1 SECTION 210- WATER-BASED FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 l Specification Sections, apply this Section. 1.2 SUMMARY A. Provide fire sprinkler system throughout the facility. This is a Youth Detention Center, Institutional Occupancy Group 1-3, Condition 5 in conformance with the 2015 International Building Code Section Only Schedule 40 pipe is permitted for this project. B. These documents reflect systems designed by licensed Fire Protection Engineers. The design is approved by the State of Missouri and modifications from the system layout and design are not permitted without the written permission from the State and Engineers ofrecord. C. The Office of Mental Health 15th Edition released in January 31, 2016 indicates that Viking VK41 0 Pendant and VK412 Sidewall Institutional Flush Sprinklers are NOT accepted for use. Do NOT use these or similar by others because the heat sensor projects below the sprinkler head enclosure and is accessible patients. D. This Section includes the following fire-suppression piping inside the building: 1. Wet-pipe sprinkler systems. 2. Preaction sprinkler systems (in residential wings) as indicated on the plans. E. Related Sections include the following: 1. Division 28 Section "Fire Detection and Alarm" for alarm devices not specified in this Section. 1.3 SYSTEM DESCRIPTIONS A. Wet-Pipe Sprinkler System: Aumatic sprinklers are attached piping containing water and that is connected water supply. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. Hose connections are included if indicated. B. Preaction Sprinkler System: Aumatic sprinklers are attached ptpmg containing air. Actuation of fire-detection system in same area as sprinklers opens deluge valve, permitting water flow in piping and discharge from sprinklers that have opened. 1.4 PERFORMANCE REQUIREMENTS A. Standard Piping System Component Working Pressure: Listed for at least 175 psig (0 kpa). WATER-BASED FIRE-SUPPRESSION SYSTEMS H

2 B. Fire-suppression sprinkler system design shall be approved by authorities having jurisdiction. 1. Margin of Safety for Available Water Flow and Pressure: 5 percent, including losses through water-service piping, valves, and backflow preventers. 2. Sprinkler Occupancy Hazard Classifications: a. Building Service Areas: Ordinmy Hazard, Group 1. b. Electrical Equipment Rooms: Ordinary Hazard, Group 1. c. General Srage Areas: Ordinary Hazard, Group 1. d. Laundries: Ordinary Hazard, Group 1. e. Mechanical Equipment Rooms: Ordinary Hazard, Group 1. f. Office and Public Areas: Light Hazard. g. Residential Living Areas: Light Hazard. h. Food Service Areas: Ordinary Hazard, Group Minimum Density for Aumatic-Sprinkler Piping Design: a. Light-Hazard Occupancy: 0.10 gpm over 1500-sq. ft. (6.3 ml/s over 139-sq. m) area. b. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. (9.5 ml/s over 139-sq. m) area. c. Ordinary-Hazard, Group 2 Occupancy: 0.20 gpm over 1500-sq. ft. (12.6 ml/s over 139-sq. m) area. d. Special Occupancy Hazard: As determined by authorities having jurisdiction. 4. Minimum Density for Dry-Sprinkler Piping Design: a. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm (9.5 ml!s) over entire area. b. Ordinary-Hazard, Group 2 Occupancy: 0.20 gpm (12.6 ml/s) over entire area. c. Special Occupancy Hazard: As determined by authorities having jurisdiction. 5. Maximum Protection Area per Sprinkler: Per UL listing. 6. Maximum Protection Area per Sprinkler: a. Office Spaces: sq. ft. (11.1 sq. m) 225 sq. ft. (20.9 sq. m). b. Srage Areas: 130 sq. ft. (12.1 sq. m). c. Mechanical Equipment Rooms: 130 sq. ft. (12.1 sq. m). d. Electrical Equipment Rooms: 130 sq. ft. (12.1 sq. m). e. Other Areas: According NFP A 13 recommendations, unless otherwise indicated. 7. Total Combined Hose-Stream Demand Requirement: According NFPA 13, unless otherwise indicated: a. Light-Hazard Occupancies: gpm (6.3 Lis) for 30 minutes. b. Ordinary-Hazard Occupancies: 250 gpm (15.75 Lis) for minutes. 1.5 SUBMITTALS A. Product Data: For the following: WATER-BASED FIRE-SUPPRESSION SYSTEMS H

3 1. Piping materials, including flexible connections and sprinkler specialty fittings. 2. Pipe hangers and supports. 3. Valves, including listed fire-protection valves, unlisted general-duty valves, and specialty valves and trim. 4. Air compressors, including electrical data. 5. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting, finish, and other pertinent data. 6. Fire department connections, including type; number, size, and arrangement of inlets; caps and chains; size and direction of outlet; escutcheon and marking; and finish. 7. Alarm devices, including electrical data. B. Shop Drawings: Diagram power, signal, and control wiring. C. Fire-hydrant flow test report. D. Approved Sprinkler Piping Drawings: Working plans, prepared according NFPA 13, that have been approved by authorities having jurisdiction, including hydraulic calculations, if applicable. E. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contracr's Material and Test Certificate for Aboveground Piping" and "Contracr's Material and Test Certificate for Underground Piping." F. G. H. Welding certificates. Field quality-control test reports. Operation and Maintenance Data: For sprinkler specialties include in emergency, operation, and maintenance manuals. 1.6 A. QUALITY ASSURANCE Installer Qualifications: 1. Installer's responsibilities include designing, fabricating, and installing fire-suppression systems and providing professional engineering services needed assume engineering responsibility. Base calculations on results of fire-hydrant flow test. a. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by a qualified professional engineer. B. Welding: Qualify processes and operars according ASME Boiler and Pressure Vessel Code: Section IX. C. NFP A Standards: Fire-suppression-system equipment, specialties, accessories, installation, and testing shall comply with the following: 1. NFPA 13, "Installation of Sprinkler Systems." WATER-BASED FIRE-SUPPRESSION SYSTEMS H

4 1.7 COORDINATION A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light fixtures, HV AC equipment, and partition assemblies. 1.8 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for srage and identified with labels describing contents. 1. Sprinkler Cabinets: Finished, wall-mounting, steel cabinet with hinged cover, with space for minimum of six spare sprinklers plus sprinkler wrench. Include number of sprinklers required by NFPA 13 and sprinkler wrench. Include separate cabinet with sprinklers and wrench for each type of sprinkler on Project. PART 2- PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply product selection: 1. Available Manufacturers: Subject compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited, manufacturers specified. 2.2 STEEL PIPE AND FITTINGS A. Threaded-End, Standard-Weight Steel Pipe: ASTM A 53/A 53M, ASTM A 135, or ASTM A 795, with facry- or field-formed threaded ends. 1. Cast-Iron Threaded Flanges: ASME B Malleable-Iron Threaded Fittings: ASME B Gray-Iron Threaded Fittings: ASME B Steel Threaded Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M or ASTM A 106, Schedule 40, seamless steel pipe. Include ends matching joining method. 5. Steel Threaded Couplings: ASTM A Grooved-End Fittings: UL-listed, ASTM A 536, ductile-iron casting with OD matching steel-pipe OD. 7. Grooved-End-Pipe Couplings: UL 213 and A WWA C606, rigid pattern, unless otherwise indicated; gasketed fitting matching steel-pipe OD. Include ductile-iron housing with keys matching steel-pipe and fitting grooves, prelubricated rubber gasket listed for use with housing, and steel bolts and nuts. WATER-BASED FIRE-SUPPRESSION SYSTEMS H

