 4 scenarios listed in Table 2 above. Case No. Case 1 Case 2 Location Central Virtual Central Physical West Virtual West Physical Table 3 Calculated Movement Time Travel Speed (m/min) Travel Time (s) Calculated Flow (p/min) Passage Time (s) Movement Time (s) , ,

7 Case No. Case 1 Case 2 Location Central Virtual Central Physical West Virtual West Physical Table 4 Required Safe Egress Time (RSET) Detection Time (s) Notification Time (s) Pre- Movement Time (s) Movement Time (s) RSET (s) FDS Simulation Results Case 1 A design fire in the center of the Central is simulated with provision of physical separation (i.e., roll-down fire shutters) and virtual separation (i.e., exhaust the virtual compartment in alarm and supply from adjacent virtual compartments). The smoke layer interface at 1.83 meters (6 feet) height above the floor are compared in Figure 2 and Figure 3, which present the outcomes of visibility, a dominant criterion among the three design evaluation criteria to justify the smoke layer height. Central Physical at t=288s Central Virtual at t=900s Central Physical at t=549s Central Virtual at t=1,800s Figure 2. Visibility (m) isosurfaces indicating where visibility is 10m (black line shows 1.83m)

8 Central Physical at t=288s Central Virtual at t=900s Central Physical at t=549s Central Virtual at t=1,800s Figure 3. Visibility (m) horizontal slices indicating where visibility is 10m at 1.83m above floor For the physical compartment, the simulation results show that the smoke layer height starts descending below 1.83 meter (6 feet) around 288 seconds at the physical barrier area and the entire compartment becomes untenable at approximately 549 seconds (all exits blocked by smoke) after ignition of the design fire. For the virtual compartment, the smoke layer height remains above 1.83 meter (6 feet) for the whole simulation duration of 1,800 seconds (30 minutes). As shown in Figure 2, smoke is almost fully constrained within the virtual compartment in fire and does not spread to adjacent non-fire virtual compartments. In addition, the simulation results in Figure 3 for the physical compartment clearly indicate that the smoke layer height descends below 1.83 meter (6 feet) starting from two ends of the compartment.

9 Case 2 A design fire in the center of the West (end compartment) is simulated with provision of physical and virtual separation. The smoke layer interface at 1.83 meter (6 feet) height above the floor are compared in Figure 4 and Figure 5 that only show the visibility simulation outcomes. West Physical at t=270s West Virtual at t=810s West Physical at t=468s West Virtual at t=1,800s Figure 4. Visibility (m) isosurfaces indicating where visibility is 10m (black line shows 1.83m) The simulation results show that the smoke layer height begins descending below 1.83 meter (6 feet) around 270 seconds at the physical barrier area and the entire compartment becomes untenable at approximately 468 seconds (all exits blocked by smoke) after ignition of the design fire in the physical compartment. In the virtual compartment, the smoke layer height descends below 1.83 meter (6 feet) about 810 seconds at the end of fire-side area but remains above 1.83 meter (6 feet) at all other areas for the whole simulation duration of 1,800 seconds (30 minutes). When compared with Case 1 results, similar outcomes are obtained: smoke is contained within the virtual compartment in fire and the smoke layer height descends below 1.83 meter (6 feet) starting from two ends of the compartment.

10 West Physical at t=270s West Virtual at t=810s West Physical at t=468s West Virtual at t=1,800s Figure 5. Visibility (m) horizontal slices indicating where visibility is 10m at 1.83m above floor Discussion In comparison of the timed egress analysis and FDS simulation results, the ASET of 288 seconds is less than the RSET of 714 seconds for the Case 1 physical compartment scenario. Similarly, the ASET of 270 seconds is less than the RSET of 714 seconds for the Case 2 physical compartment scenario. Thus, the physical compartment approach cannot ensure occupants to safely evacuate or relocate to adjacent compartments and most of occupants in the fire compartment may be exposed to an unsafe environment. In contrast, in all virtual compartment scenarios, the ASET is greater than the RSET and occupants are able to safely evacuate or relocate from the fire compartment. Typically, the design fire size is one of key factors to impact duration of tenability. For the physical compartment approach, the larger the design fire is, the quicker the compartment

