1 Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction Page 3 Application Description 3 Sequence of Operation *3 Design Considerations *5 Application Details 9 Main Function 9 Location *9 Graphic Representation 9 Point List 10 GX-9100 Printouts 11 Variations 18 * Indicates those sections where changes have occurred since the last printing Johnson Controls, Inc. 1 Code No. LIT

2 2 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

3 Introduction Application Description Sequence of Operation This application is for warehouse smoke exhaust and reset logic for a rooftop unit. During a fire alarm, the process described in this document controls a rooftop unit to minimize the spread of smoke. After the fire alarm is cleared, you must reset the process to monitor for subsequent alarms. Notes: Smoke control applications, such as this, issue commands to controlled devices that pressurize or exhaust an area of a building. This application note presents only an example of a smoke control strategy. Realize that since every building is unique, the details of applying the strategy will vary. This application note, then, is offered to assist you in developing an application that will be appropriate for your project. When an automatic detector in the warehouse indicates an alarm, the process is triggered. This process turns off the supply fan, turns on the exhaust fan, opens the modulated exhaust dampers, closes the return air dampers, closes the outside air dampers, opens the inlet vanes on the exhaust fan, and closes the inlet vanes on the supply fan. This process locks out heating and cooling, and locks out all other commands for this HVAC equipment (including low-limit controls). Subsequent alarms and subsequent action will be locked out, except for manual override from the Firefighter s Smoke Control Station (FSCS). The alarm condition has higher priority than HVAC control. The supply fan is normally controlled through the PID using normal HVAC processes to disable the fan by the external forcing connection of the PID to Off or changing the setpoint via the Off mode control connection. An alarm controls direct forcing of the hardware outputs. The priority order for the DX-9100/9120 is as follows (1 being highest): 1. Output forcing (AO) 2. External forcing (PID) 3. Off mode control (PID) DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 3

4 When all of the fire alarms have been cleared, you must reset the process from Alarm mode back into Monitor mode. To do this, use the Fire Operator Workstation (Fire OWS) to command the manual reset input to On. All of the objects for the rooftop unit, including the local sonalert, automatically receive a release priority command. Command the manual reset to Off using the Fire OWS. The warehouse is purged because the supply fan is Off and the exhaust fan is On, creating a negative pressure in the warehouse. Negative pressure in the warehouse also prevents the smoke from spreading to other areas. 4 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

5 Design Considerations Take the following design considerations into account when designing your system. In addition, refer to the Smoke Control Technical Bulletin (LIT ) in this manual. You can find instructions and guidelines for using the GX-9100 software tool in the GX-9100 Software Configuration Tool for Windows (LIT ) document of the System 9100 Technical Manual (FAN 636.4). You can find important instructions and guidelines for using this application in How to Use the Metasys Smoke Control Library (LIT ), located in the Smoke Control section of this manual. For information on the definition and the initial configuration of the program and Programmable Logic Controller (PLC) modules, use the GX-9100 software tool to examine this configuration. You must define system and object names for all objects. The process runs once per second, which is the DX-9100/9120 scan rate. You must define the hardware location for each object. This automatic smoke control application does not provide a manual override. Overrides are available from an operator at the Fire OWS or at the FSCS. Most rooftop units have a purge function used when the cooling or heating system ends its On cycle. This should not be confused with a smoke control purge process or used as such. You can simply reset from Alarm mode back to Monitor mode without running purge. An alarm will occur if the command does not equal the condition for any controlled device output, including smoke dampers. Each Binary Output (BO) object for pressurization and exhaust outputs must be configured to have its own feedback (proof sensor) input. The BO s alarm attribute will indicate when command does not equal condition. The alarm attribute must be used in other applications, such as initiating the local sonalert application. For smoke dampers, there must be a positive indication of the damper s fully opened position and its fully closed position. DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 5

