Report on First Revision June 2014 NFPA 101

Size: px
Start display at page:

Download "Report on First Revision June 2014 NFPA 101"

Transcription

1 101- Log #62 SAF-BSF Final Action: (9.2.3) Submitter: Doug Hohbein, Northcentral Regional Fire Code Development Committee Recommendation: Revise to read: Commercial Cooking Equipment Operations. Unless prohibited by Chapters 11 through 43, commercial cooking equipment operations shall be in accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, unless such installations are approved existing installations, which shall be permitted to be continued in service The requirements of shall be met unless such installations are approved existing installations, which shall be permitted to be continued in service. Substantiation: The word Equipment should be replaced with Operations as NFPA 96 applies to commercial and residential cooking equipment. The phrase Unless prohibited by Chapters 11 through 43 is needed as Chapters 18/19 alter the requirements of and chapter 24 does not apply; as written, is mandatory language applicable to all occupancies. The last stipulation in is an exception and should be placed in a separate paragraph per the MOS. The Code is not currently formatted to prohibit the use of Rather, other sections of the Code specify when compliance with is required. Also see First Revision 101- Log #FR600 (FR 1-NFPA ) Log #348 SAF-BSF Final Action: (9.2.4) Submitter: Chad E. Beebe, ASHE - AHA Recommendation: Revise to read: Ventilating Systems in Laboratories Using Chemicals. Ventilating systems in laboratories using chemicals shall be in accordance with NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, or NFPA 99, Health Care Facilities Code, as appropriate. Substantiation: There is no longer any need to reference NFPA 45 and NFPA 99, The requirements for ventilation of laboratories have been removed from NFPA 99, and users are directed to NFPA 45. " Ventilating Systems in Laboratories Using Chemicals. Ventilating systems in laboratories using chemicals shall be in accordance with NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals. [101:9.2.4]" See First Revision 101- Log #FR631 (FR 2-NFPA ) which incorporates the suggested revision. 1

2 101- Log #325 SAF-BSF Final Action: (9.5) Submitter: Sharon S. Gilyeat, Koffel Associates, Inc. Recommendation: Revise text: 9.5 Rubbish Chutes, Incinerators, and Laundry Chutes Enclosure. Installation and Maintenance. Waste chutes, linen chutes, and incinerators shall be installed and maintained in accordance with NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment, unless such installations are approved existing installations Rubbish chutes and laundry chutes All new waste chutes and linen chutes shall be separately enclosed by walls or partitions in accordance with the provisions of NFPA 82 and Section Inlet openings All new iintake openings serving chutes shall be protected in accordance with NFPA 82 and Section The All new doors of chutes specified in shall open only to a room that is designed and used exclusively for accessing the chute opening The room All new rooms used for accessing the chute opening shall be separated from other spaces in accordance with NFPA 82 and Section The requirements of through shall not apply where otherwise permitted by the following: Existing installations having properly enclosed service chutes and properly installed and maintained service maintained intake openings shall be permitted to have inlets open to a corridor or normally occupied space Rubbish and laundry Waste chutes and linen chutes shall be permitted to open into rooms not exceeding 400 ft 2 (37 m 2 ) that are used for storage, provided that the room is protected by automatic sprinklers Installation and Maintenance. Rubbish chutes, laundry chutes, and incinerators shall be installed and maintained in accordance with NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment, unless such installations are approved existing installations, which shall be permitted to be continued in service. Substantiation: The proposed changes are made to eliminate any conflicts with NFPA 82, to make the terminology standard between the 101 and 82, and to relocate the most significant requirement in the section to the top position. NFPA 101 should start out saying that the design and maintenance shall be in accordance with NFPA 82 and then make changes as required for existing or new if necessary. The only technical change made in the revisions recommended was to eliminate the requirement for new intake rooms to be rated in accordance with 8.7. This would allow a nonrated sprinklered intake room which would contradict NFPA 82. Because most jurisdictions and designers rely on NFPA 82, the protection of these rooms should not be diminished below the requirements in NFPA 82. NFPA 82 now only requires 1-hr intake rooms if sprinkler protected. Several of the proposed revisions appear to be redundant. The proposed use of the term 'all new' throughout the section is inconsistent with the formatting of the remainder of Chapter 9. See First Revision 101- Log #FR607 (FR 4-NFPA ) for terminology revisions for consistency with NFPA 82. 2

