Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Size: px
Start display at page:

Download "Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture"

Transcription

1 Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT Release 1.2 Issued January 10, 2005 Document Introduction Related Documentation Application Overview Building Overview Smoke Control Priority Levels Automatic Smoke Control Manual Smoke Control Auto Command Retry Logic FSCS Assigning the Fire Object Category to Smoke Control Objects Security Administration System Roles and User Accounts Overview UUKL Smoke Control Security Administration Details Security Administration Detailed Procedures Creating a New Role Creating a New User Account Configuring User Profiles Configuring Role Properties Assigning System Access Permissions Design Considerations DX Design Considerations Smoke Control NAE Design Considerations DX-9100 Mall Smoke Control Application Application File Location GX Control Logic Point List GX Configuration Parameters Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended 1

2 Smoke Control NAE Application Application File Location Metasys System Extended Architecture Objects Mall Control Mall Logic All Store Logic Store 1 Logic Store 2 Logic Store 3 Logic Store 4 Logic Store 5 Logic Store 6 Logic Mall Logic Alarm Lockout Lockout Logic FSCS Control FSCS Store 2 Smoke Interlock Definition rd Party Zone Interlock Definition FSCS Zone Switch Logic FSCS Store 2 Exhaust Fan 1 Logic FSCS Store 2 Supply Fan 1 Logic FSCS Zone Smoke LED Logic Zone Smoke LED - IFC Zone Detector Trouble Interlock Definition Zone Smoke LED - IFC Zone Trouble Interlock Definition Zone Smoke LED - 3rd Party Zone Trouble Interlock Definition Fire Fighter Control Logic

3 Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Document Introduction Smoke control applications issue commands to controlled devices that pressurize or depressurize an area of a building to minimize the spread of smoke. This document describes smoke control of a single story enclosed shopping mall in the Metasys system extended architecture. The smoke control strategy is achieved with the DX-9100 (DX) application and the smoke control Network Automation Engine (NAE) application described in this document, with manual override of the smoke control logic provided by the Fire Fighter s Smoke Control Station (FSCS). Note: These application notes only present an example of one smoke control strategy. Since every building is unique, the details of applying the strategy vary. These application notes can help you develop an appropriate application for your project. Related Documentation Table 1 lists related smoke control documentation. Table 1: Related Documentation For Information On Refer To LIT No./Part No. General smoke control information Logic programming for the DX-9100 controller Multi-story building smoke control Warehouse smoke control Weekly testing of dedicated stairwell pressurization fans Weekly testing of dedicated smoke control dampers Specific wiring requirements UL 864 UUKL requirements Metasys System Extended Architecture Smoke Control System Technical Bulletin GX-9100 Software Configuration Tool Technical Bulletin Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Warehouse Smoke Control with FSCS Override - Metasys System Extended Weekly Testing of Dedicated Stairwell Pressurization Fans - Metasys System Extended Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin MSEA Smoke Control UL 864 UUKL Compliance Checklist LIT LIT LIT LIT LIT LIT LIT LIT

4 Application Overview The DX application and the smoke control NAE application both provide smoke control for a single story mall with a rooftop unit. The DX controllers provide field connections, and the DX application provides basic HVAC and automatic smoke control for the rooftop unit. The smoke control NAE provides a connection to the FSCS, and the smoke control NAE application provides automatic smoke control and fire fighter manual override for the smoke control system. Note: These application notes only present an example of one smoke control strategy. Since every building is unique, the details of applying the strategy vary. These application notes can help you develop an appropriate application for your project. Building Overview The single story mall in this application (Figure 1) contains a central mall area and six stores, with each store controlled by its own roof top unit. The mall area has a pressurization fan and an exhaust fan. Figure 1: Single Story Enclosed Shopping Mall Smoke alarms, detected by an automatic smoke detector in the mall area (Figure 2), start to the process to depressurize the mall area. The mall area exhaust fan turns on and the mall supply fan turns off. This creates a negative pressure in the mall area. The stores surrounding the mall area will be positively pressurized by starting their supply fan and stopping their exhaust fan. Subsequent alarms and subsequent action will be locked out, except for manual override from the FSCS. 4

5 The system only returns to the pre-smoke control configuration when all automatic alarm/smoke control initiating devices return to the normal condition, and the manual override switches on the FSCS return to the Auto position. Figure 2: Smoke Detected in the Mall Area 5

6 Store smoke alarms, detected by the store s automatic smoke detector, start the process to depressurize the store in alarm. The store s exhaust fan starts and its supply fan stops. The stores on either side of the store in alarm are then positively pressurized. All other stores remain in the state they were in before the store went into alarm. The mall area is positively pressurized when any store is in alarm. (Figure 3). Subsequent alarms and actions are locked out. Figure 3: Smoke Detected in a Store This process has a manual reset, which re-enables alarm processing after all alarms have been cleared. The reset is issued using the smoke control NAE to command the manual reset input to On. The manual reset sends a release command to all pressurization and exhaust outputs and the Sonalert. The manual reset then must be turned off to return to normal operation. Smoke Control Priority Levels All automatic smoke control commands are commanded at a Priority 3. Fire fighter manual overrides issued from the FSCS panel to pressurize or depressurize zones are commanded at a Priority 2. Fire fighter manual override commands, issued from the FSCS panel to control individual fans and air duct dampers, are issued at Priority 1. 6

7 Automatic Smoke Control Automatic Smoke Control provides the logic for UUKL first incident rule by locking out subsequent alarms from automatic smoke control. All Store logic depressurizes the store that goes into smoke alarm and pressurizes all adjacent stores. Pressurize and depressurize commands in automatic smoke control are commanded at a Priority 3. Priority 3 commands are released when the smoke alarm is reset. If a store or the mall area is under smoke control, the FSCS panel controls the Light-Emitting Diodes (LEDs) next to each FSCS switch to indicate the current status of the fans, dampers, and zone. Status LEDs for a fan show whether the fan is either On, Off, or in Trouble. Status LEDs for a damper indicate whether the damper is either Open, Closed, or in Trouble. Status LEDs for a zone (store/mall area) indicate whether the zone is either in Pressurize mode, Depressurize mode or Purge mode. The Auto LED for each fan, damper, and zone switch remains on while the point is in automatic smoke control. The logic to check the status of fans and dampers for trouble is initiated when a store or the mall area goes into smoke control. If a fan does not reach its set point within 60 seconds, its Trouble LED is turned on. If a damper does not reach its set point within 75 seconds, its Trouble LED is turned on. After a commanded point goes into Trouble, the Auto Command Retry logic repeats the command that failed every 60 seconds. For more detailed information, see the Design Considerations section in this manual. Manual Smoke Control Manual Smoke Control logic is initiated when a fire fighter turns the FSCS Panel Enable key from the Auto position to the Fire Fighter Control position and initiates a manual override of a fan, damper, or zone point from the Auto setting on the FSCS panel. This turns off the Panel Enable switch Auto LED and turns on the Panel Enable switch Fire Fighter Control LED. There are two levels of manual smoke control. A fire fighter can put a store in manual smoke control by turning the zone knob to Pressurize, Depressurize, or Purge. The zone smoke control commands are issued at Priority 2. Priority 2 commands are released when the fire fighter turns the zone knob back to Auto or turns the Panel Enable key back to Auto. A fire fighter can put a point in manual smoke control by flipping a fan toggle switch to On or Off or a damper toggle switch to Open or Close. Individual points are commanded at Priority 1. Priority 1 commands are released when the fire fighter turn flips the toggle switch to Auto or turns the Panel Enable key back to Auto. 7

