1 Craig Wolfe Toxalert International, Inc. Mound, MN

2 Codes & Standards Technologies & Locating Sensors System Maintenance

3 Codes and Standards ANSI/ASHRAE International Mechanical Code (IMC) 2006 International Fire Code (IFC) 2006

4 Codes and Standards ANSI/ASHRAE Safety Standard for Refrigeration Systems

5 ASHRAE Forward Care should be taken to avoid stagnant pockets of refrigerant vapors by proper location of ventilation inlet and exhaust openings. All machinery rooms are required to have detectors that will activate an alarm and mechanical ventilation at a value not greater than the corresponding TLV-TWA. Informative Appendix I provides guidance on integrating the requirements of this standard with occupational health & safety programs.

6 ASHRAE Refrigerating Machinery Room, General Requirements Each machinery room shall contain a detector, located in an area where refrigerant from a leak will concentrate, that actuates an alarm & mechanical ventilation at a value not greater than the corresponding TLV-TWA (or toxicity measure consistent therewith). The alarm shall annunciate visual & audible alarms inside the refrigerating machinery room & outside each entrance to the refrigerating machinery room. The alarms required in this section shall be of the manual reset type with the reset located inside the refrigerating machinery room..

7 ASHRAE Combustion equipment shall not be installed in the same machinery room with refrigerant-containing equipment except under one of the following conditions: (a) combustion air is ducted (b) a refrigerant detector, is employed to automatically shut down the combustion process in the event of refrigerant leakage.

8 ASHRAE Machinery Room, Special Requirements i. Remote control of mechanical equipment in the refrigerating machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separated electrical circuit and have a control switch located immediately outside the machinery room door.

9 Codes and Standards 2006 IMC General. Refrigeration systems shall comply with the requirements of this code and, except as modified by this code, ASHRAE 15. Ammonia-refrigerating systems shall comply with this code and, except as modified by this code, ASHRAE 15.

10 2006 IMC Refrigerant detector. Refrigerant detectors in machinery rooms shall be provided as required by Sections of the International Fire Code.

11 2006 IMC Remote controls. Remote control of the mechanical equipment and appliances located in the machinery room shall be provided as required by Sections of the International Fire Code.

12 2006 IMC Remote controls Refrigerant system. A clearly identified switch of the break-glass type shall provide off-only control of electrically energized equipment and appliances in the machinery room, other than refrigerant leak detectors and machinery room ventilation.

13 2006 IMC Remote controls Ventilation system. A clearly identified switch of the break-glass type shall provide on-only control of machinery room ventilation fans.

14 Codes and Standards 2006 IFC Refrigerant detector. Machinery rooms shall contain a refrigerant detector with an audible and visual alarm. The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant from a leak will concentrate. The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values shown in the International Mechanical Code for the refrigerant classification. Detectors and alarm shall be placed in approved locations.

15 2006 IFC Remote controls. Remote control of the mechanical equipment and appliances located in the machinery room shall be provided at an approved location immediately outside the machinery room and adjacent to its principal entrance.

16 2006 IFC Remote controls Refrigerant system. A clearly identified switch of the break-glass type shall provide off-only control of electrically energized equipment and appliances in the machinery room, other than refrigerant leak detectors and machinery room ventilation.

17 2006 IFC Remote controls Ventilation system. A clearly identified switch of the break-glass type shall provide on-only control of machinery room ventilation fans.

18 Sensor Technologies Monitoring Systems Locating Sensors

19 Sensor Technology Common Types Of Refrigerant Leak Sensors Metal Oxide Semiconductor (MOS) Non Dispersive & Photoacoustic Infrared

20 Sensor Technology MOS SENSOR Heater Coil Sensor Element Pin

21 Sensor Technology Infrared Sensor LIGHT FILTERS SENSOR CHAMBER LIGHT DETECTOR INFRARED LIGHT SOURCE SIGNAL PROCESSOR

22 Leak Detection Systems Sampling Systems & Electronic/Diffusion Systems

23 Leak Detection Systems Sampling System CONTROLLER EXHAUST LINE DRAW PUMP SENSOR SOLENOID VALVES TUBING SAMPLE POINT FILTERS

