Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Size: px
Start display at page:

Download "Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture"

Transcription

1 Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT Release 1.2 Issued January 10, 2005 Document Introduction Related Documentation Application Overview Automatic Smoke Control Pullstation Logic Automatic Smoke Control Priorities Manual Smoke Control Auto Command Retry Logic FSCS Assigning the Fire Object Category to Smoke Control Objects Security Administration System Roles and User Accounts Overview UUKL Smoke Control Security Administration Details Security Administration Detailed Procedures Creating a New Role Creating a New User Account Configuring User Profiles Configuring Role Properties Assigning System Access Permissions Design Considerations DX Design Considerations Smoke Control NAE Design Considerations DX-9100 Multi-Story Building Smoke Control Application Application File Location GX Control Logic Point List GX Configuration Parameters Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture 1

2 Smoke Control NAE Application Application File Location Metasys System Extended Architecture Objects Multi-Story Building Smoke Control Floor Above/Floor Below Logic All Floors Logic Lock Alarms Logic Alarm Lockout Interlock Logic FSCS Control FSCS Zone 2 IFC Zone Interlock Definition FSCS Zone 2 3rd Party Zone Interlock Definition FSCS Zone 2 Smoke Interlock Definition FSCS Zone Switch Logic FSCS Floor 2 Supply Fan 1 Logic Floor 2 VMA 1 Logic FSCS Floor 2 Damper 1 Logic FSCS Floor 2 Damper 2 Logic FSCS Floor 2 Zone Smoke LED Logic FSCS Floor 2 Damper 3 Logic FSCS Floor 2 Exhaust Fan 1 Logic FSCS Stairwell Fan 1 Logic FSCS Elevator Fan Logic FSCS Firefighter Control Logic Using Multiple Smoke Control NAEs or NIEs Requirements for Larger Sites Object Limits Site Director Smoke Control NAE FSCS Smoke Control NAE Smoke Control System Connection Overview FSCS Alarms Monitoring the Site Director Smoke Control NAE Monitoring a Smoke Control NIE

3 Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Document Introduction Smoke control applications issue commands to controlled devices that pressurize or exhaust an area of a building. This document describes smoke control for a multi-story building with floor above/floor below pressurization in the Metasys system extended architecture. The smoke control strategy is achieved with the DX-9100 (DX) application and the smoke control Network Automation Engine (NAE) application described in this document, with manual override of the smoke control logic provided by the Fire Fighter s Smoke Control Station (FSCS). Note: These application notes only present an example of one smoke control strategy. Since every building is unique, the details of applying the strategy vary. These application notes can help you develop an appropriate application for your project. Related Documentation Table 1 lists related smoke control documentation. Table 1: Related Documentation For Information On Refer To LIT No./Part No. General smoke control information Logic programming for the DX-9100 controller Single story enclosed shopping mall smoke control Warehouse smoke control Weekly testing of dedicated stairwell pressurization fans Weekly testing of dedicated smoke control dampers Metasys System Extended Architecture Smoke Control System Technical Bulletin GX-9100 Software Configuration Tool Technical Bulletin Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Warehouse Smoke Control with FSCS Override - Metasys System Extended Architecture Weekly Testing of Dedicated Stairwell Pressurization Fans - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture LIT LIT LIT LIT LIT LIT Specific wiring requirements Metasys System Extended Architecture LIT Smoke Control Wiring Technical Bulletin UL 864 UUKL requirements MSEA UL 864 UUKL Compliance Checklist LIT

4 Application Overview This application provides smoke control for a multi-story building. The application logic provides automatic smoke control, floor above/floor below pressurization and exhaust, stairwell and elevator pressurization, and fire fighter manual override. The DX controllers provide field connections, and the DX application provides basic HVAC and automatic smoke control for the multi-story building. The smoke control NAE provides a connection to the FSCS, and the smoke control NAE application provides automatic smoke control and fire fighter manual override for the smoke control system. Automatic Smoke Control Automatic Smoke Control provides the logic for UUKL first incident rule by locking out subsequent alarms from automatic smoke control. Floor Above/ Floor Below logic depressurizes the floor that goes into smoke alarm. The floor above the alarm, floor below the alarm, stairwell and elevator shaft are pressurized. Pressurize and Depressurize commands in automatic smoke control are commanded at a Priority 3. Priority 3 commands are released when the smoke alarm is reset. If a floor, stairwell, or elevator shaft is under smoke control, the FSCS controls the Light-Emitting Diodes (LEDs) next to each FSCS switch to indicate the current status of the fans, dampers, and zone. Status LEDs for a fan show the fan status as On, Off, or in Trouble. Status LEDs for a damper show the damper status as Open, Closed or in Trouble. Status LEDs for a zone (store or mall area) show the zone status as Pressurize mode, Depressurize mode, or Purge mode. The Auto LED for each fan, damper, and zone switch remains on while the point is in automatic smoke control. The logic to check the status of fans and dampers for trouble is initiated when a floor, stairwell, or elevator shaft goes into smoke control. If a fan does not reach its set point within 60 seconds, its Trouble LED on the FSCS is turned on. If a damper does not reach its set point within 75 seconds, its Trouble LED on the FSCS is turned on. After a commanded point goes into Trouble, the Automatic Command Retry logic repeats the command that failed every 60 seconds until the command is successful. Pullstation Logic Pullstations are not allowed to initiate automatic smoke control for individual floors. However, they are allowed to initiate smoke control pressurization for stairwells and elevators. 4

5 Automatic Smoke Control Priorities All automatic smoke control commands are commanded at a Priority 3. Fire fighter manual overrides, issued from the FSCS panel, to pressurize or depressurize zones, are commanded at a Priority 2. Fire fighter manual overrides, done from the FSCS panel, to control individual fans and dampers, are done at a Priority 1. Manual Smoke Control Manual Smoke Control logic is initiated when a fire fighter turns the FSCS Panel Enable key from the Auto position to the Fire Fighter Control position and initiates a manual override of a fan, damper, or zone point from the Auto setting on the FSCS panel. This turns off the Panel Enable switch Auto LED, and turns on the Panel Enable switch Fire Fighter Control LED. There are two levels of manual smoke control. A fire fighter can put a floor in manual smoke control by turning the zone knob to Pressurize, Depressurize, or Purge. The zone smoke control commands are commanded at Priority 2. Priority 2 commands are released when the fire fighter turns the zone knob back to Auto or turns the Panel Enable key back to Auto. A fire fighter can put a point in manual smoke control by flipping a fan toggle switch to On or Off, or a damper or Variable Air Volume (VAV) toggle switch to Open or Close. Individual points are commanded at Priority 1. Priority 1 commands are released when the fire fighter flips the toggle switch to Auto or turns the Panel Enable key back to Auto. Any point that is under manual smoke control activates the trouble checking logic. If a fan does not reach its set point within 60 seconds, its Trouble LED turns on. If a damper does not reach its set point within 75 seconds, its Trouble LED turns on. After a commanded point goes into Trouble, the Automatic Command Retry logic repeats the command that failed every 60 seconds until the command is successful. Auto Command Retry Logic The Auto Command Retry logic is used for fans, dampers, and VMAs. It does a comparison check between the commanded state and the actual device state, to verify that the command was successful. In the event a command to a fan, damper, or VMA fails, possibly because the MCO for the commanded device is on a remote smoke control NAE panel. The additional time required to communicate with the remote smoke control NAE might exceed the command response limit. Therefore, the command is resent every 60 seconds until the command is successful. The Auto Command Retry logic is used when either a device MCO does not match command, a fan, damper, or VMA status does not match its commanded value, or a fan, damper, or VMA trouble input is active. 5

6 FSCS The FSCS panel example (Figure 1) shows the manually controlled devices for Floor 6 only, the elevator supply fan, and stairwell supply fan. The devices for Floor 6 are three dampers, a supply fan, an exhaust fan, and a VAV. The LEDs next to each dial or toggle switch (Table 2) designate the status of each device or zone. The Smoke LED indicates a smoke alarm for the zone (floor).the FSCS in this application has six floors and additional controls not shown here. Figure 1: FSCS Panel Floor 6 Example The LEDs on the FSCS panel (Figure 1) can be set to the following values. Table 2: FSCS LED Blink Condition FSCS LED Value LED Blink Condition 0 LED is off 1 LED is on continuously 2 LED slow blink 3 LED fast blink and Sonalert turns on The FSCS panel is responsible for all Sonalert logic. A Trouble LED is lit when a fan or damper fails to achieve its commanded state, an automatic smoke detector triggers an alarm, or an AI or DI fuse on the DX fails. The LED value is set to 3 or 4, as described in Table 2, and the Sonalert sounds. Pressing the Silence button on the FSCS panel silences the Sonalert and changes the Trouble LED to a slow blink. The Trouble LED remains on slow blink until it is commanded off. The panel starts a timer and resounds the Sonalert within 24 hours if the Trouble LED is not turned off. The Sonalert sounds if the FSCS Panel Enable key is turned from the Firefighter Control position to the Auto position and all zone knobs and point toggle switches are not set to Auto. The FSCS still goes into Auto mode, but the Sonalert reminds the firefighter to set the manual smoke control switches to the Auto position. 6

