SAFETY POLICY AND PROCEDURE MANUAL All Euramax Subsidiaries. Number F-2.0 Emergency Eyewash / Emergency Showers
|
|
- Arnold Shanon Bailey
- 6 years ago
- Views:
Transcription
1 Number F-2.0 Issued: 1/2009 Revised: 9/2013 Page 1 of PURPOSE: To minimize the risk of injury by providing emergency eyewash and/or emergency shower stations at all manufacturing facilities and to comply with ANSI #Z POLICY: All Euramax facilities shall have emergency eyewash stations. If the facility uses corrosive materials, emergency showers will also be provided. 3.0 RESPONSIBILITIES: A. It is the responsibility of the Facility Leader to ensure compliance with this procedure in its entirety. B. It is the responsibility of all Employees to follow the requirements of this procedure. 4.0 PROCEDURE: A. All employees will be trained along with a demonstration in the basic operation and use of emergency eyewash equipment and emergency showers (if applicable). This training will be conducted as part of a weekly safety meeting (see Procedure D-4.0: Weekly Safety Meetings) and in the New Hire Safety Orientation (see Procedure D-1.0: New Hire Safety Orientation). B. Eyewash stations will be located throughout all facilities and shall be accessible within 10 seconds of any workstation. C. Emergency showers (if applicable) will be located throughout all facilities and be accessible within 10 seconds of any workstations using hazardous chemicals and/or corrosive materials. The path from the workstation to the emergency shower must be unobstructed. D. Eyewash stations and emergency showers must be clearly identified using a pictogram sign. E. Eyewash must be accessible with unobstructed pathways. A no storage zone (3 x3 ) must be marked on the floor. All eyewash stations must be at least 6 from the wall and 33 to 45 above the ground.
2 Number F-2.0 Issued: 1/2009 Revised: 9/2013 Page 2 of 3 F. Plumbed eyewash stations and emergency showers must be tested and inspected each week by a member of the Safety Committee (see Procedure E-1.0: Plant Safety Committees). Weekly inspections must be posted and documented at the station (see Weekly Eyewash/Emergency Shower Inspection Form). Portable (non-plumbed) eyewash stations and emergency showers must be visually inspected each month by a member of the Safety Committee (see Procedure E-1.0: Plant Safety Committee). Monthly inspections must be posted and documented at the station (see Monthly Eyewash/Emergency Shower Inspection Form). G. The test and inspection of eyewash stations and emergency shower(s) must include: 1. Ensure access to the station/shower(s) is unobstructed and a no storage zone (3 x3 ) is marked on the floor 2. Ensure the station is clean with dust covers to protect the unit 3. Ensure eyewash protection caps are intact and working properly 4. Ensure that a five (5) gallon bucket with a hose is attached, if no drain is available 5. Ensure the station functions properly for at least 45 seconds 6. Ensure that the solution additive is not expired / will not expire in the next 30 days and is at the correct level (after testing) 7. Water and additive must be changed every six (6) months for gravity fed units H. If an emergency eyewash or emergency shower must be used, a minimum 15- minute eye flushing or body rinse must be performed. I. Employees failing to comply with this procedure will be disciplined in accordance with normal progressive disciplinary procedures for the facility. 5.0 ATTACHMENT / FORMS: A. Weekly Eyewash / Emergency Shower Inspection Form B. Monthly Eyewash / Emergency Shower Inspection Form
3 Number F-2.0 Issued: 1/2009 Revised: 9/2013 Page 3 of PROCEDURE HISTORY: Original Issue 1/2009 Reviewed and Updated 7/2010 Reviewed and Updated 9/2013
4 WEEKLY EYEWASH / EMERGENCY SHOWER INSPECTION Number F-2.0 Issued: 1/2009 Revised: 9/2013 Page 1 of 1 Facility / Location Year EMERGENCY EYEWASH STATION / EMERGENCY SHOWER (Circle One) For use with Plumbed Stations This station was inspected and tested in accordance with Procedure F-2.0 SOLUTION / WEEK ADDITIVE DATE PASSED FAILED EXPIRATION DATE INSPECTED BY DATE This form should be posted at the Eyewash/Emergency Shower Station for the entire year
5 MONTHLY EYEWASH / EMERGENCY SHOWER INSPECTION Number F-2.0 Issued: 1/2009 Revised: 9/2013 Page 1 of 1 Facility / Location Year EMERGENCY EYEWASH STATION / EMERGENCY SHOWER (Circle One) For use with Portable/Non-Plumbed Stations This station was inspected and tested in accordance with Procedure F-2.0 SOLUTION / ADDITIVE MONTH PASSED FAILED EXPIRATION DATE INSPECTED BY DATE January February March April May June July August September October November December This form should be posted at the Eyewash/Emergency Shower Station for the entire year