24 Leak Detection Systems Electronic/Diffusion System CONTROLLER REMOTE SENSORS

25 Leak Detection Systems Features Multi-Stage Control LCD Display of Refrigerant Concentration Visual Indicators for Power On Stage of Activation Fault Fan Auto/Purge Switch Audible Alarm With Silence Switch Manual/Auto Warning Stage Reset Switch

26 Leak Detection Systems Options Analog output (4-20mA or 0-10vdc) Integral strobe RS 232/485 communications for modbus, BACnet

27 Leak Detection Systems Typical Control CONTROLLER 120VAC FIRST STAGE SECOND STAGE FAULT

28 Locating Sensors Guide lines to properly locating a refrigerant sensor in an equipment room is: (a) determining the airflow pattern in the room; (b) remembering that occupant safety is the primary motive for installing the sensor; and (c) All commonly used refrigerants except ammonia are 3 to 5 times heavier than air.

29 Locating Sensors As a Minimum General Guide Locate sensors so no chiller is more than 50 ft. from a sensor.

30 CHILLER CHILLER CHILLER CHILLER Locating Sensors EXHAUST REFRIGERANT LEAK MONITOR PANEL AIR INTAKE REFRIGERANT SENSOR

31 CHILLER CHILLER CHILLER CHILLER Locating Sensors EXHAUST REFRIGERANT LEAK MONITOR PANEL AIR INTAKE REFRIGERANT SENSOR

32 CHILLER CHILLER CHILLER Locating Sensors REFRIGERANT LEAK MONITOR PANEL AIR INTAKE EXHAUST REFRIGERANT SENSOR

33 CHILLER CHILLER CHILLER Locating Sensors REFRIGERANT LEAK MONITOR PANEL AIR INTAKE EXHAUST REFRIGERANT SENSOR

34 Leak Monitoring System STROBE/REM HORN/REM SCBA TOX-REFRIG PANEL TOX-REFRIG/ANA CH-1 CH-2 ALM/REFRIG TOX-REFRIG/ANA BOILER STROBE/REM HORN/REM

35

36 Maintenance ASHRAE Standard Periodic tests. Detector(s), alarm(s), and mechanical ventilating systems shall be tested in accordance with manufacturers specifications and the requirements of the jurisdiction having authority.

37 Maintenance 2006 IMC Testing required. The following emergency devices and systems shall be periodically tested in accordance with the manufacturer s instructions and as required by the code official: Detection and alarm systems.

38 Maintenance 2006 IFC Periodic testing. The following emergency devices and systems shall be periodically tested in accordance with the manufacturer s instructions and as required by the fire code official: Detection and alarm systems.

39 Maintenance MOS/Diffusion System Periodic Maintenance Sensor calibration

40 Maintenance Sampling Infrared System Periodic Maintenance Sensor calibration Sample point filters Internal filter

41 Maintenance Calibration kit

42 Questions?

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications January 15, 2018 Revision 6 Ammonia detection system codes and design specifications Following is a discussion of ammonia detection system design

More information

Safety Standard for Refrigeration Systems

Safety Standard for Refrigeration Systems BSR/ASHRAE Addendum a ANSI/ASHRAE Standard 15-2016 First Public Review Draft Safety Standard for Refrigeration Systems First Public Review (April 2017) (Draft shows Proposed Changes to Current Standard)

More information

ICC CODE CORNER 2015 International Fire Code

ICC CODE CORNER 2015 International Fire Code SECTION 606 MECHANICAL REFRIGERATION [M] 606.1 Scope. Refrigeration systems shall be installed in Code. [M] 606.2 Refrigerants. The use and purity of new, recovered and reclaimed refrigerants shall be

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATI AND OPERATING INSTRUCTIS PRODUCTS CMD Series CO Detectors FGD Series Refrigerant Detectors AGD Series Toxic Gas Detectors CGD Series Combustible Gas Detectors (All transmitters are factory set

More information

Ammonia Refrigeration RAGAGEP

Ammonia Refrigeration RAGAGEP Providing Solutions. Simplifying Regulation. Ammonia Refrigeration RAGAGEP Peter Thomas, P.E., CSP Resource Compliance, Inc. Introduction Providing Solutions. Simplifying Regulation. Providing Solutions.