7 The General Trouble LED turns on to a fast blink if the panel loses N2 communications. Assigning the Fire Object Category to Smoke Control Objects You must assign every object used specifically for smoke control as a Fire object. This limits the control of smoke control devices and points to authorized Fire operators.! WARNING: Risk of serious injury or death if a smoke control object is not assigned as a Fire object! In the event of a fire or smoke control event, devices or points used for smoke control that are not assigned as Fire objects allow those devices and points to be controlled by non-fire authorized operators. It is imperative that every smoke control device or point be assigned as a Fire object. Use the pull down menu to assign the Fire object category (Figure 2). Figure 2: Assigning the Fire Object to Smoke Control Objects 7

8 Security Administration System The Security Administration system authenticates and authorizes users of Metasys system extended architecture applications. The Security Administrator is a browser-based interface that manages all accounts. Use the Security Administrator System to authenticate and authorize users on the Metasys system extended architecture. The Security Administrator creates User Accounts and Roles, and assigns access permissions to each user of the Metasys system extended architecture. Roles and User Accounts Overview Security is based on User Accounts and Roles. Roles are groups of users with a specific function within the Metasys system. To access the system, an individual provides a user account and the correct password. Use letters, numbers, or symbols to create user account passwords. Use the Login button from the logon prompt to send the user s credentials. A unique Session generates when the user s credentials match the logon requirements. UUKL Smoke Control Security Administration Details UUKL smoke control requires that only operators designated as fire operators be able to control the smoke control system. This required the creation of four new roles: 1. Administrator - This is the highest level of control and allows site control of all HVAC and Fire features. 8

9 2. Fire Administrator - This role is a fire manager level setting. It allows for full system control, including system modification or configuration. Figure 3: Fire Administrator Access Permissions 3. Fire User - This role is for most fire field technicians and allows system control and alarm acknowledgement, but not system modification or configuration. Figure 4: Fire User Access Permissions 9

10 4. Fire Limited - This is the lowest of the permissions and only allows the operator to view fire/smoke control devices and alarms. Security Administration Detailed Procedures Creating a New Role To create a new role: 1. From the Security Administration menu bar, select Insert > New Role. The New Role dialog box appears. 2. Fill in the information. 3. Click OK. The New Role appears in the tree. Creating a New User Account To create a new user account: 1. From the Security Administration menu bar, select Insert > New User. The User Properties tab appears. 2. Fill in the information. 3. Click OK. The New User appears in the tree. Configuring User Profiles To configure a user profile: 1. Select the user whom you wish to configure. 2. From the menu bar, select Edit > Properties. The User Properties tab appears. 3. Modify the desired user information. 4. Click OK. Figure 5: Fire Limited Access Permissions 10

11 Configuring Role Properties To configure role properties: 1. Select the user whom you wish to configure. 2. From the menu bar, select Edit > Properties. The User Properties tab appears. 3. Select the Roles tab, then select an Available Role. 4. Click Add. The selected role appears in the Assigned Role list box. 5. Click OK. Assigning System Access Permissions To assign system access permissions: 1. Select the user whom you wish to assign system access permissions. 2. From the main menu, select Edit > System Access Permissions. The System Access Permission dialog box appears. 3. Select an available privilege. 4. Click Add, then click OK to assign the user s System Access Permissions. Design Considerations This DX9100 and Smoke Control NAE application, as it exists in the Metasys System Extended Architecture Smoke Control Library, complies with the UL 864 UUKL Smoke Listing. However, you are responsible for ensuring that the application complies with state and local regulations, and is approved by the Authority Having Jurisdiction (AHJ). You are also responsible for configuring all of the smoke control components, as well as the programming of those components, in order to comply with the UL 864 UUKL Smoke Listing as documented herein. DX Design Considerations A DX will need to provide the following BACnet Binary Value object (BV) points: Zone Pressurize Command Set to true to turn on supply fans Zone Depressurize Command Set to true to turn on exhaust fans BV Auto point Normally set to true. Point is false when a fire fighter turns a fan On or Off, or sets a damper to Open or Close. BV command point for each fan BV feedback point for each fan BV command point for each damper BV open feedback point for each damper BV close feedback point for each damper 11

12 BV point for an Analog Input (AI) Fuse BV point for a Binary Input (BI) Fuse Use the following priorities for commands to DX points: Priority 3 commands from automatic smoke control Priority 2 commands from manual smoke control for zone pressurize, depressurize, and purge. Priority 1 commands from manual smoke control for individual points. For information on the definition and the initial configuration of the Programmable Logic Controllers (PLCs), use the GX-9100 Software Configuration Tool (GX Tool) to examine this program. This application can be expanded for a building with more than six stories. For further details, please contact Field Support Services in Milwaukee. You must define tag names for all points. You must define the hardware location for each object You must name each object with a descriptive name that is unique in the system. An alarm occurs if the command does not equal the condition for any pressurization or exhaust output. Each Binary Output (BO) for pressurization and exhaust outputs must be configured to have its own feedback (proof sensor) input. The FSCS indicates when command does not equal condition. For UL compliance: If DX Digital Inputs (DIs) are used for smoke control, then DI8 must be jumpered and mapped to the smoke control NAE as a normal state of On. If DI8 is off, a critical alarm must be issued at the FSCS to indicate a binary input fuse failure that must be fixed immediately, because the DI is no longer accurate. If DX Analog Outputs (AOs) are used for smoke control, then Analog Output 14 (AO14, voltage) must be wired to Analog Input 8 (AI8, voltage) and the AI must be mapped to the smoke control NAE with a low alarm limit of 20%. If the AI goes below 20%, it indicates the AO has failed because of a blown fuse, which drops the AO to 0V and the AI to 0% (low alarm). The DX is downloaded so that the AO is normally at 5V because its source point is an Analog Constant (ACO) with a default of

13 Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) For specific wiring requirements, refer to the Metasys Smoke Control Wiring Technical Bulletin (LIT ). 13

14 Smoke Control NAE Design Considerations The smoke control NAE reports critical alarms based on the alarm condition, and the alarm can only be cleared by resetting from the Intelligent Fire Controller (IFC) panel or the Firefighter s Smoke Control Station (FSCS). A Programming In Progress BV point is required. You must set this point to true any time you are making changes to the Smoke Control system. This turns on the Programming In Progress LED on the FSCS to let a fire fighter know that changes are currently being made, and the system may not be fully functional. The point must be turned off when changes are complete. A master reset interlock is required. The interlock is true after you press reset on the Intelligent Fire Controller (IFC) panel. Each floor requires a Latched Alarm BV object. The lock alarm logic sets this point to true for the first alarm detected. Each floor requires an Alarm Lockout Interlock. The interlock is true if any latched alarms for other floors is true or the master reset interlock is true. Do not include a floors latched alarm in its own Alarm Lockout Interlock. Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) For specific wiring requirements, refer to the Metasys Smoke Control Wiring Technical Bulletin (LIT ). 14

15 DX-9100 Multi-Story Building Smoke Control Application Application File Location This Metasys system extended architecture smoke control application is located on the Metasys Branch Purchase Package (BPP) CD in the Metasys System Extended Architecture Standard Smoke Control Applications directory. GX Control Logic The GX Tool was used to create the logic for this DX smoke control application. This DX smoke control application resides on each DX-9100 controller used for smoke control. Find more information and guidelines for using the GX Tool in the GX-9100 Software Configuration Tool Technical Bulletin (LIT ). The main GX screen shows the multi-story floor above/floor below smoke control application as user names (Figure 6) or tag names (Figure 7) depending on the view selected. Figure 6: GX-9100 Graphical Layout (User Names) Figure 7: GX-9100 Graphical Layout (Tag Names) 15

