1 OXNARD FIRE DEPARTMENT 360 West Second Street Oxnard, CA (805) Fax (805) REQUIREMENTS FIRE HYDRANT STANDARDS Fire hydrants and required access roads shall be provided prior to and during the time of construction. Hydrants shall be visible and accessible from the required access road. All combustible framing must be kept within 150 feet of an acceptable access road serviced with active fire hydrants. An acceptable fire access road shall have a minimum clear width of 26 feet and a vertical clearance of 13 feet, 6 inches, be an all weather paved surface and support a 75,000-pound fire apparatus. After the hydrant location plans are approved, the engineered underground supply piping plans, with hydrants shown at the approved locations, are required to be plan checked and approved prior to installation. The installation is inspected by the City of Oxnard Public Works Department. All hydrants shall be Public Hydrants located in a public right-of-way or City of Oxnard easement and maintained by the City of Oxnard Public Works Department. Private and System Side Hydrants are not allowed in The City of Oxnard. DESIGN REQUIREMENTS All new hydrants shall be 6" wet barrel with National Standard Thread, NST outlets. (Refer to Public Works Standard Plates) The sizing and type of City Oxnard approved hydrants are as follows: Type Residential R-1 Type I1 R-2 or greater 4" x 2-½" Jones or approved equal 4 x 4" x 2-½" Jones or approved equal FIRE FLOW AND HYDRANT SPACING Use Type Flow Pressure SF1 Single Family 1 1,500 GPM 20 PSI SF2 Single Family 2 2,500 GPM 20 PSI GC General Commercial 2,500 GPM 20 PSI HC Heavy Commercial 3,500 GPM 20 PSI MF Multi Family 3,000 GPM 20 PSI CBD Commercial Business District 4,000 GPM 20 PSI M/I Manufacturing/Industry 4,500 GPM 20 PSI High Rise Case by Case Basis 20 PSI FDP#33 E:\Downloads\wp-office\FDP#33 Fire Hydrant Standards.rtf Page 1 of 7

2 A sufficient number of hydrants shall be installed to concentrate the required fire flow within 400' of any structure. Hydrants shall be placed at least 50' from the structure being protected. Where this is not possible, they shall be placed where the possibility of injury from building collapse is limited. Installation locations shall be approved by the Fire Prevention Bureau. Any changes or relocation of fire hydrants from the approved hydrant location plan shall be approved by the Fire Prevention Bureau prior to installation or relocation. Streets with medians of more than four lanes of traffic shall have hydrants placed on each side of the median so that fire lines will not have to cross the street. Tactical considerations may require additional hydrants and will be considered on a project-by project basis. Onsite hydrants shall not be connected to the fire sprinkler system. When any portion of a building is more than 150 feet from a fire hydrant provided on a public street, onsite hydrants capable of providing the required fire flow will be required. Residential A spacing requirement of 500 feet with no structure more than 300 feet from a hydrant. Multiple family residential spacing is 300 feet with no structure more than 200 feet from a hydrant. Industrial and Commercial A spacing requirement of 300 feet and located so that no structure is more than 150 feet from multiple outlet hydrants (onsite hydrants are included). Schools California Fire Code Appendix C shall be used to determine distance/spacing, and number of hydrants. The State Fire Marshal (SFM) requires the Division of State Architect (DSA) to request water and access requirements and approval from the local jurisdiction. Private schools shall comply with all the requirements for commercial buildings. Local requirements are applicable to private schools. NOTE: Fire flows listed are guidelines and specific projects may require different fire flows depending on occupancy, size, and construction of a particular building. Fire flow for a project will be based on the largest building within the project. Be aware that the City Water Department has reduced the city water pressure during periods of conservation. A Fire Protection Engineer may be required to assist us with your project.

3 Fire Hydrant Standards (cont.)

4 Fire Hydrant Standards (cont.)

5

6 Fire hydrants shall be painted yellow. Prior to occupancy of any structure, fire hydrant locations shall be clearly identified by the installation of blue reflective markers in the middle of the street in accordance with Fire Department standards. If the final asphalt cap is not in place at the time final occupancy is desired, the hydrant markers shall still be installed and replaced when the final asphalt cap is completed..