3 101- Log #350 SAF-BSF Final Action: (9.5) Submitter: Joshua Elvove, U.S. General Services Administration Recommendation: *** Include 101_L350_Rec PI #289 *** Substantiation: The purpose of this public input is to make the requirements for chutes contained in NFPA 101 in concert with NFPA 82, which is the governing NFPA standard for chutes. NFPA 101 does not specifically identify requirements for chute discharge rooms and service opening rooms; instead it contains requirements for "inlet openings," a term not recognized by NFPA 82. NFPA 101 also lumps both the chute discharge and service opening rooms under a single requirement ( ) when NFPA 82 treats them differently. I recognize this adds more stringent requirements to NFPA 101, most notably for service opening rooms, but localities that enforce both NFPA 101 and 82 already need to invoke these more stringent requirements so they should be incorporated herein. Note: these requirements are only meant to apply to new construction, hence, the provisions in and through that maintain a number of exceptions for existing chute installations open to the corridor and non-rated service opening rooms as well as an exception for permitting storage in sprinklered service opening and chute discharge rooms that are under 400 sqft. I did not provide exceptions for the enclosure requirements for existing chute discharge rooms given the high risk that chute discharge doors (i.e., those doors at the bottom of the chute that are supposed to close upon activation of the fusible link) will fail to close. If the committee feels that all the changes suggested are too much to implement, especially on a retroactive basis, I encourage the committee to consider some of my suggested changes so the room terminology within the section correlates better with NFPA 82. From NFPA Chute Discharge Rooms General Waste and linen chutes shall terminate or discharge directly into a room having a minimum fire resistance rating not less than that specified for the chute Openings into such a room or compartment shall be protected by approved self-closing fire doors having a minimum fire protection rating not less than specified for the chute Service Opening Rooms General Every service opening shall be in a room or compartment that is separated from the other parts of the building by walls, partitions, floors, and floor-ceiling assemblies having a fire resistance rating of not less than the required rating of the chute enclosure Where service opening rooms are protected by automatic sprinklers, the room shall be enclosed in a minimum of 1-hour construction, and openings shall be protected with 3 4-hour fire-rated doors Openings into such a room or compartment shall be protected by approved self-closing doors that are appropriate for protecting the openings or are of not less than a 1 hour partition rating with a 3 4-hour fire-rated door The size of the service opening room or compartment shall not be less than that required to maintain a minimum mm (6 in.) clearance between the intake opening and the closed service opening room door. The proposed revisions appear to be redundant with NFPA 82 requirements. Alternative approaches might be to extract requirements from NFPA 82 or replace the NFPA 101 requirements with a reference to NFPA 82. Also see 101- Log #FR607 (FR-4 NFPA ). 3

4 9.5 Rubbish Chutes, Incinerators, and Laundry Chutes Enclosure1 Chute Enclosure Rubbish chutes and laundry chutes shall be separately enclosed by walls or partitions in accordance with the provisions of Section Chute Discharge Room Inlet openings serving chutes shall be protected in accordance with Section 8.3 Chutes shall terminate or discharge directly into a chute discharge room used exclusively for accessing the bottom of the chute The chute discharge room shall be separated from other spaces by construction having the same fire resistance rating as the chute enclosure The fire protection rating for openings into chute discharge rooms shall be commensurate for what is required for the chute enclosure The doors of chutes specified in shall open only to a room that is designed and used exclusively for accessing the chute opening 2.4 Existing chute discharge rooms shall be permitted to be used for storage, provided the room does not exceed 400 ft 2 (37 m 2 ) and the room is protected by automatic sprinklers Service Opening Rooms Service opening rooms shall provide access to the chute and be used exclusive for accessing the chute intake doors The room used for accessing the chute opening 3.2 Service opening rooms shall be separated from other spaces by construction having the same fire resistance rating as the chute enclosure Service opening rooms that are sprinkler protected in accordance with Section 9.7 shall be permitted to separated from other spaces by a one hour fire resistance rating The requirements of 3.4 The fire protection rating for openings into service opening rooms shall be commensurate for what is required for the chute enclosure through shall not apply where otherwise permitted by the following: Existing installations having properly enclosed service chutes and properly installed and maintained service openings shall be permitted to have inlets 3.5 The fire protection rating for openings into service opening rooms that are sprinklered in accordance with Section 9.7 shall be permitted to be ¾ hour Existing installations having chutes enclosed in accordance with and service openings that are installed and maintained in accordance with NFPA 82 shall be permitted to have service openings open to a corridor or normally occupied space. Rubbish chutes and laundry chutes shall be permitted to open into rooms not exceeding Existing service opening rooms serving chutes enclosed in accordance with shall be permitted in service opening rooms that meet the requirements of Section Log 350 Rec from Terra PI #289

