1 NFPA 70E Electrical Safety in the Workplace KTR Associates Engineering Solutions Joseph Deane, PE
2 Goal for Today Better understanding of NFPA 70E Raise the awareness of Electrical Hazards Why the sudden focus What one must do to become 70E compliant
3 Topics To Be Discussed Define Electrical Hazards Safety Numbers Industry Standards/Government Regulations What is an Arc Flash? Sample Arc Flash Study PPE Requirements
4 Why do we need Electrical Safety? Provide a safe work environment Reduce injuries Comply with regulations Reduce liability Reduce operating costs
5 What are the Electric Hazards? Shock Arc Flash Arc Blast
6 Terms and Definitions Electric Shock (Contact): Occurs when electricity (electric current) passes through the human body. Electric current passing through the chest area may result in death.
7 Terms and Definitions Arc Flash: Short circuit through air; defined as the rapid release of energy due to an arcing fault between two phase conductors (such as bus bar) or neutral or ground. Arc Blast: Heating of the air and vaporization of metal creates a pressure wave than can damage hearing and other injuries. Flying metal parts are a hazard.
8 Terms and Definitions Incident Energy: Energy dissipated during an arc fault, or arc flash event. Measured in cal/cm 2. Arc Thermal Performance Value (ATPV): Minimum energy causing the predicted onset of second degree burns. A second degree burn is 1.2 cal/cm 2.
9 Why the Recent Focus? NFPA 70E standard now recognizes Arc Flash as a serious consequence and requires a Flash Hazard analysis be performed on facilities. OSHA has updated its Electrical Safety Procedures for the first time in 25 years. Effective date of OSHA s updated regulations is August 13, 2007
10 Electrical Statistics At least one person a day is electrocuted in the workplace everyday Over half of the deaths are from working live electrical circuits less than 600 volts. Average of 4000 non-disabling and 3600 disabling electrical injuries occur in the US.
11 Electrocutions by Year (Construction Safety Council) # Electrocutions
12 Electrical Statistics Five to 10 arc flash explosions occur in electrical equipment every day in the US. Fourth leading cause of occupational fatalities. Over 2000 workers are admitted to burn centers each year.
13 Burn Costs Average burn case costs $12 to $20 Million Average hospital burn unit costs $400K per month Average hospital burn unit stay 3 months
14 Electrical Statistics General Industry One fatality per 300 recordable injuries. Electrical Industry One fatality per 10 recordable injuries.
15 Electrician Survey 97% had experienced an electrical shock. 26% had witnessed an injury. 58% were exposed to the possibility of an injury every day.
16 Facts on Electrical Incidents 80% of electrically related accidents and fatalities among Qualified Workers are caused by Arc Flash. 80% of electrically related accidents and fatalities among Unqualified Workers are caused by Electrocutions. Age 34 is the median age for someone killed working around electricity.
17 OSHA & NFPA 70E OSHA was created in It incorporated the National Electric Code (NFPA 70 standard 1971) into its electrical standard. NFPA 70E Standard was created at the request of OSHA in 1979 to recognize the difference between design and workplace safety. NFPA 70 (NEC) applies to installations (design). NFPA 70E addresses workplace safety.
18 OSHA Regulations OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) CFR 1926 Subpart K (Construction) OSHA recognizes NEC and NFPA 70E as an industry standards.
19 OSHA Regulations OSHA requires companies to follow its regulations and will cite companies for non-compliance under the General Duty Clause: which states, each employer shall furnish to each of its employees a place of employment that is free from recognized hazards that are likely to cause death or serious physical harm.
20 OSHA Regulations OSHA is also citing companies for the following: 29 CFR (a)(1)(i): requires the use of protective equipment when working where a potential electrical hazard exists. 29 CFR (d)(1): requires an employer assessment of all workplace hazards and the use of personal protective equipment.
21 Who is the NFPA? The National Fire Protection Association (NFPA) develops, publishes, and disseminates more than 300 consensus codes and standards intended to minimize the possibility and effects of fire and other risks. Virtually every building, process, service, design, and installation in society is affected by the NFPA documentation (Ex. the National Electric Code NFPA 70).
22 National Electric Code (NFPA 70) Utilized for design and installation of electric facilities Wiring and Protection Wiring Methods and Material Equipment for General Use Special Equipment and Conditions
23 Intent of NFPA 70E Objective is to minimize exposure to electrical hazards for personnel working around electricity. This includes: Electricians Mechanics HVAC technicians Painters Plumbers Carpenters Production Workers
24 Intent of NFPA 70E Define Safe Work Practices to avoid injury. Define the requirements for an Electrical Safety Program. Define the requirements for Training Define the requirements for PPE Applies to all types of employers and facilities, including employees, contractors, and construction workplaces.