7 DEFINITIONS Fire Hydrant Standards (cont.) ACCESS POINT: An approved access is required for all new buildings and shall reach to a point (Access Point) within 150 feet of all exterior areas of each building. CBC: California Building Code, California Code of Regulations Title 24, Part 2 CFC: California Fire Code CFC Appendix B: Fire-Flow Requirements for Buildings. EXISTING PARCELS: Parcels (or lots) that were legally divided prior to October 1, FLOOR AREA: The area included within the surrounding exterior walls of a building or portion thereof, exclusive of vent shafts and courts. The floor area of a building, or portion thereof, not provided with surrounding exterior walls shall be the usable area under the horizontal projection of the roof or floor above. Ref: CBC FIRE FLOW: The flow rate of a water supply, measured at 20 pounds per square inch (PSI) (137.9kPa) residual pressure that is available for firefighting. FIRE AREA: The total floor area, in ft 2, used to determine the required fire flow. LOCAL ORDINANCE: Amendments to the CFC adopted by City of Oxnard. NFPA 13: National Fire Protection Association, Standard for the Installation of Sprinkler Systems. OCCUPANCY TYPE: The purpose for which a building or part thereof is used or intended to be used, as determined by Chapter 3, CBC. PUBLIC HYDRANT/ON-SITE HYDRANT: Maintained by City of Oxnard Public Works Department in the public right-of-way or City of Oxnard easement. PRIVATE HYDRANT: Located on private property and not within the City of Oxnard Public Works Department s easement. Not allowed. SINGLE FAMILY DWELLING (SFD): One and two family dwellings, including attached or detached private garages. SYSTEM SIDE HYDRANT (or YARD HYDRANT): Connected to underground piping between the Fire Department Connection (FDC) and the sprinkler riser of a fire sprinkler system. Not allowed. TYPE OF CONSTRUCTION: Determined from Chapter 6 of the CBC.

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES Established 1949 FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES The following are guidelines for new development. Any submitted plans must comply with these guidelines,

More information

TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954)

TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954) TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida 33321 Telephone: (954) 597-3800, Fax: (954) 597-3810 SITE PLAN REVIEW CHECKLIST A goal of the Tamarac Fire

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD STANDPIPE SYSTEMS PURPOSE This standard outlines the general requirements for the installation of standpipe systems. CODE REFERENCES

More information

Fire & Life Safety Supplemental Rules & Regulations for New Construction & Significant Remodels

Fire & Life Safety Supplemental Rules & Regulations for New Construction & Significant Remodels DEPARTMENT OF PUBLIC SAFETY FIRE MARSHAL S OFFICE 9611 SE 36 TH ST Mercer Island, WA 98040 (206) 236-3515 direct; (206) 236-3622 FAX Rod Mandery, Fire Marshal Updated version: 03-19-2002 Fire & Life Safety

More information

PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT

PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT Amendments for 2015 IFC CHAPTER 1 SCOPE AND ADMINISTRATION Section 101.2.1 Appendices. All appendices to be adopted Section 113.2 Schedule of permit fees. Is AMENDED to read: A fee for each permit shall

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Installation of Residential Fire Sprinkler Systems STANDARD #C-002 EFFECTIVE 03-19-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

FIRE PLAN CHECK CORRECTION List for Commercial Occupancies

FIRE PLAN CHECK CORRECTION List for Commercial Occupancies PASS / RESUBMIT Rancho Santa Fe Fire Protection District P.O. Box 410 18027 Calle Ambiente Rancho Santa Fe California 92067-0410 Tel. (858) 756-5971 Fax (858) 756-4799 FIRE PLAN CHECK CORRECTION List for

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

Water Mutuals or Private Wells

Water Mutuals or Private Wells Theseguidelinesapplyto: SantaClaraCounty FireMarshal soffice FireProtectionWaterSupplyRequirementsforPropertiesservedby WaterMutualsorPrivateWells Non residentialstructures Newconstructionandadditionsover500sq.ft.

