1 SECTION WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Sprinklers. 4. Alarm devices. 5. Pressure gages. B. Related Sections: 1. Section "Interior Painting 2. Section " Sleeves and Sleeve Seals For Fire-Suppression Piping " 3. Section "Escutcheons For Fire-Suppression Piping 4. Section "Identification For Fire-Suppression Piping and Equipment" 5. Section Dry-Pipe Sprinkler Systems 6. Section "Digital, Addressable Fire-Alarm System 1.3 DEFINITIONS A. Standard-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure of 175 psig maximum. 1.4 SYSTEM DESCRIPTIONS A. Wet-Pipe Sprinkler System: Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. WET-PIPE SPRINKLER SYSTEMS

2 B. Contractor shall provide a complete new hydraulically calculated automatic wet-pipe sprinkler system including backflow preventor, department connection and sprinkler header in Tool Storage 161 of University Services Annex. 1.5 PERFORMANCE REQUIREMENTS A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure. B. Sprinkler system design shall be approved by authorities having jurisdiction. 1. Margin of Safety for Available Water Flow and Pressure: 15 psi including losses through water-service piping, valves, and backflow preventers. C. Wet sprinkler system design shall be approved by the authorities having jurisdiction. 1. Available fire-hydrant flow test records indicate the following conditions: a. Date: 09/14/2010, City of Harrisonburg b. Location of Residual Fire Hydrant R: 24-U c. Location of Flow Fire Hydrant F: 24-Q d. Static Pressure at Residual Fire Hydrant R: 104 psig. e. Measured Flow at Flow Fire Hydrant F: 1,278 gpm. f. Residual Pressure at Residual Fire Hydrant R: 84 psig. 2. Sprinkler Occupancy Hazard Classifications: a. Mechanical Equipment Rooms: Ordinary Hazard, Group 1. b. IT, Custodial, Janitor, File Areas: Ordinary Hazard, Group 1. c. Electrical Equipment Rooms: Ordinary Hazard, Group 1. d. Main Materials, Tools and Chemical Storage Rooms: Ordinary Hazard, Group 2. e. Paint Shop, Staging, Truck Bay Wash: Ordinary Hazard, Group 2. f. Paint Booths: Extra Hazard, Group 2 g. Corridors, Offices, Restrooms, Common Areas: Light Hazard. 3. Minimum Density for Automatic-Sprinkler Piping Design: a. Light-Hazard Occupancy: 0.10 gpm over 1500-sq. ft. area. b. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. area. c. Ordinary-Hazard, Group 2 Occupancy: 0.20 gpm over 1500-sq. ft. area. d. Extra-Hazard, Group 2 Occupancy: 0.40 gpm over 2500-sq. ft. area. e. Area reduction below minimum design area of 1500 sq. ft. allowed for quick response. 4. Maximum Protection Area per Sprinkler: Per UL listing. 5. Maximum Protection Area per Sprinkler: a. Office Spaces: 225 sq. ft b. Corridors, Common Areas: 225 sq. ft. WET-PIPE SPRINKLER SYSTEMS

3 c. Storage Areas: 130 sq. ft. d. Mechanical Equipment Rooms: 130 sq. ft. e. Electrical Equipment Rooms: 130 sq. ft. f. Paint Shop, Staging, Truck Bay Wash: 130 sq. ft. g. Paint Booths: 100 sq. ft. h. Hazardous Exhaust Ducts: 100 sq. ft. i. Other Areas: According to NFPA 13 recommendations unless otherwise indicated. 6. Total Combined Hose-Stream Demand Requirement: According to NFPA 13 unless otherwise indicated: a. Light-Hazard Occupancies: 100 gpm for 30 minutes. b. Ordinary-Hazard Occupancies: 250 gpm for 60 to 90 minutes. 1.6 SUBMITTALS A. General Submission Requirements: 1. Contractor shall submit the following items to the Architect. Submittals shall be prepared in accordance with contract specifications, NFPA and the VUSBC Complete fire protection shop drawings, hydraulic calculations and product data shall be reviewed and approved by the A/E of Record prior to submission to BCOM for final approval of conformance with the Codes and Standards. B. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories. All equipment submitted must be UL listed and FM approved for its intended use. Evidence of such listings and approvals must be evident on the product data sheets submitted. Data shall be submitted for each type of product specified in Part 2 of this Section. Datasheets that include multiple products or multiple product part or model numbers shall be clarified to indicate the exact products to be utilized for this specific project. Products to be submitted include, but are not limited to, 1. Piping materials, including sprinkler specialty fittings. 2. Pipe hangers, attachments and supports. 3. Valves, including listed fire-protection valves, unlisted general-duty valves, and specialty valves and trim. 4. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting, finish, and other pertinent data. C. Shop Drawings: For wet-pipe sprinkler systems. Include plans, elevations, sections, details, and attachments to other work. Include full sprinkler head and piping layout, including piping elevations, hanger locations, hanger details, hydraulic information, building sections, details, etc., as required and prepared according to NFPA 13 section Working Plans. WET-PIPE SPRINKLER SYSTEMS