6 Each BO object has an alarm number. Use the Report Router/Alarm Management feature to create alarm messages, and link the alarm messages to alarm numbers. For example, the alarm message may read: Alarm Number 1 - Feedback does not match the command sent to the Binary Output Obj. This application, as it exists in the GX-9100 Smoke Control Library, complies with the UL 864 UUKL Smoke Control Listing. However, you are responsible for ensuring that the Fire OWS point interface as outlined is included. Also, the application must comply with state and local regulations and be approved by the Authority Having Jurisdiction (AHJ). For UL compliance: The Fire OWS reports critical alarms based on the alarm condition, and the alarm can only be cleared by resetting from the Fire OWS or the FSCS (Firefighter s Smoke Control Station). If the DIs are used for smoke control then DI1 must be jumpered and mapped to the Fire OWS as a normal state of On. When DI1 is off, a critical alarm must be issued at both the printer and the terminal. This indicates a binary input fuse failure that must be fixed immediately, because the DI is no longer accurate. If the AOs are used for smoke control then Analog Output 1 (AO1, voltage) must be wired to Analog Input 1 (AI1, voltage) and the AI must be mapped to the Fire OWS with a low alarm limit of 20%. When the AI goes below this, it indicates that the AOs failed because of a blown fuse, which drops the AO to 0V and the AI to 0% (low alarm). The DX-9100/9120 is downloaded so that the AO is normally at 5V because its source point is an Analog Constant (ACO) with a default of 50. Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) 6 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

7 To maintain UL 864 UUKL Smoke Control Listing, you must connect a printer model number PRN-3 or PRN-4 to the Fire OWS or directly to the Fire Network Control Module (NCM). For printer installation, refer to the manual included with the printer. Also, configure the Report Router/Alarm Management feature to route your alarm messages to the printer. For specific wiring requirements, refer to Metasys Smoke Control Wiring Technical Bulletin (LIT ). DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 7

8 8 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

9 Application Details Main Function Location This application provides warehouse smoke exhaust and reset logic for a rooftop unit. During a fire alarm, this process controls a rooftop unit to minimize the spread of smoke. The Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit application is located under the Fire/Security/ILC Conference of the Engineering Services Bulletin Board (BBS). Once logged on the BBS, you can download the file to your computer. The application is also located on the Advisor. Follow the path Offices>SystemServicesMilwaukee>EngineeringServices>Fire&Security. Graphic Representation layo ut Figure 1: GX-9100 Graphic Layout DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 9

10 Point List Table 1: Hardware I/O Requirements Input Requirements Hardware Name of Location Module Engineer Units Req? Description AI1 FUSE3 % Yes Monitor AO Fuse DI1 FUSE5 ALA/NOR Yes DI Fuse Monitor DI2 Alarm NOR/ALA Yes Smoke/Fire Alarm DI3 SFAN_FB OFF/ON Yes Supply Fan Feedback DI4 EFAN_FB OFF/ON Yes Exhaust Fan Feedback DI5 ODA_CLO OPN/CLO Yes Outdoor Air Damper Feedback DI6 RET_CLO OPN/CLO Yes Return Air Damper Feedback Output Requirements Hardware Name of Location Module Engineer Units Req? Description AO1 FUSE3 % OPN Yes Monitor AO Fuse AO9 ODA_DPRS % OPN Yes Outside Air Dampers AO10 RET_DPRS % OPN Yes Return Air Dampers AO11 INLT_VN OFF/ON Yes Inlet Vanes DO3 SFANSS OFF/ON Yes RU Supply Fan Start/Stop DO4 EFANSS Yes Exhaust Fan Start/Stop Table 2: Software I/O Requirements Hardware Location Name of Point Engineer Units Req? Description DCO1 OWS_RST OFF/ON Yes Manual Reset ACO6 FUSE % Yes Setpoint to Maintain 5V LRS1 OUT_FRC NOR/FRC Yes Shutdown Rooftop Unit LRS2 SFAN_CTL OFF/ON Yes SFAN Control LRS3 EFAN_CTL OFF/ON Yes EFAN Control LRS9 SFANALM NOR/ALA Yes Supply Fan Alarm LRS10 EFANALM NOR/ALA Yes Exhaust Fan Alarm LRS11 ODA_ALM NOR/ALA Yes Outdoor Air Damper Alarm LRS12 RET_ALM NOR/ALA Yes Return Air Damper Alarm TS1OUT OCCD UNO/OCC Yes Occupied Control Time Schedule 10 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

