ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

Size: px
Start display at page:

Download "ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415"

Transcription

1 ASSESSMENT REVIEW Review of Assessment Report WFRA C91415 Fire resistance performance of steel electrical wall boxes mounted in plasterboard partitions with modified mounting arrangements, box design and facia plates EWFA Report No: Report Sponsor: Schneider Electric () Pty Ltd Port Wakefield Road Gepps Cross SA 5094 AUSTRALIA

2 Page 2 of 6 DOCUMENT REVISION STATUS Date Issued Issue No Description 11/03/ Initial Issue CONTACT INFORMATION Exova Warringtonfire Aus Pty Ltd - ABN NATA Registered Laboratory Unit 2, Hammond Road Dandenong Victoria 3175 T: +61 (0) F: +61 (0) New South Wales Suite 2002a, Level 20, 44 Market Street Sydney NSW 2000 T: +61 (0) F: +61 (0) Victoria Unit 2, Hammond Road Dandenong Victoria 3175 T: +61 (0) F: +61 (0) Queensland Northpoint, Unit 29, Level North Quay Brisbane QLD 4000 T: +61 (0) F: +61 (0)

3 Page 3 of 6 1 INTRODUCTION The assessment referenced WFRA C91415, dated 12th August 1996 and provided an opinion about the fire resistance performance of steel electrical wall boxes with Grafitex intumescent material when mounted in plasterboard partitions if tested in accordance with AS and AS CONFIRMATION OF SPECIFICATION The sponsor of the tests and assessment was Gerard Industries Pty Ltd, which is now named Schneider Electric () Pty Ltd (recently changed from Clipsal Pty Ltd). Schneider Electric () Pty Ltd has confirmed in writing that there are no changes to the specification, design and material of the protection systems or components since the issue of the original formal assessment, i.e. WFRA C Schneider Electric () Pty Ltd has given permission for the preparation of this review. Schneider Electric () Pty Ltd has however changed the names under which the assessed products are sold. The table below shows the names of the products assessed in C91415 and the equivalent name the products are currently sold under. Product Name as Assessed in C91415 Current Product Name 2157/3 2157/3F 2157/2 2157/2F 157/2 157/2F 157/1 157/1F The performance of various steel electrical wall boxes was assessed in reports C91357 and C91358, dated and respectively, in accordance with AS and AS Assessment report WFRA C91415 dated referred to C91357 and C91358 when assessing performance if tested in accordance with AS and AS Since the issue of the assessment report WFRA C91415, revised n Standards AS and AS have been issued. The assessment WFRA C91415 was prepared with respect to AS and AS and there are variations between these test methods and AS and AS These variations and the affect these differences have on fire resistance performance of the referenced test specimens are discussed below. Temperature Regime The furnace heating regime in fire resistance tests conducted in accordance with AS follows a similar trend to that in AS The specified specimen heating rate in AS is given by: Where; T t -T 0 = 345log (8t+1) T t = Furnace temperature at time t, in degrees Celsius. T o = Initial furnace temperature, in degrees Celsius, not less than 10 C nor more than 40 C. t = Time into the test, measured from the ignition of the furnace, in minutes. The heating regimes in AS and AS vary in that the former is an expression of the temperature rise in the furnace above an initial ambient temperature, and the latter although similar, assumes that the initial furnace temperature (T o ) is 20 C irrespective of the actual temperature. A test conducted in accordance with AS on a warm day (ambient temperature above 20 o C) could therefore be slightly more onerous than that in accordance with AS