More information

Guidelines for the Design Engineer

Guidelines for the Design Engineer Carbon Monoxide (CO) Detection and Control Systems for Parking Structures Guidelines for the Rev 1.13 1 General Overview... 3 1.1 Carbon Monoxide and Its Effects... 3 2 Installation and Application Codes

More information

HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL

HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL S E R I A L N O. M O D E L N O. T e m p. R a n g e 1 - = > 6 0 o F 2 - = 4 0-6 0 o F 3 - = < 4 0 o F - G a s T y p e 1 - R -1 1 2

More information

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL SE R IA L N O. M O D E L N O. Tem p. Range 1 - = > 60 o F 2 - = 40-60 o F 3 - = < 40 o F G as Type 1 - R-11 2 - R-12 3

More information

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro A d e v i h c r D c o n e m u WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship

More information

incontrol Systems Inc. Flame and Gas Detection

incontrol Systems Inc. Flame and Gas Detection incontrol Systems Inc. Flame and Gas Detection Our flame and gas detectors are globally certified to the latest product approval standards Wherever toxic or combustible gases are part of an industrial

More information

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC

More information

Warranty Registration

Warranty Registration WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free from defects in workmanship and materials for a period

More information

ASHRAE Safety Standards. Mechanical Rooms and Gas Detection in Commercial Applications

ASHRAE Safety Standards. Mechanical Rooms and Gas Detection in Commercial Applications HA University ASHRAE Safety Standards Mechanical Rooms and Gas Detection in Commercial Applications presented by Greg Kaufman - Honeywell Analytics Gas Hazards Three main types of Gas Hazards: Flammable

More information

Model D12-IR. Digital Gas Transmitter...

Model D12-IR. Digital Gas Transmitter... Model D12-IR Digital Gas Transmitter... ATI s Series D12 gas transmitter line now includes a versatile Infrared system that can be configured for LEL or select toxic gases. The D12-IR utilizes a compact

More information

MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors)

MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors) MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors) Refrigerant Monitor User Manual Technical Support Continental North America Toll Free 1-(800) 387-9487

More information

Chillgard Refrigerant Monitor

Chillgard Refrigerant Monitor Chillgard 5000 Refrigerant Monitor Chillgard 5000 7 Mechanical Equipment Room Gas Monitoring Stay in compliance with ASHRAE 15, the Environmental Protection Agency and local building codes with the Chillgard

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Annex 2, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Section 1 Application 1 The following new sentence is added to the end of paragraph 1.2:

More information

ASHRAE WILL GIVE YOU THE WORLD

ASHRAE WILL GIVE YOU THE WORLD ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee 1 Complete the Distinguished Lecturer Event Summary Critique CTTC

More information

RAGAGEP UPDATE. Douglas Reindl, Director, IRC 2016 IRC R&T Forum

RAGAGEP UPDATE. Douglas Reindl, Director, IRC 2016 IRC R&T Forum RAGAGEP UPDATE Douglas Reindl, Director, IRC 2016 IRC R&T Forum What s the point? Process safety information (d)(3)(ii) The employer shall document that equipment complies with recognized and generally

More information

EXAMPLES OF HOW TO ORDER

EXAMPLES OF HOW TO ORDER E 3 Point PRODUCT SUBMITTAL Toxic and Combustible Gas Detector Standalone Platform (Single or Dual-Gas Monitoring) ORDERING INFORMATION Single-Gas or Dual-Gas Configuration: Base Unit, Surface-Mount Base

More information

EXAMPLES OF HOW TO ORDER

EXAMPLES OF HOW TO ORDER E 3 Point PRODUCT SUBMITTAL Toxic and Combustible Gas Detector Standalone Platform (Single or Dual-Gas Monitoring) ORDERING INFORMATION Single-Gas or Dual-Gas Configuration: Base Unit, Surface-Mount Base

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Murco Core Product Guide Gas Leak Detection Solutions for all your building needs

Murco Core Product Guide Gas Leak Detection Solutions for all your building needs Murco Core Product Guide Gas Leak Detection Solutions for all your building needs Refrigerant Gases Toxic Gases Combustible Gases VOC s Legislation: F Gas Regulation, EH40 Standards: EN378 Lloyds Approval