25 NFPA 70E Electrical Safety Standard in the Workplace Chapter 1 Safety Related Work Practices Chapter 2 Safety Related Maintenance Requirements Chapter 3 Safety Requirements for Special Equipment Chapter 4 NEC Related Installation Material
26 NFPA 70E covers Public and private buildings Carnivals Industrial Substations Any installation of electrical equipment to the supply of electricity
27 NFPA 70E does not cover Utilities Ships Mines Railways Communication equipment under control of communication utilities
28 NFPA 70E Chapter 1 Article 110 Provides General Requirements Responsibility Electrical Hazard Analysis Training Requirements Electrical Safety Program Article 120 Emphasizes Working Deenergized & Describes the Work Practices Article 130 Provides Requirements for Working On or Near Electrical Components
29 Chapter 1 Responsibility Employers are responsible for providing work practices and procedures. Employees are responsible for implementing them.
30 Chapter 1 Multiemployer Relationship Recognizes that more than one employer may be responsible for hazardous conditions on a worksite. Outside contractors are contractually obligated to the onsite employer. Both employers must share their Electrical Safety Programs with each other.
31 Chapter 1 Multiemployer Relationship Onsite employers and outside contractors shall inform each other: Of existing hazards PPE requirements Safe work practice procedures Emergency procedures Coordination should include a meeting and documentation
32 Chapter 1 Electrical Safety Program What needs to be in it? Scope Philosophy Principles Responsibilities Safety Procedures
33 Chapter 1 Electrical Safety Program PPE Requirements Controls Training Requirements Auditing Other?
34 Chapter 1 Training Requirements Trained to understand the specific risks associated with electric energy. Trained on safe work practices and procedures. Trained on emergency procedures. Training may be both classroom and on the job.
35 Training Session Misc. Real World Examples Refeeding Panels (What needs to be checked?) Transformer Connections (Why they are important) Types of Grounding Systems Explain how voltage is a difference in potential
36 Chapter 1 Electrical Hazard Analysis Requires an electrical hazard analysis, which is a study of a worker s potential exposure to: Shock Arc Flash/Blast It determines the appropriate levels of Personal Protective Equipment (PPE) and work practices.
37 Electric Shock The original purpose of NFPA 70E Determine the voltage to which personnel will be exposed. Boundary Requirements PPE Requirements
38 Exposure to Shock Requires exposure to a difference of potential The National Electric Code reduces this risk under normal conditions. NFPA 70E reduces the risk under abnormal conditions
39 NEC Protects - Normal Conditions
40 70E Protects - Abnormal Condition
41 Effects of Electric Current on the Human Body Amps < 1 ma Barely perceptible 5-10 ma Tingling sensation (annoying) ma Let Go threshold (discomfort) ma Painful, cannot Let Go ma Ventricular fibrillation Amps > 100 ma Cardiac arrest
42 Effects of Electric Current on the Human Body Electric current greater than the Let Go threshold ( current > 20 ma) contracts the human body s muscles. Individuals unable to Let Go an energized line face life threatening damage to their bodies. If this current level continues for an extended period of time, respiratory paralysis is possible. Ventricular fibrillation (uneven pumping of the heart) causes death to lack of oxygen to the brain.
43 Arc Flash/Blast Electrical Arc between Conductors Intense Light Molten Metal Pressure Wave Sound Wave Shrapnel Hot Air Rapid Expansion
44 Dangers of Arc Flash Arcs in enclosures, such as MCCs and switchgear, magnify a blast outward as energy is transmitted to the open side of the enclosure. Fatal Burns (Molten metal at high speed pressure). Falls from ladders (Blast pressure waves). Hearing loss from sound blast.
45 Causes of Arc Flash Contamination Dust, Dirt or Vapor Corrosion Moisture Ingress Dropping tools or equipment Insulation Breakdown/Aging Narrow Gaps
46 NFPA 70E Arc Flash Hazard Analysis A flash hazard analysis shall be done for two purposes: Determine the arc flash protection boundary. Determine the proper PPE (rating of flame retardant clothing). The Flash Protection Boundary is the approach limit from which a person could receive a second degree burn if an arc flash occurs.
47 Sample Arc Flash Study How do you do an Arc Flash Study? Results of an Arc Flash Study
48 IEEE 1584 Standard Guide for Performing Arc Flash Hazard Calculations Performing the Arc Flash Study
49 IEEE 1584 Standard Guide for Performing Arc Flash Hazard Calculations Nine Step Process Collect system and installation data Determine system mode of operation Determine bolted fault currents Determine arc fault currents Find protective device characteristics and arc duration
50 IEEE 1584 Standard Guide for Performing Arc Flash Hazard Calculations Nine Step Process (continued) Document system voltages and equipment class Select working distances Calculate the incident energy Calculate the Flash Protection Boundary From this info, select the proper PPE
51
52 KTR Associates
53 Purpose of Safety Related Work Practices (Article 120) A set of rules that ensure an Electrically Safe Work Condition. De-energizing is safest work condition. Protect employees from: Shock Arc Flash burns Arc Blast injuries
54 Steps to Create an Electrically Safe Work Condition (De-energized state) Check drawings and identify all possible sources Interrupt load current and open disconnects Visually verify opening of contacts where possible Apply lockout/tagout devices according to policy Test voltage and verify operation of tester Apply grounds where necessary
55 Working on or near energized circuits (Article 130) Why work on energized circuits?
56 Examples of working on energized equipment Startup or troubleshooting Life Support systems Emergency systems Ventilation systems for hazardous locations
57 Examples of working on energized equipment Infeasibility due to equipment design or operational limitations Circuits that are part of integral process.