More information

MONTECITO FIRE PROTECTION DISTRICT

MONTECITO FIRE PROTECTION DISTRICT Section 5a MONTECITO FIRE PROTECTION DISTRICT FIRE PROTECTION PLAN Residential Automatic Fire Sprinkler System Installations I Automatic Fire Sprinkler System Standards 1. Definition and Standard: An automatic

More information

Sprinkler Permit Applications

Sprinkler Permit Applications REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations

More information

Fire Sprinkler System Design and Installation Requirements

Fire Sprinkler System Design and Installation Requirements Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah

More information

Residential Based Care Facility Guidelines

Residential Based Care Facility Guidelines Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities

More information

Tents and Temporary Membrane Structures Permit Procedure

Tents and Temporary Membrane Structures Permit Procedure FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1040 E. Hillsdale Blvd. Foster City, CA 94404 (650) 522-7940 FAX: (650) 522-7941 Tents and Temporary Membrane Structures

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION CHAPTER 23.45 LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION Sections 23.45.100... Local amendments to the International Fire Code, 2012 Edition.... 2 23.45.105.4.2 Information on construction

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Technical Policy Title: Plant Processing and Extraction

More information

GENERAL AREAS OF INSPECTION

GENERAL AREAS OF INSPECTION This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that

More information

To expedite the plan review and inspection processes, please refer to the information below.

To expedite the plan review and inspection processes, please refer to the information below. Guidelines: The goal of the Denison Fire Department is to assist its customers in understanding our submittal, plan review and inspection process and policies, as they pertain to new construction. Familiarity

More information

LANDSCAPE AND IRRIGATION PLAN PREPARATION GUIDELINES

LANDSCAPE AND IRRIGATION PLAN PREPARATION GUIDELINES LANDSCAPE AND IRRIGATION PLAN PREPARATION GUIDELINES The Parks Planning and Development Division of the City of Modesto s Parks, Recreation and Neighborhoods Department is responsible for the task of reviewing

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2005-02 ADOPTING FIRE PREVENTION REGULATIONS FOR THE PURPOSE OF GOVERNING CONDITIONS HAZARDOUS TO LIFE AND PROPERTY FROM FIRE OR EXPLOSION, AND ESTABLISHING A BUREAU OF FIRE PREVENTION BE

More information

CCCFPD RESIDENTIAL BUILDING REQUIREMENTS

CCCFPD RESIDENTIAL BUILDING REQUIREMENTS Coal Creek Canyon Fire Protection District P.O. Box 7187 Crescent Branch Golden, Colorado 80403 303-642-3121 Fax 303-642-1652 www.coalcreekcanyonfd.org CCCFPD@aol.com Dear Property Owner / Contractor:

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

IV. ENVIRONMENTAL IMPACT ANALYSIS F. PUBLIC SERVICES 1. FIRE PROTECTION

IV. ENVIRONMENTAL IMPACT ANALYSIS F. PUBLIC SERVICES 1. FIRE PROTECTION IV. ENVIRONMENTAL IMPACT ANALYSIS F. PUBLIC SERVICES 1. FIRE PROTECTION 1. INTRODUCTION This section addresses potential impacts on fire protection and emergency medical services provided by the Fire Department

More information

ENVIRONMENTAL IMPACT ANALYSIS PUBLIC SERVICES: FIRE PROTECTION 1. INTRODUCTION

ENVIRONMENTAL IMPACT ANALYSIS PUBLIC SERVICES: FIRE PROTECTION 1. INTRODUCTION IV. K.1. ENVIRONMENTAL IMPACT ANALYSIS PUBLIC SERVICES: FIRE PROTECTION 1. INTRODUCTION This section discusses the physical setting and provides analysis of fire protection services in the area where the

More information

Orange Township Fire Department Fire Prevention Bureau

Orange Township Fire Department Fire Prevention Bureau Orange Township Fire Department Fire Prevention Bureau Under Ground Fire Protection Plan Submittal Checklist Project Name: Project Address: Date: Designers Name: Company Name: Phone Number: Email: Fax:

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1040 East Hillsdale Blvd Foster City, CA 94404 (650) 522-7940 FAX: (650) 522-7941 MAINTENANCE AND SERVICE OF AUTOMATIC FIRE

More information

CITY OF PALM BEACH GARDENS ORDINANCE NO. 12, 2002

CITY OF PALM BEACH GARDENS ORDINANCE NO. 12, 2002 CITY OF PALM BEACH GARDENS ORDINANCE NO. 12, 2002 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF PALM BEACH GARDENS, FLORIDA, ADOPTING THE FLORIDA FIRE PREVENTION CODE; REPEALING ARTICLE III, "STANDARDS,"

More information

WALL ESCUTCHEON PIPE SEAL WITH APPROVED FIRE CAULKING (SEE SPECIFICATIONS) NOTE: 12" 12" 24"