5 2.3 SPRINKLER SPECIALTY FITTINGS A. Sprinkler specialty fittings shall be UL listed or FMG approved, with 175-psig (0-kPa) minimum working-pressure rating, and made of materials compatible with piping. Outlet Specialty Fittings: 1. Available Manufacturers: a. Anvil International, Inc. b. Central Sprinkler Corp. c. JDH Pacific, Inc. d. National Fittings, Inc. e. Shurjoint Piping Products, Inc. f. Southwestern Pipe, Inc. g. Star Pipe Products; Star Fittings Div. h. Victaulic Co. of America. i. Ward Manufacturing. 2. Mechanical-T and -Cross Fittings: UL 213, ductile-iron housing with gaskets, bolts and nuts, and threaded, locking-lug, or grooved outlets. 3. Snap-On and Strapless Outlet Fittings: UL 213, ductile-iron housing or casting with gasket and threaded outlet. B. Sprinkler Drain and Alarm Test Fittings: Cast- or ductile-iron body; with threaded or lockinglug inlet and outlet, test valve, and orifice and sight glass. 1. Available Manufacturers: a. Central Sprinkler Corp. b. Fire-End and Croker Corp. c. Viking Corp. d. Victaulic Co. of America. C. Sprinkler Branch-Line Test Fittings: Brass body with threaded inlet, capped drain outlet, and threaded outlet for sprinkler. 1. Available Manufacturers: a. Elkhart Brass Mfg. Co., Inc. b. Fire-End and Croker Corp. c. Potier-Roemer; Fire-Protection Div. D. Sprinkler Inspecr's Test Fitting: Cast- or ductile-iron housing with threaded inlet and drain outlet and sight glass. 1. Available Manufacturers: a. AGF Manufacturing Co. b. Central Sprinkler Corp. c. G/J Innovations, Inc. d. Triple R Specialty of Ajax, Inc. WATER-BASED FIRE-SUPPRESSION SYSTEMS H

6 E. Drop-Nipple Fittings: UL 1474, adjustable with threaded inlet and outlet, and seals. 1. Available Manufacturers: a. CECA, LLC. b. Merit. c. Viking Corp. F. Dry-Pipe-System Fittings: UL listed for dry-pipe service. 2.4 LISTED FIRE-PROTECTION VALVES A. Valves shall be UL listed or FMG approved, with 175-psig (0 kpa) minimum pressure rating. B. Ball Valves: Comply with UL 1091, except with ball instead of disc. 1. NPS 1-1/2 (DN 40) and Smaller: Bronze body with threaded ends. 2. NPS 2 and NPS 2-1/2 (DN 50 and DN 65): Bronze body with threaded ends or ductileiron body with grooved ends. 3. NPS 3 (DN 80): Ductile-iron body with grooved ends. 4. Available Manufacturers: a. NIDCO. b. Victaulic Co. of America. c. TYCO C. Butterfly Valves: UL NPS 2 (DN 50) and Smaller: Bronze body with threaded ends. a. Available Manufacturers: 1) Global Safety Products, Inc. 2) Milwaukee Valve Company. 3) TYCO 2. NPS 2-1/2 (DN 65) and Larger: Bronze, cast-iron, or ductile-iron body; wafer type or with flanged or grooved ends. a. Available Manufacturers: 1) Central Sprinkler Corp. 2) Global Safety Products, Inc. 3) McWane, Inc.; Kennedy Valve Div. 4) Mueller Company. 5) NIDCO. 6) Pratt, Henry Company. 7) Victaulic Co. of America. WATER-BASED FIRE-SUPPRESSION SYSTEMS H

7 D. Check Valves NPS 2 (DN 50) and Larger: UL 312, swing type, cast-iron body with flanged or grooved ends. 1. Available Manufacturers: a. Central Sprinkler Corp. b. Firematic Sprinkler Devices, Inc. c. Globe Fire Sprinkler Corporation. d. Grinnell Fire Protection. e. NIBCO. f. Potter-Roemer; Fire Protection Div. g. Reliable Aumatic Sprinkler Co., Inc. h. Victaulic Co. of America. i. Watts Industries, Inc.; Water Products Div. E. Gate Valves: UL 262, OS&Y type. 1. NPS 2 (DN 50) and Smaller: Bronze body with threaded ends. a. Available Manufacturers: 1) Crane Co.; Crane Valve Group; Crane Valves. 2) Hammond Valve. 3) NIBCO. 4) United Brass Works, Inc. 2. NPS 2-1/2 (DN 65) and Larger: Cast-iron body with flanged ends. a. Available Manufacturers: 1) Clow Valve Co. 2) Crane Co.; Crane Valve Group; Crane Valves. 3) Crane Co.; Crane Valve Group; Jenkins Valves. 4) Hammond Valve. 5) Milwaukee Valve Company. 6) Mueller Company. 7) NIBCO. 8) Red-White Valve Corp. 9) United Brass Works, Inc. F. Indicating Valves: UL 1091, with integral indicating device and ends matching connecting piping. 1. Indicar: Electrical, 115-V ac, prewired, single-circuit, supervisory switch 2. NPS 2 (DN 50) and Smaller: Ball or butterfly valve with bronze body and threaded ends. a. Available Manufacturers: 1) Milwaukee Valve Company. 2) NIBCO. 3) Victaulic Co. of America. WATER-BASED FIRE-SUPPRESSION SYSTEMS H