58 NFPA 70E Requirements for Working on or Near Live Parts Complete Energized Electrical Work Permit Perform Hazard/Risk Analysis Select PPE Ensure task specific training Conduct a job briefing
59 Energized Electrical Work Permit Requires written authorization Requires the worker to: Identify and understand the hazards Be a qualified person Wear proper PPE Restrict access to unqualified persons Complete a job briefing
60 No Permit Required When Testing (voltage, current, phasing) Troubleshooting Circuit Identification
61 Approach Distances to Exposed Live Parts
62 PPE Requirements Protect against shock and burns Designed to protect specific areas of the body: Head, face, neck Ear protection Eye protection Body protection Hand and arm protection Foot and leg protection
63 Flash Protection Boundary & PPE When working within the flash protection boundary, PPE must be worn. PPE is determined by the level of incident energy exposure.
64 Personal Protective Equipment (PPE) Flash Hazard Risk Category Range of Calculated incident energy Min. PPE Rating Clothing Required 0 0 to 1.2 cal/cm 2 N/A Untreated cotton to 4 cal/cm 2 4 cal/cm 2 FR shirt and pants 2 4+ to 8 cal/cm 2 8 cal/cm 2 Cotton underwear plus FR shirt and pants 25 cal/cm 2 Cotton underwear plus 3 8+ to 25 cal/cm 2 FR shirt and pants plus FR coveralls 40 cal/cm 2 Cotton underwear plus FR shirt, to 40 cal/cm 2 pants, plus multilayer layer flash suit
65 Personal Protective Equipment (PPE) Category 0 (Min. PPE Arc Rating N/A) Untreated Cotton Safety Glasses Category 1 (Min. PPE Arc Rating 4) Long Sleeve FR Shirt & Pants Hard Hat Safety Glasses Leather Gloves & Shoes
66 Personal Protective Equipment (PPE) Category 2 (Min. PPE Arc Rating 8) Cotton Underwear FR Shirt & Pants Arc Rated Face Shield Safety Glasses Hearing Protection Leather Gloves & Shoes Category 3 (Min. PPE Arc Rating 25) Same as Cat 2 but include FR coveralls & Flash Suit Hood
67 Personal Protective Equipment (PPE) Category 4 (Min. PPE Arc Rating 40) Cotton Underwear FR Shirt & Pants Full Flash Suit & Hood Hearing Protection Leather Gloves & Shoes
68 Labeling NEC Article requires arc flash labeling in electrical enclosures that might be maintained and accessed while energized. Switchboards, panelboards, industrial control panels, MCCs, etc.
69 Arc Flash Labeling
70 Warning Label Examples
71 Recent Example of Arc Flash Incident Electrician using multimeter shorted out resulting in three phase arc flash. Gloves and radiological PPE were melted and he suffered minor burns. Test equipment defective (CEN-TECH Digital Multimeter). No certification from a national testing laboratory.
72 KTR Associates
73 KTR Associates
74 KTR Associates
75 KTR Associates
76 KTR Associates
77 Sample Electrical Power Design Maintenance Mode Switch (utilizing Microprocessorbased Protective Relays Alternate Settings) Control cabinet containing switches to close breakers
78 What must I do to become NFPA 70E compliant? Conduct an Arc Flash hazard analysis. Provide labeling on electrical equipment per NEC article Flash Protection. Document your Electrical Safety Program. Provide training to your employees. Provide the proper tools and PPE for job tasks employee would be performing.
79 Other Issues to Think About Determine Qualified vs Un-Qualified Who s permitted to reset CBs? Anyone? Which methodology should I use for calculating incident energy? NPFA 70E IEEE 1584 Energized Work Permit when do I need this? Circuit Breaker Interrupting Ratings When do I apply OSHA ?
80 Don t Learn Safety by Accident KTR Associates
81 Don t Learn Safety by Accident Stop! Think! Then Act! NFPA 70E is your guide for Electrical Safety in the Workplace
82 Questions Thank-you for your interest!
NFPA 70E Electrical Safety in the Workplace
NFPA 70E Electrical Safety in the Workplace Objectives What NFPA 70E covers Understand Arc Flash, Incident Energy, & Flash Protection Boundary Standards, Enforcement, & Safe Practices Arc Flash Hazard
More informationSafety Meeting Topic #37 NFPA 70E What is it?
