OXNARD FIRE DEPARTMENT 360 West Second Street Oxnard, CA (805) Fax (805)
|
|
- Junior Martin
- 6 years ago
- Views:
Transcription
1 OXNARD FIRE DEPARTMENT 360 West Second Street Oxnard, CA (805) Fax (805) REQUIREMENTS FIRE HYDRANT STANDARDS Fire hydrants and required access roads shall be provided prior to and during the time of construction. Hydrants shall be visible and accessible from the required access road. All combustible framing must be kept within 150 feet of an acceptable access road serviced with active fire hydrants. An acceptable fire access road shall have a minimum clear width of 26 feet and a vertical clearance of 13 feet, 6 inches, be an all weather paved surface and support a 75,000-pound fire apparatus. After the hydrant location plans are approved, the engineered underground supply piping plans, with hydrants shown at the approved locations, are required to be plan checked and approved prior to installation. The installation is inspected by the City of Oxnard Public Works Department. All hydrants shall be Public Hydrants located in a public right-of-way or City of Oxnard easement and maintained by the City of Oxnard Public Works Department. Private and System Side Hydrants are not allowed in The City of Oxnard. DESIGN REQUIREMENTS All new hydrants shall be 6" wet barrel with National Standard Thread, NST outlets. (Refer to Public Works Standard Plates) The sizing and type of City Oxnard approved hydrants are as follows: Type Residential R-1 Type I1 R-2 or greater 4" x 2-½" Jones or approved equal 4 x 4" x 2-½" Jones or approved equal FIRE FLOW AND HYDRANT SPACING Use Type Flow Pressure SF1 Single Family 1 1,500 GPM 20 PSI SF2 Single Family 2 2,500 GPM 20 PSI GC General Commercial 2,500 GPM 20 PSI HC Heavy Commercial 3,500 GPM 20 PSI MF Multi Family 3,000 GPM 20 PSI CBD Commercial Business District 4,000 GPM 20 PSI M/I Manufacturing/Industry 4,500 GPM 20 PSI High Rise Case by Case Basis 20 PSI FDP#33 E:\Downloads\wp-office\FDP#33 Fire Hydrant Standards.rtf Page 1 of 7
2 A sufficient number of hydrants shall be installed to concentrate the required fire flow within 400' of any structure. Hydrants shall be placed at least 50' from the structure being protected. Where this is not possible, they shall be placed where the possibility of injury from building collapse is limited. Installation locations shall be approved by the Fire Prevention Bureau. Any changes or relocation of fire hydrants from the approved hydrant location plan shall be approved by the Fire Prevention Bureau prior to installation or relocation. Streets with medians of more than four lanes of traffic shall have hydrants placed on each side of the median so that fire lines will not have to cross the street. Tactical considerations may require additional hydrants and will be considered on a project-by project basis. Onsite hydrants shall not be connected to the fire sprinkler system. When any portion of a building is more than 150 feet from a fire hydrant provided on a public street, onsite hydrants capable of providing the required fire flow will be required. Residential A spacing requirement of 500 feet with no structure more than 300 feet from a hydrant. Multiple family residential spacing is 300 feet with no structure more than 200 feet from a hydrant. Industrial and Commercial A spacing requirement of 300 feet and located so that no structure is more than 150 feet from multiple outlet hydrants (onsite hydrants are included). Schools California Fire Code Appendix C shall be used to determine distance/spacing, and number of hydrants. The State Fire Marshal (SFM) requires the Division of State Architect (DSA) to request water and access requirements and approval from the local jurisdiction. Private schools shall comply with all the requirements for commercial buildings. Local requirements are applicable to private schools. NOTE: Fire flows listed are guidelines and specific projects may require different fire flows depending on occupancy, size, and construction of a particular building. Fire flow for a project will be based on the largest building within the project. Be aware that the City Water Department has reduced the city water pressure during periods of conservation. A Fire Protection Engineer may be required to assist us with your project.