11 GX-9100 Printouts Table 3: PID1 Data PID (PID1) - Data User Name :HEATING Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level Local Set Pt.(LSP) Ena Startup: 0=N 0 Proport. Band(PB) Startup Out Level Reset Action(TI) Ena Symm Mode: 0=N 0 Rate Action(TD) ExtForce Out Level Standby Bias(BSB) Ena PID to P: 0=N 0 Off Mode Bias(BOF) Remote Mode: 0=N 0 Symmetry Band(SBC) Ena OFF Trans: 0=N 0 Err Deadband(EDB) Process Variable --> HTG_PV Output Bias(OB) Remote Setpoint --> Out High Lmt(HIL) Reference Variable--> Out Low Lmt(LOL) Proportional Band --> Dev H.H.Limit(DHH) OFF Mode Control --> /SFANSS Dev High Limit(DH) Standby Control --> Dev Low Limit(DL) Reverse Action --> Dev L.L.Limit(DLL) External Forcing --> OUT_FRC Minimum WSP(MNWS) Output Bias --> Maximum WSP(MXWS) Minimum WSP --> Table 4: PID2 Data PID (PID2) - Data User Name :COOLING Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level Local Set Pt.(LSP) Ena Startup: 0=N 0 Proport. Band(PB) Startup Out Level Reset Action(TI) Ena Symm Mode: 0=N 0 Rate Action(TD) ExtForce Out Level Standby Bias(BSB) Ena PID to P: 0=N 0 Off Mode Bias(BOF) Remote Mode: 0=N 0 Symmetry Band(SBC) Ena OFF Trans: 0=N 0 Err Deadband(EDB) Process Variable --> CLG_PV Output Bias(OB) Remote Setpoint --> Out High Lmt(HIL) Reference Variable--> Out Low Lmt(LOL) Proportional Band --> Dev H.H.Limit(DHH) OFF Mode Control --> /SFANSS Dev High Limit(DH) Standby Control --> Dev Low Limit(DL) Reverse Action --> Dev L.L.Limit(DLL) External Forcing --> OUT_FRC Minimum WSP(MNWS) Output Bias --> Maximum WSP(MXWS) Minimum WSP --> DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 11

12 Table 5: PID3 Data PID (PID3) - Data User Name :RET DMPR Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level Local Set Pt.(LSP) Ena Startup: 0=N 0 Proport. Band(PB) Startup Out Level Reset Action(TI) Ena Symm Mode: 0=N 0 Rate Action(TD) ExtForce Out Level Standby Bias(BSB) Ena PID to P: 0=N 0 Off Mode Bias(BOF) Remote Mode: 0=N 0 Symmetry Band(SBC) Ena OFF Trans: 0=N 0 Err Deadband(EDB) Process Variable --> RDMPR_PV Output Bias(OB) Remote Setpoint --> Out High Lmt(HIL) Reference Variable--> Out Low Lmt(LOL) Proportional Band --> Dev H.H.Limit(DHH) OFF Mode Control --> Dev High Limit(DH) Standby Control --> Dev Low Limit(DL) Reverse Action --> Dev L.L.Limit(DLL) External Forcing --> /SFANSS Minimum WSP(MNWS) Output Bias --> Maximum WSP(MXWS) Minimum WSP --> Table 6: PID4 Data PID (PID4) - Data User Name :FAN CTRL Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level Local Set Pt.(LSP) Ena Startup: 0=N 0 Proport. Band(PB) Startup Out Level Reset Action(TI) Ena Symm Mode: 0=N 0 Rate Action(TD) ExtForce Out Level Standby Bias(BSB) Ena PID to P: 0=N 0 Off Mode Bias(BOF) Remote Mode: 0=N 0 Symmetry Band(SBC) Ena OFF Trans: 0=N 0 Err Deadband(EDB) Process Variable --> VANE_PV Output Bias(OB) Remote Setpoint --> Out High Lmt(HIL) Reference Variable--> Out Low Lmt(LOL) Proportional Band --> Dev H.H.Limit(DHH) OFF Mode Control --> Dev High Limit(DH) Standby Control --> Dev Low Limit(DL) Reverse Action --> Dev L.L.Limit(DLL) External Forcing --> /SFANSS Minimum WSP(MNWS) Output Bias --> Maximum WSP(MXWS) Minimum WSP --> 12 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

