Three-Phase Power Conditioner. Solatron Series. Instruction Manual

Size: px
Start display at page:

Download "Three-Phase Power Conditioner. Solatron Series. Instruction Manual"

Transcription

1 Three-Phase Power Conditioner Solatron Series Instruction Manual

2 ii Contents CONTENTS Important Safety Instructions 1 Receiving and Unpacking 2 Moving and Lifting 2 Storage 2 Installation 3 Mechanical Considerations Electrical Considerations To Maintain UL1012 Listing Lug Size Tables To Install the Solatron Unit 6 Startup 7 Normal Operation 7 Automatic Internal Bypass 8 Circuit Breaker Operation 9 Surge Suppression 9 Alarms 9 Remote Alarm Relay Dry Contacts Status Indicator Lights 10 Maintenance 10 General Condition

3 SOLATRON SERIES iii CONTENTS Maintenance Log 11 Troubleshooting 11 Troubleshooting Table Specifications 13 Contact Information 14 Warranty 14 FIGURES Figure 1: Component Layout Figure 2: Overview Figure 3: Status Indicators

4 1 Important Safety Instructions Important Safety Instructions The Solatron unit and related equipment must be installed, operated, and maintained in accordance with this manual. After complying with all of the information in this manual, it should be saved for future reference. Failure to follow all instructions herein will cause death, severe injury, or significant equipment damage, and Only properly qualified and trained personnel should be permitted to install, service, and operate this equipment. Follow all safe electrical work practices. Use all applicable personal protective equipment (PPE). The unit is intended to be installed where it is not accessible to the general public. Access to this equipment must be limited to properly qualified and trained personnel. Dangerous and potentially lethal voltages are present inside the enclosure of the unit; the hazard of electric shock, arc flash, and explosion are present. Under no circumstances should anyone be permitted to operate or energize the unit without all covers in place, doors closed, and all safeguards in place. Under no circumstances should anyone be permitted to reach into or perform any action within the enclosure for maintenance, decommissioning, or other purposes without properly de-energizing and grounding the unit. The transformer coils must be discharged of any potential static charge. The unit must be installed in accordance with all applicable federal, state, and local codes. The unit enclosure must be properly grounded using the provided ground connections. The unit must be installed a safe distance from any combustible material unless separated and shielded by appropriate fire resistance and heat dissipative barriers in accordance with the National Electrical Code (NEC) and all applicable local codes. The unit must only be installed in locations suitable for the level of protection afforded by the enclosure type. No claim is made that these instructions cover all possible details or variations in unit manufacture or address all possible contingencies that might be encountered during the installation, operation, or maintenance of the unit. All questions, concerns, informational needs, or problems that arise regarding receiving, unpacking, moving, lifting, storing, installing, operating, or maintaining the unit which are not sufficiently addressed herein should be referred to SolaHD.

5 SOLATRON SERIES 2 Receiving and Unpacking Prior to removing any shipping or packing material, the unit must be immediately inspected upon receipt for any indication of damage sustained during shipping. During unpacking, inspect the inside and outside of the unit for any dents, scrapes, bent or loose parts, water entry, moisture, or any other signs of damage. If there is any reason to believe that the unit has been damaged: Note the damage on the shipping documentation and notify the carrier. Document and photograph any damage found. Contact the shipping company to file a claim if necessary or SolaHD Customer Service. Moving and Lifting The Solatron unit must be lifted by the base only using a pallet jack or forklift. The center of gravity may not be in the center of the unit. Use appropriate procedures for handling unbalanced loads. Do not lift the Solatron from the top. Ensure that the capacity of the lifting equipment is appropriately sized for lifting and moving the Solatron. Contact SolaHD Technical Support if there are any questions or concerns regarding moving or lifting the unit. Storage Prior to installation, the Solatron must be stored in a location which prohibits the entry of liquid or moisture into the enclosure. Condensation must not be allowed to form on the internal components. Contact SolaHD Technical Support if there are any questions or concerns regarding storage.

6 3 Installation Installation The Solatron unit must be installed in an area appropriate for industrial electrical equipment, which includes but is not limited to the following characteristics: Concrete or other non-combustible, non-flammable floor adequate to support the weight of the unit. Adequate ventilation. Free from combustible or flammable materials, liquids, gases, or dust. Secure from unauthorized access by the general public. Consistent with the NEMA duty rating of the enclosure (NEMA 1). Contact SolaHD Technical Support if there are questions or concerns regarding installation. Mechanical Considerations Cable entry and exit must be made through the sides or top of the enclosure. Cable entry and exit penetrations must be made by the end user. Debris from creating cable penetrations must not be allowed on any component within the enclosure. The input and output connection locations and phase sequence are shown in Figure 1. The unit must be installed with the clearances shown in Figure 2. Only the top, front, and rear enclosure panels are removable. The front panel can only be removed with the input circuit breaker handle in the OFF (OPEN) position. Remote Alarm Contacts Input Circuit Breaker Output Distribution Blocks Auxiliary Circuit Breakers (CB2, CB3) Control Board Figure 1: Component Layout Front View

