1 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 1
2 Life Safety Code 2012 Edition Chapter 2 Referenced Publications Become part of the LSC, but only to the extent called for within the other chapters of the LSC Where requirements differ, LSC governs Not the intent too continually upgrade existing buildings Some, are referenced or adopted in total (NFPA 99, 72, 25, etc ) NFPA 10 Portable Fire Extinguishers 2010 Edition Life Safety Code tells us where required: In all health care occupancies In ambulatory health care facilities NFPA 10 tells us: Selection of extinguisher Installation & Travel Distances to extinguishers 2
3 NFPA 10 Portable Fire Extinguishers 2010 Edition Chapter 6 Installation General (Section 6.1) 5 ft < 40 lbs; 3.5 ft > 40 lbs (Max heights) No less than 4 from floor Obvious, signage if not or marking on cabinet Signage for extinguishers near stove hood systems Cabinets can not be locked NFPA 10 Portable Fire Extinguishers 2010 Edition Chapter 7 Inspection Maintenance & Recharging Maintained at a minimum of 1 year interval o Internal exam of fire extinguishers per chart Persons performing maintenance and recharging of fire extinguishers must be certified o NFPA 10 (1998 Edition) only requires person to be trained 3
4 NFPA 10 Portable Fire Extinguishers 2010 Edition Chapter 7 Inspection Maintenance & Recharging Inspected at a minimum of 30 day intervals manually or by electronic monitoring, If used, the electronic monitoring device must be tested annually. NFPA 13 Installation of Sprinkler Systems 2010 Edition Where Required All high rise health care facilities 12 yrs Anywhere accommodations are taken due to sprinkling (e.g., no smoke dampers in smoke barriers, door locking with QRS, etc.) General Requirements Installation Standard Water supply Installed throughout Heads installed properly (QRS vs. Standard Response; coverage, etc.) 4
5 NFPA 13 Installation of Sprinkler Systems 2010 Edition NFPA 13 Installation of Sprinkler Systems 2010 Edition Some Operational Issues Including: Obstructions to spray pattern Obstructions from ceiling mounted items Obstructions from floor mounted obstructions Clearance to Storage 18 5
6 NFPA 13 Installation of Sprinkler Systems 2010 Edition Some Operational Issues Including: Obstructions to spray pattern Obstructions from ceiling mounted items Obstructions from floor mounted items Clearance to Storage 18 Annex Note: A Indicates perimeter shelving and storage can extend higher, provided sprinkler head is not directly above. NFPA 20 Installation of Stationary Pumps For Fire Protection 2010 Edition Installation Standard Acceptance Testing Performance Standards Refers to NFPA 25 for periodic Inspection Testing, and Maintenance Emergency lighting shall be provided in accordance with NFPA 101, Life Safety Code. Note: Old edition allowed fixed or portable batteryoperated lights, including flashlights. 6
7 NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 2011 Edition Includes ITM for Sprinklers, Standpipes, Fire Pumps, Private Fire Service Mains, other Provides components, criteria and frequency of ITM Sample forms provided and charts for ease of use In two new annexes information is provided for classification of needed repairs and hazard evaluation. Adds new definitions differentiating the levels of deficiency for determining the priority of repair. Updates testing frequencies based on a growing data base of inspection, testing, and maintenance records. NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 2011 Edition Water flow alarms (vane-type & pressure switch type) inspections o Was quarterly now semiannual o Mechanical types still quarterly. 7
8 NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 2011 Edition Hose Connection Pressure Reducing Valves & Hose Rack Assembly Pressure Reducing Valves o Was quarterly now annual inspection NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 2011 Edition Main Drain Test o Was quarterly now annual test o Also still required any time the control valve is closed and reopened at a system riser 8
9 NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 2011 Edition Fire Pump Testing o Diesel engine driven fire pumps shall be operated weekly. o Electric motor driven fire pumps shall be operated monthly. (was weekly) NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 2011 Edition Sprinkler Head Testing o In service > 50 yrs: replace or test (repeat every 10 yrs.) o Sprinklers manufactured prior to 1920 shall be replaced. o Fast response > 20 yrs in service: replace or test (repeat every 10 yrs.) o Extra High Temp sprinklers, exposed to extreme temps: test at 5-year intervals. o In service > 75 yrs: replace or test (repeat every 5 yrs.) o Dry sprinklers that have been in service for 10 years shall be replaced or representative samples shall be tested and then retested at 10-year intervals (NEW). 9
10 NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 2011 Edition Internal Inspection of Piping / 5 yr Flushing o o o o Required to be done in two places: By opening a flushing connection at the end of one main and By removing a sprinkler toward the end of one branch line for the purpose of inspecting for the presence of foreign organic and inorganic material. Alternative nondestructive examination methods shall be permitted. Tubercules or slime, if found, shall be tested for indications of microbiologically influenced corrosion (MIC). If the presence of sufficient foreign organic or inorganic material is found to obstruct pipe or sprinklers, an obstruction investigation shall be conducted as described in Section NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 2011 Edition Internal Inspection of Piping / 5 yr Flushing Note: fully blocked sprinkler head Height of internal blockage 10