8 Any point under manual smoke control activates the trouble checking logic. If a fan does not reach its set point within 60 seconds, its Trouble LED is turned on. If a damper does not reach its set point within 75 seconds, its Trouble LED is turned on. After a commanded point goes into Trouble, the Auto Command Retry logic repeats the command that failed every 60 seconds. For more detailed information, see the Design Considerations section in this manual. Auto Command Retry Logic The Auto Command Retry logic is used for fans, dampers, and VMAs. It does a comparison check between the commanded state and the actual device state, to verify that the command was successful. In the event a command to a fan, damper, or VMA fails, possibly because the MCO for the commanded device is on a remote smoke control NAE panel. The additional time required to communicate with the remote smoke control NAE might exceed the command response limit. Therefore, the command is resent every 60 seconds until the command is successful. The Auto Command Retry logic is used when either a device MCO does not match command, a fan, damper, or VMA status does not match its commanded value, or a fan, damper, or VMA trouble input is active. FSCS The FSCS is responsible for all Sonalert logic. When an LED value is set to 3 or 4, the Sonalert sounds. Press the Silence button on the FSCS panel to silence the Sonalert and change the LED to a slow blink. The LED will remain on slow blink until it is commanded off. The panel will start a timer and resound the sonalert within 24 hours if the LED is not turned off. The FSCS panel switches and LEDs for the Mall Common Area are shown in Figure 4. Each store in the mall has similar panel controls.the controls shown under the Mall Common Area zone are master controls for the entire FSCS mall control panel. Figure 4: FSCS Panel - Mall Common Area 8

9 The Sonalert sounds if the FSCS Panel Enable key is turned from the Firefighter Control position to the Auto position and all zone knobs and point toggle switches are not set to Auto. The FSCS still goes into Auto mode, but the Sonalert reminds the firefighter to set the manual smoke control switches to the Auto position. The General Trouble LED will be turned on to a fast blink if the panel looses N2 communications.the LEDs on the FSCS panel can be set to the following values (Table 2). Table 2: FSCS LED Blink Condition FSCS LED Value LED Blink Condition 0 LED is off 1 LED is on continuously 2 LED slow blink 3 LED fast blink and sonalert turned on 9

10 Assigning the Fire Object Category to Smoke Control Objects You must assign every object used specifically for smoke control as a Fire object. This limits the control of smoke control devices and points to authorized Fire operators.use the pull down menu to assign the Fire object category (Figure 5). Figure 5: Assigning the Fire Object to Smoke Control Objects! WARNING: Risk of serious injury or death if a smoke control object is not assigned as a Fire object! In the event of a fire or smoke control event, devices or points used for smoke control that are not assigned as Fire objects allow those devices and points to be controlled by non-fire authorized operators. It is imperative that every smoke control device or point be assigned as a Fire object. Security Administration System The Security Administration system authenticates and authorizes users of Metasys system extended architecture applications. The Security Administrator is a browser-based interface that manages all accounts. Use the Security Administrator System to authenticate and authorize users on the Metasys system extended architecture. The Security Administrator creates User Accounts and Roles, and assigns access permissions to each user of the Metasys system extended architecture. 10

11 Roles and User Accounts Overview Security is based on User Accounts and Roles. Roles are groups of users with a specific function within the Metasys system. To access the system, an individual provides a user account and the correct password. Use letters, numbers, or symbols to create user account passwords. Use the Login button from the logon prompt to send the user s credentials. A unique Session generates when the user s credentials match the logon requirements. UUKL Smoke Control Security Administration Details UUKL smoke control requires that only operators designated as fire operators be able to control the smoke control system. This required the creation of four new roles: 1. Administrator - This is the highest level of control and allows site control of all HVAC and Fire features.fire Administrator - This role is a fire manager level setting. It allows for full system control, including system modification or configuration. 2. Fire Administrator - This role is a fire manager level setting. It allows for full system control, including system modification or configuration. Figure 6: Fire Administrator Access Permissions 11

12 3. Fire User - This role is for most fire field technicians and allows system control and alarm acknowledgement, but not system modification or configuration. Figure 7: Fire User Access Permissions 4. Fire Limited - This is the lowest of the permissions and only allows the operator to view fire/smoke control devices and alarms. Figure 8: Fire Limited Access Permissions 12

13 Security Administration Detailed Procedures Creating a New Role To create a new role: 1. From the Security Administration menu bar, select Insert > New Role. The New Role dialog box appears. 2. Fill in the information. 3. Click OK. The New Role appears in the tree. Creating a New User Account To create a new user account: 1. From the Security Administration menu bar, select Insert > New User. The User Properties tab appears. 2. Fill in the information. 3. Click OK. The New User appears in the tree. Configuring User Profiles To configure a user profile: 1. Select the user whom you wish to configure. 2. From the menu bar, select Edit > Properties. The User Properties tab appears. 3. Modify the desired user information. 4. Click OK. Configuring Role Properties To configure role properties: 1. Select the user whom you wish to configure. 2. From the menu bar, select Edit > Properties. The User Properties tab appears. 3. Select the Roles tab, then select an Available Role. 4. Click Add. The selected role appears in the Assigned Role list box. 5. Click OK. Assigning System Access Permissions To assign system access permissions: 1. Select the user whom you wish to assign system access permissions. 2. From the main menu, select Edit > System Access Permissions. The System Access Permission dialog box appears. 3. Select an available privilege. 4. Click Add, then click OK to assign the user s System Access Permissions. 13

14 Design Considerations This DX-9100 and Smoke Control NAE application, as it exists in the Metasys System Extended Architecture Smoke Control Library, complies with the UL 864 UUKL Smoke Listing. However, you are responsible for ensuring that the application complies with state and local regulations, and is approved by the Authority Having Jurisdiction (AHJ). You are also responsible for configuring all of the smoke control components, as well as the programming of those components, in order to comply with the UL 864 UUKL Smoke Listing as documented herein. DX Design Considerations For information on the definition and the initial configuration of this DX-9100 smoke control application, use the GX-9100 Software Configuration Tool (GX Tool) to examine this smoke control application. You can find instructions and guidelines for using the GX Tool in the GX-9100 Software Configuration Tool Technical Bulletin (LIT ). You may define system and object names for all objects. You must define the hardware location for each object. The process runs once per second, since this is the DX-9100 scan rate. An alarm will occur if the command does not equal the condition for any controlled device output. Each Binary Output (BO) for pressurization and exhaust outputs must be configured to have its own feedback (proof sensor) input. The system will indicate when the command does not equal the condition. The alarm must be used in other applications, such as a graphical presentation of feedback information, use the FSCS. This DX-9100 automatic smoke control application does not provide a manual override. Override is available from the operator at the smoke control NAE or the FSCS. For multi-level structures, use the same, predefined program. You may want to positively pressurize the stores above and below the area of incidence, subject to the approval of the AHJ. Depending on the application and the specifics of the building, the same logic may be used in atriums, subject to the approval of the AHJ. Using multiple DX-9100s, this application can be expanded to work for a mall with six or more stores. For further details, please contact the Field Support Center in Milwaukee. 14