3 Fire Hydrant Standards (cont.)
4 Fire Hydrant Standards (cont.)
5
6 Fire hydrants shall be painted yellow. Prior to occupancy of any structure, fire hydrant locations shall be clearly identified by the installation of blue reflective markers in the middle of the street in accordance with Fire Department standards. If the final asphalt cap is not in place at the time final occupancy is desired, the hydrant markers shall still be installed and replaced when the final asphalt cap is completed..
7 DEFINITIONS Fire Hydrant Standards (cont.) ACCESS POINT: An approved access is required for all new buildings and shall reach to a point (Access Point) within 150 feet of all exterior areas of each building. CBC: California Building Code, California Code of Regulations Title 24, Part 2 CFC: California Fire Code CFC Appendix B: Fire-Flow Requirements for Buildings. EXISTING PARCELS: Parcels (or lots) that were legally divided prior to October 1, FLOOR AREA: The area included within the surrounding exterior walls of a building or portion thereof, exclusive of vent shafts and courts. The floor area of a building, or portion thereof, not provided with surrounding exterior walls shall be the usable area under the horizontal projection of the roof or floor above. Ref: CBC FIRE FLOW: The flow rate of a water supply, measured at 20 pounds per square inch (PSI) (137.9kPa) residual pressure that is available for firefighting. FIRE AREA: The total floor area, in ft 2, used to determine the required fire flow. LOCAL ORDINANCE: Amendments to the CFC adopted by City of Oxnard. NFPA 13: National Fire Protection Association, Standard for the Installation of Sprinkler Systems. OCCUPANCY TYPE: The purpose for which a building or part thereof is used or intended to be used, as determined by Chapter 3, CBC. PUBLIC HYDRANT/ON-SITE HYDRANT: Maintained by City of Oxnard Public Works Department in the public right-of-way or City of Oxnard easement. PRIVATE HYDRANT: Located on private property and not within the City of Oxnard Public Works Department s easement. Not allowed. SINGLE FAMILY DWELLING (SFD): One and two family dwellings, including attached or detached private garages. SYSTEM SIDE HYDRANT (or YARD HYDRANT): Connected to underground piping between the Fire Department Connection (FDC) and the sprinkler riser of a fire sprinkler system. Not allowed. TYPE OF CONSTRUCTION: Determined from Chapter 6 of the CBC.
Mobile Fire Rescue Department Bureau of Fire Prevention
222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief January 2011 Fire Protection Water Supply 507.1 Required water supply. An approved water supply
More informationCity of Vista Fire Department
City of Vista Fire Department Development Services Section 600 Eucalyptus Avenue, Vista CA 92084 Guideline: Underground Piping for Private Fire Hydrants & Fire Sprinkler Supply. Updated: January, 2008
More informationFire & Life Safety Requirements For Fire Department Access and Water Supplies
Fire & Life Safety Requirements For Fire Department Access and Water Supplies This brochure is being provided as a resource only. The items listed inside are the requirements most generally cited on plans
More informationOxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)
Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD STANDPIPE SYSTEMS PURPOSE This standard outlines the general requirements for the installation of standpipe systems. CODE REFERENCES
More informationFIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES
Established 1949 FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES The following are guidelines for new development. Any submitted plans must comply with these guidelines,
More informationFire Flow Requirements Standard
Fire Flow Requirements Standard Scope This standard documents the requirements for fire flow within the Fresno County Fire Protection District (FCFPD). This includes areas that have a water purveyor who
More informationFire Flow Requirements Standard
Fire Flow Requirements Standard Scope This standard documents the requirements for fire flow within the Fresno County Fire Protection District (FCFPD). This includes areas that have a water purveyor who
More informationTAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954)
TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida 33321 Telephone: (954) 597-3800, Fax: (954) 597-3810 SITE PLAN REVIEW CHECKLIST A goal of the Tamarac Fire
More informationCITY OF PASADENA FIRE DEPARTMENT
Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in
More informationFIRE APPARATUS ACCESS AND WATER SUPPLY GUIDELINE
City of Conroe Fire Department Fire Marshal s Office 300 W. Davis 1 st Floor Conroe, Texas 77301 T: (936) 522-3080 F: (936) 522-3079 firecodes@cityofconroe.org FIRE APPARATUS ACCESS AND WATER SUPPLY GUIDELINE
More informationTETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition. Chapter I General Provisions
TETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition Chapter I General Provisions SECTION 1.1: TITLE. This Resolution shall be known as the Teton County Fire Protection Resolution
More informationThis guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.