More information

Gas Detection division of Arjay Engineering. Gas Detection Maintenance Facilities Parking Garages Warehouses. EN-GD-11a

Gas Detection division of Arjay Engineering. Gas Detection Maintenance Facilities Parking Garages Warehouses. EN-GD-11a Gas Detection division of Arjay Engineering Gas Detection Maintenance Facilities Parking Garages Warehouses EN--11a A Company from Strong Roots The Enmet Canada series of gas detection is a product division

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

COLUMBIA PUBLIC SCHOOLS HVAC IMPROVEMENTS - PHASE COLUMBIA, MISSOURI

COLUMBIA PUBLIC SCHOOLS HVAC IMPROVEMENTS - PHASE COLUMBIA, MISSOURI SECTION 283111 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SAM-MAX Refrigerant Monitors

SAM-MAX Refrigerant Monitors SAM-MAX Refrigerant Monitors Monitor Refrigerants Including CFCs, HFCs and Ammonia Monitor Carbon Monoxide Exceeds ASHRAE 5-99 and USEPA 608 Monitoring Requirements Provide for Single or Multipoint Sampling

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6 Digital Gas Transmitters with Auxiliary s & Control Specifications subject to change without notice. USA 181011 Page 1 of 5 DESCRIPTION Digital RS-485 communicating, addressable toxic and combustible gas

More information

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability GasSens Modular Gas Detector... Self Checking Gas Sensors GasSens is a flexible component system providing a variety of options to meet individual gas detection and alarm requirements. From chemical and

More information

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER The 2016 Denver Building and Fire Code includes the following codes except as amendment herein. 2015 IBC (Building) 2015 IFC (Fire)

More information

Your trusted partner in providing the best fixed Gas Detection Sales and Service in Western Canada

Your trusted partner in providing the best fixed Gas Detection Sales and Service in Western Canada Your trusted partner in providing the best fixed Gas Detection Sales and Service in Western Canada MultiGas Detection Ltd. Introduction & Capabilities Leduc Head Office Calgary Office MultiGas Detection

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

Honeywell SLATE ICM Platform

Honeywell SLATE ICM Platform Honeywell SLATE ICM Platform SUBMITTAL SPECIFICATION Note to specifiers: To specify Honeywell SLATE Integrated Combustion Management System with specified packaged boiler manufactures, Copy and Paste both

More information

Ammonia Leak Detector Manual

Ammonia Leak Detector Manual Ammonia Leak Detector Manual Document No. 70-PHW-1023-R2.5 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical,

More information

JAMES MOODY IM FLASH LIFE SAFETY AHJ

JAMES MOODY IM FLASH LIFE SAFETY AHJ TOXIC GAS MONITORING JAMES MOODY IM FLASH LIFE SAFETY AHJ AGENDA 2 Toxic Gas Primary Gas Hazards SemiConductor Industry Code Requirements Large Toxic Gas Monitoring Systems Block Diagram TGM Detection

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

GAS DETECTION. Parking Garage Guide

GAS DETECTION. Parking Garage Guide GAS DETECTION Parking Garage Guide Building owners and facility managers want to provide safe and effective parking garages while minimizing the energy costs associated with heating, ventilation and air

More information

Gas detection in refrigeration systems

Gas detection in refrigeration systems Application Guide Gas detection in refrigeration systems GDIR.danfoss.com Contents Page Commonly used abbreviations...3 Introduction...4 Sensor technology....4 EC - Electrochemical sensor...4 SC - Semiconductor

More information

Recalibrate the way you look at gas detection

Recalibrate the way you look at gas detection Catalogue Gas detection solution Recalibrate the way you look at gas detection Next generation gas detection for industrial refrigeration The next generation of Danfoss gas detectors are based on a digital

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual Toxic and Explosive Smart Gas Monitor PN 151022/151023 Installation and User Manual Quest Controls, Inc. 208 9 th Street Dr. West Palmetto, FL 34221 www.questcontrols.com Phone: (941) 729-4799 Fax: (941)

More information

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES USER INSTRUCTIONS FOR THE CHEMGARD INFRARED GAS MONITOR SERIES To completely customize the specification to your exact application, modification to the

More information

Smoke detection in hazardous areas:

Smoke detection in hazardous areas: WHITE PAPER Smoke detection in hazardous areas: What you need to know Smoke detection in hazardous areas requires detectors that operate effectively and safely in explosive environments. Having the correct

More information

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS RESOLUTION MSC.292(87) THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, NOTING resolution MSC.98(73)

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

Fixed Ammonia Gas Detection. Why it's needed and what it can do for you.