16 Point List Table 3 and Table 4 show the hardware and software point requirements for the GX configuration. Table 3: Hardware I/O Requirements Input Requirements Hardware Location Name of Module Engineer Units Req? Description AI1 DA-T F Yes Discharge Air Temp AI3 STATIC-P PSI Yes Static Pressure AI8 AI-FUSE % Yes AO-AI FUSE CHECK DI8 DI-FUSE ON/OFF Yes DI FUSE CHECK Output Requirements Hardware Location Name of Module Engineer Units Req? Description AO1 CLG-VLV % Yes Cooling Valve AO2 INLT-VN OPN/CLO Yes Inlet Vane Control AO14 AO-FUSE % Yes AO FUSE MONITOR DO3 SF-SS ON/OFF Yes AHU SUPPLY FAN STA/ST DO4 EF-SS ON/OFF Yes AHU EXH FAN STA/STO DO5 ODA-DPR % Yes OUTDOOR AIR DAMPER DO6 RA-DPR % Yes RETURN AIR DAMPER DO7 EA-DPR % Yes EXHAUST AIR DAMPER TDO1 ON-DELAY SECONDS Yes TIMER ON DELAY Table 4: Software I/O Requirements (Part 1 of 2) Module Name of Module Engineer Units Req? Description ACO1 DAT-SP F Yes Discharge Air Temp Setpoint ACO2 STATP-SP PSI Yes Static Pressure Setpoint ACO8 AOFUSE-O ON/OFF Yes Manual Reset DCO1 PRESSURE OPN/CLO Yes Inlet Vane Control DOC2 EXHAUST % Yes AO FUSE MONITOR DCO4 OCC- ON/OFF Yes AHU SUPPLY FAN STA/ST NORM DCO6 OAD-AUTO ON/OFF Yes AHU EXH FAN STA/STO DCO7 OAD-OVR ON/OFF Yes Outdoor Air Damper DCO8 RAD-AUTO ACT/INA Yes Return Air Damper Auto DCO9 RAD-OVR OPEN Yes Return Air Damper Override DCO10 EAD-AUTO ACT/INA Yes Exhaust Air Damper Auto DCO11 EAD-OVR OPEN Yes Exhaust Air Damper Override DCO12 SF-AUTO ACT/INA Yes Supply Fan Auto DCO13 SF-OVR OPEN Yes Supply Fan Override DCO14 EF-AUTO ACT/INA Yes Exhaust Fan Auto DCO15 EF-OVR ON/OFF Yes Return Air Damper LRS1 SF-CTL ON/OFF Yes Supply Fan Control 16

17 Table 4: Software I/O Requirements (Part 2 of 2) Module Name of Engineer Req? Description Module Units LRS2 EF-CTL ON/OFF Yes Exhaust Fan Control LRS3 ODADPR-C CLOSE Yes Outdoor Air Damper Close LRS4 RADPR-C CLOSE Yes Return Air Damper Close LRS5 EADPR-C CLOSE Yes Exhaust Air Damper Close LRS6 SF-GO ON/OFF Yes Supply Fan LRS7 ALM-MODE ALM/ NORM Yes Automatic Smoke Control Return Air Damper Control GX Configuration Parameters Figure 8 through Figure 10 show the configuration parameters for the control loops, output points, and programmable logic. PID data values shown are default values and must be tuned upon commissioning. TIMER (TIMER3) - Data User Name : Description : TIMER #1 TYPE 4 TIMER #5 TYPE 0 Input Connection #1--> LRS5 Input Connection #5--> Reset Connection #1--> Reset Connection #5--> Time Period #1 30. Time Period #5 10. Time Units #1 0 Time Units #5 0 TIMER #2 TYPE 0 TIMER #6 TYPE 0 Input Connection #2--> Input Connection #6--> Reset Connection #2--> Reset Connection #6--> Time Period #2 10. Time Period #6 10. Time Units #2 0 Time Units #6 0 TIMER #3 TYPE 0 TIMER #7 TYPE 0 Input Connection #3--> Input Connection #7--> Reset Connection #3--> Reset Connection #7--> Time Period #3 10. Time Period #7 10. Time Units #3 0 Time Units #7 0 TIMER #4 TYPE 0 TIMER #8 TYPE 0 Input Connection #4--> Input Connection #8--> Reset Connection #4--> Reset Connection #8--> Time Period #4 10. Time Period #8 10. Time Units #4 0 Time Units #8 0 Figure 8: Timer 3 Data 17

18 PID (PID1) Data User Name :CLG-CNTL Description :COOLING CONTROL Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level Local Set Pt.(LSP) Ena Startup: 0=N 0 Proport. Band(PB) Startup Out Level Reset Action(TI) Ena Symm Mode: 0=N 0 Rate Action(TD) ExtForce Out Level Standby Bias(BSB) Ena PID to P: 0=N 0 Off Mode Bias(BOF) Remote Mode: 0=N 0 Symmetry Band(SBC) Ena OFF Trans: 0=N 0 Err Deadband(EDB) Process Variable --> AI1 Output Bias(OB) Remote Setpoint --> ACO1 Out High Lmt(HIL) Reference Variable--> Out Low Lmt(LOL) Proportional Band --> Dev H.H.Limit(DHH) OFF Mode Control --> Dev High Limit(DH) Standby Control --> Dev Low Limit(DL) Reverse Action --> Dev L.L.Limit(DLL) External Forcing --> Minimum WSP(MNWS) Output Bias --> Maximum WSP(MXWS) Minimum WSP --> Figure 9: PID1 Data 18

19 PID (PID2) Data User Name :InltVane Description :Inlet Vane Control Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level Local Set Pt.(LSP) Ena Startup: 0=N 0 Proport. Band(PB) Startup Out Level Reset Action(TI) Ena Symm Mode: 0=N 0 Rate Action(TD) ExtForce Out Level Standby Bias(BSB) Ena PID to P: 0=N 0 Off Mode Bias(BOF) Remote Mode: 0=N 0 Symmetry Band(SBC) Ena OFF Trans: 0=N 0 Err Deadband(EDB) Process Variable --> AI3 Output Bias(OB) Remote Setpoint --> ACO2 Out High Lmt(HIL) Reference Variable--> Out Low Lmt(LOL) Proportional Band --> Dev H.H.Limit(DHH) OFF Mode Control --> Dev High Limit(DH) Standby Control --> Dev Low Limit(DL) Reverse Action --> Dev L.L.Limit(DLL) External Forcing --> Minimum WSP(MNWS) Output Bias --> Maximum WSP(MXWS) Minimum WSP --> Figure 10: PID2 Data An alarm is generated: if the command to the fan is On and the feedback does not come On within 60 seconds if the command to the fan is Off and the feedback does not go Off within 60 seconds whenever there is a mismatch between the command and the feedback 19

20 Figure 11: Logic Module Ladder Diagram - PLC1 The PLC1 logic module ladder diagram (Figure 11) logic states: If in Pressurize mode (floor above or below is in alarm) or normal Occupied mode, and the FSCS Supply fan switch is in Auto mode (SF-AUTO) or Override mode (SF-OVR), then start the AHU supply fan. If in Unoccupied mode, then stop/shutdown the AHU supply fan. If AHU supply fan is commanded on, and the FSCS Outdoor Air Damper switch is in Auto mode (OAD-AUTO) or Override mode (OAD-OVR), then start/open the Outdoor Air Damper. If in Pressurize mode (floor above or below in alarm) or Exhaust mode (this floor in alarm), then start a pseudo point called alm-mode. 20

21 Figure 12: Logic Module Ladder Diagram - PLC2 The PLC2 logic module ladder diagram (Figure 12) logic states: If in normal occupied mode and not in alm-mode (not Pressurize or Exhaust), and the FSCS Return Air Damper switch is set to Auto (RAD-AUTO) or Override (RAD-OVR), then start/open Return Air Damper. If in Unoccupied mode or alm-mode, then stop/close the Return Air Damper. If in normal Occupied mode or in Exhaust mode, and the FSCS Exhaust Air Damper switch is set to Auto (EAD-AUTO) or Override (EAD-OVR), then start/open the Exhaust Air Damper. If in Unoccupied mode, then stop/close the Exhaust Air Damper. If Exhaust Air Damper is open, and the time delay has completed, and the FSCS Exhaust Fan switch is in Auto mode (EF-AUTO) or Override mode (EF-OVR), then start the Exhaust Fan. If the Exhaust Air Damper is not commanded to open, then stop the Exhaust Fan. 21