This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue. North Operating Center 11945 SW 70 th Avenue Tigard, OR 97223 Phone:
More informationAccess Aisle (Van) (Flow Test) Water Mains (Location & Sizes) Building Entrances. Building, Facilities, Element. Curb Ramps (Built-up)
GWINNETT COUNTY Department of Fire & Emergency Services Office of the Fire Marshall S001 Access Aisle (Car) S005 S010 S015 S020 S025 S030 S035 S040 S045 S050 S055 S060 S065 S070 S075 S080 S085 Access Aisle
More informationAUTOMATIC FIRE SPRINKLER SYSTEMS
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system
More informationTABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES...
TABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES... 4 SITE AND DEVELOPMENT PLAN REVIEW TURNAROUND TIMES... 4 DEVELOPMENT
More informationLarge Family Daycare Guideline
Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose
More informationFire District Dwelling Construction Requirements
Fire District Dwelling Construction Requirements Includes Sacramento County Fire Marshals Association Standard for Residential Sprinklers City of Rancho Cordova Building & Safety Department 2729 Prospect
More information4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.
Everything a firefighter wants to tell a design professional or building code official, in one hour. 1 2 3 1 4 The job of the fire department is to put the wet stuff on the red stuff. 5 Job #1. of the
More informationFIRE PLAN CHECK FORM/CORRECTION List for Single Family Residences, Duplexes, and Garages
City of Escondido Fire Department 1163 N Centre City Parkway Escondido, CA 92026 Phone: 760-839-5400 FAX: 760-739-7060 PASS / RESUBMIT FIRE PLAN CHECK FORM/CORRECTION List for Single Family Residences,
More informationSite Plans. Fire Code Requirements
Site Plans Fire Code Requirements Outline Before you start Critical building information drives requirements Access Requirements Access, aerial access, road design, remoteness, fire lanes, residential
More informationFIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS
Department of Fire Rescue & Emergency Services Fire Marshal s Office Dania Beach District 103 West Dania Beach Blvd. Dania Beach, Florida 33004 Office: (954)342-4262 Fax: (954)342-4265 FIRE SPRINKLER SHOP
More informationC I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) PHONE (951) FAX
C I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) 922-3210 - PHONE (951) 922-0318 - FAX CITY OF BANNING FIRE SERVICES STANDARD CONDITIONS OF APPROVAL FOR RESIDENTIAL BUILDINGS
More informationFire & Life Safety Supplemental Rules & Regulations for New Construction & Significant Remodels
DEPARTMENT OF PUBLIC SAFETY FIRE MARSHAL S OFFICE 9611 SE 36 TH ST Mercer Island, WA 98040 (206) 236-3515 direct; (206) 236-3622 FAX Rod Mandery, Fire Marshal Updated version: 03-19-2002 Fire & Life Safety
More informationAUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)
AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with
More informationCITY OF SIMI VALLEY MEMORANDUM
CITY OF SIMI VALLEY MEMORANDUM AGENDA ITEM NO. Consent (10) November 14, 2016 TO: FROM: City Council Department of Environmental Services SUBJECT: ADOPTION OF A RESOLUTION TO RATIFY VENTURA COUNTY FIRE
More informationFIRE PLAN CHECK CORRECTION List for Commercial Occupancies
PASS / RESUBMIT Rancho Santa Fe Fire Protection District P.O. Box 410 18027 Calle Ambiente Rancho Santa Fe California 92067-0410 Tel. (858) 756-5971 Fax (858) 756-4799 FIRE PLAN CHECK CORRECTION List for
More informationDrexel Heights Fire District 2012 International Fire Code Amendments
February 15, 2013 Drexel Heights Fire District adopted the International Fire Code 2012 edition in its entirety unless otherwise amended below. CHAPTER 1 SCOPE AND ADMINISTRATION SECTION 101 SCOPE AND
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationFIRE PREVENTION CODE
164.01 Purpose 164.03 Amendments to Fire Prevention Code 164.02 Adoption of Fire Prevention Code 164.04 Board of Appeals 164.01 PURPOSE. The purpose of this chapter is to prescribe regulations governing
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;
More informationChapter 2: Identification, water and access
Chapter 2: Identification, water and access As you are approaching the occupancy to be inspected, take note of building and fire protection services. Put yourself in the shoes of a first arriving company
More informationTable of Contents, Page 10 Page CHAPTER 6 FIRE SAFETY STANDARDS 6.0 GENERAL POLICIES 6-2 6.01 Authority 6-2 6.02 Scope 6-2 6.03 Consistency with Other Standards and Regulations 6-2 6.04 Definitions 6-3
More informationLouisville Metro Ordinance (Chapter 94: Fire Prevention) FIRE HYDRANTS, WATER MAINS AND WATER SUPPLY.
Louisville Metro Ordinance (Chapter 94: Fire Prevention) To search for all Metro Ordinances, click here to be directed to American Legal Publishing's website. 94.82 FIRE HYDRANTS, WATER MAINS AND WATER
More informationORDINANCE NO
ORDINANCE NO. 2016-14 AN ORDINANCE AMENDING THE CODE OF ORDINANCES, CITY OF BOERNE, TEXAS, BY AMENDING CHAPTER 5 - BUILDINGS AND BUILDING REGULATIONS, ARTICLE VIII, LIFE & SAFETY CODE, SECTION 5-236; AND
More informationS000 SITE REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM
APPR NO. FIRE CODE COMPLIANCE ITEM S000 S001 S005 (Automobile Access Aisle) shall be a minimum of 5 ft wide, a common access aisle may be shared by 2 vehicles. Surface slopes shall not exceed 1:50(2%)
More informationFIRE-FLOW REQUIREMENTS FOR BUILDINGS Based on the 2012 Edition of the International Fire Code
FIRE-FLOW REQUIREMENTS FOR BUILDINGS Based on the 2012 Edition of the International Fire Code One of the basic essentials needed to control and extinguish a structure fire is an adequate water supply.
