LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products

Size: px
Start display at page:

Download "LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products"

Transcription

1 ISO 900 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of single- or 2-stage forced draft oil burners in intermittent operation. Oil throughput up to 0 kg/h. The LOA2... / LOA... and this Data Sheet are intended for use by OEs which integrate the oil burner controls in their products. Use, features Use The LOA... are used for the startup, supervision and control of single- or 2-stage forced draft oil burners in intermittent operation. Yellow-burning flames are supervised with photoresistive detectors QB..., blueburning flames with blue-flame detectors QC... - Forced draft oil burners conforming to E 2 - Oil atomization burners as monoblocks conforming to E 20 General features Specific features - Undervoltage detection - Bridging contact for oil preheater (not with LOA2.A2) - Special versions including models for incinerator plant and flash-steam generators - LOA... with color LED for indicating flame strength and operation CCen HVAC Products

2 arning notes To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! Do not open, interfere with or modify the unit! Before performing any wiring changes in the connection area of the LOA..., completely isolate the unit from the mains supply (all-polar disconnection) Ensure protection against electric shock hazard by providing adequate protection for the burner control s connection terminals Check to ensure that wiring is in an orderly state and that the wires are firmly connected Press the lockout reset button / operating button only manually (applying a force of no more than 0 ), without using any tools or pointed objects Fall or shock can adversely affect the safety functions. Such units may not be put into operation, even if they do not exhibit any damage ounting notes Ensure that the relevant national safety regulations are complied with Installation notes Installation and commissioning work must be carried out by qualified staff Do not mix up live and neutral conductors Always run high-voltage ignition cables separately while observing the greatest possible distance to the unit and to other cables Electrical connection of flame detectors It is important to achieve practically disturbance- and loss-free signal transmission: ever run the detector cable together with other cables Line capacitance reduces the magnitude of the flame signal Use a separate cable Observe the permissible lengths of the flame detector cables (refer to Data Sheets (QB...) and (QC...)) Commissioning notes Commissioning work must be carried out by qualified staff hen commissioning the plant, when carrying out maintenance work, or after longer off periods, make the following safety checks: Safety check a) Burner startup with flame detector darkened b) Burner startup with flame detector exposed to extraneous light c) Simulation of flame failure during operation. For that purpose, darken the flame detector during operation and maintain this state Anticipated response Lockout at the end of «TSA» Lockout after approx. 0 seconds epetition followed by lockout at the end of «TSA» 2/0 CCen HVAC Products

3 Standards Conformity to EEC directives Electromagnetic compatibility EC (immunity) 9 / EEC Low-voltage directive / 2 EEC Service notes aintenance work must be carried out by qualified staff Each time a unit has been replaced, check wiring to ensure it is in an orderly state and that the wires are firmly connected; make the safety checks as indicated in «Commissioning notes» above Use the KF... test adapters for short periods of time only Disposal notes echanical design The unit contains electrical and electronic components and may not be disposed of together with household waste. Local and currently valid legislation must be observed. The housing is made of impact-proof, heat-resistant and flame-retarding plastic. The oil burner control is of plug-in design and engages audibly in its base. The housing accommodates the - thermal-electric sequence switch - flame signal amplifier with the flame relay - lockout reset button with its integrated fault indication lamp Type summary The type references given below apply to burner controls without base and without flame detector. Version Type reference Voltage (VAC) Undervoltage CE t t TSAmax. tn tn t eplacement for detection Standard version LOA2.B2 ²) 220 X x LAI2. LOA2.B ²) 0 X x LOA2.A2 220 X x LAI2. LOA2.A2 220 X x ith remote reset LOA2.B2 ²) 220 X x facility LOA.A2 220 X x For flash-steam LOA2.C2 220 X x LAI generators For incinerator plant LOA2.C2 ¹) 220 X LAB2 LOA2.C ¹) 0 X LOA2.A2 ¹) 220 X Legend ¹) LOA2... and LOA2... are designed for use on incinerator plant where lockout by extraneous light is not desired. These types of oil burner controls are not covered by E 20 ²) ID00 infrared flicker detectors can also be used t t tn tn t TSA Prepurge time Preignition time Long postignition time Short postignition time Interval from establishment of flame to the release of Ignition safety time /0 CCen HVAC Products