15 For UL compliance: If DX Digital Inputs (DIs) are used for smoke control, then DI8 must be jumpered and mapped to the smoke control NAE as a normal state of On. If DI8 is off, a critical alarm must be issued at the FSCS to indicate a binary input fuse failure that must be fixed immediately, because the DI is no longer accurate. If DX Analog Outputs (AOs) are used for smoke control, then Analog Output 14 (AO14, voltage) must be wired to Analog Input 8 (AI8, voltage) and the AI must be mapped to the smoke control NAE with a low alarm limit of 20%. If the AI goes below 20%, it indicates the AO has failed because of a blown fuse, which drops the AO to 0V and the AI to 0% (low alarm). The DX is downloaded so that the AO is normally at 5V because its source point is an Analog Constant (ACO) with a default of 50. Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition, to the issuing of an appropriate command to the equipment.) For specific wiring requirements, refer to Metasys Smoke Control Wiring Technical Bulletin (LIT ). For specific wiring requirements refer to Metasys System Extended Architecture Smoke Control System Wiring Technical Bulletin (LIT ). Smoke Control NAE Design Considerations Keep the following design considerations in mind when designing a single story enclosed shopping mall smoke control system with FSCS override: The smoke control NAE reports critical alarms based on the alarm condition, and the alarm can only be cleared by resetting from the Intelligent Fire Controller (IFC) panel or the Firefighter s Smoke Control Station (FSCS). You must define the hardware location for each object You must name each object with a descriptive name that is unique in the system. 15

16 A Programming In Progress BACnet Binary Value object (BV) point is required. You must set this point to true any time you are making changes to the Smoke Control system. This will turn on the Programming In Progress LED on the FSCS to let a fire fighter know that changes are being made and the system may not be fully functional. The point must be turned off when changes are complete. A master reset interlock is required. The interlock is true after the reset on the Intelligent Fire Controller (IFC) panel is pressed. Each store will need a Latched Alarm BV object. The lock alarm logic will set this point to true for the first alarm detected. Each store will need an Alarm Lockout Interlock. The interlock is true if any latched alarms for other stores is true or the master reset interlock is true. Do not include a store s latched alarm in its own Alarm Lockout Interlock. A DX will need to provide the following BV points. zone pressurize command Set to true to turn on supply fans zone depressurize command Set to true to turn on exhaust fans BV Auto point Normally set to true. Point is false when a fire fighter turns a fan On or Off, or sets a damper to Open or Close. BV command point for each fan BV feedback point for each fan BV command point for each damper BV open feedback point for each damper BV close feedback point for each damper BV point for the Analog Input (AI) Fuse BV point for the Binary Input (BI) Fuse Use the following priorities for commands to DX points. 3 commands from automatic smoke control 2 commands from manual smoke control for zone pressurize, depressurize, and purge. 1 commands from manual smoke control for individual points. 16

17 DX-9100 Mall Smoke Control Application Application File Location This Metasys system extended architecture smoke control application is located on the Metasys Branch Purchase Package (BPP) CD in the Metasys System Extended Architecture Standard Smoke Control Applications directory. GX Control Logic The GX Tool was used to create the logic for this DX single story enclosed shopping mall smoke control application. This DX smoke control application resides on each DX-9100 controller used for mall smoke control. The main GX screen shows the mall smoke control application as user names (Figure 9) or tag names (Figure 10) depending on the view selected. Figure 9: GX-9100 Mall Graphical Layout (User Names) 17

18 Point List Table 3 and Table 4 show the hardware and software point requirements for the GX configuration. Table 3: Hardware I/O Requirements (Part 1 of 2) Hardware Input Requirements Hardware Location Figure 10: GX-9100 Mall Graphical Layout (Tag Names) User Name Engineer Units Req? Description DI1 ALM_ST1 NOR/ALA Yes Alarm Store 1 DI2 ALM_ST2 NOR/ALA Yes Alarm Store 2 DI3 ALM_ST3 NOR/ALA Yes Alarm Store 3 DI4 ALM_ST4 NOR/ALA Yes Alarm Store 4 DI5 ALM_ST5 NOR/ALA Yes Alarm Store 5 DI6 ALM_ST6 NOR/ALA Yes Alarm Store 6 DI7 ALM_MALL NOR/ALA Yes Alarm Mall DI8 FUSE ALA/NOR Yes DI Fuse Monitor XT2DI1 ST1SF_S ON/OFF Yes Store 2 Supply Fan Sts XT2DI2 EXST1_FB ON/OFF Yes Store 1 Exhaust FB XT2DI3 ST2SF_S ON/OFF Yes Store 2 Supply Fan Sts XT2DI4 EXST2_FB ON/OFF Yes Store 2 Exhaust FB 18

19 Table 3: Hardware I/O Requirements (Part 2 of 2) Hardware Input Requirements Hardware Location XT3DI1 ST3SF_S ON/OFF Yes Store 3 Supply Fan Sts XT3DI2 EXST3_FB ON/OFF Yes Store 3 Exhaust FB XT3DI3 ST4SF_S ON/OFF Yes Store 4 Supply Fan Sts XT3DI4 EXST4_FB ON/OFF Yes Store 4 Exhaust FB XT3DI5 ST5SF_S ON/OFF Yes Store 5 Supply Fan Sts XT3DI6 EXST5_FB ON/OFF Yes Store 5 Exhaust FB XT3DI7 ST6SF_S ON/OFF Yes Store 6 Supply Fan Sts XT3DI8 EXST6_FB ON/OFF Yes Store 6 Exhaust FB XT4DI1 MASF_S ON/OFF Yes Mall Supply Fan Sts XT4DI3 MAEX_S ON/OFF Yes Mall Exhaust Fan Sts Hardware Output Requirements Hardware Location User Name Name of Module Engineer Units Engineer Units Req? Req? Description Description DO3 PRSS_ST1 ON/OFF Yes Pressurize Store 1 DO4 EXH_ST1 ON/OFF Yes Exhaust Store 1 DO5 PRSS_ST2 ON/OFF Yes Pressurize Store 2 DO6 EXH_ST2 ON/OFF Yes Exhaust Store 2 DO7 PRSS_ST3 ON/OFF Yes Pressurize Store 3 DO8 EXH_ST3 ON/OFF Yes Exhaust Store 3 XT1DO1 PRSS_ST4 ON/OFF Yes Pressurize Store 4 XT1DO2 EXH_ST4 ON/OFF Yes Exhaust Store 4 XT1DO3 PRSS_ST5 ON/OFF Yes Pressurize Store 5 XT1DO4 EXH_ST5 ON/OFF Yes Exhaust Store 5 XT1DO5 PRSS_ST6 ON/OFF Yes Pressurize Store 6 XT1DO6 EXH_ST6 ON/OFF Yes Exhaust Store 6 XT1DO7 MALL_PR1 ON/OFF Yes Mall Pressure Fan 1 XT2DO5 MALL_EX1 ON/OFF Yes Mall Exhaust Fan 1 XT2DO7 Sonalert ON/OFF Yes Sonalert 19