22 Smoke Control NAE Application Application File Location This Metasys system extended architecture smoke control application is located on the Metasys Branch Purchase Package (BPP) CD in the Metasys System Extended Architecture Standard Smoke Control Applications directory. Metasys System Extended Architecture Objects This smoke control NAE application resides on the smoke control NAE and was created with the System Configuration Tool (SCT) to define the required Control System, Interlock, and Multiple Command objects. The Logic Connector Tool (LCT) is used to create the logic within the Control System object. The LCT logic and configuration screens are organized into two sections: Multi-Story Building and FSCS. The Multi-Story Building section shows logic and configuration screens for the floor above/floor below pressurization and exhaust logic, lock alarms, latched alarms, and alarm lockout interlock settings for the stairwells, elevators, and each of the six floors. The FSCS section shows the logic and configuration screens for each of the devices the FSCS controls and/or displays status for. These devices include the Zone Switch, Damper 1, Supply Fan 1, Variable Air Volume Modulating Assembly (VMA) 1, Zone Smoke LED, Damper 2, Damper 3, and Exhaust Fan 1 for each of the six floors. In addition, the logic and configuration screens for the stairwell fans, elevator fans, and Fire Fighter Control is provided. 22

23 Multi-Story Building Smoke Control Floor Above/Floor Below Logic The Floor Above/Floor Below main logic (Figure 13) controls the automatic smoke control. It consists of the inputs, two system blocks, and outputs. The inputs (Figure 14) are one interlock for each floor and a master reset interlock. The Lock Alarms block (Figure 15) locks in the first incident. The All Floors Logic block determines which floors to pressurize and depressurize. Outputs (Figure 16) are binary points within a DX. Each floor has a pressurize and depressurize point. Figure 13: Floor Above/Floor Below Main Logic 23

24 The inputs and the Lock Alarms block is shown in Figure 14. Each floor has one smoke alarm interlock. The Lock Alarms block locks in the first incident. The Master Reset Interlock releases the locked alarms. There is an output alarm for each floor. Only the first floor in alarm is set to true. All other floors are set to false. Figure 14: IFC Alarm Input Points, FSCS Reset Point, and Lock Alarms Block 24

25 The Lock Alarms block and All Floors Logic block (Figure 15) show the outputs from the Lock Alarms block feeding into the All Floors Logic block, and the resulting outputs. Figure 15: Lock Alarms and All Floors Logic Blocks 25

26 The outputs from the All Floors Logic block (Figure 16) connect to zone pressurize and depressurize points in the DX. Stairwells and Elevator shafts also have pressurize points in a DX.. Figure 16: All Floors Outputs to DX Controllers 26

27 All Floors Logic The following screens show the expanded All Floors Logic block that includes a system block for each of the six floors (Figure 17), and a stairwell block and elevator block (Figure 18). Each floor logic has an input for that floors smoke alarm, one for the floor above and one for the floor below. Outputs tell the DX to pressurize or depressurize. Figure 17: All Floors - Floors 1, 2, 3, 4, 5 and 6 Logic 27

28 The Stairwell Logic block and Elevator Logic block (Figure 18) both have an input for each floor, and one pressurize output. Figure 18: All Floors - Stairwell and Elevator Logic The expanded Stairwell Logic block (Figure 19) pressurizes the stairwell if any floor is in smoke alarm or a pull station is active. Figure 19: All Floors - Stairwell Pressurization Logic 28

29 The expanded Elevator Logic block (Figure 20) pressurizes the elevator shaft if any floor is in smoke alarm or a pull station is active. Figure 20: All Floors - Elevator Pressurization Logic 29

30 Lock Alarms Logic The Lock Alarms All Floors system block (Figure 21) has a lock control system block for each floor. Inputs are that floor s alarms, an Alarm Lockout Interlock that is true if there is an alarm on any other floor, and a Master Reset Interlock. Outputs feed into the All Floors logic and to the Latched Alarm point. The latched alarm point is input into the Alarm Lockout Interlock for all other floors. Figure 21: Lock Alarms - All Floors 30

31 The expanded Floor Lock logic (Figure 22) shows the logic for a single floor. The first latch latches the alarm for that floor until it is reset. The second latch latches the first incident. Figure 22: Lock Alarms - Single Floor Lockout Logic Alarm Lockout Interlock Logic The Master Reset Interlock Definition (Figure 23) releases the locked alarms when commanded by the IFC fire panel Reset button. Figure 23: Master Reset Interlock Interlock Definition The Master Reset Interlock Action Table (Figure 24) sets the Manual Latched Alarm Reset to inactive 60 seconds after the IFC fire panel Reset button is pressed. Figure 24: Master Reset Interlock Action Table 31

32 The Alarm Lockout Interlocks for each floor (Figure 25-Figure 30) are displayed below. The Interlock definition includes the Master Reset and the Latch Alarms from all other floors. Do not include the current floor s Latch Alarm. The Floor 1 Alarm Lockout Interlock Definition (Figure 25) locks out all floors except for Floor 1, when Floor 1 is in smoke alarm. Figure 25: Floor 1 Alarm Lockout Interlock Definition The Floor 2 Alarm Lockout Interlock Definition (Figure 26) locks out all floors except for Floor 2, when Floor 2 is in smoke alarm. Figure 26: Alarm Lockout Interlock Definition 32

33 The Floor 3 Alarm Lockout Interlock Definition (Figure 27) locks out all floors except for Floor 3, when Floor 3 is in smoke alarm. Figure 27: Floor 3 Alarm Lockout Interlock Definition The Floor 4 Alarm Lockout Interlock Definition (Figure 28) locks out all floors except for Floor 4, when Floor 4 is in smoke alarm. Figure 28: Floor 4 Alarm Lockout Interlock Definition 33

34 The Floor 5 Alarm Lockout Interlock Definition (Figure 29) locks out all floors except for Floor 5, when Floor 5 is in smoke alarm. Figure 29: Floor 5 Alarm Lockout Interlock Definition The Floor 6 Alarm Lockout Interlock Definition (Figure 30) locks out all floors except for Floor 6, when Floor 6 is in smoke alarm. Figure 30: Floor 6 Alarm Lockout Interlock Definition The Pull Station Interlock Definition (Figure 31) sets the zone to be in active alarm. Its only control is to turn on the stairwell and elevator fans. Figure 31: Pull Station Interlock Definition 34

35 FSCS Control The FSCS Control section contains logic and configuration screens for each of the six floors, the stairwell, the elevator, and Fire Fighter Control. The logic for each floor is the same, with the only difference being the floor name. Floor 2 is used as an example here. FSCS Zone 2 IFC Zone Interlock Definition The FSCS Zone 2 IFC Zone Interlock Definition (Figure 32) includes the Floor 2 IFC Zones for that floor. Figure 32: Zone 2 IFC Zone Interlock Definition Table 5: IFC Point State Table BACnet Point State State 1 - Normal State 2 - Active Alarm State 3 - Fault State 4 - Disable NAE Point State State 1 - Normal State 2 - Active Alarm State 3 - Fault State 4 - Unreliable FSCS Zone 2 3rd Party Zone Interlock Definition The FSCS Zone 2 3rd Party Zone Interlock Definition (Figure 33) includes a point for an optional, third-party, normally open (N.O.) contact input connection. Figure 33: Zone 2 3rd Party Zone Interlock Definition 35

36 FSCS Zone 2 Smoke Interlock Definition The FSCS Zone 2 Smoke Interlock Definition (Figure 34) includes the Zone 2 IFC Zone Interlock and the Zone 2 third-party zone interlock. Figure 34: Zone 2 Smoke Interlock Definition FSCS Zone Switch Logic The FSCS Zone Switch main logic (Figure 35) inputs from the FSCS are Zone Pressurize, Zone Depressurize, Zone Purge, and Firefighter Control switch. Inputs from the DX are Zone Pressurize and Zone Depressurize. Outputs are the Pressurize, Auto, Depressurize, and Purge LEDs on the FSCS panel and the Zone MCO. Figure 35: Zone Control Switch Main Logic The expanded Zone Control system block logic (Figure 36) controls the FSCS Zone LEDs for the zone, depending on the Fire Fighter Control Key setting. The Purge LED is lit if the pressurize and depressurize points in the DX are true. The Pressurize LED is lit if the DX pressurize point is true and the depressurize point is false. The Depressurize LED is lit if the DX depressurize point is false and the pressurize point is true. 36