11 becomes untenable. For the virtual compartment approach, the smoke exhaust fan capacities can be adjusted along with the design fire size change to maintain tenability longer than RSET. Another finding from this study is that an apparent time lag exists between the fire side and nonfire side separated by security screens within the same fire compartment in both physical and virtual scenarios, as shown in Figures 3 and 5. The 3.66-meter (12 feet)-tall security screen is the cause of this difference. Furthermore, the isosurface outcomes presented in Figures 2 and 4 clearly demonstrate the impact of makeup air supply on tenability. When a fire occurs in the central virtual compartment, the smoke layer interface can be maintained steadily because of the equal makeup supply from the two adjacent sides. However, when a fire occurs in an end virtual compartment (west or east compartment), the smoke layer becomes fluctuated and accumulated at the dead-end side due to makeup air coming from one side only. In addition, the simulation results indicate that the smoke layer height starts to descend below 1.83 meter (6 feet) from two ends of the fire compartment in physical compartment scenarios, where the horizontal exit or exit access doors are typically located. This implies that the ASET could be greatly reduced for the physical compartment approach using the horizontal exits method. CONCLUSION This paper performed a preliminary analysis on the virtual compartment design concept. The modeling outcomes indicate that it seems to be a more effective alternate design approach when compared with physical compartment approach, since it is able to achieve the fire life safety code requirements as well as satisfying the airport operation requests. Generally speaking, prescriptive codes have advantages: it is easy to design through following prescriptions and AHJs can easily justify if such design complies with code requirements. However, prescriptive codes may not clearly address and truly implement fire life safety objectives for novel buildings and buildings associated with special operation necessity. The fire modeling analysis in this study demonstrates that the code-compliance physical compartment approach using horizontal exit method does not actually achieve the fire life safety objectives, i.e. safe evacuation or relocation of occupants in a subterranean airport pedestrian tunnel. Furthermore, the code-compliance physical compartment approach may affect TSA s justification and responses to emergency events. In contrast, the virtual compartment approach that exhausts smoke of the fire zone and supplies makeup air from adjacent zone(s) is able to achieve the equivalency of the fire life safety objective specified in building codes and standards. In addition, it does not adversely affect the airport security and normal operation requests. Although this study only analyzed a pedestrian tunnel that is divided into three virtual compartments at a meter (500 feet) length of each, this approach can be extended to

12 multiple compartments with various lengths as needed by codes and standards and as requested for airport operation purposes. In future studies, the effects of other factors, such as connection of the end compartment with the above-grade concourses and makeup air velocity, needs to be investigated. REFERENCES 1. International Code Council, 2012 International Building Code. 2. International Council of Building Officials, 1997 Uniform Building Code. 3. National Fire Protection Association, 2015 NFPA 101: Life Safety Code. 4. Airbus Group, ( 5. Boeing Company, ( 6. National Fire Protection Association, 2012 NFPA 92: Standard for Smoke Control System. 7. Purser, D.A., McAllister, J.L., Assessment of Hazards to Occupants from Smoke, Toxic Gases, and Heat, SFPE Handbook of Fire Protection Engineering Fifth Edition, SFPE, 2016, pp Klote J.H., Evans D.H., Atria and Other Large Spaces, A Guide to Smoke Control in IBC 2006, International Code Council, 2007, pp Yamada, T., Akizuki, Y., Visibility and Human Behavior in Fire Smoke, SFPE Handbook of Fire Protection Engineering Fifth Edition, SFPE, 2016, pp Committee on Toxicology, Carbon Monoxide, Acute Exposure Guideline Levels for Selected Airborne Chemicals: Volume 8, National Research Council, 2010, pp National Institute of Standards and Technology, Fire Dynamics Simulator, Klote, J.H., Method of Predicting Smoke Movement in Atria With Application to Smoke Management, Building and Fire Research Laboratory and National Institute of Standards and Technology, Nov.1994, pp Gwynne, S.M.V., Eric R.R., Employing the Hydraulic Model in Assessing Emergency Movement, SFPE Handbook of Fire Protection Engineering Fifth Edition, SFPE, 2016, pp National Fire Protection Association, 2013 NFPA 72: Standard for National Fire Alarm Code. 15. Gwynne, S.M.V., Boyce, K.E., Engineering Data, SFPE Handbook of Fire Protection Engineering Fifth Edition, SFPE, 2016, pp National Fire Protection Association, 2014 NFPA 130: Standard for Fixed Guideway Transit and Passenger Rail System.