20 Table 4: Software I/O Requirements (Part 1 of 2) Hardware Location User Name Req? Description DCO1 STR1-OCC Yes Store 1 Occupied DCO2 STR1-PRS Yes Store 1 Pressurize DCO3 STR1-EXH Yes Store 1 Exhaust DCO4 STR2-OCC Yes Store 2 Occupied DCO5 STR2-PRS Yes Store 2 Pressurize DCO6 STR2-EXH Yes Store 2 Exhaust DCO7 STR3-OCC Yes Store 3 Occupied DCO8 STR3-PRS Yes Store 3 Pressurize DCO9 STR3-EXH Yes Store 3 Exhaust DCO10 STR4-OCC Yes Store 4 Occupied DCO11 STR4-PRS Yes Store 4 Pressurize DCO12 STR4-EXH Yes Store 4 Exhaust DCO13 STR5-OCC Yes Store 5 Occupied DCO14 STR5-PRS Yes Store 5 Pressurize DCO15 STR5-EXH Yes Store 5 Exhaust DCO16 STR6-OCC Yes Store 6 Occupied DCO17 STR6-PRS Yes Store 6 Pressurize DCO18 STR6-EXH Yes Store 6 Exhaust DCO19 MALL-OCC Yes Mall Occupied DCO20 MALL-PRS Yes Mall Pressurize DCO21 MALL-EXH Yes Mall Exhaust DCO22 Sonalert Yes Sonalert LRS1 SF1-AUTO Yes Store 1 Supply Fan Auto LRS2 STR1SF-C Yes Store 1 Supply Fan Control LRS3 EF1-AUTO Yes Store 1 Exhaust Fan Auto LRS4 STR1EF-C Yes Store 1 Exhaust Fan Control LRS5 SF2-AUTO Yes Store 2 Supply Fan Auto LRS6 STR2SF-C Yes Store 2 Supply Fan Control LRS7 EF2-AUTO Yes Store 2 Exhaust Fan Auto LRS8 STR2EF-C Yes Store 2 Exhaust Fan Control LRS9 SF3-AUTO Yes Store 3 Supply Fan Auto LRS10 STR3SF-C Yes Store 3 Supply Fan Control LRS11 EF3-AUTO Yes Store 3 Exhaust Fan Auto LRS12 STR3EF-C Yes Store 3 Exhaust Fan Control LRS13 SF4-AUTO Yes Store 4 Supply Fan Auto LRS14 STR4SF-C Yes Store 4 Supply Fan Control LRS15 EF4-AUTO Yes Store 4 Exhaust Fan Auto LRS16 STR4EF-C Yes Store 4 Exhaust Fan Control LRS17 SF5-AUTO Yes Store 5 Supply Fan Auto LRS18 STR5SF-C Yes Store 5 Supply Fan Control 20

21 Table 4: Software I/O Requirements (Part 2 of 2) Hardware Location User Name Req? Description LRS19 EF5-AUTO Yes Store 5 Exhaust Fan Auto LRS20 STR5EF-C Yes Store 5 Exhaust Fan Control LRS21 SF6-AUTO Yes Store 6 Supply Fan Auto LRS22 STR6SF-C Yes Store 6 Supply Fan Control LRS23 EF6-AUTO Yes Store 6 Exhaust Fan Auto LRS24 STR6EF-C Yes Store 6 Exhaust Fan Control LRS25 MSF-AUTO Yes Mall Supply Fan Auto LRS26 MALLSF-C Yes Mall Supply Fan Control LRS27 MEF-AUTO Yes Mall Exhaust Fan Auto LRS28 MALLEF-C Yes Mall Exhaust Fan Control GX Configuration Parameters The Programmable Logic Controller (PLC) programs for each store and the mall area are shown in Figure 11 through Figure 17: Note: If the fan feedback does not match the commanded state within 60 seconds, an alarm is generated. The LRS outputs must be mapped to the NAE as critical alarms with a normal condition of Off (open). Figure 11: Logic Module Diagram - PLC1 (Store 1) Figure 11 shows the logic module ladder diagram for PLC1 (Store 1). The PLC 1 logic states: If Store 1 is in normal occupied mode (STR1-OCC), and not in alarm (STR1-EXH) and the FSCS Supply Fan switch is in either AUTO (SF1-AUTO) or in override (STR1SF-C), then turn the Store 1 RTU supply fan on. 21

22 If Store 1 is in normal occupied mode (STR1-OCC), and not in alarm (STR1-PRS) and the FSCS Exhaust Fan switch is in either AUTO (EF1-AUTO) or in override (STR1EF-C), then turn the Store 1 RTU exhaust fan on. Figure 12: Logic Module Ladder - PLC2 (Store 2) Figure 12 shows the logic module ladder diagram for PLC2 (Store 2). The PLC 2 logic states: If Store 2 is in normal occupied mode (STR2-OCC), and not in alarm (STR2-EXH) and the FSCS Supply Fan switch is in either AUTO (SF2-AUTO) or in override (STR2SF-C), then turn the Store 2 RTU supply fan on. If Store 2 is in normal occupied mode (STR2-OCC), and not in alarm (STR2-PRS) and the FSCS Exhaust Fan switch is in either AUTO (EF2-AUTO) or in override (STR2EF-C), then turn the Store 2 RTU exhaust fan on. 22

23 Figure 13: Logic Module Ladder - PLC3 (Store 3) Figure 13 shows the logic module ladder diagram for PLC3 (Store 3). The PLC 3 logic states: If Store 3 is in normal occupied mode (STR3-OCC), and not in alarm (STR3-EXH) and the FSCS Supply Fan switch is in either AUTO (SF3-AUTO) or in override (STR3SF-C), then turn the Store 3 RTU supply fan on. If Store 3 is in normal occupied mode (STR3-OCC), and not in alarm (STR3-PRS) and the FSCS Exhaust Fan switch is in either AUTO (EF3-AUTO) or in override (STR3EF-C), then turn the Store 3 RTU exhaust fan on. 23

24 Figure 14: Logic Module Ladder - PLC4 (Store 4) Figure 14 shows the logic module ladder diagram for PLC4 (Store 4). The PLC 4 logic states: If Store 4 is in normal occupied mode (STR4-OCC), and not in alarm (STR4-EXH) and the FSCS Supply Fan switch is in either AUTO (SF4-AUTO) or in override (STR4SF-C), then turn the Store 4 RTU supply fan on. If Store 4 is in normal occupied mode (STR4-OCC), and not in alarm (STR4-PRS) and the FSCS Exhaust Fan switch is in either AUTO (EF4-AUTO) or in override (STR4EF-C), then turn the Store 4 RTU exhaust fan on. 24

25 Figure 15: Logic Module Ladder - PLC5 (Store 5) Figure 15 shows the logic module ladder diagram for PLC5 (Store 5). The PLC 5 logic states: If Store 5 is in normal occupied mode (STR5-OCC), and not in alarm (STR5-EXH) and the FSCS Supply Fan switch is in either AUTO (SF5-AUTO) or in override (STR5SF-C), then turn the Store 5 RTU supply fan on. If Store 5 is in normal occupied mode (STR5-OCC), and not in alarm (STR5-PRS) and the FSCS Exhaust Fan switch is in either AUTO (EF5-AUTO) or in override (STR5EF-C), then turn the Store 5 RTU exhaust fan on. 25

26 . Figure 16: Logic Module Ladder - PLC6 (Store 6) Figure 16 shows the logic module ladder diagram for PLC6 (Store 6). The PLC 6 logic states: If Store 6 is in normal occupied mode (STR6-OCC), and not in alarm (STR6-EXH) and the FSCS Supply Fan switch is in either AUTO (SF6-AUTO) or in override (STR6SF-C), then turn the Store 6 RTU supply fan on. If Store 6 is in normal occupied mode (STR6-OCC), and not in alarm (STR6-PRS) and the FSCS Exhaust Fan switch is in either AUTO (EF6-AUTO) or in override (STR6EF-C), then turn the Store 6 RTU exhaust fan on. 26

27 . Figure 17: Logic Module Ladder - PLC7 (Mall) Figure 17 shows the logic module ladder diagram for PLC7 (Mall). The PLC 7 logic states: If the mall area is in normal occupied mode (MALL-OCC), and not in alarm (MALL-EXH) and the FSCS Supply Fan switch is in either AUTO (MALL-AUTO) or in override (MALLSF-C), then turn the mall area supply fan on. If mall area is in normal occupied mode (MALL-OCC), and not in alarm (MALL-PRS) and the FSCS Exhaust Fan switch is in either AUTO (MALL-AUTO) or in override (MALLEF-C), then turn the mall area exhaust fan on. 27