4 Page 4 of 6 The parameters outlining the accuracy of control of the furnace temperature in AS and AS are not appreciably different. Furnace overpressure AS requires a minimum pressure differential of 8Pa above the laboratory atmosphere for both vertical and horizontal specimens. AS requires a minimum pressure differential of 15Pa ± 3Pa above the laboratory atmosphere at the centre of the lowest penetration for vertical specimens and 20Pa ± 3Pa at 100mm below the soffit for horizontal specimens. The increase in furnace overpressure is only expected to be significant if cracks or fissures had developed in the test specimen. Performance Criteria AS specifies the following performance criteria for building materials and structures: Structural Adequacy Integrity Insulation Structural Adequacy The structural adequacy criteria are not relevant to this test Integrity The specimen shall be deemed to have failed the integrity criterion in accordance with AS (in regard to service penetrations) if the specimen Collapses Sustained flaming on the non fire side in excess of 10 seconds. Ignites a cotton pad within 30 seconds when applied. The integrity criterion varies slightly between AS and AS The specimen is deemed to have failed to AS if the specimen Collapses The development of cracks, fissures or other openings through which flames or hot gases can pass. Sustained flaming on the non fire side in excess of 10 seconds. The integrity criterion in accordance with AS is generally more stringent and would normally occur prior to integrity failure in accordance with AS Insulation The insulation criteria of AS and AS remain the same, although the location of thermocouples has been revised. AS specifies thermocouples to be located 25mm and 400mm from the separating element on the penetrating element to the unexposed side. Although AS does not specify the location of thermocouples, it refers back to AS which only specifies thermocouples to be located 25mm from the separating element on the penetrating element. The insulation criterion in accordance with AS is generally more stringent and would normally occur prior to insulation failure in accordance with AS Applicability of Test Data in General In general the test specimen furnace exposure conditions of AS are not appreciably different from the requirements of AS The difference in specified furnace pressures between the revisions of AS (1990 to 2005) is only expected to be significant if cracks or fissures had developed in the test specimen as higher furnace overpressure has a greater tendency to force hot gases from the furnace to the non-fire side, potentially adversely affecting both the integrity and insulation performance.

5 Page 5 of 6 Referenced test data in C91357 indicated that no integrity failure nor through gaps were observed in the service penetrations for the period of the assessed Fire Resistance Level of 60 minutes. Test results referenced in C91358 indicated that integrity failure of some test specimens occurred before 120 minutes. However, the failure was attributed to the premature collapse of part of the separating element cause by the presence of a large opening, independent to the protection system considered in this report. It is considered that the increased overpressure requirement specified in AS would not have a significant influence to the fire resistance performance of the test specimen. The integrity criterion in accordance with AS is generally more stringent and would normally occur prior to integrity failure in accordance with AS because under most circumstances, a through gap permitting an uninterrupted view into the furnace interior would first form to allow passage of a gap gauge and based on the above discussion with respect to furnace overpressure the differences in integrity performance requirements specified in AS would not have a significant influence to the fire resistance performance of the test specimen. Based on the above discussion it is considered that insulation and integrity results of the tests referenced in WFRA C91415 can be used to assess the insulation and integrity performance of specimen if subjected to a fire resistance test in accordance with AS FORMAL OPINION SUMMARY Since the issue of assessment report WFRA C91415, n Standard AS and AS have been revised. The relevance of the differences between this and the earlier Standards have been discussed in Section 2 and not found to significantly affect the technical conclusions of the assessment. The procedures adopted for the original assessment have been re-examined and are similar to those currently in use. The specification used for the original assessment has been re-examined and found to be satisfactory. Therefore, with respect to the opinion about the fire resistance performance of steel electrical wall boxes with Grafitex intumescent material when mounted in plasterboard partitions referenced in Assessment Report WFRA C91415, it is confirmed that the assessed performance is considered valid with respect to AS and AS , subject to the validity requirements in Section 4. 4 VALIDITY This assessment review does not provide an endorsement by Exova Warringtonfire Aus Pty Ltd of the actual products assessed. This review is based on information and experience available at the time of preparation. The published procedures for the conduct of tests and the assessment of test results are the subject of constant review and improvement and it is recommended that this report be reviewed on or before the stated expiry date. This review remains valid until the expiry date stated in Section 5.5 subject to compliance with the applicant undertakings and conditions in the original assessment and this review.