7 SOLATRON SERIES Status Indicator Lights See Detail A Mounting Holes (4X) 3/8 Clearance Figure 2: Overview Over-temp Normal Bypass Detail A: Status Display Lights (Front Panel Figure 3: Status Indicators 4

8 5 Installation Electrical Considerations The nominal input voltage applied to the Solatron unit shall be as listed on the unit nameplate. The nominal operating frequency must match the nameplate frequency. The maximum continuous load must not exceed the kva nameplate rating. The unit must be grounded using the provided ground lugs. The unit must be installed in a location appropriate for industrial electrical equipment, which includes but is not limited to the following characteristics: Compliance with IEEE 519. The input voltage waveform shall maintain 5% or less THD. If the THD percentage exceeds this value, the unit s performance may be adversely affected. To Maintain UL1012 Listing: Each AC output power circuit shall be provided with overcurrent protection for all ungrounded conductors. The voltage rating of the overcurrent protection shall not be less than the rating of the circuit which with which it is used. The overcurrent protection device shall be a circuit breaker or a fuse evaluated for use as branch circuit protection. The rating of the overcurrent protection device must meet NEC Article 240 requirements. The output overcurrent protection devices are not included with the unit and must be provided by the end user or purchaser. Failure to install the output overcurrent protection devices voids the UL1012 listing for the unit. Lug Size Tables Input Circuit Breaker Lug Sizes (Copper wire only) 208V 240V 480V 600V Cable Range Torque Cable Range Torque Cable Range Torque Cable Range Torque 20kVA #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. 30kVA #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. 50kVA #10-250mcm 14Nm or in-lb. #10-250mcm 14Nm or in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. 75kVA (2) 3/0-250mcm 18Nm or in-lb. #10-250mcm 14Nm or in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. Output Distribution Block Sizes (Copper wire only) 208V 240V 480V 600V Cable Range Torque Cable Range Torque Cable Range Torque Cable Range Torque 20kVA #14-2/0 #14-2/0 #14-2/0 #14-2/0 30kVA #14-2/0 #14-2/0 #14-2/0 #14-2/0 50kVA #14-2/0 #14-2/0 #14-2/0 #14-2/0 75kVA #4-500mcm 56.49Nm or 500in-lb. #4-500mcm 56.49Nm or 500in-lb. #14-2/0 #14-2/0

9 SOLATRON SERIES 6 To Install the Solatron Unit: The following instructions must be followed. Contact SolaHD Technical Support with any questions or concerns. 1. Ensure that all electrical circuits are properly de-energized and locked out. 2. Locate and access the input and output terminal blocks or lugs. 3. Ensure that cable entry points comply with the appropriate NEMA rating of the enclosure (NEMA 1). Cable entry points should not be made through removable or panels. 4. Ensure that the enclosure and internal components are not damaged when installing source and load cabling. 5. Route and restrain the source and load cabling within the enclosure such that it is not in contact with any components, surface, or sharp corners. Note that all source and load wiring must be installed in accordance with all applicable federal, state, and local codes. 6. If required, install appropriately rated remote alarm cabling. Refer to the Alarms section for details and contact ratings. 7. After installation of the source and load wiring, inspect all wiring and internal components for any sign of damage. Ensure that all connections are tight and wires are secure. Report any signs of damage to components, connectors, or wiring insulation to SolaHD Technical Support prior to energizing the unit. 8. Ensure that the internal auxiliary circuit breakers (CB2 and CB3) are ON (CLOSED). 9. Replace all removable panels which were opened during installation. Ensure that all retaining bolts are reinstalled.

10 7 Startup Startup When powering the Solatron unit for the first time, please follow these instructions to ensure normal operation. Note that the unit has been fully tested and calibrated and requires no user adjustments during startup or during normal operation. If there are any questions or concerns, please contact SolaHD Technical Support immediately. If any of the checks during startup are not satisfactory, do not continue to the next step, and refer to the Troubleshooting section or contact SolaHD Technical Support. Ensure that all installation requirements have been met. All field installed wiring must be complete and secure and the unit enclosure must be fully closed and secured. 1. Ensure that the input breaker is OFF (OPEN). 2. Turn ON the upstream source to apply voltage to the Solatron. 3. Turn the input circuit breaker handle to the ON (CLOSED) position. This energizes the control circuits and the transformers. After several seconds, the Normal light is illuminated indicating normal operation. The Bypass and Overtemp lights are not illuminated indicating that there are no alarm conditions. The Solatron is now in normal operation mode and is supplying regulated voltage to the load. Normal Operation The Solatron is considered to be in normal operation mode when the load is supplied with regulated voltage. The unit is in normal operation mode when the following conditions are met: The input circuit breaker is ON (CLOSED). The Normal status indicator light is illuminated. If one or more of the normal conditions are not met, the load may not be supplied with power, or the power supplied to the load may be unregulated. While in normal operation, the Solatron automatically regulates the output voltage to within the output voltage regulation range. The unit selects discrete transformer taps to regulate the output voltage. Each phase of the Solatron is regulated independently to achieve optimum phase balance within the regulation range. When the unit changes taps, it is not unusual to see a change in output voltage equal to approximately the total output regulation range. The output regulation range is +/-3%, so the output voltage may change up to 6% during a tap change. The resulting output voltage remains within the output regulation range.