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS

TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS Arthur H. Gager III, PE and Gary Dominguez 1 Jensen Hughes agager@jensenhughes.com 2 Jensen Hughes gdominguez@jensehughes.com Abstract. FDS

More information

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses

More information

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo,

More information

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG 1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for

More information

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson Construction Warehouse FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson 1 Statement of Disclaimer This project report is a result of a class assignment;

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces ZHENKUN WU 1,2, HAIHANG LI 1, YAPING HE 3, DECHUANG ZHOU 1, JIAN WANG 1 1 State Key Laboratory of Fire Science, University of

More information

The Study of Evacuation Times from the Multiplex Theatres

The Study of Evacuation Times from the Multiplex Theatres American Journal of Applied Sciences 9 (3): 321-326, 2012 ISSN 1546-9239 2012 Science Publications The Study of Evacuation Times from the Multiplex Theatres 1 Khanitha Songsakulchai, 2 Supat Patvichaichod

More information

Will Clay Spring 2014

Will Clay Spring 2014 Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in

More information

Sprinklers Modeling for Tunnel Road Fire Fighting

Sprinklers Modeling for Tunnel Road Fire Fighting Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and

More information

Figure 1. Structure Used For the Simulations.

Figure 1. Structure Used For the Simulations. OVERVIEW: Vent, Enter, Search (VES) is one of the most talked about tactics in the fire service today. When used correctly, its positive impact can be measured by the lives it saves. The VES method is

More information

Statue of Liberty: A Risk Analysis

Statue of Liberty: A Risk Analysis Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress

More information

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS PROCEEDINGS, Fire and Evacuation Modeling Technical Conference 211 Baltimore, Maryland, August 15-16, 211 EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS Brian Salyers, Bevan Jones Holmes Fire 13 Sutter

More information

Construction Innovation Center Building 186

Construction Innovation Center Building 186 Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview

More information

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Recent BRANZFIRE enhancements and validation

Recent BRANZFIRE enhancements and validation Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately

More information

Smoke Management in Subway Stations Due to Train Arson Fire Scenario

Smoke Management in Subway Stations Due to Train Arson Fire Scenario Smoke Management in Subway Stations Due to Train Arson Fire Yunlong Liu 1, Sean Cassady 1, Jerry Casey 1, Sanja Zlatanic 2 & Nasri Munfah 2 1. HNTB Corporation, 600 108 th Avenue NE STE 900, Bellevue,

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

EVACUATION MODELLING IN ROAD TUNNEL FIRES

EVACUATION MODELLING IN ROAD TUNNEL FIRES Complex Underground Multipurpose Facilities: Safety Challenges and Solutions Workshop organised by the ITA-COSUF as part of the ITA-AITES World Tunnel Congress 2013 EVACUATION MODELLING IN ROAD TUNNEL

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology PO Box 310 North

More information

Smoke Management in High-Rise Structures

Smoke Management in High-Rise Structures Smoke Management in High-Rise Structures Most modern building codes define a high-rise structure as a building greater than 75 feet in height from the lowest level of fire department vehicle access to

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 909 SMOKE CONTROL SYSTEMS 909.1 Scope and purpose. This section applies to mechanical or passive smoke control systems when they are required for new buildings or portions thereof by provisions

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

Case Study 1 Underground car park

Case Study 1 Underground car park Case Study 1 Underground car park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, INBEPO Wroclaw, Poland 1. Introduction

More information

Practicalities and Limitations of Coupling FDS with Evacuation Software

Practicalities and Limitations of Coupling FDS with Evacuation Software ABSTRACT Practicalities and Limitations of Coupling FDS with Evacuation Software Daniel Rådemar, WSP, Sweden Daniel Blixt, WSP, Sweden Brecht Debrouwere, WSP, Sweden Björn Grybäck Melin, WSP, Sweden Andrew

More information

Potential Impact of New UL Fire Test Criteria

Potential Impact of New UL Fire Test Criteria Potential Impact of New UL Fire Test Criteria Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 7, 2014 Outline Background Recent History Task Group Progress

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

Fire Hazard Analysis of Technical Area 53 Building 1

Fire Hazard Analysis of Technical Area 53 Building 1 Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the

More information

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav

More information

Case Study 2 (Production and Storage Buildings) - Spain

Case Study 2 (Production and Storage Buildings) - Spain Case Study 2 (Production and Storage Buildings) - Spain OBJECTIVE Developed by the SFPE Spanish Chapter Editor: Jimmy Jönsson, JVVA Fire & Risk The objective of this case study is to show how a project

More information

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University

More information

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass.