37 The Auto LED is lit only if the Zone Switch on the FSCS panel is not set to Pressurize, Depressurize, or Purge. The Pressurize, Depressurize, and Purge settings on the FSCS panel are not functional unless the Fire Fighter Control Key has been turned on. If the Fire Fighter Control Key is off, the FSCS Request is set to 0. Figure 36: Expanded Zone 2 Control Switch Logic 37

38 The Zone 2 MCO Action Table is shown in Figure 37. Figure 37: Zone 2 Switch MCO Action 38

39 The FSCS Zone Switch setting determines the state value (Table 6), which in turn determines the smoke control action. Table 6: FSCS Zone Switch State Value FSCS Zone Switch Position State Value Smoke Control Action Pressurize 1 Zone s Supply Fan On Auto 0 Auto Depressurize 2 Zone s Exhaust Fan On Purge 3 Zone s Supply Fan On Zone s Exhaust Fan On 39

40 The Zone 2 Pressurize MCO Action Table is shown in Figure 38. Figure 38: Zone 2 Pressurize MCO Action Table 40

41 The Zone 2 Depressurize MCO Action Table is shown in Figure 39. Figure 39: Zone 2 Depressurize MCO Action Table 41

42 FSCS Floor 2 Supply Fan 1 Logic FSCS Floor 2 Supply Fan 1 (Figure 40) inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 40: Supply Fan 1 Main Logic 42

43 The FSCS and Fan Trouble Control blocks are shown in Figure 41. Figure 41: Supply Fan 1 FSCS and Fan Trouble Control Main Logic The expanded FSCS Fan block logic is shown in Figure 42. Figure 42: Supply Fan 1 FSCS Logic 43

44 The expanded Fan Trouble Control block logic is shown in Figure 43. Figure 43: Supply Fan 1 Fan Trouble Control Logic The Supply Fan 1 Interlock Definition (Figure 44) sets the values that, when reached, trigger a trouble alarm. The definition includes status and reliability points for the DX AO and BI fuses, supply fan reliability and DX offline status. Figure 44: Supply Fan 2-1 Trouble Interlock Definition 44

45 The Supply Fan 1 MCO Action is shown in Figure 45. The Supply Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Supply Fan Auto point is turned off. The Supply Fan Command is a point in the DX to control the fan. Figure 45: Supply Fan 1 MCO Action The FSCS Supply Fan toggle switch setting (Table 7) determines the state value, which in turn determines the smoke control action. Table 7: FSCS Supply Fan 1 Switch State Value FSCS Supply Fan 1 Toggle Switch Position State Value Smoke Control Action On 1 Supply Fan 1 On Auto 0 Auto Off 2 Supply Fan 1 Off 45

46 Floor 2 VMA 1 Logic The VMA main logic (Figure 46) consists of a VMA system control block. Inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 46: VMA Main Logic 46

47 The expanded VMA block consists of two system blocks, the FSCS block and the VMA Trouble Control block (Figure 47). The FSCS block controls the LEDs on the FSCS panel and commands the DX. The VMA Trouble Control block sets the Trouble LED on the FSCS. Figure 47: VMA1 FSCS and VMA 1 Trouble Control Main Logic 47

48 The expanded FSCS block (Figure 48) controls the Open, Close, and Auto LEDs of the FSCS. The Open LED is lit only if the FSCS is in Fire Fighter Control and the VMA Interlock is true. The Close LED is lit only if the FSCS is in Fire Fighter Control and the VMA Interlock is false. The Auto LED is lit only if the toggle switch is not in the Open or Close setting. If the Fire Fighter Control Key is Off, FSCS Request is set to 0. If the Fire Fighter Control Key is On, FSCS Request is set to the following values depending on the position of the toggle switch. Figure 48: VMA 1 Expanded FSCS Logic 48

49 The expanded VMA Trouble Control block (Figure 49) controls the FSCS Trouble LED. The Trouble LED is lit if the VMA is in smoke control and the VMA Interlock has not reached its desired set point within 75 seconds or one of the DX fuses has blown. A VMA is in smoke control if either the DX is in pressurize or depressurize mode, or, the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close. Figure 49: VMA 1 Expanded Trouble Control Logic The VMA 1 Close Interlock Definition (Figure 50) sends the VAV close command as a group, in the event there is more than one VAV. If any VAV in the group fails to close its damper, the FSCS VAV Trouble LED turns on. Figure 50: VMA1 Close Interlock Definition 49

50 The VMA 1 Open Interlock Definition (Figure 51) sends the VAV open command as a group, in the event there is more than one VAV. If any VAV in the group fails to open its damper, the FSCS VAV Trouble LED turns on. Figure 51: VMA 1 Open Interlock Definition The VMA 2-1 Trouble Interlock Definition (Figure 52) sets the values that, when reached, trigger a trouble alarm. The definition includes DX offline status and reliability points for the Network Integration Engine (NIE) Monitor and the VMA Open and Close commands. Figure 52: Trouble Interlock Definition 50

51 The VMA 1 MCO Action is shown in Figure 53. The VAV Auto point is a binary point in the DX to indicate that the VAV is under automatic smoke control. When a fire fighter sets the VMA to open or close, the VAV Auto point is turned off. The VAV Command is a point in the DX to control the VAV. Figure 53: VMA 1 MCO Action The FSCS VAV toggle switch setting (Table 8) determines the state value, which in turn determines the smoke control action. Table 8: FSCS VMA 1 Switch State Value FSCS VAV Toggle Switch Position State Value Smoke Control Action Open 1 Open VAV Damper Auto 0 Auto Close 2 Close VAV Damper 51

52 FSCS Floor 2 Damper 1 Logic Floor 2 Damper 1 (Figure 54) main logic inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 54: Damper 1 Main Logic 52

53 The expanded Damper 1 block (Figure 55) consists of two control systems, the FSCS block, and the Damper Trouble Control block. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED on the FSCS.. Figure 55: Damper 1 FSCS and Damper Trouble Control Main Logic 53

54 The expanded Damper 1 FSCS block is shown in Figure 56. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: Open 1 Auto 0 Close 2 Figure 56: Damper 1 Expanded FSCS Logic 54

55 The expanded Damper 1 Trouble Control block is shown in Figure 57. The Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if either the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close.. Figure 57: Damper 1 Expanded Trouble Control Logic The Damper 2-1 Trouble Interlock Definition (Figure 58) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the NIE Monitor, the exhaust air damper close and open commands, and the DX offline status. Figure 58: Damper 2-1 Trouble Interlock Definition 55

56 The Damper 2-1 MCO Action Table is shown in Figure 59. The Damper Auto point is a binary point in the DX to indicate that the exhaust air damper is under automatic smoke control. When a fire fighter sets the exhaust air damper to open or close, the exhaust air damper Auto point is turned off. The Damper Command is a point in the DX to control the exhaust air damper. Figure 59: Damper 1 MCO Action The FSCS Damper 1 toggle switch setting (Table 9) determines the state value, which in turn determines the smoke control action. Table 9: FSCS Damper 1 Switch State Value FSCS Damper 1 Toggle Switch Position State Value Smoke Control Action Open 1 Open Damper 1 Auto 0 Auto Close 2 Close Damper 1 56

57 FSCS Floor 2 Damper 2 Logic FSCS Floor 2 Damper 2 main logic is shown in Figure 60. Inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 60: Damper 2 Main Logic 57

58 The expanded Damper block (Figure 61) consists of two control blocks: the FSCS block, and the Damper Trouble Control block. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED.. Figure 61: Damper 2 FSCS and Damper Trouble Control Main Logic 58

59 The FSCS block expanded logic is shown in Figure 62. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting.. Figure 62: Damper 2 FSCS Logic 59

60 The expanded Damper 2 Trouble logic is shown in Figure 63. The Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close. Figure 63: Damper 2 Trouble Control Logic The Damper 2-2 Trouble Interlock Definition (Figure 64) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the return air damper close and open commands, and the DX offline status. Figure 64: Damper 2-2 Trouble Interlock Definition 60

61 The Damper 2-2 MCO Action Table is shown in Figure 65. The Damper Auto point is a binary point in the DX to indicate that the return air damper is under automatic smoke control. When a fire fighter sets the return air damper to open or close, the return air damper Auto point is turned off. The Damper Command is a point in the DX to control the return air damper. Figure 65: Damper 2 MCO Action The FSCS Damper 2 toggle switch setting (Table 10) determines the state value, which in turn determines the smoke control action. Table 10: FSCS Damper 2 Switch State Value FSCS Damper 2 Toggle Switch Position State Value Smoke Control Action Open 1 Open Damper 2 Auto 0 Auto Close 2 Close Damper 2 61