11 SOLATRON SERIES 8 Automatic Internal Bypass The unit has an automatic internal bypass mode included with the objective of protecting the switching semiconductors in the event of failure modes which include but are not limited to: Semiconductor malfunction Severe over-currents Control board malfunction Power supply malfunction The unit is in automatic internal bypass mode if either or both of the internal auxiliary circuit breakers (CB2 or CB3) are tripped. In most cases, the power to the load is maintained, but the output voltage is not regulated. The unit is in automatic internal bypass mode if all of the following conditions are met: The input circuit breaker is ON (CLOSED) The Bypass status indicator light is illuminated Note that while the automatic internal bypass mode protects the Solatron unit and maintains power to the load, it does not cover all possible contingencies or failure modes. The output terminals of the unit remain energized when in automatic internal bypass mode. To return the Solatron unit from automatic internal bypass mode to normal operation mode: The unit must be de-energized with the input breaker OFF (OPEN) before proceeding. Step 1 Verify that there are no exposed voltages in the electronics compartment. Step 2 Determine which auxiliary circuit breaker(s) have tripped. Step 3 Reset each tripped breaker. Step 4 Once all auxiliary circuit breakers are ON (CLOSED), replace all access panels and close all access doors, and follow the instructions for returning the unit to normal operation (See Startup Section).

12 9 Circuit Breaker Operation Circuit Breaker Operation The input circuit breaker is mechanically operated by a handle on the front panel. To reset the input circuit breaker, it must be turned OFF (OPEN) before it may be turned ON (CLOSED). Do not operate the input breaker by any operating mechanisms other than those on the front panel of the Solatron. Surge Suppression The Solatron contains a transient voltage surge suppression device (SPD) unit which is wired to the input circuit breaker load terminals. Alarms Remote Alarm Relay Dry Contacts The Solatron unit provides dry relay contacts for remotely monitoring the operating condition. Note that the dry relay contacts must be field-wired, and no wire or cable is provided to make such connections. The remote alarm contacts are one set of dry normally closed Form B contacts from a pilot relay available at DIN terminal blocks labeled Remote Alarm. During normal operation, the relay is energized. The relay is de-energized for conditions where the unit may require attention which includes: Automatic Internal Bypass mode ( Bypass light is illuminated). High temperate ( Overtemp light is illuminated). Input circuit breaker is OFF (OPEN). Loss of utility power. The unit is NOT in normal operation Max. Switching Voltage Rated Current Switching Power Min. Switching Voltage UL Contact Ratings Contact Ratings 220VDC, 250VAC 2A 60W, 62.5VA 100uV 30VDC, 2A, 60W (N.O. Only) 110VDC, 0.3A, 33W 220VDC, 0.27A, 60W 125VAC, 0.5A, 62.5W 250VAC, 0.25A, 62.5W

13 SOLATRON SERIES 10 Status Indicator Lights The Solatron unit is equipped with three status indicator lights: Normal, Overtemp, and Bypass. The function of the Normal light is to indicate that the unit is in normal operation mode. The Overtemp light is an indication that the transformer coils may be overheating. If the Overtemp light is illuminated, the unit requires immediate attention. The unit may require cleaning, may have been overloaded, or may be in an environment with a high ambient temperature. Refer to the troubleshooting section for more information. The Bypass light is an indication that the unit is in automatic internal bypass mode. If the Bypass light is illuminated, one or both of the internal auxiliary circuit breakers (CB2 and CB3) may need to be reset. Refer to the troubleshooting section for more information. Note that both the Overtemp and Bypass indicator lights activate the remote alarm contacts. If either of the Overtemp or Bypass lights are illuminated, the unit is not in normal operation, and the Normal light is not illuminated. Maintenance The following items should be addressed at least annually as part of a responsible maintenance routine. If there are any questions regarding the functionality of the unit during any maintenance procedures, please contact SolaHD Technical Support. The included log should be used to log and record maintenance activities. General Condition The Solatron unit must be completely de-energized, including power on the line side of the input circuit breaker and any remote alarm contact power. Failure to observe maintenance may degrade unit performance or cause load power interruption. The entirety of the enclosure should be thoroughly examined for any signs of damage, moisture, or liquids. All wires and cables should be inspected for signs of damaged insulation or overheating. SolaHD Technical Support should be contacted if any of these signs are present. The enclosure should be free from dust and debris. The unit should be cleaned in accordance with good cleaning practices for industrial electronic equipment.