4 1. Comprehensive plan view layouts and details, elevations and sections of the system piping. Indicate the location of piping in relation to the ceiling layout, showing pipe lengths and sizes, hanger locations and indicated all sprinkler locations coordinated with other ceiling components. 2. Hydraulic calculations in accordance with NFPA 13, utilizing the new contractor performed water supply flow test results. 3. Ceiling heights of all ceilings shall be indicated on the shop drawings. 4. Full height building section, including routing of sprinkler piping, shall be indicated on the shop drawings. 5. Shop drawings and hydraulic calculations shall be based on a coordinated set of sprinklers and sprinkler piping. Sprinkler locations and all sprinkler piping locations and elevations shall be coordinated with ductwork, piping, conduit, soffits, building structure, etc., prior to the first shop drawing submission. D. Delegated-Design Submittal: For sprinkler systems indicated to comply with performance requirements and design criteria, shop drawings and hydraulic calculations shall be signed and sealed by the qualified professional engineer responsible for their preparation prior to their submission to the A/E. E. Coordination Drawings: Sprinkler systems, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved: 1. Domestic water piping. 2. Compressed air piping. 3. HVAC hydronic piping. 4. HVAC Ductwork and Equipment. 5. Electrical Panels and Conduit. 6. Items penetrating finished ceiling include a. Lighting fixtures. b. Air outlets and inlets. c. Fire alarm devices. d. A/V devices. e. Access doors/panels. f. Soffits. g. Projectors and Projector Screens h. Other items not specifically listed. F. Qualification Data: For qualified Installer and professional engineer. G. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, including hydraulic calculations, that have been approved by authorities having jurisdiction (A/E and BCOM). WET-PIPE SPRINKLER SYSTEMS

5 H. Welding certificates. I. Fire-hydrant flow test report. J. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for Aboveground Piping." Include the NFPA 24 flushing certificate prior to connecting the backflow preventor to the new underground water service. K. Field quality-control reports. L. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and maintenance manuals. 1.7 QUALITY ASSURANCE A. Installer Qualifications: 1. Installer's responsibilities include designing, fabricating, and installing sprinkler systems and providing professional engineering services needed to assume engineering responsibility. Base calculations on results of new contractor provided fire-hydrant flow test. Base calculations on results of fire-hydrant flow test performed within 12 months of contract award. a. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by a qualified professional engineer in fire protection. B. Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code. C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. D. NFPA Standards: Sprinkler system equipment, specialties, accessories, installation, design, installation, flushing and testing shall comply with 1. NFPA 13, 2010 Edition, "Installation of Sprinkler Systems." 2. NFPA 24, 2010 Edition, "Installation of Private Fire Service Mains and Their Appurtenances." 1.8 COORDINATION A. Coordinate layout and installation of sprinklers with all other construction that penetrates ceilings, including light fixtures, fire alarm devices, HVAC equipment, access doors, A/V devices, partition assemblies, soffits, projectors, projector screens and any other item not specifically listed. WET-PIPE SPRINKLER SYSTEMS

6 1.9 CLOSEOUT SUBMITTALS UNIVERSITY SERVICES ANNEX A. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and maintenance manuals EXTRA MATERIALS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Sprinkler Cabinets: Finished, wall-mounted, steel cabinet with hinged cover, and with space for minimum of six spare sprinklers plus sprinkler wrench. Include number of sprinklers required by NFPA 13 and sprinkler wrench. Include separate cabinet with sprinklers and wrench for each type of sprinkler used on Project. PART 2 - PRODUCTS 2.1 PIPING MATERIALS A. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, and fitting materials, and for joining methods for specific services, service locations, and pipe sizes. 2.2 STEEL PIPE AND FITTINGS A. Standard Weight, Black Steel Pipe: ASTM A 53/A 53M, Type E Grade B. Pipe ends may be factory or field formed to match joining method. B. Schedule 10, Black-Steel Pipe: ASTM A 135 or ASTM A 795/A 795M, Schedule 10 in NPS 2.5 through 5; and NFPA 13-specified wall thickness in NPS 6 to NPS 10, plain end. C. Black Steel Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M, standard-weight, seamless steel pipe with threaded ends. D. Steel Couplings: ASTM A 865, threaded. E. Gray-Iron Threaded Fittings: ASME B16.4, Class 125, standard pattern. F. Malleable- or Ductile-Iron Unions: UL 860. G. Cast-Iron Flanges: ASME 16.1, Class 125. H. Steel Flanges and Flanged Fittings: ASME B16.5, Class 150. I. Steel Welding Fittings: ASTM A 234/A 234M and ASME B16.9. WET-PIPE SPRINKLER SYSTEMS