62 FSCS Floor 2 Zone Smoke LED Logic The Floor 2 Zone Smoke LED main logic (Figure 66) controls the Zone 2 Smoke LED on the FSCS. Figure 66: Zone Smoke LED Main Logic The Zone Smoke expanded logic (Figure 67) has the following logic: If the zone is in smoke control, turn the Smoke LED on. If the panel status is Off Normal, flash the Smoke LED. Figure 67: Zone Smoke Logic 62

63 The Zone Smoke LED IFC Zone Trouble Interlock Definition (Figure 68) includes points for status and reliability each zone in the list, reliability of the smoke interlock and the status of the IFC Zone Detector Trouble point. Any zone that goes offline or has a status of unreliable will light that zone s trouble LED. Figure 68: Zone Smoke LED IFC Zone Trouble Interlock Definition 63

64 The Zone Smoke LED IFC Zone Detector Trouble Interlock Definition (Figure 69) includes points for reliability each smoke detector in the list. A smoke detector status that goes to unreliable will light that zone s smoke LED. Figure 69: Zone Smoke LED IFC Zone Detector Trouble Interlock Definition The Zone Smoke LED 3rd Party Zone Trouble Interlock Definition (Figure 70) includes a point for reliability of the 3rd party zone interlock and offline status and reliability of the 3rd party zone. Any zone that goes offline or has a status of unreliable will light that zone s trouble LED. Figure 70: Zone Smoke LED 3rd Party Zone Trouble Interlock Definition 64

65 FSCS Floor 2 Damper 3 Logic The Floor 2 Damper 3 main logic is shown in Figure 71. Inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS, and an MCO that commands the DX points. Figure 71: Floor 2 Damper 3 Main Logic 65

66 The Floor 2 Damper 3 expanded logic (Figure 72) consists of two control blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED. Figure 72: Floor 2 Damper 3 FSCS and Damper Trouble Control Main Logic 66

67 The Damper 3 FSCS block logic shown in Figure 73. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: Open 1 Auto 0 Close 2 Figure 73: Damper 3 FSCS Block Expanded Logic 67

68 The expanded Damper Trouble Control block is shown in Figure 74. The damper Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close. Figure 74: Damper 3 Damper Trouble Control Logic The Damper 2-3 Trouble Interlock Definition (Figure 75) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the NIE Monitor, the outside air damper close and open commands, and the DX offline status. Figure 75: Damper 2-3 Trouble Interlock Definition 68

69 The Damper 3 MCO Action Table is shown in Figure 76. The Damper Auto point is a binary point in the DX to indicate that the outside air damper is under automatic smoke control. When a fire fighter sets the outside air damper to open or close, the outside air damper Auto point is turned off. The Damper Command is a point in the DX to control the outside air damper Figure 76: Damper 3 MCO Action The FSCS Damper 3 toggle switch setting (Table 11) determines the state value, which in turn determines the smoke control action. Table 11: FSCS Damper 3 Switch State Value FSCS Damper 3 Toggle State Value Switch Position Smoke Control Action Open 1 Open Damper 3 Auto 0 Auto Close 2 Close Damper 3 69

70 FSCS Floor 2 Exhaust Fan 1 Logic The Floor 2 Exhaust Fan 1 main logic is shown in Figure 77. Inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 77: Exhaust Fan 1 Main Logic 70

71 The Exhaust Fan 1 expanded main logic (Figure 78) consists of two control blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED. Figure 78: Exhaust Fan 1 FSCS and Fan Trouble Control Logic 71

72 The FSCS block logic is shown in Figure 79. The On LED is lit only if the FSCS is in Fire Fighter Control and the fan is on. The Off LED is lit only if the FSCS is in Fire Fighter Control and the fan is off. The Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: On 1 Auto 0 Off 2 Figure 79: Exhaust Fan 1 FSCS Block Logic 72

73 The Fan Trouble Control block logic is shown in Figure 80. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if, the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off. Figure 80: Exhaust FAN 1 Fan Trouble Control Block Logic The Exhaust Fan 2-1 Trouble Interlock Definition (Figure 81) includes the DX DI Fuse and AO Fuse.. Figure 81: Exhaust Fan 2-1 Trouble interlock Definition 73

74 The Exhaust Fan 2-1 MCO Action is shown in Figure 82. The Exhaust Fan Auto point is a binary point in the DX to indicate that the Fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Exhaust Fan Auto point is turned off. The Exhaust Fan Command is a point in the DX to control the fan.. Figure 82: Exhaust Fan 2-1 MCO Action The FSCS Exhaust Fan 1 toggle switch setting (Table 12) determines the state value, which in turn determines the smoke control action. Table 12: FSCS Exhaust Fan 1 Switch State Value FSCS Exhaust Fan 1 State Value Smoke Control Action Toggle Switch Position On 1 Exhaust Fan 1 On Auto 0 Auto Off 2 Exhaust Fan 1 Off 74

75 FSCS Stairwell Fan 1 Logic The FSCS Stairwell Fan 1 main logic (Figure 83) inputs on the DX are the Fan Commanded State, Fan Present Value, and Stairwell Pressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points.. Figure 83: FSCS Stairwell Fan 1 Main Logic 75

76 The FSCS Stairwell Fan 1 expanded logic (Figure 84) consists of two system blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Fan Trouble LED.. Figure 84: Stairwell 1 FSCS and Fan Trouble Control Main Logic 76

77 The FSCS Stairwell 1 FSCS block logic is shown in Figure 85. The On LED is lit only if the FSCS is in Fire Fighter Control and the fan is on. The Off LED is lit only if the FSCS is in Fire Fighter Control and the fan is off. The Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: On 1 Auto 0 Off 2 Figure 85: Stairwell 1 FSCS Logic 77

78 The Fan Trouble Control module logic is shown in Figure 86. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off.. Figure 86: Stairwell 1 Fan Trouble Control Logic The Stairwell Fan 1 Trouble Interlock Definition (Figure 87) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the stairwell supply fan, the DX offline status, and the stairwell fan failure. The stairwell fan failure alarm is triggered if the stairwell fan fails a weekly test. Figure 87: Stairwell Fan 1 Trouble Interlock Definition 78

79 The Stairwell Fan 1 MCO Action Table is shown in Figure 88. The Stairwell Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. This MCO controls the stairwell fan during manual smoke control. When a fire fighter turns the FSCS Stairwell Fan switch on or off, the stairwell fan responds accordingly and the Stairwell Fan Auto point is turned off. Figure 88: Stairwell Fan 1 MCO Action 79

80 The Stairwell Auto Pressure MCO Action Table (Figure 89) controls the stairwell fan when it is not in manual smoke control. The MCO turns the stairwell fan on if an automatic smoke control device detects smoke, a pullstation is pulled, or an FSCS floor zone switch is turned on. When a fire fighter turns the FSCS Stairwell Fan on or off, the Stairwell Fan Auto point is turned off. Figure 89: Stairwell Auto Pressure MCO Action Table The FSCS Stairwell Fan 1 switch setting (Table 13) determines the state value, which in turn determines the smoke control action. Table 13: FSCS Stairwell Fan 1 Switch State Value FSCS Stairwell Fan 1 Toggle Switch Position State Value Smoke Control Action On 1 Stairwell Fan 1 On Auto 0 Auto Off 2 Stairwell Fan 1 Off 80

81 FSCS Elevator Fan Logic The FSCS Elevator Fan 1 main logic (Figure 90) inputs from the DX are the Fan Commanded State, Fan Present Value, and Stairwell Pressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points.. Figure 90: FSCS Elevator Fan 1 Main Logic 81

82 The expanded elevator fan logic (Figure 91) consists of two control blocks: the FSCS block (Figure 92) and the Fan Trouble Control block (Figure 93). Figure 91: FSCS Elevator Fan 1 FSCS and Fan Trouble Control Main Logic 82

83 The FSCS logic (Figure 92) controls the elevator LEDs on the FSCS panel and commands the DX. The elevator On LED is lit only if the FSCS is in Fire Fighter Control and the elevator fan is on. The elevator Off LED is lit only if the FSCS is in Fire Fighter Control and the elevator fan is off. The elevator Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: On 1 Auto 0 Off 2 Figure 92: FSCS Elevator Fan 1 FSCS Logic 83