8 3. NPS 2-1/2 (DN 65) and Larger: Butterfly valve with cast- or ductile-iron body; wafer type or with flanged or grooved ends. a. Available Manufacturers: 1) Central Sprinkler Corp. 2) Grinnell Fire Protection. 3) McWane, Inc.; Kennedy Valve Div. 4) Milwaukee Valve Company. 5) NIBCO. 6) Victaulic Co. of America. 2.5 UNLISTED GENERAL-DUTY VALVES A. Ball Valves NPS 2 (DN 50) and Smaller: MSS SP-110, 2-piece copper-alloy body with chrome-plated brass ball, 600-psig (4140-kPa) minimum CWP rating, blowout-proof stem, and threaded ends. B. Gate Valves NPS 2 (DN 50) and Smaller: MSS SP-80, Type 2, Class 125 minimum, with bronze body, solid wedge, and threaded ends. C. Globe Valves NPS 2 (DN 50) and Smaller: MSS SP-80, Type 2, Class 125 minimum, with bronze body, nonmetallic disc, and threaded ends. 2.6 SPECIALTY VALVES 1. Sprinkler System Control Valves: UL listed or FMG approved, cast- or ductile-iron body with flanged or grooved ends, and 175-psig (0-kPa) minimum pressure rating. Available Manufacturers: a. AFAC Inc. b. Central Sprinkler Corp. c. Firematic Sprinkler Devices, Inc. d. Globe Fire Sprinkler Corporation. e. Grinnell Fire Protection. f. Reliable Aumatic Sprinkler Co., Inc. g. Star Sprinkler Inc. h. Venus Fire Protection, Ltd. i. Victaulic Co. of America. J. Viking Corp. 2. Dry-Pipe Valves: UL 260, differential type; with bronze seat with 0-ring seals, singlehinge pin, and latch design. Include UL 1486, quick-opening devices, trim sets for air supply, drain, priming level, alarm connections, ball drip valves, pressure gages, priming chamber attachment, and fill-line attachment. a. Air Compressor: UL 753, fractional horsepower, -V ac, 60Hz, single phase. 1) Available Manufacturers: WATER-BASED FIRE-SUPPRESSION SYSTEMS H

9 a) AFAC Inc. b) Gast Manufacturing, Inc. c) Grinnell Fire Protection. d) Reliable Aumatic Sprinkler Co., Inc. e) Viking Corp. B. Aumatic Drain Valves: UL 1726, NPS 3/4 (DN 20), ball-check device with threaded ends. I. Available Manufacturers: a. AFAC Inc. b. Grinnell Fire Protection. c. TYCO 2.7 MANUAL CONTROL STATIONS A. Manual Control Stations: UL listed or FMG approved, hydraulic operation, with union, NPS 1/2 (DN 15) pipe nipple, and bronze ball valve. Include metal enclosure labeled "MANUAL CONTROL STATION" with operating instructions and cover held closed by breakable strut prevent accidental opening. 2.8 CONTROL PANELS I. Fire alarm scope includes the releasing panel for the preaction system. 2.9 SPRINKLERS A. Sprinklers shall be UL listed or FMG approved, with 175-psig (0-kPa) minimum pressure rating. A vail able Manufacturers: 1. AFAC Inc. 2. Central Sprinkler Corp. 3. Firematic Sprinkler Devices, Inc. 4. Globe Fire Sprinkler Corporation. 5. Grinnell Fire Protection. 6. Reliable Aumatic Sprinkler Co., Inc. 7. Star Sprinkler Inc. 8. TYCO 9. Venus Fire Protection, Ltd. 10. Victaulic Co. of America. 11. Viking Corp. B. Aumatic Sprinklers: With heat-responsive element complying with the following: 1. UL 199, for nonresidential applications. 2. UL 1626, for residential applications. WATER-BASED FIRE-SUPPRESSION SYSTEMS Hl IOOO- 9

10 C. Sprinkler Types and Categories: Nominal 1/2-inch (12.7-mm) orifice for "Ordinary" temperature classification rating, unless otherwise indicated or required by application. D. Sprinkler types, features, and options as follows: 1. Concealed ceiling sprinklers, including cover plate. 2. Extended-coverage sprinklers. 3. Flush ceiling sprinklers, including escutcheon. 4. Institution sprinklers, made with a small, breakaway projection. 5. Pendent sprinklers. 6. Pendent, dry-type sprinklers. 7. Quick-response sprinklers. 8. Recessed sprinklers, including escutcheon. 9. Sidewall sprinklers. 10. Sidewall, dry-type sprinklers. 11. Upright sprinklers. E. Sprinkler Finishes: Chrome plated, bronze, and painted. F. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers. 1. Ceiling Mounting: Chrome-plated steel, one piece, flat or Chrome-plated steel, 2 piece, with l-inch (25-mm) vertical adjustment. 2. Sidewall Mounting: Chrome-plated steel, one piece, flat. G. Sprinkler Guards: Wire-cage type, including fastening device for attaching sprinkler FIRE DEPARTMENT CONNECTIONS A. Available Manufacturers: 1. AFAC Inc. 2. Central Sprinkler Corp. 3. Elkhart Brass Mfg. Co., Inc. 4. Fire-End and Croker Corp. 5. Fire Protection Products, Inc. 6. GMR International Equipment Corporation. 7. Guardian Fire Equipment Incorporated. 8. Potier-Roemer; Fire-Protection Div. 9. Reliable Aumatic Sprinkler Co., Inc. 10. United Brass Works, Inc. B. Wall-Type, Fire Department Connection: UL 405, 175-psig (0-kPa) minimum pressure rating; with corrosion-resistant-metal body with brass inlets, brass wall escutcheon plate, brass lugged caps with gaskets and brass chains, and brass lugged swivel connections. Include inlets with threads according NFP A 1963 and matching local fire department sizes and threads, outlet with pipe threads, extension pipe nipples, check devices or clappers for inlets, and WATER-BASED FIRE-SUPPRESSION SYSTEMS H

11 escutcheon plate with marking similar "AUTO SPKR." Fire department connection can match riser size. 1. Type: Exposed, projecting, with two inlets and round escutcheon plate. 2. Finish: Polished chrome-plated or Rough chrome-plated ALARM DEVICES A. Alarm-device types shall match piping and equipment connections. B. Electrically Operated Alarm: UL 464, with 6-inch- (150-mm-) minimum- diameter, vibratingtype, metal alarm bell with red-enamel facry finish and suitable for outdoor use. 1. Available Manufacturers: a. Potter Electric Signal Company. b. System Sensor. c. FPPI, Fire Protection Products, Inc. C. Water-Flow Indicar: UL 346, electrical-supervision, paddle-operated-type, water-flow detecr with 250-psig (1725-kPa) pressure rating and designed for horizontal or vertical installation. Include two single-pole, double-throw circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-V de; complete with facry-set, fieldadjustable retard element prevent false signals and tamperproof cover that sends signal if removed. 1. Available Manufacturers: a. ADT Security Services, Inc. b. Grinnell Fire Protection. c. ITT McDonnell & Miller. d. Potter Electric Signal Company. e. System Sensor. f. Viking Corp. g. Watts Industries, Inc.; Water Products Div. D. Pressure Switch: UL 753, electrical-supervision-type, water-flow switch with retard feature. Include single-pole, double-throw, normally closed contacts and design that operates on rising pressure and signals water flow. 1. Available Manufacturers: a. Grinnell Fire Protection. b. Potter Electric Signal Company. c. System Sensor. d. Viking Corp. E. Valve Supervisory Switch: UL 753, electrical, single-pole, double-throw switch with normally closed contacts. Include design that signals controlled valve is in other than fully open position. 1. Available Manufacturers: WATER-BASED FIRE-SUPPRESSION SYSTEMS Hl