13 Table 7: PID5 Data PID (PID5) - Data User Name :OA DMPR Description : Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level Local Set Pt.(LSP) Ena Startup: 0=N 0 Proport. Band(PB) Startup Out Level Reset Action(TI) Ena Symm Mode: 0=N 0 Rate Action(TD) ExtForce Out Level Standby Bias(BSB) Ena PID to P: 0=N 0 Off Mode Bias(BOF) Remote Mode: 0=N 0 Symmetry Band(SBC) Ena OFF Trans: 0=N 0 Err Deadband(EDB) Process Variable --> ODMPR_PV Output Bias(OB) Remote Setpoint --> Out High Lmt(HIL) Reference Variable--> Out Low Lmt(LOL) Proportional Band --> Dev H.H.Limit(DHH) OFF Mode Control --> Dev High Limit(DH) Standby Control --> Dev Low Limit(DL) Reverse Action --> Dev L.L.Limit(DLL) External Forcing --> /SFANSS Minimum WSP(MNWS) Output Bias --> Maximum WSP(MXWS) Minimum WSP --> DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 13

14 Table 8: Timer 6 Data TIMER (TIMER6) - Data User Name :HDW_ALMS Description :Hardware Alarms TIMER #1 TYPE 4 TIMER #5 TYPE 4 Input Connection #1--> SFANSS Input Connection #5--> OUT_FRC Reset Connection #1--> SFAN_FB Reset Connection #5--> ODA_CLO Time Period # Time Period # Time Units #1 0 Time Units #5 0 TIMER #2 TYPE 4 TIMER #6 TYPE 4 Input Connection #2--> /SFANSS Input Connection #6--> OUT_FRC Reset Connection #2--> /SFAN_FB Reset Connection #6--> RET_CLO Time Period # Time Period # Time Units #2 0 Time Units #6 0 TIMER #3 TYPE 4 TIMER #7 TYPE 0 Input Connection #3--> EFANSS Input Connection #7--> Reset Connection #3--> EFAN-FB Reset Connection #7--> Time Period # Time Period # Time Units #3 0 Time Units #7 0 TIMER #4 TYPE 4 TIMER #8 TYPE 0 Input Connection #4--> /EFANSS Input Connection #8--> Reset Connection #4--> /EFAN_FB Reset Connection #8--> Time Period # Time Period # Time Units #4 0 Time Units #8 0 This module will indicate a failure condition if the commanded condition and feedback of the fans and dampers do not match. 14 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

15 Table 9: TS1 Data TIME SCHEDULE (TS1) - Data User Name :OCCUPIED Description : External Extension --> Stop Time Event #4 0:0 External Forcing ON--> Days for Event #4 0 External Forcing OFF--> Start Time Event #5 0:0 Extension Time Stop Time Event #5 0:0 Start Time Event #1 8:00 Days for Event #5 Stop Time Event #1 17:00 Start Time Event #6 0:0 Days for Event #1 9 Stop Time Event #6 0:0 Start Time Event #2 0:0 Days for Event #6 Stop Time Event #2 0:0 Start Time Event #7 0:0 Days for Event #2 0 Stop Time Event #7 0:0 Start Time Event #3 0:0 Days for Event #7 Stop Time Event #3 0:0 Start Time Event #8 0:0 Days for Event #3 0 Stop Time Event #8 0:0 Start Time Event #4 0:0 Days for Event #8 Table 10: AO9 Data ANALOG OUT (AO9) - Data User Name :ODA_DPRS Description :Outside Air Dampers Type of Output 1 Low Range Source Point --> PM5OCM High Limit (%) Output Forcing --> OUT_FRC Low Limit (%) Enable Limits --> Forcing Level (%) Increase Source --> Hold on Powerup(0=N) 0 Decrease Source --> Auto on Powerup(0=N) 0 High Range Table 11: AO10 Data ANALOG OUT (AO10) - Data User Name :RET_DPRS Description :Return Air Dampers Type of Output 1 Low Range Source Point --> PM3OCM High Limit (%) Output Forcing --> OUT_FRC Low Limit (%) Enable Limits --> Forcing Level (%) Increase Source --> Hold on Powerup(0=N) 0 Decrease Source --> Auto on Powerup(0=N) 0 High Range DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 15