4 Ordering Oil burner control without plug-in base refer to «Type summary» Electrical connections refer to Data Sheet 20 - Plug-in base AGK... - Cable holders AGK..., AGK, AGK... - Cable strain relief elements for AGK... Electrical connections refer to Data Sheet 20 - Plug-in base AGK - Plug-in housing AGK - Cover AGK Flame detectors - Photoresistive detectors QB... refer to Data Sheet - Blue-flame detectors QC... refer to Data Sheet Pedestal (empty housing) - To increase the overall height of the LOA...to that of the LAI... / LAB... emote reset module - For use with the LOA2... / LOA... printed circuit board versions Adapter - For replacing LAB... / LAI... by LOA... - o rewiring of plug-in base required AGK2 AK2A2 KF9 Demo case - For showing the functioning of burner controls - efer to Operating Instructions B99 Test case, for making functional tests - For testing burner controls - efer to Operating Instructions B9 Test adapter - For testing burner controls - ith switch for manual startup of burner - ith switch for simulating the oil preheater s release contact - ith 2 pairs of jacks for measuring the flame detector current - efer to ounting Instructions C9 Test adapter - For testing burner controls fitted to the burner - ith signal lamps for program indication - ith 2 jacks for measuring the flame detector current KF9 KF KF KF Test adapter - For testing burner controls fitted to the burner - ith signal lamps for program indication - ith switch for simulating the flame signal - ith holes for checking the control voltages at the tabs of the burner control - ith 2 jacks for measuring the flame detector s resistance KF0 /0 CCen HVAC Products

5 Technical data General unit data ains voltage AC 220 V %...AC 20 V +0 % AC 00 V %...AC 0 V +0 % ains frequency Hz ± % External primary fuse (Si) 0 A (fast) Power consumption approx. VA Degree of protection IP 0, must be ensured through mounting Safety class I Perm. cable lengths - Detector cable laid separately - emote reset laid separately ounting position eight Input current to - - max. m with 00 pf/m line capacitance max. 20 m max. 20 m optional approx. 0 g A (short-time A for max. 0. s) A (excl. current draw of burner motor and oil preheater) ax. perm. current at cos 0. LOA2.B2 LOA2.B LOA2.C2 LOA2.C2 LOA2.C LOA2.A2 LOA2.A2 LOA2.A2 0 A A 2 A 2 A A A A A 2 A. A A A LOA2.B2 A A 2 A 0. A A A LOA.A2 Environmental conditions Transport DI E Climatic conditions class 2K2 echanical conditions class 22 Temperature range C Humidity < 9 % r.h. Operation DI E Climatic conditions class K echanical conditions class 2 Temperature range C Humidity < 9 % r.h. Condensation, formation of ice and ingress of water are not permitted! /0 CCen HVAC Products

6 Flame detectors QB... QC... For measuring circuits and detector cable lengths, refer to Data Sheets (QB...) and (QC...). Type of burner control LOA2.B2 / LOA2.B LOA2.C2 LOA2.C2 / LOA2.C LOA2.B2 LOA2.A2 LOA2.A2 LOA2.A2 in. detector current required (with flame) QB... (typically) ax. perm. detector current (without flame) ax. detector current possible (with flame) 0 µa. µa 20 µa µa. µa µa LOA.A2 0 µa. µa 900 µa Type of burner control LOA2.B2 LOA2.C2 LOA2.B2 in. detector current required (with flame) QC... (typically) ax. perm. detector current (without flame) ax. detector current possible (with flame) 0 µa. µa 0 µa LOA2.B 0 µa. µa 90 µa LOA2.C2 ¹) LOA2.C ¹) LOA2.A2 ¹) LOA2.A2 LOA2.A µa. µa µa LOA.A2 0 µa. µa 0 µa ¹) These types of LOA... may not be used in connection with QC...blue-flame detectors Data given in the above table only apply under the folllowing conditions: - ains voltage AC 20 V - Ambient temperature 2 C easuring curcuit for detector current QB... 2 LOA... bl sw + µa DC v0/002 QC... 2 LOA... bl sw br + µa DC v02/002 Legend µa DC DC microammeter with an internal resistance of i = max. k bl Blue sw Black br Brown QB... QC... Only with LOA... Indication of flame strength Detector current LED lit - ith QB... - ith QC... min. 0 µa ± % min. 0 µa ± % /0 CCen HVAC Products

