tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual

Size: px
Start display at page:

Download "tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual"

Transcription

1 tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual This manual covers operation of the tcm100 and tcm101 Series Temperature Control Modules. The term "tcm100" is used throughout this manual as the generic name for this family of temperature controllers. Likewise, the term "itc2000" is the generic name for a family of heating system cabinets that includes the itc20l2, itc2024 and itc2036 Series Temperature Control Systems. VTI, Inc. 24 McMillan Way Newark, DE Phone (302) FAX (302) Manual No. Revision Level 0.03 June 1998 Operations Manual

2 1. INTRODUCTION To insure proper operation, this manual must be read prior to starting the equipment. 2. GENERAL DESCRIPTION The tcm100 Temperature Control Module is designed as a plug in temperature controller for the VTI itc2000 Series Temperature Control System. The tcm100 module contains the following: two miniature contactors which switch power to the heater, an ammeter to indicate heater current, heater current high and low current alarms, heater continuity monitor and alarm circuitry, ground fault monitoring and alarm circuits. The power switching devices in the tcm100 Temperature Control Module consists of UL Listed contactors rated at 30 Amps for 240 VAC operation. The power contactors are arranged to interrupt both sides of the line simultaneously and therefore assures that the heater is completely disconnected from the line when heat is not required. For 208 VAC and 240 VAC applications, this is especially important to assure that no ground leakage current flows once the circuit is interrupted. An analog meter (0 to 25 Amp range) is provided on the front panel to indicate heater current. Electronic monitoring circuitry is provided to detect when the current increases or decreases outside of the user programmed limits. If the current exceeds the high limit for more than a pre selected time, then a high current alarm will be initiated. If the current drops below the low limit for more than 5 seconds, then a low current alarm will be initiated. The tcm100 contains circuitry to monitor heater circuit continuity when used with the PTS100 or the PTS100/3 Pipe Temperature Sensor and monitor wire heater cable. This circuit operates at all times (even when the heater is not powered) to detect an open monitor circuit (and therefore an open heater circuit) and initiates an alarm. This alarm is combined with a voltage monitoring circuit to detect if the input line voltage drops below 85% of nominal while power is applied to the heater. A ground fault current monitor circuit is included in the tcm100 to monitor any leakage current in the heater circuit. This GFI current monitor utilizes a detector which can detect current imbalance in the range of 30 to 100 Milliamps. An alarm is initiated if the GFI current exceeds a user preset limit. 2

3 The tcm100 Temperature Control Module provides a six contact connector (rated at 30 Amps per contact) for the power circuits plus a 16 pin DIN connector for the alarm and control signals. These connectors mate with companion connectors located on the back of the racks in the VTI itc2000 Series Temperature Control System cabinets. 3. MODULE CONFIGURATION The model number imprinted on the handle of the tcml00 or tcm101 Temperature Control Module determines the operating voltage for that module: tcm100 module is designed to operate on 120 VAC or 208 VAC. The voltage selection jumpers on the tcm100 are installed from P4 to P5, P6 to P7, and from P9 to P10. tcm101 module is designed to operate on 240 VAC. The voltage selection jumpers on the tcm101 are installed from P5 to P6 and from P8 to P9. The operating mode and alarm setpoint parameters must be programmed by placing the appropriate jump jax to the desired selection, as described in the table below: DESIG PARAMETER SELECTIONS JP1 HEATER TYPE TWO WIRE or THREE WIRE JP2 JP3 or CONTROL SOURCE PIPE SENSING or AMBIENT SENSING JP4 SENSOR TYPE CONTACT (thermostat) or PTS100 JP5 HIGH CURRENT TIME DELAY 1.1, 2.3, or 4.5 MINUTES JP6 CONTINUITY LATCH or NONLATCH JP7 HIGH CURRENT LATCH or NONLATCH JP8 LOW CURRENT LATCH or NONLATCH DP1 HIGH CURRENT ALARM Disable, 3, 4, 5, 8, 10, 15, 20, 25 Amps DP2 LOW CURRENT ALARM Disable, 0.1, 1, 2, 3, 5, 7, 10, 15 Amps DP3 GROUND FAULT ALARM 30, 50, 70, 100 Milliamps 3.1 CONTROL SOURCE The tcm100 is designed to operate in two modes: Pipe Temperature Sensing or Ambient Temperature Sensing. This choice is made by placing the Control Source jump jax selector to the desired position: for PIPE SENSING place on header JP2 or for AMBIENT SENSING place on header JP3. 3 In the Pipe Temperature Sensing mode, the temperature sensor is located at the point where the desired temperature is to be maintained. An individual temperature sensor