84 The Fan Trouble Control logic (Figure 93) sets the elevator fan Trouble LED on the FSCS. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off. Figure 93: FSCS Elevator Fan 1 Fan Trouble Control Logic The Elevator Fan 1 Trouble Interlock Definition (Figure 94) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the elevator supply fan, the DX offline status, and the elevator fan failure alarm. The elevator supply fan failure alarm is triggered if the elevator supply fan fails a weekly test. Figure 94: FSCS Elevator Fan 1 Trouble Interlock Definition 84

85 The Elevator Fan 1 MCO Action is shown in Figure 95. The Elevator Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Elevator Fan Auto point is turned off. The Elevator Fan Command is a point in the DX to control the fan. The FSCS Elevator Fan 1 toggle switch setting (Table 14) determines the state value, which in turn determines the smoke control action. Table 14: FSCS Elevator Fan 1 Switch State Value FSCS Elevator Fan 1 Switch Position Figure 95: FSCS Elevator Fan 1 MCO Action State Value Smoke Control Action On 1 Elevator Fan 1 On Auto 0 Auto Off 2 Elevator Fan 1 Off 85

86 The FSCS Elevator Fan 1 Auto Pressure MCO Action Table (Figure 96) determines the state value, which in turn determines the smoke control action. Figure 96: FSCS Elevator Auto Pressure MCO Action Table FSCS Firefighter Control Logic The FSCS Fighter Control main logic (Figure 97) turns the Fire Fighter Control Auto LED on if the Fire Fighter Control Key is off. It turns the Fire Fighter Control LED on if the Fire Fighter Control Key is on. If the Programming in Progress point is on, the logic turns on the Programming Active LED. This point must be turned on any time changes are being made to the LCT application. Figure 97: Fire Fighter Control LED Main Logic 86

87 The expanded Fire Fighter Control logic is shown in (Figure 98). Figure 98: Fire Fighter Control Logic

88 Using Multiple Smoke Control NAEs or NIEs Requirements for Larger Sites There are larger sites where, due to a large number of objects, several smoke control NAEs or NIEs may be required. If this is the case, then one smoke control NAE must be designated as the FSCS smoke control NAE and must connected directly to the FSCS. A Site Director smoke control NAE is used to monitor all smoke control NAEs and smoke control NIEs. Object Limits Each device and its programmed points use objects. There is a suggested object limit of, for performance purposes, 5,000 objects per smoke control NAE/NIE. When approaching the object limit it is sometimes necessary to add additional smoke control NAEs or NIEs. Site Director Smoke Control NAE The Site Director smoke control NAE provides the ability to monitor and control all devices connected to the smoke control system. FSCS Smoke Control NAE The FSCS smoke control NAE connects directly to the FSCS and monitors the Site Director smoke control NAE. Smoke Control System Connection Overview The example multi-story smoke control system (Figure 99) shows the IFC panels, the FSCS panel, the Site Director smoke control NAE, the smoke control FSCS NAE, a smoke control NIE, and various N1 and N2 devices, communicating over Ethernet and fiberoptic connections. 88

89 Figure 99: Example Multi-Story Smoke Control System

90 FSCS Alarms Table 15 shows the resulting FSCS alarms when any of the devices in the example multi-story smoke control system (Figure 99) go offline. Table 15: Example System Offline Device Alarms Offline Device FSCS Alarm FSCS Smoke Control NAE Offline Site Director Smoke Control NAE Offline Smoke Control NIE Offline NCM 350 Floor 1 Offline NCM 350 Floor 2 Offline Floor 1 DX9100 Offline Floor 2 VMA Offline Monitoring the Site Director Smoke Control NAE General Trouble LED + Sonalert Floors 1,2,3 All Point Trouble LEDs + Sonalert Floors 1,2 All Point Trouble LEDs + Sonalert Floor 1 All Point Trouble LEDs + Sonalert Floor 2 All Point Trouble LEDs + Sonalert Floor 1 Damper and Fan Trouble LEDs + Sonalert Floor 2 VMA Trouble LED + Sonalert The Site Director smoke control NAE must be monitored by the FSCS smoke control NAE in the event it goes offline. The NAE Site Director Monitor Interlock (Figure 100) is used to monitor the Site Director. If the Site Director smoke control NAE goes offline the FSCS Smoke control NAE detects the offline alarm and sends trouble alarms to the FSCS for any floors, devices, or points being controlled by the Site Director smoke control NAE.. Figure 100: Site Director Offline Monitor Point Interlock Definition To monitor the Site Director smoke control NAE: 1. Add a Site Director Monitor point (Figure 101) to the tree in the FSCS folder of the FSCS smoke control NAE 2. Create a folder inside the FSCS folder of the FSCS smoke control NAE for each floor the Site Director smoke control NAE monitors. 3. Inside each newly created floor folder, create a folder for Damper 1, Damper 2, Damper 3, Exhaust Fan 1, Supply Fan 1, VMA 1, and Zone Smoke LED. 90

91 4. Add a Trouble LED Control interlock point for each device in the device s respective folder (Figure 102). Include the Action Table for each device (Figure 103). Figure 101: NAE Connections 91

92 Figure 102: Trouble LED Control Interlock Definition Figure 103: Damper 3-2 Trouble LED Control Action Table 92

93 Monitoring a Smoke Control NIE Each smoke control NIE must be monitored by the Site Director in the event it goes offline. If a smoke control NIE goes offline the Site Director smoke control NAE detects the offline alarm and sends trouble alarms to the FSCS smoke control NAE for any floors, devices, or points being controlled by the smoke control NIE. To monitor a smoke control NIE: 1. Add an NIE monitor point (Figure 105) to the tree in the FSCS folder of the Site Director smoke control NAE (Figure 104). Figure 104: NIE Monitor and Trouble Interlocks 93

94 Figure 105: NIE Monitor Trouble Interlock 2. Add the NIE Monitor point to the Trouble Interlock for the fans, dampers and VMA of every floor the NIE controls (Figure 106). Figure 106: NIE Monitor Trouble Interlock Controls Group 507 E. Michigan Street Milwaukee, WI Metasys is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. 2005Johnson Controls, Inc. 94 Published in U.S.A.

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note Code No. LIT-1201736 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction

More information

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans Introduction

More information

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT-1201754 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLCATN NT Multi-Story Building Floor Above/Floor Below Pressurization and xhaust Logic ntroduction Page 3

More information

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway Code No. LIT-1201993 Software Release 2.1 Issued April 12, 2006 Supersedes July 20, 2005 Document Introduction.................................................

More information

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43 Metasys etwork Technical Manual 636 Objects Section Technical Bulletin Issue Date 696 Fire System Objects Introduction Page *3 Description *3 Purpose *5 Capabilities *7 Functional Diagram *1 Operator Interface

More information

DX-9100/9120 Local Sonalert Logic

DX-9100/9120 Local Sonalert Logic Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPICATION NOTE DX-9100/9120 ocal Sonalert ogic Introduction Page 3 Application Description *3 Design

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Metasys System Extended Architecture Smoke Control System

Metasys System Extended Architecture Smoke Control System Metasys System Extended Architecture Smoke Control System Technical Bulletin MS-NAE5510-0U Code No. LIT-1201684 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

Fire Operator Workstation (Fire OWS) User s Guide

Fire Operator Workstation (Fire OWS) User s Guide Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units... Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 GPL Applications Section Application Note ssue Date 0497 APPLATN NTE Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit ntroduction Page 3 Application Description

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

1.0 Digital Controller

1.0 Digital Controller 1.0 Digital Controller...1 1.1 Display Function Keys...1 1.2 Thermostat Display...2 1.3 Controller hardware input output points... 4 2.0 Sequence of Operation...5 2.1 States of Operation...5 2.2 Modes

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

Feature Summary. I. System

Feature Summary. I. System I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in

More information

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12011781 Software Release 3.12 Issued June 20, 2013 Supersedes April 20, 2012 Refer to the QuickLIT Web site for the most up-to-date version

More information

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application 2273 Application Note 140-1045 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front

More information

Solution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview

Solution Guide. UUKL Smoke Control System.  1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview Solution Guide UL 864, 9th Edition, UUKL Smoke Control Listing Overview Applications Distech Controls UUKL smoke control system can be used for: Dedicated smoke control applications: Used exclusively for