Safety Meeting Topic #37 NFPA 70E What is it? The National Fire Protection Association (NFPA) 70E is the standard for Electrical Safety Requirements for Employee Workplaces and is a supplement to the NFPA70
More informationApplying the 2012 NFPA 70E. Arc Flash Standard
Applying the 2012 NFPA 70E Arc Flash Standard Suncoast Industrial Services, Inc. 80-6A Industrial Loop N. Orange Park, Fl 32073 904-269-4403 904-269-4404 (fax) wehbysis@suncoastind.com 1 Suncoast Suncoast
More informationHESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove
HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove Jim Dungar, P.E. Principal Engineer Schneider Electric Engineering Services Jim.dungar@schneider-electric.com (920-766-8012)
More informationElectrical Safety Compliance: NFPA 70E
Electrical Safety Compliance: NFPA 70E From Graybar and Schneider Electric Risks associated with shock and electrocution from inadvertent contact with energized parts have long been recognized as a threat
More informationNFPA 70E Electrical Safety & Arc Flash Training
NFPA 70E Electrical Safety & Arc Flash Training OSHA 1910.332(a) Training, 1910.332(a) Scope. The training requirements contained in this section apply to employees who face a risk of electric shock that
More informationGuide to Compliance with the Electrical Workplace Safety Standards in the United States
Guide to Compliance with the Electrical Workplace Safety Standards in the United States July 2011/1910DB1102 by Joseph H. Weigel, Product Manager Schneider Electric USA, Inc. Make the most of your energy
More information2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100
Significant Changes to the NFPA 70E Standard 2012 Edition Tech Topics: Standards & Codes Note 4, Issue 1 Peter Walsh, PE Sr. Field Engineer Points of Interest: Arc-Rated (AR) vs. Flame-Resistant (FR) Training
More informationPROTECTING AGAINST ARC FLASH HAZARDS
PROTECTING AGAINST ARC FLASH HAZARDS Presented by: Andrew J. Fitzpatrick, P.E. Electricity Simply stated electricity is the flow of electrons Electricity is governed by laws: Ohms Law : V=IR Kirchoff s
More information6/23/ National Electrical Contractors Association and Intec, Inc.
2012 National Electrical Contractors Association and Intec, Inc. 1 Palmer Hickman Director of Codes and Standards electrical training ALLIANCE Jim Dollard Safety IBEW 98 Objectives Explain why work should
More informationArc Flash Protection Training - NFPA 70e Electrical Safety
Arc Flash Protection Training - NFPA 70e Electrical Safety Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq
More informationNFPA 70E Edition Update
NFPA 70E- 2018 Edition Update Paul Colangelo- STSC, CHST, CET, CRIS National Director of Compliance Programs ClickSafety 1 ASSE Construction Practice Specialty Quarterly Meeting 11/17/2017 Agenda Overview
More informationNFPA 70E Update: Key Changes You Need to Know to Assure Compliance
NFPA 70E Update: Key Changes You Need to Know to Assure Compliance Presented by: Andrew Reisinger EHS International Inc. Thursday, August 22, 2013 1:30 p.m. to 3:00 p.m. Eastern 12:30 p.m. to 2:00 p.m.
More informationElectrical Hazards and NFPA-70E: Protecting Your Employees
Electrical Hazards and NFPA-70E: Protecting Your Employees Presented By Mark B. Haskins, MS, CSP Practical Safety Solutions, LLC At the CBIA Safety Health and Wellness Conference May 22, 2014 PRESENTATION
More informationElectrical Safety for Facility Managers and Building Owners
CEU s Copy of Slides Evaluation Form Follow up information Disclaimer. This seminar was produced to help explain the importance and need for electrical safety specifically for Facility Managers. It does
More informationThe Basics Arc Flash Protection
2008 The Basics Arc Flash Protection An arcing fault can be defined as the flow of current through a path where it is not intended to flow Rob Vajko 12/15/2008 What is an Arc Flash? An arc flash starts
More informationT22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards
T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards v2-5058-co900h Copyright 2016 Rockwell Automation, Inc. All Rights Reserved. 1 Agenda 1. Background 2. Related Electrical
More informationMay is National Electrical Safety Month, an AND THE ELECTRICAL INSPECTOR. by Mark Hilbert and Laura L. Hildreth
by Mark Hilbert and Laura L. Hildreth AND THE ELECTRICAL INSPECTOR May is National Electrical Safety Month, an annual effort to help reduce electricallyrelated fatalities, injuries, and property loss both
More informationDEMYSTIFYING FR CLAIMS: AN ERGODYNE WHITE PAPER
DEMYSTIFYING FR CLAIMS: AN ERGODYNE WHITE PAPER Each year, hundreds of burn injuries and deaths are recorded from workers encountering open flame and high heat or exposure to flash fires and electrical
More informationYour Global Automation Partner. Minimizing Arc Flash Exposure in Industrial Applications. White Paper - W1000
Your Global Automation Partner Minimizing Arc Flash Exposure in Industrial Applications White Paper - W1000 Industrial environments present multiple safety challenges, including fire hazards that require
More informationIEEE Std IEEE Recommended Practice for Electrical Installations on Shipboard Safety Considerations
IEEE Std 45.5-2014 IEEE Recommended Practice for Electrical Installations on Shipboard Safety Considerations Presented by Dennis K. Neitzel, CPE, CESCP Director Emeritus Keeping People Safe from Electrical
More informationNFPA 70E Elevates Safety. with Heightened Risk Awareness
NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness Next Page NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness: Significant Changes Since 2012 Compel Updated Electrical Safety Training
More informationWebinar November 12, 2014
Webinar November 12, 2014 Dennis L. Mater dennis.l.mater@dupont.com FR Apparel Sales Technical Leader North America Webinar Overview Introduction Hazard Risk Types Contrast Short Duration Fire and Arc
More informationArc Flash Analysis. Arc flash hazard analysis is required to determine the risk to personnel, warn them of the
GROUP Arc Flash Analysis Arc Flash Hazard Analysis : Arc flash hazard analysis is required to determine the risk to personnel, warn them of the hazards, and to instruct working personals as to what kind
More informationNECA. Standard for Electrical Safety in the Workplace
4/23/2018 N E R C e- A di st N rib ot ut Fo io r n NECA Significant Changes to the 2018 NFPA 70E Standard for Electrical Safety in the Workplace NFPA 70E Standard for Electrical Safety in the Workplace
More informationNECA S System Approach to Electrical Safety for NFPA 70E
NECA S System Approach to Electrical Safety for NFPA 70E NECA s Systems Approach to NFPA 70E Easy to understand NFPA 70E employer requirements, Provides Supervisors with key on the job information, De-energize
More information2014 National Electrical Code & NFPA 70E/Arc Flash
Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the
More informationELECTRICAL SAFETY GUIDELINE
ELECTRICAL SAFETY GUIDELINE November 2015 Electrical Safety Guidelines Table of Contents I. General II. General Electrical Safety A. Definitions B. Circuit Breaker Loads C. Electrical Grounding D. Electrical
More informationPromoting Electrical Safety through NFPA 70E Standards Adherence
Promoting Electrical Safety through NFPA 70E Standards Adherence October 2018 Kim Cavaliero-Keller, MELTRIC 1 PROMOTING ELECTRICAL SAFETY INTRODUCTION Electrical injuries claim hundreds of lives each year
More informationNECA S System Approach to Electrical Safety for NFPA 70E
NECA S System Approach to Electrical Safety for NFPA 70E NECA s Systems Approach to NFPA 70E Easy to understand NFPA 70E employer requirements, Provides Supervisors with key on the job information, De
More informationSEL Arc-Flash Solutions
SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment
More informationSUMMARY: Policy Title: Electrical Safety Work Practice Program. Policy Number: UNIV-EHS 430 Policy Approved: January 2014
Policy Title: Electrical Safety Work Practice Program Policy Number: UNIV-EHS 430 Policy Approved: January 2014 Policies Superseded: FINA-730 Policy Management Area: Environmental Health and Safety Created/Revision(s):
More informationSEL Arc-Flash Solutions
SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment
More informationBrian McCauley December 2017
Brian McCauley December 2017 ELECTRICAL SAFETY COMPLIANCE & NFPA 70E 2018 Agenda 1 Introduction Electrical Safety Basics Electrical Safety Statistics NFPA 70E 2018 Updates PPE Questions A Little bit of
More informationArc Fault Detection Devices (AFDDs) Protecting People and Property
Arc Fault Detection Devices (AFDDs) Protecting People and Property Singapore Standard : CP5 Code of practice for electrical installations - Foreword 2 BS 7671 : the 18 th Edition report Short Brief 3 BS
More informationPREPARING YOUR ORGANIZATION FOR NFPA 70E 2015
PREPARING YOUR ORGANIZATION FOR NFPA 70E 2015 Presenter Name Date JOSE DE LA MAZA April 27, 2016 Region IX VPPPA Safety Summit Agenda 1 Electrical Safety Basics Electrical Safety Statistics OSHA & NFPA
More informationNATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY
A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -
More informationSALISBURY ASSESSMENT SOLUTIONS
SALISBURY ASSESSMENT SOLUTIONS Electrical engineering services for a safe and compliant workplace Electrical Safety Program Assessment - Safety Training Arc Flash Hazard Analysis - Power Systems Engineering
More informationThe Electrical Safety Guide
Leviton Learning Lab Presents The Electrical Safety Guide An Educational Training Manual for Industry Professionals Learning Lab Series a EDUCATION & TRAINING - Source: www.hospitalconnect.com Electrical
More informationYour Turnkey Solution for Mitigating the Hazards of Arc Flash Incidents in the Workplace
Your Turnkey Solution for Mitigating the Hazards of Arc Flash Incidents in the Workplace ith today s powerful, complex electrical distribution systems, shock isn t the only danger facing those who work
More informationArc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702
Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 by Reza Tajali, Schneider Electric Engineering Services Summary 1.0 Abstract 2.0 OSHA and NFPA Rules 3.0 Use of NFPA 70E
More informationPREVIEW COPY. Table of Contents. Annexes and Supplemental Materials Lesson One Article 90: Introduction and Purpose... 3
Table of Contents Lesson One Article 90: Introduction and Purpose... 3 Lesson Two Articles 100 and 105: Terms and Definitions... 17 Lesson Three Article 110: General Requirements for Work Practices...
More informationImplementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation
Implementing an Energized Electrical Work Program SESHA Hill Country Chapter May 22, 2009 Brett Jay Davis, PE Zephyr Environmental Corporation bdavis@zephyrenv.com, 512 879-6628 Presentation Outline 1.
More informationNFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC
NFPA 70E Arc Flash Considerations for MV Equipment By: Dominik Pieniazek, P.E. dominik@hv-eng.com HV Engineering, LLC http://sites.ieee.org/houston/ Full link for PDF copies of presentations: http://sites.ieee.org/houston/communities/ie
More informationProfessional Seminar. The Electrically Safe Workplace. Understanding the NFPA 70E Electrical Safety Standard, 2012 Edition ...
Professional Seminar The Electrically Safe Workplace Understanding the NFPA 70E Electrical Safety Standard, 2012 Edition Includes Complete Copy of NFPA 70E, 2012 Edition! Learn the Key Concepts of NFPA
More informationChanges to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC
Changes to NFPA 70E - The Role of PdM &Safe PdM Work Practices Tim Rohrer Exiscan LLC Tim@Exiscan.com 585-705-7775 Joe Gierlach ABM Joseph.Gierlach@ABM.com 412-394-4678 Preview Electrical Safety Risk Management
More informationArc Flash Mitigation Solutions: A Proactive Approach To Arc Flash Risk
Arc Flash Mitigation Solutions: A Proactive Approach To Arc Flash Risk Unrestricted Siemens Industry, Inc. 2015 All rights reserved. usa.siemens.com/arc-flash Everyone is concerned about the risk of Arc
More informationElectric Fire Pump Controller Inspection, Test & Maintenance Arc Flash Hazard White Paper
Electric Fire Pump Controller Inspection, Test & Maintenance Arc Flash Hazard White Paper March 27, 2017 Prepared by: Tracey D. Bellamy, PE, CFPS Telgian Corporation Submitted on behalf of: The Home Depot
More informationHow many time has your company been asked by an owner or customer to work on equipment energized?
How many time has your company been asked by an owner or customer to work on equipment energized? How many times has an electrician choose to not turn a circuit off because it was an inconvenience? How
More informationJanine Bain Rhonda Lewis Harland Hirst Sandra Olive David Johnson Edward Maurer Kathy Felsten Joe Halle
WEST CENTRAL FLORIDA SAFETY ALLIANCE MEETING NOTES July 20, 2012, 10:00 AM Noon Our thanks to Lanier Upshaw of Lakeland for hosting us at their facility and to Saddle Creek Corporation for sponsoring the
More informationUnderstanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the
More informationIMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS
IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS By Thomas Smith, Product Specialist, Brady Corporation Last updated: February, 2015 The Occupational Safety and Health Administration
More informationHow to reduce exposure to arc flash hazards
GE Electrical Distribution How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not only
More informationethekwini Electricity MV Switchgear flash over, and injury to staff member. Presentation to AMEU Technical Meeting Sept 2009.
ethekwini Electricity MV Switchgear flash over, and injury to staff member. Presentation to AMEU Technical Meeting Sept 2009. By Roy Wienand 1 ARC FASH A bad day at the office for Electricians: ARC FLASH
More informationElectrical Safety Program
Electrical Safety Program Developed by: The Office of Environmental Health and Safety June, 2010 Table of Contents Introduction 3 Scope..3 Definitions.3-5 CSU Electrical Shop...5 Responsibilities.5-6 Employees.....5
More informationHOW TO CHOOSE THE RIGHT PROTECTION FOR FIRES, FLASH FIRES & ARC FLASHES
PAPER HOW TO CHOOSE THE RIGHT PROTECTION FOR FIRES, FLASH FIRES & ARC FLASHES How to Choose the Right Protection for Fires, Flash Fires & Arc Flashes An employee in Arkansas is killed when an overhead
More information2009 NFPA 70E Clearing Up Confusion
2009 NFPA 70E Clearing Up Confusion Contact Info: Brian Downie Project Manager Faith Technologies, Inc. PO Box 627 Appleton, WI 54944 800-274-2345 ext. 6513 brian.downie@faithtechnologies.com Today s Goals:
More informationProtection from Electric Shock and Arc Flash. Meeting OSHA Regulations and NFPA 70E Standards.
Be Smart. Be Safe. Protection from Electric Shock and Arc Flash. Meeting OSHA Regulations and NFPA 70E Standards. ISO 9001:2000 Registered SALISBURY 7520 N Long Ave Skokie Il 60077 Toll Free 877.406.4501
More informationAGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE We are here to make a choice between the quick and the dead Bernard Baruch, U.N. Atomic Energy
More informationVeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage
VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted
More informationNFPA 70E Standard for Electrical Safety in the Workplace. EEI Safety and Health Meeting May 2011
NFPA 70E Standard for Electrical Safety in the Workplace EEI Safety and Health Meeting May 2011 NFPA Structure NFPA 70E Technical Committee reports to: NEC Technical Correlating Committee reports to: NFPA
More informationArc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance
Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance An arc flash can cause serious injury or death to anyone in its path. The National Electrical Code provides
More informationNECA & Salisbury Assessment Solutions Partnership
NECA & Salisbury Assessment Solutions Partnership Contents Intro to Salisbury Assessment Solutions (SAS) - Overview - Tools - Compliance - Training NECA Partnership & History - Salisbury Partnership Advantages?
More informationElectrical Safety Program.