4 is required for each controller operating in this mode. In the Ambient Temperature Sensing mode, the temperature sensor simply measures the outside ambient temperature. A single Ambient Temperature Sensor is used to control a large number of tcm100 Series Temperature Control Modules. 3.2 SENSOR TYPE When operating in the Pipe Temperature Sensing mode, the tcm100 is designed to accept an external temperature signal from either a contact making device such as a capillary thermostat or a VTI PTS100 Pipe Temperature Sensor. This choice is made by placing the jump jax selector to the desired position: CONTACT or PTS100 on header JP HEATER TYPE The tcm100 is designed to operate with either a two conductor heating wire or a three conductor heating wire which contains a monitor wire. The monitor wire is used to assure that the heating cable is intact. This choice is made by placing the jump jax selector to the desired position: 2 WIRE HEATER or 3 WIRE HEATER on header JP HIGH CURRENT TIME DELAY The tcm100 contains a heater current monitor circuit which may be programmed to alarm if the current exceeds the high limit after a programmable time delay period. This time period may be selected for 1.1, 2.3, or 4.5 minutes by moving a jump jax to one of these three locations on header JP5. These numbers represent the time delay after the heater is turned on until the high current alarm circuit is enabled. With self limiting heating cable, the heater current will be higher than normal during the first few minutes of operation. This current will gradually decrease and stabilize after several minutes. This programmable time delay will enable the operator to select a time period sufficient to allow the cable to stabilize before enabling the high current alarm. The time delay will be repeated each time that heat is required. 3.5 CONTINUITY and VOLTAGE The tcm100 contains a continuity and line voltage monitoring circuit which lights a green LED whenever both the heater continuity circuit is complete and the line voltage is greater than 85%. The LED indicator is programmable as LATCH or NONLATCH by placing the JP6 jump jax selector to L for latch or N for nonlatch. In the latch position, if the line voltage drops below 85% or if the heater circuit continuity is interrupted for any reason, the ALARM LED indicator will light and the CONTINUITY & VOLTAGE LED indicator will go off and remain off until the problem has been corrected and the RESET push button is momentarily depressed. 4

5 In the nonlatch position, if the line voltage drops below 85% or if the heater circuit continuity is interrupted momentarily, the ALARM LED indicator will light and remain lighted, however, the CONTINUITY & VOLTAGE LED indicator will remain off only as long as the low voltage condition exists or as long as the heater continuity is interrupted. 3.6 HIGH CURRENT ALARM The tcm100 contains a current monitoring circuit which monitors the heater current and provides an alarm output whenever the heater current exceeds the pre selected limit after the time delay selected in Section 3.4 above. This limit may be set by placing the jump jax selector for DP1 to one of the following positions: DISABLE 3 AMPS 4 AMPS 5 AMPS 8 AMPS 10 AMPS 15 AMPS 20 AMPS 25 AMPS A red HIGH CURRENT LED alarm indicator is provided on the front panel to indicate when a high current alarm has occurred. A programming selector JP7 has been provided to enable the operator to select the mode of operation of the high current alarm. When the JP7 jump jax selector is placed in the L or LATCH mode, the red HIGH CURRENT LED, as well as the red master ALARM LED, will light when a high current condition exists for a time in excess of the preset time delay and will remain lit even if the heater current eventually decreases below the preset limit. The HIGH CURRENT LED and ALARM LED indicator can only be reset by momentarily depressing the RESET push button after the heater current drops below the high current setpoint. When the JP7 jump jax selector is placed in the N or NONLATCH position, the red HIGH CURRENT LED, as well as the red master ALARM LED, will light when a high current condition exists for a time in excess of the preset time delay, but the red HIGH CURRENT LED indicator will go off if the heater current eventually decreases below the high current setpoint. However, the red master ALARM LED indicator can only be reset by depressing the RESET push button after the condition causing the alarm has been corrected. 5

