ADEMCO LYNX XL SERIES Security System

Size: px
Start display at page:

Download "ADEMCO LYNX XL SERIES Security System"

Transcription

1 ADEMCO LYNX XL SERIES Security System LXL-1010 Installation and Setup Guide BETA DRAFT COPY 8/23/04 K /04 Rev. A

2 RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below. Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended. For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. In addition, we recommend the following: Install a smoke detector inside every bedroom where a smoker sleeps. Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed. DINING LIVING ROOM KITCHEN BEDROOM LVNG RM BASEMENT BEDROOM TO BR BEDROOM BEDROOM BEDROOM BEDROOM KTCHN. CLOSED DOOR TV ROOM BEDROOM GARAGE KITCHEN DINING BDRM LIVING ROOM BDRM Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors floor_plan-001-v0 Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or humidifiers) are used. Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long. Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion. THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES. Recommendations For Proper Intrusion Protection For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial premises. This would include any skylights that may be present, and the upper windows in a multi-level building. In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station). ii

3 Table of Contents Features and Installation Highlights About LYNX LXL Capabilities Zones Security Codes Downloading Functions Compatible Devices System Features Tamper Protection LED Indications Important Installation Highlights (Installer Please Read) Quick Start Installation Guide General Removing the Cover Selecting a Installation Site Connecting the Installer Keypad Program the LXL Quick Mode Programming Installer Keypad Functions Enter Quick Mode Programming SELECT DEAULTS Program a Default Table PRI PHONE Add Primary Phone Number PRI SUB ID Add Primary Sub ID Account Number SEC PHONE Add Secondary Phone Number SEC SUB ID Add Secondary Sub ID Account Number ADD SENSORS Add A Door Sensor To Add a Window, Motion, Fire, Glass Break, or Shock Sensor Add Emergency Sensor Add Keyfob DELETE SENSORS Delete Sensors EXPERT MODE Enter Expert Programming Mode Completing Programming Final Mounting Phone Line Connections Test the System Programming Overview About Programming Keypads Alpha Keypads: Fixed Glass Keypads: Wireless Programming Options Transmitters, and Wireless Keys (Keyfobs) Transmitters Wireless Keys Pager Programming Function Keys Output Devices (X-10) Quick Mode Programming Zone Type Definitions Mechanics of Programming iii

4 Table of Contents Installer Keypad Functions Data Field Programming Procedures Interactive Mode Programming (, *56, *57, *58, *79, *80, *81, *82) Loading Factory Defaults/Initializing for Download Exiting the Programming Mode Data Field Programming About Data Field Programming Programming Data Fields Zone Programming ( 56 and 58 Menu Modes) About Zone Programming Zone Programming Procedure Function Key Programming ( 57 Menu Mode) About Function Keys Output Device Programming ( 79 and 80 Menu Mode) About Device Programming Output Identification Output Definition Components Zone Lists ( 81) About Zone Lists (81 menu Mode) Alpha Descriptor Programming ( 82 Menu Mode) About Descriptor Programming Creating Schedules System Communication LXL-1010 and Dialer Communication with Central Station System Operation LED Indications System Security Codes Keypad Functions Voice Keypads Keypad Commands Panic Keys Setting the Real-Time Clock Testing LXL About Test Procedures System Test Checking Transmitter Enrollment (Sniffer Mode) Go/No Go Test Mode Dialer Communication Test and Periodic Test Reports Automatic Periodic Test Report Automatic Standby Battery Tests Specifications & Accessories iv

5 S E C T I O N 1 Features and Installation Highlights About LYNX LXL-1010 LYNX LXL-1010 is a compact security system featuring total wireless zone protection. Integral to the LXL-1010 control, requiring no installation action is the sounder and RF receiver/transmitter, and a digital communicator. LXL-1010 also contains a rechargeable battery that provides up to 24 hours of standby operation in the event of AC loss. The LXL control is mounted to a duplex receptacle and the only external interface is telephone wiring. Refer to Figure 1 for the LXL-1010 internal overview. COVER TAMPER SOUNDER SOUNDER JUMPER BATTERY RJ31 TELEPHONE JACK AUX TELEPHONE JACK RJ11 SECURITY SYSTEM CONTROL STATUS LEDs (3) INSTALLER KEYPAD PROGRAMMING CONNECTOR - + BATTERY CONNECTOR RF LED ANTENNA ANTENNA QM-041-V0 Figure 1. LXL-1010 Internal Overview Capabilities Zones Supports up to 32 wireless transmitter zones (5800 series; zones 1-32) plus 8 keyfob zones (zones 33-40) for total of 40 zones Security Codes Up to 32 Security Codes, each with separate authority levels Downloading Via an IBM compatible computer, Compass downloading software, and a compatible HAYES or ADEMCO CIA modem specified by Ademco. 1 1

6 LXL-1010 Installation and Setup Guide Functions Night Stay and step arming can be set on the keypad Single-button arming feature (on keypads or keyfobs): Can use dedicated keys to arm the system AWAY or STAY Up to 8 schedules, to control devices and/or auto-arm/disarm the system Up to two keypad macros, which can be activated by wireless keypads Paging feature allows certain system conditions to be reported to pager phone numbers; can use a dedicated key on keypads to send a signal to a pager (supports 2 pagers) Built-in Telephone Line Monitoring option can monitor the telephone line voltage and can cause a local display, or a display and trouble/alarm sound. Event Logging records up to 50 selected events in a history log; control and readout from the log is done via Ademco Compass Downloader software or installer/master code at 5839 Alpha RF Keypad Zone descriptors for all zones Optional RF jam detection for wireless systems detects a condition that may impede proper RF reception (i.e., jamming or other RF interference); causes keypad display, and sends a report to the central monitoring station (if trouble reporting is enabled). Compatible Devices System Features Supports up to seven 5839 Alpha RF Keypads and unlimited 5828 Fixed RF Keypads or 5828V Fixed RF Voice Keypads (Function keys will not work as set in *57) Supports 5800 series transmitters Powerline Carrier Devices (X-10 type) For programming the control during installation, supports either a 6160 or 6139 Alpha keypad (Installer Keypad). Tamper Protection The control is tampered protected. An alarm will sound if the cover is removed or if the control is removed from it s mounted location. LED Indications One Rf activity indicator, activates momentarily when Rf is received (used during installation to program sensors serial number to the control) The control utilizes three Security System Control Status LEDs that indicate control arming state and power status as follows: The Red LED: Lights or flashes when system is armed AWAY or STAY mode. Lit Steady = system armed AWAY or system armed STAY and exit delay has expired Flashing = system armed STAY and exit delay timer active Rapid Flashing = an alarm has occurred (memory of alarm) The Yellow LED: Indicates system power status. Lit Steady = AC power on Flashing = low battery Off = AC power off, discharged battery Green LED lights when the system is disarmed and ready to be armed (no open zones). If the system is disarmed and the green light is off, it indicates the system is not ready (one or more zones are open). 1 2

7 Section 1: Features and Installation Highlights Important Installation Highlights (Installer Please Read) The Installer keypad (6160 or 6139) for programming uses address 16. Before beginning the installation refer to Section 2, Setup and Mountingand Quick Mode Programming Installer Keypad Functions to become familiar with the use of the Installer Keypads keys used to program the control. The system can use up to seven 5839 keypads, the first keypad uses address 01 and the subsequent keypad(s) (if used) uses address 02, 03, 04, 05, 06, 07 respectively. The 5828 series keypads use the house ID. Relays have two programming menu modes: Use *79 Menu mode to map device (output) numbers. Use *80 Menu mode to define the output functions (see Output Device Programming section). This system supports programmable function keys. Use *57 Menu mode to define the function keys (see Function Key Programming section). This system provides various paging features. Refer to Section 3, Programming Overview section for a summary on pager programming. For UL installations only, LXL-1010 and TELCO line must be located within the same room. 1 3

8 LXL-1010 Installation and Setup Guide 1 4

9 R S E C T I O N 2 Quick Start Installation Guide General The Quick Start Installation Guide provides you with the necessary installation procedures to get the LXL-1010 mounted and operational. The sections that follow provide detailed information designed to further enhance or modify the LXL-1010 standard defaulted operational functions. 1. Removing the Cover During normal operation, the cover of the LXL-1010 control remains in place. Press inward on the two locking tabs shown in Figure 1 and remove the cover. COVER LOCKING TAB (TYPICAL L/R) QuikMate Figure 1. LXL-1010 Cover Locking Tabs Referring to Figure 2, install the battery and battery bracket as shown and then connect the battery connector to the pc board. Observe installing the battery with the polarization orientation as shown in Figure 2. QM-023-V0 QM-039-V0 Figure 2. Battery Installation 2 1