16 Table 12: AO11 Data ANALOG OUT (AO11) - Data User Name :INLT_VN Description :Inlet Vanes Type of Output 1 Low Range Source Point --> PM4OCM High Limit (%) Output Forcing --> OUT_FRC Low Limit (%) Enable Limits --> Forcing Level (%) Increase Source --> Hold on Powerup(0=N) 0 Decrease Source --> Auto on Powerup(0=N) 0 High Range Table 13: DO3 Data ON/OFF (DO3) - Data User Name :SFANSS Description :RU Supply Fan Start/Stop Source Point --> SFAN_CTL Table 14: DO4 Data ON/OFF (DO4) - Data User Name :EFANSS Description :Exhaust Fan Start/Stop Source Point --> /EFAN_CTL 16 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

17 Logic Module Ladder Diagram - PLC1 User Name :Override Description: A larm L OUT_FRC SET OW S_RST L A larm OUT_FRC RST Occd L OUT_FRC SFAN_CTL ( ) Alarm L Occd OUT_FRC EFAN_CTL ( ) Alarm L Occd wareplc1 Figure 2: Logic Module Ladder Diagram - PLC1 Figure 2 shows the logic module ladder diagram for PLC1. If the alarm is On, the logic shuts down the HVAC equipment and turns on the exhaust fan during occupied and unoccupied modes. If reset is turned on from the Fire OWS and the alarm is Off, the release override goes back to normal HVAC control. If occupied normal control is On, the logic starts the supply fan and the exhaust fan. If occupied normal control is Off, the logic stops the supply fan and the exhaust fan. DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 17

18 SFANALON L SFANALOF OUT_FRC Logic Module Ladder Diagram - PLC2 User Name : FB_ALMS Description: Feedback Alarms LRS9 ( ) EFANALON L EFANALOF OUT_FRC LRS10 ( ) ODA_ALM L RET_ALM L OUT_FRC OUT_FRC LRS11 ( ) LRS12 ( ) wareplc2 Figure 3: Logic Module Ladder Diagram - PLC2 PLC2 checks for a hardware alarm condition. If there is a fire alarm and the fans do not operate properly, or the dampers do not go to 0%, an alarm is generated. Map the LRS points to Metasys with a normal condition of Off. Variations This program is set up as normal HVAC control with the process variables used as ACOs sent through the Fire OWS. The main supply fan is started based on a DX time schedule and operates in standalone mode. 18 DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

19 Notes DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit 19

20 Notes Controls Group FAN E. Michigan Street Metasys Network Technical Manual P.O. Box 423 Printed in U.S.A. Milwaukee, WI DX-9100/9120 Applications--DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Introduction

More information

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT-1201736 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

DX-9100/9120 Local Sonalert Logic

DX-9100/9120 Local Sonalert Logic Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPICATION NOTE DX-9100/9120 ocal Sonalert ogic Introduction Page 3 Application Description *3 Design

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLATN NTE Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit ntroduction Page 3 Application Description

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLCATN NT Multi-Story Building Floor Above/Floor Below Pressurization and xhaust Logic ntroduction Page 3

More information

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT-1201754 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units... Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

Fire Operator Workstation (Fire OWS) User s Guide

Fire Operator Workstation (Fire OWS) User s Guide Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43 Metasys etwork Technical Manual 636 Objects Section Technical Bulletin Issue Date 696 Fire System Objects Introduction Page *3 Description *3 Purpose *5 Capabilities *7 Functional Diagram *1 Operator Interface

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Metasys Integrator Cleaver-Brooks Application

Metasys Integrator Cleaver-Brooks Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details

More information

Metasys Integrator Compu-Aire Application

Metasys Integrator Compu-Aire Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 Application Note 140-1042 Building Technologies Table of Contents Overview... 4 Hardware

More information

DACC - NMDA BUILDINGS

DACC - NMDA BUILDINGS A PROJECT FOR: LAS CRUCES, NEW MEXICO PROJECT LOCATION LOCATION MAP INDEX OF DRAWINGS: CV001 - COVER SHEET M101 - OVERALL CAMPUS STEAM UTILITY PLAN M102 - DACC DAMA 341 PLAN M103 - DACC LRC & CLASSROOM

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front

More information

Solution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview

Solution Guide. UUKL Smoke Control System.  1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview Solution Guide UL 864, 9th Edition, UUKL Smoke Control Listing Overview Applications Distech Controls UUKL smoke control system can be used for: Dedicated smoke control applications: Used exclusively for