More informationA Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE
A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE Fire Department Core Values Protect lives, property, and the environment through preparedness, prevention,
More informationTRI-LAKES MONUMENT FIRE PROTECTION DISTRICT
TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationPINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT
Amendments for 2015 IFC CHAPTER 1 SCOPE AND ADMINISTRATION Section 101.2.1 Appendices. All appendices to be adopted Section 113.2 Schedule of permit fees. Is AMENDED to read: A fee for each permit shall
More informationFIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Installation of Residential Fire Sprinkler Systems STANDARD #C-002 EFFECTIVE 03-19-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationORDINANCE NO, 5907 AN ORDINANCE AMENDING ALBANY MUNICIPAL CODE CHAPTER , UNIFORM FIRE CODE
ORDINANCE NO, 5907 AN ORDINANCE AMENDING ALBANY MUNICIPAL CODE CHAPTER 17. 28, UNIFORM FIRE CODE WHEREAS, the state of Oregon has adopted the current edition of the Oregon Fire Code authorized by ORS 476.035,
More informationSACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET
SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET 1 SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT
More informationCALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM 1 2 1/AC AC SS SS/CC
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Adopting Agency BSC SFM HCD DSA OSHPD CSA DPH AGR DWR CA 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:
More informationPRESENTERS OVERVIEW COMMUNITY WORKSHOP OVERVIEW OF THE 2010 EDITION OF THE CALIFORNIA BUILDING STANDARDS CODE AND LOCAL AMENDMENTS
COMMUNITY WORKSHOP OVERVIEW OF THE 2010 EDITION OF THE CALIFORNIA BUILDING STANDARDS CODE AND LOCAL AMENDMENTS Prepared By PRESENTERS Truong Huynh, Building and Safety Bureau David Zinnen, Fire Prevention
More informationCITY OF HEALDSBURG SENIOR CENTER IMPROVEMENT PROJECT
CITY OF HEALDSBURG 2015-16 MEASURE V SENIOR CENTER IMPROVEMENT PROJECT VICINITY MAP DRAWING INDEX ARCHITECTURAL A-0 COVER SHEET HEALDSBURG SENIOR CENTER SC-1 SENIOR CENTER FLOOR PLAN SC-1.1 SENIOR CENTER
More informationREGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES
REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES DATE: January 6, 2014 INFORMATION BULLETIN: F-14-002 APPROVED BY: W. Schellhous 2013 California Fire Code (CFC) and Riverside Municipal
More information2016 California Building Code Adoption OC amendments Summary Title/Subject Justification/Comments Action
OC Ordinance 7-1-12 2016 Code 2013 Code 2016 Adoption OC amendments Summary Title/Subject Justification/Comments Action Adoption of the, International Building Code, California Residential Code, California
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 2017 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD SPECIAL EVENT PUBLIC ASSEMBLY PURPOSE This standard is applicable to any public event, exhibit space, booth, festival or any other similar
More informationWater Mutuals or Private Wells
Theseguidelinesapplyto: SantaClaraCounty FireMarshal soffice FireProtectionWaterSupplyRequirementsforPropertiesservedby WaterMutualsorPrivateWells Non residentialstructures Newconstructionandadditionsover500sq.ft.
More informationDiesel Fuel System Report
Transbay Transit Center San Francisco, CA Prepared for: Pelli Clarke Pelli Architects 1056 Chapel Street New Haven, CT 06510 Prepared by: WSP 405 Howard Street, Suite 500 San Francisco, CA 94105 Mechanical
More informationCHAPTER 6 FIRE SAFETY STANDARDS. Adopted: September 22, Revised: August 7, April 1, May 15, June 1, 2003
CHAPTER 6 FIRE SAFETY STANDARDS Adopted: September 22, 1981 Revised: August 7, 1986 September 29, 1988 April 1, 1992 September 4, 1992 May 15, 2001 June 1, 2003 September 15, 2004 December 1, 2015 6.0
More informationVACAVILLE FIRE PROTECTION DISTRICT 420 Vine Street Vacaville, California (707)
VACAVILLE FIRE PROTECTION DISTRICT 420 Vine Street Vacaville, California 95688 (707) 447-2252 Requirements for new construction within the boundaries of the Vacaville Fire Protection District include,
More informationORDINANCE NO WHEREAS, the City of Hammond Water Department owns and operates