6 3.7 LOW CURRENT ALARM The tcm100 contains a current monitoring circuit which monitors the heater current and provides an alarm output whenever the heater current decreases below the pre selected limit for 5 seconds. This limit may be set by placing the jump jax selector for DP2 to one of the following positions: DISABLE 1 AMPS 2 AMPS 3 AMPS 5 AMPS 7 AMPS 10 AMPS 15 AMPS A red LOW CURRENT LED alarm indicator is provided on the front panel of the tcm100 module to indicate when a low current alarm has occurred. A programming selector JP8 has been provided to enable the operator to select the mode of operation of the low current alarm. When the JP8 jump jax selector is placed in the L or LATCH mode, the red LOW CURRENT LED, as well as the red master ALARM LED, will light after a short time delay when the heater current decreases below the selected current. The LOW CURRENT LED and ALARM LED indicator can only be reset by momentarily depressing the RESET push button once the heater current returns to a level above the selected current. When the JP8 jump jax selector is placed in the N or NONLATCH position, the red LOW CURRENT LED, as well as the red master ALARM LED, will light after a short time delay when a low current condition exists but the red LOW CURRENT LED indicator will go off if the heater current eventually increases above the low current setpoint. However, the red master ALARM LED indicator can only be reset by depressing the RESET push button after the condition causing the alarm has been corrected. 3.8 GROUND FAULT CURRENT ALARM 6 The tcm100 contains a current monitoring circuit which monitors imbalance in the heater current and provides an alarm output whenever the imbalance in heater current exceeds the pre selected limit for 1 second. This limit may be set by placing the jump jax selector for DP3 to one of the following positions: 30 Milliamps 50 Milliamps

7 70 Milliamps 100 Milliamps A GROUND FAULT ALARM state is indicated when both the red GFI LED and master red ALARM LED on the front panel are lighted. This alarm is always a latched alarm and will remove power from the heater when it occurs. The condition causing the alarm must be corrected before normal operation can be restored. 4. OPERATION 7 The tcm100 Series Temperature Control Module should be installed in either an itc2012, itc2024 or itc2036 Series Temperature Control System cabinet which has been installed and connected according to the itc2000 INSTALLATION AND OPERATION MANUAL. If the tcm100 module has been configured and installed in the rack properly and the circuit breaker for that zone has been placed in the ON position, then the green CONTINUITY & VOLTAGE LED should illuminate. If heat is required as sensed by either the pipe sensor or the ambient sensor, then the yellow TEMP. LOW LED will illuminate and power will be applied to the heater. No red ALARM LED indications should appear. If the heater current exceeds the high current setpoint (DPl) for a time greater than the selected time delay, then the red HIGH CURRENT LED alarm indicator, as well as the red master ALARM LED indicator, will illuminate and the master alarm relay will be de energized. If JP7 is programmed to operate in the latch mode of operation, the HIGH CURRENT and master ALARM indication, as well as the alarm relay, may be cleared/energized by momentarily depressing the RESET push button on the front panel. If JP7 is programmed to operate in the nonlatch mode of operation, the HIGH CURRENT LED indicator will remain illuminated only as long as the heater current exceeds the high current set point. If the heater current decreases below the low current setpoint (DP2) for more than 5 seconds, the red LOW CURRENT LED alarm indicator, as well as the red master ALARM LED indicator, will illuminate and the master alarm relay will be de energized. If JP8 is programmed to operate in the latch mode of operation, the LOW CURRENT and master ALARM indication may be cleared/energized by momentarily depressing the RESET push button on the front panel. If JP8 is programmed to operate in the nonlatch mode of operation, the LOW CURRENT LED indicator will remain illuminated only as long as the heater current remains below the low current set point. If the leakage current in the heater load circuit exceeds the ground fault current setpoint, the red GFI LED indicator as well as the master red ALARM LED indicator will illuminate and the master alarm relay will be de energized. Simultaneously, the load contacts on the tcm100 module will open to remove power from both sides of the heating circuit. Power must be removed from the heating