7 J. Grooved-Joint, Steel-Pipe Appurtenances: UNIVERSITY SERVICES ANNEX a. Anvil International, Inc. b. Shurjoint Piping Products. c. Tyco Fire & Building Products LP. d. Victaulic Company. 2. Pressure Rating: 300 psig minimum. 3. Grooved-End Fittings for Steel Piping: ASTM A 47/A 47M, malleable-iron casting or ASTM A 536, ductile-iron casting; with dimensions matching steel pipe. 4. Grooved-End-Pipe Couplings for Steel Piping: AWWA C606 and UL 213, rigid pattern, unless otherwise indicated, for steel-pipe dimensions. Include ferrous housing sections, EPDM-rubber gasket, and bolts and nuts. 2.3 PIPING JOINING MATERIALS A. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch thick. 1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges: Full-face gaskets. B. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise indicated. 2.4 LISTED FIRE-PROTECTION VALVES A. General Requirements: 1. Valves shall be UL listed and FM approved. 2. Minimum Pressure Rating for Standard-Pressure Piping: 175 psig. B. Ball Valves: a. Anvil International, Inc. b. NIBCO INC. c. Tyco Fire & Building Products LP. d. Victaulic Company. 2. Standard: UL 1091 except with ball instead of disc. WET-PIPE SPRINKLER SYSTEMS

8 3. Valves NPS 2 and Smaller: Bronze body with threaded ends. 4. Valves NPS 2-1/2: Bronze body with threaded ends or ductile-iron body with grooved ends. 5. Valves NPS 3: Ductile-iron body with grooved ends. C. Iron OS&Y Gate Valves: a. American Cast Iron Pipe Company; Waterous Company Subsidiary. b. American Valve, Inc. c. Crane Co.; Crane Valve Group; Stockham Division. d. Milwaukee Valve Company. e. Mueller Co.; Water Products Division. f. Tyco Fire & Building Products LP. g. United Brass Works, Inc. h. Watts Water Technologies, Inc. 2. Standard: UL Pressure Rating: 250 psig minimum. 4. Body Material: Cast or ductile iron. 5. End Connections: Flanged or grooved. D. Indicating-Type Butterfly Valves: a. Anvil International, Inc. b. Kennedy Valve; a division of McWane, Inc. c. Milwaukee Valve Company. d. NIBCO INC. e. Tyco Fire & Building Products LP. f. Victaulic Company. 2. Standard: UL Pressure Rating: 175 psig minimum. 4. Valves NPS 2-1/2 and Larger: a. Valve Type: Butterfly. b. Body Material: Cast or ductile iron. c. End Connections: Flanged, grooved, or wafer. WET-PIPE SPRINKLER SYSTEMS

9 5. Valve Operation: Integral electrical, 115-V ac, prewired, two-circuit, supervisory switch indicating device. E. Check Valves: a. Anvil International, Inc. b. Kennedy Valve; a division of McWane, Inc. c. Reliable Automatic Sprinkler Co., Inc. d. Tyco Fire & Building Products LP. e. Victaulic Company. f. Viking Corporation. 2. Standard: UL Pressure Rating: 250 psig minimum. 4. Type: Swing check. 5. Body Material: Cast iron. 6. End Connections: Flanged or grooved. 2.5 BACKFLOW PREVENTERS A. Double-Check, Backflow-Prevention Assemblies: a. Ames Fire & Waterworks; a division of Watts Water Technologies, Inc. b. Conbraco Industries, Inc.; Apollo Valves. c. FEBCO; SPX Valves & Controls. d. Watts Water Technologies, Inc. e. Zurn Plumbing Products Group; Wilkins Water Control Products Division. 2. Standard: ASSE 1015 or AWWA C Operation: Continuous-pressure applications unless otherwise indicated. 4. Pressure Loss: 4 psig maximum, through middle one-third of flow range. 5. Size: 6 NPS. 6. Design Flow Rate: 500 gpm. 7. Selected Unit Flow Range Limits: 750 gpm. 8. Pressure Loss at Design Flow Rate: 3 psig for NPS Body Material: Stainless steel for NPS 2-1/2 and larger. 10. End Connections: Flanged for NPS 2-1/2 and larger. 11. Configuration: Designed for horizontal, straight through flow. WET-PIPE SPRINKLER SYSTEMS