WALL ESCUTCHEON PIPE SEAL WITH APPROVED FIRE CAULKING (SEE SPECIFICATIONS) NOTE: 12 12 24 SOUTH TEJON ST., SUITE 00 COLORADO SPRINGS, CO. 00 TELE.: FAX: WALL ESCUTCHEON PACK ANNULAR SPACE WITH MINERAL WOOL GENERAL NOTES. THIS PROJECT INCLUDES THE DESIGN AND PROVISION OF A NEW WET SPRINKLER

More information

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91% 210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent

More information

GOLDEN FIRE DEPARTMENT FIRE & LIFE SAFETY DIVISION

GOLDEN FIRE DEPARTMENT FIRE & LIFE SAFETY DIVISION GOLDEN FIRE DEPARTMENT FIRE & LIFE SAFETY DIVISION 911 10 th Street Golden, Colorado 80401 303-384-8094 Contractor s Permit & Inspection Guide *Note: this is not an all-inclusive list of requirements;

More information

SECTION 5.9 Fire Protection

SECTION 5.9 Fire Protection SECTION 5.9 Fire Protection 5.9 FIRE PROTECTION This section provides an analysis of fire protection services, which is based on information provided by the Los Angeles County Fire Department (LACFD).

More information

WEST VIRGINIA UNIVERSITY

WEST VIRGINIA UNIVERSITY WEST VIRGINIA UNIVERSITY Environmental Health and Safety (SOP) WV State Fire Marshal (SFM) Project Plans Review Process & Procedures West Virginia University Environmental Health & Safety Page 1 of 10

More information

Chapter PEDESTRIAN COMMERCIAL (PC) ZONING DISTRICT

Chapter PEDESTRIAN COMMERCIAL (PC) ZONING DISTRICT Chapter 11-17 PEDESTRIAN COMMERCIAL (PC) ZONING DISTRICT Sections: 11-17-01 GENERAL PURPOSE 11-17-02 PERMITTED BUILDING TYPES 11-17-03 USES PERMITTED WITH DESIGN REVIEW 11-17-04 USES PERMITTED BY CONDITIONAL

More information

CITY OF VACAVILLE PLANNING COMMISSION Agenda Item No. G.1 STAFF REPORT January 20, 2015 Staff Contact: Peyman Behvand (707)

CITY OF VACAVILLE PLANNING COMMISSION Agenda Item No. G.1 STAFF REPORT January 20, 2015 Staff Contact: Peyman Behvand (707) CITY OF VACAVILLE PLANNING COMMISSION Agenda Item No. G.1 STAFF REPORT January 20, 2015 Staff Contact: Peyman Behvand (707) 449-5140 TITLE: SOUTHTOWN FIRE STATION 75 REQUEST: DESIGN REVIEW REQUEST TO CONSTRUCT

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

Expectations (continued)

Expectations (continued) Expectations (continued) The work is ready to be inspected. If a problem develops where the work is not ready for inspection, call the FMO and cancel the inspection as soon as you are aware there is a

More information

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA Page of 5. DESCRIPTION Viking EC/QREC Ordinary Hazard ELO Fusible Element Sprinkler VK535 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying

More information

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property City of Chilliwack Bylaw No. 3464 A bylaw to regulate fire prevention and the protection of life and property NOW THEREFORE the Council of the City of Chilliwack in open meeting assembled enacts as follows:

More information

[NOTE: Proposed additions to existing code language are highlighted in yellow.]

[NOTE: Proposed additions to existing code language are highlighted in yellow.] PROPOSED AMENDMENTS TO THE 2015 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY LARIMER COUNTY FOR VACATION HOMES, LARGE VACATION HOMES AND SMALL HOTELS WITHIN THE ESTES VALLEY PLANNING AREA [NOTE: Proposed

More information

Access Management and Site Plan Review. Robert W. Hofrichter Asst Administrator, Transportation and Mobility Planning Division April 2014

Access Management and Site Plan Review. Robert W. Hofrichter Asst Administrator, Transportation and Mobility Planning Division April 2014 Access Management and Site Plan Review Robert W. Hofrichter Asst Administrator, Transportation and Mobility Planning Division April 2014 Access Management 2 Access Management What is Access Management?