6 Page 6 of 6 5 AUTHORITY 5.1 APPLICANT UNDERTAKINGS AND CONDITIONS OF USE By using this report as evidence of compliance or performance, the applicant(s) confirms that: to their knowledge the component or element of structure, which is the subject of this review, has not been subjected to a fire test to the Standard against which this assessment is being made, and they agree to withdraw the reviewed assessment from circulation should the component or element of structure be the subject of a fire test by a test authority in accordance with the Standard against which this review is being made and the results are not in agreement with the reviewed assessment, and they are not aware of any information that could adversely affect the conclusions of the reviewed assessment and if they subsequently become aware of any such information, agree to ask the assessing authority to withdraw the reviewed assessment. there have been no changes to the materials and elements that are the subject of this assessment since the fire test other than addressed in the reports referenced in this assessment. 5.2 GENERAL CONDITIONS OF USE This report may only be reproduced in full without modifications by the report sponsor. Copies, extracts or abridgments of this report in any form shall not be published by other organisations without the permission of Exova Warringtonfire Aus Pty Ltd 5.3 AUTHORISATION ON BEHALF OF EXOVA WARRINGTONFIRE AUS PTY LTD Prepared by: Reviewed by: S. Hu K. G. Nicholls 5.4 DATE OF ISSUE 11/03/ EXPIRY DATE 31/03/2018

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves. Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves Report No: 172158 Prepared for: Lindab Ventilation AB SE 26982 Båstad Järnvägsgatan

More information

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Air Leakage Performance of

More information

Fire Collars for Floor Wastes Understanding BCA Compliance Options

Fire Collars for Floor Wastes Understanding BCA Compliance Options Fire Collars for Floor Wastes Understanding BCA Compliance Options February 2005 Introduction There has been a great deal of discussion in recent times regarding fire testing requirements for fire collars

More information

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES Report number FSP 1360 CSIRO job number SP3241 Date of issue 31 JULY 2009 Client SNAP FIRE SYSTEMS PTY LTD. Commercial-in-confidence

More information

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS Report number FSP 1290A CSIRO job number LP46ASP3085 Date of issue 30 NOVEMBER 2007 Client EFFICIENCY MATRIX PTY LTD and YOUNGEN

More information

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report

More information

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Page 1 of 27 Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Test Sponsor Saveguard (UK) Limited Warrington Fire Research Centre Ltd.,

More information

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services Test Report Author: Peter Gordon Report number: FSP 1960 Date: 5 February 2019 Client:

More information

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services Test Report Author: Mario Lara-Ledermann Report number: FSP 1658 Date: 15 January

More information

BS EN ISO : 2010

BS EN ISO : 2010 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination

More information

BS EN : 2001 & IEC :2000

BS EN : 2001 & IEC :2000 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 60695-2-11: 2001 & IEC 60695-2-11:2000

More information

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 1716: 2010 Determination Of The

More information

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

Fire-resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Chris Wojcik Report number: FSP 1735 Date: 8 September 2016 Client:

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13 Test Report No. AJHG1501000530FB Date: FEB.17, 2015 Page 1 of 13 ZHEJIANG TERASUN AIR DUCT CO., LTD MAREN VILLAGE, CHONGREN INDUSTRIAL ZONE, CHONGREN TOWN, SHENGZHOU CITY, ZHEJIANG PROVINCE, CHINA The

More information

BS EN ISO : 2010

BS EN ISO : 2010 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Fire Tests For Determination Of The Burning

More information

Fire resistance test on fire collars protecting a concrete slab penetrated by services

Fire resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1601a Date: 11 April 2014 (This report

More information

25 th November Title:

25 th November Title: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IEC 60331-11-21 Method of test defined in

More information

BS EN ISO : 2010

BS EN ISO : 2010 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination

More information

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2002 Fire Tests For

More information

BS 476: Part 6: 1989+A1:2009

BS 476: Part 6: 1989+A1:2009 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test