12 a. McWane, Inc.; Kennedy Valve Div. b. Potter Electric Signal Company. c. System Sensor PRESSURE GAGES A. Available Manufacturers: 1. AGF Manufacturing Co. 2. AMETEK, Inc.; U.S. Gauge. 3. Brecco Corporation. 4. Dresser Equipment Group; Instrument Div. 5. Marsh Bellofram. 6. WIKA Instrument Corporation. B. Description: UL 393, 3-1/2-4-1/2-inch- ( mm-) diameter, dial pressure gage with range of psig ( kpa) minimum. 1. Water System Piping: Include caption "WATER" or "AIR/WATER" on dial face. 2. Air System Piping: Include retard feature and caption "AIR" or "AIR/WATER" on dial face NITROGEN CORROSION INHIBITING SYSTEM A. Available Manufacturers: 1. N-2 Blast by South-Tek Systems 2. ECS Protecr by Engineered Corrosion Solutions 3. MICBlast by National Fire Equipment, Ltd. 4. Potter Corrosion Solutions by Potter Electric Signal Co, LLC B. Description: Engineered UL listed corrosion inhibiting system by introducing Nitrogen and deoxygenated air in piping with separate air compressor as needed meet 30 minute NFPA 13 fill requirements and integral Nitrogen Srage tanks. PART 3 -EXECUTION 3.1 PREPARATION A. Results of a new fire-hydrant flow test are provided. The test was performed according NFPA 13 and NFPA 291. Use results for system design calculations required in Patt 1 "Quality Assurance" Article. B. Repott test results promptly and in writing. WATER-BASED FIRE-SUPPRESSION SYSTEMS H

13 3.2 EXAMINATION' A. Examine existing building verify actual locations of existing piping, ceilings and other equipment before installation. B. Proceed with installation only after unsatisfacry conditions have been corrected. 3.3 PIPING APPLICATIONS, GENERAL A. Shop weld pipe joints where welded piping is indicated. B. Flanges, flanged fittings, unions, nipples, and transition and special fittings with finish and pressure ratings same as or higher than system's pressure rating may be used in aboveground applications, unless otherwise indicated. C. Piping between Fire Department Connections and Check Valves: Standard-weight steel pipe with threaded ends; cast- or malleable-iron threaded fittings; and threaded or grooved ends; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. 3.4 SPRINKLER SYSTEM PIPING APPLICATIONS A. Standard-Pressure, Wet-Pipe Sprinkler System, 175-psig (0-kPa) Maximum Working Pressure: 1. Sprinkler-Piping Fitting Option: Specialty sprinkler fittings, NPS 2 (DN 50) and smaller, including mechanical-t and -cross fittings, may be used downstream from sprinkler zone valves. 2. NPS 2 (DN 50) and smaller: Threaded-end, black, standard-weight steel pipe; cast- or malleable-iron threaded fittings; and threaded joints. All exposed pipe shall have threaded joints and fittings. 3. NPS 1-1/2 (DN 40) and larger: Grooved-end, Schedule 40 steel pipe; steel welding fittings, grooved-end fittings; grooved-end-pipe couplings; and grooved joints. All exposed pipe shall have threaded joints and fittings. B. Standard-Pressure, Preaction (Single Interlock) -Pipe Sprinkler System, 175-psig (0-kPa) Maximum Working Pressure: 1. Sprinkler-Piping Fitting Option: Specialty sprinkler fittings, NPS 2 (DN 50) NPS 2-1/2 (DN 65) NPS 3 (DN 80) and smaller, including mechanical-t and -cross fittings, may be used downstream from sprinkler zone valves. 2. NPS 2 (DN 50) and larger: Threaded-end, standard-weight steel pipe; cast- or malleableiron threaded fittings; and threaded joints. All exposed pipe shall have threaded joints and fittings. 3. NPS 2 (DN 50) and smaller: Threaded-end, Schedule 30 steel pipe; cast- or malleableiron threaded fittings; and threaded joints. 4. NPS 1-1/2 (DN 40): Grooved-end, Schedule 40 steel pipe; steel welding fittings, grooved-end fittings; grooved-end-pipe couplings; and grooved joints. All exposed pipe shall have threaded joints and fittings. WATER-BASED FIRE-SUPPRESSION SYSTEMS H

14 3.5 VALVE APPLICATIONS A. Drawings indicate valve types be used. Where specific valve types are not indicated, the following requirements apply: 1. Listed Fire-Protection Valves: UL listed and FMG approved for applications where required by NFP A 13. a. Shuff Duty: Use ball, butterfly, or gate valves. 2. Unlisted General-Duty Valves: For applications where UL-listed and FMG-approved valves are not required by NFPA 13. a. Shuff Duty: Use ball, butterfly, or gate valves. b. Throttling Duty: Use ball or globe valves. 3.6 JOINT CONSTRUCTION A. Threaded Joints: Comply with NFPA 13 for pipe thickness and threads. Do not thread pipe smaller than NPS 8 (DN 200) with wall thickness less than Schedule 40 unless approved by authorities having jurisdiction and thre~ds are checked by a ring gage and comply with ASME B B. All exposed pipe shall have threaded joints and fittings. C. Grooved Joints: Assemble joints with listed coupling and gasket, lubricant, and bolts. 1. Steel Pipe: Square-cut or roll-groove piping as indicated. Use grooved-end fittings and rigid, grooved-end-pipe couplings, unless otherwise indicated. 2. Dry-Pipe Systems: Use fittings and gaskets listed for dry-pipe service. 3.7 WATER-SUPPLY CONNECTION A. Connect fire-suppression piping building's interior water distribution piping. Install shuff valve, backflow preventer, pressure gage, drain, and other accessories indicated at connection water distribution piping. Install shuff valve, check valve, pressure gage, and drain at connection water supply. 3.8 PIPING INSTALLATION A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical. 1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. B. Use approved fittings make changes in direction, branch takeoffs from mains, and reductions in pipe sizes. WATER-BASED FIRE-SUPPRESSION SYSTEMS H