10 12. Accessories: OS&Y gate valves with flanged ends on inlet and outlet of NPS 2-1/2 and larger. 2.6 TRIM AND DRAIN VALVES A. General Requirements: 1. Standard: UL's "Fire Protection Equipment Directory" listing and "Approval Guide," published by FM Global, listing. 2. Pressure Rating: 175 psig minimum. B. Ball Valves: C. Globe Valves: a. Affiliated Distributors. b. Anvil International, Inc. c. Kennedy Valve; a division of McWane, Inc. d. Milwaukee Valve Company. e. NIBCO INC. f. Tyco Fire & Building Products LP. g. Victaulic Company. h. Watts Water Technologies, Inc. a. Fire Protection Products, Inc. b. United Brass Works, Inc. c. Victaulic Company. d. Watts Water Technologies, Inc. 2.7 SPRINKLER SPECIALTY PIPE FITTINGS A. Branch Outlet Fittings: a. Anvil International, Inc. WET-PIPE SPRINKLER SYSTEMS

11 b. National Fittings, Inc. c. Shurjoint Piping Products. d. Tyco Fire & Building Products LP. e. Victaulic Company. 2. Standard: UL 213 and "Approval Guide," published by FM Global, listing. 3. Pressure Rating: 175 psig minimum. 4. Body Material: Ductile-iron housing with EPDM seals and bolts and nuts. 5. Type: Mechanical-T and -cross fittings. 6. Configurations: Snap-on and strapless, ductile-iron housing with branch outlets. 7. Size: Of dimension to fit onto sprinkler main and with outlet connections as required to match connected branch piping. 8. Branch Outlets: Grooved or threaded. B. Automatic (Ball Drip) Drain Valves: 2. Basis-of-Design Product: Subject to compliance with requirements, provide [product a. AFAC Inc. b. Reliable Automatic Sprinkler Co., Inc. c. Tyco Fire & Building Products LP. 3. Standard: UL Pressure Rating: 175 psig minimum. 5. Type: Automatic draining, ball check. 6. Size: NPS 3/4. 7. End Connections: Threaded. C. Sprinkler Inspector's Test Fittings: a. AGF Manufacturing Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. d. Viking Corporation. 2. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. 3. Pressure Rating: 175 psig minimum. 4. Body Material: Cast- or ductile-iron housing with sight glass. 5. Size: Same as connected piping. 6. Inlet and Outlet: Threaded. WET-PIPE SPRINKLER SYSTEMS

12 7. Relief Valve: Include. 2.1 FIRE DEPARTMENT CONNECTIONS A. Yard-Type, Fire Department Connection: UNIVERSITY SERVICES ANNEX a. AFAC, Inc. b. Elkhart Brass Mfg. Company, Inc. c. Fire-End & Croker Corporation. d. Fire Protection Products, Inc. e. GMR International Equipment Corporation. f. Guardian Fire Equipment, Inc. 2. Standard: UL Type: Exposed, freestanding. 4. Pressure Rating: 175 psig minimum. 5. Body Material: Corrosion-resistant metal. 6. Inlets: Brass with threads according to NFPA 1963 and matching local fire-department sizes and threads. Include extension pipe nipples, brass lugged swivel connections, and check devices or clappers. 7. Caps: Brass, lugged type, with gasket and chain. 8. Escutcheon Plate: Round, brass, floor type. 9. Outlet Location: Bottom, with pipe threads. 10. Number of Inlets: Two. 11. Sleeve: Brass. 12. Sleeve Height: 18 inches. 13. Escutcheon Plate Marking: Similar to "AUTO SPKR" 14. Finish: Rough brass or bronze. 15. Outlet Size: NPS SPRINKLERS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, 1. Reliable Automatic Sprinkler Co., Inc. 2. Tyco Fire & Building Products LP. 3. Victaulic Company. 4. Viking Corporation. B. General Requirements: WET-PIPE SPRINKLER SYSTEMS

13 1. Standard: UL's "Fire Protection Equipment Directory" listing and "Approval Guide," published by FM Global, listing. 2. Pressure Rating for Residential Sprinklers: 175 psig maximum. 3. Pressure Rating for Automatic Sprinklers: 175 psig minimum. C. Automatic Sprinklers with Heat-Responsive Element: 1. Nonresidential Applications: UL Characteristics: Nominal 1/2-inch orifice, Quick Response, with Discharge Coefficient K of 5.6, and for "Ordinary" temperature classification rating unless otherwise indicated or required by application. D. Sprinkler Finishes: 1. Chrome plated. 2. Bronze. 3. Painted. E. Special Coatings: 1. Wax. 2. Lead. 3. Corrosion-resistant paint. F. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers. 1. Ceiling Mounting: Chrome-plated steel, two-piece, recessed with 1-inch vertical adjustment. G. Sprinkler Guards: a. Reliable Automatic Sprinkler Co., Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. d. Viking Corporation. 2. Standard: UL Type: Wire cage with fastening device for attaching to sprinkler. WET-PIPE SPRINKLER SYSTEMS