More information

BS 476: Part 6: 1989+A1:2009

BS 476: Part 6: 1989+A1:2009 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test

More information

Review Fire Test Report

Review Fire Test Report Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Review Fire Test Report Determination of

More information

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions... Contents Page No Page 1 of 14... 1 1 Introduction... 3 2 Specimen verification... 3 3 Description of supporting constructions... 3 4 Description of specimen... 3 4.1 Air transfer grille blocks... 3 5 Test

More information

NF X : Parts 1, 2, 3, 4 & 5

NF X : Parts 1, 2, 3, 4 & 5 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com NF X 10-702: Parts 1, 2, 3, 4 & 5 Fire test

More information

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 153420 Date: 28 th April 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 153420 BS 476: Part

More information

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com EN 45545-2: 2013 Summary Test Report Requirement

More information

IMO Resolution MSC 61(67): Annex 1: Part 2

IMO Resolution MSC 61(67): Annex 1: Part 2 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IMO Resolution MSC 61(67): Annex 1: Part

More information

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 158117 Date: 13 th October 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 158117 BS 476:

More information

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor: IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2 Smoke & Toxicity Test WF Report Number: 166040 Date: 13 th August 2007 Test Sponsor: Fiba Tech Industries Ltd. 0249 Page 2 of 13 Bodycote warringtonfire

More information

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests

More information

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in INFRASTRUCTURE TECHNOLOGIES Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in accordance with AS/NZS 3837:1998 Fire Testing Report Author: Heherson Alarde Report Number:

More information

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions. BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions WF Report Number: 147709 Test Sponsor: FTC - Fabbrica Trentina Conduttori

More information

Fire resistance testing of technical cabinets in accordance with EN

Fire resistance testing of technical cabinets in accordance with EN Fire resistance testing of technical cabinets in accordance with EN - Pierre-Yves MAZILLE 0/0/07 Introduction In depth look into specification of..h) in EN - Review of standard fire resistance test methods

More information

FTSG RESOLUTIONS. This document of FTSG resolutions was issued by the Company Secretary 20 July 2012.

FTSG RESOLUTIONS. This document of FTSG resolutions was issued by the Company Secretary 20 July 2012. FTSG RESOLUTIONS This document of FTSG resolutions was issued by the Company Secretary 20 July 2012. TABLE OF CONTENTS No. 1 Moisture Content... 3 No. 2 Moisture Content Limits... 4 No. 3 Moisture Content...

More information

Australian Standard. Components for the protection of openings in fire-resistant walls. Part 1: Fire-resistant doorsets AS AS 1905.

Australian Standard. Components for the protection of openings in fire-resistant walls. Part 1: Fire-resistant doorsets AS AS 1905. AS 1905.1 2005 AS 1905.1 2005 Australian Standard Components for the protection of openings in fire-resistant walls Part 1: Fire-resistant doorsets This Australian Standard was prepared by Committee FP-019,

More information

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal

More information

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor: BS EN 61034-2: 2005 Measurements Of Smoke Density Of Electric Cables WF Report Number 177599 Date: 17 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of 13 Bodycote warringtonfire

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 2243.5 Australian/New Zealand Standard Safety in laboratories Part 5: Non-ionizing radiations Electromagnetic, sound and ultrasound This Joint Australian/New Zealand Standard was prepared by Joint

More information

PQS Independent type-testing protocol

PQS Independent type-testing protocol PQS Independent type-testing protocol WHO/XXX Original: English Distribution: General TITLE: Integrated electronic maximum-minimum thermometer, with factory programmed alarms, for vaccine refrigerators

More information

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions.