SPONSOR: Scott Rakos 6 th District Councilman ORDINANCE NO. 9424 AN ORDINANCE TO CREATE A NEW SECTION OF CHAPTER 93 (FIRE WHEREAS, the City of Hammond Water Department owns and operates municipal water
More informationFIRE SERVICE FEATURES
CHAPTER 5 FIRE SERVICE FEATURES SECTION 501 GENERAL 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this chapter. 501.2 Permits. A permit shall be required as
More informationHCD DSA OSHPD 1 2 1/AC AC SS SS/CC
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency
More informationRocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO
Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3
More informationGLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE
GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: From: Subject: Whom It May Concern Carl Ray Austerman, Fire Marshal Contractor s Guide Welcome to the Glendale Fire Department s Contractors Guide. This
More informationResidential-based Care Facility R-4 Guideline
Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care
More informationFire Department Fire Prevention Inspection Services. HIGH RISE STRUCTURE Fire Inspection Program
HIGH RISE STRUCTURE Fire Inspection Program Meeting Agenda Fire Prevention Mission High Rise Fire Inspection Program Question and Answer 2 Fire Chief Bertral Washington 3 Our Mission Deputy Fire Marshal
More informationBusiness Fire Inspection. City of Guadalupe
Business Fire Inspection City of Guadalupe Intent Provide general information on the California Fire Code (CFC) and City of Guadalupe Municipal Code (GMC) requirements. Provide information and the most
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven
More informationGLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE
GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: Contractors From: Charles Jenkins, Fire Marshal Subject: Contractor s Guide This guide is provided by the Fire Marshal as a service to the construction
More informationMcMAHON FP200 OUTAGAMIE COUNTY ADMINISTRATION CENTER S. WALNUT & W. 8TH, APPLETON, WI ALTERATION / ADDITION
4/5/017 1:58:50 PM C. 1445 DRIVE NEENAH, WI 54956 EXISTING JUSTICE CENTER IS FULLY SPRINKLED C. EXISTING FIRE PUMP BASEMENT LEVEL EXISTING FDC FOR DRY STANDPIPE IN STAIRWELL SHALL BE DEMOLISHED, SEE FP
More informationSprinkler Permit Applications
REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationAPPENDIX X. Contents:
PARISH OF ASCENSION OFFICE OF PLANNING AND DEVELOPMENT APPENDIX X FIRE HYDRANT CODE Contents: 17-1001. 17-1002. 17-1003. 17-1004. 17-1005. 17-1006. 17-1007. 17-1008. 17-1009. Purpose... 3 Fire Hydrants
More informationThis guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.
This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue. North Operating Center 11945 SW 70 th Avenue Tigard, OR 97223 Phone:
More informationCAMP VERDE FIRE DISTRICT
CAMP VERDE FIRE DISTRICT FIRE PROTECTION DEVELOPMENT STANDARDS INTRODUCTION Pursuant to Section 101 of the International Fire Code, 2012 edition, with local amendments, the following specifications and
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved;
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationFire Suppression Introduction Contact Information
Contact Information Jeffrey Mayers Fire Safety Engineering Manager Georgia State Fire Marshal s Office 404-617-8515 E-mail: jmayers@sfm.ga.gov 1 Goal of This Seminar: Hierarchy of Codes List reference
More informationCarbon Dioxide Enrichment Systems
Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA. 92602 www.ocfa.org 714-573-6100 Carbon Dioxide Enrichment Systems Guideline G-17 Serving the Cities
More informationRED BOOK CONTRACTOR S. Fire Department Access and Design Engineering Information
RED CONTRACTOR S BOOK Fire Department Access and Design Engineering Information Orange County Fire Rescue Department An Accredited; Class One Department OFFICE OF THE FIRE MARSHAL David G. Kilbury, Fire
More informationMONTECITO FIRE PROTECTION DISTRICT
Section 5a MONTECITO FIRE PROTECTION DISTRICT FIRE PROTECTION PLAN Residential Automatic Fire Sprinkler System Installations I Automatic Fire Sprinkler System Standards 1. Definition and Standard: An automatic
More information1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)
1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors) 1. What is the minimum diameter for a non-hydraulically calculated Class III fire standpipe that is part of a combined