10 LXL-1010 Installation and Setup Guide 2. Selecting a Installation Site Plug the LXL-1010 control in at the desired location. Select a duplex outlet location where the controls Red RF LED is not lit. The RED RF LED located on the receiver's circuit board should be used as an indicator of strong local radio frequency interference. If this LED is continuously illuminated, the control should be relocated. Optimum RF performance can usually be found at the highest point within a building, with the fewest number of walls between the control and the outside of the premises. Avoid mounting the LXL-1010 near other electronic devices. Table 1 provides minimum distances. Highest RF energy is in the direct, horizontal line of the antenna. Therefore, vertical separation (moving electronic devices either higher or lower on the wall) provides a higher level of isolation from the control. Table 1. Minimum Distances from Electrical Equipment EQUIPMENT DISTANCE PIR 10 ft. FM radio or TV antenna 25 ft. Other devices 10 ft. minimum The LXL-1010 is intended for indoor installation only. Mounting outdoors will cause system failure and may present a shock hazard. 3. Connecting the Installer Keypad Connect the Installer Keypad to the Programming Connector as shown in Figure 3 and then set the Installer Keypad address to 16. YELLOW NOT USED RED BLACK GREEN TO PROGRAMMING KEYPAD KEYPAD PROGRAMMING CONNECTOR QM-025-V1 Figure 3. Connecting Installer Keypad. 4. Program the LXL-1010 The LXL-1010 should be programmed and tested prior to Final Mounting. Refer to Quick Mode Programming procedures that follow to Select System Defaults, Add Primary Phone Number, Add Primary Sub ID Account Number, Add Secondary Phone Number, Add Secondary Sub ID Account Number, Add Sensors, Delete Sensors, and enter Expert Programming Mode. to finalize system features. Quick Mode Programming Installer Keypad Functions The keys shown below are used to navigate through the Quick Mode Programming options. 2 2

11 Section 2: Quick Start Installation Guide ARMED READY ESC ADD DELETE SELECT OFF AWAY STAY MAX TEST CODE INSTANT BYPASS CHIME READY * 0 PANIC # INDEX # KEY FUNCTION 1 ESC Used at any time to exit the current menu (without saving current input unless * is pressed) and return to the previous menu. 2 ADD Used to add sensors or keys, or save data when entering phone or account numbers. 3 DELETE Used to delete a sensor when in the Delete Sensors Menu. 4 SELECT Used to confirm a selection. 5 3 Used to scroll up through menu choices QM-011-V0 Used to scroll down through menu choices. Enter Quick Mode Programming 1. Enter Installer Code ( ) Once you have entered Quick Mode the programming keypad will display, Add Sensors. 3. Press the 6 or 3 key to scroll through the options: Add Sensors Sec Sub ID Delete Sensors Select Defaults Pri Phone Program LRR Pri Sub ID LRR Registration Sec Phone Expert Mode 4. Press the SELECT function key to select the option for editing. Program each option as follows: If you make a mistake editing an option you must exit the option and then renter it. Press the ADD key to enter the edited option field data. When stepping through the Phone Number and Sub ID (subscriber ID and Central station) phone number fields, the existing data is displayed. If the field is selected for editing, the data in that field will be deleted. The field can be left blank by pressing the ADD key. Enter new data and then press the ADD key. When you have completed each programming option, press the ESC to return to the prior prompt. 2 3

12 LXL-1010 Installation and Setup Guide SELECT DEAULTSError! Bookmark not defined.. Scroll to the Select Defaults option to change the current default table. You have a choice of four different default tables. The defaults associated with each configuration are shown in the LXL-1010 Installation and Setup Guide Programming Form. Program a Default Table Scroll to "Defaults" Press [SELECT] Scroll to select Configuration Press [ADD] Scroll to next option or ESC Default Configurations Config 1 Config 2 Config 3 Config 4 Refer to the Default Tables shown in the Programming Guide QM-020-V0 PRI PHONE. Scroll to the Pri Phone option to enter or modify the central station primary phone number in the system. Valid entries for the entering the primary phone number are 0 9, # + 11 for, # + 12 for #, # + 13 for a pause (2 seconds). Note: When stepping through the Phone Number and Sub ID (subscriber ID and Central station phone number fields), the existing data is displayed. If the field is selected for editing, the data in that field will be deleted. The field can be left blank by pressing the ADD key. Enter new data and then press the ADD key. Add Primary Phone Number Scroll to "Pri. Phone" Enter first central station phone number (up to 20 digits) Press [SELECT] Press [ADD] Scroll to next option or ESC QM-016-V0 PRI SUB ID. Scroll to the Pri Sub Id option to enter the central station primary subscriber ID account number in the system. Note: When stepping through the Phone Number and Sub ID (subscriber ID and Central station phone number fields), the existing data is displayed. If the field is selected for editing, the data in that field will be deleted. The field can be left blank by pressing the ADD key. Enter new data and then press the ADD key. All four digits of the Central Station Account number must be entered. If ten-digit format is! being used, all ten digits must be entered. Add Primary Sub ID Account Number Scroll to "Pri. Sub ID" Enter first central station account number (up to 4 or 10 digits) Press [SELECT] Press [ADD] Scroll to next option or ESC QM-017-V0 2 4

13 Section 2: Quick Start Installation Guide SEC PHONE. Scroll to the Sec Phone option to enter the central station secondary phone number in the system. Valid entries for the entering the secondary phone number are 0 9, # + 11 for, # + 12 for #, # + 13 for a pause (2 seconds). Note: When stepping through the Phone Number and Sub ID (subscriber ID and Central station phone number fields), the existing data is displayed. If the field is selected for editing, the data in that field will be deleted. The field can be left blank by pressing the ADD key. Enter new data and then press the ADD key. Add Secondary Phone Number Scroll to "Pri. Phone" Enter first central station phone number (up to 20 digits) Press [SELECT] Press [ADD] Scroll to next option or ESC QM-016-V0 SEC SUB ID Scroll to the Sec Sub Id option to enter the central station secondary subscriber ID account number in the system. Note: When stepping through the Phone Number and Sub ID (subscriber ID and Central station phone number fields), the existing data is displayed. If the field is selected for editing, the data in that field will be deleted. The field can be left blank by pressing the ADD key. Enter new data and then press the ADD key.! All four digits of the Central Station Account number must be entered. If ten-digit format is being used, all ten digits must be entered. Add Secondary Sub ID Account Number Scroll to "Sec. Sub ID" Enter second central station account number (up to 4 or 10 digits) Press [SELECT] Press [ADD] Scroll to next option or ESC QM-019-V0 ADD SENSORS. Scroll to the Add Sensors option to enroll RF sensors in the system.! The LXL-1010 will enroll a sensor once the transmitter has been activated twice. LXL confirms the enrollment following subsequent activation of the same transmitter. Add A Door Sensor Doors added have Zone Type 01, exit/entry operation. Scroll to "Add Sensors" Press [SELECT] Scroll to "Add Door Sensor" Press [SELECT] Scroll to sensor location Press [SELECT] Scroll to Sensor location Press [SELECT] Activate transmitter twice. To enter S/N manually Press (SELECT) Press [ADD] Scroll to next option or ESC QM-012-V0 2 5

14 LXL-1010 Installation and Setup Guide To Add a Window, Motion, Fire, Glass Break, or Shock Sensor Scroll to "Add Sensors" Press [SELECT] Scroll to sensor type See (1) Press [SELECT] Scroll to sensor location See (2) Press [SELECT] Activate transmitter twice or enter S/N manually Press [ADD] Scroll to next option or ESC QM-013-V1 (1) Sensor Type (2) Sensor Location Window Dining room Master Bedroom Basement Motion Detector Family Room Bedroom Den Fire Detection Guest Room Bathroom Garage Laundry Room Nursery Attic Living room Kitchen Office Utility Room Hall Upstairs Add Emergency Sensor Scroll to "Emergency" Scroll to pendant type Press [SELECT] Press [SELECT] Activate transmitter twice or enter S/N manually Press [ADD] Scroll to next option or ESC (5) Pendant Type Medical Fire Silent Police Police Add Keyfob! When adding wireless keys, wait 5 seconds between transmissions. QM-014-V1 Scroll to "Add Sensors" Press [SELECT] Scroll to "Add Keyfob" Press [SELECT] See (1) Scroll to desired template Press [SELECT] Activate transmitter twice or enter S/N manually Press [ADD] Enter User No. Press [ADD] Scroll to next option or ESC QM-015-V1 (1) Wireless Key Default Templates TEMPLATE 1 Loop Function TEMPLATE 4 Loop Function No Alm DISARM AWAY No Alm No Alm No Alm AWAY DISARM TEMPLATE 2 Loop Function TEMPLATE 5 Loop Function No Alm DISARM AWAY STAY No Alm STAY AWAY DISARM TEMPLATE 3 Loop Function TEMPLATE 6 Loop Function Hr DISARM AWAY STAY Hr STAY AWAY DISARM 2 6

15 Section 2: Quick Start Installation Guide DELETE SENSORS. Scroll to the Delete Sensor option to delete sensors in the system. Delete Sensors Scroll to "Delete Sensors" Scroll to "Delete Zone" Scroll to "Zone XX" Delete "DelZn XX" Press [SELECT] Press [SELECT] Scroll to zone number to be deleted Press [SELECT] Press [DELETE] Scroll to "Del Transmitter" Scroll to "Zone XX" Delete "DelZn XX" OR SCROLL Press [SELECT] Scroll to zone number to be deleted Press [SELECT] Press [DELETE] Note: Del Transmitter option functions the same as Delete Zone, except that all loops associated with that transmitter will be deleted including all zones using that transmitters serial number. EXPERT MODE To complete the programming requirements for your installation Scroll to the Expert Programming Mode option to exit the Quick Programming Mode and enable Standard Data Field Programming to enter *24 RF House Id code, *190 Site Id 5839 Keypad Options, and *191 Site Id 5839 Enrollment mode. In addition use this option to change a specific default for example, *34 Exit Delay, *35 Entry Delay, *47 Phone System Select, *48 Report Format, and *50 Burglary Dialer Delay. Once Expert Mode is selected from QUICK MODE programming you will be locked out of Quick Mode programming. You should choose this entry only if you desire to restrict reentry into Data Field Programming via *98 exit. Enter Expert Programming Mode Once you have entered the Expert Programming Mode, the [ESC] key cannot be used to return to Quick Mode Programming mode.! QM-036-V0 Scroll to "Expert programming mode" Press [SELECT] System switches to Expert Programming Mode (Refer to the Installation and Setup Guide or the Programming Guide for additional programming instructions) QM-021-V0 5. Completing Programming When you have finished programming all zones, test each zone using the system s TEST mode. Do not use the Transmitter ID Sniffer Mode for checking wireless transmitting devices, as it will only check for transmission of one zone on a particular transmitter, NOT the zones assigned to each additional loop. 6. Final Mounting When a good programming and testing is complete, unplug LXL-1010 and remove the existing duplex or Decora receptacle cover plate. Do not discard screw(s) they will be used in the next step. Using the appropriate receptacle adapter supplied, standard duplex or Decora, attach the adapter to the wall receptacle using the screws removed in step 1. A typical installation is shown in Figure