15 C. Install unions adjacent each valve in pipes NPS 2 (DN 50) and smaller. Unions are not required on flanged devices or in piping installations using grooved joints. D. Install flanges or flange adapters on valves, apparatus, and equipment having NPS 2-1/2 (DN 65) and larger connections. E. Install "Inspecr's Test Connections" in sprinkler system piping, complete with shuff valve, sized and located according NFP A 13. F. Install sprinkler piping with drains for complete system drainage. G. Install ball drip valves drain piping between fire department connections and check valves. Drain floor drain or outside building. H. Install alarm devices in piping systems. I. Hangers and Supports: Comply with NFPA 13 for hanger materials. J. Install sprinkler system piping according NFPA 13. K. Install pressure gages on riser or feed main, at each sprinkler test connection. Include pressure gages with connection not less than NPS 114 (DN 8) and with soft metal seated globe valve, arranged for draining pipe between gage and valve. Install gages permit removal, and install where they will not be subject freezing. L. M. N. Drain preaction piping. Pressurize and check preaction pipe sprinkler system piping and air compressors. Fill wet-pipe sprinkler system piping with water. 3.9 A. B. VALVE INSTALLATION Install listed fire-protection valves, unlisted general-duty valves, specialty valves and trim, controls, and specialties according NFP A 13 and authorities having jurisdiction. Install listed fire-protection shuff valves supervised-open, located control sources of water supply except from fire department connections. Install permanent identification signs indicating portion of system controlled by each valve. C. Install check valve in each water-supply connection. Install backflow preventers instead of check valves in potable-water supply sources. D. Specialty Valves: 1. Dry-Pipe Valves: Install trim sets for air supply, drain, priming level, alarm connections, ball drip valves, pressure gages, priming chamber attachment, and fill-line attachment. a. Install air compressor and compressed-air supply piping. WATER-BASED FIRE-SUPPRESSION SYSTEMS H

16 3.I 0 SPRINKLER APPLICATIONS A. Drawings indicate sprinkler types be used. Where specific types are not indicated, use the following sprinkler types: 1. Rooms without Ceilings: Upright sprinklers. 2. Rooms with Suspended Ceilings: Pendent, recessed, flush, and concealed sprinklers, as indicated. 3. Wall Mounting: Sidewall sprinklers. 4. Spaces Subject Freezing: Upright, pendent, dry sprinklers; and sidewall, dry sprinklers as indicated. 5. Special Applications: Extended-coverage, and quick-response sprinklers where indicated. 6. Sprinkler Finishes: a. Upright, Pendent, and Sidewall Sprinklers: Chrome plated in finished spaces exposed view; rough bronze in unfinished spaces not exposed view. b. Concealed Sprinklers: Rough brass, with facry-painted white cover plate. c. Flush Sprinklers: Bright chrome, with chrome escutcheon. d. Recessed Sprinklers: Bright chrome, with bright chrome escutcheon. e. Residential Sprinklers: Dull chrome SPRINKLER lnst ALLA TION A. Install sprinklers in suspended ceilings in center of narrow dimension of acoustical ceiling panels and tiles. B. Do not install pendent or sidewall, wet-type sprinklers in areas subject freezing. Use drytype sprinklers with water supply from heated space FIRE DEPARTMENT CONNECTION INSTALLATION A. Install wall-type, fire department connections in vertical wall. B. Install ball drip valve at each check valve for fire department connection CONNECTIONS A. Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent equipment allow service and maintenance. C. Connect water-supply piping fire-suppression piping. Include backflow preventer between potable-water piping and fire-suppression piping. Refer Division 22 Section "Domestic Water Piping Specialties" for backflow preventers. D. Install ball drip valves at each check valve for fire department connection. Drain floor drain or outside building. E. Connect piping specialty valves, specialties, fire department connections, and accessories. WATER-BASED FIRE-SUPPRESSION SYSTEMS Hl

17 F. Connect air compressor the following piping and wiring: 1. Pressure gages and controls. 2. Electrical power system. 3. Fire alarm devices, including low-pressure alarm. G. H. Connect alarm devices fire alarm. Tighten electrical connecrs and terminals according manufacturer's published rquetightening values. If manufacturer's rque values are not indicated, use those specified in UL 486A and UL 486B A. LABELING AND IDENTIFICATION Install labeling and pipe markers on equipment and piping according requirements m NFPA A. FIELD QUALITY CONTROL Perform the following field tests and inspections and prepare test reports: 1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. 2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. 3. Energize circuits electrical equipment and devices. 4. Start and run air compressors. 5. Flush, test, and inspect sprinkler systems according NFPA 13, "Systems Acceptance" Chapter. 6. Coordinate with fire alarm tests. Operate as required. 7. Verify that equipment hose threads are same as local fire department equipment. B. Report test results promptly and in writing Architect and authorities having jurisdiction A. B. c. CLEANING AND PROTECTION Clean dirt and debris from sprinklers. Remove and replace sprinklers with paint other than facry finish. Protect sprinklers from damage until Substantial Completion A. DEMONSTRATION Engage a facry-authorized service representative train Owner's maintenance personnel adjust, operate, and maintain specialty valves. Refer Division 0 I Section "Demonstration and Training." WATER-BASED FIRE-SUPPRESSION SYSTEMS Hl

18 END OF SECTION 210 WATER-BASED FIRE-SUPPRESSION SYSTEMS H

19 Hydraulic Calculations Fire Protection System Upgrades Northwest Regional Youth Center Kansas City, MO Project# H Site# 5703 Facility # Date: Calculated by: Paul C. Link, P.E. Area Summary: Area Description GPM PSI Demand Location Area #1 Area #2 Area#3 Dormiry Kitchen Classroom At connection supply 45.9 At connection supply 44.6 At connection supply cii1ag flve '

20 Fire Sprinkler Solutions, Inc. NWMO Youth- Area #1 Page Date Hydraulic Desiqn Information Sheet Name - Northwest Regional Youth Center - Area #1 Location - Dormiry Building - Northwest Regional Youth Center Contracr - Calculated By - Paul C. Link, P.E. Construction: ( ) Combustible (X) Non-Combustible Occupancy - Dorm I educational Date System No. - pre-action Contract No. - Drawing No. - 5 Ceiling Height - 13' s y s T E M D E s I G N (X) NFPA 13 (X) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 ( ) Ex.Haz. ( ) NFPA 231 ( ) NFPA 231C Other ( ) Figure Curve Specific Ruling Made By Date Area of Sprinkler Operation Density Area Per Sprinkler Elevation at Highest Outlet - 13 Hose Allowance - Inside Rack Sprinkler Allowance Hose Allowance - Outside - Note System Type ( ) Wet ( ) Dry ( ) Deluge (X) Preaction ( ) Other Sprinkler/Nozzle Make Model Size 1/2" K-Facr Temp.Rat.155 Calculation Summary Flow Required C-Facr Used: Press Required Overhead 140 Underground w A T E R s u Water Flow Test: Pump Data: Tank or Reservoir: Date of Test Cap. - Time of Test Rated Cap. Elev.- Static Press - Press Residual Press - 99 Elev. Well Flow Proof Flow Elevation - 0 P Location - Flow hydrant: west of site P Static I residual hydrant: front of building by west driveway L Source of Information - KCMO Water Dept. and Jayhawk Fire Sprinkler Co. y c 0 M M S R T A 0 c R K A G E Commodity Srage Ht. Srage Method: Single Row Double Row Mult. Row Flue Spacing Longitudinal Solid Piled Class Area % Conven. Pallet Slave Pallet Horizontal Barriers Provided: Location Aisle W. Palletized ( ) Au. Srage (. ) Solid Shelf ( ) Open Shelf Rack Clearance:Srage Ceiling Transverse Encap. Non