More information

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

TEC210x-2 Series Networked Thermostats

TEC210x-2 Series Networked Thermostats Product Bulletin Issue Date February 1, 2005 TEC210x-2 Series Networked Thermostats The TEC210x-2 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12011781 Software Release 3.12 Issued June 20, 2013 Supersedes April 20, 2012 Refer to the QuickLIT Web site for the most up-to-date version

More information

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application 2273 Application Note 140-1045 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

Metasys System Extended Architecture Smoke Control System

Metasys System Extended Architecture Smoke Control System Metasys System Extended Architecture Smoke Control System Technical Bulletin MS-NAE5510-0U Code No. LIT-1201684 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...

More information

Multistate Alarm. Introduction

Multistate Alarm. Introduction Object Dictionary 1 Multistate Alarm Introduction The Multistate Alarm object adds the alarming capability for a Boolean or multistate attribute for any object, such as the Present Value of a Binary Input

More information

TEC2100 Series Networked Thermostats

TEC2100 Series Networked Thermostats Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

BACnet Points List for Single Compressor Water to Water PROSSWWE-01 The network variables will be listed by point type instance convention. 2:1 would mean point type 2, point instance 1. All volatile (Output) type points will revert to the uncommanded values after a power

More information

Johnson Controls Fan Coil Units and Direct Digital Controls

Johnson Controls Fan Coil Units and Direct Digital Controls Product Bulletin Issue Date August 12, 2005 Johnson Controls Fan Coil Units and Direct Digital Controls This offering includes Johnson Controls fan coil units with a factory-installed Johnson Controls

More information

Feature Summary. I. System

Feature Summary. I. System I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in

More information

Using the Room View Window

Using the Room View Window CIT5 User s Guide 4-1 Chapter 4 Introduction The Room View window uses a tabbed display to present the information about one selected room. This chapter describes the tabs and features of the Room View

More information

Natural Ventilation Controller with 24vDC drive NVC-1204

Natural Ventilation Controller with 24vDC drive NVC-1204 Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-036 08/11 FEATURES > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) > 3 x 0-10V outputs

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

1.0 Digital Controller

1.0 Digital Controller 1.0 Digital Controller...1 1.1 Display Function Keys...1 1.2 Thermostat Display...2 1.3 Controller hardware input output points... 4 2.0 Sequence of Operation...5 2.1 States of Operation...5 2.2 Modes

More information

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 2 OCCUPIED MODE: When the program control source calls for

More information

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application 2050 Application Note 140-1136 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware Outputs...

More information

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH, SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS Options AG3 Unit-Mounted Ductstat Options AG15, AG16 A = Ductstat Temperature Module P/N 115848 B = Stage Adder Module, P/N 115849 (quantity varies

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-537-01 1/9/2018 Verify that you have the most current version of this document

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

Introduction. Introduction

Introduction. Introduction M-Alarm User s Guide 1-1 Chapter 1 Introduction Introduction M-Alarm allows the user to view, store, and manipulate current alarms received by N1 or BACnet Object Linking and Embedding (OLE) for Process

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification SCC Inc. LMV51 Control Product Description February 7, 2017 The LMV51 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

American University Design Standards

American University Design Standards 25 95 00 CONTROL SEQUENCES FOR HVAC PART 1. GENERAL 1.01 SECTION INCLUDES A. Description of Work B. Control Sequences General Requirements C. System Specific Control Sequences 1.02 RELATED DOCUMENTS A.

More information

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 422 - Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12012141 Software Release 3.14 SP1 Issued June 23, 2017 The Johnson Controls P2000 Security Management System supports the integration

More information

TEC1100 Series Thermostats

TEC1100 Series Thermostats Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0601 TEC1100 Series Thermostats TEC1100 is a series of non-programmable thermostats with a

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Product Bulletin T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4, T601DFH-4+PIR, T602DFH-4+PIR,

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

DCS2000 DEMENTIA CARE SYSTEM USER GUIDE. For Software Version 1.2 1

DCS2000 DEMENTIA CARE SYSTEM USER GUIDE. For Software Version 1.2 1 DCS2000 DEMENTIA CARE SYSTEM USER GUIDE For Software Version 1.2 1 Contents 1. INTRODUCTION...3 2. TYPICAL ROOM LAYOUT...4 3. DCS 2000 CONTROL PANEL...5 4. ON / OFF...6 5. SELECTING PROFILES...7 6. STATUS