8 circuit and the cause of the ground fault must be identified and corrected prior to restoring power to the heater circuit. The tcm100 Series Temperature Control Module may be tested when not powering the load by momentarily depressing the TEST push button on the front panel. As long as the TEST push button is depressed, power will be applied to the heater and the master alarm relay and ALARM LED will be illuminated. 5. OPERATION with PTS100 or PTS100/3 PIPE TEMPERATURE SENSOR The tcm100 is designed to operate with either a VTI model PTS100 Pipe Temperature Sensor (single temperature sensor channel) or a PTS100/3 Pipe Temperature Sensor (three temperature sensing channels). If the temperature sensed by the one type "K" thermocouple probe (PTS100) or by any one of the three type "K" thermocouple probes (PTS100/3) decreases below the setpoint, then the HEAT ON LED in the PTS100 will light and power will be applied to the heater. As the temperature of the single thermocouple (PTS100) or all three thermocouples (PTS100/3) increases approximately 3 F above the setpoint, then the HEAT ON LED will go off. The tcm100 provides the DC power required for operating the PTS100 Temperature Sensor, as well as the current mode temperature monitoring circuitry, which enables the tcm100 to sense when heat is required. This is accomplished by using a third wire in the connection cable from the tcm100 located in the itc2000 Temperature Control System cabinet to the PTS100 located at the heater. Two wires power the heater and the third wire conveys the temperature status. The tcm100 can detect three levels of current in the third wire circuit: OPEN CIRCUIT (Less than 2 Milliamps) CONTINUITY (2 to 5 Milliamps) HEAT REQUIRED (8 to 10 Milliamps) The PTS100 contains a DC/DC converter which is used to isolate the temperature monitoring circuitry from the heater power circuit as well as to convert the incoming power to the low voltage required by the temperature measuring circuitry. The normal current required to operate the DC/DC converter is approximately 4 to 5 Milliamps which is monitored by the tcm100 to assure continuity exists in the heater load and monitor circuit. When the temperature sensing circuit determines that heat is required, the total current increases to 8 to 10 Milliamps. The PTS100 and PTS100/3 have provisions to detect an open thermocouple condition. If an open thermocouple condition is detected, the current flow in the PTS100 and PTS100/3 is momentarily interrupted. As a result, the green CONTINUITY LED on the front of the tcm100 module will flash at the rate of approximately 1 HZ. 8

9 5.1 SETTING TEMPERATURE SETPOINT on the PTS100 With power removed from the heating circuit, remove the existing type "K" thermocouple from channel #1 on the PTS100 terminal block. Connect a Thermocouple Simulator to these terminals observing polarity as shown on the PTS100 cover plate. Also turn the temperature setpoint trim pot on the PTS100 to the maximum counterclockwise position. Reapply power to this heating control circuit by turning on the appropriate branch circuit breaker. The POWER ON LED should light to indicate that power is applied to the PTS100. The Thermocouple Simulator should be set to type "K" and the desired setpoint temperature. The temperature setpoint trim pot on the PTS100 should be adjusted in the clockwise direction until the HEAT ON LED lights. To verify the accuracy of the temperature setpoint and test the 3 F temperature hysteresis designed into the PTS100, adjust the Thermocouple Simulator above and below setpoint. The HEAT ON LED should light whenever the simulated temperature is below setpoint. The HEAT ON LED should go off when the simulated temperature is adjusted 3 F above setpoint. This completes setting and testing of the PTS100 Pipe Temperature Sensor. 5.2 SETTING TEMPERATURE SETPOINT on the PTS100/3 9 With power removed from the heating circuit, remove the existing type "K" thermocouples from channel #1, #2, and #3 on the PTS100/3 terminal block. Connect three Thermocouple Simulators to these terminals observing polarity as shown on the PTS100/3 cover plate. Also turn the temperature setpoint trim pot on the PTS100/3 to the maximum counterclockwise position. Reapply power to this heating control circuit by turning on the appropriate branch circuit breaker. The POWER ON LED should light to indicate that power is applied to the PTS100/3. The Thermocouple Simulator for channel #1 should be set to type "K" and the desired setpoint temperature. The Thermocouple Simulator for channels #2 an #3 should be set 10 degrees higher than the temperature for channel #1. The temperature setpoint trim pot on the PTS100/3 should be adjusted in the clockwise direction until the HEAT ON LED lights. To verify the accuracy of the temperature setpoint and test the 3 F temperature hysteresis designed into the PTS100/3, adjust the Thermocouple Simulator for channel #1 above and below setpoint. The HEAT ON LED should light whenever the simulated temperature is below setpoint. The HEAT ON LED should go off when the simulated temperature is adjusted 3 F above setpoint. Then adjust the Thermocouple Simulator for channel #1 to l0 F above setpoint. To verify operation of channel #2, decrease the Thermocouple Simulator for channel #2 to a temperature below setpoint. The HEAT ON LED indicator should light as the simulated temperature decreases below setpoint. Now adjust the Thermocouple