28 Smoke Control NAE Application Application File Location This Metasys system extended architecture smoke control application is located on the Metasys Branch Purchase Package (BPP) CD in the Metasys System Extended Architecture Standard Smoke Control Applications directory. Metasys System Extended Architecture Objects This smoke control application resides on the smoke control NAE. Smoke control logic screens are created with the System Configuration Tool (SCT) to define the required Control System, Interlock, and Multiple Command objects. The Logic Connector Tool (LCT) is used to create the logic within the control system object. System points, interlocks, MCOs, and alarms are configured with the SCT. The LCT logic is organized into two sections: Mall Control and FSCS Control. The Mall Control section controls the automatic smoke control logic for the mall. It evaluates the inputs from the fire alarm panel and the master reset command from the FSCS to activate/inactivate the exhaust mode (DCO1) in the DX-9100 controller. The FSCS Control section contains smoke control override logic for each of the six stores, the Mall common area, and Firefighter Control (FFC). The FSCS section contains the logic and configuration screens for each of the smoke control devices the FSCS controls and/or displays status for. These devices include Exhaust Fan 1, Supply Fan 1, Zone Switch, and Zone Smoke LED, for each store and the mall area. The Fire Fighter Control folder contains logic for the FSCS panel s Fire Fighter Control LED and the Programming In Progress LED. 28

29 Mall Control Mall Logic The main LCT logic screen for the Single Story Enclosed Shopping Mall with FSCS Override application (Figure 18), controls the automatic smoke control. It consists of the inputs, two system blocks, and outputs. The inputs (Figure 19), are one interlock for each store and the mall, and a master reset interlock. The Lock Alarms block (Figure 20) locks in the first incident. The All Stores Logic block determines which store, or the mall area, to pressurize and depressurize. Outputs (Figure 21) are binary points within a DX. Each store will have a pressurize and a depressurize (exhaust) point. Figure 18: Logic Diagram for All Stores and Mall Area 29

30 The main logic for the mall is fairly large and has been broken down into smaller pieces to allow you to see the block, input, and output names. The inputs and the Lock Alarms block are shown in Figure 19. Each of the six stores and the mall area have one smoke alarm interlock. The Lock Alarms block locks in the first incident. The Master Reset Interlock releases the locked alarms. There is one output alarm for each store and one for the mall area. Only the first smoke zone in alarm (Store 1-Store 6, or the mall area) will be true. All other zones (Store 1-Store 6, or the mall area) will be false. Figure 19: Alarm Inputs, Manual Reset, and 1 st Alarm Lockout Logic 30

31 The Lock Alarms system block and All Store Logic system block (Figure 20) show the outputs from the Lock Alarms block feeding into the All Store Logic block, and the resulting outputs. Figure 20: Alarm Lockout and Alarm Outputs 31

32 The outputs from the All Store Logic system block (Figure 21) connect to store pressurize and exhaust (depressurize) points in the DX. Figure 21: Alarm Outputs to Controllers All Store Logic The All Store Logic block contains logic for each store and the mall area, and determines which store, or the mall area, to pressurize and depressurize.outputs (Figure 21) are binary points within a DX. The expanded logic for each store and the mall area are explained in the following figures. See Figure 2 for an example of a mall area alarm, and Figure 3 for an example of a store alarm. A value of True enables the logic. 32

33 Store 1 Logic Store 1 logic (Figure 22) states that if Store 1 is in alarm, and the mall area or Store 2 are not in alarm, then exhaust Store 1. However, if Store 1 is not in alarm, and either the mall area or Store 2 are in alarm, then pressurize Store 1. Figure 22: Store 1 Logic Store 2 Logic Store 2 logic (Figure 23) states that if Store 2 is in alarm, and either the mall area, Store 1, or Store 3 are not in alarm, then exhaust Store 2. However, if Store 2 is not in alarm, and the either the mall area, Store 1, or Store 3 are in alarm, then pressurize Store 2. Figure 23: Store 2 Logic 33

34 Store 3 Logic Store 3 logic (Figure 24) states that if Store 3 is in alarm, and either the mall area or Store 2 are not in alarm, then exhaust Store 3. However, if Store 2 is not in alarm, and the either the mall area, Store 1, or Store 3 are in alarm, then pressurize Store 2. Figure 24: Store 3 Logic Store 4 Logic Store 4 logic (Figure 25) states that if Store 4 is in alarm, and either the mall area or Store 5 are not in alarm, then exhaust Store 4. However, if Store 4 is not in alarm, and the either the mall area or Store 5 are in alarm, then pressurize Store 4. Figure 25: Store 4 Logic 34

35 Store 5 Logic Store 5 logic (Figure 26) states that if Store 5 is in alarm, and either the mall area, Store 4, or Store 6 are not in alarm, then exhaust Store 5. However, if Store 5 is not in alarm, and the either the mall area, Store 4, or Store 6 are in alarm, then pressurize Store 5. Figure 26: Store 5 Logic Store 6 Logic Store 6 logic (Figure 27) states that if Store 6 is in alarm, and either the mall area or Store 5 are not in alarm, then exhaust Store 6. However, if Store 6 is not in alarm, and the either the mall area or Store 5 are in alarm, then pressurize Store 6. Figure 27: Store 6 Logic 35

36 Mall Logic Mall logic (Figure 28) states that if the mall area is in alarm, and either the Store 1, Store 2, Store 3, Store 4, Store 5, or Store 6 are not in alarm, then exhaust the mall area. However, if the mall area is not in alarm, and Store 1, Store 2, Store 3, Store 4, Store 5, or Store 6 is in alarm, then pressurize the mall area. Figure 28: Mall Logic Alarm Lockout Alarm Lockout uses an Interlock object type with a True/False state. When there are no alarms, each zone has a lockout state of False. When the first zone (store) goes into alarm, all other zones (stores) are commanded to a True state. The Alarm lockout interlock definition for Store 2 (Figure 29) shows the logic used when Store 2 is the first zone in alarm. The True/False values for all other zones are locked to a state of True which prevents them from being overridden, unless commanded by the Master Reset Interlock. Figure 29: Store 2 Alarm Lockout Interlock Definition 36

37 The Master Reset Interlock (Figure 30) releases the locked alarms when commanded by the IFC fire panel Reset button. Figure 30: Master Reset Interlock Definition The Master Reset Interlock Action Table (Figure 31) sets the Master Reset to Off after the last locked alarm is released. Figure 31: Master Reset Interlock Action Table Lockout Logic The Alarm Lockout logic for Store 1 (Figure 32) is the same for each store and the mall area. The only difference is the name in the lockout tab of the logic. Figure 32: Lockout Logic for Store 1 37

38 FSCS Control The FSCS Control section contains logic for each of the six stores, the mall common area, and Fire Fighter Control. The mall common area and each store have their own Zone Interlock Definition, Zone Switch, Exhaust Fan 1, Supply Fan 1, and the Zone Smoke LED logic and configuration screens. Note: The FSCS logic for each store and the mall area is the same, with the only difference being the store name. Store 2 is used as an example here. The term zone, as used in the logic names, means the same as store. Zone 2 is the same as Store 2. Store 2 Exhaust Fan 1 is shown as Exhaust Fan 2-1. FSCS Store 2 Smoke Interlock Definition The FSCS Store 2 (Zone 2) Smoke Interlock Definition (Figure 33) includes the Store 2 IFC Zone Interlock and a point for an optional third-party zone interlock. Figure 33: Zone 2 Smoke Interlock Definition Table 5: IFC Point State Table BACnet Point State State 1 - Normal State 2 - Active Alarm State 3 - Fault State 4 - Disable NAE Point State State 1 - Normal State 2 - Active Alarm State 3 - Fault State 4 - Unreliable The Store 2 IFC Zone Interlock Definition (Figure 34) includes all zones for Store 2. Figure 34: IFC Zone Interlock Definition 38