11 NFPA 72 National Fire Alarm and Signaling Code 2010 Edition Installation Standard (many updates designers should be aware of) Inspection, Testing and Maintenance Standard (some minor changes vendors should be aware of) Sample forms provided and charts for ease of use Major change in the scope and organization of the document. This is reflected in the new title, National Fire Alarm and Signaling Code. Two new chapters have also been on circuits and pathways and emergency control functions and interfaces. Two new guidance annexes, Annex C on System Performance and Design, and Annex D on Speech Intelligibility. NFPA 72 National Fire Alarm and Signaling Code 2010 Edition Smoke detector placement near Heating, Ventilation & Air Conditioning (HVAC) Annex Note: Detectors should not be located in a direct airflow or closer than 36 in. (910 mm) from an air supply diffuser or return air opening. Nothing new here!! 11
12 NFPA 72 National Fire Alarm and Signaling Code 2010 Edition Manual Fire Alarm Pull Stations o Unless installed in an environment that precludes the use of red paint or red plastic, manual fire alarm boxes shall be red in color. o Manual pull stations for initiating other than the fire alarm shall be permitted if the devices are differentiated by a color other than red and labeling. o Manual fire alarm boxes shall be mounted on a background of contrasting color. NFPA 90A Standard for the Installation of Air- Conditioning and Ventilating Systems 2012 Edition Installation Standard (many updates designers should be aware of) Testing and inspection moved to: o NFPA 80 Standard for Fire Doors and Other Opening Protectives o NFPA 105 Standard for Smoke Door Assemblies and Other Opening Protectives Test and inspection frequency shall then be every 4 years, except in hospitals, where the frequency shall be every 6 years. 12
13 NFPA 110 Standard for Emergency Power and Standby Power Systems 2010 Edition Installation Standard Also provide Maintenance and Operational Testing Now allows maintenance free batteries New monthly and annual load test requirements ATS testing requirements Need to meet with your vendor or staff to review all requirements!!! Now a CODE vs Edition was a STANDARD & was applicable only as referenced by NFPA 101 CMS applies to all Health Care and Ambulatory Healthcare Occupancies 13
14 Chapters 1-4: Core Chapters Chapter 1: Administration Chapter 2: Referenced Publications Chapter 3: Definitions Chapter 4: Fundamentals Chapter 4 Fundamentals Building systems in health care facilities shall be designed to meet system Category 1 through Category 4 requirements as detailed in the code. Categories shall be determined by following and documenting a defined risk assessment procedure. The Category definitions in Chapter 4 shall apply to Chapters 5-11 (Specific Systems). 14
15 Chapter 4 Fundamentals Category 1: likely to cause major injury or death Category 2: likely to cause minor injury Category 3: not likely to cause injury Category 4: would have no impact on patient care Chapter 4 Fundamentals Expect CMS to confirm that you are using a risk assessment No need to submit to CMS Examples provided in NFPA 99 Annex (limited) American Society of Healthcare Engineers (ASHE) 15
16 Chapters 12-15: Specific Considerations Chapter 5: Gas & Vacuum Systems Chapter 6: Electrical Systems Wet Procedure Locations Need special protection * Determined by the organization ORs shall be considered to be a wet location unless a risk assessment determines otherwise. * Exception for existing construction inspection procedures Chapters 5-11: Specific Systems & Equipment Chapter 7: IT & Communication Systems * Chapter 8: Plumbing * * CMS chose not to regulate ( no authority ) 16
17 Chapter 9: Heating, Ventilation and Air Conditioning NFPA 99 (1999 Ed.) Required that mechanical systems have the capability of controlling humidity levels at 35% or above April 19, 2013 S & C Memo allows a lower limited of 20% humidity to be used NFPA 99 (2012 Ed.) References ASHRAE , not most current ASHRAE that references 20% RH NFPA 99(2012 Ed.) removed smoke control requirement in anesthetizing locations CMS Proposed Rule referenced to retain it but FINAL RULE did not!! 17
18 Chapter 11 Gas Equipment Chapters 12-15: Specific Considerations Chapter 12 Emergency Management * Chapter 13 Security Management * 18
19 Chapters 12-15: Specific Considerations Chapter 14: Hyperbaric Facilities Chapter 15: Features of Fire Protection Fire Loss Prevention in Operating Rooms Fire Risk Assessment & preoperative time out Flammable Prep policies and procedures Emergency / Fire Procedures specific to ORs Orientation & Training for ALL STAFF! THANK YOU Dave Hood President Nick Gabriele Vice President 19
NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,
NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101
More informationThe Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99
The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 Sharon S. Gilyeat, P.E. Lauren Schrumpf August 8, 2018 Expertly Engineering
More informationFACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)
FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT
More informationFACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS
FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT
More informationOther EC and LS documents may be requested by surveyors, as needed, throughout the survey.
Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the
More informationMAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationNFPA 99 for Facility Managers
NFPA 99 for Facility Managers Application to Existing Facilities October 13, 2015 Jonathan Hart: Senior Fire Protection Engineer Learning Objectives Review the layout of NFPA 99 Understand the application
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationCompliance w/ the 2012 Life Safety Code
Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides
More informationCMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA
Adoption of 2012 Life Safety Code Health Care Facilities Code Kenneth Daily, LNHA kenn@qissurvey.com CMS Announcement May 2016 Life Safety Code Health Care Code Effective July 5 th Numerous changes many
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationEC 5.10 FIRE PREVENTION MANAGEMENT
EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively
More informationService Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT
58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the
More informationCMS Regulatory Update & Survey Trends: Life Safety Code
CMS Regulatory Update & Survey Trends: Life Safety Code CMS Physical Environment Compliance Challenges William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides
More information2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7
WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves
More informationLIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE
California Society for Healthcare Engineering SOUTHERN CALIFORNIA SEMINAR LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE 1 PROGRAM AGENDA Adoption of 2012 LSC CMS Final Rule / Amendments
More informationUnderstanding and Applying NFPA 25
Understanding and Applying NFPA 25 Texas Edition Learning Objectives Describe the scope of NFPA 25. Distinguish between sprinkler system problems that fall within the scope of NFPA 25 and those that do
More informationNew DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE
DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in
More informationNFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering
NFPA 101 and NFPA 99, 2012 Editions Code Update where art meets engineering Austin Dallas Denver Houston Kansas City Miami Nashville Phoenix Richmond Washington DC NFPA 101 and NFPA 99 where art meets
More informationFHCA 2014 Annual Conference & Trade Show
FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion
More informationTOPICS IN CODE ENFORCEMENT
TOPICS IN CODE ENFORCEMENT CAHED SE DISTRICT MEETING FEBRUARY 17, 2017 Mark Jelinske Cator, Ruma, and Associates mjelinske@catorruma.com 303-462-8475 TALKING POINTS Conducting Surveys on NFPA 2012 as of
More information1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time.
Sprinkler 1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time. 2. Does the annual sprinkler head inspection have to be done by a licensed technician
More informationFalse Sense of Security???
IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire
More informationQuick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/
Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA 25 2017 & NFPA 13/72 2016 The purpose of this guide is to help you determine if the system will work as
More informationMAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS
FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are
More informationDeveloping a Healthcare Facility Fire Door Inspection Program
Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationSkilled Healthcare Documentation Requirements Life Safety and Fire Protection
DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required
More informationCalifornia Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19
PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction
More informationJOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015
JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL
More informationBrighton Area Fire Authority
615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following
More informationBuilding Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1
Building Codes & Standards for Healthcare Building Codes and Standards AHJs Codes Defend in Place Walls Sprinklers Fire Alarm Important Dates for Healthcare Facilities 7/5/16 NFPA Life Safety Code 101
More informationCenter for Clinical Standards and Quality /Survey & Certification Group
DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality /Survey
More information9/15/ Cantara Lane Vista, CA (760)
28 th Annual AHCA/FHEA SEMINAR Sprinkler System Inspection, Testing & Maintenance 1 Speaker Information: Bob Caputo, CFPS, CET Vice President Fire & Life Safety America 657 Cantara Lane Vista, CA 92081
More informationNFPA 101 Code Update from 2012 Edition to the 2015 Edition
NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls
More informationChapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.