10 Simulator for channel #2 above setpoint. As the simulated temperature increases to approximately 3 F above setpoint, the HEAT ON LED should go off. Then adjust the Thermocouple Simulator for channel #2 to 10 F above setpoint. To verify operation of channel #3, decrease the Thermocouple Simulator for channel #3 to a temperature below setpoint. The HEAT ON LED indicator should light as the simulated temperature decreases below setpoint. Now adjust the Thermocouple Simulator for channel #3 above setpoint. As the simulated temperature increases to approximately 3 F above setpoint, the HEAT ON LED should go off. Now adjust the Thermocouple Simulator for channel #3 to 10 F above setpoint. This completes setting and testing of the PTS100/3 Pipe Temperature Sensor. 6. ADDENDUM 6.1 REFERENCE DRAWINGS E tcm100 MAIN ASSEMBLY B tcm100 SCHEMATIC C PTS100 MAIN ASSEMBLY C PTS100 PC ASSEMBLY C PTS100 SCHEMATIC E itc2036 MAIN CABINET ASSEMBLY E itc2036 CABINET WIRING E itc2036 SINGLE LINE DIAGRAM E itc2024 MAIN CABINET ASSEMBLY E itc2024 WIRING DIAGRAM E itc2024 SINGLE LINE DIAGRAM 10

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL 1 Operations Manual for the VTI Model itc5000 Heat Tracing Control System Description The VTI Model itc5000 Heat Tracing Control System consists

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector) SMAC Controller Industrial Lubrication Systems Operation The SMAC Controller is a multi-purpose programmable controller used with industrial lubrication systems. Controller settings are saved whenever

More information

Residual Current Devices

Residual Current Devices Residual devices F200 Series UL 1053 Residual devices F200 Series Residual Current Devices Description The F200 Series residual devices offer a wide range of product for all of your fault protection needs.

More information

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd. F-2000 PC and AO OUTPUT BOARDS INSTRUCTION MANUAL Blue-White R Industries, Ltd. 500 Business Drive Huntington Beach, CA 92649 USA Phone: 714-89-8529 FAX: 714-894-9492 E mail: sales@blue-white.com or techsupport@blue-white.com

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS... SECTION Table of Contents SECTION 1 INTRODUCTION...................... 1.1 Description............................... 1.2 Features................................. 1.3 Models..................................

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview Water Leak Detector - Four Zone with open/short-circuit detection Product overview The AX-WLDF is a four zone water leak detection module with open or short circuit sensor cable detection. The module must

More information

Getting Started Quick Reference Guide

Getting Started Quick Reference Guide Getting Started Quick Reference Guide Parts List Installation Instructions Important Please review this entire document and all information included with this product before beginning installation or setup.

More information

TCM120. Operation Manual

TCM120. Operation Manual TCM120 Operation Manual This manual covers operation of the tcm120, tcm121, tcm122, tcm123, tcm125, and the European version tcm121e. The term tcm120 is used throughout this manual as the generic name

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000.

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000. INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3 M336 Rev F November 21, 2000 ÇConsilium Consilium US, Inc. 59 Porter Rd Littleton, MA 01460-1431 USA

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER PNEUMERCATOR Liquid Level Control Systems Electronic Systems Excluding LC2000 And TMS Series MAINTENANCE & TROUBLESHOOTING GUIDE 400 300 500 FUEL LEVEL LEAK MONITOR 1 200 600 OIL/GAS NORMAL WATER PNEUMERCATOR

More information

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1. Data Sheet Ref: 90501085 WD-CS Water leak detection cable Technical Overview The WD-CS range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

Installation Instructions

Installation Instructions 50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions

More information

Process Alarm Module RTA 421

Process Alarm Module RTA 421 Technical Information TI 074R/24/ae Process Alarm Module RTA 421 Alarm module and power supply for monitoring current or voltage signals Application Areas Plant and machine construction Panel builders

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

TCM-2 Thyristor Control Module DATA SHEET

TCM-2 Thyristor Control Module DATA SHEET TCM-2 Thyristor Control Module TCM-2 Thyristor DATA DATA SHEET Control Module DATA SHEET Alarm panels Type Compact Q96 design Extremely easy push-button programming (no jumpers or the like) Individual

More information

Installation and Operation Manual

Installation and Operation Manual Electronic Thermostats with Ground Fault Equipment Protection Model SST 2 40 Freeze Protection Thermostat P/N 22744 MANUAL We Manage Heat Model SST 2 175 Fixed Set Point Thermostat P/N 23708 Installation