C. EWFs shall deliver the quality and quantity of water that is satisfactory for emergency washing purposes.
22 45 00 PART 1 - GENERAL 1.01 SCOPE A. Emergency Washing Facilities (EWFs) shall be readily available in the immediate work area for employees, students and visitors who may be at risk for exposure to
More informationUniversity of California, Davis Laboratory Self-Inspection Checklist
University of California, Davis Laboratory Self-Inspection Checklist Principal Investigator/Laboratory Supervisor: Laboratories Reviewed: Date: Reviewer: Revised 11/2014 I. SAFETY PROGRAM ADMINISTRATON
More informationModel 7501/7501T/7501TH/7501T240/7501T240H Portable Eyewash/Portable Eyewash with Heater
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS No. 2080045(15) Model 7501/7501T/7501TH/7501T240/7501T240H Portable Eyewash/Portable Eyewash with Heater NOTE TO INSTALLER: Please leave this information
More informationEMERGENCY EYEWASH AND SHOWER TECHNOLOGY
EMERGENCY EYEWASH AND SHOWER TECHNOLOGY We are proud to present the Guardian range of Emergency Shower and Eyewash Equipment. A premium range of products that has been manufactured in the US for 30 years,
More informationContents. Eye/Face Washes... 3 Eyewashes... 3 Swing-Away Eyewashes... 4 Eyewash/Drench Hose Units... 4 Emergency Showers... 4 Safety Stations...
Contents Eye/Face Washes... 3 Eyewashes... 3 Swing-Away Eyewashes... 4 Eyewash/Drench Hose Units... 4 Emergency Showers... 4 Safety Stations... 5 Portable Eyewashes... 5 Faucet Mounted Eyewashes... 6 Barrier-Free
More informationROCKAWAY BOARDWALK Community Board 14 Parks Committee Meeting June 4, 2014
ROCKAWAY BOARDWALK Community Board 14 Parks Committee Meeting June 4, 2014 Introduction 2 Agenda Design Update Construction Update Local Hiring Update 3 Community Input 7 Meeting Date September 17, 2013
More informationSPEAKMAN GRAVITYFLO PORTABLE EYEWASH SE-4000
SPEAKMAN GRAVITYFLO PORTABLE EYEWASH SE-4000 TM INSTALLATION AND OWNER S MANUAL C O N T E N T S I. Introduction II. Product Dimensions III. Installation IV. Operation in Emergency Situation V. Periodic
More informationSPEAKMAN GRAVITYFLO PORTABLE EYEWASH SE-4000
SPEAKMAN GRAVITYFLO PORTABLE EYEWASH SE-4000 TM INSTALLATION AND OWNER S MANUAL C O N T E N T S I. Introduction II. Product Dimensions III. Installation IV. Operation in Emergency Situation V. Periodic
More informationModel 7500EB Portable Eyewash with Heater
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS 1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424 E-mail: haws@hawsco.com website: www.hawsco.com Model 7500EB Portable Eyewash
More informationSAFETY SHOWERS AND EYEWASHES 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS
224500 SAFETY SHOWERS AND EYEWASHES Cornell s Design and Construction Standards provide mandatory design constraints and acceptable or required products for all construction at Cornell University. These
More information7000BT Eye/Face Washes
7000BT es Safety 8" x 10-3/4" universal emergency sign make the unit easily detected in an emergency. Test card to record weekly checks helps maintain the unit s best working quality. Flow Control Omni-Flo
More informationSMALL PASSENGER VESSEL LOG BOOK
SMALL PASSENGER VESSEL LOG BOOK DRILLS, TRAINING, TESTS, MAINTENANCE Vessel Name U.S. Coast Guard Sector Baltimore 2401 Hawkins Point Road Baltimore, MD 21286 (410) 576-2685 /2553 fax 24 Small Passenger