More informationTents and Temporary Membrane Structures Permit Procedure
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1040 E. Hillsdale Blvd. Foster City, CA 94404 (650) 522-7940 FAX: (650) 522-7941 Tents and Temporary Membrane Structures
More informationRESIDENTIAL CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2017 LACRC
RESIDENTIAL CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2017 LACRC No. 1006 R313.2 Article 1 03-01-17 Page 1 of 5 AUTOMATIC FIRE SPRINKLER SYSTEM
More informationFire Sprinkler System Design and Installation Requirements
Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah
More informationSECTION POLICY MANUAL
Menlo Park Fire Protection District Bureau of Fire Prevention and Life Safety 170 Middlefield Rd. Menlo Park, CA 94025 650-688-8425 Bureau of Fire Prevention and Life Safety SECTION 101.6 POLICY MANUAL
More informationRequirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011
1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection
More information2015 Recommended Building Code with Amendments. The Executive Committee of the Central Iowa Code Consortium does ordain as follows:
2015 Recommended with Amendments A resolution of the Central Iowa Code Consortium recommending adoption of the 2015 edition of the International, regulating and governing the conditions and maintenance
More informationSingle Room Occupancy Hotel Safety & Stabilization Task Force
Page 1 of 6 Graphics Version Skip to Content Single Room Occupancy Hotel Safety & Stabilization Task Force sfgov residents business government visitors online serviceshelp Single Room Occupancy (SRO) Hotel
More informationFIRE PREVENTION CODE. conditions hazardous to life and property from fire, hazardous materials, or explosion.
ORDINANCE 14-18 AN ORDINANCE REGARDING THE PROPOSED ADOPTION BY REFERENCE THE INTERNATIONAL FIRE CODE, 2015 EDITION AND INCLUDING APPENDIX B, D, E, F, G AND I AND PROVIDING PENALTIES. BE IT ORDAINED BY
More informationResidential Based Care Facility Guidelines
Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities
More informationSOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21
SOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21 ARTICLE I FIRE PREVENTION CODE 21-1. Statutory authority 21-2. Adoption of standards 21-3. Definitions 21-4. Exceptions to Fire Prevention Code
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationFIRE PREVENTION STANDARDS
DATE: 04/11/02 APPROVED: NUMBER: FP0-010 REVISED: FIRE PREVENTION STANDARDS TITLE: Large Family Day Cares (9-14 kids) PURPOSE: The purpose of this standard is to acquaint the applicant with the applicable
More informationFIRE CODE APPLICATION GUIDE FOR DEVELOPMENT IN UNINCORPORATED MULTNOMAH COUNTY
FIRE CODE APPLICATION GUIDE FOR DEVELOPMENT IN UNINCORPORATED MULTNOMAH COUNTY This guide is intended to provide assistance in the application of the fire code in Unincorporated Multnomah County. October
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationConstruction and Development Guide
Construction and Development Guide **Based on the 2014 Indiana Fire Prevention Code and relevant NFPA Codes and Standards ** Copyright 2018 Clay Fire CRRD 1 P a g e Table of Contents Map of Jurisdiction...
More informationCHAPTER FIRE CODE
Section 12. Chapter 17.32, Title 17 of the Ordinance Code of the County of Kern, is hereby repealed; and a new Chapter 17.32, Title 17 of the Ordinance Code of the County of Kern, is hereby added to read
More information5.8 PUBLIC SERVICES FIRE PROTECTION AND EMERGENCY SERVICES
5.8 PUBLIC SERVICES FIRE PROTECTION AND EMERGENCY SERVICES 5.8.1 INTRODUCTION This section assesses the proposed projects potential impacts on fire protection services. Information for the following analysis
More informationTents and Temporary Membrane Structures Packet
Tents and Temporary Membrane Structures Packet Tents and Temporary Membrane Structures Permit Procedure VERSION 1.0 12/2015 SCOPE: These provisions shall apply to any tent or temporary membrane structure
More informationTo expedite the plan review and inspection processes, please refer to the information below.
Guidelines: The goal of the Denison Fire Department is to assist its customers in understanding our submittal, plan review and inspection process and policies, as they pertain to new construction. Familiarity
More information