More information

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs TEC2620 Series Non-Programmable Fan Coil Network Thermostat ler and Remote I/O Relay Packs TEC2620H-0, TEC2620C-0, TEC2620H-0+PIR, TEC2620C-0+PIR, TEC2621H-0, TEC2621C-0, TEC2621H-0+PIR, TEC2621C-0+PIR

More information

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2. VCB-X Modular Service Tool Technical Guide VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.0 and up Table of Contents INTRODUCTION... 3 Modular Service Tool...3 SYSTEM

More information

ACT2-CS Convenience Store Controller

ACT2-CS Convenience Store Controller Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,

More information

ZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until

More information

Wiring Diagrams. NOTE: This literature applies to units produced after 11/3/96 (software version 2.0 or greater) DIAGRAM INDEX

Wiring Diagrams. NOTE: This literature applies to units produced after 11/3/96 (software version 2.0 or greater) DIAGRAM INDEX 48/50EJ,EK,EW,EY024-068 50EJQ,EWQ024,028 Gas Heating/Electric Cooling Electric Cooling and Heat Pump Units (50/60 Hz) Wiring Diagrams NOTE: This literature applies to units produced after 11/3/96 (software

More information

Ei600ZW Z-Wave Module for 10 Year Smoke Sensor with Siren

Ei600ZW Z-Wave Module for 10 Year Smoke Sensor with Siren Ei600ZW Z-Wave Module for 10 Year Smoke Sensor with Siren Quick Start This device is a combination of a Z-Wave sensor (smoke sensor) and a Z-Wave actuator. Pressing the button 'Inclusion Button' for one

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Natural Ventilation Controller with 24vDC drive NVC-1204

Natural Ventilation Controller with 24vDC drive NVC-1204 Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-038 08/16 FEATURES SPECIFICATION > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) >

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS. CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS Table of Contents 2.A.1 SCADA Standards 2.5-2 2.A.1.1 Generators 2.5-2 2.A.1.2 Building

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

TEC Networked Multi-Stage Economizer Thermostat

TEC Networked Multi-Stage Economizer Thermostat Installation Instructions Issue Date January 19, 2005 TEC2104-2 Networked Multi-Stage Economizer Thermostat Application The TEC2104-2 thermostat is an N2 networked thermostat that provides control of single-

More information

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical MS4PMUHVT Issue Date 09/30/02 MS4PMUHVT Multi-Stage Electronic Control with Relay Pack The MS4PMUHVT Multi-Stage Electronic Control is intended for multi-stage temperature control applications.

More information

INTELLIGENT FIRE ALARM CONTROL PANEL

INTELLIGENT FIRE ALARM CONTROL PANEL INTELLIGENT FIRE ALARM CONTROL PANEL FX-2000 SERIES Description Mircom s FX-2000 Series Intelligent Analog Fire Alarm Control Panel is designed to provide maximum flexibility of analog system requirements

More information

Applications i.cas typical application is control of compressed air systems. It eliminates energy waste, provides state of the art compressor sequencing, load matching, independent user zones with isolation

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 SEQUENCE OF OPERATION The ALC controller is turned on

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

Spartan Peripheral Devices. TE 256S Thermostat Applications

Spartan Peripheral Devices. TE 256S Thermostat Applications Spartan Peripheral Devices TE 256S Thermostat Applications Revision 1.0 TE 256S modulating Proportional plus Integral controller is specifically designed to control heating and cooling with 6 port modulating

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

i-vu CCN 4.0 Owner s Guide

i-vu CCN 4.0 Owner s Guide i-vu CCN 4.0 Owner s Guide CARRIER CORPORAION 2007 A member of the United echnologies Corporation family. Stock symbol UX. 11-808-377-01 07/07 able of Contents ACCESSING YOUR SYSEM... 3 YOUR SYSEM DEAILS...

More information

Metasys Integrator Vilter Application

Metasys Integrator Vilter Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 1294 APPLICATION NOTE Metasys Integrator Vilter Application lntroduction Page 3 Application Details *3

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information