More informationWinthrop University Police Department. Daily Fire Log. Month of January, 2013
Month of January, 2013 Date Reported:01/16/2013 Time Reported:4:00 PM Incident #:N/A Lee Wicker Fire Drill Required scheduled fire drill. Complete Date Reported: 01/24/2013 Time Reported:1:40 PM Incident
More informationEmergency Showers & Eye Wash Stations
Emergency Showers & Eye Wash Stations Emergency Showers & Eye Wash Stations The Ultimate in Initial First Aid Treatment for chemical & burn injuries. Environmental and site safety solutions Features include:
More informationCompany Information. Location Map. Ryonan is: 60 minutes from Makati City. 60 minutes from Ninoy Aquino International Airport NAIA)
Company Information Location Map Ryonan is 60 minutes from Makati City 60 minutes from Ninoy Aquino International Airport NAIA) 90 minutes to Manila Bay MILESTONE Date of PEZA Registration December 20,
More informationChemical Science Lab High Risk Workspace Inspection Form
Chemical Science Lab High Risk Workspace Inspection Form 1. High Risk Chemical Science Lab Workspace College Pierre Elliot Trudeau Science Department (CPET-SCI) Kildonan East Collegaite Science Department
More informationLaboratory Information
Laboratory Information Lab Information Department Room number and function Principal investigator (PI) PI telephone number PI email address Lab Safety contact person Lab Safety contact telephone number
More informationRevised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*
1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system
More informationFACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)
FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH) Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT
More informationService Bulletin
Service Bulletin 14-063 November 20, 2014 ATB 00239-01113 REV1 (1411) Low Heat From the Driver s-side Vent Supersedes 14-063, dated November 1, 2014, to revise the information highlighted in yellow. AFFECTED
More informationValue Adds For all half page or larger advertisers. Product Spotlight for construction safety and foot protection advertisers. National Heart Month
January 2018 Ad close: 11/21/17 Materials due: 11/29/17 es Year in Review Construction Safety PPE:, Foot Protection IH: Chemical Safety/SDS Training: Disaster Preparedness Plus: Emergency Showers & Eyewash,
More informationSaskatchewan Piping Industry Joint Training Board January to October 2015 Training Schedule (Revised)
Saskatchewan Piping Industry Joint Training Board January to October 2015 Training Schedule (Revised) Basic Welding Weekend Classes December 13, 14, January 10, 11, 2015 CWB Recert January 9, 2015 Orientation
More informationDepartment Of Public Works: Internal Operations
Department Of Public Works: Internal Operations A Checklist There are over 800 municipalities in the Michigan Municipal League s Pool and Fund Programs. Most perform public works functions of one type
More informationEMERGENCY DRENCH SHOWER
EMERGENCY DRENCH SHOWER PRODUCT CODE S2200 Date: March 2014 Horizontally Mounted Emergency Shower, Stainless Steel Shower Head Model S2200 is a horizontally mounted emergency shower with a stainless steel
More informationCountywide Recycling and Disposal Facility Weekly Progress Report 08/22/08
Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08 This Weekly Progress Report is prepared by Countywide and submitted to the OEPA weekly by the close of business on each Friday.