21 Water Supply Curve C Fire Sprinkler Solutions, Inc. NWMO Youth - Area #1 Page 2 Date City Water Supj:!ly: C1 - Stat1c Pressure : 101 C2 - Residual Pressure: 99 C2 - Residual Flow : 770 Demand: D1 - Elevation D2 - System Flow D2- System Pressure Hose ( Demand ) D3 - System Demand Safety Margin : 30 : : : : : C1 I I 1 I 7 v ll"''"l! ~I JJ FLOW ( N A 1.85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

22 Fittings Used Summary Fire Sprinkler Solutions, Inc. NWMO Youth -Area #1 Page 3 Date Fitting Legend Abbrev. Name Vz % 1 1% 1Vz 2 2% 3 3Vz B E G s T NFPA 13 Butterfly Valve NFPA 13 90' Standard Elbow NFPA 13 Gate Valve NFPA 13 Swing Check NFPA 13 90' Flow thru Tee Units Summary Diameter Units length Units Flow Units Pressure Units Inches Feet US Gallons per Minute Pounds per Square Inch Note: Fitting legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFacrs of i 20 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFacrs and they require no adjustment. All values for fittings not marked with a* will be adjusted in the calculation for CFacrs of other than i 20 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

23 Flow Summary- NFPA 2007 Fire Sprinkler Solutions, Inc. NWMO Youth- Area #1 Page 4 Date SUPPLY ANALYSIS Node at Source Static Pressure Residual Pressure Flow Available Pressure Total Demand Required Pressure TST NODE ANALYSIS Node Tag Elevation Node Type Pressure at Node Discharge at Node Notes BPR 2 1 TOR BOR UG1 TST Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

24 Final Calculations - Hazen-Williams Fire Sprinkler Solutions, Inc. NWMO Youth- Area #1 Page 5 Date Node1 Elev1 K Node2 Elev2 Fact Qa Nom Fitting or Qt Act Eqv. Ln. Pipe Ftng's Total CFact Pf/Ft Pt Pe Pf ******* Notes ****** BPR 9 BPR T T E T T E T E E E E T B s El E 21.0 T Vel= 5.57 Vel= 6.45 Vel= 7.31 Vel= 4.44 Vel"' 7.47 Vel= Vel= Vel= Vel= Vel= Vel= Vel= Vel= Vel= Vel= Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

25 Final Calculations - Hazen-Williams Fire Sprinkler Solutions, Inc. Page 6 NWMO Youth- Area #1 Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf Vel= E T TOR Vel= 6.04 TOR * * Fixed Loss = 4 BOR Vel= 6.04 BOR 0 4 E T UG B Vel= 6.04 UG E T TST G Vel= 5.83 Oa= TST K Facr = E Vel"' K Facr= Vel= E T Vel= Vel= Vel= K Facr:::: Vel= E T Vel= K Facr = Vel= 5.75 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

26 Final Calculations - Hazen-Williams Fire Sprinkler Solutions, Inc. NWMO Youth- Area #1 Page 7. Date Node1 Elev1 K Node2 Elev2 Fact Qa Nom Fitting or Qt Act Eqv. Ln. Pipe Ftng's Total CFact Pf/Ft Pt Pe Pf ******* Notes ****** E T E T E T E T Vel= 6.89 K Facr= 11 Vel= 6.05 K Facr= 5.56 Vel= 6.04 Vel= K Facr= 8.75 Vel= 6.89 Vel= K Facr= 8.80 Vel= 9.73 K Facr= 5.22 Compute'r Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

27 Fire Sprinkler Solutions, Inc. NW MO Youth - Area #2 Page Date Hydraulic Design Information Sheet Name - Northwest Regional Youth Center - Area #2 Location - Kitchen Building - Northwest Regional Youth Center Contracr - Calculated By - Paul C. Link, P.E. Construction: ( ) Combustible (X) Non-Combustible Occupancy - Dorm I educational Date System No. - wet Contract No. - Drawing No. - 5 Ceiling Height - 9' s y s T E M D E s I G N (X) NFPA 13 ( ) NFPA 231 Other Specific Ruling Lt. Haz. Ord.Haz.Gp. (X) 1 () 2 () 3 () Ex.Haz. NFPA 231C ( ) Figure Curve Area of Sprinkler Operation Density Area Per Sprinkler - varies Elevation at Highest Outlet - 9' Hose Allowance - Inside Rack Sprinkler Allowance Hose Allowance - Outside - Note Made By System Type (X) Wet ( ) Dry ( ) Deluge ( ) Preaction ( ) Other Date Sprinkler/Nozzle Make Model Size 1/2", 3/4" K-Facr, 11.2 Temp.Rat.155 Calculation Flow Required Summary C-Facr Used: Press Required Overhead 140 Underground w A T E R s u Water Flow Test: Date of Test Time of Test Static Press Residual Press - 99 Flow Elevation - 0 Pump Data: Rated Press Elev. Tank or Reservoir: Cap. - Elev.- Well Proof Flow P Location - Flow hydrant: west of site P Static I residual hydrant: front of building by west driveway L Source of Information - KCMO Water Dept. and Jayhawk Fire Sprinkler Co. y c 0 M M S R T A 0 c R K A G E Commodity Srage Ht. Srage Method: Single Row Double Row Mult. Row Flue Spacing Longitudinal Class Location Area Aisle W. Solid Piled % Palletized % Conven. Pallet Slave Pallet Horizontal Barriers Provided: ( ) Au. Srage (. ) Solid Shelf ( ) Open Shelf Rack Clearance:Srage Ceiling Transverse Encap. Non

28 Water Supply Curve C Fire Sprinkler Solutions, Inc. NWMO Youth- Area#2 Page 2 Date City Water Suwly: C1 - Static Pressure : 101 C2 - Residual Pressure: 99 C2 - Residual Flow : 770 Demand: D1 -Elevation 02 - System Flow D2 - System Pressure Hose ( Demand ) D3 - System Demand Safety Margin : : : : : : p R 110 E s 90 s 80 u 70 C1 C2 R 60 E A v.. n:11 L v / ln_'l_,... D FLOW ( N A 1.85 ) Computer Programs by Hydratec Inc. Route 11 i Windham N.H. USA 03087