More information

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15 N/A N/A 2015 International Fire Code 2015 International Building Code Codes Jurisdictions for Fire and Building Codes Source of Information Building Fire Plumbing Mechanical Electrical Energy Code Accessibility

More information

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX: Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean

More information

Thursday, February 28, :15 a.m. - 11:15 a.m. Sacramento Convention Center Room # 306. Workshop #47. DSA Academy Update

Thursday, February 28, :15 a.m. - 11:15 a.m. Sacramento Convention Center Room # 306. Workshop #47. DSA Academy Update C.A.S.H. 29 TH ANNUAL CONFERENCE ON SCHOOL FACILITIES NEW PROGRAMS, NEW PROMISE CALIFORNIA SCHOOL FACILITIES 2008 Thursday, February 28, 2008 10:15 a.m. - 11:15 a.m. Sacramento Convention Center Room #

More information

Q-0751 Principles of Building Construction Resources

Q-0751 Principles of Building Construction Resources Q-0751 Principles of Building Construction Resources U.S. DEPARTMENT OF HOMELAND SECURITY FEDERAL EMERGENCY MANAGEMENT AGENCY U.S. FIRE ADMINISTRATION NATIONAL FIRE ACADEMY This page intentionally left

More information

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010) CHAPTER 1 SCOPE AND ADMINISTRATION 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 47 and such codes and standards shall

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

Fire Department Fees.

Fire Department Fees. Fire Department Fees. North Liberty Fire Department 25 W. Cherry St., North Liberty, IA Phone: (319) 626-5717 Fax: (319) 626-3238 Fire Department Fee Schedule Council Members, I just wanted to take a moment

More information

IV. Environmental Impact Analysis L. Public Services. 1. Fire Protection. a. Introduction. b. Environmental Setting. (1) Existing Conditions

IV. Environmental Impact Analysis L. Public Services. 1. Fire Protection. a. Introduction. b. Environmental Setting. (1) Existing Conditions IV. Environmental Impact Analysis L. Public Services 1. Fire Protection a. Introduction This section analyzes the Proposed Project s impacts relative to the fire and emergency medical services ( EMS )

More information

CHAPTER 05 - OFFICE OF STATE FIRE MARSHAL SUBCHAPTER 05A - FIRE AND RESCUE SECTION.0900 PUBLIC PROTECTION CLASSIFICATIONS FOR FIRE DISTRICTS

CHAPTER 05 - OFFICE OF STATE FIRE MARSHAL SUBCHAPTER 05A - FIRE AND RESCUE SECTION.0900 PUBLIC PROTECTION CLASSIFICATIONS FOR FIRE DISTRICTS CHAPTER 05 - OFFICE OF STATE FIRE MARSHAL SUBCHAPTER 05A - FIRE AND RESCUE SECTION.0900 PUBLIC PROTECTION CLASSIFICATIONS FOR FIRE DISTRICTS 11 NCAC 05A.0901 DEFINITIONS As used in this Subchapter: (1)

More information

1 Exam Prep. Questions and Answers

1 Exam Prep. Questions and Answers 1 Exam Prep NFPA 14: Standard for the Installation of Standpipe and Hose Systems Questions and Answers 1. According to the NFPA-14, class I standpipes shall be at least inches in size. A. 2" 1/2" C. 3"

More information

For additional information regarding Group I occupancies please call (951)

For additional information regarding Group I occupancies please call (951) Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las

More information

WHEREAS, the City Commission of the City of Cocoa Beach, Florida finds that this ordinance promotes the public health, safety and welfare.

WHEREAS, the City Commission of the City of Cocoa Beach, Florida finds that this ordinance promotes the public health, safety and welfare. 0 1 0 1 ORDINANCE NO. AN ORDINANCE OF THE CITY OF COCOA BEACH, BREVARD COUNTY, FLORIDA, AMENDING THE COCOA BEACH CODE OF ORDINANCES, CHAPTER, ENTITLED FIRE PREVENTION BY: - CORRECTING SCRIVENER ERRORS

More information

Local Amendments 2009 International Fire Code

Local Amendments 2009 International Fire Code Local Amendments 2009 International Fire Code By the following jurisdictions: Black Forest Fire & Rescue Cimarron Hills Fire Department Wescott Fire Department Falcon Fire Department Security Fire Department

More information

The project scope work is 90% new construction and 10% remodel in Esslinger Hall.