University of North Carolina Wilmington Environmental Health & Safety Workplace Safety Electrical Safety Program GENERAL The UNCW Environmental Health & Safety Department (EH&S) is authorized by UNCW Policy
More informationRutgers Environmental Health and Safety (REHS)
Rutgers Environmental Health and Safety (REHS) Program Name: Laboratory Laser Safety Program Responsible Executive: Executive Director of REHS Adopted: February 20, 2001 Reviewed/Revised: July 10, 2018
More informationWhite Paper. NFPA 70E 2018 Edition Changes and Implications for. Personnel Performing Condition Based Maintenance. Abstract: iriss.
NFPA 70E 2018 Edition Changes and Implications for Personnel Performing Condition Based Maintenance By Rudy Wodrich, P.Eng., MBA, CRL, L1 Thermographer, VP Engineering Services, IRISS Inc. Abstract: The
More informationWelcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo
2017 NFPA Conference & Expo Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard Presented by: Tracey D. Bellamy, PE, CFPS Chief Engineering Officer Telgian Corporation Welcome Instructor
More informationWhite Paper. OSHA and NFPA 70 Understanding NFPA 70 and its. Implications in Electrical Inspections Abstract: iriss.com
OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010 By Martin Robinson, CMRP Level III Thermographer President, IRISS Inc. Abstract: The National Fire Protection
More informationThe safe way to verify the absence of voltage.
VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted
More informationELECTRICAL SAFETY. Jorge Andrade Safety Supervisor CSM, CSA FRCSW. FRCSW, San Diego, CA
ELECTRICAL SAFETY Jorge Andrade Safety Supervisor CSM, CSA FRCSW FRCSW, San Diego, CA. 92135-7058 I 1 Electrical Safety All employers including government activities are to provide employees with a safe
More informationUNDERSTANDING 2015 CHANGES TO NFPA 70E
UNDERSTANDING 2015 CHANGES TO NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the
More informationUNDERSTANDING 2015 CHANGES TO NFPA 70E
UNDERSTANDING 2015 CHANGES TO NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for commercial and industrial facilities TWO STAGE POWER
More informationactoolsupply.com YOUR SINGLE SOURCE FOR INDUSTRIAL ELECTRICAL PROTECTION actoolsupply.com
YOUR SINGLE SOURCE FOR INDUSTRIAL ELECTRICAL PROTECTION 2014 Salisbury Honeywell SK100 pro wear arc flash clothing kit Salisbury Honeywell SK75 pro wear arc flash clothing kit Salisbury Honeywell SK55
More informationDON T GET BURNED BY THE CONFUSION:
DON T GET BURNED BY THE CONFUSION: A Safety Manager s Guide to Understanding FR Rainwear There could be a dark secret lurking in your workplace. While it isn t the kind of bombshell that you d hear about
More informationWHY ELECTRICAL PREVENTIVE MAINTENANCE IS ESSENTIAL TO A SAFE AND PRODUCTIVE WORKPLACE
WHY ELECTRICAL PREVENTIVE MAINTENANCE IS ESSENTIAL TO A SAFE AND PRODUCTIVE WORKPLACE AGENDA SCRWA 14 SEPTEMBER 2016 Definition Why EDPM is essential to productivity Fiscal sustainability Why EDPM is essential
More informationCentennial Energized Electrical Work Permit Instructions
Centennial Energized Electrical Work Permit Instructions PART I. GENERAL INFORMATION DESCRIPTION OF CIRCUIT/EQUIPMENT/JOB LOCATION: The description of the circuit to be worked in an energized state shall
More informationThis page intentionally left blank
This page intentionally left blank TABLE OF CONTENTS ACRONYMS...iii EXECUTIVE SUMMARY... v 1.0 INTRODUCTION... 1 2.0 SUMMARY OF RESULTS... 1 2.1 Personal Protective Equipment... 1 2.1.1 Insulated Gloves...
More informationDANGERS AND HAZARDS OF ENTERING LIVE SUBSTATIONS AND ENCLOSURES Barry Gass Actom Protection and Control
DANGERS AND HAZARDS OF ENTERING LIVE SUBSTATIONS AND ENCLOSURES Barry Gass Actom Protection and Control INTRODUCTION There are many dangers and hazards which have to be taken into account when entering
More informationRegional Training. Seminar. » EasyPower Hands-On» Protective Device Coordination» Arc Flash Hazard Analysis. March 12-16, 2018 Austin, TX
Regional Training» EasyPower Hands-On» Protective Device Coordination» Arc Flash Hazard Analysis Seminar March 12-16, 2018 Austin, TX DoubleTree Austin EasyPower, state-of-the-art Power System Analysis
More informationLicensed Electrician Dies When Electrocuted by 480Volts Incident Number: 03KY115
Licensed Electrician Dies When Electrocuted by 480Volts Incident Number: 03KY115 An example of wires lead electrician was taping in his palm when he was electrocuted. Kentucky Fatality Assessment and Control
More informationFire ground electrocution
Fire ground electrocution By VINCENT DUNN Ret Chief FDNY To survive firefighting, firefighters must know how other firefighters have died fighting fires. Electrocution is one cause of fire ground death.