More information

ESSEX ENGINEERING CORPORATION

ESSEX ENGINEERING CORPORATION WATER/WASTEWATER TREATMENT CONTROL SYSTEMS AND SUBSYSTEMS 2000 SERIES CONTROL SYSTEMS: 2000 series are for surface mounting inside a control cabinet Model 2024 Electronic Alternator Duplex (two pump) pump

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 1F82-51 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

SAFETY INFORMATION AND WARNINGS

SAFETY INFORMATION AND WARNINGS This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and

More information

HT-2 / 9600 Series Control Contents

HT-2 / 9600 Series Control Contents HT-2 / 9600 Series Control Contents Tools & Parts Tools Required Parts Required Error Messages 3 Flashing Dots Pressure or Flow Switch Not Activated Pressure or Flow Switch Activated Temperature Sensor

More information

ANCHOR BOLT DETAIL. Non-Shrink Grout. Poured In Place, After Equipment Setting. "L" Type Anchor Bolt Carbon Steel AISI 304 S.S.

ANCHOR BOLT DETAIL. Non-Shrink Grout. Poured In Place, After Equipment Setting. L Type Anchor Bolt Carbon Steel AISI 304 S.S. ANCHOR BOLT DETAIL Heavy Flat Washer Heavy Hex Nut UNC Th'd Mounting Flange Of Equipment To Be Mounted C B A D Non-Shrink Grout. Poured In Place, After Equipment Setting. Heavy Flat Washer Heavy Hex Nut

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

INTAC Microprocessor Humidifier Controller

INTAC Microprocessor Humidifier Controller TM READ AND SAVE THESE INSTRUCTIONS INTAC Microprocessor Humidifier Controller Installation Instructions Operation and Maintenance Manual % Power 68% Heaters 1 2 3 002 INTAC Humidifier Control System NORMAL

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

Analog Input Module IC670ALG630

Analog Input Module IC670ALG630 1 IC670ALG630 The Thermocouple (IC670ALG630) accepts 8 independent thermocouple or millivolt inputs. Module features include: Self calibration Two data acquisition rates based on 50 Hz and 60 Hz line frequencies

More information

This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly qualified.

This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly qualified. SERVICE MANUAL ERA & EBD SERIES ELECTRIC FRYERS WITH KLEENSCREEN PLUS FILTRATION SYSTEMS 2ER50AF KLEENSCREEN FRYER BATTERY MODEL ML MODEL ML 1ER50A 136730 2XER50AF 136747 1E50BD 136730 2XE50BDF 136747

More information

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy

More information

Sierra Series 900 Single & Dual Channel System. Instruction Manual

Sierra Series 900 Single & Dual Channel System. Instruction Manual Series 240/24 Instruction Manual Table of Contents Sierra Series 900 Single & Dual Channel System Instruction Manual Part Number IM-90-07/05 Revision D. 5 Harris Court, Building L Monterey, CA 93940 (83)

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA) R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

Instructions. Easy-wire terminal strip Microprocessor-operated. Easy remote sense. Self-checking program. Diagnostic/status LED s

Instructions. Easy-wire terminal strip Microprocessor-operated. Easy remote sense. Self-checking program. Diagnostic/status LED s Instructions Rear (size reduced) Easy-wire terminal strip Microprocessor-operated Front (Processor coordinates operation and diagnostic) Easy remote sense (Electronic sensor, wired to control) Self-checking

More information

Instruction Manual Model A

Instruction Manual Model A 706 Bostwick Avenue, Bridgeport, CT 06605 TEL: 203-368-6751 FAX: 203-368-3747 1-800-566-6822 www.devarinc.com Instruction Manual Model 18-232A LOOP POWERED ALARM MANUAL NO. 990029 MODEL 18-232A LOOP POWERED

More information

Sapphire Series TSVW & TWWS Chillwater Digital Thermostats

Sapphire Series TSVW & TWWS Chillwater Digital Thermostats Sapphire Series TSVW & TWWS Chillwater Digital Thermostats Table of Contents 1. Introduction 3 TSVW Main Components 3 TWWS Main Components 4 2. Display Panels for TSVW and TWWS Thermostats 4 TSVW Display

More information

MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL. SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623

MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL. SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623 MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623 PHONE 585-321-5800 FAX 585-321-5218 REVISIONS, IF ANY,

More information

INSTRUCTION MANUAL Portable Refrigerator Units MODEL 15-LITER Including the Standard Battery Backup System (BBS)