The project scope work is 90% new construction and 10% remodel in Esslinger Hall. CREIGHTON ENGINEERING INC. FIRE PROTECTION CONSULTING ENGINEERS 210 N. University Road, Suite 100 Spokane Valley, WA 99206 TEL: 509.921.9755 FAX: 509.921.9806 WEB: www.creightoneng.com SCOTT R. CREIGHTON,

More information

HILLSIDE BUILDING COMMITTEE PLAN REVIEW DIRECTIONS

HILLSIDE BUILDING COMMITTEE PLAN REVIEW DIRECTIONS HILLSIDE BUILDING COMMITTEE PLAN REVIEW DIRECTIONS 1 1. Review Hillside Regulations to ensure your design is in conformance with current Town Code. 2. Complete page 3 and contact Paul Mood at 480-348-3573,

More information

Prepared by: Casey Kempenaar, Senior Planner

Prepared by: Casey Kempenaar, Senior Planner CITY OF CITRUS HEIGHTS PLANNING DIVISION STAFF REPORT PLANNING COMMISSION MEETING September 13, 2017 Prepared by: Casey Kempenaar, Senior Planner REQUEST The applicant requests a Design Review Permit Modification

More information

What Builders Need to Know about Residential Sprinkler Design

What Builders Need to Know about Residential Sprinkler Design What Builders Need to Know about Residential Sprinkler Design Melisa Rodriguez, P.E., NICET IV Design Services Supervisor, Fire Safety melisa.rodriguez@uponor.com www.uponor-usa.com Agenda Brief history

More information

Level I Chapter 1 Worksheet

Level I Chapter 1 Worksheet Chapter 1 Worksheet 1. When the present code requires certain safety to life requirements for existing buildings, those requirements shall. a. be void b. apply c. be approved d. be grand-fathered 2. The

More information

standard/quick response extended coverage light and ordinary hazard elo sprinklers

standard/quick response extended coverage light and ordinary hazard elo sprinklers January 27, 2012 Sprinkler 83a 1. DESCRIPTION Viking EC/QREC Light and Ordinary Hazard Extra-Large Orifice Sprinklers VK532 and VK534 are thermosensitive spray sprinklers available in several different

More information

LAND USE PERMITS (GALLATIN COUNTY) AND PRE-CONSTRUCTION SAFETY REVIEWS (MADISON COUNTY)

LAND USE PERMITS (GALLATIN COUNTY) AND PRE-CONSTRUCTION SAFETY REVIEWS (MADISON COUNTY) All property development will follow the standards set forth in International Fire Code, 2012 edition, the Big Sky Fire District Property Annexation Policy and include the policies drawn from the Fire

More information

What You Need to Know about Residential Sprinkler Design

What You Need to Know about Residential Sprinkler Design What You Need to Know about Residential Sprinkler Design Melisa Rodriguez, P.E., NICET IV Design Services Supervisor, Fire Safety melisa.rodriguez@uponor.com www.uponor-usa.com The Residential Sprinkler

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

West Chester Fire Dept. Fire Code Maintenance Handbook. Fire Prevention Saves Lives and Property

West Chester Fire Dept. Fire Code Maintenance Handbook. Fire Prevention Saves Lives and Property Fire Code Maintenance Handbook Fire Prevention Saves Lives and Property 8/10/2006 Our Mission The West Chester Fire Department Loss Prevention Bureau is committed to the safety of its firefighters, and

More information

Richardson Fire Department 136 N. Greenville Avenue, Richardson, TX Telephone: Fax:

Richardson Fire Department 136 N. Greenville Avenue, Richardson, TX Telephone: Fax: I. General II. III. Richardson Fire Department 136 N. Greenville Avenue, Richardson, TX 75081 Telephone: 972-744-5750 Fax: 972-918-0971 www.cor.net/fire Security Gates - Policy [revised 10/03/2017] Submittals

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

Fire Prevention Program

Fire Prevention Program Fire Prevention Program Updated February 2010 REGULATORY AUTHORITY California Code of Regulations, Title 8, Section 3221, Title 19 (19CCR) and Title 24 (24CCR), along with National Fire Protection Association

More information

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured

More information

REVISION RECORD FOR THE STATE OF CALIFORNIA SUPPLEMENT

REVISION RECORD FOR THE STATE OF CALIFORNIA SUPPLEMENT REVISION RECORD FOR THE STATE OF CALIFORNIA SUPPLEMENT July 1, 2018 2016 Title 24, Part 12, California Referenced Standards Code General Information: 1. The date of this supplement is for identification

More information

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF

More information

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Section No. Subject Page No. 1 Authority and Purpose 10-1 2 Definitions