14 2.3 ALARM DEVICES A. Alarm-device types shall match piping and equipment connections. B. Electrically Operated Alarm Bell: a. Fire-Lite Alarms, Inc.; a Honeywell company. b. Notifier; a Honeywell company. c. Potter Electric Signal Company. d. Tyco Fire & Building Products LP. e. Viking Corporation. 2. Standard: UL Type: Vibrating, metal alarm bell. 4. Size: 8-inch minimum diameter. 5. Finish: Red-enamel factory finish, suitable for outdoor use. C. Water-Flow Indicators: a. Potter Electric Signal Company. b. System Sensor; a Honeywell company. c. Tyco Fire & Building Products LP. d. Viking Corporation 2. Standard: UL Water-Flow Detector: Electrically supervised. 4. Components: Two single-pole, double-throw circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-V dc; complete with factory-set, fieldadjustable retard element to prevent false signals and tamperproof cover that sends signal if removed. 5. Type: Paddle operated. 6. Pressure Rating: 250 psig. 7. Design Installation: Horizontal or vertical. D. Valve Supervisory Switches: WET-PIPE SPRINKLER SYSTEMS

15 a. Potter Electric Signal Company. b. System Sensor; a Honeywell company. c. Tyco Fire & Building Products LP. d. Viking Corporation 2. Standard: UL Type: Electrically supervised. 4. Components: Single-pole, double-throw switch with normally closed contacts. 5. Design: Signals that controlled valve is in other than fully open position. 2.4 PRESSURE GAGES A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, 1. AMETEK; U.S. Gauge Division. 2. Ashcroft, Inc. 3. Brecco Corporation. 4. WIKA Instrument Corporation. B. Standard: UL 393. C. Dial Size: 3-1/2- to 4-1/2-inch diameter. D. Pressure Gage Range: 0 to 250 psig minimum. E. Water System Piping Gage: Include "WATER" or "AIR/WATER" label on dial face. PART 3 - EXECUTION 3.1 WATER-SUPPLY CONNECTIONS A. Provide new control valves, backflow preventor, fire department connection and sprinkler header in the tool storage room. B. Perform new fire-hydrant flow test according to NFPA 13 and NFPA 291. Use results for system design calculations required in "Quality Assurance" Article. Report results promptly and in writing to the architect after completion of the flow test and prior to the first sprinkler system shop drawing submission. The fire-hydrant flow test as shown in the Contract Documents does not alleviate the contractor from performing their own flow test. WET-PIPE SPRINKLER SYSTEMS

16 3.2 PIPING INSTALLATION UNIVERSITY SERVICES ANNEX A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical. 1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. File written approval with the Engineer before deviating from approved working plans. B. Piping Standard: Comply with requirements for installation of sprinkler piping in NFPA 13. C. Use listed fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes. D. Install unions adjacent to each valve in pipes NPS 2 and smaller. E. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections. F. Install "Inspector's Test Connections" in sprinkler system piping, complete with shutoff valve, relief valve and sized and located according to NFPA 13. G. Install sprinkler piping with drains for complete system drainage. H. Install hangers and supports for sprinkler system piping according to NFPA 13. Comply with requirements for hanger materials in NFPA 13. Comply with NFPA 13 hanger requirements for pressures exceeding 100 psi. I. Install automatic (ball drip) drain valve at the check valve for fire-department connection, to drain piping between fire-department connection and check valve. Install drain piping to and spill over floor drain or to outside building. J. Install alarm devices in piping systems. K. Fill sprinkler system piping with water. L. Install sleeves for piping penetrations of walls, ceilings, and floors. Comply with requirements for sleeves specified in Section "Sleeves and Sleeve Seals for Fire-Suppression Piping." M. Install sleeve seals for piping penetrations of concrete walls and slabs. Comply with requirements for sleeve seals specified in Section "Sleeves and Sleeve Seals for Fire- Suppression Piping." N. Install escutcheons for piping penetrations of walls, ceilings, and floors. Comply with requirements for escutcheons specified in Section "Escutcheons for Fire-Suppression Piping." WET-PIPE SPRINKLER SYSTEMS