5 Existing service opening rooms shall be permitted to be used for storage, provided the room does not exceed 400 ft 2 (37 m 2 ) that are used for storage, provided that the and the room is protected by automatic sprinklers Installation 4 Installation and Maintenance. Rubbish chutes, laundry chutes, and incinerators shall be installed and maintained in accordance with NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment, unless such installations are approved existing installations, which shall be permitted to be continued in service. 101 Log 350 Rec from Terra PI #289

6 101- Log #250 SAF-BSF Final Action: ( (2)) Submitter: Scott J. Harrison, Marioff Inc. Recommendation: Revise text to read as follows: (2) Rubbish chutes and laundry chutes shall be permitted to open into rooms not exceeding 400 ft 2 (37 m 2 ) that are used for storage, provided that the room is protected by automatic sprinklers or water mist systems. Substantiation: Water Mist systems have been approved and installed in many sprinkler applications globally for over 15 years. They have been listed by national and internationally recognized testing laboratories such as: UL (Ordinary Hazard Group 1), FM (Light Hazard Occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces), City of New York (Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), VdS Germany (Light Hazard, Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), KfV Austria (Light Hazard, Ord Haz Grp I, Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protection to the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to accept water mist systems as equivalent to an approved automatic sprinkler system where the application is listed or approved, thereby allowing construction alternatives without having to prove equivalency or be considered an alternative extinguishing system. The Code already permits the use of alternative systems in There is no need to single out water mist systems, other systems are specified by Table for certain applications Log #351 SAF-BSF Final Action: (9.5.5, , , , , and 9.5.2) Submitter: Joshua Elvove, U.S. General Services Administration Recommendation: Revise to read: Rubbish Waste Chutes, Incinerators, and Laundry Chutes Enclosure Rubbish Waste chutes and laundry chutes shall be separately enclosed by walls or partitions in accordance with the provisions of Section Inlet openings serving chutes Chute intake doors shall be protected in accordance with Section The room used for accessing the chute opening Chute service opening rooms shall be separated from other spaces in accordance with Section The requirements of through shall not apply where otherwise permitted by the following: (1) Existing installations having properly enclosed service chutes and properly installed and maintained service openings shall chute intake doors shall be permitted to have inlets chute intake doors open to a corridor or normally occupied space. (2) Rubbish Waste chutes and laundry chutes shall be permitted to open into rooms not exceeding 400 ft 2 (37 m 2 ) that are used for storage, provided that the room is protected by automatic sprinklers Installation and Maintenance. Rubbish Waste chutes, laundry chutes, and incinerators shall be installed and maintained in accordance with NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment, unless such installations are approved existing installations, which shall be permitted to be continued in service. Substantiation: To be consistent with language in NFPA 82. NFPA 82 uses the term waste (and trash ) and doesn t use the term rubbish. NFPA 82 uses the term chute intake doors for accessing chutes. NFPA 82 uses the term Service opening rooms for those rooms that serve to access the chute (i.e., that house the chute intake doors ). Note: if this is to be accepted (or accepted in principle), suggest forwarding this to all the occupancy chapters so they can make similar changes. See First Revision 101- Log #FR607 (FR 4-NFPA ) which incorporates the suggested revisions. 4

7 101- Log #380 SAF-BSF Final Action: ( ) Submitter: William E. Koffel, Koffel Associates, Inc. Recommendation: Revise to read: * Where a required fire alarm system is out of service for more than 4 hours in a 24-hour period, the authority having jurisdiction shall be notified, and the building shall be evacuated, or an approved fire watch shall be provided for all parties left unprotected by the shutdown until the fire alarm system has been returned to service. Fire alarm system impairment procedures shall comply with NFPA 72, National Fire Alarm and Signaling Code. Substantiation: A similar change was made last cycle to Paragraph regarding sprinkler systems. The intent is to refer to the reference standard, in this case NFPA 72, to identify when impairment procedures need to be implemented and what procedures are to be implemented. See First Revision 101- Log #FR609 (FR 7-NFPA ) which incorporates the suggested revision. 5