16 LXL-1010 Installation and Setup Guide Using the screws and anchors supplied attach the controls mounting plate to the receptacle adapter and the wall as shown in Figure 5. Figure 5 shows a typical mounting installation using the duplex receptacle adapter. 1 REMOVE RECEPTACLE COVER PLATE OUTLET MOUNTING SCREW 2 RECEPTACLE ADAPTER PLATE 3 INSTALL MOUNTING PLATE WALL ANCHOR (5 SUPPLIED) WALL MOUNTING SCREWS (4 TYP.) OUTLET MOUNTING SCREW TAMPER MOUNTING SCREW QM-008-V1 Figure 5. Installing the LXL-1010 Control Mounting Plate Position the control on it s mounting plate and secure with the screws supplied as shown in Figure 6. Install the cover. QM-010-V1 Figure 6. Installing the Control on Mounting Plate 2 8

17 R Section 2: Quick Start Installation Guide 6. Phone Line Connections For incoming phone line and handset wiring refer to Figure 7. The AUX phone jack on the LXL-1010 provides a convenient means of connecting an additional telephone. DETAIL A SIDE VIEW INCOMING PHONE LINE RING TIP RJ31 JACK AUX JACK RJ11 RED GREY RJ31X GREEN RING TIP BROWN TO PREMISES PHONES SEE DETAIL A DIRECT CONNECT CORD QM-024-V0 Figure 7. Phone Line and Handset Wiring. 7. Test the System Refer to Testing LXL-1010 Section 13, and perform a System Test. 2 9

18 LXL-1010 Installation and Setup Guide 2 10

19 S E C T I O N 3 Programming Overview About Programming You can program the system at any time, even at the installer's premises prior to the actual installation. Programming can also be performed remotely from the installer s office/home, using an IBM personal computer, a modem, and Compass downloading software. The following is a list of the various Programming modes used to program this system. Programming Mode Data Field Programming Quick Mode Programming 56 Zone Programming 57 Function Key Programming 58 Zone Programming 79 Output Device Mapping 80 Output Definitions Used to Program basic data fields used for setting the various system options. Most of the data fields in this system have been programmed for specific default values. However, some fields must be programmed for each particular installation to establish its specific alarm and reporting features. The Quick Mode Programming is a simplified programming option that can be used to modify defaulted programming options. Assign zone characteristics, report codes, alpha descriptors, and serial numbers for 5800 RF transmitters. Programs each 5839 used four alphabet function keys to perform one of several system operations. Assign zone attributes similar to 56 mode, but provides a faster programming procedure and is intended for those more experienced in programming controls of this type. Assign unit codes for Powerline Carrier devices (X-10). Define up to 24 output definitions which can control the output relays mapped using *79 Output Device Mapping mode. 81 Zone List Programming Create Zone Lists for zones that will activate X-10 devices, chime, night-stay, and pagers. 82 Alpha Programming Scheduling Mode (code + [#] +64) Create alpha descriptors for easy zone identification. Create schedules to automate various system functions. 3 1

20 LXL-1010 Installation and Setup Guide Keypads 3 2 Alpha KeypadsError! Bookmark not defined.: Alpha keypads are identified by predefined addresses as follows: This Device Uses Address Reports As Zone Enabled By 6160/6139 Installer Keypad always enabled, all sounds enabled 5839 keypad data field *190, * keypad data field *190, * keypad data field *190, * keypad data field *190, * keypad data field *190, * keypad data field *190, * keypad data field *190, *191 Fixed Glass Keypads: If using 5828 series keypads set the HOUSE CODE ID for each keypad to be used (refer to keypad s instructions for setting the HOUSE CODE ID). Wireless Programming Options *22 RF Jam Option *24 RF House ID Code (if using 5828/5828V wireless keypads) *67 Transmitter Low Battery Report Code *75 Transmitter Low battery restore report code Transmitters, and Wireless Keys (Keyfobs) Transmitters Use *56, *58 Zone Programming Menu modes, or Quick Programming Mode to program zone information and enroll transmitters (zones 1-32, buttons 33-40). Wireless Keys Use Wireless Key Programming Templates section of the *58 Zone Programming Menu mode or Quick Programming Mode to program zone information and enroll each button of the wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before it becomes active. See Adding/Deleting Security Codes section for procedure. Pager Programming The system can send various reports to up to two pagers. To program pager reporting, do the following: 1. Enter the appropriate information in the following data fields: *160, *163 Pager Phone Numbers (for pagers 1-2 respectively) *161, *164 Pager Prefix Characters (for pagers 1-2 respectively) *162, *165 Pager Reporting Options (for pagers 1-2 respectively) 2. Enable Pager Delay, if desired, in field *172 (delays alarm reporting for ALL pagers). 3. Enable appropriate user open/close pager reports using the user attribute command (master code + [8] + user no. + [#] [5] + [1]). Users that perform actions will, if enabled, attempt to report to all pagers enabled for open/close reporting 4. If using latchkey pager report, define the latchkey report schedule using Scheduling mode (master code + [#] [6] [4] then select event type 03 ). 5. If using a function key to manually send a message to a pager, see Function Keys on next page. 6. If reporting zone alarms and troubles to a pager, use *81 Zone List menu mode to assign the zones associated with each pager (zone lists 9-10).

21 Section 3: Programming Overview Function KeysError! Bookmark not defined. To assign functions to 5828/5828V Function Keys refer to the 5828/5828V Installation and Setup Guide. To assign functions to 5839 function keys, use *57 Function Key menu mode. To assign emergency key functions (function key option 00 ), first program the respective emergency zone number (95 for A key, 96 for C key, 99 for B key) with the desired zone type using *56 Zone Programming mode, then use *57 Function Key menu mode to assign the desired key. If using a function key to activate a relay action (*57 Menu mode key function 07), use *79 Menu mode to map the output, and use *80 Menu mode to define the output s action; select system operation type 66. If using a function key for a user macro, use *57 menu mode to activate the desired key, then define the actual macro functions using the user code + [#] + [6] [6] command. Output Devices (X-10) To program a device for manual activation (user code + [#] [7] / [#] [8] + 2-digit device number) or for scheduled automatic activation, simply map the device using *79 Menu mode. To program a device to automatically activate upon a system event (or function key), use *79 Menu mode to map the device, then use *80 Menu mode to define the automated device action. If the device action is based on more than one zone, use *81 Zone List menu mode to assign the zones. Quick Mode Programming Quick Mode programming enables you to quickly program the defaulted programming features by responding to a series of displayed prompts. Quick Mode is entered by pressing (Installer code) followed by on the Installers Keypad, after the initial startup delay busy standby is terminated or expires. Zone Type Definitions A zone type must be assigned to each zone. Zone type defines the way in which the system responds to faults in that zone. Quick Mode Programming automatically assigns zone types based on the sensor selected. When using Data Field Programming you must assign a zone type to each zone. Zone types are defined as follows. Zone Type Description Type 00 Program a zone with this zone type if the zone is not used. Zone Not Used Type 01 Entry/Exit Burglary #1 Type 02 Entry/Exit Burglary #2 Type 03 Perimeter Burglary Type 04 Assign to zones that are used for primary entry and exit. Provides entry delay if control is armed in the Away, Stay, or Night-Stay modes. Entry Delay 1 timer is programmable in field *35. No entry delay provided when the panel is armed in the Instant/Maximum mode. Exit delay begins whenever the control is armed, regardless of the arming mode selected. Exit delay timer is programmable in field *34. Assign to zones that are used for entry and exit and require more time than the primary entry/exit point. Entry Delay 2 timer is programmable in field *36. Provides a secondary entry delay, in same manner as entry delay #1. Exit delay begins whenever the control is armed, regardless of the arming mode selected. Exit delay timer is programmable in field *34. Assign to all sensors or contacts on exterior doors and windows. Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, Night-Stay, Instant or Maximum modes. Assign to a zone covering an area such as a foyer, lobby, or hallway 3 3