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

At the Montréal city council meeting of April 10, 1995, it was enacted that:

At the Montréal city council meeting of April 10, 1995, it was enacted that: CITY OF MONTRÉAL BY-LAW 95-065 BY-LAW AMENDING THE BUILDING BY-LAW (B-1) At the Montréal city council meeting of April 10, 1995, it was enacted that: 1. Article 3 of the Building By-law (R.B.C.M., chapter

More information

CITY OF SAN MATEO ORDINANCE NO

CITY OF SAN MATEO ORDINANCE NO CITY OF SAN MATEO ORDINANCE NO. 2012-4 AMENDING SECTION 27.38.090, OPEN SPACE REQUIREMENTS, OF CHAPTER 27.38, CBD DISTRICTS-CENTRAL BUSINESS DISTRICT, SECTION 27.64.023, PARKING PROHIBITED ON LAWNS, FLOWERS,

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway AIA Healthcare Group Introductions Presenters Coffman Engineers Scott M. Twele, P.E. Operations Manager,

More information

2009 International Residential Code Draft of New Fire Sprinkler Related Requirements

2009 International Residential Code Draft of New Fire Sprinkler Related Requirements 1. IRC Sections R313 and R314, insert two new sections as follows: R313 FIRE SPRINKLER SYSTEM FOR TOWNHOUSES R313.1 Required Installation. An automatic residential fire sprinkler system shall be installed

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Fire Prevention Ordinance. Section 12

Fire Prevention Ordinance. Section 12 Fire Prevention Ordinance Section 12 February 7, 2005 CHAPTER 12 TOWN OF WILLIAMSTON FIRE PREVENTION TABLE OF CONTENTS Section 12-1 Jurisdiction Page 4 Section 12-2 Purpose 4 Section 12-3 Relationship

More information

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition

More information

S 2758 S T A T E O F R H O D E I S L A N D

S 2758 S T A T E O F R H O D E I S L A N D LC00 01 -- S S T A T E O F R H O D E I S L A N D IN GENERAL ASSEMBLY JANUARY SESSION, A.D. 01 A N A C T RELATING TO HEALTH AND SAFETY - FIRE SAFETY Introduced By: Senator Ryan W. Pearson Date Introduced:

More information

Reason for Amendment (Statute, Rule, FBC, Industry) (11)(a)

Reason for Amendment (Statute, Rule, FBC, Industry) (11)(a) Code Reference NFPA 1 1.1.2.1 Florida Specific Amendment Anytime a reference is made to NFPA 1 or NFPA 101 within this code it shall be the Florida specific version of NFPA 1 and NFPA 101. Reason for Amendment

More information

LANDSCAPE DOCUMENTATION PACKAGE SUBMITTAL FORM To be completed by applicant and submitted with the required materials.

LANDSCAPE DOCUMENTATION PACKAGE SUBMITTAL FORM To be completed by applicant and submitted with the required materials. COMMUNITY DEVELOPMENT AND SUSTAINABILITY DEPARTMENT 23 Russell Boulevard, Suite 2 Davis, California 95616 530/757-5610 FAX: 530/757-5660 TDD: 530/757-5666 LANDSCAPE DOCUMENTATION PACKAGE SUBMITTAL FORM

More information

PROJECT DESCRIPTION ENVIRONMENTAL SETTING. Project Site Location FIGURE 1 - REGIONAL LOCATION MAP

PROJECT DESCRIPTION ENVIRONMENTAL SETTING. Project Site Location FIGURE 1 - REGIONAL LOCATION MAP PROJECT DESCRIPTION ENVIRONMENTAL SETTING Project Site Location The proposed project site is located within the City of Camarillo in Ventura County. As shown in Figure 1, the City of Camarillo is located

More information

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference: Oklahoma 310:451-1-3. Adopted references The Board of Health hereby incorporates by reference the International Code Council (ICC) 2006 (IBC) Edition International Building Code; the 2007 Edition Standard

More information

COMMERCIAL SITE PLAN SUMMARY & DEVELOPMENT GUIDE

COMMERCIAL SITE PLAN SUMMARY & DEVELOPMENT GUIDE COMMERCIAL SITE PLAN SUMMARY & DEVELOPMENT GUIDE DEPARTMENT CONTACT: York County Development Coordinating Center (c/o Bea McCarter) 1070 Heckle Boulevard, Suite 107 Rock Hill, South Carolina 29732 Phone