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions. Method of test defined in IEC 60331-21 for determining the circuit integrity performance of a cable under fire conditions. WF Report Number: 148371 Test Sponsor: FTC - Fabbrica Trentina Conduttori Srl

More information

PQS Independent type-testing protocol

PQS Independent type-testing protocol PQS Independent type-testing protocol WHO/XXX Original: English Distribution: General TITLE: Wall-mounted pen recording thermometer Product verification protocol: E06/TR04VP Applies to specification ref(s):

More information

Intumescent Fire Dampers

Intumescent Fire Dampers Ph 1300 858 010 Intumescent Fire Dampers Fire resistant walls and floors in a building play an important part in containing the spread of fire and smoke. However, a building also needs to be well ventilated

More information

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS Report number FSZ 1572 CSIRO job number SV3559 Date of issue 22 FEBRUARY 2013 Client BREEZWAY AUSTRALIA PTY LTD Commercial-in-confidence Copyright CSIRO 2013 Copying

More information

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008. BS EN 60332-1-2:2004 Test On Electric And Optical Fibre Cables Under Fire Conditions WF Report Number 177604 Date: 14 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of

More information

STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL

STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL 14SH200001022 STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL DUCTLINER GS - VENTILATION, SMOKE OUTLET AND KITCHEN EXTRACT DUCT SYSTEMS Tested under BS 476: Part 24: 1987 Fire tests building materials

More information

AS/NZS 4745:2012. Code of practice for handling combustible dusts AS/NZS 4745:2012. Australian/New Zealand Standard. Superseding AS/NZS 4745:2004

AS/NZS 4745:2012. Code of practice for handling combustible dusts AS/NZS 4745:2012. Australian/New Zealand Standard. Superseding AS/NZS 4745:2004 AS/NZS 4745:2012 (Incorporating Amendment No. 1) Australian/New Zealand Standard Code of practice for handling combustible dusts Superseding AS/NZS 4745:2004 AS/NZS 4745:2012 AS/NZS 4745:2012 This Joint

More information

CERTIFICATE OF FIRE APPROVAL

CERTIFICATE OF FIRE APPROVAL LR427.203.2 CERTIFICATE OF FIRE APPROVAL This is to certify that The product(s) detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations for use on offshore

More information

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E. Benefiting Government, Industry and the Public Through Innovative Science and Technology Barry L. Badders, Jr. P.E. 7 December 2011 Part 1 Non-Combustibility Test Part 3 Test for A, B,, and F Class Divisions

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60287-3-1 Edition 1.1 1999-05 Edition 1:1995 consolidated with amendment 1:1999 Electric cables Calculation of the current rating Part 3-1: Sections on operating conditions IEC

More information

ISO INTERNATIONAL STANDARD. Fire-resistance tests Elements of building construction Part 1: General requirements

ISO INTERNATIONAL STANDARD. Fire-resistance tests Elements of building construction Part 1: General requirements INTERNATIONAL STANDARD ISO 834-1 First edition 1999-09-15 Fire-resistance tests Elements of building construction Part 1: General requirements Essai de résistance au feu Éléments de construction Partie

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 871 Third edition 2006-11-15 Plastics Determination of ignition temperature using a hot-air furnace Plastiques Détermination de la température d'allumage au moyen d'un four à

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 61779.6:2000 (Incorporating Amendment No. 1) AS/NZS 61779.6:2000 Australian/New Zealand Standard Electrical apparatus for the detection and measurement of flammable gases Part 6: Guide for the selection,

More information

Australian Standard. Methods for fire tests on building materials, components and structures

Australian Standard. Methods for fire tests on building materials, components and structures AS 1530.3 1989 Australian Standard Methods for fire tests on building materials, components and structures Part 3: Simultaneous determination of ignitability, flame propagation, heat release and smoke

More information

C-01 FIRE DECKS AND BULKHEADS

C-01 FIRE DECKS AND BULKHEADS Guideline No.: C-01(201510) C-01 FIRE DECKS AND BULKHEADS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008. BS EN 60332-1-2:2004 Test On Electric And Optical Fibre Cables Under Fire Conditions WF Report Number 177603 Date: 14 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 2918:2001 AS/NZS 2918 Australian/New Zealand Standard Domestic solid fuel burning appliances Installation Building Code of Australia Primary referenced Standard AS/NZS 2918:2001 This Joint Australian/New