29 Fittings Used Summary Fire Sprinkler Solutions, Inc. NWMO Youth -Area #2 Page 3 Date Fitting Legend Abbrev. Name '12 % 1 1V.. 1'12 2 2'12 3 3' B E G T NFPA 13 Butterfly Valve NFPA 13 90' Standard Elbow NFPA 13 Gate Valve NFPA 13 90' Flow thru Tee Units Summary Diameter Units Length Units Flow Units Pressure Units Inches Feet US Gallons per Minute Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFacrs of except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFacrs and they require no adjustment. All values for fittings not marked with a * wfll be adjusted in the calculation for CFacrs of other than and diameters other than Sched 40 per NFP A. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

30 Flow Summary- NFPA 2007 Fire Sprinkler Solutions, Inc. NWMO Youth Area #2 Page 4 Date SUPPLY ANALYSIS Node at Source Static Pressure Residual Pressure Flow Available Pressure Total Demand Required Pressure TST NODE ANALYSIS Node Tag Elevation Node Type Pressure at Node Discharge at Node Notes DP01 EQ TOR BOR UG1 TST K=K@ EQ01 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

31 Final Calculations - Hazen-Williams Fire Sprinkler Solutions, Inc. NWMO Youth - Area #2 Page 5 Date Node1 Elev1 K Node2 Elev2 Fact Qa Nom Fitting or Qt Act Eqv. Ln. Pipe Ftng's Total CFact Pf/Ft Pt Pe Pf ******* Notes ****** DP EQ01 9 EQ TOR 9 TOR 9 BOR 0 BOR 0 UG1 0 UG1 0 TST 0 TST T T E E T E 267 T G E T T Vel= 5.57 K Facr= 5.74 Vel= 8.17 Vel= Vel= Vel= Vel= Vel= 8.46 * * Fixed Loss = 4 Vel= 8.46 Vel= 8.46 Vel= 9.14 Oa= K Facr = Vel= 7.22 Vel= 8.60 Vel= 9.54 K Facr = Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

32 Final Calculations - Hazen-Williams Fire Sprinkler Solutions, Inc. Page 6 NWMO Youth- Area #2 Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf E Vel= K Facr= T Vel= Vel= T o.o Vel= K Facr = T Vel= K Facr= T Vel= K Facr= Vel= E T Vel= Vel= Vel= E T Vel= K Facr = Vel= 9.20 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

33 Final Calculations - Hazen-Williams Fire Sprinkler Solutions, Inc. Page 7 NWMO Youth- Area #2 Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt or Ftng's Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf T Vel= Vel= Vel"' K Facr= E K= K@ EQ01 T Vel= K Facr= 5.50 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

34 Fire Sprinkler Solutions, Inc. NW MO Youth - Area #3 Page Date Hydraulic Design Information Sheet Name - Northwest Regional Youth Center - Area #3 Location - Classroom Building - Northwest Regional Youth Center Contracr - Calculated By - Paul C. Link, P.E. Construction: ( ) Combustible (X) Non-Combustible Occupancy - Dorm I educational Date System No. - wet Contract No. - Drawing No. - 5 Ceiling Height - 9' s y s T E M D E s I G N (X) NFPA 13 (X) Lt. Haz. ( ) NFPA 231 ( ) NFPA 231C Other Specific Ruling Area of Sprinkler Operation Density Area Per Sprinkler Elevation at Highest Outlet - 9' Hose Allowance - Inside Rack Sprinkler Allowance Hose Allowance - Outside - Note Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 ( ) Figure Curve Made By System Type ( ) Wet ( ) Dry ( ) Deluge (X) Preaction ( ) Other ( ) Ex.Haz. Date Sprinkler/Nozzle Make Model Size 1/2" K-Facr Temp.Rat.155 Calculation Flow Required Summary C-Facr Used: Press Required Overhead 140 Underground w A T E R s u p p L y Water Flow Test: Date of Test Time of Test Static Press Residual Press - 99 Flow Elevation - 0 Pump Data: Rated Press Elev. Tank or Reservoir: Cap. - Elev.- Well Proof Flow Location - Flow hydrant: west of site Static I residual hydrant: front of building by west driveway Source of Information - KCMO Water Dept. and Jayhawk Fire Sprinkler Co. c 0 M M S R T A 0 c R K A G E Commodity Srage Ht. Srage Method: Single Row Double Row Mult. Row Flue Spacing Longitudinal Class Location Area Aisle W. Solid Piled % Palletized % Conven. Pallet Slave Pallet Horizontal Barriers Provided: ( ) Au. Srage (.) Solid Shelf ( ) Open Shelf Rack Clearance:Srage Ceiling Transverse Encap. Non

A. This Section includes the following fire-suppression piping inside the building:

A. This Section includes the following fire-suppression piping inside the building: SECTION 211000 - WATER-BASED FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following fire-suppression piping inside the building: 1. Automatic wet-type, standpipe systems.

More information

WET-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

North Hanover Township School District North Hanover Township, New Jersey

North Hanover Township School District North Hanover Township, New Jersey SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

B. Related Sections: The following Sections contain requirements that relate to this Section.

B. Related Sections: The following Sections contain requirements that relate to this Section. SECTION 211313- FIRE-SUPPRESSION PIPING PART1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION FIRE-SUPPRESSION PIPING

SECTION FIRE-SUPPRESSION PIPING SECTION 211313 FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure. SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum. Page 211200-1 SECTION 211200 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD.

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD. TECHNICAL SPECIFICATIONS SECTION 211316 DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD Prepared for: Mr. Cab Vinton Director Plaistow Public Library 85

More information

SECTION PREACTION SPRINKLER SYSTEMS

SECTION PREACTION SPRINKLER SYSTEMS PART 1 GENERAL SECTION 211316 - PREACTION SPRINKLER SYSTEMS 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION SECTION 211200 - FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Hose connections. 4. Fire-department connections.