7 Function Preconditions for startup Burner control is reset Contacts in the line are closed o undervoltage Flame detector is darkened, no extraneous light Undervoltage detection Control sequence in the event of fault An additional electronic circuit ensures that if mains voltage drops below approximately AC V, burner startup will be prevented, or without release of oil lockout will be triggered. henever lockout occurs, the outputs for the fuel valves, the burner motor, oil preheater and ignition equipment will immediately be deactivated (< second). The lockout indication lamp changes to red and terminal 0 («AL») for remote lockout indication receives voltage. This state is also maintained in the event of mains voltage failure. Cause ains voltage failure Extraneous light on burner startup o flame at the end of «TSA» Loss of flame during operation esponse ew start Lockout; with LOA2... / LOA2...: Prevention of start Lockout epetition eset After lockout, the burner control can be reset after seconds (also refer to «arning notes»). Indications Lockout position Flame strength The lockout position is indicated with the lamp integrated in the lockout reset button. Only with LOA... Indication of the flame strength (green LED) is used for checking the flame signal. To ensure reliable burner operation, this LED must be lit. If the green LED flickers or extinguishes during burner operation, the light conditions at the burner are poor, caused by dirt for instance. Operation Only with LOA... hen the contacts of the control thermostat are closed, the orange LED is lit, indicating the start of the oil preheater s heating up phase (if present). /0 CCen HVAC Products

8 Connection diagram and internal diagram Control sequence LOA2.B2 LOA2.B LOA2.C2 EK Si L L x tz2 fr a b T AL y z c d tz e f g K BV F V bl QB QC br sw a0/002 A A B C D BV FS tw t t TSA d0/002 tn t 2 LOA2.A2 LOA2.A2 EK L tz2 tz fr x y z a b c d e f g K F V a0/002 A A B C D Si L T AL BV bl QB QC br sw BV FS tw tn t tn t TSA t d0/002 2 LOA2.C2 LOA2.C LOA2.A2 EK L tz2 x y z fr** a b c d tz e f g K F V a0/002 A A B C D 2 0 T Si L AL BV QB. BV FS tw t tn t TSA d02/002 t 2 fr** ot provided with the LOA2.A2 ) LOA2.C2 / LOA2.C 2) LOA2.A2 /0 CCen HVAC Products

9 Connection diagram and internal diagram Control sequence LOA2.B2 ith AK2 remote lockout reset module EK tz2 tz fr L x y z c d e f g a b F K V T a0/002 A A B C D tw t tn Si L AL SA BV 0 bl QB QC br sw SA BV t TSA t AK2A2 EK2 FS d0/002 2 LOA.A2 ith AK2 remote lockout reset module EK tz2 tz fr L x y z c d e f g LED a b F K V L2 T a09/002 A A B C D tw t tn Si L AL SA BV 0 bl QB QC br sw SA BV t TSA t AK2A2 EK2 FS d0/002 2 Legend AL Alarm device elease contact of oil preheater BV... Fuel valve Oil preheater EK Lockout reset button QB Photoresistive detector EK2 emote lockout reset button QC Blue-flame detector F Flame relay with contacts «fr» bl = blue, br = brown, sw = black fr Bridging contact for release contact of Control thermostat or pressurestat FS Flame signal SA Actuator with automatic setback K Catch of flame relay for locking contact «tz» Safety limit thermostat in the event of premature flame signals or for locking Si External primary fuse the contact when the flame signal is correct T Thermal-electric sequence switch L Indication of faults (red) tz... Contacts of «T» L2 Indication of operation (green) Limit thermostat or pressure switch LED Indication of flame strength (green) V Flame signal amplifier Burner motor Ignition transformer TSA Ignition safety time A Beginning of the startup sequence with burners using an tw aiting time A Beginning of the startup sequence with burners using no t Prepurge time B Time of flame establishment t Preignition time C unning position tn Long postignition time D Controlled shutdown by tn Short postignition time t Interval between flame signal and release of Control signals delivered by the LOA... equired input signals Permissible input signals 9/0 CCen HVAC Products

10 Dimensions Dimensions in mm LOA m0/002 2,, 9, LOA2... LOA... xxxxxxxxxx 2, xxxxxxxxxx 2, 22, m0/000 Status indication, orange Indication of flame strength, green 2 2,, 0 emote lockout reset module AK2A2 + + m0/000 emote lockout reset module for use with the LOA2... / LOA... Printed circuit board with no housing. Degree of protection IP 00, which means that protection against electric shock hazard must be ensured through mounting. Do not place any metal objects in the hatched area. The module must be fitted with the help of spacers made of plastic. Do not use spacers made of metal Subject to change! 0/0 CCen HVAC Products