More information

AS/NZS :2016. Refrigerating systems and heat pumps Safety and environmental requirements AS/NZS :2016. Part 3: Installation site

AS/NZS :2016. Refrigerating systems and heat pumps Safety and environmental requirements AS/NZS :2016. Part 3: Installation site Australian/New Zealand Standard (ISO 5149-3:2014, MOD) Refrigerating systems and heat pumps Safety and environmental requirements Part 3: Installation site Superseding in part AS/NZS 1677.2:1998 This joint

More information

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: Page 1 of 10 TEST REPORT REPORT NUMBER: 102317918SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112

More information

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS AS 4214 2002 (Incorporating Amendment No. 1) AS 4214 2002 Australian Standard Gaseous fire extinguishing systems This Australian Standard was prepared by Committee FP-011, Gaseous Fire Protection. It was

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60216-4-1 Fourth edition 2006-01 Electrical insulating materials Thermal endurance properties Part 4-1: Ageing ovens IEC 2006 Copyright - all rights reserved No part of this

More information

AS/NZS :2008

AS/NZS :2008 AS/NZS 60079.29.2:2008 Australian/New Zealand Standard Explosive atmospheres Part 29.2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen AS/NZS 60079.29.2:2008

More information

C-Bus Pascal Automation Controller 5500PACA. Installation Instructions

C-Bus Pascal Automation Controller 5500PACA. Installation Instructions C-Bus Pascal Automation Controller 5500PACA Installation Instructions Contents 1.0 Description...3 2.0 Important Notes...3 3.0 Capabilities...3 4.0 Wiring Instructions...4 4.1 Battery Back up...5 4.2 Connecting

More information

COMPETENCE. Lead Fire Warden. Standard Title Lead Fire Warden Competence Assessment Standard Lead Fire Warden Competence Assessment Standard

COMPETENCE. Lead Fire Warden. Standard Title Lead Fire Warden Competence Assessment Standard Lead Fire Warden Competence Assessment Standard Lead Fire Warden COMPETENCE CRO EMERGENCY RESPONSE COMPETENCE ASSESMENT Standard Title Code Lead Fire Warden Competence Assessment Standard 4502 Revision 0 (28th October 2016) Page 1 of 29 OPITO STANDARDS

More information

Interim Australian Standard

Interim Australian Standard AS 1735.10(Int) 1998 (Incorporating Amendment Nos 1 and 2) Expries 5 August 2003) AS 1735.10(Int) Interim Australian Standard Lifts, escalators and moving walks Part 10: Tests This Australian Standard

More information

Are Your Kitchen Hood Filters Compliant?

Are Your Kitchen Hood Filters Compliant? Are Your Kitchen Hood Filters Compliant? Do your kitchen hood filters comply with the current Australian Standards for fire safety? Why Install Kitchen Exhaust Hood Filters? The purpose of a kitchen exhaust

More information

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device

More information

SIGMADEK, LTD. FIRE TEST REPORT

SIGMADEK, LTD. FIRE TEST REPORT SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION

More information

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY White Paper BACKGROUND: Safety is paramount in the home appliance industry. Due to the possibility of human mis-application, over-current, or short circuit

More information

AS Australian Standard. Domestic solid fuel burning appliances Installation. This is a free 6 page sample. Access the full version online.

AS Australian Standard. Domestic solid fuel burning appliances Installation. This is a free 6 page sample. Access the full version online. AS 2918 1990 Australian Standard Domestic solid fuel burning appliances Installation This Australian Standard was prepared by Committee CS/62, Solid Fuel Burning Appliances. It was approved on behalf of

More information

AS/NZS :2016. Refrigerating systems and heat pumps Safety and environmental requirements AS/NZS :2016

AS/NZS :2016. Refrigerating systems and heat pumps Safety and environmental requirements AS/NZS :2016 Australian/New Zealand Standard AS/NZS 5149.1:2016 (ISO 5149-1:2014, MOD) Incorporating Amendment No. 1 Refrigerating systems and heat pumps Safety and environmental requirements Part 1: Definitions, classification