More informationEyewash and Eye/Face Wash units that are either wall mounted or pedestal mounted. 7260B B 7270B
Eyewash & Eyewash and units that are either wall mounted or pedestal mounted. Choose from a safety green ABS plastic bowl resistant to damage from alkaline, salt solutions, most acids and sun damage, or
More informationWinthrop University Police Department. Daily Fire Log. Month of January, Incident #: Location: Incident Type: Synopsis: Disposition:
Month of January, 2018 Month of February, 2018 N/A 02/01/2018 02/01/2018 Phelps Hall Fire Alarm Activation 1:32 PM 1:32 PM Officer responded in reference to a fire alarm. The officer went to the second
More informationFire Inspection & Prevention Initiative. Fire Safety Plan Documentation Guide. Part 3 (of 3) Format Guide Edition. (December 5, 2014)
Fire Inspection & Prevention Initiative Fire Safety Plan Documentation Guide Part 3 (of 3) Format Guide 2012 Edition (December 5, 2014) FSP Documentation Guide - Part 3: Format Guide Fire Safety Plan Documentation
More informationCedar Fire Department Run Statistics and Analysis January 1 st December 31 st, 2013
Cedar Fire Department Run Statistics and Analysis January 1 st December 31 st, January 1 st December 31 th EMS/FIRE Total EMS Runs and Fire Runs Prepared by: Tim Johnson Organizational Chart of Statistics
More informationParts List. Modular Crescent Cuber. Models KMD-460MAH, MWH KMD-530MAH, MWH, MRH. hoshizakiamerica.com
Parts List Modular Crescent Cuber Models KMD-460MAH, MWH KMD-530MAH, MWH, MRH hoshizakiamerica.com Number: 71357 Issued: 11-19-2014 Revised: 11-28-2017 CONTENTS Auxiliary Codes... 3 Note About Ordering
More informationSanitation Checklist SANITATION CHECKLIST Month Year 1/9/2013. Inmate Living Areas Clean. Sewer Sys. Maint T.D.H. Inspection
Sanitation hecklist SANITATION HEKLIST Month Year Inmate Living Areas lean Sewer Sys. Maint T.D.H. Inspection A A leaning Equipement A Adequate Trash ans w/ lids Emptied Toilets and Sinks Inspected and
More informationWhy be an advocate for street trees?
Street Tree Care Why be an advocate for street trees? Urban stress Loss of green space Neglect Climate change storms Pests and diseases Asian Longhorn Beetle Gypsy Moth Dutch Elm Disease Oak Wilt Emerald
More informationSafety Manual: Emergency Response
Safety Manual: Emergency Response January, 2017 6.0 Emergency Preparedness Introduction This Chapter provides guidelines for dealing with Emergencies. Fires, no matter how small, must be reported to management
More informationWORKPAPER TITLE Overhead Loaders. WITNESS Garry G. Yee
Overhead Loaders Overhead Category Overhead Rate Loading Base Payroll Taxes 8.% Direct Vacation and Sick Time 6.89% Direct Benefits (non-balanced only).7% Direct Workers' Compensation.86% Direct Public
More informationHealth Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
More informationHonolulu Community College Health & Safety Inspection Checklist for Shops Tech I. Program: Conducted by: Date: Reference 29 CFR 1910.
Program: Conducted by: Date: Means of Egress/Escape Are exits provided to permit the prompt escape of occupants in case of fire or other emergency? Is every exit, way of approach, and way to travel from
More informationTR Shower Panel. Operating manual. Hygiene Equipment Designed for People. Serial Number:
Operating manual Serial Number: Registered at Medical Products Agency, Sweden, as a MD Class 1 product, MDD 93/42EEC. TR reserves the right to make design changes and/or improvements without notice. Always
More informationCBT LW MAINTENANCE GUIDE
CBT LW MAINTENANCE GUIDE PICTOGRAMS Each Signifier displayed here is specific to this User Manual. Menu Previous Advance Note Tip Example Powder Feeder Mixing Bowl Weigh Scale CBP Tanks Control Panel PSD
More informationWhole House Descaler Installation Instructions
Whole House Descaler Installation Instructions MODEL HF-SOFT Safe, effective scale prevention without the use of chemicals or salt. HF-SOFT DIRECTION OF FLOW 26" Shut-Off Valve 48" 5-Micron Pre-Filter
More informationLABORATORY INSPECTION CHECKLIST
LABORATORY INSPECTION CHECKLIST Date of Inspection: Conducted by: Department: Building/Room #: Principal Investigator: PI Present? Yes No Type of Inspection: Semi-Annual (scheduled) Complaint Follow Up
More informationRemi Mendoza City Planning Academy March 13, 2017
Remi Mendoza City Planning Academy March 13, 2017 1 What is the General Plan? The 2030 General Plan 5-Year Update (2035 General Plan) Questions and Answers 2 Guidebook for development and growth Required
More informationDevice Reprocessing Checklist Scoring Matrix 1=low 5=high
Measure Standard Q1 Q2 Q3 Q4 Point of Use Gross Debris Removed during & after procedure (use of water preferred) 5 Delicate instruments on top of heavy or separate 5 Devices contained & identified as biohazard
More informationEmergency Response Procedures
Individual Exposure Eye Wash 1. Flush eyes for 15 minutes 2. Seek medical Attention 3. Flush eyewash weekly and keep a record 4. Do not block the eyewash Safety Shower 1. Remove contaminated clothing 2.
More informationFACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS
FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS Presented by: Alise Howlett, Assoc. AIA,CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 FREQUENT PHYSICAL ENVIRONMENT
More informationTo-Do List for Rhododendron Year (October September)
To-Do List for Rhododendron Year (October September) October October is fall planting time. Select your favorite digging tool! Fall planting will result in a better root system developing over winter.
More informationAldine Independent School District Aldine Westfield Road Houston, Texas Phone (281)
Aldine Independent School District 14910 Aldine Westfield Road Houston, Texas 77032 Phone (281) 985-6265 Created on August 2007 ALDINE INDEPENDENT SCHOOL DISTRICT BUILDINGS AND PROPERTIES 14910 Aldine-Westfield
More informationNational Certificate in Fire and Rescue Services (Vegetation) (Level 3)
NZQF NQ Ref 0540 Version 5 Page 1 of 8 National Certificate in Fire and Rescue Services (Vegetation) (Level 3) Level 3 Credits 55 This qualification is expiring. The last date to meet the requirements
More informationCOUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION
COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION Document # GI-16 Page 1 of 7 Large Family Day Care Homes Large family day care homes are licensed for day
More informationSHOWER, EYEWASH & FACEWASH PRODUCTS
EYE/FACEWASH PARTS SERVICE KNOWLEDGE SELF- CONTAINED QUALITY INNOVATION SHOWER, EYEWASH & FACEWASH PRODUCTS PRICELIST 2017 Effective January 1 st, 2017 Issued November 17 th, 2016 LEADERS SOLUTIONS SHOWER
More informationMost Frequently Cited Serious Violations in General Industry 2016
29 CFR 1910 SUBPARTS Most Frequently Cited Serious Violations in General Industry 2016 HAZARD COMMUNICATION WRITTEN PROGRAM MACHINE GUARDS GENERAL HAZARD COMMUNICATION INFORMATION AND TRAINING LOCKOUT/TAGOUT
More informationSample Safety Inspection Checklist
INSPECTION HEALTH AND CHECKLIST SAFETY COMMITTEES 1 Sample Safety Workplace: Date: Inspected By: Each No answer may indicate a problem. Yes No FLOORS AND WALKWAYS Are walkways and stairways kept clear
More informationCuyamaca College Administrative Services
Follow-ups Thursday, July 22 1:00 PM Emergency Procedure Presentation a. Kits Sandi s Recommendations Purchase 3 more 54 gallon can on wheels, 1 for Health Services, 1 CDC and 1 for REBRAC Purchase 8 First
More informationFire/General Safety Review Program Key Performance Indicators Environmental Health and Safety
Fire/General Safety Review Program Key Performance Indicators Environmental Health and Safety Fire and CO Detection Systems Fire alarm pull station obstructed. Annunciation panel obstructed. Lack of approved
More informationWell Disinfection. Safety Concerns. Electrical. Chemical
Environmental Health Division P.O. Box 64975 St. Paul, Minnesota 55164-0975 651-201-4600 or 800-383-9808 www.health.state.mn.us/divs/eh/wells Well Disinfection This handout provides instructions for disinfecting
More informationSA gal, 6 min. Flush (Eng. inst.) 19 SAM gal, 6 min. Flush (Fr. inst.) 19
Flash Flood Portable self-contained eyewash station, clas sified as a personal (se condary) eyewash device, provides flexible emergency eyewash capability in economical systems. Includes a 1 gallon container