3610 COMMERCE DR SUITE 817 BALTIMORE MD 21227 P 410.737.8677 F 410.737.8688 www.haifire.com May 5, 2014 Review of Regulations 42 CFR Parts 403, 416, 418, 460, 482, 483 and 485 Medicare and Medicaid Programs;
More informationAPPENDIX H (DESIGN SUBMISSION CRITERIA)
APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation
More informationSystem Test Report CLEAN AGENT
City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information
More informationAgency for Health Care Administration
Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other
More informationDanilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services
Life Safety Code Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services danilo.concepcion@stjoe.org 714-771-8944 The findings and conclusions in this presentation are
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationAgency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014
Agency for Health Care Administration Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014 CMS S&C Letter Interpretation CMS- S&C: 13-58-LSC Dated: 08/30/2013 Several Categorical LSC
More informationAgency for Health Care Administration
Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements
More informationLIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN
Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION
More information27th Annual AHCA Seminar
27th Annual AHCA Seminar NFPA 99 2012 Edition Overview and Discussion Presented by James Peterkin, PE Sr. Fire Protection Engineer Heery International Monday September 26, 2011 Disclaimer Not Speaking
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationFire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours
Fire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours United Facilities Criteria U. S. Department of Defense UFC 3-601-02 PDH Academy PO Box 449 Pewaukee, WI 53072 www.pdhacademy.com pdhacademy@gmail.com
More informationFIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY
FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1
More informationRequirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011
1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection
More informationTire Storage. Michigan Fire Inspectors Society Fall Conference
Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationYORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS
YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS The York County Department of Fire Safety reviews all commercial building plan submittals for compliance with the 2015 International
More informationTennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities
Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities 1 Colby Henson Fire Safety Supervisor 665 Mainstream Drive 2nd floor 615-806-4798 Colby.Henson@tn.gov
More informationTHE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission
2013 THE HEALTHCARE ENVIRONMENT UPDATE Anne M. Guglielmo, Engineer Engineering Department The Joint Commission Standard/NPSG 2012 Non Compliance 2013 Non Compliance (1 st Six Months) RC.01.01.01 61% 55%
More informationCandy Easterling K-063. Adequate and Reliable Water Supply for the Sprinkler System. CITY WATER or WATER TANK for Sprinkler System
Candy Easterling K-063 Adequate and Reliable Water Supply for the Sprinkler System CITY WATER or WATER TANK for Sprinkler System Life Safety Code Presentation 1 Fire Extinguishers K-064 2000 NFPA 101,
More informationAgency for Health Care Administration
Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER
More informationPresented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC
Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC Changes to Life Safety Compliance Healthcare leaders will have to deal with many changes in Life Safety compliance when
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationUnderstanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training
Understanding, Applying and Enforcing NFPA 25 James D. Lake NFSA Director of Training When Sprinklers Are Ineffective Water did not reach fire 8% 7% 7% 5% 44% Not enough water released Damaged Component
More informationEC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10
MSL Healthcare Partners, Inc. Wild Card EPs Paraphrase K-tag # EC.02.04.03 EP 14 All other electrical K-920 equipment in patient care vicinity NFPA 992012, Chapter 10 K-924 K-928 K-931 K-tag Description
More informationSACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET
SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET 1 SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT
More informationFire Sprinkler Plan Submittal Form
Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10
More information10/25/2018. Facilitators. Emergency Preparedness &Life Safety Code for Administrators. Participant Guide
Emergency Preparedness &Life Safety Code for Administrators 1 Participant Guide Emergency PreparednessHandouts Graphic Organizer Sample Checklist for Emergency Preparedness Regulation Compliance Crosswalk
More information4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code.
Carsten Lunde, ASSE 6050 Instructor April 20, 2017 Carsten s Yearly Analysis, Inc. Any opinions expressed verbally by the speaker before you and all text in this presentation should be considered the speakers
More informationAgency for Health Care Administration
Page 1 of 41 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0011 - LIFE SAFETY CODE STANDARD If the building has a common wall with a nonconforming building, the common
More informationWHEA FSE inspections.
WHEA FSE inspections www.jfahern.com FEC.02.03.05 Features of Fire Safety Buildings are protected from fire by a series of detection, notification and suppression devices Each feature of fire safety must
More informationReview of Revisions to NFPA 1, 2015 Edition
James S Peterkin, PE, LEED AP Senior Fire Protection Engineer TLC Engineering for Architecture Anthony Apfelbeck, CFPS, CBO, CFO, FM, FIFireE, MPA Building and Fire Official City of Altamonte Springs,
More informationThe Healthcare Environment Update
2017 The Healthcare Environment Update John Maurer, SASHE, CHFM, CHSP Engineering Department The Joint Commission Engineering Department 2017-1 Most Cited Standards Standard 2015 % Noncompliance 2016 %
More informationIMC Significant Changes Summary Tier I
2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just
More informationMedical Gas Inspections and Maintenance Programs. HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson
Medical Gas Inspections and Maintenance Programs HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson Mathis Carlson I have worked for the last 15+ years in the Medical
More informationNFPA 72 Code Changes vs 2013
NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996
More informationKoffel Associates, Inc.