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass. THE CAPABILITIES OF SMOKE CONTROL: FUNDAMENTALS AND ZONE SMOKE CONTROL John H. Klote Center for Fire Research National Institute of Standards and Technology Gaithersburg, Maryland, U.S.A. 20899 Edward

More information

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,

More information

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016 FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural

More information

Selecting appropriate egress strategies

Selecting appropriate egress strategies Selecting appropriate egress strategies The selection of an appropriate egress strategy requires a good understing of the building its occupants, the protection measures in place, the expected emergency

More information

4.13 Security and System Safety

4.13 Security and System Safety 4.13 4.13.1 Introduction This section describes the affected environment and environmental consequences related to security and system safety from operations of the NEPA Alternatives. Information regarding

More information

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

Emergency Ventilation System Design - Preliminary Report Shishir Gupta Emergency Ventilation System Design - Preliminary Report Shishir Gupta (shishir@mechartes.com), Abstract The existing stations and tunnels of Metro Railway, Kolkata are not equipped with effective emergency

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED - 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company

More information

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-02-07 THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS March, 2007 Society of Fire Protection Engineers - 1 - Position

More information

The Singapore Fire safety Engineering Guidelines (SFEG)

The Singapore Fire safety Engineering Guidelines (SFEG) The Singapore Fire safety Engineering Guidelines (SFEG) Nicholas Lee Senior Consultant (Performance-Based) Fire Safety & Shelter Department Singapore Civil Defence Force Introduction The fire safety standards

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project Fire Protection System and Life Safety Evaluation Of Building X By Anthony W. Sublett Culminating Project Presented to the Faculty of the Graduate School of California Polytechnic State University in Partial

More information

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007

More information

26 June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

26 June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1002 26 June 2001 GUIDELINES ON ALTERNATIVE

More information

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

Natural Ventilation A Green Smoke Control Approach

Natural Ventilation A Green Smoke Control Approach Natural Ventilation A Green Smoke Control Approach Presented By: William Koffel, P.E., FSFPE Adam Graybeal, P.E. Authored by: Erik Anderson, P.E Koffel Associates Background New Engineering, Aviation,

More information

Fire Protection Analysis DCI Data Center Building

Fire Protection Analysis DCI Data Center Building Fire Protection Analysis DCI Data Center Building California Polytechnic State University FPE 596 Culminating Experience in Fire Protection Engineering Bryan Hathaway M.S. Fire Protection Engineering -

More information

An Overview to Designing Smoke-Control Systems

An Overview to Designing Smoke-Control Systems The following article was published in ASHRAE Journal, June, 2002. Copyright 2002 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Aspirating Gas Detection CFD Modelling Predicts Application Performance Aspirating Gas Detection CFD Modelling Predicts Application Performance Yun Jiang Xtralis, Bentleigh East, Australia Claudio Groppetti Xtralis, Avon, MA, USA Abstract Historically gas detection has utilized

More information

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building D. YUNG, G.V. HADJISOPHOCLEOUS and G. PROULX National Fire Laboratory Institute

More information

Fire Scenario Influence of Material of Boundary Condition on Results

Fire Scenario Influence of Material of Boundary Condition on Results Fire Scenario Influence of Material of Boundary Condition on Results HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING Luciano Nigro Andrea Ferrari Elisabetta Filippo Hughes Associates Europe srl

More information

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title: ctbuh.org/papers Title: Authors: Subjects: Keywords: Fire Engineering the Tallest Building in the Historic City of Manchester, UK Dean McGrail, Associate Director, WSP Group Simon Lay, Technical Director,

More information

AHC Meeting #7 July 12-13, Fire Safety WG Report. A Cycle Approved Code Changes

AHC Meeting #7 July 12-13, Fire Safety WG Report. A Cycle Approved Code Changes AHC Meeting #7 July 12-13, 2012 A. 2012 Cycle Approved Code Changes The following are the APPROVED Group A code changes created by the AHC Fire Safety Work Group that were considered at the 2012 Code Development

More information

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD BFS 2011:27 with amendments up to BFS 2013:12 The

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363) EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT 20-07 TASK 363) Louis Ruzzi PennDOT District 11 Igor Maevski, PhD, PE - Jacobs Agenda AASHTO T20 Technical Committee Roadway Tunnels

More information

Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)

Case Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) So What Are You We Going to Show You? A lot of tables, simplified methods