Fixed Ammonia Gas Detection. Why it's needed and what it can do for you. Fixed Ammonia Gas Detection Why it's needed and what it can do for you. Presented by: Marc Shoub Crown Systems, Inc. Phoenix, AZ PH: 602-381-8855 email: CrownPhx@aol.com June 28, 2007 1 RETA Arizona Chapter

More information

HALOGUARD TM II MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL

HALOGUARD TM II MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL HALOGUARD TM II MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL SERIAL NO. MODEL NO. Temp. Range - = > 0 o F - = 0-0 o F - = < 0 o F No. of Sensors/Gas Type A - R- B - R- C - R- Outputs D - R-a - x A

More information

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy. Installation manual detector and controller Code no. 20711062 Page 1/30 CONTENTS Controller... 2 Function of the Relays... 2 Gas Detectors... 2 Cabling... 4 Mechanical Installation of the gas detectors...

More information

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

Process Control PIP PCEA001 Fixed Gas Detection Guidelines November 2015 Process Control PIP PCEA001 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical

More information

AT-G-SENSE Gas Sensing System

AT-G-SENSE Gas Sensing System AT-G-SENSE Gas Sensing System INSTALLATION & OPERATING MANUAL INSTALLATION INSTRUCTIONS Open the AT-G-SENSE by undoing the two screws. Remove metal faceplate, turn over and check connection terminals (maximum

More information

Danfoss Gas Sensor DGS MODBUS

Danfoss Gas Sensor DGS MODBUS Installation Guide Danfoss Gas Sensor DGS MODBUS ADAP-KOOL Refrigeration Control System DGS - Location instructions Location of Sensors Sensors must be located within the appropriate wire lengths from

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

Products and performance

Products and performance Products and performance February 26, 2016 GfG Instrumentation overview of fixed system products Slide 1 GfG Instrumentation, Inc. 1194 Oak Valley Drive, Suite 20, Ann Arbor, Michigan 48108 Toll free (USA

More information

CO and NO 2 Monitoring Systems for Parking Structures

CO and NO 2 Monitoring Systems for Parking Structures Parking Garage Guide This step-by-step guide describes set-up procedures to help provide a safe parking garage while minimizing energy costs associated with ventilation and heating. CO and NO 2 Monitoring

More information

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters.

More information

Guide Specification - MasterFormat 2017 Style SECTION FLOW INSTRUMENTS PART 2 PRODUCTS 2.1 SECTION INCLUDES 2.2 ACCEPTABLE MANUFACTURERS

Guide Specification - MasterFormat 2017 Style SECTION FLOW INSTRUMENTS PART 2 PRODUCTS 2.1 SECTION INCLUDES 2.2 ACCEPTABLE MANUFACTURERS SECTION 230923.14 FLOW INSTRUMENTS Data contained in this guide specification may be placed in either of the following sections, depending on the specifics of the system design, or incorporated within

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

1. PURPOSE This standard specifies safe design, construction, installation, and operation of refrigeration systems.

1. PURPOSE This standard specifies safe design, construction, installation, and operation of refrigeration systems. ants. Over the next 11 years, representatives from the American Gas Association, American Institute of Electrical Engineers, American Institute of Refrigeration, American Chemical Society, American Society

More information

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications SAFETY MANUAL Intelligent Sensors for H 2 S Gas Applications The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

AquiTron DATA S HEET. AT-GU Commercial Refrigerant Sensor

AquiTron DATA S HEET. AT-GU Commercial Refrigerant Sensor AquiTron DATA S HEET Commercial Refrigerant Sensor CONTENTS 1.0 Overview 1.1 General Information 1.2 Technical Specifications 2.0 Front Panel Layout 2.1 General Placement Guidelines 2.2 Components and