NFPA 25: STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com
More informationNFPA Impacts Training presentation for: AlaSHE Spring 2017 Conference David Stymiest, Senior Consultant, Smith Seckman Reid, Inc.
NFPA 99-2012 Impacts Training presentation for: AlaSHE Spring 2017 Conference David Stymiest, Senior Consultant, Smith Seckman Reid, Inc. Content Disclaimer - Content Disclaimer: These slides are only
More informationBuilding Analytics and Compliance: How analytics can be used to aid in performancebased certifications. Bryant M. Kirkland Jr, PE, CCP, LEED AP
Building Analytics and Compliance: How analytics can be used to aid in performancebased certifications Bryant M. Kirkland Jr, PE, CCP, LEED AP AIA Quality Assurance The Building Commissioning Association
More informationRevised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*
1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system
More informationApartment Fire & Safety Inspection. City of Guadalupe
Apartment Fire & Safety Inspection City of Guadalupe Intent Provide information and the most common violation. It is NOT the intent to Identify all hazards a building may experience. It is NOT intended
More informationNFPA 80 Overview January 21, 2016
NFPA 80 Overview January 21, 2016 Kristin Bigda, P.E. Senior Fire Protection Engineer National Fire Protection Association Presenter Kristin Bigda, P.E. Senior Fire Protection Engineer, NFPA Building Fire
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More information2017 Accreditation Updates
2017 Accreditation Updates Tennessee Healthcare Engineers Association 2017 Spring Conference Pickwick Landing State Park Counce, Tennessee 38326 Presented May 17, 2017 By Ken Gregory Vice President, Accreditation
More informationCommon Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive.
Common Fire Code Violation Checklist Listed are some of the most commonly found fire code violations and should not be considered as all inclusive. Exterior Features All fire access roads signed per TFD
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationLife Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved
Life Safety Code Common Discepancies Course# LSC102 EZpdh.com All Rights Reserved 1. K147 Electrical - Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code. 9.1.2
More information10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION
Enjoy Your TJC Survey Bill H. McCully CHFM SASHE Senior Consultant MSL Healthcare Partners PREPARATION 1 Top Eight Most Cited Standards (George Mills) EC News May 2015 Top Citations EC.02.06.01 56% EC.02.05.01
More informationChanges to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates
Issued September 20, 2017 Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Home Care (OME) Accreditation
More information2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance
2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance Will begin at 1 pm Housekeeping Announcements Problems during the call? Press *0
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationReport on First Revisions with Statement June 2014 NFPA 101
101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies
More informationEXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5
UNIT PRICING IS A "NOT TO EXCEED" PRICE EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 Unit Pricing to perform all required Test
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationAgency for Health Care Administration
Page 1 of 94 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2
THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationChanges to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates
Issued June 28, 207 Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates Environment of Care (EC) Chapter Nursing Care Center (NCC) Accreditation Program Standard
More informationHeathcare Interpretations Task Force
Healthcare Interpretations Task Force MEMORANDUM TO: FROM: Heathcare Interpretations Task Force Robert Solomon DATE: May 30, 2014 SUBJ: HITF Meeting Agenda and Meeting Room Location Information Attached
More information2016 Joint Commission Update
2016 Joint Commission Update Bert M. Gumeringer, MBA, CHFM, FASHE Asst. Vice President-Facilities Operations Texas Children s Hospital August 12, 2016 11:30am-12:30pm Top 10 Findings Comparison-2015 vs.2016
More informationEstablished /10/2015. Doran Pruisner Dan Wood
Established 1911 Doran Pruisner Dan Wood The International Fire Code, 2009 Edition shall apply to all occupancies except for those that are explicitly excluded by these provisions. 1 Buildings built between
More informationCALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS
CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review
More informationThere are many changes to NFPA 99 from 1993 to 2015, but we want to concentrate on the changes made from 2012 to 2015, and we need to know a little
There are many changes to NFPA 99 from 1993 to 2015, but we want to concentrate on the changes made from 2012 to 2015, and we need to know a little about how all of this developed into the 2015 edition.
More informationAmerican Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.
American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals
More information