More information

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition International Journal of Ventilation ISSN 1473-3315 Volume 8 No 4 Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition Y. Liu 1, J. Munro 1 and B. Dandie 2 1 Parsons

More information

Preliminary Fire/Life Safety Assessment Task No (Submittal No. PH b14

Preliminary Fire/Life Safety Assessment Task No (Submittal No. PH b14 ` REGIONAL CONNECTOR TRANSIT CORRIDOR PROJECT Contract No. E0119 Preliminary Fire/Life Safety Assessment Task No. 7.1.1.2 (Submittal No. PH2.7.1.1.2.b14 Prepared for: Prepared by: The Connector Partnership

More information

A New Zealand Case Study Building Design 11 th International Conference on Performance

A New Zealand Case Study Building Design 11 th International Conference on Performance A New Zealand Case Study Building Design 11 th International Conference on Performance Prof Charles Fleischmann University of Canterbury Dept. Civil and Nat Res Eng. Christchurch, New Zealand Carol Caldwell

More information

A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A

A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A Ludwig Jerräng Carlstedt Fire Protection Engineer, bachelor's level 2017 Luleå University

More information

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com

More information

SMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame

SMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame SMOKE CONTROL: ISSUES / APPROACHES Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony Journal of Civil Engineering and Architecture 9 (215) 1341-1353 doi: 1.17265/1934-7359/215.11.9 D DAVID PUBLISHING Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters

More information

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management

More information

SFPE PUBLICATIONS & TRAINING. The leaders in engineering a fire safe world.

SFPE PUBLICATIONS & TRAINING. The leaders in engineering a fire safe world. SFPE PUBLICATIONS & TRAINING The leaders in engineering a fire safe world. Did you know that SFPE offers premier on-site training throughout the world? SFPE on-site training courses are a cost-effective

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

Fire Research and Education at the University of Maryland

Fire Research and Education at the University of Maryland Fire Research and Education at the University of Maryland J. G. Quintiere Department of Fire Protection Engineering March 7,8 2005 2nd Int. Symp. 21st Century Center of Excellence Program History of FPE

More information

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol

More information

Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building

Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building 5A-4 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building A. Sekizawa 1, S. Nakahama

More information

Is There A Need to ENCLOSE ELEVATOR LOBBIES IN TALL BUILDINGS?

Is There A Need to ENCLOSE ELEVATOR LOBBIES IN TALL BUILDINGS? Is There A Need to ENCLOSE ELEVATOR LOBBIES IN TALL BUILDINGS? by Richard W. Bukowski, P.E., FSFPE Several proposals have been submitted in recent years to model building code organizations to require

More information

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS.

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-01-05 THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS October, 2005 Society of Fire Protection Engineers - 1 - Position Statement

More information

Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium

Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium Ramisetti Sairam Department of Building Technologies &Services, School of Planning and Architecture, JNA&FAU Hyd E-mail :

More information

A Monte Carlo Approach for the Design of Thermal Fire Detection System

A Monte Carlo Approach for the Design of Thermal Fire Detection System A Monte Carlo Approach for the Design of Thermal Fire Detection System Walter W. Yuen Department of Mechanical & Environmental Engineering University of California at Santa Barbara California, USA and

More information

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects

A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety Davood Afshari 1 Richard Welsh 2 Maryam Moghaddas 3 Sara Afsharikia 1 Amir Tavakoli 4 1 Lead Technical

More information

BR-BO Adopted June 1, Evacuation Safety Performance Evaluation Manual

BR-BO Adopted June 1, Evacuation Safety Performance Evaluation Manual BR-BO-07-01 Adopted June 1, 2000 Evacuation Safety Performance Evaluation Manual Article 1: Scope of Application This manual applies to the following types of performance evaluations: (1) Performance evaluations

More information

( )

( ) Course Title: Fire Dynamics (3087) Course Number: FST - 3087 Course Credit Hours: (3) Three Semester Hours Instructor Information: Bernard W. Becker, III, MS (937-751-7371) ccfdchiefbecker@yahoo.com Textbook:

More information

F.R.A.M.E. EVENT NETWORKS used in "FRAME".

F.R.A.M.E. EVENT NETWORKS used in FRAME. EVENT NETWORKS used in "FRAME". In 2004, Dipl. Ing. Trond Maag wrote his doctorates' thesis "Risikobasierte Beurteilung der Personensicherheit von Wohnbauten im Brandfall unter Verwendung von Bayes'schen

More information