More information

3. Aspects of the Proposed District Plan that may impact upon the operation of properties that the NZFS Commission owns.

3. Aspects of the Proposed District Plan that may impact upon the operation of properties that the NZFS Commission owns. Objective 8.1, Policy 8.5, Rule 8.4.3.3 and Rule 8.4.3.3 3. Aspects of the Proposed District Plan that may impact upon the operation of properties that the NZFS Commission owns. Rules: Rule 4.6.7, Rule

More information

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA Page 1 of 6 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Dry Horizontal Sidewall Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. The sprinklers

More information

F. Driveways. Driveways which provide access to off-street parking or loading from public streets shall comply with the following:

F. Driveways. Driveways which provide access to off-street parking or loading from public streets shall comply with the following: Section 20.945.040 General Design Standards for Surface Parking Areas. A. Review Authority. Parking lot design and drainage shall be subject to review and approval of the City Transportation Manager. B.

More information

MONTECITO FIRE PROTECTION DISTRICT

MONTECITO FIRE PROTECTION DISTRICT Contents: MONTECITO FIRE PROTECTION DISTRICT FIRE PROTECTION PLAN Section 1 ROOFING REQUIREMENTS Section 2 1 Memorandum of overview for roofing permit process and scoping of roofing ordinance VEGETATION

More information

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5.

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5. Page:1 of 6 Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5.6, SIN: SS3561 GENERAL DESCRIPTION The Model RC-QR-EC Commercial

More information

freedom residential concealed pendent sprinkler vk474 (K5.8)

freedom residential concealed pendent sprinkler vk474 (K5.8) Page of sprinkler vk7 (K5.) The Viking Corporation, 0 N Industrial Park Drive, Hastings MI 905 Telephone: 69-95-950 Technical Services: 77--56 Fax: 69--0 Email: techsvcs@vikingcorp.com. DESCRIPTION Viking

More information

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

Committee Input No. 28-NFPA 13R-2013 [ Global Input ] Page 1 of 6 Committee Input No. 28-NFPA 13R-2013 [ Global Input ] 6.2.2 Outside Dwelling Units. 6.2.2.1 All sprinklers used outside of the dwelling units shall be in accordance with 6.2.2 7.2 and 7.3.

More information

Model CV-1F Grooved End Swing Check Valves. General Description. Technical Data. Installation. Page 1 of 6 FEBRUARY 2016 TFP1550. Worldwide Contacts

Model CV-1F Grooved End Swing Check Valves. General Description. Technical Data. Installation. Page 1 of 6 FEBRUARY 2016 TFP1550. Worldwide Contacts Worldwide Contacts www.tyco-fire.com Model CV-F Grooved End Swing Check Valves General Description The TYCO Model CV-F Grooved End Swing Check Valves are compact and rugged swing-type units that allow

More information

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and

More information

2016 Plumbing Supplemental Plan Review List

2016 Plumbing Supplemental Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for

More information

REVISION RECORD FOR THE STATE OF CALIFORNIA ERRATA

REVISION RECORD FOR THE STATE OF CALIFORNIA ERRATA REVISION RECORD FOR THE STATE OF CALIFORNIA ERRATA September 1, 2017 2016 Title 24, Part 9, California Fire Code General Information: 1. The date of these errata is for identification purposes only. See

More information

CITY OF VACAVILLE PLANNING COMMISSION Agenda Item No. G. 1 STAFF REPORT August 4, Staff Contact: Tricia Shortridge (707)

CITY OF VACAVILLE PLANNING COMMISSION Agenda Item No. G. 1 STAFF REPORT August 4, Staff Contact: Tricia Shortridge (707) CITY OF VACAVILLE PLANNING COMMISSION Agenda Item No. G. 1 STAFF REPORT August 4, 2009 Staff Contact: Tricia Shortridge (707) 449-5140 TITLE: REQUEST: LONGS / CVS DRIVE-THRU PHARMACY & REMODEL TIME EXTENSION

More information

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER The 2016 Denver Building and Fire Code includes the following codes except as amendment herein. 2015 IBC (Building) 2015 IFC (Fire)

More information

Program of Instruction Course Syllabus

Program of Instruction Course Syllabus Program of Instruction Course Syllabus Course Title: Program: Course Duration: Course Prerequisites: Fire Prevention Principles Fire Officer 40 Hours OSFM Firefighter II or Basic Firefighter Certification

More information