Oil Burner Controls LOA3... Building Technologies HVAC Products

Oil Burner Controls LOA3... Building Technologies HVAC Products LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of - or 2-stage forced draft oil burners in intermittent operation. Oil throughput up to 0

More information

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division 7 8 ISO 900 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of single- or twostage oil burners with an oil throughput of up to 0 kg/h in intermittent

More information

Oil Burner Controls LOA3... Building Technologies Division

Oil Burner Controls LOA3... Building Technologies Division 7 8 LOA2... LOA... Oil Burner Controls LOA2... LOA... Oil burner controls for the supervision, startup and control of - or 2-stage forced draft oil burners in intermittent operation. Oil throughput of

More information

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products Distribuitor: FLAME POWER SRL 021-3121727 ; 0744-340566 contact@arzatoare.ro ; www.arzatoare.ro 7 128 Oil Burner Control LOA44.252A27 Oil burner control for the supervision, startup and control of 1- or

More information

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44... 7 130 Oil Burner Controls LMO14... LMO24... LMO44... Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Standard versions

More information

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44... 7 130 Oil Burner Controls LMO14... LMO24... LMO44... Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Standard versions

More information

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products 7 418 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of small to medium capacity (without fan) in intermittent operation. The LGA... and this

More information

LGA... Gas Burner Controls. Building Technologies Division

LGA... Gas Burner Controls. Building Technologies Division 7 418 Gas Burner Controls LGA... The gas burner controls are used for supervision, startup and control of atmospheric gas burners of small to medium capacity without a fan in intermittent operation. The

More information

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division 7 418 ISO 9001 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of low to medium capacity, without fan assistance, in intermittent operation. The

More information

Burner controls. Building Technologies HVAC Products

Burner controls. Building Technologies HVAC Products 7 101 Burner controls LE... Burner controls for the supervision of 1- or 2-stage gas or gas / oil burners of small to medium capacity, intermittent operation with or without fan. The LE and this Data Sheet

More information

Burner Controls. Building Technologies HVAC Products

Burner Controls. Building Technologies HVAC Products 7 101 Burner Controls E... Burner controls for the supervision of 1- or 2-stage gas or gas / oil burners of small to medium capacity, operation, with or without fan in intermittent. The E and this Data

More information

Gas Burner Controls. Building Technologies HVAC Products

Gas Burner Controls. Building Technologies HVAC Products 7 101 Gas Burner Controls E... Gas burner controls for the supervision of 1- or 2-stage gas burners of small to medium capacity, in intermittent operation. The E and this Data Sheet are intended for use

More information

Use. The burner controls are certified to EN 230 and EN 298.

Use. The burner controls are certified to EN 230 and EN 298. 7 421 SO 9001 Burner Controls G2... Burner controls for the supervision of single- or two-stage forced draught gas or gas / oil burners of small to medium capacity (typically up to 350 kw) in intermittent

More information

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation.

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation. 7 2 SO 900 Burner Controls Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation. The burner controls are certified to E 230 and E 298.

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

C Note! LGI16... Burner Controls. Building Technologies

C Note! LGI16... Burner Controls. Building Technologies 7 786 Burner Controls LGI16... Burner controls For use on industrial furnaces For burners in continuous operation Without fan control and air pressure supervision Flame supervision - with QR53... / QR55,

More information

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products 7 716 QRC1... for frontal illumination Blue-flame Detectors QRC1... for lateral illumination QRC1... Blue-flame detectors for the supervision of ue- or yellow-burning oil or gas flames. Blue-flame detectors

More information

Infrared Flame Detectors

Infrared Flame Detectors 7 719 Infrared Flame Detectors QRI... Infrared flame detectors for use with Siemens burner controls, for the supervision of gas, oil and other flames that emit infrared light. The QRI... are suited for

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR 7 783 DETACTOGYR Flame Safeguard The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil or gas burners or

More information

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products 7 711 Flame Detector QRA4.U Flame detector for use with burner controls from for the supervision of gas or oil flames. The QRA4.U and this Data Sheet are intended for use by OEMs which integrate the flame