22 LXL-1010 Installation and Setup Guide Zone Type Interior Follower Type 05 Trouble by Day/ Alarm by Night Type hour Silent Alarm Type hour Audible Alarm Type hour Auxiliary Alarm Type 09 Supervised Fire Type 10 Interior w/delay Type 12 Monitor Zone Type 14 Description through which one must pass upon entry (to and from the keypad). Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first. Otherwise this zone type gives an instant alarm. Active when the panel is armed in the Away mode. Bypassed automatically when the panel is armed in the Stay or Instant modes; if armed in Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not bypassed when system armed in Night-Stay mode. Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering a sensitive area such as a stock room, drug supply room, etc. Can also be used on a sensor or contact in an area where immediate notification of an entry is desired. Provides an instant alarm if faulted when armed in the Away, Stay, Night-Stay, Instant or Maximum (night) modes. During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a central station report, if desired). Usually assigned to a zone containing an emergency button. Sends a report to the central station but provides no keypad display or sounding. Assign to a zone that has an emergency button. Sends a report to the central station, and provides an alarm sound at the keypad, internal sounder, and an audible external alarm. Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as water or temperature sensors. Sends a report to the central station and provides an alarm sound at the keypad, internal sounder, and an audible external alarm. Provides a fire alarm when detector is faulted and a trouble condition when the cover is removed. A fire alarm produces a pulsing internal sounder output. This zone type is always active and cannot be bypassed. Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away mode. Entry Delay 1 timer is programmable in field *35. Entry Delay 1 begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit delay zone was tripped first. Bypassed when the panel is armed in the Stay or Instant modes; if armed in Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not bypassed when system armed in Night-Stay mode. Works as a dynamic monitor of a zone fault/trouble (not alarm). The system keypad will display a check message indicating the appropriate zone (but keypad beeping does not occur). The check message will automatically disappear from the keypad dynamically, when the zone restores; a user code + off sequence is not needed to reset the zone. Faults of this zone type are independent of the system, and can exist at the time of arming without interference. Since this is a trouble zone type, do not use this zone type with X- 10 Powerline Carrier Devices set to activate upon alarm. Assigned to any zone with a carbon monoxide detector. 3 4

23 Section 3: Programming Overview Zone Type 24 Hour Carbon Monoxide Monitor Type 20 Arm-Stay (BR only) Type 21 Arm-Away (BR only) Type 22 Disarm (BR only) Type 23 No Alarm Response Type 24 Silent Burglary Types Configurable Description The internal sounder output will pulse when this zone type is alarmed. Always active and cannot be bypassed. Arms the system in Stay mode when the zone is activated. Pushbutton units send the user number to the central station when arming or disarming. User number for button must be assigned. Arms the system in Away mode when the zone is activated. Pushbutton units send the user number to the central station when arming or disarming. User number for button must be assigned. Disarms the system when the zone is activated. User number for button must be assigned. Can be used on a zone when an X-10 powerline carrier device action is desired, but with no accompanying alarm (e.g., lobby door access). The system can still be armed when these zone types are in a faulted condition. Usually assigned to all sensors or contacts on exterior doors and windows where internal sounder is NOT desired. Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is faulted when the system is armed in the Away, Stay, Instant, or Maximum modes. A report is sent to the central station. Allows for various custom responses. Options include response to entry/exit delays, zone faults, types of alarm/trouble sounding, dial delay, and unique Contact ID report codes. UL installations: Zone Types may not be used as fire or burglar alarm zones on fire or UL burglar alarm installations. Mechanics of Programming To program the system from a keypad: You must use an Installer Keypad 6160 or System must be disarmed. Installer Keypad Functions A Standard 6139 or 6160 alpha keypad is used to program, test, and diagnose the control and is referred to as the Installer Keypad. The Installer Keypad is automatically sensed when connected and is powered by the control. The Installer Keypad is connected to the installer keypad programming connector shown in Figure 1. Address 16 is reserved for the Installer keypad. NOTE: The Installer Keypad keys function are dependent on program mode selected, Data Field Programming, or Quick Mode Programming. 3 5

24 LXL-1010 Installation and Setup Guide Data Field ProgrammingError! Bookmark not defined. Procedures Task Entering Programming Mode Go to a Data Field Entering Data Review a Data Field Deleting an Entry Procedure A) Press both [ ] and [#] at the same time within 50 seconds after power is applied to the control, OR B) After power-up ( Busy Standby D1 display clears), enter [Installer code ( )] (method B is disabled if you exit the program mode using 98) Press [ ] + [Field Number] (for example, 21). A display of EE or Entry Error means you have entered a nonexistent field. Simply re-enter [ ] plus a valid field number. When the desired field number appears, simply enter the digits required. The keypad beeps three times after the last digit is entered and automatically displays the next data field in sequence. If entering less than the maximum digits available (e.g., phone number field), enter the desired digits, then press [ ] to end the entry. Press [#] + [Field Number]. That field s data is displayed, but no changes can be made. Interactive Mode Programming (*56, *57, *58, *79, *80, *81, *82) Task Procedure Entering Interactive Mode Loading Factory Defaults/Initializing for Download Task Procedure To Load Default Entries To Initialize Download ID Exiting the Programming Mode Press [ ] + [Field No.] + [ ] (applies only to phone number, account number, and pager character fields). Press [ ] + [Interactive Mode No.] (for example, 56) while in Program Mode. The Alpha display keypad will display the first of a series of prompts requesting entries. After making the appropriate entry, press the [ ] key to accept the entry and continue to the next prompt. Press 97 while in Program Mode and enter the desired default table number (1 4) to enter the desired default table values (shown on the Program Form). Use 97 only if you wish to return to one of the four original factory-programmed defaults. Press 96 while in Program Mode. This initializes the system for downloading and resets all the subscriber account numbers and CSID. Task Prevent installer code reentry Allow installer code reentry Procedure This is the default Program Mode Lockout Option (field *88). Press 98. Exits Programming Mode and prevents re-entry by: Installer Code + [8] + [0] + [0]. To enter the programming mode if 98 was used to exit, you must first power the system down. Then power up again, and press [ ] and [#] at the same time, within 50 seconds of powering up. See field *88 for other Program mode lockout options. Press 99. Exits Programming Mode and allows re-entry by: Installer Code + [8] + [0] + [0] or by: Pressing [ ] and [#] at the same time, within 50 seconds of power-up. 3 6

25 S E C T I O N 4 Data Field Programming About Data Field Programming The following pages list this control s data fields in numerical order. Field numbers are listed in the left column followed by a Title and Data Entries column, which lists the valid entries for each field. Experienced installers can simply follow this column when programming the data fields. The Explanation column provides explanatory information and special notes where applicable. Do not press *97 to load defaults if any programming has been done previously data already programmed into the system will be changed! Refer to the Programming Form for Default Tables 1 4. Programming Data Fields Data field programming involves making the appropriate entries for each of the data fields. Start Data Field programming by entering the installer code System Setup Fields ( 20 29) FIELD TITLE and DATA ENTRIES EXPLANATION *20 Installer Code Enter 4 digits, 0-9 *21 Quick Arm Enable 0 = do not allow quick arm 1 = allow quick arm *22 RF Jam Option 0 = no RF jam detection 1 = send RF jam report *23 Quick (Forced) Bypass 0 = no quick bypass 1 = allow quick bypass (code + [6] + [#] ) *24 RF House ID Code 00 = disable all wireless keypad usage = House ID *26 Chime By Zone List 3 0 = no zone list (chimes on fault of any entry/exit or perimeter zone when chime mode on) 1 = use zone list (chimes on fault of specific zones programmed in relay zone list 3 when Chime mode on) *27 Powerline Carrier Device (X-10) House ID 0 = A 6 = G # + 11 = L 1 = B 7 = H # + 12 = M 2 = C 8 = I # + 13 = N 3 = D 9 = J # + 14 = O 4 = E # + 10 = K # + 15 = P 5 = F The Installer Code can perform all system functions except it cannot disarm the system unless it is used to arm the system. If enabled, a user code is not needed to arm the system. Instead, users can press the [#] followed by an arming key to arm the system. However, the user code is always needed to disarm the system. If enabled, a report is sent if the system detects an RF jamming signal. UL installations must be 1 if wireless devices are used. All zones bypassed by this function will be displayed after the bypass is initiated. UL installations must be 0 (no forced bypass) The House ID identifies receivers, wireless keypads, and other devices that report status. If a 5828 or 5828V Wireless Keypad or 5804BD Transmitter is being used, a House ID code must be entered, and the keypad should be set to the same House ID. If enabled, you can define the specific zones intended to chime when faulted while the system is in Chime mode. Use zone list 3 to assign these zones (see 81 Zone List Programming section for details). Powerline Carrier devices require a House ID, identified in this field. Program Powerline Carrier devices in interactive modes 79, *80 and *81. Not intended for fire or UL installations. 4 1