8 101- Log #172 SAF-BSF Final Action: ( ) Submitter: Peter A. Larrimer, US Department of Veterans Affairs Recommendation: Delete text: Protection of Fire Alarm System * In areas that are not continuously occupied, and unless otherwise permitted by or , automatic smoke detection shall be installed to provide notification of fire at the following locations: (1 )Each fire alarm control unit (2) Notification appliance circuit power extenders (3) Supervising station transmitting equipment The provisions of (2) and (3) shall not apply to existing alarm systems Where ambient conditions prohibit installation of a smoke detector, a heat detector shall be used. Substantiation: This change will remove the retroactive requirement to install a smoke detector (or a heat detector) above an existing fire alarm control unit since the installation of that detector may not have originally been required by the installation standard and there is no reason to retroactively requrie a detector above an existing control unit. If the installation standard required it at the time of installation, then the detector should be there. Section requires fire alarm systems to be installed in accordance with NFPA 72 unless it is an approved existing system. NFPA 72 has not always required protection of the fire alarm system to be provided. For instance, the 2007 Edition of NFPA 72 allowed the sprinkler exception as follows: NFPA 72 (2007): 4.4.5* Protection of Fire Alarm System. In areas that are not continuously occupied, automatic smoke detection shall be provided at the location of each fire alarm control unit(s), notification appliance circuit power extenders, and supervising station transmitting equipment to provide notification of fire at that location. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. Exception No. 2: Fully sprinklered buildings shall not require protection in accordance with In addition, prior to the 2007 Edition, the requirement to protect the notification appliance circuit power extenders and supervising station transmitting equipment was not included in NFPA 72. Since all new systems will have to meet the requirements of NFPA 72 and approved existing installations don t, this will eliminated the need to extract this material from NFPA 72. In addition, the only reason that reads the way it does is that the fire alarm code can t mandate any device to protect itself other than fire alarm devices. It is hard to understand why the Life Safety Code would want to permit one heat detector to protect the fire alarm system when the Life Safety Code could use a room full of heat detectors with water behind them (known as sprinklers) to actually protected the unit and initiate the signal. Acceptance of this proposal would also be in line with the retroactivity clause of NFPA 72 that reads as follows: 1.4 Retroactivity Unless otherwise noted, it is not intended that the provisions of this document be applied to facilities, equipment, structures, or installations that were existing or approved for construction or installation prior to the effective date of the document In those cases where it is determined by the authority having jurisdiction that the existing situation involves a distinct hazard to life or property, retroactive application of the provisions of this document shall be permitted. Note that it is also the intent to delete the annex note associate with this section. See First Revision 101- Log #FR608 (FR 9-NFPA ) which incorporates the suggested revision. 6

9 101- Log #146 SAF-BSF Final Action: ( ) Submitter: Vince Baclawski, National Electrical Manufacturers Association (NEMA) Recommendation: Revise to read: Where required by another section of this Code, single-station and multiple-station smoke alarms shall be in accordance with NFPA 72, National Fire Alarm and Signaling Code, unless otherwise provided in , , or , or Substantiation: This proposal is intended to reduce nuisance alarms attributed to locating smoke alarms or smoke detectors in close proximity to cooking appliances and bathrooms in which steam is produced. The proposed provisions are based on the findings in the Task Group Report - Minimum Performance Requirements for Smoke Alarm Detection Technology - February 22, 2008 and are consistent with similar requirements included in the 2010 edition of NFPA 72. Section already requires smoke alarms to be installed in accordance with NFPA 72, which theoretically describes where alarms should and should not be installed. As a convenience to the code user, requirements on where smoke alarms should not be installed in proximity to permanently installed cooking appliances and steam producing bathrooms will be included in this section. See First Revision 101- Log #FR615 (FR-12-NFPA ) which incorporates the suggested revision Log #259 SAF-BSF Final Action: ( ) Submitter: Wayne D. Moore, Hughes Associates, Inc. Recommendation: Add a new as follows: Smoke alarms shall not be used as a substitute for automatic smoke detection where required by Chapters 11 through 43. Substantiation: There continues to misapplication of installers and architects using smoke alarms as a cheaper version of monitored smoke detection. Smoke alarms are designed for residential applications specifically to awaken those in a bedroom of a 1-2 family home of the sleeping room of any of the other residential occupancies. There are being misapplied in corridors and other locations. See First Revision 101- Log #FR615 (FR-12-NFPA ) which incorporates the suggested revision. 7