More information

LAE10 LFE10. Use. Series 02

LAE10 LFE10. Use. Series 02 ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,

More information

Infrared Flame Detectors

Infrared Flame Detectors 7 719 Infrared Flame Detectors QRI... Infrared flame detectors for use with Siemens burner controls, for the supervision of gas, oil and other flames that emit infrared light. The QRI... are suited for

More information

Flame detector. The QRA4.U is for use with the following types of burner control:

Flame detector. The QRA4.U is for use with the following types of burner control: 7 711 Flame detector QRA4.U UV flame detector for use with burner controls from Siemens for the supervision of gas or oil flames. The QRA4.U and this Data Sheet are intended for use by OEMs which integrate

More information

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products 7 712 ISO 9001 QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... The flame detectors are designed for use with our burner controls, for the supervision

More information

Flame detector. The QRA4.U is for use with the following types of burner control:

Flame detector. The QRA4.U is for use with the following types of burner control: 7 711 Flame detector QRA4.U UV flame detector for use with burner controls from Siemens for the supervision of gas or oil flames. The QRA4.U and this Data Sheet are intended for use by OEMs which integrate

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

RAR... Photocell Detectors. Building Technologies Division

RAR... Photocell Detectors. Building Technologies Division 7 71 Photocell Detectors RR... The photocell detectors are designed for use with burner controls, for the supervision of yellow-flame oil flames. They are used especially in connection with burner controls

More information

Flame detector. Building Technologies Division Infrastructure & Cities Sector

Flame detector. Building Technologies Division Infrastructure & Cities Sector 7 711 Flame detector QRA4 UV flame detector for use with burner controls from Siemens for the supervision of gas or oil flames. The QRA4... and this Data Sheet are intended for use by OEMs which integrate

More information

Burner Management System

Burner Management System 7 541 Burner Management System MV27.1... Burner control with integrated air / fuel ratio control for forced draft burners. The MV27.1 are designed for intermittent operation. The MV27.1... and this Data

More information

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55... 7 712 QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... The UV flame detectors are designed for use with Siemens burner controls, for the supervision

More information

Blue-flame Detectors

Blue-flame Detectors 7 716 QRC1... for frontal illumination QRC1... for lateral illumination Blue-flame Detectors QRC1... Blue-flame detectors for the supervision of ue- or yellow-burning oil or gas flames. Blue-flame detectors

More information

Building Technologies Division

Building Technologies Division 7 154 Burner control LMO39... Burner control for the uperviion of 1- or 2-tage oil burner of mall to medium capacity, with or without fan in intermittent operation. The LMO39 and thi Data Sheet are intended

More information

Building Technologies Division

Building Technologies Division 7 782 Flame safeguard LFS1... Flame safeguard with approval for continuous operation for the supervision of oil flames and gas flames in applications with an ionization probe and a photocell detector RAR9.

More information

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55... 7 712 QRA7 with clamp QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... QRA73 QRA75 The UV flame detectors are designed for use with Siemens burner

More information

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55... 7 712 QRA7 with clamp QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... QRA73 QRA75 The UV flame detectors are designed for use with Siemens burner

More information

Burner Management System

Burner Management System 7 54 Burner Management System MV27... Burner control with integrated air / fuel ratio control for forced draft burners. The MV27. are designed for intermittent operation with ionization probe or with optical

More information

Building Technologies

Building Technologies 7 782 Flame safeguard LFS1... Flame safeguard with approval for continuous operation for the supervision of oil flames and gas flames in applications with an ionization probe and a photocell detector RAR9.

More information

Basic unit with integrated air-fuel ratio control for forced draft burners

Basic unit with integrated air-fuel ratio control for forced draft burners 7 546 Basic unit with integrated air-fuel ratio control for forced draft burners LMV37.4... The LMV37... is a microprocessor-based burner management system with matching system components for the control

More information

Program module for burner control LME71.000

Program module for burner control LME71.000 Presentation example PME7... Presentation example LME7... PME7.2... Program module for burner control LME7.000 User Documentation Application: - -stage, direct or pilot ignited atmospheric burners - Response

More information

Burner Management System

Burner Management System 7 546 Burner Management System MV37.4... Burner control with integrated air / fuel ratio control for forced draft burners. The MV37.4... are designed for intermittent operation with ionization probe or

More information

EUROBOX SERIES TYPES CM... SM... MM...