More information

AS/NZS 4821:2014. Protective footwear for firefighters Requirements and test methods AS/NZS 4821:2014. Australian/New Zealand Standard

AS/NZS 4821:2014. Protective footwear for firefighters Requirements and test methods AS/NZS 4821:2014. Australian/New Zealand Standard Australian/New Zealand Standard AS/NZS 4821:2014 (EN 15090:2012, MOD) Protective footwear for firefighters Requirements and test methods Superseding AS/NZS 4821:2006 AS/NZS 4821:2014 This standard, is

More information

Australian Standard. Security screen doors and security window grilles AS AS 5039

Australian Standard. Security screen doors and security window grilles AS AS 5039 AS 5039 2003 AS 5039 Australian Standard Security screen doors and security window grilles This Australian Standard was prepared by Committee CS-023, Security Screen Doors and Security Window Grilles.

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 3008-2 Second edition 2017-05 Fire-resistance tests Part 2: Lift landing door assemblies Essais de résistance au feu Partie 2: Assemblage de porte palière d ascenseur Reference

More information

Product. Regulations. Agrément Certificate No 92/2841 Third issue* Designated by Government to issue European Technical Approvals

Product. Regulations. Agrément Certificate No 92/2841 Third issue* Designated by Government to issue European Technical Approvals Lorient Polyproducts Ltd Fairfax Road Heathfield Industrial Estate Newton Abbot Devon TQ12 6UD Tel: 01626 834252 Fax: 01626 833166 e-mail: admin@lorientuk.com website: www.lorientgroup.com CI/SfB (32.5)

More information

Occupational Health and Safety. Radiation Protection Regulation Amended in 2013 Highlights

Occupational Health and Safety. Radiation Protection Regulation Amended in 2013 Highlights Occupational Health and Safety Bulletin Radiation Protection Regulation Amended in 2013 Highlights The Radiation Protection Amendment Regulation came into effect on July 25, 2013. This Regulation was made

More information

research highlight Canadian Housing Fire Statistics Findings

research highlight Canadian Housing Fire Statistics Findings research highlight August 2004 Socio-economic Series 04-004 Introduction The project, completed under the CMHC External Research Program, develops benchmarks and indicators related to fire losses in housing

More information

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES

More information

AS/NZS :1998 AS/NZS ISO

AS/NZS :1998 AS/NZS ISO (ISO 817:2014, IDT) Australian/New Zealand Standard Refrigerants Designation and safety classification Superseding AS/NZS 1677.1:1998 AS/NZS ISO 817:2016 This joint Australian/New Zealand standard was

More information

Provläsningsexemplar / Preview INTERNATIONAL

Provläsningsexemplar / Preview INTERNATIONAL INTERNATIONAL IEC STANDARD 60587 Third edition 2007-05 Electrical insulating materials used under severe ambient conditions Test methods for evaluating resistance to tracking and erosion Reference number

More information

Test Report: ICL/H18/9039 Rev 1

Test Report: ICL/H18/9039 Rev 1 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk

More information

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook Useful Contact Numbers Promat Technical Services Department Telephone: 01344 381 400 Fax: 01344 381 401 E-mail: technicaluk@promat.co.uk Promat Marketing Services Department Telephone: 01344 381 350 Fax:

More information

HTA ACCREDITATIONS. NADCAP (Heat Treating) 2 AS 9100C 5-6 ISO NADCAP (Heat Treating) 3 AS 9100C 5-6 ISO NADCAP (Heat Treating) 4

HTA ACCREDITATIONS. NADCAP (Heat Treating) 2 AS 9100C 5-6 ISO NADCAP (Heat Treating) 3 AS 9100C 5-6 ISO NADCAP (Heat Treating) 4 HTA ACCREDITATIONS page HTA AEROSPACE & DEFENSE / HTA BRISBANE NADCAP (Heat Treating) 2 AS 9100C 5-6 ISO 9001 7-8 HTA AEROSPACE & DEFENSE / HTA MELBOURNE NADCAP (Heat Treating) 3 AS 9100C 5-6 HTA SYDNEY