17 3.3 JOINT CONSTRUCTION UNIVERSITY SERVICES ANNEX A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special fittings that have finish and pressure ratings same as or higher than system's pressure rating for aboveground applications unless otherwise indicated. B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe. C. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings before assembly. D. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable for water service. Join flanges with gasket and bolts according to ASME B31.9. E. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. Apply appropriate tape or thread compound to external pipe threads. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. F. Steel-Piping, Roll-Grooved Joints: Roll rounded-edge groove in end of pipe according to AWWA C606. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for steel-pipe grooved joints. 3.4 VALVE AND SPECIALTIES INSTALLATION A. Install listed fire-protection valves, trim and drain valves, specialty valves and trim, controls, and specialties according to NFPA 13 and authorities having jurisdiction. B. Install listed fire-protection shutoff valves supervised open, located to control sources of water supply except from fire-department connections. Install permanent identification signs indicating portion of system controlled by each valve. C. Install backflow preventers in potable-water-supply sources. 3.5 SPRINKLER INSTALLATION A. Install sprinklers in suspended ceilings as shown on the drawings and in the center of the acoustical ceiling tiles in both directions. Install all sprinklers utilizing return bends from the branchlines to the sprinklers. WET-PIPE SPRINKLER SYSTEMS

18 3.6 FIRE-DEPARTMENT CONNECTION INSTALLATION A. Install yard-type fire-department connections in concrete slab support. Comply with requirements for concrete in Section "Cast-in-Place Concrete." B. Install two protective pipe bollards on sides of each fire-department connection. Comply with requirements for bollards in Section "Metal Fabrications." C. Install automatic (ball drip) drain valve at each check valve for fire-department connection. 3.7 PENETRATIONS A. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials and utilize a UL-listed firestop assembly for each penetration. B. Smoke Penetration Sealing: Fill the void opening around the item penetrating the wall with a noncombustible material such as mineral wool or another listed fill-void material. The fill void material shall have a coating of sealant applied and smoothened to close any gaps. The sealant shall be non-combustible or have a Class A flame spread combustibility rating. 3.8 IDENTIFICATION A. Install labeling and pipe markers on equipment and piping according to requirements in NFPA 13 and Section Identification For Fire-Suppression Piping and Equipment". 3.9 FIELD QUALITY CONTROL A. Perform all required pre- and final tests and inspections per the Virginia State Fire Marshal, BCOM, JMU and NFPA 13 requirements. B. Contractor shall be responsible for coordinating all pre- and final tests and inspections with the Virginia State Fire Marshal, BCOM, JMU and the project manager. C. Tests and Inspections: 1. Leak Test: After installation, charge systems and test for leaks. Repair leaks and retest until no leaks exist. 2. Flush, test, and inspect sprinkler systems according to NFPA 13, "Systems Acceptance" Chapter. 3. Perform a forward flow backflow preventor test at system design flow. Record pressures upstream and downstream of the backflow preventor. 4. Energize circuits to electrical equipment and devices. 5. Coordinate with fire-alarm tests. Operate as required. WET-PIPE SPRINKLER SYSTEMS

19 D. Sprinkler piping system will be considered defective if it does not pass tests and inspections. E. Prepare test and inspection reports CLEANING A. Clean dirt and debris from sprinklers. B. Remove and replace sprinklers with paint other than factory finish PIPING SCHEDULE A. Piping between Fire-Department Connections and Check Valves: Galvanized, standard-weight steel pipe with grooved ends; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. B. Standard-pressure, wet-pipe sprinkler system, NPS 2 and smaller, shall be 1. Standard-weight, black-steel pipe with threaded ends; uncoated, gray-iron threaded fittings; and threaded joints. C. Standard-pressure, wet-pipe sprinkler system, NPS 2-1/2 to NPS 4, shall be one of the following: 1. Standard-weight, black-steel pipe with threaded ends; uncoated, gray-iron threaded fittings; and threaded joints. 2. Standard-weight, black-steel pipe with cut or roll grooved ends; uncoated, grooved-end fittings for steel piping; grooved-end-pipe couplings for steel piping; and grooved joints. 3. Schedule 10, black-steel pipe with roll-grooved ends; uncoated, grooved-end fittings for steel piping; grooved-end-pipe couplings for steel piping; and grooved joints. D. Standard-pressure, wet-pipe sprinkler system, NPS 5 and larger, shall be one of 1. Standard-weight black-steel pipe with threaded ends; uncoated, gray-iron threaded fittings; and threaded joints. 2. Standard-weight, black-steel pipe with cut or roll-grooved ends; uncoated, grooved-end fittings for steel piping; grooved-end-pipe couplings for steel piping; and grooved joints. 3. Schedule 10, black-steel pipe with roll-grooved ends; uncoated, grooved-end fittings for steel piping; grooved-end-pipe couplings for steel piping; and grooved joints SPRINKLER SCHEDULE A. Use sprinkler types in subparagraphs below for the following applications: WET-PIPE SPRINKLER SYSTEMS

20 1. Rooms with Suspended Ceilings: Recessed sprinklers as indicated. 2. Rooms without Ceilings: Upright sprinklers. 3. Wall Mounting: Sidewall sprinklers. 4. Spaces Subject to Freezing: Dry sprinklers B. Provide sprinkler types in subparagraphs below with finishes indicated. 1. Recessed Sprinklers: Bright chrome, with bright chrome escutcheon. 2. Upright Sprinklers in exposed areas: Rough bronze. END OF SECTION WET-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