INSTRUCTION MANUAL Portable Refrigerator Units MODEL 15-LITER Including the Standard Battery Backup System (BBS) 1 INSTRUCTION MANUAL Portable Refrigerator Units MODEL 15-LITER Including the Standard Battery Backup System (BBS) SECTION TITLE PAGES 1 Introduction and Basic Operation 2-3 2 Cleaning & Storing 4 3 Basic

More information

SEC 2000 Millenium Infrared Gas Detector

SEC 2000 Millenium Infrared Gas Detector SEC 2000 Millenium Infrared Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 USA (952) 938-9486 Fax (952) 938-9617 Email: sales@sensorelectronic.com

More information

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning

More information

6 Zone 120/60/1vac 3A 24 VAC class 2 2 x 40 VA 2 x 5 amp fuses 1/6 hp, 120 VAC

6 Zone 120/60/1vac 3A 24 VAC class 2 2 x 40 VA 2 x 5 amp fuses 1/6 hp, 120 VAC Viega Zone Control Applications The Viega Zone Control is a wiring and switching center for individual and / or multi- room control. The Zone Control simplifies wiring between Thermostats and Powerheads.

More information

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc Table of Contents Introduction...2 Mounting...2 Dimensions...2 Controls...3 Screen Displays...3 Screen Messages...4 Light Test...5 Control Power...5 Wiring...5 Inputs...7 Outputs...7 Programming...8 Technical

More information

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5

More information

The next generation thermometer from the global leader

The next generation thermometer from the global leader akm oti/wti Remote mount thermometers The next generation thermometer from the global leader Accomplish the most demanding control and alarm configurations Reduce failure costs with reliable AKM bellows

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

MPT Electric Fire Pump Controller

MPT Electric Fire Pump Controller MPT Electric Fire Pump Controller Alarm Messages and Guide This manual provides alarm descriptions, troubleshooting steps, and alarm set point configuration information for Metron MPT Fire Pump Controllers

More information

Water Detection Controllers

Water Detection Controllers Page 1 of 5 Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation or erosion

More information

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

Instructions Oxygen Controller R8471C 2.1 8/

Instructions Oxygen Controller R8471C 2.1 8/ Instructions 95-8405 Oxygen Controller R8471C 8/07 95-8405 Table Of Contents Section I - General Information APPLICATION...1 FEATURES...1 DESCRIPTION...1 SPECIFICATIONS...2 Controller...2 C7052C O2 Detector...2

More information

ACCURATE ELECTRONICS INC

ACCURATE ELECTRONICS INC ACCURATE ELECTRONICS INC Page 1 of 7 Model 108078 2 Sept 09 WWW.ACCURATE.ORG PO BOX 1654 97075-1654 8687 SW Hall Blvd 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 Practice Section 108078 Rev A

More information

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION: RELEASE DEVICES MADE IN THE U.S.A. RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: The "WPS" World Power Series, Time Delay Release

More information

STATUS ALARM HISTORY ALARM RESET

STATUS ALARM HISTORY ALARM RESET Instruction Manual Model 1582-42L Data Switch February 1999, Rev 0 CH1 AUTO CH2 SWITCH 1 2 1 2 STATUS 1 2 MODEL 1582 SWITCH CROSS TECHNOLOGIES INC. CH1 ONLINE MANUAL SELECT CH2 ONLINE SWITCH RESET MAN

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Table of Contents SECTION PAGE

Table of Contents SECTION PAGE Table of Contents SECTION PAGE SECTION 1 INTRODUCTION................... 1.1 Description.............................. 1.2 Features................................ 1.3 Models.................................

More information

Operations Manual. Motion Detector Module Model ZS10

Operations Manual. Motion Detector Module Model ZS10 Motion Detector Module Model ZS10 The must be referred to for correct installation. Failure to comply with the shall void all warranties and liabilities. Overview The ZS10 Motion Detector Module is an

More information

Universal Gas Detector

Universal Gas Detector Universal Gas Detector Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 pureairemonitoring.com

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS GENERAL INDEECO Industrial Control Panels are designed to provide years of trouble free operation if properly

More information

Getting Started Quick Reference Guide

Getting Started Quick Reference Guide Getting Started Quick Reference Guide Parts List Installation Instructions Important Please review this entire document and all information included with this product before beginning installation or setup.

More information

Duct and Rough Service Carbon Monoxide Sensor

Duct and Rough Service Carbon Monoxide Sensor Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.