14 11 Maintenance Log Maintenance Log Installation Date: Model #: Serial #: Inspection/ Maintenance Date Personnel Inspections Performed/Actions Taken Troubleshooting Refer to the Important Safety Information section prior to troubleshooting. The Solatron unit must be completely de-energized and locked out prior to troubleshooting. In the event of alarm conditions or unexpected operation, please refer to the Troubleshooting Table on the next page as a guide to return Solatron unit to normal operation. Note that while many conditions are described, no claim is made that all possible contingencies are covered. If the Troubleshooting Table is unclear, the condition is not listed, or the troubleshooting action does not remedy the condition, please contact SolaHD Technical Support: Option #2 or solahd.technicalservices@emerson.com.

15 SOLATRON SERIES 12 Troubleshooting Table Condition Possible Causes Troubleshooting Action The external ambient temperature exceeds the temperature rating of the unit Take measures to reduce the ambient temperature or prevent excessive heating The Overtemp indicator light is illuminated The unit may have been overloaded Confirm that the load does not exceed the nameplate rating of the unit An auxiliary circuit breaker may have TRIPPED The Bypass indicator light is illuminated One or more semiconductor devices may have failed The control board may have failed Follow the steps in the automatic internal bypass section to return the unit to normal operation. If the unit continually enters internal automatic bypass mode, please contact SolaHD Technical Support. The unit may have been overloaded Confirm that the load does not exceed the nameplate rating of the unit The input circuit breaker is TRIPPED The unit may have been overloaded Confirm that the load does not exceed the nameplate rating of the unit. Refer to the Circuit Breaker Operation section for resetting the circuit breaker. The remote alarm contacts are closed The unit may be in an alarm condition or de-energized Re-energize the unit or refer to the status indicator lights on the front of the unit.

16 13 Specifications Specifications Application Model Number 63TXY3ZZ: Nominal Input Voltage X = A (208V), B (240V), C (480V), D (600V) Nominal Output Voltage Y = A (208V), B (240V), C (480V), D (600V) Power Rating / Size ZZ = 20, 30, 50, or 75kVA Phases - Frequency 3 phase, 60Hz nominal Input Voltage Range +10% to -25% of nominal input voltage Output Voltage Regulation +/-3% of nominal output voltage Connections 3 Wire plus ground (Delta) input, 4 Wire plus ground (Wye) output Operating Characteristics Regulation Variation None - regulation constant for 0 to 100% load Overload Capacity 1000% for 1 second, 500% for 5 seconds, 200% for 1 minute % fault clearing Minimum Load No minimum load or part load limitations Load Power Factor No limitations, compatible with all load types Tap Switching No load current interruption on switching regardless of load or power factor Zero Crossing Sensitivity Tap switching not dependent on determining load current zero crossing Harmonic Distortion No distortion added regardless of load or power factor Response Time 1 cycle typical regardless of load or load power factor Efficiency 96% Typical EMI <0.2 gauss at a distance of 3 feet Insulation Resistance 100 megohms from winding to core measured at 500VDC Operating Frequency ±3% of nominal frequency Noise/Surge Suppression & Short Circuit Protection Noise Attenuation 150 db at 100kHz common mode; 65 db at 100 khz normal mode Surge Suppression Included, complies with ANSI/IEEE C26.41 Input Circuit Breaker Included, standard Automatic Bypass Internal auxiliary circuit breakers; No load interruption on activation Construction Technology Electronically-controlled tap switching with series transformer Switching Semiconductors Non-full power semiconductors - individual SCRs do not carry full unit current Controls Microprocessor-based control, RMS based measurements Cooling Natural Convection Transformer Isolation: Delta-Wye Enclosure NEMA 1 Environmental Requirements & Conditions Audible Sound Level Meets or exceeds NEMA standards Temperature - Humidity Ambient 32 to 104 F (0 to 40 C) - Relative humidity 0-95% non-condensing Operating Altitude 0 to 10,000 ft. (3000m)

17 SOLATRON SERIES 14 The information in this manual is provided as a guide for installation, operation, and maintenance and does not affect or exceed SolaHD s obligations under its terms and conditions. Contact Information Website: Technical Services solahd.technicalservices@emerson.com Note that unit specifications are subject to change without notice. Warranty Please see the Terms & Conditions of Sale.