10 101- Log #146a SAF-BSF Final Action: ( and (New) ) Submitter: Vince Baclawski, National Electrical Manufacturers Association (NEMA) Recommendation: Add new section to read: Smoke alarms shall comply with the following requirements: 1.Smoke alarms installed between 10 ft and 20 ft of a stationary or fixed cooking appliance shall be photoelectric technology or be ionization technology equipped with an alarm-silencing means. 2.Smoke alarms shall not be installed less than 10 ft from a permanently installed cooking appliance. 3.Photoelectric smoke alarms shall be allowed to be installed between 6 feet and 10 feet of a permanently installed cooking appliance when the 10 ft area of exclusion would prohibit the placement of a smoke alarm required by other sections of the code Smoke alarms shall not be installed within a 3 feet from a door to a bathroom that contains a shower or tub. Renumber to Substantiation: This proposal is intended to reduce nuisance alarms attributed to locating smoke alarms or smoke detectors in close proximity to cooking appliances and bathrooms in which steam is produced. The proposed provisions are based on the findings in the Task Group Report - Minimum Performance Requirements for Smoke Alarm Detection Technology - February 22, 2008 and are consistent with similar requirements included in the 2010 edition of NFPA 72. Section already requires smoke alarms to be installed in accordance with NFPA 72, which theoretically describes where alarms should and should not be installed. As a convenience to the code user, requirements on where smoke alarms should not be installed in proximity to permanently installed cooking appliances and steam producing bathrooms will be included in this section. See First Revisions 101- Log #FR615 (FR-12-NFPA ) and 101- Log #FR632 (FR-30-NFPA ) which incorporate the PI by extracting applicable text from NFPA Log #298 SAF-BSF Final Action: ( ) Submitter: Wayne D. Moore, Hughes Assoc., Inc. Recommendation: Add a New to read as follows: Smoke alarms shall not be used as a substitute for automatic smoke detection where required by Chapters 11 through 43. Substantiation: There continues to misapplication of installers and architects using smoke alarms as a cheaper version of smoke detection. Smoke alarms are designed for residential applications specifically to awaken those in a bedroom of a 1-2 family home of the sleeping room of any of the other residential occupancies. There are being misapplied in corridors and other locations. See First Revision 101- Log #FR614 (FR-13-NFPA ), which deletes

11 101- Log #251 SAF-BSF Final Action: ( ) Submitter: Scott J. Harrison, Marioff Inc. Recommendation: Add text to read as follows: Where the building is protected by a water mist system in accordance with , and table , the area of the fire alarm zone shall be permitted to coincide with the allowable area of the water mist system. Substantiation: Water Mist systems are installed in equivalent sprinkler applications. Water mist sprinkler heads are spaced in similar areas of protection configurations. The fire alarm zone should be monitoring the same protection area as the mist system coverage just as with a sprinkler system. This is not original material; its reference/source is as follows: Some text was extracted from NFPA 101 paragraph See First Revision 101- Log #FR633 (FR-23-NFPA ) which incorporates the suggested revision Log #252 SAF-BSF Final Action: ( ) Submitter: Scott J. Harrison, Marioff Inc. Recommendation: Add new text to read as follows: Unless otherwise prohibited elsewhere in this Code, where a building not exceeding four stories in height is protected by an automatic water mist system in accordance with 9.7.3, the water mist system shall be permitted to be annunciated on the fire alarm system as a single zone. Substantiation: Water Mist systems are installed in equivalent sprinkler applications. Water mist sprinkler heads are spaced in similar areas of protection configurations. The fire alarm zone should be monitoring the same protection area as the mist system coverage just as with a sprinkler system. This is not original material; its reference/source is as follows: Some text was extracted from NFPA 101 paragraph See First Revision 101- Log #FR606 which incorporates the suggested revision Log #253 SAF-BSF Final Action: ( ) Submitter: Scott J. Harrison, Marioff Inc. Recommendation: Add new text to read as follows: Where the building is protected by an automatic sprinkler or water mist system in accordance with 9.7 the sprinkler or water mist system shall be permitted to be annunciated on the fire alarm system as a single zone. Substantiation: Water Mist systems are installed in equivalent sprinkler applications. Water mist sprinkler heads are spaced to protect the same areas as sprinkler systems. Where a water mist system is installed in lieu of an automatic sprinkler system, it should be annunciated on the fire alarm system in the same manner as a sprinkler system. This is not original material; its reference/source is as follows: Some text was extracted from NFPA 101 paragraph The language on which the PI is based ( and ) is limited to residential sprinkler systems in accordance with NFPA 13R and NFPA 13D. The source language recognizes "birdcage" designs in which it is impractical to annunciate sprinkler water flow on a floor-by-floor basis. No substantiation was provided to support that such designs are applicable to water mist systems. 9