26 LXL-1010 Installation and Setup Guide Zone Sounds & Timing ( 31 39) FIELD TITLE and DATA ENTRIES EXPLANATION *31 Single Alarm Sounding Per Zone (per armed period) 0 = no limit on alarm sounding per zone 1 = limit alarm sounding to once per arming period for a given zone *32 Fire Alarm Sounder Timeout 0 = yes; fire sounder timeout after time programmed in field 33 1 = no fire sounder timeout; continue sounding until manually turned off *33 Alarm Sounder Timeout 0 = No timeout 3 = 12 min 1 = 4 min 4 = 16 min 2 = 8 min *34 Exit Delay = 0-96 seconds 97 = 120 seconds *35 Entry Delay = 0-96 seconds 97 = 120 seconds 98 = 180 seconds 99 = 240 seconds *36 Entry Delay 2 See *35 above for entries. *37 Audible Exit Warning 0 = no; 1 = yes *38 Confirmation Of Arming Ding 0 = no ding 1 = confirmation ding after arming system 2 = confirmation ding after arming from RF button or RF keypad only *39 Power-Up In Previous State 0 = always power-up in a disarmed state 1 = assume the system status prior to power down Note: This field applies to the internal sounder only. UL installations must be 0 (no limit). This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of the following: 3 pulses pause 3 pulses pause 3 pulses. UL fire alarm installations: must be 1. This field determines whether the sounder will shut off after time allotted, or continue until manually turned off. UL installations: For residential fire alarm installation, must be set for a minimum of 4 min (option 1); for UL Commercial Burglary installations, must be minimum 16 min (option 4). The system waits the time entered before arming entry/exit zones. If the entry/exit door is left open after this time expires, an alarm will occur. UL installations: For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm installations with line security, total exit time must not exceed 60 seconds. For UL Burglar Alarm installations without line security (Grade A), total exit time must not exceed 120 seconds. SIA Installations: minimum exit delay is 45 seconds Upon entering, the system must be disarmed before the time entered expires, otherwise it sounds an alarm. UL installations: For UL Residential Burglary Alarm installations, must be set for a maximum of 30 seconds; entry delay plus dial delay should not exceed 1 min. For UL Commercial Burglar Alarm, total entry delay may not exceed 45 seconds. SIA Installations: minimum entry delay is 30 seconds See *35 above for explanation. Warning sound consists of slow continuous beeps until last 10 seconds, then it changes to fast beeps. Sound ends when exit time expires. SIA Installations: must be enabled (enter 1) Confirmation of arming is 1/2 second internal sounder ding. When enabled, ding will occur at the end of exit time, or after closing report has been sent (if programmed). If 1 selected, ding occurs when closing report is sent, or at the end of Exit Delay. If 2 selected, ding occurs upon reception of the wireless arming command. UL installations: must be 1 for UL Commercial Burglar Alarm installations. When the system powers up armed, an alarm will occur 1 minute after arming if a zone is faulted. Note that if the previous state was armed Away or Stay, the system will not respond to sensor changes for 1 minute, which allows time for sensors such as PIRs to stabilize. UL installations: must be 1 (power-up in previous state) 4 2

27 Dialer Programming ( 40 50) FIELD TITLE and DATA ENTRIES EXPLANATION *40 PABX Access Code Enter up to 6 digits if PABX is needed to access an outside line. Do not fill unused spaces. 0 9, # + 11 for, # + 12 for #, # + 13 for a pause (2 seconds) *41 Primary Phone No. Enter up to 20 digits. Do not fill unused spaces. 0 9, # + 11 for, # + 12 for #, # + 13 for a pause (2 seconds) *42 Secondary Phone No. Enter up to 20 digits. 0 9, # + 11 for, # + 12 for #, # + 13 for a pause (2 seconds) *43 Primary Subs. Acct. No. Enter digits 0 9; # + 11 for B, # + 12 for C, # + 13 for D, # + 14 for E, # + 15 for F. *44 Secondary Subs. Acct. No. Enter digits 0 9; # + 11 for B, # + 12 for C, # + 13 for D, # + 14 for E, # + 15 for F. *47 Phone System Select If Central Station Receiver is not on WATS line: 0 = Pulse Dial; 1 = Tone Dial If Central Station Receiver is on WATS line: 2 = Pulse Dial; 3 = Tone Dial *48 Report Format (Primary/Secondary) 0 = 3+1, 4+1 ADEMCO L/S STANDARD 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 ADEMCO L/S STANDARD 3 = 4+2 RADIONICS STANDARD 5 = ADEMCO Contact ID - 10-digit format 6 = 4+2 ADEMCO EXPRESS 7 = ADEMCO Contact ID - 4-digit format 8 = 3+1, 4+1 ADEMCO L/S EXPANDED 9 = 3+1, 4+1 RADIONICS EXPANDED *49 Split/Dual Reporting 0 = standard/backup reporting only (all reports only to primary unless unsuccessful, then will attempt secondary) 1-5 (see table to right) *50 Burglary Dialer Delay 0 = no dial delay 1 = 15 seconds 2 = 30 seconds 3 = 45 seconds *53 SESCOA/Radionics Select 0 = Radionics (0-9, B-F reporting) 1 = SESCOA (0-9 only reporting) Section 4: Data Field Programming To clear entries from field, press 40. If fewer than 6 digits need to be entered, exit by pressing [ ], which advances to the next field. Call Waiting: If the subscriber s phone service has call waiting (and is not using PABX), enter *70 (# + 11), 7, 0, (# + 13) (pause) as the PABX entry to disable call waiting during control panel calls. If the subscriber does not have call waiting and is not using PABX, make no entry in this field. If you enter fewer than 20 digits, exit by pressing [ ]. To clear entries from field, press 41. NOTE: Backup reporting (in which 8 calls are made to the secondary phone number if no kissoff is received after 8 attempts to the primary number) is automatic only if there is a secondary phone number (field 42). If you enter fewer than 20 digits, exit by pressing [ ]. To clear entries from field, press 42. See backup reporting note for field 41. Don t fill unused spaces. To clear entries from field, press 43. To clear entries from field, press 44. Select the type of telephone service. Select report format for primary and secondary phone numbers. To Primary No. To Secondary No. 1 = alarms, restore, cancel others 2 = all except open/close, test open/close, test 3 = alarms, restore, cancel all 4 = all except open/close, test all 5 = all all Provides delay of BURGLARY ALARM report to the central station and AlarmNet, which allows time for the subscriber to avoid a false alarm transmission. This delay does not apply to zone type 24 alarms (silent burglary) or to 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which are always sent as soon as they occur. UL: must be 0 SIA Installations: delay must be minimum of 30 seconds Select SESCOA or Radionics format. Select 0 for all other formats. 4 3

ADEMCO LYNX XL SERIES Security System

ADEMCO LYNX XL SERIES Security System ADEMCO LYNX XL SERIES Security System LXL-1000 Installation and Setup Guide Beta Draft Copy 8/23/04 K9349 8/04 Rev. A RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location

More information

ADEMCO LYNX XL SERIES Security System

ADEMCO LYNX XL SERIES Security System ADEMCO LYNX XL SERIES Security System LXL-1000 Installation and Setup Guide K9349V1 3/05 Rev. A RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary

More information

LYNX ,QVWDOODWLRQ,QVWUXFWLRQV. ALPHA DRAFT. June 5, 1998 N8889 5/98 OFF AWAY STAY AUX

LYNX ,QVWDOODWLRQ,QVWUXFWLRQV.  ALPHA DRAFT. June 5, 1998 N8889 5/98 OFF AWAY STAY AUX LYNX Security System,QVWDOODWLRQ,QVWUXFWLRQV ALPHA DRAFT June 5, 1998 OFF AWAY STAY AUX N8889 5/98 RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations For The Location Of Fire And Burglary

More information

ADEMCO VISTA-10P ADEMCO VISTA-10PSIA Security Systems

ADEMCO VISTA-10P ADEMCO VISTA-10PSIA Security Systems ADEMCO VISTA-10P ADEMCO VISTA-10PSIA Security Systems Programming Guide K0735PRV5 3/15 Rev A COMPATIBILITY: This Programming Guide is intended for VISTA-10P/VISTA-10PSIA controls with firmware revision

More information

$'(0&2 9,67$ 3DUWLWLRQHG 6HFXULW\ 6\VWHP 8VHU *XLGH N7003V3 5/04 Rev A

$'(0&2 9,67$ 3DUWLWLRQHG 6HFXULW\ 6\VWHP 8VHU *XLGH N7003V3 5/04 Rev A $'(0&29,67$ 3DUWLWLRQHG6HFXULW\6\VWHP 8VHU*XLGH N7003V3 5/04 Rev A 2 TABLE OF CONTENTS SYSTEM OVERVIEW...5 General...5 A Partitioned System...5 Zones...5 Fire Protection...6 Burglary Protection...6 Alarms...6

More information

ADEMCO LYNXR Series Security Systems

ADEMCO LYNXR Series Security Systems ADEMCO LYNXR Series Security Systems LYNXR/LYNXR24 and LYNXR-EN Installation and Setup Guide ARMED READY OFF ESCAPE AWAY ADD STAY RECORD LIGHTS ON 1 2 3 VOLUME 4 5 6 TEST 7 8 9 PLAY BYPASS DELETE AUX LIGHTS

More information

SECURITY SYSTEM 4110DL. Programming Form Programming Form Programming Form 4110DL-PRV3 10/96

SECURITY SYSTEM 4110DL. Programming Form Programming Form Programming Form 4110DL-PRV3 10/96 SECURITY SYSTEM 4110DL Programming Form Programming Form Programming Form 4110DL-PRV3 10/96 4110DL PROGRAMMING FORM FIELD FUNCTION [ ] = Default Value SYSTEM OPTIONS (*20-*28) *20 MASTER SECURITY CODE

More information

Technical Manuals Online! - K4855V1 3/00 FA560 3 STAY B 1 OFF 2 AWAY 6 C D 5 TEST 9 CHIME # 8 CODE I I I I I I READY ARMED MAX

Technical Manuals Online! -   K4855V1 3/00 FA560 3 STAY B 1 OFF 2 AWAY 6 C D 5 TEST 9 CHIME # 8 CODE I I I I I I READY ARMED MAX ARMED MAX INSTANT READY READY R BYPASS R R )$& )$&&1 6HFXULW\6\VWHP A 1 OFF 2 AWAY 3 STAY B 4 5 TEST 6 C D 7 * FA560 8 CODE 0 9 CHIME # I I I I I I HEAT COOL BYPASS ACTIVE 8VHU*XLGH K4855V1 3/00 TABLE

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

VISTA-20PMT. Programming Guide. This control is a certified SIA-compliant control that meets SIA specifications for False Alarm Reduction.