More information

MSA Customer Service MSA-INST

MSA Customer Service MSA-INST Our Mission, Your Safety MSA s mission is to ensure that men and women may work in safety and that they, their families and their communities may live in health throughout the world. Our vision is to be

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

CO2 transmitters TRANSMITTERS TO DETECT CARBON DIOXIDE (CO 2 )

CO2 transmitters TRANSMITTERS TO DETECT CARBON DIOXIDE (CO 2 ) CO2 transmitters TRANSMITTERS TO DETECT CARBON DIOXIDE (CO 2 ) Measure carbon dioxide (CO2), carbon monoxide (CO) and temperature (T) Infrared measurement technology (NDIR) Automatic calibration eliminates

More information

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL SAFETY MANUAL PointWatch Eclipse Infrared Hydrocarbon Gas Detector SIL 2 Certified Model PIRECL Safety Certified Model PIRECL PointWatch Eclipse IR Gas Detector This manual addresses the specific requirements

More information

AIRFLOW MEASUREMENT AND CONTROL PRODUCT CATALOG. Phone: 877-4GNTROL ( ) - Internet: GreenTrol.com. r1f

AIRFLOW MEASUREMENT AND CONTROL PRODUCT CATALOG. Phone: 877-4GNTROL ( ) - Internet: GreenTrol.com. r1f AIRFLOW MEASUREMENT AND CONTROL PRODUCT CATALOG Phone: 877-4GNTROL (446-8765) - Internet: GreenTrol.com r1f GreenTrol Automation Inc. GreenFlow GF Series Airflow Measurement Series Overview Thermal Dispersion

More information

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS RHODE ISLAND STATE BUILDING CODE SBC-4 State Mechanical Code Effective August 1, 2007 Replaces Regulation SBC-4 Dated September 1, 2004 STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS Department of Administration

More information

CAUTION & SYMBOL DEFINITIONS:

CAUTION & SYMBOL DEFINITIONS: 1441 Rice Street, St. Paul, MN 55117-3899 USA Phone (651) 487-8844 Fax (651) 487-8857 info@coolairinc.com www.coolairinc.com CAUTION & SYMBOL DEFINITIONS: LBW-50 SPECIFICATIONS (cont d) CAUTION: Gives

More information

Inc Series Digital Gas Detector/Controller. Operation Manual

Inc Series Digital Gas Detector/Controller. Operation Manual 5 Series Digital Gas Detector/Controller Operation Manual TABLE OF CONTENTS 1. 2. 3. 4. 5. 6. 7. General Description 1.1 Applications 1.2 Features Model Selection Guide Characteristics Installation 4.1

More information

SenSmart Universal Gas Detector Series

SenSmart Universal Gas Detector Series SenSmart Universal Gas Detector Series Installation Guide Flammable & Toxic Gas Detectors Smart Alarm Controllers Fire & Gas System Engineering Technical Service & Support Warning: Read & understand contents

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

CH 4 C 2 H 2 C 3 H 8 CO 2 H 2 H 2 S HFC NH 3 NO 2 O 2 O 3 SO 2

CH 4 C 2 H 2 C 3 H 8 CO 2 H 2 H 2 S HFC NH 3 NO 2 O 2 O 3 SO 2 PluraSens CH 4 C 2 H 2 C 3 H 8 CO CO 2 H 2 H 2 S HFC NH 3 NO 2 O 2 O 3 SO 2 VOC E2600 Family Gas Detectors E2610 Series Compact wall-mount housing providing optimal airflow Integrated sensor with long

More information

Todd Jekel, Assistant Director, IRC Feb. 8, Standard Definition. What is a machinery room?

Todd Jekel, Assistant Director, IRC Feb. 8, Standard Definition. What is a machinery room? Machinery Room Requirements & Best Practices Design Todd Jekel, Assistant Director, IRC Feb. 8, 2007 Standard Definition What is a machinery room? ASHRAE 15-2004 3 states: a space, meeting the requirements

More information

Operation Manual. Rev. D GEM-II Self-Contained Gas Detector.