EUROBOX SERIES TYPES CM... SM... MM... EUROBOX SERIES TYPES CM... SM... MM... AUTOMATIC GAS BURNER CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN Application This range of electronic gas burner control systems

More information

LFL Series Burner Flame Safeguard Control

LFL Series Burner Flame Safeguard Control LFL Series Burner Flame Safeguard Control Technical Instructions Document No. 74US LFL Rev. 2 November, 2004 The LFL is a compact electro-mechanical primary flame safeguard control designed to provide

More information

Heating Element. Building Technologies HVAC Products

Heating Element. Building Technologies HVAC Products 7 923 Heating Element AGA63 Heating element for use with SKP... and SKL actuators. The AGA63 extends the field of use of actuators and makes them more reliable at low or significantly varying ambient temperatures.

More information

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division 7 547 LMV26.300... Basic unit with integrated fuel-air ratio control for forced draft burners Dual fuel switch unit AGM60.1... LMV26.300... AGM60.1... The LMV26... burner management system is a microprocessor-based

More information

EUROFLAT SERIES TYPES C... S... M...

EUROFLAT SERIES TYPES C... S... M... EUROFLAT SERIES TYPES C... S... M... AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN APPLICATION The electronic systems of this range are suitable to control gas

More information

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies 7 54 Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV27.00... The LMV27... is a microprocessor-based burner control with matching system components for the control and supervision

More information

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55... 7 712 QRA7 with clamp QRA10... QRA53..., QRA55... with clamp QRA2... with clamp Flame Detectors QRA2... QRA10... QRA53... QRA55... QRA73 QRA75 The UV flame detectors are designed for use with Siemens burner

More information

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR.. EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR.. AUTOMATIC OIL BURNER CONTROL SYSTEMS APPLICATION This range of electronic oil burner controls has been specifically designed for oil burners for non

More information

Immersion Temperature Controller

Immersion Temperature Controller 3 333 Synco 100 Immersion emperature Controller with 2 outputs DC 0 RLE162 Immersion temperature controller for water-side control in heating and cooling plants Compact design with 2 analog control outputs

More information

EUROBOX SERIES TYPES CM...N SM...N MM...N

EUROBOX SERIES TYPES CM...N SM...N MM...N EUROBOX SERIES TYPES CM...N SM...N MM...N AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN (MANUAL RESET) DESCRIPTION This series of electronic systems is suitable

More information

MICROFLAT SERIES TYPES C.../U T X

MICROFLAT SERIES TYPES C.../U T X MICOFLAT SEIES TYPES C.../U T X AUTOMATIC GAS BUNE CONTOL SYSTEMS FO GAS BUNES AND GAS BUNING APPLIANCES WITH O WITHOUT FAN APPLICATION This range of electronic gas burner control systems is suitable for

More information

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit 7 618 Gas Burner Controls with automatic ignition and control functions for the heating and domestic hot water circuit ISO 9001 Microprocessor-based gas burner controls providing all control functions

More information

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage forced draught and combi oil/gas burners Possible flame detectors: - Ionisation probe

More information

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage atmospheric gas burners Flame detection: - Ionisation probe - Infrared-flicker detector

More information

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit Possible

More information

MANUAL OF - INSTALLATION - OPERATION - MAINTENANCE LIGHT OIL BURNERS G4 - G6 G10 - G18 SINGLE STAGE

MANUAL OF - INSTALLATION - OPERATION - MAINTENANCE LIGHT OIL BURNERS G4 - G6 G10 - G18 SINGLE STAGE MANUAL OF - INSTALLATION - OPERATION - MAINTENANCE LIGHT OIL BURNERS G4 - G6 G10 - G18 SINGLE STAGE M03964CC Rel. 2.1 02/13 Complying with EMC 79/336/CEE LV 73/23/CEE Documentazione Tecnica CIB Unigas

More information

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS SERIES 35-65 24 VAC Microprocessor-Based Hot Surface Ignition Control F-35-65 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings* 120/240

More information

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit A Honeywell Company Gas Burner Safety Control For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit Possible flame detectors: - Ionisation probe - Infrared flicker

More information

Eclipse Trilogy Flame Safeguard Modulating Sequences

Eclipse Trilogy Flame Safeguard Modulating Sequences Instruction Manual 830-2 2/25/2011 Eclipse Trilogy Flame Safeguard Modulating Sequences Series T420 Version 1 Copyright Copyright 2009 by Eclipse, Inc. All rights reserved worldwide. This publication is