39 3rd Party Zone Interlock Definition The 3rd Party Zone Interlock Definition (Figure 35) includes a point for a optional third-party, normally open (N.O.) contact input connection. Figure 35: 3rd Party Zone Interlock Definition FSCS Zone Switch Logic The Zone Switch main logic inputs (Figure 36) from the FSCS are Zone Pressurize, Zone Depressurize, Zone Purge, and Firefighter Control switch. Inputs from the DX are Zone Pressurize and Zone Depressurize. Outputs are the Pressurize, Auto, Depressurize, and Purge LEDs on the FSCS panel and the Zone MCO. Figure 36: Zone Control Switch Main Logic The Zone Control system block logic (Figure 37) controls the FSCS Zone LEDs for the zone, depending on the Fire Fighter Control Key setting. The Pressurize, Depressurize, and Purge settings on the FSCS panel are not functional unless the Fire Fighter Control Key has been turned on. If the Fire Fighter Control Key is off, the FSCS Request will be set to 0. The Purge LED is lit if the pressurize and depressurize points in the DX are true. The Pressurize LED is lit if the DX pressurize point is true and the depressurize point is false. 39

40 The Depressurize LED is lit if the DX depressurize point is false and the pressurize point is true. The Auto LED is lit only if the Zone Switch on the FSCS panel is not set to Pressurize, Depressurize, or Purged. Figure 37: Zone Control Block Logic 40

41 The Zone 2 MCO Action Table is shown in Figure 38. Multiple Command Object (MCO) action tables are created on the SCT by adding a Multiple Command object. Figure 38: Zone 2 MCO Action Table 41

42 The FSCS Zone Switch setting determines the state value (Table 6), which in turn determines the smoke control action. Table 6: FSCS Zone Switch State Value FSCS Zone Switch Position State Value Smoke Control Action Pressurize 1 Zone s Supply Fan On Auto 0 Auto Depressurize 2 Zone s Exhaust Fan On Purge 3 Zone s Supply Fan On Zone s Exhaust Fan On The Zone 2 Pressurize MCO Action Table is shown in Figure 39. Figure 39: Zone 2 Pressurize MCO Action Table 42

43 The Zone 2 Depressurize MCO Action Table is shown in Figure 40. Figure 40: Zone 2 Depressurize MCO Action Table 43

44 FSCS Store 2 Exhaust Fan 1 Logic The Store 2 Exhaust Fan 1 main logic is shown in Figure 41. Inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 41: Exhaust Fan 1 Main Logic 44

45 The Exhaust Fan 1 expanded main logic (Figure 42) consists of two control blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED. Figure 42: Exhaust Fan 1 FSCS and Fan Trouble Control Logic 45

46 The FSCS block logic is shown in Figure 43. The Exhaust Fan 1 On LED is lit only if the FSCS is in Fire Fighter Control and the fan is on. The Exhaust Fan 1 Off LED is lit only if the FSCS is in Fire Fighter Control and Exhaust Fan 1 is off. The Exhaust Fan 1 Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, the FSCS Request is set to the following values, depending on the position of the toggle switch: On 1 Auto 0 Off 2 Figure 43: Exhaust Fan 1 FSCS Block Logic 46

47 The Fan Trouble Control block logic is shown in Figure 44. The Exhaust Fan 1 Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if, either the DX is in pressurize or depressurize mode, or, the Fire Fighter Control Key is on and the FSCS Exhaust Fan 1 toggle switch is set to On or Off. Figure 44: Exhaust Fan 1 Fan Trouble Control Block Logic The Exhaust Fan 2-1 Trouble Interlock Definition (Figure 45) sets the values that, when reached, trigger a trouble alarm. The definition includes status and reliability points for the DX AO Fuse, BI Fuse, exhaust fan reliability, and the DX offline status. Figure 45: Exhaust Fan 2-1 Trouble Interlock Definition 47

48 The Exhaust Fan 2-1 MCO Action Table is shown in Figure 46. The Exhaust Fan Auto point is a binary point in the DX to indicate that the Fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Exhaust Fan Auto point is turned off. The Exhaust Fan Command is a point in the DX to control the fan. Figure 46: Exhaust Fan 2-1 MCO Action Table The FSCS Exhaust Fan 1 toggle switch setting (Table 7) determines the state value, which in turn determines the smoke control action. Table 7: FSCS Exhaust Fan 1 Switch State Value FSCS Exhaust Fan 1 Toggle Switch Position State Value Smoke Control Action On 1 Depressurize Auto 0 Auto Off 2 Exhaust Fan 1 Off 48

49 FSCS Store 2 Supply Fan 1 Logic The FSCS Store 2 Supply Fan 1 (Figure 47) inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that will command the DX points. Figure 47: Supply Fan 1 Main Logic 49

50 The Supply Fan 1 expanded main logic (Figure 48) consists of two control blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Supply Fan 1 Trouble LED. Figure 48: Supply Fan 1 FSCS and Fan Trouble Control Main Logic 50

51 The FSCS block logic is shown in Figure 49. The Supply Fan 1 On LED is lit only if the FSCS is in Fire Fighter Control and the fan is on. The Supply Fan 1 Off LED is lit only if the FSCS is in Fire Fighter Control and the supply fan is off. The Supply Fan 1 Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the values shown in Table 8, depending on the position of the toggle switch. Table 8: Supply Fan Switch FSCS Request FSCS Supply Fan Toggle Switch Position FSCS Request Value Smoke Control Action On 1 Pressurize Auto 0 Auto Off 2 Supply Fan Off Figure 49: Supply Fan 1 FSCS Logic 51

52 The Fan Trouble Control block logic is shown in Figure 50. The Supply Fan 1 Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if, either the DX is in pressurize or depressurize mode, or, the Fire Fighter Control Key is on and the FSCS Supply Fan 1 toggle switch is set to On or Off. Figure 50: Supply Fan 1 Fan Trouble Control Logic The Supply Fan 1 Interlock Definition (Figure 51) sets the values that, when reached, trigger a trouble alarm. The definition includes status and reliability points for the DX AO Fuse, BI Fuse, supply fan reliability, and the DX offline status. Figure 51: Supply Fan 2-1 Trouble Interlock Definition 52

53 The Supply Fan 1 MCO Action Table is shown in Figure 52. The Supply Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Supply Fan Auto point is turned off. The Supply Fan Command is a point in the DX to control the fan. MCO action tables are created on the SCT by adding a Multiple Command object. Figure 52: Supply Fan 1 MCO Action Table The FSCS Supply Fan toggle switch setting (Table 9) determines the state value, which in turn determines the smoke control action. Table 9: FSCS Supply Fan 1 Switch State Value FSCS Supply Fan 1 Toggle Switch State Value Position Smoke Control Action On 1 Pressurize Auto 0 Auto Off 2 Supply Fan 1 Off 53

54 FSCS Zone Smoke LED Logic The Floor 2 Zone Smoke LED main logic (Figure 53) controls the Zone 2 Smoke LED on the FSCS. Figure 53: Zone Smoke LED Main Logic The Zone Smoke expanded logic (Figure 54) has the following logic: If the zone is in smoke control turn the FSCS Smoke LED on solid. If the panel status is bad, flash the FSCS Smoke LED. Figure 54: Zone Smoke Block Logic 54