18

19

20 United States (Headquarters) Appleton Grp LLC 9377 W. Higgins Road Rosemont, IL United States T Europe ATX SAS Espace Industriel Nord 35, rue André Durouchez, CS Amiens Cedex 2, France T Canada EGS Electrical Group Canada Ltd. 99 Union Street Elmira ON, N3B 3L7 Canada T Asia Pacific EGS Private Ltd. Block 4008, Ang Mo Kio Ave 10, #04-16 TechPlace 1, Singapore T Latin America EGS Comercializadora Mexico S de RL de CV Calle 10 N 145 Piso 3 Col. San Pedro de los Pinos Del. Álvaro Obregon Ciudad de México T Australia Sales Office Bayswater, Victoria T China Sales Office Shanghai T Middle East Sales Office Dammam, Saudi Arabia T Chile Sales Office Las Condes T India Sales Office Chennai T Korea Sales Office Seoul T Appleton Grp LLC d/b/a Appleton Group. The Emerson logo is a trademark and a service mark of Emerson Electric Co. All other product or service names are the property of their registered owners. Appleton Grp LLC. All rights reserved. 2017, Emerson Electric Co. P/N: A Rev. 6 5/2017

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

INSTALLATION, OPERATION AND MAINTENANCE

INSTALLATION, OPERATION AND MAINTENANCE INLINE HEATER INSTALLATION, OPERATION AND MAINTENANCE MODELS: ILS SERIES 1.5kW 120V SINGLE PHASE BEFORE YOU BEGIN CHECK ALL ELECTRICAL CONNECTIONS TO ALL COMPONENTS WITHIN THE HEATER FOR TIGHTNESS. CONNECTIONS

More information

Bulletin 1608N MiniDySC Dynamic Sag Corrector

Bulletin 1608N MiniDySC Dynamic Sag Corrector User Manual Bulletin 1608N MiniDySC Dynamic Sag Corrector Single Phase Voltage Sag Correction 2...6 Amps (250...750 VA) Important User Information Solid-state equipment has operational characteristics

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

Installation Instructions

Installation Instructions 50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions

More information

Installation Instructions

Installation Instructions Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A Manufactured Home Installation Instructions NOTE: The Dual Point Kit can only be installed on

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

SIMPLIFIED LIGHTING. TRUSTED PROTECTION. CODE MASTER LED LUMINAIRES CLASS I, DIVISION 1

SIMPLIFIED LIGHTING. TRUSTED PROTECTION. CODE MASTER LED LUMINAIRES CLASS I, DIVISION 1 SIMPLIFIED LIGHTING. TRUSTED PROTECTION. CODE MASTER LED LUMINAIRES CLASS I, DIVISION 1 Simplify lighting for harsh and hazardous locations exposed to ignitable vapors and dusts, dirt, moisture and corrosive

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

PANELBOARD PROTECTION ON A GLOBAL SCALE

PANELBOARD PROTECTION ON A GLOBAL SCALE PANELBOARD PROTECTION ON A GLOBAL SCALE INTRODUCTION WHY? No matter what environment, location or power requirement, Appleton panelboards have you and your facility covered. From a petrochemical plant

More information

Installation Instructions

Installation Instructions Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A, Z Chassis Installation Instructions NOTE: Read the entire instruction manual before starting

More information

CurrentGuard TM. Installation, Operation and Maintenance Manual. CurrentGuardTM. Flush Mount. Surge Protective Devices A00

CurrentGuard TM. Installation, Operation and Maintenance Manual. CurrentGuardTM. Flush Mount. Surge Protective Devices A00 TM CGFS u r g e P R O T E C T I O N CurrentGuardTM Installation, Operation and Maintenance Manual 750-0098-006 A00 Surge Protective Devices CurrentGuard TM Flush Mount Table of Contents Guide to Installation

More information

LORAIN CIP 4890/48120 DC Power System

LORAIN CIP 4890/48120 DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides rectifiers, distribution, and controller in one shelf Constant power delivers more current at lower voltages to meet

More information

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM TTC-1 TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION The nvent RAYCHEM TraceTek TTC-1 sensing module is used with TraceTek sensing cables to detect liquid leaks.

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. I 2017 Pentair Equipment Protection P/N

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. I 2017 Pentair Equipment Protection P/N CLIMAGUARD Air-to-Air Outdoor Heat Exchangers TX23, TX33, TX38, TX52 Models INSTRUCTION MANUAL Rev. I 2017 Pentair Equipment Protection P/N 10-1008-221 87976519 TABLE OF CONTENTS Warranty and Return Policy...2

More information

MODELS 304GC, 304GCX, 314GC, and 314GCX

MODELS 304GC, 304GCX, 314GC, and 314GCX 2562109A REV. A1 0317 Printed in U.S.A. MODELS 304GC, 304GCX, 314GC, and 314GCX INSTALLATION AND SERVICE INSTRUCTIONS FOR SELECTONE Limited Warranty This product is subject to and covered by a limited