Operation Manual. Rev. D GEM-II Self-Contained Gas Detector. Operation Manual Rev. D 2012.04 GEM-II Self-Contained Gas Detector www.critical-environment.com Rev. D 2012.04 GEM-II Operation Manual TABLE OF CONTENTS 1 POLICIES... 5 1.1 Important Note... 5 1.2 Warranty

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40020 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SL-2000 Series Smoke Detectors, Model EXSAA and EXSAB (Ionization), EXSAG and EXSAH (Photoelectric) Air Specialties Express, 448 S. Main

More information

Multi-Gas-Controller MGC2

Multi-Gas-Controller MGC2 Page 1 Aug. 2018 Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology for continuous monitoring of the ambient air to detect toxic and combustible gases, refrigerants

More information

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation Gas Detection Control Panel Analog and digital controller 4 or 8 lines / 6 to detectors max Highly versatile controller Cost savings on wiring installation Certifications The The Fixed Fixed Gas Gas Detection

More information

Industrial Grade Gas Detection Detecting The Difference

Industrial Grade Gas Detection Detecting The Difference detcon inc. Industrial Grade Gas Detection Detecting The Difference PO Box 8067 The Woodlands, TX 77387 888-367-4286 (toll free) 713-559-9200 281-292-2860 (fax) sales@detcon.com Catalog #CB-0409 www.detcon.com

More information

ENERSAVE Hydrocarbon Scroll Water Cooled Chiller

ENERSAVE Hydrocarbon Scroll Water Cooled Chiller ENERSAVE Hydrocarbon Scroll Water Cooled Chiller Your Green Input to Chiller ever found in the market To eliminate the threat of environmental impact by utilizing environmental friendly refrigerant gas-

More information

Remote Storage Safety 3 Alarm Installation Guide

Remote Storage Safety 3 Alarm Installation Guide Product Description Remote Storage Safety 3 Alarm Installation Guide Model: RAD-0102-6 Thank you for selecting the RAD-0102-6 Remote Storage Safety 3 Alarm. This monitor is designed to protect customers

More information

Control Sequence Number

Control Sequence Number R Control Sequence Number DIGITAL CONTROLS 9800 24 VAC HOT MON NOTE 1: 24VAC MUST BE EARTH GROUNDED COOLING INPUT HOT AI4 AI5 AI6 24 VAC POWER ANALOG INPUTS PRICE UMCB 24VAC BINARY OUTPUTS HOT B01 B02

More information

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control. Détecteur de gaz OLCT80 Detectors-Transmitters for Flammable, Toxic Gases and Oxygen Non-intrusive operation via intrinsically safe infrared remote control Disponible en version déportée, ADF ou de SI

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS

GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS [Second Revised Edition] April, 2003 Issued by: Mechanical and Engineering Branch Room 500, Norquay Building

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee Gil Rossmiller In the construction industry for over 30 years ICC IRC Plumbing & Mechanical Code Development Committee ICC- IECC Commercial Energy Code Development Committee Building Official Parker, Colorado

More information

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector CAUTION & SYMBOL DEFINITIONS: CAUTION: Gives detailed description of different situations to avoid or not avoid for the proper operation of the

More information

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector. Introduction United Safety applies the detection system as a multi-point monitoring for toxic gases, combustibles and oxygen hazards. Self-powered and solar-capable, the features unequaled versatility,

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08 GasScanner 4C Four Channel Monitor Operator s Manual MINT-0280-XX Rev. A 02/25/08 Product Warranty Matheson Tri-Gas., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations

More information

Refrigerant Leak Detector Manual

Refrigerant Leak Detector Manual Refrigerant Leak Detector Manual Document No. 70-PHW-1018-R2.4 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical,

More information

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM User Instructions For The Model 5200 Gas Monitor System To completely customize the specifications to your exact application, modifications to the following

More information

You in Control PRODUCT OVERVIEW

You in Control PRODUCT OVERVIEW AIR PRODUCTS AND CONTROLS You in Control AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SERIES PLENUM DUCT SMOKE DETECTORS NO-FLOW LOW-FLOW SPECIAL APPLICATION -N -P PRODUCT

More information