VISTA-20PMT. Programming Guide. This control is a certified SIA-compliant control that meets SIA specifications for False Alarm Reduction. ARMED 7 INSTANT 8 CODE VISTA-15PMT VISTA-20PMT Programming Guide ARMED READY 1 OFF 4 MAX 7 INSTANT READY 0 2 AWAY 5 TEST 8 CODE # 3 STAY 6 BYPASS 9 CHIME READY 1 OFF ON OFF 4 MAX 5 TEST 2 AWAY 3 STAY 6BYPASS

More information

FA130CP. Installation and Set-Up Guide. K0735-1V1 4/04 Rev. A OFF FA260 3 STAY 2 AWAY 1 OFF 6 9 CHIME # 5 TEST 8 CODE B C # FA560 READY R BYPASS MAX

FA130CP. Installation and Set-Up Guide. K0735-1V1 4/04 Rev. A OFF FA260 3 STAY 2 AWAY 1 OFF 6 9 CHIME # 5 TEST 8 CODE B C # FA560 READY R BYPASS MAX MAX INSTANT READY R BYPASS AWAY ARMED READY 1 OFF MAX INSTANT READY R 2 AWAY 3 STAY BYPASS FA130CP Security System Installation and Set-Up Guide ARMED READY A B C D 7 4 1 OFF FA260 2 AWAY 5 TEST 8 CODE

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

Safewatch QuickConnect

Safewatch QuickConnect Safewatch QuickConnect Security System Installation and Setup Guide ARMED READY OFF ESCAPE AWAY ADD STAY DELETE AUX 1 2 3 RECORD VOLUME PLAY 4 5 6 TEST 7 8 9 CODE 0 # BYPASS CHIME SELECT STATUS FUNCTION

More information

ADEMCO VISTA SERIES VISTA-21iP / VISTA-21iPSIA Security Systems

ADEMCO VISTA SERIES VISTA-21iP / VISTA-21iPSIA Security Systems ADEMCO VISTA SERIES VISTA-21iP / VISTA-21iPSIA Security Systems Programming Guide K14488PRV3 10/12 Rev B RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and

More information

Security System With Scheduling. User Guide. N5943-8V4 7/04 Rev A

Security System With Scheduling. User Guide. N5943-8V4 7/04 Rev A ADEMCO VISTA-120 Security System With Scheduling User Guide N5943-8V4 7/04 Rev A Your Honeywell security system is designed for use with devices manufactured or approved by Honeywell for use with your

More information

ADEMCO VISTA SERIES User Guide

ADEMCO VISTA SERIES User Guide ADEMCO VISTA SERIES VISTA-15P VISTA-15PSIA VISTA-20P VISTA-20PSIA User Guide K5309-1V7 3/15 Rev B IMPORTANT! PROPER INTRUSION PROTECTION For proper intrusion coverage, sensors should be located at every

More information

First Alert 1200C Installer Notes M. Leuck

First Alert 1200C Installer Notes M. Leuck First Alert 2C Installer Notes M. Leuck. Programming can done by standard keypads 2. Enter programming with Installer Code + 8 + + 3. Another method of entering programming: Power system down, then back

More information

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98

USER'S GUIDE FA1220CV. 2-Partition Security System N7003-1V2 7/98 USER'S GUIDE FA1220CV 2-Partition Security System N7003-1V2 7/98 SYSTEM OVERVIEW... 3 General... 3 A Partitioned System... 3 Zones... 3 Burglary Protection... 4 Fire Protection... 4 Alarms... 5 Emergency

More information

ADEMCO LYNXR-I Security Systems

ADEMCO LYNXR-I Security Systems ADEMCO LYNXR-I Security Systems Installation and Setup Guide ARMED READY OFF ESCAPE AWAY ADD STAY RECORD LIGHTS ON 1 2 3 VOLUME 4 5 6 TEST 7 8 9 PLAY BYPASS DELETE AUX LIGHTS OFF CODE CHIME 0 # SELECT

More information

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B VISTA-32FBPT Commercial Fire and Burglary Partitioned Security Systems with Scheduling User Guide 800-11045 2/12 Rev. B 2 TABLE OF CONTENTS SYSTEM OVERVIEW...5 General...5 A Partitioned System...5 Zones...6

More information

LYNX Touch Series Security Systems

LYNX Touch Series Security Systems LYNX Touch Series Security Systems Installation and Setup Guide ARMED READY 800-06834 1/11 Rev. A RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary

More information

VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA

VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA Commercial Burglary Partitioned Security System With Scheduling User Guide 800-06905 6/10 Rev. E IMPORTANT! RECOMMENDATIONS FOR PROPER INTRUSION PROTECTION For

More information

&RPPHUFLDO%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ

&RPPHUFLDO%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ READY ARMED READY 1 OFF 7 INSTANT READY 2 AWAY 8 CODE 6BYPASS 9 CHIME 9,67$% &RPPHUFLDO%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 8VHU*XLGH ARMED READY 1 OFF 2 AWAY 3 STAY 4 MAX 5 TEST 6 BYPASS

More information

&RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ

&RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 9,67$)% &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 8VHU*XLGH FIRE FIRE * PULL K3522 3/99 TABLE OF CONTENTS SYSTEM OVERVIEW...4 General...4 A Partitioned System...4 Zones...5 Fire

More information

/10 Rev A

/10 Rev A VISTA-128BPT/ VISTA-250BPT/ VISTA-128BPTSIA Commercial Burglary Partitioned Security System With Scheduling User Guide 800-06905 6/10 Rev A Your Honeywell security system is designed for use with devices

More information

ADEMCO VISTA-10P ADEMCO VISTA-10PSIA Security Systems

ADEMCO VISTA-10P ADEMCO VISTA-10PSIA Security Systems ADEMCO VISTA-10P ADEMCO VISTA-10PSIA Security Systems User Guide K0736V4 10/08 Rev. B IMPORTANT! PROPER INTRUSION PROTECTION For proper intrusion coverage, sensors should be located at every possible point

More information

User's Manual VIA-30PSE, VISTA-10SE. N7229V2 Rev C. 5/02

User's Manual VIA-30PSE, VISTA-10SE. N7229V2 Rev C. 5/02 Security System User's Manual VIA-30PSE, VISTA-10SE N7229V2 Rev C. 5/02 National Security Systems (800)457-1999 SYSTEM OVERVIEW...3 General...3 Zones...3 Burglary Protection...3 Chime Feature...3 Alarms...4

More information

ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Security Systems

ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Security Systems ADEMCO VISTA SERIES VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA Security Systems User Guide K5309-1V4 10/04 Rev. A IMPORTANT! PROPER INTRUSION PROTECTION For proper intrusion coverage, sensors should

More information

VISTA-50P VISTA-50PUL

VISTA-50P VISTA-50PUL Security System User's Manual VISTA-50P VISTA-50PUL N5943-6V1 Rev B 4/99 TABLE OF CONTENTS SYSTEM OVERVIEW...4 General...4 A Partitioned System...4 Zones...4 Fire Protection...5 Burglary Protection...5

More information

Understanding the Code Pad lights...4. Code Pad tones...5. Fully arming the system On MODE...6. Fully arming the system - Quick Arm MODE...

Understanding the Code Pad lights...4. Code Pad tones...5. Fully arming the system On MODE...6. Fully arming the system - Quick Arm MODE... TABLE OF CONTENTS...Glossary of terms...2...code Pad Diagram...3 Understanding the Code Pad lights...4 Code Pad tones...5 Fully arming the system On MODE...6 Fully arming the system - Quick Arm MODE...6

More information

TABLE OF CONTENTS TABLE OF CONTENTS 1

TABLE OF CONTENTS TABLE OF CONTENTS 1 TABLE OF CONTENTS TABLE OF CONTENTS 1 FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2

More information

User s Guide FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA. K5309-5V5 11/08 Rev. A OFF 3 STAY 2 AWAY 1 OFF A B C D 5 TEST 8 CODE 9 CHIME FA260 # FA560

User s Guide FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA. K5309-5V5 11/08 Rev. A OFF 3 STAY 2 AWAY 1 OFF A B C D 5 TEST 8 CODE 9 CHIME FA260 # FA560 MAX INSTANT READY R BYPASS AWAY STAY PAGE ARMED READY 1 OFF MAX INSTANT READY R 2 AWAY 3 STAY BYPASS 9 CHIME FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA Security Systems ARMED READY A B C D 7 4 1 2 3 OFF

More information

VISTA-10SE. Security System. Installation Instructions Installation Instructions Installation Instructions

VISTA-10SE. Security System. Installation Instructions Installation Instructions Installation Instructions Security System VISTA-10SE THIS ISSUE INCLUDES THE NEW QED (QUICK ENROLLMENT OF DEVICES) PROCEDURE FOR 5800 SERIES TRANSMITTERS Installation Instructions Installation Instructions Installation Instructions

More information

**** **** A B ARMED FIRE FIRE C D READY OFF AWAY STAY 2 3 MAXIMUM TEST BYPASS PULL INSTANT CODE CHIME. First Alert READY. * 0 # Professional

**** **** A B ARMED FIRE FIRE C D READY OFF AWAY STAY 2 3 MAXIMUM TEST BYPASS PULL INSTANT CODE CHIME. First Alert READY. * 0 # Professional ARMED READY READY )$&&$&% )LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHPV ZLWK6FKHGXOLQJ **** **** A B C D FIRE FIRE First Alert OFF AWAY STAY 2 3 1 4 5 6 7 8 9 MAXIMUM TEST BYPASS INSTANT CODE CHIME * 0 #