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

DKO 974/976 DKO 974 N/976 N. Oil Burner Safety Control

DKO 974/976 DKO 974 N/976 N. Oil Burner Safety Control Oil Burner Safety Control A Honeywell Company DKO 974 N/976 N For 1- or 2-stage oil burners up to 30 kg/h throughput and intermittent operations with or without oil preheating Flame detection: - Photoresistor

More information

BC-R10 Series. Burner Controllers

BC-R10 Series. Burner Controllers No. CP-SS-1885E BC-R10 Series Burner Controllers Summary BC-R10 Series burner controllers are combustion safety controllers specifically designed for batch operation (systems which start and stop at least

More information

TWO STAGE HEAVY OIL BURNERS

TWO STAGE HEAVY OIL BURNERS TWO STAGE HEAVY OIL BURNERS PRESS N SERIES PRESS 30 N 85/171 342 kw PRESS 45 N 114/205 513 kw PRESS 60 N 171/342 684 kw PRESS 100 N 285/490 1140 kw The PRESS N series of burners covers a firing range from

More information

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-703 120 VAC Microprocessor-Based Intermittent Pilot Ignition Control F-35-703 July 2016 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

MMG Gas burner safety control

MMG Gas burner safety control A Honeywell Company Gas burner safety control INTRODUCTION gas burner safety controls are suitable for fully automatic forced and induced draught gas burners which have an intermittent (expanding flame)

More information

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module 7800 SERIES RM7840E,G,L,M; EC7840L Relay Module SPECIFICATION DATA Valve Proving features including: VPS test time When (Never, Before, After, Split or Both) FEATURES APPLICATION The Honeywell RM7840 is

More information

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

ELECTRONIC FLAME SUPERVISION MULTI-BURNER MULTI-BURNER MODEL: SENS-A-FLAME II Revision: 0 7112 DESCRIPTION Model 7112 Sens-A-Flame II is a second generation solid-state programmable combustion safeguard for supervising multiple burner ovens, furnaces,

More information

Model 60200FR Gas Primary Control Data Sheet

Model 60200FR Gas Primary Control Data Sheet Programmable, Microprocessor Based Gas Burner Primary Controls On-Board LCD Screen Easy to Understand Icons for Inputs and Outputs Displays micro-amp Flame reading Display operational information Fault

More information

Gas burner automatic safety control MMI / 811.1

Gas burner automatic safety control MMI / 811.1 Gas burner automatic safety control MMI 810.1 / 811.1 For 2-stage forced draught and combi oil/ gas burners Possible flame detectors: - Ionization probe - Infrared flicker detector INTRODUCTION 0708.21-01-e/04/99

More information

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage

More information

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21... Use Type summary Operating voltage AC 24 V or DC 13.5...3 Signal output DC 0...10 V for relative humidity Signal output

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA) R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80 Installation, use and maintenance instructions Heavy oil burner CODE MODEL TYPE 3434985 PRESS 60 N 616 T80 3434986 PRESS 60 N 616 T80 291 (2) - 01/2009 Thermal power - Output Operation Fuel Electrical

More information

MMI (40-34) Gas burner safty control

MMI (40-34) Gas burner safty control certified Qualitysystem ISO 9001 / EN 29001 A Honeywell Company Reg. Nr. 10529 (40-34) Gas burner safty control 0708.22-01-e/12/98 INTRODUCTION The Mod 40-34 gas burner safety control is suitable for fully

More information

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS 50M56-743 Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD

More information

for relative humidity and temperature

for relative humidity and temperature 1 861 1861P01 Duct sensor for relative humidity and temperature QFM65 Operating voltage AC 24 V Signal output DC 0...10 V for relative humidity and temperature Measurement accuracy ±3 % r. h. within the

More information

Room Air Quality Sensors

Room Air Quality Sensors 1 961 1961P1 1961P2 QPA2 QPA2D Room Air Quality Sensors QPA2 With maintenance-free photoacoustic CO 2 sensing element and depending on the type of sensor VOC 1) sensing element, based on a heated tin dioxide