55 Zone Smoke LED - IFC Zone Detector Trouble Interlock Definition The IFC Zone Detector Trouble Interlock Definition (Figure 55) contains a point for each detector in the mall. When a detector goes into alarm the FSCS Trouble LED for that zone is illuminated. Figure 55: IFC Zone Detector Interlock Definition Zone Smoke LED - IFC Zone Trouble Interlock Definition The IFC Zone Trouble Interlock Definition (Figure 56) contains a point for the present state and reliability of the zone, and a point for the IFC Zone Detector Trouble. Figure 56: IFC Zone Trouble Interlock Definition Table 10: IFC Point State Table BACnet Point State State 1 - Normal State 2 - Active Alarm State 3 - Fault State 4 - Disable NAE Point State State 1 - Normal State 2 - Active Alarm State 3 - Fault State 4 - Unreliable 55

56 Zone Smoke LED - 3rd Party Zone Trouble Interlock Definition The 3rd Party Zone Trouble Interlock Definition (Figure 57) contains an optional, third-party, normally open (N.O.) contact input connection, and a point to monitor the DX offline status. If the third party point goes unreliable or the DX monitoring the third party point goes offline, the Zone LED is lit. Figure 57: 3rd Party Zone Trouble Interlock Definition 56

57 Fire Fighter Control Logic The FSCS Fighter Control main logic (Figure 58) turns the Fire Fighter Control Auto LED on if the Fire Fighter Control Key is off. It turns the Fire Fighter Control LED on if the Fire Fighter Control Key is on. If the Programming in Progress point is on, the logic turns on the Programming Active LED. This point must be turned on any time changes are being made to the LCT application. The expanded FFC block is shown in Figure 59. Figure 58: Fire Fighter Control LED Main Logic Figure 59: FFC Block Logic Controls Group 507 E. Michigan Street Milwaukee, WI Metasys is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners Johnson Controls, Inc. Published in U.S.A. 57

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction

More information

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Introduction

More information

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT-1201754 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

DX-9100/9120 Local Sonalert Logic

DX-9100/9120 Local Sonalert Logic Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPICATION NOTE DX-9100/9120 ocal Sonalert ogic Introduction Page 3 Application Description *3 Design

More information

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Code No. LIT-1201993 Software Release 2.1 Issued April 12, 2006 Supersedes July 20, 2005 Document Introduction.................................................

More information

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLCATN NT Multi-Story Building Floor Above/Floor Below Pressurization and xhaust Logic ntroduction Page 3

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43 Metasys etwork Technical Manual 636 Objects Section Technical Bulletin Issue Date 696 Fire System Objects Introduction Page *3 Description *3 Purpose *5 Capabilities *7 Functional Diagram *1 Operator Interface

More information

Metasys System Extended Architecture Smoke Control System

Metasys System Extended Architecture Smoke Control System Metasys System Extended Architecture Smoke Control System Technical Bulletin MS-NAE5510-0U Code No. LIT-1201684 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLATN NTE Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit ntroduction Page 3 Application Description

More information

Fire Operator Workstation (Fire OWS) User s Guide

Fire Operator Workstation (Fire OWS) User s Guide Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

Table of Contents. i-vu CCN Standard 4.2

Table of Contents. i-vu CCN Standard 4.2 i-vu CCN Standard 4.2 Owner's Guide CARRIER CORPORATION 2009 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-381-01 7/13/2009 Table of Contents Accessing your

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units... Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12011781 Software Release 3.12 Issued June 20, 2013 Supersedes April 20, 2012 Refer to the QuickLIT Web site for the most up-to-date version

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12012141 Software Release 3.14 SP1 Issued June 23, 2017 The Johnson Controls P2000 Security Management System supports the integration

More information

i-vu CCN 4.0 Owner s Guide

i-vu CCN 4.0 Owner s Guide i-vu CCN 4.0 Owner s Guide CARRIER CORPORAION 2007 A member of the United echnologies Corporation family. Stock symbol UX. 11-808-377-01 07/07 able of Contents ACCESSING YOUR SYSEM... 3 YOUR SYSEM DEAILS...

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Solution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview

Solution Guide. UUKL Smoke Control System.  1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview Solution Guide UL 864, 9th Edition, UUKL Smoke Control Listing Overview Applications Distech Controls UUKL smoke control system can be used for: Dedicated smoke control applications: Used exclusively for

More information

TEC Networked Multi-Stage Economizer Thermostat

TEC Networked Multi-Stage Economizer Thermostat Installation Instructions Issue Date January 19, 2005 TEC2104-2 Networked Multi-Stage Economizer Thermostat Application The TEC2104-2 thermostat is an N2 networked thermostat that provides control of single-

More information

CSP-204 CSP-208 CSP-104 CSP-108

CSP-204 CSP-208 CSP-104 CSP-108 Fire Alarm Control Panel CSP-204 CSP-208 CSP-104 CSP-108 Operation manual Firmware version 1.1 csp-x_o_en 06/15 SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk POLAND tel. 58 320 94 00 www.satel.eu CONTENTS

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Security System. User Guide for the LED Command Center

Security System. User Guide for the LED Command Center Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

RPM1600 Series Room Pressure Monitors

RPM1600 Series Room Pressure Monitors RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT-12012228 Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How

More information

Metasys Integrator Compu-Aire Application

Metasys Integrator Compu-Aire Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

Autoclave Operations Manual

Autoclave Operations Manual UNIVERSITY OF ILLINOIS AT URBANA/CHAMPAIGN - COMPOSITES MANUFACTURING LAB Autoclave Operations Manual Version 1 Written by KRH 2/21/2011 Contents ACCS... 4 Alarms... 7 Main Display Tabs... 7 Process Control

More information

JCI - Smoke Control Systems Overview 10/27/2016

JCI - Smoke Control Systems Overview 10/27/2016 If the you can read this Click on the icon to choose a picture or To Reset: Right click on the slide thumbnail and select reset slide or choose the Reset button on the Home ribbon (next to the font choice

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

Synergis Master Controller 2.2 Integration Guide for Assa Abloy IP Locks

Synergis Master Controller 2.2 Integration Guide for Assa Abloy IP Locks Synergis Master Controller 2.2 Integration Guide for Assa Abloy IP Locks This guide supplements the Synergis Master Controller Configuration Guide and explains how to configure Assa Abloy IP locks (PoE

More information

IT801 Thermostat. User s Manual. The complete guide to the set up and operation of your new smart Wi-Fi thermostat.

IT801 Thermostat. User s Manual. The complete guide to the set up and operation of your new smart Wi-Fi thermostat. IT801 Thermostat User s Manual The complete guide to the set up and operation of your new smart Wi-Fi thermostat. The smart Wi-Fi thermostat system learns your comfort preferences, then finds opportunities

More information

Smoke Control Manual

Smoke Control Manual Smoke Control Manual For BACnet Systems ON BAC-5800 Controller OFF ON BAC-5800 Controller Pressurized Third Floor Stairwell Fan ON OFF BAC-5800 Controller Exhausted Second Floor OFF BAC-5800 Controller

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front

More information

Feature Summary. I. System

Feature Summary. I. System I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in

More information

Peak Partners Web-Programmable Thermostat Homeowner s Manual. Look inside for a complete guide to the setup and operation of your new thermostat.

Peak Partners Web-Programmable Thermostat Homeowner s Manual. Look inside for a complete guide to the setup and operation of your new thermostat. Peak Partners Web-Programmable Thermostat Homeowner s Manual Look inside for a complete guide to the setup and operation of your new thermostat. Table of Contents Step 1: Getting Started...4-6 A. Thermostat

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

TEC Networked Single-Stage Thermostat

TEC Networked Single-Stage Thermostat Installation Instructions Issue Date January 19, 2005 TEC2101-2 Networked Single-Stage Thermostat Application The TEC2101-2 thermostat is an N2 networked thermostat that provides control of single-stage

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 OPERATORS MANUAL AFP-300/400 INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02) 9899-4155

More information

Ion Gateway Cellular Gateway and Wireless Sensors

Ion Gateway Cellular Gateway and Wireless Sensors Page 1 of 9 Account & Network Setup If this is your first time using the Ion Gateway online system site you will need to create a new account. If you have already created an account you can skip to the

More information

HikCentral Web Client. User Manual

HikCentral Web Client. User Manual HikCentral Web Client User Manual Legal Information User Manual 2018 Hangzhou Hikvision Digital Technology Co., Ltd. About this Manual This Manual is subject to domestic and international copyright protection.