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

Powerohm Resistors Digital HRG System

Powerohm Resistors Digital HRG System Installation and Operating Instructions Powerohm Resistors Digital HRG System This manual provides general information, installation, operation, maintenance, and system setup information for the Powerohm

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Quartzone. Infrared Quartz Tube & Metal Sheathed Electric Heaters. Owner s Manual. File E COMFORT HEATERS for INDOOR* and OUTDOOR** USE

Quartzone. Infrared Quartz Tube & Metal Sheathed Electric Heaters. Owner s Manual. File E COMFORT HEATERS for INDOOR* and OUTDOOR** USE Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath

More information

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM 216279-000 rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM IDENTIFYING YOUR SYSTEM IOM216279-000 The HOTSTART heating system is designed to heat fluids for use in marine

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

Liebert PPC Second Generation Power Distribution Cabinet

Liebert PPC Second Generation Power Distribution Cabinet Liebert PPC Second Generation Power Distribution Cabinet Emerson Network Power Delivers The Packaged Power Solution Creating high quality power is a major step towards protecting the operation of a critical

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS GENERAL INDEECO Industrial Control Panels are designed to provide years of trouble free operation if properly

More information

SECTION ISOLATED POWER SYSTEMS

SECTION ISOLATED POWER SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM) Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay 905-0005-01 (100/25 PPM) 905-0005-02 (200/35 PPM) 1. INTRODUCTION Your COSTAR VC carbon monoxide detecting ventilation

More information

SAFETY INFORMATION AND WARNINGS

SAFETY INFORMATION AND WARNINGS This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-8-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

MODELS ASHP, ASHH, ASUP, and ASUH

MODELS ASHP, ASHH, ASUP, and ASUH 2562229A REV. A 1210 Printed in U.S.A. MODELS ASHP, ASHH, ASUP, and ASUH INSTALLATION AND SERVICE INSTRUCTIONS blank page INSTALLATION AND SERVICE INSTRUCTIONS FOR MODELS ASHP, ASHH, ASUP, AND ASUH SAFETY

More information

Watt-Muncher Load Bank Manual WATT-MUNCHER. Portable Load Bank. 6 June 2018 Simplex Service Page 1 of 13

Watt-Muncher Load Bank Manual WATT-MUNCHER. Portable Load Bank. 6 June 2018 Simplex Service Page 1 of 13 WATT-MUNCHER Portable Load Bank 6 June 2018 Simplex Service 800-637-8603 Page 1 of 13 This manual was last revised: 6 June 2018 For up-to-date information on this product or others, please contact Simplex

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120 LowProfile Series: 080 and 120 Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA 1.800.647.1911 www.tpssurge.com LOWPROFILE InstaLLatIOn, OPERatIOn

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

LORAIN CSP DC Power System

LORAIN CSP DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides more space for revenue generating equipment Constant power delivers more current at lower voltages to meet load or recharge

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

! The Caution Symbol (exclamation point) alerts you to a CAUTION, a safety or I&M NUMBER: 316-42-10-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

Installation Manual CARBONATOR With Plain-Water Booster

Installation Manual CARBONATOR With Plain-Water Booster CORNELIUS INC One Cornelius Place Anoka, MN 55303-6234 Telephone (800) 238-3600 Facsimile (763) 422-3246 Installation Manual CARBONATOR With Plain-Water Booster IMPORTANT: It is the responsibility of the

More information

FF-SR Series. FF-SR25933 Two-hand Safety Control Module FF-SR25933

FF-SR Series. FF-SR25933 Two-hand Safety Control Module FF-SR25933 Two-hand Safety Control Module FF-SR Series FEATURES Complies with the Machinery Directive 98/37/EC and UL 508 Type III C per EN 574, Category 4 per EN 954-1 Inputs for two dual-contact pushbuttons 0,5

More information

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS PART 1 GENERAL 1.01 SUMMARY SECTION 26 22 00 (16460) - LOW-VOLTAGE TRANSFORMERS A. Section Includes: 1. Dry-Type Distribution And Specialty Transformers Rated 1000 V And Less. a. General-Purpose Distribution

More information

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4. I&M NUMBER: 316-42-3-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to elements

More information

PME. Series Enclosures. Battery Enclosure (BE) Field Upgrade Installation Instructions. Effective: January, Alpha Technologies

PME. Series Enclosures. Battery Enclosure (BE) Field Upgrade Installation Instructions. Effective: January, Alpha Technologies PME Series Enclosures Battery Enclosure (BE) Field Upgrade Installation Instructions Effective: January, 2004 Alpha Technologies Power Alpha Technologies. Protecting The Power in Communications. Preface

More information

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES C US INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES Made in the USA by: Goodman Manufacturing Company, L.P. I0-240B 2550 North Loop West, Suite 400, Houston, TX 77092 www.goodmanmfg.com