More informationOSHA-Required Trainings Offered by Ultimate Risk Services
Emergency Action & Fire Prevention Portable Fire Extinguishers Personal Protective Equipment Hazard Communication 1910.38 1910.157 1910.132 1910.133 1910.135 1910.136 1910.138 1910.95 1910.1200 All employees
More informationNFPA 70E STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE 2012 Edition
NFPA 70E STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE 2012 Edition Presented to: IES ALC Fall Conference 2011 Presented by: Carl Johnson Mark Goodacre 2011 NFPA 70E; STANDARD FOR ELECTRICAL SAFETY IN
More informationProperty risk solutions
Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions
More informationFlame Resistant Clothing: Statistics, Standards and Safety
Session No. 570 Flame Resistant Clothing: Statistics, Standards and Safety Introduction Rob Whittenberger President Tyndale Company, Inc. Pipersville, Pennsylvania For over twelve years, the author has
More informationElectric Shock Drowning
Electric Shock Drowning Your logo here Electric Shock Drowning Navigating Changing Code Requirements Slide 1 Electric Shock Drowning - Safety and Maintenance 2 What is Electric Shock Drowning? Electric
More informationContractor Safety. Workplace Safety & Environmental Division
Contractor Safety Workplace Safety & Environmental Division Click to edit Master title style This information is designed for tradespersons and persons supervising tradespersons who are performing work
More information9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.
Chapter 1 GROUNDING AND BONDING 1 Proper grounding practices protect people from the hazards of electric shock and ensure the correct operation of overcurrent protection devices. Grounding is the intentional
More information17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee
17 TH APRIL Switch Board Monitoring Protecting Switchboard Courtesy of ABB. www.fengshengelectric.com.sg Paul Lee Agenda 1. Introduction 2. IEC 61439 3. Why Switchboard Monitoring 4. Switchboard Monitoring
More informationThis section applies to the use of cord- and plug-connected equipment, including cord sets (extension cords).
(B) Portable Electric Equipment. This section applies to the use of cord- and plug-connected equipment, including cord sets (extension cords). (1) Handling. Portable equipment shall be handled in a manner
More informationIR Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows
IR Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows Abstract There exists a dangerous misconception regarding the Arc Rating of IR viewing windows or viewing panes.
More informationSECTION 1-1 SAFETY PRECAUTIONS DOUBLE ARM MIXER CHAPTER 1: SAFETY
SECTION 1-1 SAFETY PRECAUTIONS Peerless mixers are designed and built to operate as safety as possible. However, if the precautions and procedures explained in this manual are not followed at all times,
More informationELECTRICAL CURRICULA OUTLINE CORE CURRICULUM 2015
ELECTRICAL CURRICULA OUTLINE CORE CURRICULUM 2015 Basic Safety (Construction Site Safety Orientation) (12.5 Hours) (Module ID 00101-15) Presents basic jobsite safety information to prepare workers for
More informationElectrical Safety Myths and Facts
Electrical Safety Myths and Facts Copyright Material IEEE Paper No. ESW James R. White Senior Member IEEE Shermco Industries, Inc.2425 E. Pioneer Drive Irving, Texas 75061 jrwhite@shermco.com Abstract
More informationIn the Eye of the Beholder: Electrical Codes from the View of the AHJ and the Designer
Humanizing Health Care Environments 10/17/17 In the Eye of the Beholder: Electrical Codes from the View of the AHJ and the Designer Alex Masterton Professional Engineer II Office of Plans & Construction
More informationHot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope
1. Purpose The purpose of the University of Denver Hot Work policy is to protect personnel and property from a fire caused by hot work. The DU Hot Work policy defines the responsibilities and requirements
More informationFacility Safety Rules Hazard Communication Emergency Procedures Fire Safety. Safety Orientation
Facility Safety Rules Hazard Communication Emergency Procedures Fire Safety Safety Orientation Facility Safety Rules Report all hazards, unsafe acts, unsafe conditions and unsafe equipment to your Supervisor
More informationElectrical Preventive Maintenance (EPM) Program
Electrical Preventive Maintenance (EPM) Program Only qualified and properly trained persons may work on electric circuit parts or equipment. Such persons shall be capable of working safely and shall be
More informationTABLE OF CONTENTS 1 AVO TRAINING INSTITUTE MISSION STATEMENT 2 AVO AT A GLANCE 4 TRAINING LOCATIONS 6 ELECTRICAL CONSULTING SERVICES
TABLE OF CONTENTS Click below to view catalog sections. 1 AVO TRAINING INSTITUTE MISSION STATEMENT 2 AVO AT A GLANCE 4 TRAINING LOCATIONS 6 ELECTRICAL CONSULTING SERVICES 8 AVO ELECTRICAL ENGINEERING DIVISION
More informationCSE. Arc Flash Safety eguide. Sponsor Overview. Preventing Arc Flash Incidents By Design. Integrating Electrical Safety With Design
CSE Arc Flash Safety eguide Sponsor Overview Sponsor Overview At Eaton, we re energized by the challenge of powering a world that demands more. With over 100 years experience in electrical power management,
More information