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

Security System. User s Guide for the Text Command Center

Security System. User s Guide for the Text Command Center User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:

More information

Siemens Thermostats. RDY2000BN Thermostat

Siemens Thermostats. RDY2000BN Thermostat Siemens Thermostats RDY2000BN Thermostat Answers for infrastructure and cities. Introducing the RDY2000BN BACnet Commercial Thermostat Bring more buildings and zones under control Reduce energy costs BACnet

More information

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND

More information

Raytec Avigilon Integration User Guide Integrating Raytec Network Illuminators with Avigilon Control Center Document Revision 2.0

Raytec Avigilon Integration User Guide Integrating Raytec Network Illuminators with Avigilon Control Center Document Revision 2.0 Raytec Avigilon Integration User Guide Integrating Raytec Network Illuminators with Avigilon Control Center Document Revision 2.0 Table of Contents 1 INTRODUCTION... 3 1.1 OVERVIEW... 3 1.2 SOFTWARE COMPONENTS...

More information

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual Instruction manual MTL process alarm equipment October 2016 CSM 725B rev 2 MTL RTK 725B Configuration Software Manual SECTION 1 - INTRODUCTION... 5 Basic Requirements... 5 SECTION 2 - SOFTWARE INSTALLATION...

More information

Installation, Configuration and User Manual

Installation, Configuration and User Manual Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.

More information

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS CONTENTS 1. System Overview 2. User responsibilities 3. First Line controls and indications 3.1 Logging on to the fire alarm system 3.2 Checking system status

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 2 OCCUPIED MODE: When the program control source calls for

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

HikCentral Web Client. User Manual

HikCentral Web Client. User Manual HikCentral Web Client User Manual Legal Information User Manual 2018 Hangzhou Hikvision Digital Technology Co., Ltd. About this Manual This Manual is subject to domestic and international copyright protection.

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

Avigilon Control Center 5 System Integration Guide

Avigilon Control Center 5 System Integration Guide Avigilon Control Center 5 System Integration Guide for Paxton Net2 Access Control Systems 2014 Avigilon Corporation. All rights reserved. Unless expressly granted in writing, no license is granted with

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

RMS-I-DE-01 Smoke Detector

RMS-I-DE-01 Smoke Detector RMS-I-DE-01 Smoke Detector 2012 CONTEG, spol. s r.o. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted or stored in any retrieval system of any nature,

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

Avigilon System Integration Guide. Avigilon Control Center with AMAG Symmetry Security Management System 7.0

Avigilon System Integration Guide. Avigilon Control Center with AMAG Symmetry Security Management System 7.0 Avigilon System Integration Guide Avigilon Control Center with AMAG Symmetry Security Management System 7.0 2013-2016, Avigilon Corporation. All rights reserved. AVIGILON, the AVIGILON logo, HDSM, HIGH

More information

TEC Networked Multi-Stage Thermostat

TEC Networked Multi-Stage Thermostat Installation Instructions Issue Date September 2, 2003 TEC2103-1 Networked Multi-Stage Thermostat Application The TEC2103-1 is an N2 networked thermostat that provides control of multi-stage Heating, Ventilating,

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

INTELLIGENT FIRE ALARM CONTROL PANEL

INTELLIGENT FIRE ALARM CONTROL PANEL INTELLIGENT FIRE ALARM CONTROL PANEL FX-2000 SERIES Description Mircom s FX-2000 Series Intelligent Analog Fire Alarm Control Panel is designed to provide maximum flexibility of analog system requirements

More information

Tebis application software

Tebis application software 5 Tebis application software STG51x Radio smoke detector STG54x Radio heatstroke Electrical / Mechanical characteristics: see product information Product reference Designation ETS version TP device RF

More information

Kaleidescape Programming Manual for Elan Home Systems

Kaleidescape Programming Manual for Elan Home Systems Kaleidescape Programming Manual for Elan Home Systems Rev.1, July 2008 Elan Templates v1.0 2007-2008 Kaleidescape, Inc. All rights reserved. Kaleidescape and the Kaleidescape logo are trademarks of Kaleidescape,

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and if found, report it immediately to the carrier. Also check

More information

ZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

Ovation Alarm Management System

Ovation Alarm Management System Ovation Alarm Management System Features Multiple types of fully configurable, easy-tounderstand alarm displays Convenient access to past alarms, returns and state changes Simplified ability to acknowledge,

More information

TEC210x-2 Series Networked Thermostats

TEC210x-2 Series Networked Thermostats Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

AdaptAire. Digital Control System. User Manual. Expert Systems

AdaptAire. Digital Control System. User Manual. Expert Systems AdaptAire Digital Control System User Manual Expert Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 10 ADAPTAIRE DEFAULT SETTINGS... 10 UNIT OPERATING MODES... 11 MRT Controls:...

More information

Flopurge TS. Operation Manual

Flopurge TS. Operation Manual Flopurge TS Operation Manual Part Number 079-0204 Spectron Gas Control Systems United Kingdom Unit 4, Herald Court, University of Warwick Science Park, Coventry, CV4 7EZ +44 (0)24 7641 6234 sales@spectron-gcs.com

More information

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626)

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626) PF1000 CONTROLLER for the AQUARIUS I/II DEIONIZED WATER HEATING SYSTEM Heateflex Corporation 405 E. Santa Clara St. TEL: (626)599-8566; FAX: (626)599-9567 Rev. 07 10/19/10, (PF1000) 1 2 TABLE OF CONTENTS

More information

End To End Optical Beam Smoke Detector. Additional Information

End To End Optical Beam Smoke Detector. Additional Information End To End Optical Beam Smoke Detector Additional Information EN 1. Multiple Zone Wiring When using more than one System Controller on a single zone of a conventional Fire Control Panel (FCP), it is important

More information

Section 8 System Operation

Section 8 System Operation Section 8 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this

More information

F series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC

F series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC echoflex Powered by ETC ER1S-FC Slim Line Dimming Controller F series This guide covers the F series of the Complete Room Controller, model number ER1S-FCU equipped with a 902 MHz radio. The box contents

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Monitoring Operator Guide. Access Control Manager Software Version

Monitoring Operator Guide. Access Control Manager Software Version Monitoring Operator Guide Access Control Manager Software Version 5.10.10 2018, Avigilon Corporation. All rights reserved. AVIGILON, the AVIGILON logo, ACCESS CONTROL MANAGER, ACM, ACM VERIFY AND TRUSTED

More information

Metasys Integrator Cleaver-Brooks Application

Metasys Integrator Cleaver-Brooks Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details

More information

TEC1100 Series Thermostats

TEC1100 Series Thermostats Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0601 TEC1100 Series Thermostats TEC1100 is a series of non-programmable thermostats with a

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

Avigilon Control Center 5 System Integration Guide

Avigilon Control Center 5 System Integration Guide Avigilon Control Center 5 System Integration Guide with Hirsch Velocity INT-HIRSCH-B-Rev1 2012 2014 Avigilon Corporation. All rights reserved. Unless expressly granted in writing, no license is granted

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 SEQUENCE OF OPERATION The ALC controller is turned on

More information