12 101- Log #471 SAF-BSF Final Action: ( ) Submitter: Jeffrey M. Hugo, National Fire Sprinkler Association, Inc. Recommendation: Revise to read: Sprinkler piping serving not more than six sprinklers for any isolated hazardous area shall be permitted to be connected directly to a domestic water supply system having a capacity sufficient to provide 0.15 gpm/ft 2 (6.1 mm/min) throughout the entire enclosed area or assembly. An indicating shutoff valve, supervised in accordance with or NFPA 13, Standard for the Installation of Sprinkler Systems, shall be installed in an accessible, visible location between the sprinklers and the connection to the domestic water supply. Substantiation: The concept of an isolated hazardous area has not been defined in the Code. The use of the term hazardous area, as defined by section clarifies that the user can protect any hazardous area with a maximum of six sprinklers from the domestic system. The Code has been interpreted as only allowing those hazardous areas listed in the X sections of the occupancy chapters to use the connection to the domestic system. Acceptance of this proposal will clarify that this provision is not limited to the hazards listed in X Any partial sprinkler system, including one protecting windows or walls should be permitted to be connected to the domestic system as long as it meets the requirements of See First Revision 101- Log #FR612 (FR-32-NFPA ) which deletes the term 'isolated' as proposed, but does not add the term 'or assembly' as it is not the Code's intent to permit such installations for the protection of windows or wall assemblies Log #245 SAF-BSF Final Action: ( ) Submitter: Scott J. Harrison, Marioff Inc. Recommendation: Add text to read as follows: (New) Automatic water mist systems designed and installed according to NFPA 750 to make use of an alternative permitted by this Code shall be considered required systems and shall meet the provisions of this Code that apply to required systems. Substantiation: Water Mist systems have been approved and installed in many sprinkler applications globally for over 15 years. They have been listed by national and internationally recognized testing laboratories such as: UL (Ordinary Hazard Group 1), FM (Light Hazard Occupancies, Computer Rooms, Subfloors, Special Hazard Machinery & spaces), City of New York (Light Hazard Occupancies, Combustion Turbines, Machinery Spaces), VdS Germany (Light Hazard, Ord Haz Grp I,II parking garages & III selected occupancies, Cable Tunnels), KfV Austria (Light Hazard, Ord Haz Grp I, Combustion Turbines) and other agencies. These listings and installations have demonstrated equivalent fire protection to the authority having jurisdiction (AHJ). The addition of the proposed text will provide the AHJ a clear option to accept water mist systems as equivalent to an approved automatic sprinkler system where the application is listed or approved, thereby allowing construction alternatives without having to prove equivalency or be considered an alternative extinguishing system. This is not original material; its reference/source is as follows: Some text was extracted from NFPA 101 paragraph The Code does not contain alternatives based on the installation of water mist systems. 10

13 101- Log #34 SAF-BSF Final Action: ( ) NOTE: This proposal appeared as Comment (Log #248) which was held from the A11 ROC on Proposal a. Submitter: Ignatius Kapalczynski, CT Office of State Fire Marshal Recommendation: Reconsider. Substantiation: Alternative fire suppression systems are generally provided for one of two reasons: 1) for the protection of equipment that is sensitive to damage by water 2) for fires adversely affected by the application of water The first condition is not a life safety concern and should not be a consideration. The second condition is addressed by other standards. Adding clarifies protected throughout an approved sprinkler system. Protected throughout by an approved sprinkler system, refers to a system in accordance with NFPA 13. NFPA 13 lists areas where sprinkler protection may be omitted. These should be the only areas that this chapter recognizes. The commentary to IFC which states Although the use of an alternative extinguishing system allowed by 904, such as a carbon dioxide system or clean-agent system, would satisfy the requirements of Section 903.2, it would not be considered an acceptable alternative for the purpose of exceptions, reductions of other code trade-offs that would be applicable if an automatic sprinkler system were installed recognizes the value of a sprinkler system in accordance with NFPA 13. If ICC recognizes NFPA 13 as the standard for the installation of sprinkler systems, NFPA 101 should. To accept a clean agent fire extinguishing system as an equivalent to automatic sprinklers for the purpose of life safety would not be an even exchange. Just one example of this is duration. Total flooding fire suppression for a clean agent extinguishing system involves the discharge of a clean extinguishing agent that is typically required to provide protection within the design envelope for a minimum ten to twenty minute period. The average required duration for an automatic sprinkler system protecting an ordinary hazard occupancy is 60 minutes. There is ongoing debate as to whether water mist and other alternative extinguishing systems are equivalent to automatic sprinkler systems. Such determination should be case-specific and evaluated by the AHJ Log #527 SAF-BSF Final Action: (9.9.2 and 9.9.3) Submitter: John Hamilton, International Certification Board Recommendation: Revise to read: The special inspector's relevant experience in the design, installation, and testing of the fire protection systems being tested shall be documented. This section should say that the special inspector is a registered mechanical engineer or a person certified by a Nationally recognized organization The design documents shall provide the procedures and methods to be used and items subject to special inspections and tests. Or follow a national standard for testing like SMACNA procedural guides. Substantiation: Many areas of the country do not know what a special inspector is. This alleviates that issue and gives them proper direction. The public input does not include specific code revisions. Registered design professionals other than mechanical engineers could meet the required qualifications of special inspectors as determined by the AHJ. The term 'nationally recognized organization' is not defined and types of certifications are not specified. 11