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 211313 WET-PIPE SPRINKLER SYSTEMS PRT 1 GENERL 1.01 RELTED DOCUMENTS. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION Table of Contents TOC Page 1 DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION 210517 SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING 08/15/18 0 210523 GENERAL-DUTY VALVES FOR FIRE PROTECTION PIPING

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314D - AUTOMATIC SPRINKLER SYSTEMS (DRY-PIPE) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 13900 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION FIRE-SUPPRESSION SYSTEMS

SECTION FIRE-SUPPRESSION SYSTEMS SECTION 13900 FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Automatic wet-type, Class I, fire-suppression standpipes and branches for sprinklers. 2. Wet-pipe, fire-suppression

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 1314W - AUTOMATIC SPRINKLER SYSTEMS (WET PIPE SYSTEMS) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING SECTION 210517- SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES SECTION 15300 FIRE PROTECTION PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. Dartmouth College is currently insured by Factory Mutual. References to the owner s insurance company in this specification

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

Facility Fire-Suppression Water-Service Piping

Facility Fire-Suppression Water-Service Piping University of New Hampshire University of New Hampshire Scholars' Repository Division 21 Fire Supression Chapter 5 Technical Construction and Renovation Standards 4-23-2015 211100 - Facility Fire-Suppression

More information

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements. SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

A. Section includes wet-pipe sprinkler system, system design, installation, and certification. SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes wet-pipe sprinkler system, system design, installation, and certification. 1.2 REFERENCES A. General: Comply

More information

University of Missouri St. Louis September 9, 2013 Recreation and Wellness Center #S

University of Missouri St. Louis September 9, 2013 Recreation and Wellness Center #S SECTION 210548 - VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Isolation pads. 2. Isolation mounts. 3.

More information

ADDENDUM NO. 3 March 19, 2018

ADDENDUM NO. 3 March 19, 2018 ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION Bluffs Tower Apartments Section TOC Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION 211000 WATER-BASED FIRE-SUPPRESSION SYSTEMS 213113 ELECTRIC-DRIVE, CENTRIFUGAL FIRE

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14 SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide

More information

Addendum No. 2 to the Contract Documents

Addendum No. 2 to the Contract Documents Addendum No. 2 to the Contract Documents Lewis County Jefferson Community College Education Center Project CONTRACT 2A: GENERAL CONSTRUCTION CONTRACT 2B: ELECTRICAL CONSTRUCTION CONTRACT 2C: MECHANICAL

More information

Gas Station & C Store SECTION CWM Job No

Gas Station & C Store SECTION CWM Job No SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL SECTION 21 05 00 - COMMON WORK RESULTS FOR FIRE SUPPRESSION 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION SECTION 15300 - FIRE PROTECTION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY. Copyright 2016 by The American Institute of Architects (AIA) Exclusively published and distributed by AVITRU, LLC for the AIA This Product MasterSpec Section is licensed by AVITRU, LLC to Victaulic Company

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

END OF SECTION

END OF SECTION SECTION 210553 ~IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT PART 1 -GENERAL 1.1 SUMMARY Section Includes: I. Equipment labels. 2. Warning signs and labels. 3. Pipe labels. 1.2 ACTION SUBMITTALS

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY. This Product MasterSpec Section is licensed by AVITRU, LLC to Victaulic Company ("Licensee"). This Product MasterSpec Section modifies the original MasterSpec text and does not include the full content

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 22 63 13 GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8 City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire

More information

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13930 WET-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete wet-pipe fire sprinkler system in new addition only as specified

More information

SECTION FIRE SUPPRESSION SYSTEMS

SECTION FIRE SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2

More information

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS SECTION 13935 DRY-PIPE FIRE-SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install complete fire sprinkler system as specified in Contract Documents. B.

More information

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Port of St Helens SIA Aircraft Hanger Scappoose, OR Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance

More information

SECTION AUTOMATIC SPRINKLER PIPING

SECTION AUTOMATIC SPRINKLER PIPING SECTION 15330 AUTOMATIC SPRINKLER PIPING ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: This section contains several types of automatic sprinkler piping. Some piping is allowed

More information

2. Welding Materials and Procedures shall conform to the ASME Code.

2. Welding Materials and Procedures shall conform to the ASME Code. PART 1 GENERAL 1.01 Scope of Standard A. The design guidelines contained herein include the requirements for systems, materials, fittings and valves utilized for fire protection systems at Sam Houston

More information

A. This section includes design and performance information for fire protection and suppression systems.

A. This section includes design and performance information for fire protection and suppression systems. SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials

More information

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS DIVISION 21: FIRE SUPPRESSION 21 1000 WATER BASED FIRE SUPRESSION SYSTEMS 21 1200 FIRE-SUPPRESSION DRY STANDPIPES 21 1313 WET PIPE SPRINKLER PROTECTION SYSTEM 21 1314 WET-PIPE AUTOMATIC SPRINKLER SYSTEM

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

A. This Section includes the following domestic water piping specialties:

A. This Section includes the following domestic water piping specialties: SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified

More information

SECTION DOMESTIC WATER PIPING SPECIALTIES

SECTION DOMESTIC WATER PIPING SPECIALTIES SECTION 22 11 19 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

B. Section Identification for Fire Suppression Piping and Equipment.

B. Section Identification for Fire Suppression Piping and Equipment. SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 21 13 13 FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS A. Furnish all labor, materials, equipment services and incidentals required to design and install properly

More information

PROJ. NO SECTION REFRIGERANT PIPING

PROJ. NO SECTION REFRIGERANT PIPING SECTION 23 23 00 REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

NATURAL GAS PIPING

NATURAL GAS PIPING SECTION 15496 - NATURAL GAS PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation.

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation. SECTION 211100 - FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University FIRE SPRINKLER SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS DIVISION 21 - FIRE SUPPRESSION Includes the following sections: None DESIGN REQUIREMENTS It is the policy of City of Santa Cruz to install fire sprinkler systems in all new construction/facilities. If

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION SECTION 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL 1.1 SUMMARY A. This section supplements all sections in this division, including pipe, fittings, valves, and connections for sprinkler

More information

SECTION WET FIRE SPRINKLER SYSTEMS

SECTION WET FIRE SPRINKLER SYSTEMS SUNY GENESEO 211310-1 PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in

More information

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13. 21 10 00 PART 1 - GENERAL 1.01 SCOPE A. The following standards and procedures apply to the design and installation of all wet pipe and dry pipe sprinkler systems. The design of fire suppression systems

More information

B. Shop Drawings: Detail fabrication of pipe anchors, hangers, special pipe support assemblies, alignment guides, expansion joints and loops,

B. Shop Drawings: Detail fabrication of pipe anchors, hangers, special pipe support assemblies, alignment guides, expansion joints and loops, SECTION 23 21 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

esfr dry pendent sprinkler Vk501 (k14.0)

esfr dry pendent sprinkler Vk501 (k14.0) September 13, 2012 Sprinkler 122a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK501 is a fast response fusible element type sprinkler designed for use in storage

More information

TECHNOLOGY EDUCATION CENTER

TECHNOLOGY EDUCATION CENTER PROJECT MANUAL - VOLUME 2 DIVISIONS 21-32 Issued for Bidding: July 1, 2013 Project No.: 13-005 TECHNOLOGY EDUCATION CENTER for Kankakee Community College 100 College Drive Kankakee, Illinois 60901 125

More information

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed. Page 1 of 10 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK504 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals. SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information