More information

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-2-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to elements

More information

SPA HEATER INSTALLATION, OPERATION AND MAINTENANCE

SPA HEATER INSTALLATION, OPERATION AND MAINTENANCE SPA INSTALLATION, OPERATION AND MAINTENANCE MODELS: ST SERIES 5.5 & 11kW 240V SINGLE PHASE BEFORE YOU BEGIN CHECK ALL ELECTRICAL CONNECTIONS TO ALL COMPONENTS WITHIN THE FOR TIGHTNESS. CONNECTIONS CAN

More information

Mains Power Filter 970MF10 970MF20. Installation Instructions

Mains Power Filter 970MF10 970MF20. Installation Instructions Mains Power Filter Installation Instructions and Table of Contents 1.0 Warnings... 3 2.0 Introduction... 3 3.0 Quick Installation Overview... 3 4.0 Typical Installations... 3 5.0 Protection Concepts...

More information

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features: PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fast-transfer central battery inverters with the following features: 1. Emergency-only circuits. 1.2 DEFINITIONS A. LCD: Liquid-crystal display. B.

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

Installation Instructions Type XPMC Air Heater for Hazardous Locations

Installation Instructions Type XPMC Air Heater for Hazardous Locations Installation Instructions Type XPMC Air for Hazardous Locations 1 PF500-1 161-302639-005 May 2017 XPMC Air for Hazardous Locations 12", 2 Heat Sinks with Fixed Thermostat 12", 2 Heat Sinks with Adjustable

More information

CLM-SERIES SOLID STATE POWER CONTROLLER. Product Highlights: Model Numbers:

CLM-SERIES SOLID STATE POWER CONTROLLER. Product Highlights: Model Numbers: CLM-Series - Solid State Power Controller - Overview CLM-SERIES SOLID STATE POWER CONTROLLER The CLM-Series is a 12 output, solid state power controller. It provides fast switching with low loss solid

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

Installation Instructions

Installation Instructions 50ES---A, 50EZ---A, 50VL---A, 50VG---A, 50VR---A, 50VT---A, 604D--- ---A, 607C--- ---A, 607E,--- ---A, 704D--- ---A, 707C--- ---A, 707E--- ---A PA3G --- --- A, PH3G --- --- A SMALL PACKAGED PRODUCTS Electric

More information

CLM-SERIES SOLID STATE POWER CONTROLLER. Product Highlights: Model Numbers:

CLM-SERIES SOLID STATE POWER CONTROLLER. Product Highlights: Model Numbers: CLM-Series - Solid State Power Controller - Overview CLM-SERIES SOLID STATE POWER CONTROLLER The CLM-Series is a 12 output, solid state power controller. It provides fast switching with low loss solid

More information

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3 Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3 Manufactured by SJE-Rhombus Installation Instructions and Operation/Troubleshooting Manual 7000 Apple Tree Avenue Bergen, New York 14416 Phone:

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL 216300-000 rev2 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM FOR HAZARDOUS LOCATIONS MODEL OSE OSX (this page intentionally left blank) IDENTIFYING YOUR SYSTEM IOM216300-000 The HOTSTART

More information

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

4 & 8-POINT ANNUNCIATORS Instruction Manual

4 & 8-POINT ANNUNCIATORS Instruction Manual 4 & 8-POINT ANNUNCIATORS Instruction Manual 8 Field Selectable Sequences All Common ISA Sequences 4 or 8-Point (Channel) Monitoring Free Replaceable Message Labels Type 4X, NEMA 4X, IP65 Front Universal

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Installation Instructions

Installation Instructions 50ES--A, 50EZ--A, 50VG--A, B, 50VL--A, B, 50VR--A, 50VT--A, B 604D-- --A, 607C-- --A, B, 607E-- --A, 704D-- --A, 707C-- --A, B, 707E-- --A PA3G -- -- A, PH3G -- -- A, PA4G, PH4G PAD3, PHD3, PAD4, PHD4,

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

Model GIT 4 Gutter Snow and Ice Melting Control

Model GIT 4 Gutter Snow and Ice Melting Control We manage heat Model GIT 4 Gutter Snow and Ice Melting Control Part Number 19556 Installation and Operation Manual WARNING Hazard of electrical shock. Follow all safety procedures. Any installation involving

More information

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Installing the Cisco ONS FAP-4 Fuse Alarm Panel Installing the Cisco ONS 15454-FAP-4 Fuse Alarm Panel Product Number: 15454-FAP-4= This document explains how to install, test, operate, and maintain the Cisco ONS 15454-FAP-4 fuse alarm panel. This document

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00 I&M NUMBER: 316-42-16-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

Power Management Module-c (PMM-c)

Power Management Module-c (PMM-c) Power Management Module-c (PMM-c) 60 160 kva Installation, Operation and Maintenance 11/2013 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider

More information

IMPORTANT INSTRUCTIONS

IMPORTANT INSTRUCTIONS IMPORTANT INSTRUCTIONS W Fan Force Electric Space Heater DANGER ELECTRIC SHOCK OR FIRE HAZARD Figure 1 Covers all W Series models WARNING Read Carefully - These instructions are written in an effort to

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

INSTALLATION INSTRUCTIONS MODEL PA-250 AND PA-500 BOOSTER AMPLIFIER

INSTALLATION INSTRUCTIONS MODEL PA-250 AND PA-500 BOOSTER AMPLIFIER 273 Branchport Avenue Long Branch, N.J. 07740 (908) 222-6880 INSTALLATION INSTRUCTIONS MODEL PA-250 AND PA-500 BOOSTER AMPLIFIER GENERAL: The Series PA-250 and PA-500 Watt Booster Amplifiers are designed

More information

Corning LSE 6L Digital Water Bath

Corning LSE 6L Digital Water Bath Corning LSE 6L Digital Water Bath INSTRUCTION MANUAL Models 6783 (120V US) 6784 (230V EU) Table of Contents 1.0 Warning 1 2.0 Safety Information 1 3.0 Package Contents 1 4.0 Unpacking 2 5.0 Installation

More information

ESP TECHNOLOGIES LIMITED

ESP TECHNOLOGIES LIMITED Alarm Technology ESPAN-01 Series Annunciator System Combination type User Manual (Rev. 1) ESP TECHNOLOGIES LIMITED www.esptechno.com Content Page Introduction 2 General Description 2 Overview - Annunciator

More information

Property risk solutions

Property risk solutions Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions

More information

Surna 25-Ton Chiller Operating & Maintenance Manual

Surna 25-Ton Chiller Operating & Maintenance Manual www.surna.com 303.993.5271 Surna 25-Ton Chiller Operating & Maintenance Manual Models: 300F3-3. 300F4-3, 300FW-3 Revised: July 2015 Table of Contents Warranty Information 4 Limited Warranty 4 Limitation

More information

Fisher LCP100 Local Control Panel

Fisher LCP100 Local Control Panel Instruction Manual LCP100 Local Control Panel Fisher LCP100 Local Control Panel Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications... 2 Installation... 3 Hazardous Area Classifications

More information

Installation Instructions

Installation Instructions EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 Installation Instructions NOTE: Read the entire instruction manual before starting

More information

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model COSTAR 24VC-e Single Relay

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model COSTAR 24VC-e Single Relay Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model COSTAR 24VC-e Single Relay Part No. 905-0000-09 Replacement Sensor Module is Part Number 905-0001-09 1. INTRODUCTION Your COSTAR 24VC-e carbon

More information

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc flash detection units. Product picture Arc flash detection units VAMP 120 and 121(D) are extremely fast arc flash detection units for LV and MV switchgear and controlgear. The units are especially designed to increase the safety and to minimize

More information

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-5-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Watlow heaters are built to comply with UL and CSA dielectric requirements, it may be

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

MIRUS International Inc.

MIRUS International Inc. MIRUS International Inc. INSTALLATION, OPERATION AND MAINTENANCE GUIDE HARMONY Series Transformers Harmony Transformers HARMONY Owner's Manual H-M001-A2 HARMONY Warranty Seller warrants to the Ultimate

More information

WATLOW IND. Thermostat Control Installation & Maintenance Manual I&M NUMBER

WATLOW IND. Thermostat Control Installation & Maintenance Manual I&M NUMBER age:1 re Installation Check to make sure that the thermostat received is the same as that ordered. Check capillary for kinks and damage to the bulb Safety Fire and electrical shock may result if thermostats

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA. OWNER S MANUAL Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750 Proudly Made in the USA support@aquacomfort.com 888-475-7443 Manufacturing High Quality, High Efficiency Heat

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

Technical Manual. Operation and installation cooling units PKS 3000 SERIES 115V / 230V / 460V. Version 1.0, March 2018

Technical Manual. Operation and installation cooling units PKS 3000 SERIES 115V / 230V / 460V. Version 1.0, March 2018 Technical Manual Operation and installation cooling units PKS 3000 SERIES 115V / 230V / 460V Version 1.0, March 2018 Preface The skills and information provided in the ORIGINAL OPERATING MANUAL are required

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

ENVIRO-PAK. Operation and Maintenance Manual. Manufacturer of

ENVIRO-PAK. Operation and Maintenance Manual. Manufacturer of ENVIRO-PAK H Series Single Chamber Compactor Operation and Maintenance Manual Manufacturer of ENVIRO-PAK SAFESUB WINDCHILLER 800-737-5533 WWW.ENVIRO-PAK.NET SALES@ENVIRO-PAK.NET 4308 West Admiral Doyle

More information