More information[Department Name- Division] [Building Name and Address] [Date or Revision Date]
[Department Name- Division] [Building Name and Address] [Date or Revision Date] **Note: This is a template. Each Fire Prevention Plan needs to be sitespecific and take into account all possible fire hazards
More informationSample Safety Inspection Checklist for Schools
INSPECTION Health and CHECKLIST Safety Committees 1 Sample Safety for Schools School: Date: Inspected By: Each No answer may indicate a problem. Floors and Walkways Are walkways and stairways kept clear
More informationNZQA Expiring unit standard 3397 version 4 Page 1 of 5. Convert an automotive air conditioning system from R-12 to R-134a
Page 1 of 5 Title Convert an automotive air conditioning system from R-12 to R-134a Level 3 Credits 2 Purpose This unit standard is for people in the automotive repair industry. People credited with this
More informationNEW GARDEN MAINTENANCE GUIDE. Enjoy a luscious garden with our simple month-by-month garden TLC guide
NEW GARDEN MAINTENANCE GUIDE Enjoy a luscious garden with our simple month-by-month garden TLC guide JANUARY When weather conditions are suitable, ensure that the soil is well aerated by spiking it regularly
More informationMartha s Vineyard Airport Water, Wastewater, Facilities Department Report
Martha s Vineyard Airport Water, Wastewater, Facilities Department Report 508-693-3783 October 2017 Water, Wastewater, Facilities Department Report from Michael Eldridge, Christina Colarusso and Jeremy
More informationSALAMA SAFETY SIGNS SALAMA SAFETY SIGNS SAFETY SIGNS PHOTOLUMINESCENT
R A Product of www.signindustries.co.tz Other manuals: TIME FOR A SIGN Designer Signs Logo designing, hints & tips 2 INDEX Index 1.0 Safety Signs and Colour at Work 1.1 Safety Sign Categories 1.2 Sign
More informationOBSERVATIONS AND RESPONSES
OBSERVATIONS AND RESPONSES 1- Some operating procedures were not kept up-to-date. OPERATING PROCEDURES 96 Item 6.4.2 of procedure PFN-00191 v.4 Leukodepletion Method (PCS) specified that, in the event
More informationGarver Feed Mill Timeline
Garver Feed Mill Timeline 1) 1989 Garver Feed Mill is designated as a CDA Redevelopment Project 2) 1991 Olbrich Botanical Gardens opens Bolz Conservatory, Schumacher Library, and associated buildings 3)
More informationScience Department Safety Training Notes
SCIENTIFIC Science Department Safety Training Notes Discussion and Notes Five-Minute Safety Inspection Our Five-Minute Safety Equipment Inspection can be used to quickly and easily evaluate the readiness
More informationTEMPERED WATER. Solutions for Safety Showers
TEMPERED WATER Solutions for Safety Showers A company with experience With more than 50 years of experience as a manufacturer of quality safety equipment, Encon has earned a reputation for providing reliable,
More informationPROVIDES TEPID WATER FOR EMERGENCY SHOWER
PROVIDES TEPID WATER FOR EMERGENCY SHOWER Model EMV FEATURES Heavy Duty Construction Hydrastone cement lining provides tank longevity Copper-silicon alloy tappings cannot rust or corrode High impact composite
More information8200 Combination Units
8200 Combination Units 1-1/4 Schedule 40 hot-dipped galvanized steel pipe and fittings along with powder-coated cast-iron 9 diameter floor flange provide corrosion resistance in a long lasting product.