More information

User's Manual. Safewatch Pro. N7229 6V1 Rev B 4/99

User's Manual. Safewatch Pro. N7229 6V1 Rev B 4/99 Security System User's Manual Safewatch Pro N7229 6V1 Rev B 4/99 IMPORTANT! PROPER INTRUSION PROTECTION For proper intrusion coverage, sensors should be located at every possible point of entry to a home

More information

VISTA-20PMT. Security. Systems. User s Guide. Monitronics

VISTA-20PMT. Security. Systems. User s Guide. Monitronics VISTA-15PMT VISTA-20PMT Security Systems User s Guide Monitronics R I N T E R N A T I O N A L, I N C. K5309-1MTV2 7/04 Rev. A Reference: MTV15P, MTV20P IMPORTANT! PROPER INTRUSION PROTECTION For proper

More information

VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C

VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C VISTA-128BP/VISTA-250BP/ VISTA-128SIA Enhanced Commercial Burglary Partitioned Security System With Scheduling User Guide K5895V5 4/09 Rev C Your Honeywell security system is designed for use with devices

More information

AXI LED USER MANUAL (REV. 1.0)

AXI LED USER MANUAL (REV. 1.0) Security & Home Automation System AXI LED USER MANUAL (REV. 1.0) CONTENTS PREFACE FEATURES LED KEYPAD OUTLOOK 1.0 LIGHT INDICATION 1 2 4 6 CHAPTER 1: ALARM SYSTEM CONTROL 1.0 USING LED KEYPAD 1.0.1 ARMING

More information

LYNX Touch Security System

LYNX Touch Security System LYNX Touch Security System Programming Guide ARMED READY 800-06895 3/11 Rev. A Table of Contents Entering Programming Mode... 3 Programming the Data Fields... 3 Loading a Default Set... 3 Exiting Programming

More information

Lynx Plus Series Security Systems

Lynx Plus Series Security Systems Lynx Plus Series Security Systems Installation and Setup Guide ARMED READY ESCAPE ADD OFF AWAY RECORD LIGHTS ON 1 2 3 VOLUME TEST PLAY 4 5 6 BYPASS 7 8 9 STAY DELETE AUX SELECT LIGHTS OFF 0 CODE CHIME

More information

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS Feature Charts Control Panels FEATURE CHART LYNX Plus (L3000) (Supported Feature) (Not Supported) N/A (Not Applicable) LYNX Touch (L5210)

More information

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

Security System. User s Guide for the Text Command Center

Security System. User s Guide for the Text Command Center User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:

More information

User's Manual VISTA-40 N7003V1 6/97

User's Manual VISTA-40 N7003V1 6/97 S e c u r i t y S y s t e m User's Manual VISTA-40 N7003V1 6/97 SYSTEM OVERVIEW...3 General...3 A Partitioned System...3 Zones...3 Burglary Protection...4 Fire Protection...4 Alarms...5 Emergency (Panic)

More information

LYNX Touch L5210 Series Security System

LYNX Touch L5210 Series Security System LYNX Touch L5210 Series Security System User Guide 800-19975 12/14 Rev. B LYNX Touch L5210 Series Your Honeywell security system is designed for use with devices manufactured or approved by Honeywell for

More information

NetworX NX-8V2. LED Keypad User Manual

NetworX NX-8V2. LED Keypad User Manual NetworX NX-8V2 LED Keypad User Manual POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous

More information

ADEMCO VISTA-48 SERIES

ADEMCO VISTA-48 SERIES ADEMCO VISTA-48 SERIES Security Systems User Guide This control complies with EN50131-3:2009 and conforms to UL requirements. K0750ENV2 5/11 Rev. A Table of Contents Burglary System Overview...3 Basic

More information

&RPPHUFLDO%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ

&RPPHUFLDO%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ READY ARMED READY 1 OFF 7 INSTANT 2 AWAY 8 CODE 6BYPASS 9 CHIME 9,67$%3 9,67$%3 &RPPHUFLDO%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 8VHU*XLGH ARMED READY 1 OFF 2 AWAY 3 STAY 4 MAX 5 TEST 6 BYPASS

More information

Security System. User Guide for the LED Command Center

Security System. User Guide for the LED Command Center Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY

More information

9,67$36HULHV 6HFXULW\6\VWHPV 8VHU*XLGH K5309-1V1 7/02

9,67$36HULHV 6HFXULW\6\VWHPV 8VHU*XLGH K5309-1V1 7/02 9,67$3366HULHV 9,67$36HULHV 6HFXULW\6\VWHPV 8VHU*XLGH K5309-1V1 7/02 IMPORTANT! PROPER INTRUSION PROTECTION For proper intrusion coverage, sensors should be located at every possible point of entry to

More information

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160 All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

LYNXR-2 Series Security System

LYNXR-2 Series Security System For Service Call: (866) 401-4842 LYNXR-2 Series Security System User Guide ARMED READY OFF 1 2 3 ESCAPE RECORD VOLUME AWAY 4 5 6 PLAY ADD STAY LIGHTS ON TEST BYPASS 7 8 9 DELETE LIGHTS OFF CODE CHIME AUX

More information

LYNX Security System 8VHU V0DQXDO. ALPHA DRAFT June 5, 1998 N8891 5/98 OFF AWAY STAY AUX

LYNX Security System 8VHU V0DQXDO. ALPHA DRAFT June 5, 1998 N8891 5/98 OFF AWAY STAY AUX LYNX Security System 8VHU V0DQXDO ALPHA DRAFT June 5, 1998 OFF AWAY STAY AUX N8891 5/98 7$%/(2)&217(176 SYSTEM OVERVIEW...3 Features...3 General Operation...4 Quick View of System Functions...5 About the

More information

HILLS Series LED Code Pad User Manual

HILLS Series LED Code Pad User Manual HILLS Series LED Code Pad User Manual Not all features may be available on your system Check with your installer to find out which features are programmed Page 2 TABLE OF CONTENTS Code Pad Diagrams...2

More information

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. TABLE OF CONTENTS... P.1 2. GENERAL DESCRIPTION... P.2... 3. STANDARD AND OPTIONAL PARTS LIST... P.2... 4. FEATURE

More information

Technical Manuals Online! - USER'S MANUAL

Technical Manuals Online! -   USER'S MANUAL USER'S MANUAL FA162C Security System N7527-1V2 Rev B 4/99 2 SYSTEM OVERVIEW... 4 General... 4 A Partitioned System... 4 Zones... 4 Burglary Protection... 5 Security Codes... 5 Fire Protection... 6 Alarms...

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-12 Control/Communicator Installation Manual General Description...2 Ordering Information...2 Option Definitions...3 Programming the LED Code Pads...5 Programming the NX-12...9 Types of Programming

More information

ADEMCO VISTA-12A ADEMCO VISTA-12E

ADEMCO VISTA-12A ADEMCO VISTA-12E ADEMCO VISTA-12A ADEMCO VISTA-12E Security Systems User Guide K10021-1 9/04 Rev. A Table of Contents Burglary System Features... 3 Basic Features... 3 Exit/Entry Delays... 3 Before Arming (Ready [ ] Key)...

More information

SENTROL ZX400/ZX410. Security System Control. Programming

SENTROL ZX400/ZX410. Security System Control. Programming SENTROL ZX400/ZX410 Security System Control Programming 1 2 TABLE OF CONTENTS Table of Contents Operating the System... 5 Introduction...5 Powering Up With the Control Station...5 Control Stations...6

More information

Safewatch Pro 3000EN Entrepreneur 3000EN Security Manager 3000EN

Safewatch Pro 3000EN Entrepreneur 3000EN Security Manager 3000EN ARMED READY OFF INSTANT READY AWAY TEST CODE STAY BYPASS CHIME ARMED READY OFF INSTANT READY AWAY TEST CODE STAY BYPASS CHIME Safewatch Pro 3000EN Entrepreneur 3000EN Security Manager 3000EN Security Systems

More information

9,67$ 6(D 6\VWHP 6HFXULW\ 86(5 *8,'( N7229AUV2 12/99

9,67$ 6(D 6\VWHP 6HFXULW\ 86(5 *8,'( N7229AUV2 12/99 9,67$6(D 6\VWHP6HFXULW\ 86(5*8,'( N7229AUV2 12/99 TABLE OF CONTENTS SYSTEM OVERVIEW...4 General...4 Burglary Protection...4 Zones...4 Alarms...5 Fire Protection...5 Chime Feature...5 Phone Access & Voice

More information

USING DEVICE COMMANDS

USING DEVICE COMMANDS TABLE OF CONTENTS SYSTEM OVERVIEW... 3 General... 3 A Partitioned System... 3 Zones... 3 Burglary Protection... 4 Security Codes... 4 Fire Protection... 5 Alarms... 5 Memory of Alarm... 5 Phone Access

More information

LYNX Touch Security System

LYNX Touch Security System LYNX Touch Security System User Guide 1:35 2 PM October 26, 2011 72 Mostly Sunny 68 F F Feels Like 71 Security Messages Automation 5-Day Forecast News Traffic 800-10615 1/12 Rev. A LYNX Touch L5100 Series

More information

NetworX Series NX-1500E LED Keypad

NetworX Series NX-1500E LED Keypad NetworX Series NX-1500E LED Keypad User Manual SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function This system

More information

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1.2 1725, 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX TABLE OF CONTENTS HOW DO I PROGRAM THE SYSTEM?... 4 Single Digit Data Entry Method (Hexadecimal

More information

VISTA-20SE/VISTA-20HWSE

VISTA-20SE/VISTA-20HWSE Security System User's Manual VISTA-20SE/VISTA-20HWSE N7527V2 6/97 2 SYSTEM OVERVIEW... 4 General... 4 A Partitioned System... 4 Zones... 4 Burglary Protection... 5 Security Codes... 5 Fire Protection...