14 101- Log #32 SAF-BSF Final Action: (A ) NOTE: This proposal appeared as Comment (Log #172) which was held from the A11 ROC on Proposal Submitter: Kenneth E. Isman, National Fire Sprinkler Association Recommendation: Insert a new annex note to as follows: A There are typically two different ways that extinguishing systems other than fire sprinkler systems are used. The first is when the entire building is protected with one of these alternate systems. When this is the case, the exceptions, reductions and alternative code provisions that are offered as options when fire sprinkler systems are installed should not be granted to the other extinguishing system unless the other system has demonstrated the same temperature control during a fire and reliability of operation as a fire sprinkler system. Reliability of operation needs to extend to the long-term use of the other system and an analysis of the reliability of the component parts. Some component of other extinguishing systems can show reliability data from their use in systems outside of fire protection where they get exercised on a regular basis, but acceptance on this basis is cautioned because many mechanical parts that sit for a long time without being exercised, as fire protection systems need to do, may not have the same reliability. A reliability analysis should also take into account inspection, testing and maintenance criteria and the likelihood of a building owner knowing and understanding what needs to be performed to keep the other system operational. The second manner in which other systems are used as alternatives to fire sprinkler systems are in individual rooms or spaces of otherwise sprinklered occupancies. Here the Authority Having Jurisdiction needs to use some judgment in the application of exceptions, reductions and alternative code provisions that are offered for sprinklered occupancies. The permission to utilize such exceptions, reductions and alternative code provisions far from the space with the other fire protection system should be granted. Closer to the space with the alternate system, exceptions, reductions and alternate code provisions for sprinklers could be granted if the system was analyzed as discussed above and found to be equivalent to a fire sprinkler system. Substantiation: After experiencing the discussion from the SAF-BSF committee and several of the occupancy committees, it is clear that something needs to be said in the Life Safety Code about this subject. But a blanket ban on using the sprinkler trade-ups, or a blanket statement that you can always use the sprinkler trade-ups, does not seem to work either way. Some judgment needs to be used depending on the type of alternative system proposed and the extent to which it is substituting for the sprinkler system. Some of these alternative systems are very good fire protection agents with a good history. Others are just coming to the market place and are using equipment that has not traditionally been used in fire protection systems and we just don t know how well they will work in the long-run. The annex note seemed to be the best way to provide guidance to AHJ s for now. See First Revision 101- Log #FR635 (FR-31-NFPA ) which incorporates the proposed annex language. 12

15 101- Log #296 SAF-BSF Final Action: (A (New) ) Submitter: Vickie J. Lovell, InterCode Incorporated Recommendation: Add new text to read as follows: A As smoke control systems become more elaborate and building systems become more integrated, it is essential to utilize individuals who are trained and qualified for inspection and testing such systems. Acceptable qualifications for acceptance testing and follow up testing for maintenance of smoke control systems are ultimately determined by the authority having jurisdiction. However, comprehensive study programs that result in certifications to inspect smoke control systems are available from third party organizations. In addition to passing the dedicated study programs pertaining to smoke control systems, eligibility criteria to become certified to inspect and test smoke control systems in third party programs should include a college/university degree in engineering with experience in HVAC installation or design work, associate degree in HVAC with at additional experience in HVAC installation or design work, or a certified testing and air balancers with extensive experience in HVAC installation or design. Substantiation: Section states that the acceptance testing for a smoke control system shall be performed by a special inspector in accordance with 9.9. However, section simply states that the special inspectors relevant experience related to the inspection and testing of the fire protection system (in this case the smoke control systems) shall be documented. It provides no guidance as to what appropriate credentials might be for that scope of work. This annex proposal provides information that may be useful to the authority having jurisdiction to determine the appropriate qualifications. The AHJ determines the required qualifications for special inspectors. The Code does not specify education requirements for other inspection, testing, or maintenance personnel. 13