More informationACTION PLAN. Recommendation: Continuity of Operations (COOP): Resources
ACTION PLAN Agency Name: Texas State University Agency Number: 754 Date of Visit: 11/03/2014 11/04/2014 SORM Risk Manager: Christine Wright Recommendation: 15-11-01 Continuity of Operations (COOP): Resources
More informationYear / Planting Season
Year / Planting Season 2013-2014 Allotment First Established: 2010 2012 / 2013: 21 Plots 24 Active members 2013 / 2014: 24 Plots 28 Active members (Not including number of schoolchildren & members children
More informationBar valve with fixed and adjustable shower heads. Installation guide. Midas Plus installation instructions Page 1
Midas Plus Bar valve with fixed and adjustable shower heads Installation guide Midas Plus installation instructions Page 1 Midas Plus Midas Plus installation instructions Page 2 Components Literature not
More informationOwasco Sewer District No. 3
Owasco Sewer District No. 3 Town of Owasco, Cayuga County Public Hearing October 4, 2014 and October 9, 2014 Town Supervisor - Ed Wagner Town Board Michael J. Aldrich Anthony Gucciardi Tim Kerstetter Richard
More informationCity of Deerfield Beach. Fire Rescue
City of Deerfield Beach Fire Rescue Fire Suppression Emergency Medical Services Life Safety Education Emergency Operation Coordination The City contracts fire rescue services with the Broward Sheriff s
More informationInstallation Instructions EQ-AST-WH & EQ-AST-WH-C. Whole House Water Filter
Installation Instructions EQ-AST-WH & EQ-AST-WH-C Whole House Water Filter Welcome to the Aquasana experience. You are about to enjoy clean, clear water and the peace of mind that comes from knowing award
More informationHARDWOOD INDUSTRY FACILITY & SAFETY INSPECTION CHECKLIST
Company: Inspection Completed By: Date: Administrative: 1. Written safety rules/safe job procedures in place 2. OSHA log updated/safety posters displayed 3. Management Safety Policy in place 4. All planned
More informationQuarterly Safety/Building Inspection Form
Date: Quarter: (Check one) Jan - March, April - June, July - September, Oct - Dec, Campus: Program Name/Building/Room Number: Inspector's Name: 3 4 5 Fire Safety and Emergency Equipment Are all fire extinguishers
More informationParts List. Refrigerated Kitchen Equipment Models Refrigerated Prep Table with Raised Rail. hoshizakiamerica.com
Parts List Refrigerated Kitchen Equipment Models Refrigerated Prep Table with Raised Rail hoshizakiamerica.com Number: 00 Issued: --009 Revised: 4--06 CONTENTS Auxiliary Codes... Auxiliary Code Breakdown...
More informationTitle: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015
Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015 Fire Protection I. INTRODUCTION II. GENERAL GUIDELINES III.
More informationProgrammatic Policy and Procedure
Page 1 of 6 Programmatic Policy and Procedure Section Sub-section Psychiatric Health Facility (PHF) Crisis and Emergency Response Effective: Version: Policy Emergency Subsistence Management Last Revised:
More information2016 Annual Inspection Report
2016 Annual Inspection Report for Compliance with the Coal Combustion Residuals Rule (40 CFR Part 257) Hayden Station 13125 U.S. Highway 40 Hayden, Colorado 81638 January 18, 2017 Table of Contents Certification...
More informationSECTION LABORATORY EQUIPMENT CONSTRUCTION STANDARD PART 1: GENERAL Scope of Standard
PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of the University of Texas at Austin for safety equipment used in or in support of
More informationPage 2 of 5. SOP SF SOP for Water Bath Maintenance
Page 2 of 5 4.1. The SOP applies to all SSF staff and is intended to outline maintenance, calibration, and documentation procedures used within the laboratory to ensure that water baths perform with reliable
More informationCourse Title: Introduction to Modeling and Design 774Z
Assessments/Resources Unit 2, October Unit 1, September What is my learning style? How do engineers and designers put their ideas into forms that can be understood by others? How is a tower designed and
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-002 EFFECTIVE 05-27-2009 PURPOSE: To define the requirements for a License. To facilitate the quick application and review of new or changed
More informationAQ150:Midas 10/9/15 14:50 Page 1 AQ150. Thermostatic bar mixer valve with adjustable head. Installation guide
AQ150:Midas 10/9/15 14:50 Page 1 AQ150 Thermostatic bar mixer valve with adjustable head Installation guide AQ150:Midas 10/9/15 14:50 Page 2 Important information Introduction The product is an exposed