More information

TEC Networked Multi-Stage Economizer Thermostat

TEC Networked Multi-Stage Economizer Thermostat Installation Instructions Issue Date January 19, 2005 TEC2104-2 Networked Multi-Stage Economizer Thermostat Application The TEC2104-2 thermostat is an N2 networked thermostat that provides control of single-

More information

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 Application Note 140-1042 Building Technologies Table of Contents Overview... 4 Hardware

More information

Autoclave Operations Manual

Autoclave Operations Manual UNIVERSITY OF ILLINOIS AT URBANA/CHAMPAIGN - COMPOSITES MANUFACTURING LAB Autoclave Operations Manual Version 1 Written by KRH 2/21/2011 Contents ACCS... 4 Alarms... 7 Main Display Tabs... 7 Process Control

More information

DACC - NMDA BUILDINGS

DACC - NMDA BUILDINGS A PROJECT FOR: LAS CRUCES, NEW MEXICO PROJECT LOCATION LOCATION MAP INDEX OF DRAWINGS: CV001 - COVER SHEET M101 - OVERALL CAMPUS STEAM UTILITY PLAN M102 - DACC DAMA 341 PLAN M103 - DACC LRC & CLASSROOM

More information

P2000 and Metasys System Integration

P2000 and Metasys System Integration P2000 and Metasys System Integration Product Bulletin Code No. LIT-12012141 Software Release 3.14 SP1 Issued June 23, 2017 The Johnson Controls P2000 Security Management System supports the integration

More information

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

ASHRAE Guideline 36 Advanced HVAC Control Sequences

ASHRAE Guideline 36 Advanced HVAC Control Sequences ASHRAE Guideline 36 Advanced HVAC Control Sequences Rick Stehmeyer - Senior Engineer Matt Napolitan, P.E., CCP, CPMP, LEED AP BD+C - Principal Image Source: http://worldatdistance.com/2013/10/07/the-complete-noobs-guide-to-making-a-website//

More information

i-vu CCN 4.0 Owner s Guide

i-vu CCN 4.0 Owner s Guide i-vu CCN 4.0 Owner s Guide CARRIER CORPORAION 2007 A member of the United echnologies Corporation family. Stock symbol UX. 11-808-377-01 07/07 able of Contents ACCESSING YOUR SYSEM... 3 YOUR SYSEM DEAILS...

More information

Table of Contents. i-vu CCN Standard 4.2

Table of Contents. i-vu CCN Standard 4.2 i-vu CCN Standard 4.2 Owner's Guide CARRIER CORPORATION 2009 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-381-01 7/13/2009 Table of Contents Accessing your

More information

AdaptAire. Digital Control System. User Manual

AdaptAire. Digital Control System. User Manual AdaptAire Digital Control System User Manual Rev. 10-22-07 1 Table of Contents OVERVIEW... 6 NETWORKING... 7 ADAPTAIRE DEFAULT SETTINGS... 7 UNIT OPERATING MODES... 8 MDT Controls:... 8 UNIT OFF MODE...8

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

American University Design Standards

American University Design Standards 25 95 00 CONTROL SEQUENCES FOR HVAC PART 1. GENERAL 1.01 SECTION INCLUDES A. Description of Work B. Control Sequences General Requirements C. System Specific Control Sequences 1.02 RELATED DOCUMENTS A.

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-537-01 1/9/2018 Verify that you have the most current version of this document

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

Smoke Control Manual

Smoke Control Manual Smoke Control Manual For BACnet Systems ON BAC-5800 Controller OFF ON BAC-5800 Controller Pressurized Third Floor Stairwell Fan ON OFF BAC-5800 Controller Exhausted Second Floor OFF BAC-5800 Controller

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 2 OCCUPIED MODE: When the program control source calls for

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application 2050 Application Note 140-1136 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware Outputs...

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

RPM1600 Series Room Pressure Monitors

RPM1600 Series Room Pressure Monitors RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT-12012228 Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

CSP-204 CSP-208 CSP-104 CSP-108

CSP-204 CSP-208 CSP-104 CSP-108 Fire Alarm Control Panel CSP-204 CSP-208 CSP-104 CSP-108 Operation manual Firmware version 1.1 csp-x_o_en 06/15 SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk POLAND tel. 58 320 94 00 www.satel.eu CONTENTS

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS CONTENTS 1. System Overview 2. User responsibilities 3. First Line controls and indications 3.1 Logging on to the fire alarm system 3.2 Checking system status

More information

Ion Gateway Cellular Gateway and Wireless Sensors

Ion Gateway Cellular Gateway and Wireless Sensors Page 1 of 9 Account & Network Setup If this is your first time using the Ion Gateway online system site you will need to create a new account. If you have already created an account you can skip to the

More information

Security System. User Guide for the LED Command Center

Security System. User Guide for the LED Command Center Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY

More information

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND

More information

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...

More information

Siemens Thermostats. RDY2000BN Thermostat

Siemens Thermostats. RDY2000BN Thermostat Siemens Thermostats RDY2000BN Thermostat Answers for infrastructure and cities. Introducing the RDY2000BN BACnet Commercial Thermostat Bring more buildings and zones under control Reduce energy costs BACnet

More information

Rotem One Touch. User Manual PRELIMINARY DOCUMENT. Ag/MIS/UmGB /18 Rev 1.0 P/N:

Rotem One Touch. User Manual PRELIMINARY DOCUMENT. Ag/MIS/UmGB /18 Rev 1.0 P/N: User Manual Rotem One Touch Rotem One Touch Ag/MIS/UmGB-2603-06/18 Rev 1.0 P/N: 110741 Rotem One Touch User Manual Revision: N.1.0 of 02.2018 Product Software: 7.14 This manual for use and maintenance

More information

Natural Ventilation Controller with 24vDC drive NVC-1204

Natural Ventilation Controller with 24vDC drive NVC-1204 Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-036 08/11 FEATURES > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) > 3 x 0-10V outputs

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

TEC Networked Single-Stage Thermostat

TEC Networked Single-Stage Thermostat Installation Instructions Issue Date January 19, 2005 TEC2101-2 Networked Single-Stage Thermostat Application The TEC2101-2 thermostat is an N2 networked thermostat that provides control of single-stage

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

BACnet Points List for Single Compressor Water to Water PROSSWWE-01 The network variables will be listed by point type instance convention. 2:1 would mean point type 2, point instance 1. All volatile (Output) type points will revert to the uncommanded values after a power

More information

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

Instruction, Operation, and Maintenance: Controls Software Versions: R37+ Instruction, Operation, and Maintenance: Controls Software Versions: R37+ VPR Series VPRX Series VPRE Series VPRP Series Version October 2011 Table of Contents Safety... 3 Special Design Requests... 3

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626)

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626) PF1000 CONTROLLER for the AQUARIUS I/II DEIONIZED WATER HEATING SYSTEM Heateflex Corporation 405 E. Santa Clara St. TEL: (626)599-8566; FAX: (626)599-9567 Rev. 07 10/19/10, (PF1000) 1 2 TABLE OF CONTENTS

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

Platinum Touch/Rotem One Touch

Platinum Touch/Rotem One Touch User Manual Platinum Touch / Rotem One Touch Platinum Touch/Rotem One Touch Climate Controllers Ag/MIS/UmGB-2583-05/18 Rev 1.0 P/N: 116556 Platinum Touch/Rotem One Touch User Manual Revision: N.1.0 of

More information

ZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until

More information

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11 Table of Contents 1. OVERVIEW... 3 2. SYSTEM LAYOUT... 4 3. SPECIFICATIONS... 8 3.1 SYSTEM COMPONENTS...9 3.2 PLC INPUTS AND OUTPUTS...9 3.3 FUNCTION KEYS...10 3.4 DEFAULT SET POINTS AND TIMERS...10 4.

More information

The Information Contained in this Document is Proprietary and should only be used for Service or Training of Authorized Blodgett Servicers who will

The Information Contained in this Document is Proprietary and should only be used for Service or Training of Authorized Blodgett Servicers who will The formation Contained in this Document is Proprietary and should only be used for Service or Training of Authorized Blodgett Servicers who will be working on the Blodgett XR8 Oven. All other uses are

More information

VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors

VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors Overview 2 This procedure shows how to replace VT8000 Room Controllers already installed, as

More information

Using the Room View Window

Using the Room View Window CIT5 User s Guide 4-1 Chapter 4 Introduction The Room View window uses a tabbed display to present the information about one selected room. This chapter describes the tabs and features of the Room View

More information