More information

BOSCH CONDENS 5000W ZSB18-2A

BOSCH CONDENS 5000W ZSB18-2A 6720646195-00.1Wo HYDRONIC GAS SYSTEM BOILER 18kW BOSCH CONDENS 5000W ZSB18-2A Installation and Servicing Instructions 10 Boiler information AU/NZ 1 2 3 4 5 15 6 14 7 8 6720644743-04.1Wo 13 12 11 10 9

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-61 24 VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay F-35-61 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge

More information

Quickheat 30 weather compensated boiler control

Quickheat 30 weather compensated boiler control Quickheat 0 weather compensated boiler control A compact and sophisticated heating controller The compact KM controller is designed for the control of fan assisted boilers with modulating burners. The

More information

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21 Operating voltage AC 24 V / DC 13535 V Signal output DC 010 V / 420 ma for relative humidity Signal output DC 010 V / 420 ma

More information

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products 1 821 1821P01 Frost sensors for use on the air side Active capillary tube sensor for measuring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10 V Use On

More information

PRELIMINARY EDITION

PRELIMINARY EDITION 3 131 PRELIMINARY EDITION 14.01.2003 Synco 700 Heating Controllers Heating controller for medium-size and large buildings. The is used as a heating circuit or primary controller. The controller is supplied

More information

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw The RL/1 burners series covers a firing range from 107 to 398 kw, and it has been designed for use in low or medium temperature hot water boilers, hot air or steam boilers, diathermic oil boilers. Optimisation

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! 50A66-743 Integrated Furnace Control Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL

More information

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION M-4000 JANUARY 29, 200 FIREYE M4RT1 FLAME SAFEGUARD CONTROLS WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government

More information

Quick Reference Guide. Application. Gas Furnaces Boilers Water Heaters Commercial Cooking. Features

Quick Reference Guide. Application. Gas Furnaces Boilers Water Heaters Commercial Cooking. Features Installation Instructions E14QRG Issue Date June 28, 2018 Quick Reference Guide The Direct Spark Gas Ignition control module is designed for direct burner ignition and supervision. It can be used in new

More information

24 VAC Intermittent Pilot Gas Ignition Control

24 VAC Intermittent Pilot Gas Ignition Control C610U Universal 24 VAC Intermittent Pilot Gas Ignition Control Issue Date: 08/24/2016 Quick Reference Guide The C610U Universal Intermittent Pilot Gas Ignition Control module replaces many popular flame

More information

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature 1 882 1882P01 Symaro Duct Sensors for relative humitidy (high accuracy) and temperature QFM31 Use Examples Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 4 20 ma for relative humidity and

More information

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD Corona Corporation This instruction manual contains important information for safe use of this device. Keep this instruction manual

More information

7800 SERIES RM7840E,G,L,M Relay Module

7800 SERIES RM7840E,G,L,M Relay Module 7800 SERIES RM7840E,G,L,M Relay Module APPLICATION SPECIFICATION DATA The Honeywell RM7840 is a microprocessor based integrated burner control for automatically fired gas, oil or combination fuel single

More information

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power. QXA2100 Condensation monitor QXA2100 Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power. Application Monitors condensation build up in buildings

More information

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS 50T35-743 Integrated Furnace Control INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY

More information

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products 2 478 Heating Controller for 2 heating circuits, d.h.w. and boiler RVP331 Multi-functional heating controller for use in residential and non-residential buildings Suitable for weather-compensated flow

More information

Old documentation - Only for your information! Product is not available anymore!

Old documentation - Only for your information! Product is not available anymore! ControlBloc Control and safety combination with directconnected automatic burner control MPC Printed in Germany ösler Druck Edition 0.01 Nr. 229 481 1 6 Technical description The ControlBloc is the combination

More information

7800 SERIES RM7888A Relay Module

7800 SERIES RM7888A Relay Module 7800 SERIES RM7888A Relay Module SPECIFICATION DATA FEATURES APPLICATION The Honeywell RM7888A Relay Module is a microprocessor-based integrated burner control for industrial process semi-automatically

More information

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - wwwmytubcouk - info@mytubcouk 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21 Use Operating voltage

More information

Advanced Ultraviolet Burner Controller

Advanced Ultraviolet Burner Controller No. CP-SS-7E Advanced Ultraviolet Burner Controller Model AUR300C/AUR30C Overview The AUR300C Advanced Ultraviolet Burner Controller and AUR30C Advanced Ultraviolet Burner Controller with Communication

More information