More informationByrd Barr Place PSE HELP Program:
Byrd Barr Place PSE HELP Program: 2017-2018 Is My Household s Average Monthly Income at or Below the Following Amounts? Eligibility is based on the average monthly income my household received for the
More informationoptimal safety and security at the workplace International Organization for Standardization H A ISO BUFEAU VERITAS Certification
Certifiied ISO 9001 by ISO 14001 BUFEAU VERITAS Certification IN DESIGNED AND MANUFACTURED S O U T F H A RI C A International Organization for Standardization optimal safety and security at the workplace
More informationGUIDELINES TO SHOP COMPLIANCE
2017 - GUIDELINES TO SHOP COMPLIANCE Please file in your Black CRA Bulletin folder Company Name:... Address:... HEALTH & SAFETY POLICY The Health and Safety in Employment Act 1992 states that all businesses
More informationTRAINING BULLETIN TOOLS 1 May 27, 2011 PRESSURIZED WATER EXTINGUISHER
TRAINING BULLETIN TOOLS 1 May 27, 2011 1. DESCRIPTION Weight is approximately 30 lbs. Water 2½ gallons. Operating Pressure: 100 psi @ 70 degrees F. Note: Water expelled in 55 seconds. Stainless Steel Cylinder
More informationSCE170 SERVICE PARTS
This is the parts list for the SCE170. When looking up part numbers, always check the complete model and serial numbers to be certain of ordering the correct parts. The SCE170 has been manufactured in
More informationFRIDAY, NOVEMBER 23, WORKPLACE SAFETY AND HEALTH (APPROVED CODES OF PRACTICE) NOTIFICATION 2018
FRIDAY, NOVEMBER 23, 2018 1 First published in the Government Gazette, Electronic Edition, on 23 November 2018 at 5 pm. No. 3135 WORKPLACE SAFETY AND HEALTH (CHAPTER 354A) WORKPLACE SAFETY AND HEALTH (APPROVED
More informationWarehouse Operations Safety Inspection Checklist
An essential part of loss prevention is the recognition and removal or correction of hazards before a loss occurs. This checklist should serve as a tool, indicating those areas needing attention. This
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#58619/Page 1/November 1, 2017 PLUMBING Executive Summary: Presently, the Plumbing Systems serving the building are cold water, hot water, sanitary, waste and vent system, storm drain piping, and natural
More informationActivity Residential Site Planning
Activity 2.3.7 Residential Site Planning Introduction When a building is designed apart from a specific site, an opportunity is lost to match the design to the strengths and weaknesses of the site. To
More informationMemorandum Planning. Thursday, January 8, 2015
Memorandum Planning Thursday, January 8, 2015 7.A. To: Coastal Advisory Committee From John Ciampa, Associate Planner Subject: Review Draft Local Coastal Program Copies: James Pechous, City Planner Purpose
More informationThird Year Renewal of Three-Year Contract Bid # LR, Fire Extinguisher Service Maintenance Department Florida Fire Services, Inc.
Department of Purchasing 813/ 794-2222 Fax: 813/ 794-2111 727/ 774-2222 TDD: 813/ 794-2484 352/ 524-2222 e-mail: kgoodman@pasco.k12.fl.us December 12, 2007 MEMORANDUM TO: FROM: RE: Honorable School Board
More information60+ NEED-TO-KNOW APPLIANCE MAINTENANCE TIPS
0+ NEED-TO-KNOW APPLIANCE MAINTENANCE TIPS Routine maintenance is the best way to get the most out of your appliances. You probably know you should clean the lint filter every time you use the dryer and
More informationHIGHWAY DEPARTMENT: Planning and Programming Division: An Inventory of Its Transportation Planning Studies
MINNESOTA HISTORICAL SOCIETY Minnesota State Archives HIGHWAY DEPARTMENT: Planning and Programming Division: An Inventory of Its Transportation Planning Studies OVERVIEW OF THE RECORDS Agency: Minnesota.
More informationParts List. Stackable Crescent Cuber. Models KM-1601SAJ/3 KM-1601SWJ/3 KM-1601SRJ/3. hoshizakiamerica.com
Parts List Stackable Crescent Cuber Models KM-1601SAJ/3 KM-1601SWJ/3 KM-1601SRJ/3 hoshizakiamerica.com Number: 71375 Issued: 5-15-017 Revised: 10-3-018 CONTENTS Auxiliary Codes... 3 Note About Ordering
More informationAS/NZS :2015. Plumbing and drainage AS/NZS :2015. Part 4: Heated water services. Australian/New Zealand Standard
AS/NZS 3500.4:2015 Incorporating Amendment No. 1 Australian/New Zealand Standard Plumbing and drainage Part 4: Heated water services Superseding AS/NZS 3500.4:2003 AS/NZS 3500.4:2015 AS/NZS 3500.4:2015
More informationGlobal Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More information