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR3002 SAF-HEA (18.1.3.2) Recommendation: 18.1.3.2 Atrium walls in accordance with 6.1.14.4.6 shall be permitted to serve as part of the separation required by 6.1.14.4.1 for creating separated occupancies

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

Committee Input No. 28-NFPA 13R-2013 [ Global Input ] Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 21 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0300 - Other

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Questions/Comments for Richard Roux from Webinar on 7/11/13

Questions/Comments for Richard Roux from Webinar on 7/11/13 Questions/Comments for Richard Roux from Webinar on 7/11/13 Below are the questions and comments from the July 11, 2013 webinar 2013 NFPA 72: Design and Installation Requirements for Mass Notification

More information

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID DEPARTMENT OF HEALTH AND HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE Intermediate Care Facilities for the Mentally Retarded LARGE PART I Figure

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 IFC Significant Changes from the 2009 to the 2015 Edition Tier 1 Several medical care definitions were created and revised in Chapter 2 of the 2012 IBC, as well as through the occupancy descriptions, and

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

SECTION 915 CARBON MONOXIDE DETECTION

SECTION 915 CARBON MONOXIDE DETECTION SECTION 915 CARBON MONOXIDE DETECTION 915.1. General. Carbon monoxide alarms and carbon monoxide detectors shall be installed in buildings as required in accordance with Section 915.2 for residential buildings

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. PIPING Various Brass REVISED

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY. STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920

More information

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to

More information

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input of 201 1/13/2014 12:51 PM Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating

More information

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed.

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Fire Protection Features Diane D. Matthews,

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference: Oklahoma 310:451-1-3. Adopted references The Board of Health hereby incorporates by reference the International Code Council (ICC) 2006 (IBC) Edition International Building Code; the 2007 Edition Standard

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Fire Prevention Coffee Break Training. May 2017

Fire Prevention Coffee Break Training. May 2017 Fire Prevention Coffee Break Training May 2017 Agenda Introduction Submittals - Phelan Changes to NFPA 13 - Phelan Questions and Answers Open Forum Please welcome our S ummer Intern Charlie Poppe Small

More information

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS June 20, 2011 TO: PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS SUBJECT: New Acceptance Criteria for Fixed Condensed Aerosol Fireextinguishing Systems, Subject AC432-0611-R1

More information

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes 2012 International Fire Code Significant Changes Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Koffel Associates, Inc. www.koffel.com Expertly Engineering Safety From

More information

Review of Revisions to NFPA 1, 2015 Edition

Review of Revisions to NFPA 1, 2015 Edition James S Peterkin, PE, LEED AP Senior Fire Protection Engineer TLC Engineering for Architecture Anthony Apfelbeck, CFPS, CBO, CFO, FM, FIFireE, MPA Building and Fire Official City of Altamonte Springs,

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &

More information

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon. SECTION SR101 GENERAL

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

CTC Meeting #27 JUNE 17 18, 2013 NIST report on the Charleston sofa store fire

CTC Meeting #27 JUNE 17 18, 2013 NIST report on the Charleston sofa store fire CTC Meeting #27 JUNE 17 18, 2013 NIST report on the Charleston sofa store fire The following 2013 Group B changes have been compiled for the above noted CTC Area of Study. Code changes with an (*) indicate

More information

Chapter 2: Definitions

Chapter 2: Definitions FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document

More information

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 130 ST - K0000 - Initial Comments Title Initial Comments Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 98 ST - Y0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. Based on the LSC surveyor's determination

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE DEPARTMENT OF HEALTH & HUMAN SERVICES CENTERS FOR MEDICARE & MEDICAID SERVICES FIRE SAFETY SURVEY REPORT - AMBULATORY SURGICAL CENTERS Medicare 1. (A) PROVIDER NUMBER Identifying information as shown in

More information

Page 1 of 10 Second Revision No. 8-NFPA 600-2014 [ Section No. 3.3.17 ] 3.3.17* Incident Management System (IMS). A system that defines the roles and responsibilities to be assumed by responders and the

More information

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963) INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information