More information

LYNX Touch L5210/L7000 Series Security Systems

LYNX Touch L5210/L7000 Series Security Systems LYNX Touch L5210/L7000 Series Security Systems Installation and Setup Guide 800-19974 12/14 Rev.B RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary

More information

User's Manual 5120XM N8031 6/96

User's Manual 5120XM N8031 6/96 Fire and Burglary System User's Manual 5120XM N8031 6/96 SYSTEM OVERVIEW...3 General...3 Zones...3 Fire & Emergency Protection...3 Burglary Protection...4 Alarms...4 Memory of Alarm...4 ABOUT THE KEYPADS...5

More information

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL

More information

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

VISTA-128B. Installation and Setup Guide. Commercial Burglary. Partitioned Security System. with Scheduling K3271 7/98

VISTA-128B. Installation and Setup Guide. Commercial Burglary. Partitioned Security System. with Scheduling K3271 7/98 VISTA-128B Commercial Burglary Partitioned Security System with Scheduling Installation and Setup Guide K3271 7/98 ADDENDUM TO: VISTA-128B INSTALLATION INSTRUCTIONS This Installation Instruction Addendum

More information

MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4. Programming Guide

MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4. Programming Guide MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4 Programming Guide We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

SECURITY SYSTEM NOTES

SECURITY SYSTEM NOTES SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary

More information

LYNX Touch Series Security Systems

LYNX Touch Series Security Systems LYNX Touch Series Security Systems Installation and Setup Guide 800-10614V1 12/12 Rev. A RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection

More information

5HDG\*XDUG5 6HFXULW\6\VWHP 8VHU*XLGHIRU5HDG\*XDUG5. K5481-1V2 10/03 Rev. A OFF STAY ESCAPE AWAY ADD DELETE AUX STAY

5HDG\*XDUG5 6HFXULW\6\VWHP 8VHU*XLGHIRU5HDG\*XDUG5. K5481-1V2 10/03 Rev. A OFF STAY ESCAPE AWAY ADD DELETE AUX STAY 5HDG\*XDUG5 6HFXULW\6\VWHP OFF ESCAPE AWAY ADD STAY DELETE AUX STAY 8VHU*XLGHIRU5HDG\*XDUG5 K5481-1V2 10/03 Rev. A 7$%/(2)&217(176 SYSTEM OVERVIEW...3 Features...3 General Operation...5 Quick View of System

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

LyricTM. Programming Guide. Controller. Ref: LCP500-L/LCP500-LC V1 11/15 Rev A

LyricTM. Programming Guide. Controller. Ref: LCP500-L/LCP500-LC V1 11/15 Rev A LyricTM Controller Programming Guide Ref: LCP500-L/LCP500-LC 800-18077V1 11/15 Rev A RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection

More information

VISTA-100 Commercial Fire & Burglary Partitioned System

VISTA-100 Commercial Fire & Burglary Partitioned System VISTA-100 Commercial Fire & Burglary Partitioned System 4XLFN6WDUW Step-by Step Programming Procedure Single and Multiple Programming Forms System Worksheets FIRE FIRE * PULL VISTA-100PR Rev B 4/99 TABLE

More information

NX-148 LCD CODE PAD TABLE OF CONTENTS

NX-148 LCD CODE PAD TABLE OF CONTENTS NX-148 LCD CODE PAD TABLE OF CONTENTS Glossary Of Terms... 4 Understanding The Lights... 5 Code Pad Functions Arming In The ON Mode... 6 Making The System Ready To Arm... 7 Using Quick Arm... 7 Arming

More information

ADEMCO 4110XM SECURITY SYSTEM. Installation Guide. N5478V5 7/96 Rev. C

ADEMCO 4110XM SECURITY SYSTEM. Installation Guide. N5478V5 7/96 Rev. C ADEMCO 4110XM SECURITY SYSTEM Installation Guide N5478V5 7/96 Rev. C RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide

More information

NETWORX TM. User manual NX-4

NETWORX TM. User manual NX-4 NETWORX TM User manual NX-4 POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous alarm.

More information

ADEMCO VISTA-12A ADEMCO VISTA-12E Security Systems

ADEMCO VISTA-12A ADEMCO VISTA-12E Security Systems ADEMCO VISTA-12A ADEMCO VISTA-12E Security Systems User Guide K10021-1V1 10/05 Rev. A SYSTEM COMPATIBILITY NOTICE Your Honeywell security system is designed for use with devices manufactured or approved

More information

Alarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual

Alarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual WIC-16Z4P WIC-5Z2P Installation & Operation User Manual Page : 1/34 INDEX # Function Page 1 Abort Current Communication and Clear Reporting Queue (*59) 13 2 Abort Current Communications (*59) 10 3 Account

More information

All-In-One Wireless Security System V1.0. Model #: MG-6060

All-In-One Wireless Security System V1.0. Model #: MG-6060 All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual DRAFT Table of Contents Introduction... 5 About Magellan and this Manual... 5 Conventions... 5 Specifications...

More information

9,67$39,67$3&1 6HFXULW\6\VWHPV ,QVWDOODWLRQDQG6HW8S*XLGH K /01 1 OFF 4 MAX OFF 7 INSTANT 9 CHIME READY

9,67$39,67$3&1 6HFXULW\6\VWHPV ,QVWDOODWLRQDQG6HW8S*XLGH K /01 1 OFF 4 MAX OFF 7 INSTANT 9 CHIME READY ARMED 7 INSTANT 8 CODE 9,67$39,67$3&1 9,67$39,67$3&1 6HFXULW\6\VWHPV,QVWDOODWLRQDQG6HW8S*XLGH ARMED READY 1 OFF 4 MAX 7 INSTANT READY 0 2 AWAY 5 TEST 8 CODE # 3 STAY 6 BYPASS 9 CHIME READY 1 OFF ON OFF

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response

More information

6HFXULW\6\VWHP 8VHU*XLGH 9HUVLRQ. Technical Manuals Online! - N /98

6HFXULW\6\VWHP 8VHU*XLGH 9HUVLRQ. Technical Manuals Online! -  N /98 ;/;/ 6HFXULW\6\VWHP 8VHU*XLGH 9HUVLRQ N9146-1 10/98 Table Of Contents Introduction...4 LCD Keypad Layout...5 LED Keypad Layout...8 System Operation...12 Arming The System...13 System Ready...13 System

More information

9,67$&1 6HFXULW\6\VWHP ,QVWDOODWLRQDQG6HWXS*XLGH K3892V1 4/00

9,67$&1 6HFXULW\6\VWHP ,QVWDOODWLRQDQG6HWXS*XLGH K3892V1 4/00 9,67$ 9,67$&1 6HFXULW\6\VWHP,QVWDOODWLRQDQG6HWXS*XLGH * K3892V1 4/00 VISTA-15/VISTA-15CN Installation & Setup Guide ii RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the location

More information

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup NetworX Series NX-8 Commercial Fire Panel Installation and Startup 2004 GE Security All rights reserved. Printed in the United States of America. These instructions do not purport to cover all details

More information

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION...P.2 2. STANDARD AND OPTIONAL PARTS LIST...P.2 3. FEATURE DEFINITIONS...P.3 4. TERMINAL DRAWING AND

More information

RE6100 Series Helix Security and Automation Platform

RE6100 Series Helix Security and Automation Platform CONFIGURATION Resolution Compatibles RE6100 Series Helix Security and Automation Platform C G UI D E Configuration Settings Table 1 - Panel Settings Table 2 - Zone Settings Table 3 - Device Settings Table

More information

ABORT Light flashes during an abort delay time; is on during or after an alarm report to the central station. EMERGENCY ACTIVATION KEYS

ABORT Light flashes during an abort delay time; is on during or after an alarm report to the central station. EMERGENCY ACTIVATION KEYS POWER Light is on when AC power is present; flashes to indicate a low battery condition. CHIME Light is on when the chime feature is active. ABORT Light flashes during an abort delay time; is on during

More information

VISTA-128FB. Installation and Setup Guide. Commercial Fire & Burglary Partitioned Security System with Scheduling

VISTA-128FB. Installation and Setup Guide. Commercial Fire & Burglary Partitioned Security System with Scheduling Features Q.E.D. programming for quick enrollment of devices. VISTA-128FB Commercial Fire & Burglary Partitioned Security System with Scheduling Installation and Setup Guide N8988 5/98 ii Recommendations

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual

All-In-One Wireless Security System V1.0. Model #: MG Reference and Installation Manual All-In-One Wireless Security System V1.0 Model #: MG-6060 Reference and Installation Manual Table of Contents Introduction... 3 About Magellan and this Manual... 3 Conventions... 3 Specifications... 3

More information

DESTINY OWNER S MANUAL

DESTINY OWNER S MANUAL DESTINY OWNER S MANUAL DESTINY You have made a wise decision to protect your family and property with the DESTINY Security System. The DESTINY has been designed to provide you with a maximum level of security

More information