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61784-5-14 Edition 1.0 2010-07 colour inside Industrial communication networks Profiles Part 5-14: Installation of fieldbuses Installation profiles for CPF 14 IEC 61784-5-14:2010(E)

More information

Alarm Signalling Equipment: Connection Requirements (Victoria) TAN 06. Technical Advisory Note. Version 1 October 2018

Alarm Signalling Equipment: Connection Requirements (Victoria) TAN 06. Technical Advisory Note. Version 1 October 2018 TAN 06 Alarm Signalling Equipment: Connection Requirements (Victoria) Version 1 October 2018 1 1 Purpose statement The purpose of this is to provide advice concerning the legislative requirements for the

More information

AS/NZS :2016

AS/NZS :2016 Australian/New Zealand Standard Luminaires Part 2.2: Particular requirements Recessed luminaires Superseding AS/NZS 60598.2.2:2001 AS/NZS 60598.2.2:2016 (IEC 60598-2-2, Ed. 3.0:2011, MOD) Incorporating

More information

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft. T F

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft.   T F ederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / etherlands Organisation for Applied Scientific Research TO report Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box 49

More information

Information Bulletin

Information Bulletin Consideration of emergency response in Alternative Solutions Version 1 Approved for release May 2015 1.0 Purpose statement The purpose of this document is to increase awareness and consideration of the

More information

The Passive Fire Protection Handbook

The Passive Fire Protection Handbook The Passive Fire Protection Handbook The UK s comprehensive guide to passive fire protection Chapter 1 Introduction AUGUST 2017 The Passive Fire Protection Handbook Contents Chapter 1: Introduction2 Applications

More information

AS AS Australian Standard. Soils for landscaping and garden use. This is a free 7 page sample. Access the full version online.

AS AS Australian Standard. Soils for landscaping and garden use. This is a free 7 page sample. Access the full version online. AS 4419 2003 AS 4419 Australian Standard Soils for landscaping and garden use This Australian Standard was prepared by Committee CS-037, Garden Soils and Potting Mixes. It was approved on behalf of the

More information

AS/NZS :2009. Performance of household electrical appliances Refrigerating appliances AS/NZS :2009

AS/NZS :2009. Performance of household electrical appliances Refrigerating appliances AS/NZS :2009 AS/NZS 4474.2:2009 (Incorporating Amendment Nos 1 and 2) Australian/New Zealand Standard Performance of household electrical appliances Refrigerating appliances Part 2: Energy labelling and minimum energy

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1196: Issue 1.2 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,

More information

CERTIFICATE OF FIRE APPROVAL

CERTIFICATE OF FIRE APPROVAL LR2009.030. CERTIFICATE OF FIRE APPROVAL This is to certify that The product(s) detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations for use on offshore

More information

AS/NZS :2015. Conduit systems for cable management AS/NZS :2015. Part 1: General requirements. Australian/New Zealand Standard

AS/NZS :2015. Conduit systems for cable management AS/NZS :2015. Part 1: General requirements. Australian/New Zealand Standard AS/NZS 61386.1:2015 Australian/New Zealand Standard Conduit systems for cable management Part 1: General requirements Superseding AS/NZS 2053.1:2001 AS/NZS 61386.1:2015 AS/NZS 61386.1:2015 This joint Australian/New

More information

Push Button Electronic Timer. 31VETR Series. Installation Instructions

Push Button Electronic Timer. 31VETR Series. Installation Instructions Push Button Electronic Timer Series Installation Instructions Contents 1.0 Product Range... 3 2.0 Description... 3 3.0 Features... 3 4.0 Important Warnings... 3 5.0 Timer Control... 4 5.1 Push Button Control...

More information