North Hanover Township School District North Hanover Township, New Jersey

North Hanover Township School District North Hanover Township, New Jersey SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure. SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 211313 WET-PIPE SPRINKLER SYSTEMS PRT 1 GENERL 1.01 RELTED DOCUMENTS. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314D - AUTOMATIC SPRINKLER SYSTEMS (DRY-PIPE) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum. Page 211200-1 SECTION 211200 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION SECTION 211200 - FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Hose connections. 4. Fire-department connections.

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314W - AUTOMATIC SPRINKLER SYSTEMS (WET PIPE SYSTEMS) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION Table of Contents TOC Page 1 DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION 210517 SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING 08/15/18 0 210523 GENERAL-DUTY VALVES FOR FIRE PROTECTION PIPING

More information

B. Related Sections: The following Sections contain requirements that relate to this Section.

B. Related Sections: The following Sections contain requirements that relate to this Section. SECTION 211313- FIRE-SUPPRESSION PIPING PART1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

A. This Section includes the following fire-suppression piping inside the building:

A. This Section includes the following fire-suppression piping inside the building: SECTION 211000 - WATER-BASED FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following fire-suppression piping inside the building: 1. Automatic wet-type, standpipe systems.

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING SECTION 210517- SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION PREACTION SPRINKLER SYSTEMS

SECTION PREACTION SPRINKLER SYSTEMS PART 1 GENERAL SECTION 211316 - PREACTION SPRINKLER SYSTEMS 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Addendum No. 2 to the Contract Documents

Addendum No. 2 to the Contract Documents Addendum No. 2 to the Contract Documents Lewis County Jefferson Community College Education Center Project CONTRACT 2A: GENERAL CONSTRUCTION CONTRACT 2B: ELECTRICAL CONSTRUCTION CONTRACT 2C: MECHANICAL

More information

SECTION FIRE-SUPPRESSION PIPING

SECTION FIRE-SUPPRESSION PIPING SECTION 211313 FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements. SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD.

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD. TECHNICAL SPECIFICATIONS SECTION 211316 DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD Prepared for: Mr. Cab Vinton Director Plaistow Public Library 85

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 13900 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14 SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

Facility Fire-Suppression Water-Service Piping

Facility Fire-Suppression Water-Service Piping University of New Hampshire University of New Hampshire Scholars' Repository Division 21 Fire Supression Chapter 5 Technical Construction and Renovation Standards 4-23-2015 211100 - Facility Fire-Suppression

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department

More information

Gas Station & C Store SECTION CWM Job No

Gas Station & C Store SECTION CWM Job No SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract

More information

END OF SECTION

END OF SECTION SECTION 210553 ~IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT PART 1 -GENERAL 1.1 SUMMARY Section Includes: I. Equipment labels. 2. Warning signs and labels. 3. Pipe labels. 1.2 ACTION SUBMITTALS

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide

More information

SECTION FIRE-SUPPRESSION SYSTEMS

SECTION FIRE-SUPPRESSION SYSTEMS SECTION 13900 FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Automatic wet-type, Class I, fire-suppression standpipes and branches for sprinklers. 2. Wet-pipe, fire-suppression

More information

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8 City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL SECTION 21 05 00 - COMMON WORK RESULTS FOR FIRE SUPPRESSION 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the

More information

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation.

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation. SECTION 211100 - FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

A. Section includes wet-pipe sprinkler system, system design, installation, and certification. SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes wet-pipe sprinkler system, system design, installation, and certification. 1.2 REFERENCES A. General: Comply

More information

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION Bluffs Tower Apartments Section TOC Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION 211000 WATER-BASED FIRE-SUPPRESSION SYSTEMS 213113 ELECTRIC-DRIVE, CENTRIFUGAL FIRE

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY. This Product MasterSpec Section is licensed by AVITRU, LLC to Victaulic Company ("Licensee"). This Product MasterSpec Section modifies the original MasterSpec text and does not include the full content

More information

ADDENDUM NO. 3 March 19, 2018

ADDENDUM NO. 3 March 19, 2018 ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

SECTION AUTOMATIC SPRINKLER PIPING

SECTION AUTOMATIC SPRINKLER PIPING SECTION 15330 AUTOMATIC SPRINKLER PIPING ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: This section contains several types of automatic sprinkler piping. Some piping is allowed

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES SECTION 15300 FIRE PROTECTION PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. Dartmouth College is currently insured by Factory Mutual. References to the owner s insurance company in this specification

More information

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Port of St Helens SIA Aircraft Hanger Scappoose, OR Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance

More information

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY. Copyright 2016 by The American Institute of Architects (AIA) Exclusively published and distributed by AVITRU, LLC for the AIA This Product MasterSpec Section is licensed by AVITRU, LLC to Victaulic Company

More information

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13930 WET-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete wet-pipe fire sprinkler system in new addition only as specified

More information

University of Missouri St. Louis September 9, 2013 Recreation and Wellness Center #S

University of Missouri St. Louis September 9, 2013 Recreation and Wellness Center #S SECTION 210548 - VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Isolation pads. 2. Isolation mounts. 3.