More information

UDC100 Universal Digital Controller Specifications

UDC100 Universal Digital Controller Specifications UDC100 Universal Digital Controller Specifications 51-52-03-29 November 1999 Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR

More information

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE -

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE - SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN VC3ED ML-137013 - NOTICE - This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 50A55-474 & 50A55-571 Integrated Furnace Controls INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN)

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN) Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN) Ovens Service Manual Models OMFP6010 CONTENTS This document has been published to be used for service only. The contents

More information

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL 500644 FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES A047-001 FIGURE 1: Demand Defrost Control Module ANTI-SHORT CYCLE DELAY

More information

Model 1062 Environment Monitor

Model 1062 Environment Monitor Model 1062 Environment Monitor Continuously Monitors Environment Temperature Humidity Barometric Pressure Line Voltage Line Frequency Applications Manufacturing The 1062A Environment Monitor will ensure

More information

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE DSGH Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE Revision History Revision History Version of manual Description Date 1.0 Initial release 051025 1.1

More information

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1-316-832-4357

More information

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,

More information

DETECTION SYSTEMS. GCM Auto Alarm. Instruction Manual. GA0203P01 Rev. D

DETECTION SYSTEMS. GCM Auto Alarm. Instruction Manual. GA0203P01 Rev. D DETECTION SYSTEMS GCM Auto Alarm Instruction Manual GA0203P01 Rev. D Contents Limited Warranty... 3 Warning... 4 Safety Consideration... 4 General Description... 5 Installation... 6 Initial Adjustments...

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

Quickheat 30 weather compensated boiler control

Quickheat 30 weather compensated boiler control Quickheat 0 weather compensated boiler control A compact and sophisticated heating controller The compact KM controller is designed for the control of fan assisted boilers with modulating burners. The

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

RTD TEMPERATURE SENSING SYSTEM

RTD TEMPERATURE SENSING SYSTEM General Overview RTD TEMPERATURE SENSING SYSTEM The Prime Technology RTD Temperature System 9219-00-0002 is a three-channel temperature measuring system that utilizes two RTD Temperature Sensor inputs

More information

S AFETY SYSTEMS TECHNOLOGY Mill Creek Drive, Suite 215 Laguna Hills, California 92653, USA Tel (949) Fax (909)

S AFETY SYSTEMS TECHNOLOGY Mill Creek Drive, Suite 215 Laguna Hills, California 92653, USA Tel (949) Fax (909) DESIGN MANUAL Model GIR911 Infrared Carbon Dioxide NOVA-Sensor 70071 The information in this document is applicable to sensors built on or after October, 2001 The information and technical data disclosed

More information

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

SOLID STATE SECURITIES, INC. THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL S S S S S S LISTED L * PATENT PENDING S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT U 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

Service Handbook. Servicing should only be performed by a Qualified Service Agent.

Service Handbook. Servicing should only be performed by a Qualified Service Agent. Service Handbook COMMERCIAL ELECTRIC WATER HEATERS Technical Support and Parts: 800-456-9805 www.americanwaterheater.com MODELS STCE3-52/80/119 & ITCE3-52/80/119 INSTALLATION CONSIDERATIONS - PRE SERVICE

More information

INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions

INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions ADI5775-B INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions Controls Corporation of America 1501 Harpers Road Virginia Beach, VA 23454 To Order

More information

K00364 Electronic Bin Thermostat

K00364 Electronic Bin Thermostat K00364 Electronic Bin Thermostat Installation Instructions This kit reduces overfill and condensation issues and can be used on any Manitowoc ice machine installed on an ice dispenser. Order kit number

More information

50A Integrated Furnace Control

50A Integrated Furnace Control Goodman White-Rodgers 0130F00005 PCBBF110 PCBBF123 50A55-743 0130F00005S PCBBF110S PCBBF123S 50A55-289 B1809926 PCBBF112 50T55-289 B1809926S PCBBF112S 50A55-743 Integrated Furnace Control INSTALLATION

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Resistance heaters. Ventilation systems. Air-air exchangers. Air-water exchangers. Cooling units. Control devices. Calculation and selection

Resistance heaters. Ventilation systems. Air-air exchangers. Air-water exchangers. Cooling units. Control devices. Calculation and selection 7 0 Selection guide TO CONTROL THE TEMPERATURE Respects the entered value Compact fixed thermostats Preset factory temperature: NA (blue button):, 0, ºC for the resistance heater. (red button):, 0, ºC

More information

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER BARD MANUFACTURING COMPANY Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual: 2100-393C Supersedes: 2100-393B File: Volume III Tab

More information