More information

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS DIVISION 21: FIRE SUPPRESSION 21 1000 WATER BASED FIRE SUPRESSION SYSTEMS 21 1200 FIRE-SUPPRESSION DRY STANDPIPES 21 1313 WET PIPE SPRINKLER PROTECTION SYSTEM 21 1314 WET-PIPE AUTOMATIC SPRINKLER SYSTEM

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 22 63 13 GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION WET FIRE SPRINKLER SYSTEMS

SECTION WET FIRE SPRINKLER SYSTEMS SUNY GENESEO 211310-1 PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION SECTION 15300 - FIRE PROTECTION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

A. This Section includes the following domestic water piping specialties:

A. This Section includes the following domestic water piping specialties: SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS DIVISION 21 - FIRE SUPPRESSION Includes the following sections: None DESIGN REQUIREMENTS It is the policy of City of Santa Cruz to install fire sprinkler systems in all new construction/facilities. If

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION FIRE SUPPRESSION SYSTEMS

SECTION FIRE SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2

More information

B. Section Identification for Fire Suppression Piping and Equipment.

B. Section Identification for Fire Suppression Piping and Equipment. SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED

More information

A. This section includes design and performance information for fire protection and suppression systems.

A. This section includes design and performance information for fire protection and suppression systems. SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials

More information

2. Welding Materials and Procedures shall conform to the ASME Code.

2. Welding Materials and Procedures shall conform to the ASME Code. PART 1 GENERAL 1.01 Scope of Standard A. The design guidelines contained herein include the requirements for systems, materials, fittings and valves utilized for fire protection systems at Sam Houston

More information

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified

More information

SECTION DOMESTIC WATER PIPING SPECIALTIES

SECTION DOMESTIC WATER PIPING SPECIALTIES SECTION 22 11 19 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

NATURAL GAS PIPING

NATURAL GAS PIPING SECTION 15496 - NATURAL GAS PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13. 21 10 00 PART 1 - GENERAL 1.01 SCOPE A. The following standards and procedures apply to the design and installation of all wet pipe and dry pipe sprinkler systems. The design of fire suppression systems

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

Mercury Plastics New Building February TABLE OF CONTENTS

Mercury Plastics New Building February TABLE OF CONTENTS DIVISION 21: FIRE SUPPRESSION 210500 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 210548 VIBRATION AND SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING AND EQUIPMENT 211300 WET PIPE FIRE SUPPRESSION SPRINKLERS

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13935 DRY-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete fire sprinkler system as specified in Contract Documents. B.

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 21 13 13 FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS A. Furnish all labor, materials, equipment services and incidentals required to design and install properly

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS FIRE PROTECTION BA SECTION 13910 - FIRE PROTECTION BASIC MATERIALS AND METHODS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Pipe, fittings, valves, and connections for sprinkler, standpipe and fire hose,

More information

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS SECTION 15932 WET-PIPE FIRE SUPPRESSION SPRINKLERS PART 1 - GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred

More information

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION SECTION 15300 PART I - GENERAL 1.01 WORK INCLUDED A. Furnish all labor, materials, tools, and equipment to complete the automatic fire sprinkler system as hereinafter described, ready for service to the

More information

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work

More information

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete automatic fire suppression system for the exhaust hood, including necessary accessories.

More information

TABLE OF CONTENTS

TABLE OF CONTENTS DIVISION 21: FIRE SUPPRESSION 21 05 00 COMMON REQUIREMENTS FOR FIRE SUPPRESSION 21 05 53 IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT 21 13 00 WET PIPE FIRE SUPPRESSION SPRINKLERS END TABLE

More information

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Codes and Standards: A. Plumbing Code Compliance: Comply with applicable portions of National Standard Plumbing Code pertaining to selection and installation of Plumbing materials

More information

SECTION HYDRONIC PIPING

SECTION HYDRONIC PIPING SECTION 23 21 13 HYDRONIC PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes pipe and fitting materials, joining methods, special-duty valves, and specialties for the following: 1. Hot-water

More information

REFRIGERANT PIPING

REFRIGERANT PIPING SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information